Fuji Electric FRENIC-5000G11S, FRENIC-5000 P11S Operating Manual

CONTENTS

Chapter 1 Specifications
1. Standard Specifications .......................................................................................... 1-2
1.1 Three-phase 230V FRENIC5000G11S Series ................................................... 1-2
1.2 Three-phase 460V FRENIC5000G11S Series ................................................... 1-3
1.3 Three-phase 230V FRENIC5000P11S Series
(for variable torque load) .................................................................................... 1-4
1.4 Three-phase 460V FRENIC5000P11S Series
2. Common Specifications .......................................................................................... 1-6
2.1 Outline of common specifications ....................................................................... 1-6
2.2 Protective functions...........................................................................................1-10
2.3 Function settings ............................................................................................... 1-11
3. Wiring Diagram ..................................................................................................... 1-19
3.1 Wiring diagram before shipment from factory ................................................... 1-19
3.2 Basic wiring diagram ......................................................................................... 1-24
3.3 Wiring diagram using options............................................................................1-29
4. Terminal ................................................................................................................ 1-33
4.1 Terminal functions .............................................................................................1-33
4.2 Main circuit and control circuit terminals ........................................................... 1-37
4.2.1 Terminal block arrangement ...................................................................... 1-37
4.2.2 Main circuit terminal ................................................................................... 1-38
4.2.3 Control circuit terminal ...............................................................................1-41
Chapter 2 Operation
1. Frequency Control Operation.................................................................................2-2
1.1 Types of frequency control signal........................................................................ 2-2
1.2 Accuracy and resolution...................................................................................... 2-3
2. KEYPAD panel ........................................................................................................2-4
3. Function Explanation .............................................................................................. 2-6
3.1 Fundamental Functions ...................................................................................... 2-6
3.2 Extension Terminal Functions ........................................................................... 2-16
3.3 Control Functions of Frequency ........................................................................ 2-26
3.4 Motor Parameters ............................................................................................. 2-31
3.5 High Performance Functions ............................................................................ 2-33
3.6 Alternative Motor Parameters ........................................................................... 2-42
4. Standard RS-485 Interface ................................................................................... 2-44
4.1 Outline............................................................................................................... 2-45
4.1.1 Features..................................................................................................... 2-45
4.1.2 Function overview ...................................................................................... 2-45
4.2 Transmission specification ................................................................................ 2-45
4.3 Connection ........................................................................................................ 2-45
4.3.1 Connection method.................................................................................... 2-45
4.3.2 RS-485....................................................................................................... 2-46
4.3.3 Example of connection of FRENIC5000G11S/P11S series ...................... 2-46
4.3.4 Example of noise prevention...................................................................... 2-47
ii Contents
4.4 Transmission method ........................................................................................2-47
4.4.1 Transmission frame.................................................................................... 2-47
4.4.2 Field description......................................................................................... 2-53
4.4.3 Procedure on the host side ........................................................................ 2-54
4.4.4 Example of communication........................................................................ 2-56
4.4.5 Communication error ................................................................................. 2-57
4.5 Functions specific for communication ...............................................................2-61
4.5.1 Command data .......................................................................................... 2-61
4.5.2 Operation command data .......................................................................... 2-61
4.5.3 Function data .............................................................................................2-62
4.5.4 Monitoring data ..........................................................................................2-63
4.6 Function data format ......................................................................................... 2-64
4.6.1 List of function data format ........................................................................ 2-64
4.6.2 Data format specification ........................................................................... 2-67
4.7 Changeover of communications ....................................................................... 2-69
4.7.1 Changeover method for communication valid/invalid................................. 2-70
