FRENIC - Ace
Common terminal for digital
Analog/Pulse train output
Power switching connector
Fan power supply switching
In case of the motor with built-in cooling fan
Current/voltage input for setting
4(0) to 20mADC / 0 to +10VDC
Voltage input for setting
DBR: Dynamic Braking Resistor
: Residual-current-operated
: Earth leakage circuit breaker
: Molded case circuit breaker
Potentiometer power supply
Quick Reference Guide
FRENIC - Ace Control Wiring
Control Card Terminals
SD DX- DX+ CMY Y1 Y2 CM X 1 X2 X3 X4 X 5 PLC
400V series
380 to 480V 50/60Hz
200V series
200 to 240V 50/60Hz
power supply
RS-485)
(0 to 1 step)
(0 to 3 step)
(0 to 7 step)
〕
0~+10VDC)
0~±10VDC)
〕
analog inputs
*1 Install a recommended molded case circuit breaker (MCCB) or residual-current-operated protective device (RCD)/earth
leakage circuit breaker (ELCB) (with overcurrent protection function) in the primary circuit of the inverter to protect wiring.
Ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity.
*2 Install a magnetic contactor (MC) for each inverter to separate the inverter from the power supply, apart from the MCCB or
RCD/ELCB, when necessary. Connect a surge absorber in parallel when installing a coil such as the MC or solenoid near the
inverter.
〕
4(0)~20mADC)
0~+10VDC)
4(0)~20mADC)
0~+10VDC)
25~32kp/s)
4(0)~20mADC)
0~+10VDC)
1
”
Detachable
terminal
block
”
for any alarm)
1
*3 The R0 and T0 terminals are provided for inverters of type 0059 or above(460V class) and type 0088 or above(230V class).
To retain an alarm output signal ALM issued on inverter's programmable output terminals by the protective function or to keep
the keypad alive even if the main power has shut down, connect these terminals to the power supply lines. Even if without
connecting the power supply to these terminals, the inverter can run as long as connecting the power supply to the terminals
L1/R, L2/S, L3/T.
*4 Normally no need to be connected. Use these terminals when the inverter is equipped with a high power-factor,
regenerative PWM converter (RHC series). (Type 0203 or above/460V only)
*5 When connecting an optional DC reactor (DCR), remove the jumper bar from the terminals P1 and P(+).
For types 0139 (ND spec.), 0168 (HD/ND spec.) and 0203 or bigger capacity types, it is required to connect the DCR (460V
only). Use a DCR when the capacity of the power supply transformer exceeds 500 kVA and is 10 times or more the inverter
rated capacity, or when there are thyristor-driven loads in the same power supply line.
*6 Inverters of type 0072 or below(460V class) and type 0115 or below(230V class) have a built-in braking chopper between
the terminals P(+) and DB.
*7 For inverters of type 0085 or above (460V class), need to use a braking unit to connect the braking resistor in order to
upgrade the braking capability of inverters. Be sure to connect the braking unit (option) to terminals P(+) and N(-). Auxiliary
terminals [1] and [2] have polarity. Be sure to connect as this figure.
*8 A grounding terminal for a motor. Use this terminal if needed.
*9 For control signal wires, use twisted or shielded-twisted wires. When using shielded-twisted wires, connect the shield of
them to the common terminals of the control circuit. To prevent malfunction due to noise, keep the control circuit wiring away
from the main circuit wiring as far as possible (recommended: 10 cm(3.9 inches) or more). Never install them in the same wire
duct. When crossing the control circuit wiring with the main circuit wiring, set them at right angles.
*10 The connection diagram shows factory default functions assigned to digital input terminals [X1] to [X5], [FWD] and [REV],
transistor output terminals [Y1] and [Y2], and monitor contact output terminals [FM] .
*11 The power switching connectors (CN UX) and the fan power supply switching connectors (CN R and CN W) are for type
0203(460 V class) or above.
*12 Slide switches on the control printed circuit board (control PCB). Use these switches to customize the inverter operations.
*13 Use auxiliary contacts of the thermal relay (manually restorable) to trip the molded case circuit breaker (MCCB) or
magnetic contactor (MC).
*14 When using the Enable input function, be sure to remove the jumper wire from terminals [EN1],[EN2] and [PLC].
*15 and are separated and insulated
30A 30B 30C
C1 11 FM1 FM2
CM FWD REV PLC EN1 EN2
11 11 12 13
Orange = Outputs, Yellow = Analog Inputs, Blue = Digital Inputs
• FWD, Rev, plus 5 Digital inputs. Congurable for
Source or Sink.
Operang
Voltage
(Sink)
Operang
Voltage
(Sink)
Item
Min. Max.
On level 0V 2V
Off leve l 22V 27V
On level 22V 27V
Off leve l 0V 2V
• 0-10VDC analog input.
• 4-20mA, 0-20mA or 0-10VDC analog input.
