• The PV panel is a DC voltage/current source. Therefore in all cases please ensure that the polarity is
respected when performing the connection between the inverter and the PV panel, otherwise either
equipment may be damaged
Risk of fire and risk of damage exist.
Notes for all drawings:
(Note 1) Install recommended circuit breakers (MCCB) or residual-current-operated protective device (RCD)/
earth leakage breakers (ELCB) (with overcurrent protective function) on the inputs of each inverter
(primary side) for wiring protection. Do not use breakers which exceed the recommended rated current
.
(Note 2) Install recommended magnetic contactors (MC) as necessary on each inverter as these will be used to
disconnect the inverter from the power supply separately from the MCCB or the RCD / ELCB.
Additionally, when installing coils such as MC or solenoid close to the inverter, connect surge absorbers
in parallel.
(Note 3) Make the necessary interlock to avoid that both PV panel supply and AC supply are connected at the
same time. Not preventing this may cause damage to the equipment.
(Note 4) Used for the protection of the PV panel and the wiring. Alternatively fuses can be also used. Please
use recommended types by the PV panel maker. The use of additional protection devices (like surge
protection devices) may be also recommended by the PV panel maker.
(Note 5) Use this terminal when supplying the inverter with DC voltage from the PV panel. Applicable for types
FRN0203E2■-4G or above. Please consult Fuji Electric.
(Note 6) Remove the shorting bar between the inverter main circuit terminals P1-P(+) before connecting the
direct current reactor (DCR) (option).
It must be connected in the following cases:
ND mode: T y pes FRN0139 E2■-4G or above, HD/ HND mode: T y pes FRN01 68E2■-4G or above, HHD
mode: Types FRN0203E2■-4G or above.
Use the direct current reactor (option) when the power supply transformer capacity is above 500 kVA
and the transformer capacity is over 10 times the rated capacity of the inverter, or when “thyristor load
exists” in the same power system. In case of PV panel supply only, DCR is not required for any
capacity.
(Note 8) This terminal is used for grounding the motor. Grounding the motor using this terminal is recommended
in order to suppress inverter noise.
(Note 9) Use twisted lines or shielded lines for the control signals.
Generally, the shielded line requires grounding, but when the effect of externally induced noise is large,
connecting to [CM] may suppress the eff ect of noise. Separate the line from the main circuit wiring and
do not enclose in the same duct. Separation distance of over 10 cm is recommended. When crossing
the main circuit wiring, make the intersection perpendicular.
(Note 10) The various functions listed for terminals [X1] to [X5] (digital inputs), terminals [Y1] to [Y2] (transistor
outputs), and terminal [FM] (monitor output) show the recommended functions for Solar Pumping
application.
(Note 11) These are conne ctors for switching the main circuit. For details, refer to “2.2.7 Switching connectors”.
(Note 12) The various switches on the control printed circuit board define the settings for the inverter operation.
For details, refer to “2.2.6 Operating slide switches”.
(Note 14) Shorting bars are connected between the safety function terminals [EN1], [EN2], and [PLC] as factory
default. Remove the shorting bars when using this function.
(Note 15)
and are separated and insulated.
(Note 16) Charge lamp does not exist in the inverters FRN0069E2■-2G/FRN0044E2■-4G/FRN0012E2■-7G or
below.