4.7.2 Link function (operation selection) .............................................................2-70
4.7.3 Coexistence of link (option) and RS-485 communication ..........................2-70
4.8 Response Time................................................................................................. 2-70
4.8.1 Response interval time .............................................................................. 2-70
4.8.2 Time of receiving preparation completion .................................................. 2-71
4.9 Function ............................................................................................................ 2-71
4.10 Troubleshooting ................................................................................................. 2-72
4.11 Appendix ........................................................................................................... 2-73
4.11.1 Communication level converter .................................................................2-73
4.11.2 ASCII code list .......................................................................................... 2-73
4.11.3 Example of a control program ................................................................... 2-74
5. Using Lifetime Forecast Functions........................................................................ 2-75
5.1 Contents of lifetime forecast functions ..............................................................2-75
5.2 How to check lifetime forecast information ........................................................ 2-75
5.3 Measuring conditions of lifetime........................................................................ 2-76
Chapter 3 Peripheral Equipment
1. Inverter Input Current .............................................................................................. 3-2
2. Circuit Breakers and Magnetic Contactors ............................................................. 3-3
3. Wire Size ................................................................................................................. 3-4
3.1 FRENIC5000G11S/P11S Series ........................................................................ 3-4
3.2 Allowable current of insulation wire..................................................................... 3-8
4. Braking Unit and Braking Resistor ........................................................................3-10
5. Braking Unit and Braking Resistor (10% ED) ....................................................... 3-12
6. Rated Sensitive Current of GFCI .......................................................................... 3-14
7. Input Circuit Noise Filter (EMC Compliance Filter) ............................................... 3-15
8. Output Circuit Noise Filter (OFL- -2/4) .......................................................... 3-16
9. Output Circuit Noise Filter (OFL- -4A) .......................................................... 3-18
10. DC REACTOR (DCR) ........................................................................................... 3-20
11. AC Reactor (ACR)................................................................................................. 3-21
12. Ferrite Ring for Reducing Radio Noise (ACL) ....................................................... 3-23
13. Power Regenerative PWM Converter (RHC) ........................................................3-23
Chapter 4 Optimal Type Selection
1. Inverter and Motor Selection ................................................................................... 4-2
1.1 Motor output torque characteristics .................................................................... 4-2
1.2 Selection procedure ............................................................................................ 4-4
1.3 Selection calculation expressions .......................................................................4-6
1.3.1 Load torque during constant speed running ................................................ 4-6
1.3.2 Acceleration and deceleration time calculation............................................ 4-7
1.3.3 Heat energy calculation of braking resistor.................................................. 4-9
1.3.4 Appendix (calculation for other than in SI Unit) ......................................... 4-10
2. Braking Unit and Braking Resistor Selection ........................................................ 4-11
2.1 Selection procedure .......................................................................................... 4-11
2.2 Notes on selection ............................................................................................ 4-11
2.3 Optional fan unit ................................................................................................ 4-11
Contents iii
Chapter 5 Option
1. Options.................................................................................................................... 5-2
1.1 Optional control cards ......................................................................................... 5-2
1.2 Other exclusive options....................................................................................... 5-2
1.3 Datailed specifications ........................................................................................ 5-3
2. Optional Peripheral Equipment .............................................................................5-14
2.1 Optional peripheral equipment .......................................................................... 5-14
2.2 Specifications and dimensions ......................................................................... 5-15
Chapter 6 Application Idea
1. Setting Items and Applications................................................................................ 6-2
2. FRENIC5000G11S/P11S Series ............................................................................ 6-4
2.1 Using with Aeration Tank Blowers .......................................................................6-4
2.2 Using with Multi-storied Automated Warehouses ............................................... 6-6
2.3 Using with Automated Parking Garages ............................................................. 6-8
2.4 Using with Vertical Circulation type Parking Facility .......................................... 6-10
2.5 Using with Bread Dough Mixers........................................................................ 6-12
2.6 Using with Commercial-use Washing Machines ............................................... 6-14
