Rated voltage *2) V 3-phase 200V/50Hz 200, 220, 230V/60Hz
OutputRated current *3)A 1.5 3.05.08.01117253346597487115 145 180 215 283 346
ratingsOverload capability150% of rated current for 1min.150% of rated current for 1min.
Rated frequencyHz 50, 60Hz
Phases, Voltage, Frequency3-phase 200 to 230V 50/60Hz
Voltage / frequency variationsVo ltage : +10 to –15% (Voltage unbalance *4) : 2% or less) Frequency :+5 to –5%
Input*5)When the input voltage drops below 165V from rated voltage, the inverter can be operated for 15ms .
ratingsThe smooth recovery method is selectable.
OutputAccuracy (Stability)•Analog setting : ± 0.2% of Maximum frequency (at 25±10°C (77±50°F))
frequency•Digital setting : ±0.01% of Maximum frequency (at –10 to +50°C (14 to 122°F))
Control0.1 to 0.9 : Manual (for variable torque load) *9)
Starting frequency0.1 to 60Hz, Holding time: 0.0 to 10.0s
Carrier frequency *8) 0.75 to15kHz
Setting resolution•Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz, 0.15Hz at 400Hz
Voltage / freq. (V/f) characteristicAdjustable at base and maximum frequency, with AVR control : 80 to 240V
To rque boostTo rque boost can be set, using Function code F09 and A05.
Starting torque200% (with Dynamic torque-vector control selected)
Braking torque*10)150%100%20%10 to 15%
Standard
Times 1055No limit
Duty cycle
Standard
Braking torque150%100%
Times 90454545302010810
Using
options
10%ED Braking torque150%*12)
Times 9045302010
DC injection brakingStarting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
*1) Inverter output capacity (kVA) at 230V. Rated capacity reduces when power supply voltage decreases.
*2) Output voltage cannot exceed the power supply voltage.
*3) Current derating may be required in case of low impedance loads such as high frequency motor.
*4) Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) =
*5) Tested at standard load condition (85% load).
*6) This value is under FUJI original calculation method.
*7) When power-factor correcting DC REACTOR (DCR) is used.
*8) When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter.
*9) When torque boost is set at 0.1, starting torque of 50% or more can be obtained.
*10) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.)
*11) Order individually.
*12) Applicable to 10%ED when using options (standard)
Duty cycle
1-2
200% of rated current for 0.5s180% of rated current for 0.5s
3-phase 200 to 220V/50Hz (220 to 230V/50Hz) *11)
200 to 230V/60Hz
kVA 0.40.61.12.02.9 4.96.99.4141923283847576995 114
•Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
• LINK setting : Selects from the following two items.
0.0: Automatic (for constant torque load)
1.0 to 1.9 : Manual (for propotional speed torque load)
2.0 to 20.0: Manual (for constant torque load)
%ED
105353232No limit
%ED
37221810755510
%ED
*Inverter restarts at the star ting frequency when operation command is input while braking is operating.
*DC injection braking does not operate at the time of change-over from forward to reverse operation.
*
DC injection braking does not operate when frequency setting is decreased while operation command (FWD, REV) is being input.
-UL/cUL -Low Voltage Directive-EMC Directive-TÜV (up to 30HP)
-IEC 61800-3 (EMC product standard including specific test methods)
Rated voltage *2) V 3-phase 380, 400, 415V/50Hz 380, 400, 440, 460V/60Hz
OutputRated current *3)A 1.5 2.5 3.7 5.5 9 13 18 24 30 39 45 60 75 91 112 150 176 210 253 304 377 415 520 585 650740
ratingsOverload capability150% of rated current for 1min.150% of rated current for 1min.
Rated frequencyHz 50, 60Hz
Phases, Voltage, Frequency3-phase 380 to 480V 50/60Hz3-phase 380 to 440V/50Hz 380 to 480V/60Hz *4)
Voltage / frequency variationsVo ltage : +10 to –15% (Voltage unbalance *5) : 2% or less) Frequency :+5 to –5%
Input*6)When the input voltage drops below 310V from rated voltage, the inverter can be operated for 15ms .
ratingsThe smooth recovery method is selectable.
OutputAccuracy (Stability)•Analog setting : ±0.2% of Maximum frequency (at 25±10°C (77±50°F))
frequency•Digital setting : ±0.01% of Maximum frequency (at –10 to +50°C (14 to 122°F))
Control0.1 to 0.9 : Manual (for variable torque load) *10)
NOTES: *1) Inverter output capacity (kVA) at 460V. Rated capacity reduces when power supply voltage decreases.
Momentary voltage dip capability When the input voltage is 310V or more, the inverter can be operated continuously.
Rated current *7) (with DCR)
A(without DCR) 1.8 3.5 6.2 9.2
Required power supply
capacity *8)
Maximum frequency 50 to 400Hz
SettingBase frequency25 to 400Hz
Starting frequency0.1 to 60Hz, Holding time: 0.0 to 10.0s
Carrier frequency *9)0.75 to 15kHz0.75 to 10kHz
Setting resolution•Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz, 0.15Hz at 400Hz
Voltage / freq. (V/f) characteristicAdjustable at base and maximum frequency, with AVR control : 320 to 480V
To rque boostTo rque boost can be set, using Function code F09 and A05.
Starting torque200% (with Dynamic torque-vector control selected) 180% (with Dynamic torque-vector control selected)
Braking torque*11) 150%100%20%10 to 15%
Standard
Times55No limit
Duty cycle
Standard
Braking torque150%100%
Times45302010810
Using
options
10%ED Braking torque150%*13)
Times45302010
Duty cycle
DC injection brakingStarting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
*2) Output voltage cannot exceed the power supply voltage.
*3) Current derating may be required in case of low impedance loads such as high frequency motor.
*4) When the input voltage is 380 to 398V/50Hz or 380 to 430V/60Hz, the tap of the auxiliary transformer must be changed.
*5) Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) =
*6) Tested at standard load condition (85% load).
*7) This value is under FUJI original calculation method.
*8) When power-factor correcting DC REACTOR (DCR) is used.
*9) When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter.
*10) When torque boost is set at 0.1, starting torque of 50% or more can be obtained.
*11) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.)
*12) Consult with Fuji Electric.
*13) Applicable to 10%ED when using options (standard)
200% of rated current for 0.5s180% of rated current for 0.5s
•Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
• LINK setting: Selects from the following two items.
0.0: Automatic (for constant torque load)
1.0 to 1.9 : Manual (for propotional speed torque load)
2.0 to 20.0: Manual (for constant torque load)
%ED
5353232No limit
%ED
22 18 10 755510
%ED
(kg)
Max. voltage [V] – Min. Voltage [V]
Three-phase average voltage[V]
10101010
*Inverter restarts at the starting frequency when operation command is input while braking is operating.
* DC injection braking does not operate at the time of change-over from forward to reverse operation.
*
DC injection braking does not operate when frequency setting is decreased while operation command (FWD, REV) is being input.
Natural cooling
-UL/cUL -Low Voltage Directive-EMC Directive-TÜV (up to 30HP)
-IEC 61800-3 (EMC product standard including specific test methods)
Rated voltage *2) V 3-phase 200V/50Hz 200, 220, 230V/60Hz
OutputRated current *3)A222942556778115145180215283346415
ratingsOverload capability110% of rated current for 1min
Rated frequencyHz 50, 60Hz
Phases, Voltage, Frequency3-phase 200 to 230V 50/60Hz
Voltage / frequency variationsVo ltage : +10 to –15% (Voltage unbalance *4) : 2% or less) Frequency :+5 to –5%
Input*5)When the input voltage drops below 165V from rated voltage, the inverter can be operated for 15ms .
ratingsThe smooth recovery method is selectable.