• 2 Transistor outputs.
Item
Operang
Voltage
(Sink)
Maximum Current at on 50mA
Max.
On level 2v
Off level 22V
• Form C contact relay
o (250VAC 0.3A, cosØ=0.3), (48VDC, .5A).
• 1 0-10VDC, 4-20mA, 0-20mA or 25-32kp/s analog
output.
• 1 0-10VDC, 4-20mA or 0-20mA analog output.
• 24VDC max 100mA DC output power.
• 10VDC output power for potentiometer.
• 2 Source only, safe torque off Enable Inputs.
• RS-485 wire terminals.
FRENIC-Ace (E2) Keypad
A. LED Display
B. Remote/Local Indicator
C. Monitoring Display Indicator
D. Program Reset Key
E. Function Data Key
F. Shift Key
G. Menu Navigation Keys
H. Local Mode Control Operators
First Power ON.
Upon powering the drive on for the rst time you must set the region in Menu 8.des, for Americas by setting the value to amer
After initial start-up you may change the region by setting the value of H101. See page 4-4 of FRENIC-ACE Instructional Manual INR-SI47-1733f-E For
more details.
Changing the regional from default value
Quick Start Menus
1.F Fundamental Functions
1.E Extension Terminal Functions
1.C Control Functions of Frequency
1.P Motor 1 Parameters
1.H High Performance Functions
1.H1 High Performance Functions
1.A Motor 2 Functions
1.J Application Functions
1.J1 PID Functions
1.d Application Functions 2
1.U Customizable Logic
1.U1 Customizable Logic
1.Y Link Functions
1.k Keypad Functions
2. rEP (Data Check)
Displays function codes that
have been changed from
factory default
3. oPE (Operations Monitor)
3_00 Output frequency Before Slip
3_01 Output frequency After Slip
3_02 Output Current
3_03 Output Voltage
3_04 Calculated Torque
3_05 Reference Frequency
3_06 Rotation Direction
3_07 Running Status
3_08 Motor Speed r/min
3_09 Load Shaft speed
3_10 PID SV
3_11 PID PV
3_12 Torque Limit Value A
3_13 Torque Limit Value B
3_14 Ratio Setting
3_15 Line Speed r/min
Fuji Electric Corp. of America
47520 Westinghouse Drive, Fremont, CA 94539
Phone: 510-440-1060
www.americas.fujielectric.com
asia to amer requires pressing and holding key while pressing
jpn
asia
+
1.F _ _
1.E _ _
1.C _ _
1.P _ _
1.H _ _
1.H1 _ _
1.A _ _
1.J _ _
1.J1 _ _
1.d _ _
1.U _ _
1.U1 _ _
1.Y _ _
1.k _ _
To access menus 2-6 change function code E52-2
2. rEP
3. oEP
4. I_O
5. CHE
6. AL
4. I_O (I/O Check)
4_00 I/O Signals on the Control Card Terminals
4_01 I/O Signals on the Control Card Terminals
under Communications.
4_02 Input Voltage on Terminal 12
4_03 Input Current on Terminal C1
4_04 Output Voltage on Terminal FMV
4_05 Output Voltage on Terminal FM2
4_06 Output Frequency on Terminal FMP
4_07 Input Voltage on Terminal C1
4_08 Output Current on Terminal FMI
4_09 Output Current on Terminal FM2
4_2
4 Cutomizable Logic Timer
chn
eu
amer
kor
5. CHE (Maintenacne Info)
5_00 Accumulated Run Time
5_01 DC Link Bus Voltage
5_03 Max Temperature of Heat Sink
5_04 Max Effectice Current
5_05 Capacitance of the DC Link Bus
Capacitance
5_06 Accumutated Run Time of Electolytic
Capacitors on the PCB
5_07 Accumulated Run Time of Cooling Fan
5_08 Number of Starts (Drive)
5_09 Input Watt-Hour
5_10 Input Watt-Hour Data
6. AL (Alarm Info)
6_00 Output Frequency
6_01 Output Current
6_02 Output Voltage
6_03 Calculated Torque
6_04 Reference Frequency
6_05 Rotational Ditection
6_06 Running Status
6_07 Accumulated Running Time
6_08 Number of Startups
6_09 DC Link Bus Voltage
6_10 Temperature Inside the Inverter
6_11 Max. Temperature of Heat Sink
6_12
Terminal I/O Status
6_13 Terminal Input Signal Status in HEX
6_14 Terminal Output Status in Hex
6_15
Number of Consecutice Occurrces
6_16 Overlapping Alarm 1
6_17 Overlapping Alarm 2
6_18 Communication Terminal Status I/0
6_19 Communication Terminal Status Input
6_20 Communication Terminal Status Output
6_21 Sub-Code
6_22 Running Status 2
6_23 Detected Speed
6_24 Running Status 3
6_25 Multiple Alarm Sub-Code
sav ue