2.7 Using with Belt Conveyors ................................................................................ 6-16
2.8 Using with Grinding Machines .......................................................................... 6-18
2.9 Using with Fans for Air Conditioning Unit (1) .................................................... 6-20
2.10 Using with Fans for Air Conditioning Unit (2) .................................................... 6-22
2.11 Using with Cold/Warm Water Pumps ................................................................ 6-24
2.12 Using with Line/Inverter Changeover Operation ............................................... 6-26
iv Contents
Chapter 7 Glossary
1. Standard Specifications .......................................................................................... 7-2
2. Common Specificationds ........................................................................................ 7-4
Chapter 8 Appendix
Appendix 1. Advantageous Use of Inverters (with regard to Electrical Noise) .............. 8-2
1.1 Effect of inverters on other devices..................................................................... 8-2
1.1.1 Effect on AM radios ..................................................................................... 8-2
1.1.2 Effect on telephones ....................................................................................8-2
1.1.3 Effect on proximity limit switches ................................................................. 8-2
1.1.4 Effect on pressure sensors ..........................................................................8-2
1.1.5 Effect on position detectors
(pulse generators; PGs, or pulse encoders) ................................................ 8-2
1.2 Noise ................................................................................................................... 8-2
1.2.1 Inverter noise ...............................................................................................8-2
1.2.2 Types of noise .............................................................................................. 8-3
1.3 Noise prevention measures ................................................................................ 8-5
1.3.1 Noise prevention treatments prior to installation.......................................... 8-5
1.3.2 Implementation of noise prevention measures ............................................8-5
1.3.3 Specific examples ........................................................................................ 8-8
Appendix 2. Effect on Insulation of General-purpose
Motor Driven with 460V Class Inverter.................................................. 8-11
2.1 Operating principle of inverter ........................................................................... 8-11
2.1.1 Main circuit configuration of inverter ..........................................................8-11
2.1.2 Control method of inverter ......................................................................... 8-11
2.2 Generating mechanism of surge voltages ........................................................ 8-11
2.3 Effect of surge voltages .................................................................................... 8-12
2.4 Countermeasures against surge voltages ........................................................ 8-12
2.4.1 Method to use motors with enhanced insulation........................................ 8-12
2.4.2 Method to suppress surge voltages ........................................................... 8-12
2.5 Regarding existing equipment .......................................................................... 8-13
2.5.1 In case of motor being driven with 400V class inverter ............................. 8-13
2.5.2 In case of existing motor driven newly with 400V class inverter ................ 8-13
Appendix 3. Example Calculation of Energy Savings .................................................. 8-14
2.1 Calculating condition ......................................................................................... 8-14
2.2 Calculation of shaft driving power .....................................................................8-14
2.3 Calculation of energy savings ........................................................................... 8-14
Appendix 4. Inverter Generating Loss .......................................................................... 8-15
Chapter 1
Specifications
Contents
1. Standard Specifications ....................................................................................... 1-2
1.1 Three-phase 230V FRENIC5000G11S Series ................................................... 1-2
1.2 Three-phase 460V FRENIC5000G11S Series ................................................... 1-3
1.3 Three-phase 230V FRENIC5000P11S Series (for variable torque load) ............ 1-4
1.4 Three-phase 460V FRENIC5000P11S Series (for variable torque load) ............ 1-5
2. Common Specifications ....................................................................................... 1-6
2.1 Outline of common specifications .......................................................................1-6
2.2 Protective functions........................................................................................... 1-10
2.3 Function settings ............................................................................................... 1-11
3. Wiring Diagram ................................................................................................... 1-19
3.1 Wiring diagram before shipment from factory ................................................... 1-19
3.2 Basic wiring diagram......................................................................................... 1-24
3.3 Wiring diagram using options ........................................................................... 1-29
1
4. Terminal ...............................................................................................................1-33
4.1 Terminal functions ............................................................................................. 1-33
4.2 Main circuit and control circuit terminals ........................................................... 1-37
4.2.1 Terminal block arrangement ...................................................................... 1-37
4.2.2 Main circuit terminal ................................................................................... 1-38
4.2.3 Control circuit terminal ...............................................................................1-41
1-1
Chapter 1