OutputAccuracy (Stability)•Analog setting : ± 0.2% of Maximum frequency (at 25±10°C (77±50°F))
frequency•Digital setting : ±0.01% of Maximum frequency (at –10 to +50°C (14 to 122°F))
Control0.1 to 0.9 : Manual (for variable torque load) *9)
Starting frequency0.1 to 60Hz, Holding time: 0.0 to 10.0s
Carrier frequency *8) 0.75 to 15kHz0.75 to 10kHz0.75 to 6kHz
Setting resolution•Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz
Voltage / freq. (V/f) characteristic Adjustable at base and maximum frequency, with AVR control : 80 to 240V
To rque boostTo rque boost can be set, using Function code F09 and A05.
Starting torque50%
Braking torque*10)20%10 to 15%
Standard
TimesNo limit
Duty cycle
Standard
Braking torque100%75%
Times157810
Using
options
10%ED Braking torque100%*12)
Times157
Duty cycle
DC injection brakingStarting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
*2) Output voltage cannot exceed the power supply voltage.
*3) Current derating may be required in case of low impedance loads such as high frequency motor.
*4) Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) =
*5) Tested at standard load condition (85% load).
*6) This value is under FUJI original calculation method.
*7) When power-factor correcting DC REACTOR (DCR) is used.
*8) When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter.
*9) When torque boost is set at 0.1, starting torque of 50% or more can be obtained.
*10) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.)
*11) Order individually.
*12) Applicable to 10%ED when using options (standard)
kVA6.99.4141923283847576995114139
•Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
• LINK setting: Selects from the following two items.
0.0: Automatic (for constant torque load)
1.0 to 1.9 : Manual (for propotional speed torque load)
* Inverter restarts at the starting frequency when operation command is input while braking is operating.
* DC injection braking does not operate at the time of change-over from forward to reverse operation.
*
DC injection braking does not operate when frequency setting is decreased while operation command (FWD, REV) is being input.
-UL/cUL -Low Voltage Directive-EMC Directive-TÜV (up to 30HP)
-IEC 61800-3 (EMC product standard including specific test methods)
• 1/20000 of Maximum frequency ex.) 0.003Hz at 60Hz, 0.006Hz at 120Hz
• 0.01Hz (Fixed)
x 67(Conforming to EN61800-3 (5.2.3))
3-phase 200 to 220V/50Hz (220 to 230V/50Hz) *11) 200 to 230V/60Hz
No limit
1-4
Chapter 1
1. Standard Specifications
1.4 Three-phase 460V FRENIC5000P11S Series (for variable torque load)
Input*6)When the input voltage drops below 310V from rated voltage, the inverter can be operated for 15ms .
ratingsThe smooth recovery method is selectable.
OutputAccuracy (Stability)·Analog setting : ±0.2% of Maximum frequency (at 25±10°C (77±50°F))
frequency·Digital setting : ±0.01% of Maximum frequency (at –10 to +50°C (14 to 122°F))
Control0.1 to 0.9 : Manual (for variable torque load) *10)
Rated voltage *2) V 3-phase 380, 400, 415V/50Hz 380, 400, 440, 460V/60Hz
Rated current *3)A
Overload capability110% of rated current for 1min
Rated frequencyHz 50, 60Hz
Phases, Voltage, Frequency
Voltage / frequency variationsVoltage : +10 to –15% (Voltage unbalance *5) : 2% or less) Frequency :+5 to –5%
Momentary voltage dip capabilityWhen the input voltage is 310V or more, the inverter can be operated continuously.
Rated current *7) (with DCR)
A(without DCR)
Required power supply
capacity *8)
Maximum frequency50 to 120Hz
SettingBase frequency25 to 120Hz
Starting frequency0.1 to 60Hz, Holding time: 0.0 to 10.0s
Carrier frequency *9)0.75 to 15kHz0.75 to 10kHz0.75 to 6kHz
Setting resolution·Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz
Voltage / freq. (V/f) characteristicAdjustable at base and maximum frequency, with AVR control : 320 to 480V
To rque boostTorque boost can be set, using Function code F09 and A05.
Starting torque50%
Braking torque*11)20%10 to 15%
Standard
TimesNo limit
Duty cycle
Standard
Braking torque100%75%
Times157810
Using
options
10%ED Braking torque100%*13)
Times157
Duty cycle
DC injection brakingStarting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
*1) Inverter output capacity (kVA) at 460V. Rated capacity reduces when power supply voltage decreases.
*2) Output voltage cannot exceed the power supply voltage.
*3) Current derating may be required in case of low impedance loads such as high frequency motor.
*4) When the input voltage is 380 to 398V/50Hz or 380 to 430V/60Hz, the tap of the auxiliary transformer must be changed.
*5) Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) =
*6) Tested at standard load condition (85% load).
*7) This value is under FUJI original calculation method.
*8) When power-factor correcting DC REACTOR (DCR) is used.
*9) When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter.
*10) When torque boost is set at 0.1, starting torque of 50% or more can be obtained.
*11) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.)
*12) Consult with Fuji Electric.
*13) Applicable to 10%ED when using options (standard)
·Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
· LINK setting : Selects from the following two items.
%ED
%ED
%ED
* Inverter restarts at the starting frequency when operation command is input while braking is operating.
* DC injection braking does not operate at the time of change-over from forward to reverse operation.
*
-UL/cUL -Low Voltage Directive -EMC Directive-TÜV (up to 30HP)
-IEC 61800-3 (EMC product standard including specific test methods)
NOTE : ( ) or < > in the “Remarks” column indicates the abbreviation of terminal function assigned to digital input terminals X1 to X9 and
1-6
transistor output terminals Y1 to Y5C.
•V/f control (Sinusoidal PWM control)
• Dynamic torque-vector control (Sinusoidal PWM control)
•Vector control with PG ...G11S only
• KEYPAD operation :
Forward or reverse operation by
Stopping by
• Digital input signal operation :
FWD·STOP command, REV·STOP command, Coast-to-stop
command, etc.
• LINK operation :
• RS-485 (standard)
• Various Bus interface is available. (Option)
• T-Link (FUJI private link) • Devicenet• CAN open
• Profibus-DP• Modbus Plus
• Interbus-S•JPCN1
• KEYPAD operation:
• External potentiometer : Variable resistor (1 to 5kΩ 1/2W)
• Analog input : External voltage or current input
(Reversible
operation)
(Inverse
operation)
• UP/DOWN control :
Output frequency increases when UP signal is ON, and
decreases when DOWN signal is ON.
• Multistep frequency selection :
Up to 16 different frequencies can be selected by digital input signal.
• Pulse train input: 0 to 100kp/s
• Digital signal (parallel) :
• LINK operation: RS-485 (standard) (RS-485FGABus)
Programmed PATTERN operation : Max. 7 stages
This operation can be performed by KEYPAD opration (
key) or digital input signal (FWD or REV).
REV
Transistor output : RUN, FAR, FDT, OL, LU, TL, etc.
(4 points)(4 output types are selectable)
Relay output: • Same as transistor output.
(2 points)• Alarm output (for any fault)
Analog output: Output frequency, Output current,
(1 point)Output voltage, Output torque, etc.
Pulse output: Output frequency, Output current,
(1 point)Output voltage, Output torque, etc.
0.01 to 3600s
Four kinds of acceleration and deceleration times can be set
independently, and the desired time is selected by combining
digital input signal (2 points).
Selects acceleration/deceleration pattern from the following 4 types.
• Linear
• S-curve (weak)
• S-curve (strong)
• Non-linear (for variable torque load)
When the acceleration time reaches 60s, the motor output torque
is automatically reduced to rated torque. Then the motor operation
mode is changed to torque limiting operation.