1. Standard Specifications

1. Standard Specifications

1.1 Three-phase 230V FRENIC5000G11S Series

Item Specifications Type FRN■■■■■■G11S-2UX F25 F50 001 002 003 005 007 010 015 020 025 030 040 050 060 075 100 125 Nominal applied motor HP 1/4 1/2 12357.5101520253040506075100125
Rated capacity *1) kVA 0.6 1.2 2.0 3.2 4.4 6.8 9.9 13 18 23 29 36 46 58 72 86 113 138
Rated voltage *2) V 3-phase 200V/50Hz 200, 220, 230V/60Hz Output Rated current *3) A 1.5 3.0 5.0 8.0 11 17 25 33 46 59 74 87 115 145 180 215 283 346 ratings Overload capability 150% of rated current for 1min. 150% of rated current for 1min.
Rated frequency Hz 50, 60Hz
Phases, Voltage, Frequency 3-phase 200 to 230V 50/60Hz
Voltage / frequency variations Vo ltage : +10 to –15% (Voltage unbalance *4) : 2% or less) Frequency :+5 to –5%
Input *5) When the input voltage drops below 165V from rated voltage, the inverter can be operated for 15ms . ratings The smooth recovery method is selectable.
Output Accuracy (Stability) •Analog setting : ± 0.2% of Maximum frequency (at 25±10°C (77±50°F)) frequency •Digital setting : ±0.01% of Maximum frequency (at –10 to +50°C (14 to 122°F))
Control 0.1 to 0.9 : Manual (for variable torque load) *9)
Braking Duty cycle
Enclosure (IEC 60529) IP 40 IP 00 ( IP 20 : Option ) Cooling method Natural cooling Fan cooling
Standards -IEC 61800-2 (Ratings, specifications for low voltage adjustable frequency a.c. power drive systems)
Weight lbs 4.9 4.9 5.5 8.4 8.4 8.4 13 13 22 22 23 23 64 79 97 101 154 254
NOTES:
Momentary voltage dip capability When the input voltage is 165V or more, the inverter can be operated continuously.
Rated current *6) (with DCR) 0.94 1.6 3.1 5.7 8.3 14.0 19.7 26.9 39.0 54.0 66.2 78.8 109 135 163 199 272 327
A(without DCR) 1.8 3.4 6.4 11.1 16.1 25.5 40.8 52.6 76.9 98.5 117 136 168 204 243 291 - -
Required power supply
capacity *7)
Maximum frequency 50 to 400Hz
Setting Base frequency 25 to 400Hz
Starting frequency 0.1 to 60Hz, Holding time: 0.0 to 10.0s Carrier frequency *8) 0.75 to15kHz
Setting resolution •Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz, 0.15Hz at 400Hz
Voltage / freq. (V/f) characteristic Adjustable at base and maximum frequency, with AVR control : 80 to 240V
To rque boost To rque boost can be set, using Function code F09 and A05.
Starting torque 200% (with Dynamic torque-vector control selected)
Braking torque *10) 150% 100% 20% 10 to 15%
Standard
Time s 10 5 5 No limit Duty cycle Standard
Braking torque 150% 100% Time s 90 45 45 45 30 20 10 8 10
Using
options
10%ED Braking torque 150% *12)
Time s 90 45 30 20 10
DC injection braking Starting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
*1) Inverter output capacity (kVA) at 230V. Rated capacity reduces when power supply voltage decreases. *2) Output voltage cannot exceed the power supply voltage. *3) Current derating may be required in case of low impedance loads such as high frequency motor. *4) Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) =
*5) Tested at standard load condition (85% load). *6) This value is under FUJI original calculation method. *7) When power-factor correcting DC REACTOR (DCR) is used. *8) When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter. *9) When torque boost is set at 0.1, starting torque of 50% or more can be obtained. *10) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.) *11) Order individually. *12) Applicable to 10%ED when using options (standard)
Duty cycle
1-2
200% of rated current for 0.5s 180% of rated current for 0.5s
3-phase 200 to 220V/50Hz (220 to 230V/50Hz) *11)
200 to 230V/60Hz
kVA 0.4 0.6 1.1 2.0 2.9 4.9 6.9 9.4 14 19 23 28 38 47 57 69 95 114
•Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
• LINK setting : Selects from the following two items.
0.0 : Automatic (for constant torque load)
1.0 to 1.9 : Manual (for propotional speed torque load)
2.0 to 20.0: Manual (for constant torque load)
%ED
10 5 353232 No limit
%ED
37 22 18 10 7 5 5 5 10
%ED
*Inverter restarts at the star ting frequency when operation command is input while braking is operating. *DC injection braking does not operate at the time of change-over from forward to reverse operation. *
DC injection braking does not operate when frequency setting is decreased while operation command (FWD, REV) is being input.
-UL/cUL -Low Voltage Directive -EMC Directive -TÜV (up to 30HP)
-IEC 61800-3 (EMC product standard including specific test methods)
(kg) (2.2) (2.2) (2.5) (3.8) (3.8) (3.8) (6.1) (6.1) (10) (10) (10.5) (10.5) (29) (36) (44) (46) (70) (115)
Max. voltage [V] – Min. Voltage [V]
Three-phase average voltage[V]
• 1/20000 of Maximum frequency ex.) 0.003Hz at 60Hz, 0.006Hz at 120Hz, 0.02Hz at 400Hz
• 0.01Hz (Fixed)
180% (with Dynamic torque-vector control selected)
10 10 10
x 67 (Conforming to EN61800-3 (5.2.3))
0.75 to 10kHz
Chapter 1
1. Standard Specifications