High and Low frequency limiters can be preset.
key
STOP
∨
0 to +10Vdc (0 to +5Vdc)
4 to 20mAdc
: Reversible operation by polarized signal can be
selected.
0 to ± 10Vdc (0 to ± 5Vdc)
: Inverse mode operation can be selected by
digital input signal (IVS).
0 to +10Vdc → 10 to 0Vdc (terminal 12)
4 to 20mAdc → 20 to 4mAdc (terminal C1)
12-bit parallel (12-bit binary) signal can be input.
(Option)• T-Link (FUJI private link)
• Profibus-DP
• Interbus-S
• Modbus Plus
• Devicenet
or
FWD
or ∨ key
REV
key
,
Option card (PG/Hz) required.
Switching between KEYPAD operation and
digital input signal operation is enabled by
pressing STOP key and RESET key at the
same time.
(LE)
• Connect to terminals 13, 12, and 11.
• Set Function code at ”F01: 1".
• Potentiometer is required separately.
0 to +5Vdc, 0 to ± 5Vdc input is enabled
when Func. code 17 (Gain for frequency
setting) is set at 200.0%.
Coast-to-stop is selectable by Function code “H11”.
(RT1, RT2)
The acceleration time is automatically
extended up to 3 times.
STOP
key and
∨
key at the
F42, A09
H30 to H39
C05 to C19
H31 to H39
F01
C21 to C28
F02
F36
E24, E25
F31
F35
H07
Chapter 1
∨
2. Common Specifications
ItemExplanationRemarksFunc. code
ControlBias frequencyF18
Gain for frequencyF17
setting
Jump frequency controlC01 to C04
Rotating motor pick upH09
(Flying start)
Auto-restart afterF14
momentary power failure
Line/Inverter
changeover operation
Slip compensationP09
Droop operationH28
Torque limitingF40, F41
Torque controlH18
PID controlH20 to H25
Automatic decelerationF41, E17
Second motor's settingA01 to A18
Energy saving operationH10
Fan stop operationH06
Universal DI
Universal DO
Bias frequency can be preset.
Gain for frequency setting can be preset. (0.0 to 200.0%)
ex.) Analog input 0 to +5Vdc with 200% gain results in
Maximum frequency at 5Vdc.
Jump frequency (3 points) and its common jump hysteresis width
(0 to 30Hz) can be preset.
A rotating motor(including inverse rotating mode) can be smoothly
picked up without stopping the motor. (speed search method)
Automatic restart is available without stopping motor after a
momentary power failure. (speed search method)
When "Smooth recovery" mode is selected, the motor speed drop
is held minimum.
Controls switching operation between line power and inverter.
The inverter has sequence function inside.
• The inverter output frequency is controlled according to the load
torque to keep motor speed constant.
• When the value is set at "0.00" and "Torque-vector" is set at "active", the
compensation value automatically selects the Fuji standard motor.
Slip compensation can be preset for the second motor.
The motor speed droops in proportional to output torque.(-9.9 to
0.0Hz) ...G11S only
When the motor torque reaches a preset limiting level, this function
automatically adjusts the output frequency to prevent the inverter
from tripping due to an overcurrent.
To rque limiting 1 and Torque limiting 2 can be individually set, and
are selectable with a digital input signal.
Output torque (or load factor ) can be controlled with an analog
input signal (terminal 12).
This function can control flowrate, pressure, etc. (with an analog feedback signal.)
••
• Reference signal
••
• KEYPAD operation (
Setting freq. / Maximum freq. X 100 [%]
•Voltage input (terminal 12 and V2) : 0 to 10Vdc / 0 to 100%
•Current input (terminal C1) : 4 to 20mAdc / 0 to 100%
• Reversible operation with polarity (terminal 12) :
0 to ± 10Vdc / 0 to ±100%
•Reversible operation with polarity (terminal 12 + V1) :
0 to ± 10Vdc / 0 to ± 100%
•Inverse mode operation (terminal 12 and V2) : 10 to 0Vdc / 0 to 100%
• Inverse mode operation (terminal C1) : 20 to 4mAdc / 0 to 100%
• PATTERN operation : Setting freq. / Maximum freq. X 100 [%]
•DI option input : • BCD...Setting freq. / Maximum freq. X 100 [%]
• Multistep frequency setting :
• RS-485 : Setting freq. / Maximum freq. X 100 [%]
••
• Feedback signal
••
• Terminal 12 (0 to 10Vdc / 0 to 100%, or 10 to 0Vdc / 0 to 100% )
• Terminal C1 (4 to 20mAdc / 0 to 100%, or 20 to 4mAdc / 0 to 100%)
Torque limiter 1 (Braking) is set at "F41: 0".
• In deceleration :
The deceleration time is automatically extended up to 3 times for
tripless operation even if a braking resistor is not used.
• In constant speed operation :
Based on regenerative energy, the frequency is increased, and
tripless operation is active.
This function is used for two motors switching operation.
• The second motor's V/f characteristics (base and maximum frequency),
rated current, torque boost, electronic thermal relay, etc. can be preset.
• The second motor's circuit parameter can be preset, and torquevector control can be applied to both motors.
This function minimizes inverter and motor losses at light load.
• This function detects temperature inside inverter to stop cooling
fans for silent operation and extending the fans' lifetime.
•On/off status of cooling fans is output.
Transmits to main controller of LINK operation
Outputs command signal from main controller of LINK operation.
∨
or
• Binary...Full scale / 100%
(Setting of Torque limiter 2 (Braking) is same.)
key) :
Setting freq. / Maximum freq. X 100
NOTE : ( ) or < > in the “Remarks” column indicates the abbreviation of terminal function assigned to digital input terminals X1 to X9 and
transistor (relay) output terminals Y1 to Y4 (Y5A, Y5C).
When the sum of setting frequency and bias
frequency is minus value, the output
frequency rise can be delayed. (No reverse
running is performed.)
(STM)
The inverter searches the motor speed, and
smoothly returns to setting frequency.
Even if the motor circuit is temporarily opened,
the inverter operates without a hitch.
(SW50, SW60)
<SW88, SW52-1, SW52-2>
Slip compensation value can be manually
set from 0.01 to 5.00Hz instead of 0.0 for
FUJI standard motor.
P11S series doesn't have this function.
(TL2/TL1)
• Torque polarity selectable. (Hz/TRQ)
• P11S series doesn't have this function.
• PID control is selected by "H20". (Hz/PID).
• Reference signal selection is made by "F01".
In "F01", "8: UP/DOWN control 1", "9: UP/
DOWN control 2", and "11: Pulse train
input" cannot be used for the reference
signal of PID control.
• Terminal V1 is optional.
• Terminal V2: EN only
[%
]
• Feedback signal selection is made by "H21".
When the deceleration time is extended to
longer than three times the setting time, the
inverter trips.
(M2/M1)
<SWM2>
<FAN>
(U-DI)
<U-DO>
H13 to H16
E01 to E09
E20 to E24, H13
A18
E16, E17
F01
C05 to C19
H21
1
1-7
Chapter 1
2. Common Specifications
ItemExplanationRemarksFunc. code
ControlZero speed control
Positioning control
Synchronized operation
Protection Overload
Overvoltage
Surge protection
Undervoltage
Input phase loss
Overheating
Short-circuit
Ground fault
Motor overloadF10 to F12
(Overload early warning)E33 to E35
DB resistor overheatingF13
Output phase loss
detection
Motor protection byH26, H27
PTC thermistor
Auto resetH04, H05
Condition Installation location
(Installation
and
operation)
Storage condition
Ambient temperature
Ambient humidity
Altitude
Vibration
The stopped motor holds its rotor angle. For a rotating motor, the
rotor angle is held after deceleration.
The SY option card can be used for positioning control by
differential counter method.
This function controls the synchronized operation between 2 axes with PGs.
Protects the inverter by electronic thermal and detection of inverter temperature.
Detects DC link circuit overvoltage, and stops the inverter.
Protects the inverter against surge voltage between the main
circuit power line and ground.
Detects DC link circuit undervoltage, and stops the inverter.
Phase loss protection for power line input
Protects the inverter by detection of inverter heat sink temperature.
Short-circuit protection for inverter output circuit
• Ground fault protection for inverter output circuit (3-phase current
• Zero-phase current detection method
• The inverter trips, and then protects the motor.
• Electronic thermal overload relay can be selected for standard
• The second motor's electronic thermal overload relay can be
• Before the inverter trips, outputs OL(Overload early warning)
• Prevents DB resistor overheating by internal electronic thermal
•Prevents DB resistor overheating by external thermal overload
When the inverter executes auto-tuning, detects each phase
impedance imbalance (and stops the inverter).
When the motor temperature exceeds allowable value, the inverter
trips automatically.
When the inverter is tripped, it resets automatically and restarts.
• Indoor use only.
• Free from corrosive gases, flammable gases, oil mist, dusts, and
-10 to +50˚C (14 to +122˚F) (For inverters of 30HP or smaller, remove the
ventilation covers when operated at temperature of 40˚C (104˚F)or above.)
5 to 95%RH (non-condensing)
33ft (1000m) or less. Applicable to 9800ft (3000m) with power
derating (-10% / 33ft (1000m))
3mm (vibration amplitude) at 2 to less than 9Hz
9.8m/s
2m/s2 at 20 to less than 55Hz (2m/s2 at 9 to less than 55Hz : G11S
125HP, P11S 150HP or more)
1m/s
• Temperature : -25 to +65°C (-13 to +149°F)
• Humidity : 5 to 95%RH (No-condensing)
detection method)
motor or inverter motor
preset for 2-motor changeover operation.
signal at a preset level.
overload relay. (10HP or smaller for G11S, 15HP or smaller for
P11S)
relay attached to DB resistor. (15HP or larger for G11S, 20HP or
larger for P11S)
direct sunlight.
2
at 9 to less than 20Hz
2
at 55 to less than 200Hz
A motor with PG and option card (OPCG11S-PG) are necessary.(ZERO)
P11S series doesn't have this function.
Option card (PG/SY) required
Option card is required.
230V : 400Vdc, 460V : 800Vdc
• Line voltage : 5kV
• Between power line and ground : 7kV (1.2/50µs)
230V : 200Vdc, 460V : 400Vdc
•
Operation details are selected by Function code F14.
• 30HP or smaller inverter
• 40HP or larger inverter
• Thermal time constant (0.5 to 75.0
minutes) can be preset for a special motor.
• External singnal is used for changeover.
Related transistor output : OL
<OL1, OL2>
• The inverter stops electricity discharge
operation, to protect the DB resistor.
Then, usually inverter displays "OU trip".
• Connects the relay output to the terminal
THR, to protect the DB resistor.
Then, usually the inverter displays "OH trip".
Number of Auto reset times and reset
interval can be preset.
Pollution degree 2 when complying with Low
Voltage Directive is needed.
*
When altitude is 6600ft (2000m) or higher,
interface circuit should be isolated from main
power lines, to comply with Low Voltage Directive.
*) ▲▲ : By function code setting, alarm output can be disabled.
NOTES :
1) Retaining alarm signal when auxiliary controll power supply is not used :
2) To issue the RESET command, press the
3) Fault history data is stored for the past four trips.
1-10
• Stops running to protect inverter from an overcurrent resulting from
overload.
• Stops running to protect inverter from an overcurrent due to a short-circuit
in the output circuit.
• Stops running to protect inverter from an overcurrent due to a ground
fault in the output circuit.
• Stops running to protect inverter from an overcurrent resulting from ground fault
in the output circuit by detecting zero-phase current. (30kW or larger model only)
• The inverter stops when it detects an overvoltage in the DC link circuit.
(230V : 400Vdc or more, 460V : 800Vdc or more)
•
Protection is not assured if excess AC line voltage is applied inadvertently.
• Protects the inverter against surge voltage between the main circuit power line and ground.
• Protects the inverter against surge voltage in the main circuit power line.
• The inverter may be tripped by some other protective function.
• Stops the inverter when the DC link circuit voltage drops below undervoltage level.
(230V series : 200V DC or less, 460V series : 400V DC or less)
• Alarm signal is not output even if the DC link circuit voltage drops, when “F14 : 3 to 5” is selected.
• The inverter is protected from being damaged when open-phase fault occurs.
• Stops the inverter when it detects excess heat sink temperature in case of cooling fan failure or
overload.
• Stops the inverter when it detects an abnormal rise in temperature in the inverter unit caused by
insufficient ventilation in cubicles or an abnormal ambient temperature.
• Stops the inverter when it detects an abnormal rise in temperature inside the inverter.
• When the built-in or external braking resistor overheats, the inverter stops discharging and running.
•
Function data appropriate for the resistor type (built-in/external) must be set. (G11S: 10HP or smaller only)
• This function stops the inverter by detecting an inverter overload.
• This function stops the inverter by detecting an overload in a standard
motor or inverter motor.
When a blown fuse is detected, the inverter stops running. (40HP or larger model only)
•
• When an output current exceeds the limit during acceleration, this function lowers output frequency
to prevent the occurrence of an OC1 trip.
• The stall prevention function can be disabled.
• During running in which acceleration is 60s or longer, this function increases the acceleration time to
prevent the occurrence of an OLU trip.
• The acceleration time can be prolonged up to three times the preset time.
• The inverter stops on receiving external alarm signals.
• Use THR terminal function (digital input).
• Stops the inverter when the output frequency exceeds the rated maximum frequency by 20%.
• If disconnection occurs in pulse generator circuits, the inverter issues an alarm.
• The inverter outputs a relay contact signal when the inverter issued an
alarm and stopped.
• An alarm-stop state of the inverter can be cleared with the RESET key or
by a digital input signal (RST).
• Store up to four instances of previous alarm data.
• The inverter can store and display details of the latest alarm history data.
• The inverter checks memory data after power-on and when the data is written. If a memory error is
detected, the inverter stops.
• If an error is detected in communication between the inverter and KEYPAD when the Keypad panel
is being used, the inverter stops.
• When operated by external signals, the inverter continues running. The alarm output (for any fault) is
not output. Only Er2 is displayed.
• If the inverter detects a CPU error caused by noise or some other factor, the inverter stops.
• If a checksum error or disconnection is detected during communication, the inverter issues an alarm.
• If a linkage error or other option error is detected, the inverter issues an alarm.
Er6 is indicated only when the inverter is forcedly stopped by [STOP1] or [STOP2] operation in E01 to
E09 (Set value: 30 or 31)
If an unbalance of output circuits is detected during auto-tuning, this function issues an alarm (and
stops the inverter).
• If an RS-485 communication error is detected, the inverter issues an alarm.
If the inverter power supply is cut off while an internal alarm signal is being output, the alarm signal cannot be retained.
LED monitor
During acceleration
During deceleration
While running at constant
speed
Groung fault
During acceleration
During deceleration
While running at constant speed
Motor 1 overload
Motor 2 overload
• Output terminals:
30A, 30B, and 30C
• Use the RST terminal
function for signal input.
• Even if main power
input is turned off, alarm
history and trip-cause
data are retained.
key on the KEYPAD panel or connect terminals RST and CM and disconnect them afterwards.
RESET
Alarm output Func. code
(30Ry) *)
F14
F13
F10 to F12
A06 to A08
F40, F41
E16, E17
––
H12
F36
F02
Chapter 1
∨
2. Common Specifications
2.3 Function settings
The function marked can be set while the inverter is running. Other functions must be set while the inverter is
stopped.