1.2 Three-phase 460V FRENIC5000G11S Series

Item Specifications Type FRN■■■■■■G11S-4UX F50 001 002 003 005 007 010 015 020 025 030 040 050 060 075 100 125 150 200 250 300 350 400 450 500 600 Nominal applied motor HP 1/2 12357.5101520253040506075100125150200250300350400450500600
Rated capacity *1) kVA 1.1 1.9 2.8 4.1 6.8 9.9 13 18 22 29 34 45 57 69 85 114 134 160 192 231 287 316 396 445 495 563
Rated voltage *2) V 3-phase 380, 400, 415V/50Hz 380, 400, 440, 460V/60Hz Output Rated current *3) A 1.5 2.5 3.7 5.5 9 13 18 24 30 39 45 60 75 91 112 150 176 210 253 304 377 415 520 585 650740 ratings Overload capability 150% of rated current for 1min. 150% of rated current for 1min.
Rated frequency Hz 50, 60Hz
Phases, Voltage, Frequency 3-phase 380 to 480V 50/60Hz 3-phase 380 to 440V/50Hz 380 to 480V/60Hz *4)
Voltage / frequency variations Vo ltage : +10 to –15% (Voltage unbalance *5) : 2% or less) Frequency :+5 to –5%
Input *6) When the input voltage drops below 310V from rated voltage, the inverter can be operated for 15ms . ratings The smooth recovery method is selectable.
Output Accuracy (Stability) •Analog setting : ±0.2% of Maximum frequency (at 25±10°C (77±50°F)) frequency •Digital setting : ±0.01% of Maximum frequency (at –10 to +50°C (14 to 122°F))
Control 0.1 to 0.9 : Manual (for variable torque load) *10)
Braking Duty cycle
Enclosure (IEC 60529) IP 40 IP 00 ( IP 20 : Option ) Cooling method
Standards -IEC 61800-2 (Ratings, specifications for low voltage adjustable frequency a.c. power drive systems)
Weight lbs 4.9 5.5 8.4 8.4 8.4 14 14 22 22 23 64 75 86
NOTES: *1) Inverter output capacity (kVA) at 460V. Rated capacity reduces when power supply voltage decreases.
Momentary voltage dip capability When the input voltage is 310V or more, the inverter can be operated continuously.
Rated current *7) (with DCR)
A(without DCR) 1.8 3.5 6.2 9.2
Required power supply
capacity *8)
Maximum frequency 50 to 400Hz
Setting Base frequency 25 to 400Hz
Starting frequency 0.1 to 60Hz, Holding time: 0.0 to 10.0s
Carrier frequency *9) 0.75 to 15kHz 0.75 to 10kHz
Setting resolution •Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz, 0.15Hz at 400Hz
Voltage / freq. (V/f) characteristic Adjustable at base and maximum frequency, with AVR control : 320 to 480V
To rque boost To rque boost can be set, using Function code F09 and A05.
Starting torque 200% (with Dynamic torque-vector control selected) 180% (with Dynamic torque-vector control selected)
Braking torque *11) 150% 100% 20% 10 to 15%
Standard
Time s 55 No limit Duty cycle Standard
Braking torque 150% 100% Time s 45 30 20 10 8 10
Using
options
10%ED Braking torque 150% *13)
Time s 45 30 20 10 Duty cycle
DC injection braking Starting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
*2) Output voltage cannot exceed the power supply voltage. *3) Current derating may be required in case of low impedance loads such as high frequency motor. *4) When the input voltage is 380 to 398V/50Hz or 380 to 430V/60Hz, the tap of the auxiliary transformer must be changed. *5) Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) =
*6) Tested at standard load condition (85% load). *7) This value is under FUJI original calculation method. *8) When power-factor correcting DC REACTOR (DCR) is used. *9) When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter. *10) When torque boost is set at 0.1, starting torque of 50% or more can be obtained. *11) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.) *12) Consult with Fuji Electric. *13) Applicable to 10%ED when using options (standard)
200% of rated current for 0.5s 180% of rated current for 0.5s
0.82
1.5 2.9 4.2 7.1
kVA 0.6 1.1 2.1 3.0 5.0 7.0 9.4 14 19 24 28 38 47 57 70 93 111 136 161 196 244 267 341 383 433 488
•Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
• LINK setting : Selects from the following two items.
0.0 : Automatic (for constant torque load)
1.0 to 1.9 : Manual (for propotional speed torque load)
2.0 to 20.0: Manual (for constant torque load)
%ED
5353232 No limit
%ED
22 18 10 7 5 5 5 10
%ED
(kg)
Max. voltage [V] – Min. Voltage [V]
Three-phase average voltage[V]
10 10 10 10
*Inverter restarts at the starting frequency when operation command is input while braking is operating. * DC injection braking does not operate at the time of change-over from forward to reverse operation. *
DC injection braking does not operate when frequency setting is decreased while operation command (FWD, REV) is being input.
Natural cooling
-UL/cUL -Low Voltage Directive -EMC Directive -TÜV (up to 30HP)
-IEC 61800-3 (EMC product standard including specific test methods)
(2.2) (2.5) (3.8) (3.8) (3.8) (6.5) (6.5) (10) (10)
10.0 13.5 19.8 26.8 33.2 39.3
14.9 21.5 27.9 39.1 50.3 59.9 69.3
• 1/20000 of Maximum frequency ex.) 0.003Hz at 60Hz, 0.006Hz at 120Hz, 0.02Hz at 400Hz
• 0.01Hz (Fixed)
(10.5) (10.5)
x 67 (Conforming to EN61800-3 (5.2.3))
54 67 81 100 134 160 196 232 282 352 385 491 552 624 704 86 104 124150 -----------
Fan cooling
23
(29) (34)
88 106 154 154 221 221 309 309 551 551 794 794
(70)(70)(48)(40)(39)
(100) (100)
(140)
(140)
(250) (250) (360)
(360)
1
1-3
Chapter 1
1. Standard Specifications