Fundamental Functions
Function
Code NameLCD monitorunit30HP40HP
F00Data protectionF00 DATA PRTC0:Data change enable
F14Restart mode (Select) F14 RESTART0 : Inactive (Trip and alarm when power failure occurs.)
after momentary1 : Inactive (Trip, and alarm when power recovers.)
power failure2 : Inactive (Deceleration stop, and alarm)
F15Frequency(High) F15 H LIMITERG11S : 0 to 400HzP11S : 0 to 120Hz
limiter(Low) F16 L LIMITERG11S : 0 to 400HzP11S : 0 to 120Hz
F16
F17Gain(for frequency F17 FREQ GAIN0.0 to 200.0%
F18Bias frequencyF18 FREQ BIASG11S : -400.0 to 400.0Hz P11S : -120.0 to 120.0Hz
F20DC brake(Starting freq.) F20 DC BRK Hz0.0 to 60.0Hz
F21(Braking level) F21 DC BRK LVLG11S : 0 to 100%P11S : 0 to 80%
F22(Braking time) F22 DC BRK t0.0 (DC brake inactive),0.1 to 30.0s
setting signal)
1:Data protection
Voltage input (terminal 12) (0 to 10Vdc, 0 to 5Vdc)
1:
2:Current input (terminal C1) (4 to 20mAdc)
3:Voltage and current input (terminals 12 and C1)
4:Reversible operation with polarity
(terminal 12) (0 to ± 10Vdc)
5:Reversible operation with polarity
(terminal 12 and V1) (0 to ± 10Vdc)
6:Inverse mode operation (terminal 12)
(+10 to 0Vdc)
7:Inverse mode operation (terminal C1)
(20 to 4mAdc)
8:UP/DOWN control 1 (initial freq. = 0Hz)
9:UP/DOWN control 2 (initial freq. = last value)
10 : PATTERN operation
11 : DI option or Pulse train input
1:External signal input (digital input)
(Operation by FWD or REV command)
P11S : 50 to 120Hz
P11S : 25 to 120Hz
supply voltage is set.
320 to 480V : AVR active (460V)
0.1 to 0.9 : Manual (for variable torque load)
1.0 to 1.9 : Manual (for proportional torque load)
2.0 to 20.0 : Manual (for constant torque load)
rated current, in Ampere
2 : Active (for external braking resistor)
[15HP or larger]
0 : Inactive
P11S [15HP or smaller]
0 : Inactive
2 : Active (for external braking resistor)
[20HP or larger]
0 : Inactive
Active (Smooth recovery by continuous operation mode)
3:
4:Active (Momentarily stops and restarts at output
frequency of before power failure)
5:Active (Momentarily stops and restarts at
starting frequency)
Setting rangeUnit
key)
or
or
FWD
REV
STOP
key)
Min. Factory setting
--0
--0
--0
Hz160
Hz 160
V1
230:(230V class)
V1230:(230V class)
s0.016.020.0
s 0.016.020.0
- 0.1G11S : 2.0
--1
A 0.01Motor rated
min0.15.010.0
--1
--0
--0
--0
--0
Hz1 70
Hz10
% 0.1100.0
Hz 0.10.0
Hz 0.10.0
% 1 0
s 0.10.0
460:(460V class)
460:(460V class)
P11S : 2.0
current
Remarks
Setting can be made so that
a set value cannot be easily
changed by KEYPAD panel
operation.
Sets the operation
command input method.
Sets the maximum output
frequency for motor 1.
Sets the base frequency for
motor 1.
Sets the output voltage at
the Base frequency 1 “F04”.
Sets the output voltage at the
Maximum frequency 1 “F03”.
During deceleration, Coastto-stop can be selected by
setting of “H11”.
Torque boost for motor 2
can also be set by “A05”.
Selection fo motor 2 can
also be made by “A06”.
Level setting for motor 2 can
also be made by “A07”.
Setting for motor 2 can also
be made by “A08”.
Not provided with models
15HP or larger.
Not provided with models
20HP or larger.
For detailed setting
procedure, see “H13” to
“H16”.
Minus bias setting is possible.
1
1-11
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is
stopped.
Function
Code NameLCD monitorunit30HP40HP
Setting rangeUnit
F23Starting frequency (Freq.) F23 START Hz0.1 to 60.0Hz
F24(Holding time) F24 HOLDING t0.0 to 10.0s
F25Stop frequencyF25 STOP Hz0.1 to 6.0Hz
F26Motor sound (Carrier freq.) F26 MTR SOUND0.75-15kHz 0.75-10kHz 0.75-6kHz
G11S-75HP100HP–
P11S-30HP40-100HP 125HP
F27 (Sound tone) F27 MTR TONE0 : Level 0
1: Level 1
2: Level 2
3: Level 3
F30FMA (Voltage adjust) F30 FMA V-ADJ0 to 200%
F31(Function) F31 FMA FUNC0 : Output frequency 1 (Before slip compensation)
1: Output frequency 2 (After slip compensation)
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback value
8: PG feedback value
9: DC link circuit voltage
10 : Universal AO
F33FMP(Pulse rate) F33 FMP PULSES300 to 6000 p/s (at full scale)
F34(Voltage adjust) F34 FMP V-ADJ0%: Pulse rate output (50% duty)
15 : Switching operation between line and inverter
(50Hz)[SW50]
16 : Switching operation between line and inverter
(60Hz)[SW60]
17 : UP command[UP]
18 : DOWN command[DOWN]
19 : Write enable for KEYPAD[WE-KP]
20 : PID control cancel[Hz/PID]
21 : Inverse mode changeover (terminals 12 and C1)
22 : Interlock signal for 52-2[IL]
23 : TRQ control cancel[Hz/TRQ]
24 : Link enable (Bus, RS-485)[LE]
25 : Universal DI[U-DI]
26 : Pick up start mode[STM]
27 : SY-PG enable[PG/Hz]
28 : Synchronization command[SYC]
29 : Zero speed command[ZERO]
30 : Forced stop command[STOP1]
31 : Forced stop command with Deceleration time 4
32 : Pre-exciting command[EXITE]
E10Acceleration time 2
E11Deceleration time 2E11 DEC TIME2
E12Acceleration time 3E12 ACC TIME3
E13Deceleration time 3E13 DEC TIME3
E14Acceleration time 4
E15Deceleration time 4E15 DEC TIME4
E16Tor que limiter 2 (Driving) E16 DRV TRQ 2G11S: 20 to 200%, 999% (999: No limit) *2)
When 15 or 16 is turned
on, the operation smoothly
changes to commercial
power operation at 50 or
60Hz, without stopping the
motor.
From 50Hz power line : (SW50)
From 60Hz power line : (SW60)
17, 18 : "F01" must be set at
"8: UP/DOWN
control 1" or "9: UP/
DOWN control 2".
20 :When this signal is on,
PID control is canceled
and KEYPAD operation
is effective.
23 :When this signal is on,
torque control is canceled.
27 : PG/Hz is option.
28 : SY is option.
29 : ZERO is option.
32 : EXITE is option.
F40, F41
29 : SY is option.
34: DNZS is option.
1
F07
F08
1-13
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is
stopped.
Function
Code NameLCD monitorunit30HP40HP
E30FAR function (Hysteresis) E30 FAR HYSTR 0.0 to 10.0 Hz
signal
Setting rangeUnit
E31FDT1 function (Level) E31 FDT1 LEVELG11S : 0 to 400 HzP11S : 0 to 120 Hz
E32signal(Hysteresis) E32 FDT HYSTR0.0 to 30.0 Hz
E33OL1 function(Mode select) E33 OL1 WARNING 0 : Thermal calculation
signal1 : Output current
E34(Level) E34 OL1 LEVELG11S : Approx. 5 to 200% of rated current
P11S : Approx. 5 to 150% of rated current
E35(Timer) E35 OL TIMER0.0 to 60.0s
E36FDT2 function (Level) E36 FDT2 LEVELG11S : 0 to 400HzP11S : 0 to 120Hz
E37OL2 function (Level) E37 OL2 LEVELG11S : Approx. 5 to 200% of rated current
P11S : Approx. 5 to 150% of rated current
E40Display coefficient AE40 COEF A-999.00 to 999.00
E41Display coefficient BE41 COEF B-999.00 to 999.00
E42LED Display filterE42 DISPLAY FL0.0 to 5.0s
E43LED Monitor (Function) E43 LED MNTR0 : Output frequency 1 (Before slip compensation)
E44(Display at STOP mode) E44 LED MNTR20 : Setting value
C31Offset(Terminal 12) C31 OFFSET 12-5.0 to +5.0%
C32Offset (Terminal C1) C32 OFFSET C1-5.0 to +5.0%
C33Analog setting signalC33 REF FILTER0.00 to 5.00s
filter
1: Voltage input (terminal 12) (0 to 10Vdc, 0 to 5Vdc)
2: Current input (terminal C1) (4 to 20mAdc)
3: Voltage and current input (terminals 12 and C1)
4: Reversible operation with polarity (terminal 12)
(0 to ± 10Vdc)
5: Reversible operation with polarity
(terminal 12 and V1) (0 to ± 10Vdc)
6: Inverse mode operation (terminal 12) (10 to 0Vdc)
7: Inverse mode operation (terminal C1) (20 to 4mAdc)
8: UP/DOWN control 1 (initial freq. = 0Hz)
9: UP/DOWN control 2 (initial freq. = last value)
10 : PATTERN operation
11 : DI option or Pulse train input
Setting rangeUnit
∨
or key)
Min. Factory setting
s0.010.00 F1
s0.010.00 F1
s0.010.00 F1
s0.010.00 F1
s0.010.00 F1
s0.010.00 F1
s0.010.00 F1
P02Motor 1(Capacity) P02 M1-CAP30HP or smaller : 0.01 to 45.00 kW
P03(Rated current) P03 M1-Ir0.00 to 2000 A
P04(Tuning) P04 M1 TUN10 : Inactive
P05(On-line Tuning) P05 M1 TUN20 : Inactive
P06(No-load current) P06 M1-Io0.00 to 2000 A
P07(%R1 setting) P07 M1-%R10.00 to 50.00 %
P08(%X setting) P08 M1-%X0.00 to 50.00 %
40HP or larger : 0.01 to 500.00 kW
1: Active (One time tuning of %R1 and %X (on
motor stopping mode ))
2: Active (One time tuning of %R1, %X and Io (on
motor running mode ))
1: Active (Real time tuning of %R2)
Setting rangeUnit
Min. Factory setting
pole 24
kW0.01 Motor Capacity
A0.01
--0
--0
A 0.01 Fuji standard
% 0.01 Fuji standard
% 0.01 Fuji standard
Motor rated
current
rated value
rated value
rated value
Remarks
Sets the number poles of
the motor 1.
Set the applied motor capacity.
This setting automatically sets
"P03" and "P06" to "P08".
Frame must be from -2 to +1.
When a frame is outside this
range, take a special note.
Sets the motor rated current.
Measure %R1 of motor, and
%X and Io at base frequency.
When "1" is selected, data is
stored in "P07" and "P08". When
"2" selected, data is stored in
"P06" to "P08".
Data in "P07" and "P08" is
not updated.
Sets exciting current at
torque-vector control.
Sets motor primary coil
resistance manually.
R1+Cable R
%R1=x 100
V/( 3 x I)
R1: Motor primary resistance [Ω]
Cable R : Resistance at output
side cable
V : Rated voltage [V]
I : Motor rated current [A]
Sets motor leakage
inductance at base
frequency manually.
P09
NOTE: Percent shall be set according to Function code "P02" or "A09", motor capacity.
(Slip compensation control 1)
P09 SLIP COMP10.00 to +15.00 Hz
Torque referenced here may not be obtainable when "P02" or "A09" is set at "0".
Hz0.010.00
X1 : Motor primary leakage
reactance [Ω]
X2 : Motor secondary leakage
reacstance [Ω]
XM : Excitation reactance [Ω]
Cable X : Cable resctance
(Primary conversion value) [Ω]
V : Rated voltage [V]
I : Motor rated current [A]
Sets the slip frequency.
1-15
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is
stopped.
High Performance Functions
1-16
Function
Code NameLCD monitorunit30HP40HP
H03Data initializingH03 DATA INIT 0 : Manual set value
H04Auto-reset(Times) H04 AUTO-RESET0 (Inactive), 1 to 10 times
H05(Reset interval) H05 RESET INT2 to 20s
H06Fan stop operationH06 FAN STOP0: Inactive
Active (Only Auto-restart after momentary power failure mode )
2: Active (All start mode)
1: Active (Only when torque boost "F09" is in
manual setting mode
1: Coast-to-stop
H16 SELFHOLD t0.0 to 30.0s, 999s (999s: The operation command is
H26 PTC MODE0 : Inactive
response error)1 : Operation for H33 timer, and alarm (Er8)
400 to 600V (460V)
held during DC link circuit voltage is larger than 50V)
1: Active (Torque control by terminal 12 (Driving))
2: Active (Torque control by terminal 12 (Driving &
P11S 0 : Inactive (Fixed)
1: Active
1: Active
2: Active (inverse operation mode)
1: Ter minal C1 (4 to 20mA)
2: Ter minal 12 (+10 to 0V)
3: Ter minal C1 (20 to 4mA)
0.1 to 3600.0s
0.01 to 10.0s
1: Active
P11S : 0.0 (Fixed)
0 :X -1:XX2 :X -X
3 :XXX
2: Operation for H33 timer,and retry to communicate.
* If the retry fails, then the inverter trips("Er 8").
3: Continuous operation
1: 9600
2: 4800
3: 2400
4: 1200
Setting rangeUnit
(0 to +10V/0 to 200%)
Braking))
(0 to +10V/0 to 200%)
command)command)
(X: Valid -: Invalid)
Min. Factory setting
--0
-10
s15
--0
--0
--0
--0
-- G11S:0
--0
--1
s0.10.5
Hz/s 0.0110.00
V 1 230V class : 235V
s0.1999
--0
--0
--0
--0
--1
-0.010.1
s 0.10.0
s 0.010.00
s 0.10.5
--0
V0.011.60
Hz0.10.0
--0
-11
--0
s 0.12.0
--1
P11S:1
460V class : 470V
Remarks
When data code is set at "1", all
function data is returned to
initial data (factory setting data).
Automatically returns to "0"
after initializing.
Time required until motor residual
voltage reduces to zero.
P11S series does not have
this function.
Gain for frequency setting
is disabled.
When the acceleration time is
longer than 60s, this function
prevents inverter trip due to
overvurrent, to accelerates
motor in a shortest time.
E01-E09:20
C33
E01-E09:21
P11S does not have this
function.
Selects type of LINK
operation in LINK operation
mode.
F01:11, C30:11,
E01-E09:24,25, F02
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is
stopped.