1.3 Three-phase 230V FRENIC5000P11S Series (for variable torque load)

Item Specifications Type FRN■■■■■■P11S-2UX 007 010 015 020 025 030 040 050 060 075 100 125 150 Nominal applied motor HP 7.5 10 15 20 25 30 40 50 60 75 100 125 150
Rated capacity *1) kVA 8.8 12 17 22 27 31 46 58 72 86 113 138 165
Rated voltage *2) V 3-phase 200V/50Hz 200, 220, 230V/60Hz Output Rated current *3) A 22 29 42 55 67 78 115 145 180 215 283 346 415 ratings Overload capability 110% of rated current for 1min
Rated frequency Hz 50, 60Hz
Phases, Voltage, Frequency 3-phase 200 to 230V 50/60Hz
Voltage / frequency variations Vo ltage : +10 to –15% (Voltage unbalance *4) : 2% or less) Frequency :+5 to –5%
Input *5) When the input voltage drops below 165V from rated voltage, the inverter can be operated for 15ms . ratings The smooth recovery method is selectable.
Output Accuracy (Stability) •Analog setting : ± 0.2% of Maximum frequency (at 25±10°C (77±50°F)) frequency •Digital setting : ±0.01% of Maximum frequency (at –10 to +50°C (14 to 122°F))
Control 0.1 to 0.9 : Manual (for variable torque load) *9)
Braking Duty cycle
Enclosure (IEC 60529) IP 40 IP 00 ( IP 20 : Option ) Cooling method Fan cooling
Standards -IEC 61800-2 (Ratings, specifications for low voltage adjustable frequency a.c. power drive systems)
Weight lbs 13 13 13 22 22 23 64 64 79 97 101 154 254
NOTES: *1) Inverter output capacity (kVA) at 230V. Rated capacity reduces when power supply voltage decreases.
Momentary voltage dip capability When the input voltage is 165V or more, the inverter can be operated continuously.
Rated current *6) (with DCR) 19.7 26.9 39.0 54.0 66.2 78.8 109 135 163 199 272 327 400
A(without DCR) 40.8 52.6 76.9 98.5 117 136 168 204 243 291 - - -
Required power supply
capacity *7)
Maximum frequency 50 to 120Hz
Setting Base frequency 25 to 120Hz
Starting frequency 0.1 to 60Hz, Holding time: 0.0 to 10.0s Carrier frequency *8) 0.75 to 15kHz 0.75 to 10kHz 0.75 to 6kHz
Setting resolution •Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz
Voltage / freq. (V/f) characteristic Adjustable at base and maximum frequency, with AVR control : 80 to 240V
To rque boost To rque boost can be set, using Function code F09 and A05.
Starting torque 50%
Braking torque *10) 20% 10 to 15%
Standard
Time s No limit Duty cycle Standard
Braking torque 100% 75% Time s 15 7 8 10
Using
options
10%ED Braking torque 100% *12)
Time s 15 7 Duty cycle
DC injection braking Starting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
*2) Output voltage cannot exceed the power supply voltage. *3) Current derating may be required in case of low impedance loads such as high frequency motor. *4) Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) =
*5) Tested at standard load condition (85% load). *6) This value is under FUJI original calculation method. *7) When power-factor correcting DC REACTOR (DCR) is used. *8) When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter. *9) When torque boost is set at 0.1, starting torque of 50% or more can be obtained. *10) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.) *11) Order individually. *12) Applicable to 10%ED when using options (standard)
kVA 6.9 9.4 14 19 23 28 38 47 57 69 95 114 139
•Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
• LINK setting : Selects from the following two items.
0.0 : Automatic (for constant torque load)
1.0 to 1.9 : Manual (for propotional speed torque load)
2.0 to 20.0 : Manual (for constant torque load)
%ED
%ED
%ED
(kg) (5.7) (5.7) (5.7) (10) (10) (10.5) (29) (29) (36) (44) (46) (70) (115)
Max. voltage [V] – Min. Voltage [V]
Three-phase average voltage[V]
3.5 3.5 4 10
10 10 10 7
* Inverter restarts at the starting frequency when operation command is input while braking is operating. * DC injection braking does not operate at the time of change-over from forward to reverse operation. *
DC injection braking does not operate when frequency setting is decreased while operation command (FWD, REV) is being input.
-UL/cUL -Low Voltage Directive -EMC Directive -TÜV (up to 30HP)
-IEC 61800-3 (EMC product standard including specific test methods)
• 1/20000 of Maximum frequency ex.) 0.003Hz at 60Hz, 0.006Hz at 120Hz
• 0.01Hz (Fixed)
x 67 (Conforming to EN61800-3 (5.2.3))
3-phase 200 to 220V/50Hz (220 to 230V/50Hz) *11) 200 to 230V/60Hz
No limit
1-4
Chapter 1
1. Standard Specifications