Function
Code NameLCD monitorunit30HP40HP
H35(Data length) H35 LENGTH0 : 8 bit1 : 7 bit
H36(Parity check) H36 PARITY0 : No checking
H37(Stop bits) H37 STOP BITS0 : 2 bit1 : 1 bit
H38
H39(Response interval) H39 INTERVAL0.00 to 1.00s
(No response error
detection time)
H38 NO RES t0 (No detection), 1 to 60s
1: Even parity
2: Odd parity
Setting rangeUnit
Alternative Motor Parameters
Min. Factory setting
--0
--0
--0
s10
s 0.010.01
Remarks
1
Function
Code NameLCD monitorunit30HP40HP
A01Maximum frequency 2 A01 MAX Hz-2G11S : 50 to 400HzP11S : 50 to 120Hz
A02 Base frequency 2A02 BASE Hz-2G11S : 25 to 400HzP11S : 25 to 120Hz
A03 Rated voltage 2A03 RATED V-20V (Free): The output voltage in proporpion to the
80 to 240V : AVR active (230V)
320 to 480V : AVR active (460V)
A04Maximum voltage 2A04 MAX V-280 to 240V : AVR active (230V)
(at Maximum frequency 2)320 to 480V : AVR active (460V)
thermal1 : Active (for 4-pole standard motor)
overload relay2 : Active (for 4-pole inverter motor)
A07for motor 2(Level) A07 OL LEVEL2Approx. 20 to 135% of the inverter rated current, in
A08 (Thermal time constant) A08 TIME CNST20.5 to 75.0 min
A09 Torque vector control 2 A09 TRQVECTOR2 0 : Inactive
A10Number of motor-2 poles A10 M2 POLES2 to 14
A11Motor 2(Capacity) A11 M2-CAP30HP or smaller : 0.01 to 45.00 kW
A12(Rated current) A12 M2-Ir0.00 to 2000 A
A13(Tuning) A13 M2 TUN10 : Inactive
A14(On-line Tuning) A14 M2 TUN20 : Inactive
A15(No-load current) A15 M2-Io 0.00 to 2000 A
A16 (%R1 setting) A16 M2-%R10.00 to 50.00 %
A17(%X setting) A17 M2-%X0.00 to 50.00 %
(Slip compensation control 2)
A18
A18 SLIP COMP20.00 to +15.00 Hz
0.1 to 0.9: Manual (for variable torque load)
1.0 to 1.9: Manual (for proportional torque load)
2.0 to 20.0 : Manual (for constant torque load)
Ampere
1: Active
40HP or larger : 0.01 to 500.00 kW
1: Active (One time tuning of %R1 and %X (on
motor stopping mode ))
2: Active (One time tuning of %R1, %X and Io (on
motor running mode ))
1: Active (Real time tuning of %R1 and %X)
Setting rangeUnit
power supply voltage is set.(at Base frequency 2)
Min. Factory setting
Hz 160
Hz 160
V 1
220:(230V class)
380:(460V class)
V 1220:(230V class)
- 0.1G11S : 2.0
--1
A 0.01Motor rated
min 0.15.010.0
--0
- 24
kw0.01 Motor Capacity
A 0.01Motor rated
--0
--0
A 0.01 Fuji standard
% 0.01 Fuji standard
% 0.01 Fuji standard
Hz0.010.00
380:(460V class)
P11S : 2.0
current
current
rated value
rated value
rated value
Remarks
Sets the maximum output
frequency for motor 2.
Sets the output voltage at
the Base frequency 2 "A02".
Sets the output voltage at the
Maximum frequency 2 "A01".
Sets the number of poles of
motor 2.
Set the applied motor capacity.
This setting automatically sets
"P03" and "P06" to "P08". Frame
must be from -2 to +1. When a
frame is outside this range, take
a special note.
Sets the motor rated current.
Measure %R1 of motor, and
%X and Io at base
frequency.
When "1" is selected, data
is stored in "A16" and "A17".
When "2" selected, data is
stored in "A15" to "A17".
Data in "A16" and "A17" is
not updated.
Sets exciting current at
torque-vector control.
Sets motor primary coil
resistance manually.
R1+Cable R
%R1=x 100
V/( 3 x I)
R1: Motor primary resistance [Ω]
Cable R : Resistance at output
side cable
V : Rated voltage [V]
I : Motor rated current [A]
Sets motor leakage
inductance at base
frequency manually.
%X=x 100
X1 : Motor primary leakage
reactance [Ω]
X2 : Motor secondary leakage
reactance [Ω]
XM : Excitation reactance [Ω]
Cable X : Cable resctance
(Primary conversion value) [Ω]
V : Rated voltage [V]
I : Motor rated current [A]
Sets the slip frequency.
XM
X1+X2 x+Cable X
X2+XM
V/ ( 3 x I)
1-17
Chapter 1
2. Common Specifications
User Functions
Function
Code NameLCD monitorunit30HP40HP
U01Maximum compensation
frequency during
braking torque limit
U021st S-shape level at
acceleration
U032nd S-shape level at
acceleration
U041st S-shape level at
deceleration
U052nd S-shape level at
deceleration
U08Main DC link capacitor
U09(Measured value)
U10PC board capacitor
powered on time
U11Cooling fan operating
time
U13Magnetize current
vibration damping gain
U15Slip compensation filter
time constant
U23Integral gain of
continuous operation
at power failure
U24Proportional gain of
continuous operation at
power failure
U48Input phase loss
protection
U49RS-485 protocol
selection
U56Speed agreement
U57/PG error
U58PG error selection
U59Braking-resistor
function select
(up to 30HP)
Manufacturer’s
function (40HP or more)
U60Regeneration
avoidance at
deceleration
U61Voltage detect offset
and gain adjustment
(Initial value)
(Detection width)
(Detection timer)
U01 USER 010 to 65535-1
U02 USER 021 to 50%%1
U03 USER 031 to 50%%1
U04 USER 041 to 50%%1
U05 USER 051 to 50%%1
U08 USER 080 to 65535-1
U09 USER 090 to 65535-1
U10 USER 100 to 65535hh1
U11 USER 110 to 65535hh1
U13 USER 130 to 32767-1
U15 USER 150 to 32767-1
U23 USER 230 to 65535-1
U24 USER 240 to 65535-1
U48 USER 480, 1, 2--
U49 USER 490, 1--
U56 USER 560 to 50%%1
U57 USER 570.0 to 10.0ss0.1
U58 USER 580, 1--
U59 USER 5900 to A8(HEX)-1
U60 USER 600, 1--
U61 USER 61Up to 30HP : F0(Fixed.)--
40HP or more : F0, 1, 2
Setting rangeUnit
Min. Factory setting
75
10
10
10
10
xxxx
0
0
0
819 410
556 546
1738 1000
1024 1000
-75HP 100HP0 1
0
10
0.5
1
00
0
0
Remarks
1-18
The information described in this document is for the purpose of selecting the
Caution
appropriate product only. Before actually using this product, be sure to read the
Instruction Manual carefully to ensure proper operation.
3. Wiring Diagram
3.1 Wiring diagram before shipment from factory
(1) 230V/460VFRENIC5000G11S: 1/4 to 1HP / 1/2, 1HP
Chapter 1
3. Wiring Diagram
Power supply ( *1)
3-phase
200 to 230V
50/60Hz
or
3-phase
400 to 480V
50/60Hz
Potentiometer power supply
Analog input
Analog output (analog monitor)
MCCB
or
GFCI
(*2)
Grounding
Voltage input
Current input
MC
(*2)
Main circuit
Jumper wire (*3)
P1
L1/R
L2/S
L3/T
SR
73
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
+0〜10Vdc
P(+)
+10Vdc
+24Vdc
DBR
0V
0V
DB
N(-)
30
U
V
W
( *4)
G
30C
30B
Alarm output (for any fault)
30A
NOTE: Common terminals [11], (CM), and <CME> for
control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage
matches the power supply voltage.
(*2) Use this peripheral device when necessary.
(*3) Terminals [P1] and [P(+)] are connected
with a jumper wire before shipping.
(*4) Terminal for grounding the motor.
Connect it, if necessary.
1
Motor
M
G
Digital input
Pulse output
(frequency monitor)
(CM)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
RS-485
Pulse output
(DX-)
(DX+)
(SD)
<Y5C>
<Y5A>
<Y4>
<Y3>
<Y2>
<Y1>
<CME>
Relay output
Transistor output
1-19
Chapter 1
3. Wiring Diagram
The information described in this document is for the purpose of selecting the
Caution
(2) 230V/460VFRENIC5000G11S : 2 to 10HP
appropriate product only. Before actually using this product, be sure to read the
Instruction Manual carefully to ensure proper operation.
FRENIC5000P11S : 7.5 to 15HP
Main circuit
Jumper wire (*3)
Power supply ( *1)
3-phase
200 to 230V
50/60Hz
or
3-phase
400 to 480V
50/60Hz
Potentiometer power supply
Analog input
Analog output (analog monitor)
Digital input
MCCB
or
GFCI
(*2)
Auxiliary control
power supply (*4)
Grounding
Voltage input
Current input
Pulse output
(frequency monitor)
MC
(*2)
P1
L1/R
L2/S
L3/T
(R0)
(T0)
SR
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
+0 〜10Vdc
Pulse output
P(+)
+10Vdc
+24Vdc
(DX-)
DBR
(*5)
0V
0V
(DX+)
DB
(SD)
N(-)
30
W
G
30C
30B
30A
<Y5C>
<Y5A>
<Y4>
<Y3>
<Y2>
<Y1>
<CME>
U
V
(*6)
Alarm output (for any fault)
NOTE: Common terminals [11], (CM), and <CME> for
control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage
matches the power supply voltage.
(*2) Use this peripheral device when necessary.
(*3) Terminals [P1] and [P(+)] are connected
with a jumper wire before shipping.
(*4) Even if these terminals are not powered,
the inverter can be operated.
(*5) The built-in braking resistor (DBR) is not
mounted on P11S models 7.5HP to 15HP
(*6) Terminal for grounding the motor.
Connect it, if necessary.
Relay output
Transistor output
Motor
M
G
1-20
RS-485
The information described in this document is for the purpose of selecting the
Caution
appropriate product only. Before actually using this product, be sure to read the
Instruction Manual carefully to ensure proper operation.
(3) 230V/460VFRENIC5000G11S : 15 to 30HP
FRENIC5000P11S : 20 to 30HP
Main circuit
Jumper wire (*3)
Chapter 1
3. Wiring Diagram
1
Power supply ( *1)
3-phase
200 to 230V
50/60Hz
or
3-phase
400 to 480V
50/60Hz
Analog input
Digital input
Auxiliary control
power supply (*4)
Potentiometer power supply
Analog output (analog monitor)
MCCB
or
GFCI
(*2)
Pulse output
(frequency monitor)
MC
(*2)
Grounding
Voltage input
Current input
P1
L1/R
L2/S
L3/T
(R0)
(T0)
SR
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
+0〜10Vdc
Pulse output
(DX-)
+10Vdc
+24Vdc
0V
0V
(DX+)
P(+)
(SD)
N(-)
30
U
V
W
G
30C
30B
30A
<Y5C>
<Y5A>
<Y4>
<Y3>
<Y2>
<Y1>
<CME>
Motor
M
G
(*5)
Alarm output (for any fault)
NOTE: Common terminals [11], (CM), and <CME> for
control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage
matches the power supply voltage.
(*2) Use this peripheral device when necessary.
(*3) Terminals [P1] and [P(+)] are connected
with a jumper wire before shipping.
(*4) Even if these terminals are not powered,
the inverter can be operated.
(*5) Terminal for grounding the motor.
Connect it, if necessary.
Relay output
Transistor output
RS-485
1-21
Chapter 1
3. Wiring Diagram
The information described in this document is for the purpose of selecting the
Caution
(4) 230V/460VFRENIC5000G11S : 40 to 75HP
appropriate product only. Before actually using this product, be sure to read the
Instruction Manual carefully to ensure proper operation.
FRENIC5000P11S : 40 to 75HP
Main circuit
Jumper wire (*3)
Power supply ( *1)
3-phase
200 to 230V
50/60Hz
or
3-phase
400 to 480V
50/60Hz
Analog input
Digital input
Auxiliary control
power supply (*4)
Potentiometer power supply
Analog output (analog monitor)
MCCB
or
GFCI
(*2)
Pulse output
(frequency monitor)
MC
(*2)
Grounding
Voltage input
Current input
P1
L1/R
L2/S
L3/T
(R0)
(T0)
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
Pulse output
SR
73
+10Vdc
+0〜10Vdc
+24Vdc
(DX-)
P(+)
CNUX (∗)
U1 U2
0V
0V
(DX+)
(SD)
N(-)
30
U
V
W
G
30C
30B
30A
<Y5C>
<Y5A>
<Y4>
<Y3>
<Y2>
<Y1>
<CME>
Motor
M
G
(*5)
Alarm output (for any fault)
NOTE: Common terminals [11], (CM), and <CME> for
control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage
matches the power supply voltage.
(*2) Use this peripheral device when necessary.
(*3) Terminals [P1] and [P(+)] are connected
with a jumper wire before shipping.
(*4) Even if these terminals are not powered,
the inverter can be operated.
(*5) Terminal for grounding the motor.
Connect it, if necessary.
Relay output
Transistor output
(∗)
400 to 440V/50Hz, 440 to 480V/60Hz
380V/50Hz (398V or smaller),
380 to 415V/60Hz (430V or smaller)
Input voltage
CNUX connector
U1
U2
1-22
RS-485
The information described in this document is for the purpose of selecting the
Caution
appropriate product only. Before actually using this product, be sure to read the
Instruction Manual carefully to ensure proper operation.
(5) 2300V/460V FRENIC5000G11S : 100, 125HP / 100 to 600HP
FRENIC5000P11S : 100 to 150HP / 100 to 800HP
DC REACTOR (DCR)
(*3)
Main circuit
MCCB
Power supply ( *1)
3-phase
200 to 230V
50/60Hz
or
3-phase
400 to 480V
50/60Hz
Auxiliary control
power supply (*4)
or
GFCI
(*2)
Grounding
MC
(*2)
L1/R
L2/S
L3/T
(R0)
(T0)
N(-)
P1
SR
73
G
P(+)
CNUX (∗)
U1 U2
Chapter 1
3. Wiring Diagram
1
U
V
W
(*5)
G
Motor
M
G
Analog input
Digital input
Potentiometer power supply
Voltage input
Current input
Analog output (analog monitor)
Pulse output
(frequency monitor)
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X1)
(X9)
(CM)
(FMP)
+0〜10Vdc
Pulse output
+10Vdc
+24Vdc
(DX-)
0V
0V
(DX+)
(SD)
30
30C
30B
30A
<Y5C>
<Y5A>
<Y4>
<Y3>
<Y2>
<Y1>
<CME>
Alarm output (for any fault)
NOTE: Common terminals [11], (CM), and <CME> for
control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage
matches the power supply voltage.
(*2) Use this peripheral device when necessary.
(*3) A DC REACTOR (DCR) is provided as standard in
JE version for inverters of 100HP or larger
(separately installed).
Be sure to connect the DCR properly.
(*4) Even if these terminals are not powered,
the inverter can be operated.
(*5) Terminal for grounding the motor.
Connect it, if necessary.
Relay output
Transistor output
(∗)
400 to 440V/50Hz, 440 to 480V/60Hz
380V/50Hz (398V or smaller),
380 to 415V/60Hz (430V or smaller)
Input voltage
CNUX connector
U1
U2
RS-485
1-23
Chapter 1
3. Wiring Diagram
The information described in this document is for the purpose of selecting the