1.4 Three-phase 460V FRENIC5000P11S Series (for variable torque load)

Item Specifications Type FRN■■■■■■P11S-4UX 007 010 015 020 025 030 040 050 060 075 100 125 150 200 250 300 350 400 450 500 600 700 800 Nominal applied motor HP 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 700 800
Rated capacity *1) kVA 10 13 18 24 29 35 48 60 72 89 119 140 167 201 242 300 330 386 414 517 589 668 764
Output raitings
Input *6) When the input voltage drops below 310V from rated voltage, the inverter can be operated for 15ms . ratings The smooth recovery method is selectable.
Output Accuracy (Stability) ·Analog setting : ±0.2% of Maximum frequency (at 25±10°C (77±50°F)) frequency ·Digital setting : ±0.01% of Maximum frequency (at –10 to +50°C (14 to 122°F))
Control 0.1 to 0.9 : Manual (for variable torque load) *10)
Braking Duty cycle
Enclosure (IEC 60529) IP 40 IP 00 ( IP 20 : Option ) Cooling method Fan cooling
Standards -IEC 61800-2 (Ratings, specifications for low voltage adjustable frequency a.c. power drive systems)
Weight lbs 13 13 13 22 22 23 64 64 75 86 88 106 154 154 221 221 309 309 309 551 551 794 794
NOTES:
Rated voltage *2) V 3-phase 380, 400, 415V/50Hz 380, 400, 440, 460V/60Hz Rated current *3) A Overload capability 110% of rated current for 1min Rated frequency Hz 50, 60Hz Phases, Voltage, Frequency Voltage / frequency variations Voltage : +10 to –15% (Voltage unbalance *5) : 2% or less) Frequency :+5 to –5% Momentary voltage dip capability When the input voltage is 310V or more, the inverter can be operated continuously.
Rated current *7) (with DCR)
A(without DCR)
Required power supply capacity *8)
Maximum frequency 50 to 120Hz
Setting Base frequency 25 to 120Hz
Starting frequency 0.1 to 60Hz, Holding time: 0.0 to 10.0s
Carrier frequency *9) 0.75 to 15kHz 0.75 to 10kHz 0.75 to 6kHz
Setting resolution ·Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz
Voltage / freq. (V/f) characteristic Adjustable at base and maximum frequency, with AVR control : 320 to 480V To rque boost Torque boost can be set, using Function code F09 and A05.
Starting torque 50%
Braking torque *11) 20% 10 to 15%
Standard
Time s No limit Duty cycle Standard
Braking torque 100% 75% Time s 15 7 8 10
Using options
10%ED Braking torque 100% *13)
Time s 15 7 Duty cycle
DC injection braking Starting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
*1) Inverter output capacity (kVA) at 460V. Rated capacity reduces when power supply voltage decreases. *2) Output voltage cannot exceed the power supply voltage. *3) Current derating may be required in case of low impedance loads such as high frequency motor. *4) When the input voltage is 380 to 398V/50Hz or 380 to 430V/60Hz, the tap of the auxiliary transformer must be changed. *5) Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) =
*6) Tested at standard load condition (85% load). *7) This value is under FUJI original calculation method. *8) When power-factor correcting DC REACTOR (DCR) is used. *9) When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter. *10) When torque boost is set at 0.1, starting torque of 50% or more can be obtained. *11) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.) *12) Consult with Fuji Electric. *13) Applicable to 10%ED when using options (standard)
Max. voltage [V] – Min. Voltage [V]
Three-phase average voltage[V]
12.5 16.5
3-phase 380 to 480V 50/60Hz
10.0 13.5 19.8 26.8 33.2 39.3
21.5 27.9 39.1 50.3 59.9 69.3
kVA 7.0 9.4 14 19 24 28 38 47 57 70 93 111 136 161 196 244 267 341 383 433 488 549 610
·Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
· LINK setting : Selects from the following two items.
%ED
%ED
%ED
* Inverter restarts at the starting frequency when operation command is input while braking is operating. * DC injection braking does not operate at the time of change-over from forward to reverse operation. *
-UL/cUL -Low Voltage Directive -EMC Directive -TÜV (up to 30HP)
-IEC 61800-3 (EMC product standard including specific test methods)
(kg)
(6.1) (6.1) (6.1)
23 30 37 44 60 75 91 112 150 176 210 253 304 377 415 520 585 650 740 840 960
3-phase 380 to 440V/50Hz 380 to 480V/60Hz *4)
54 67 81 100 134 160 196 232 282 352 385 491 552 624 704 792 880 86 104 124 150 - ------------
• 1/20000 of Maximum frequency ex.) 0.003Hz at 60Hz, 0.006Hz at 120Hz
• 0.01Hz (Fixed)
0.0 : Automatic (for constant torque load)
1.0 to 1.9 : Manual (for propotional speed torque load)
2.0 to 20.0 : Manual (for constant torque load)
No limit
3.5 3.5 4 10
10 10 7
DC injection braking does not operate when frequency setting is decreased while operation command (FWD, REV) is being input.
(10) (10)
(10.5)
(29) (29) (34) (39) (40) (70) (70)
x 67 (Conforming to EN61800-3 (5.2.3))
(48)
(100) (100) (140) (140) (140) (250) (250) (360) (360)
1
1-5
Chapter 1
FWD

2. Common Specifications

2. Common Specifications

2.1 Outline of common specifications

Item Explanation Remarks Func. code
Control Control method
Operation method F02
Frequency setting F01 (Frequency command)
Jogging operation C20
Running status signal E20 to E23
Acceleration/ F07, F08 Deceleration time E10 to E15
Active drive H19
Frequency limiter F15, F16
NOTE : ( ) or < > in the “Remarks” column indicates the abbreviation of terminal function assigned to digital input terminals X1 to X9 and
1-6
transistor output terminals Y1 to Y5C.
•V/f control (Sinusoidal PWM control)
• Dynamic torque-vector control (Sinusoidal PWM control)
•Vector control with PG ...G11S only
• KEYPAD operation : Forward or reverse operation by Stopping by
• Digital input signal operation : FWD·STOP command, REV·STOP command, Coast-to-stop command, etc.
• LINK operation :
• RS-485 (standard)
• Various Bus interface is available. (Option)
• T-Link (FUJI private link) • Devicenet • CAN open
• Profibus-DP • Modbus Plus
• Interbus-S •JPCN1
• KEYPAD operation :
• External potentiometer : Variable resistor (1 to 5k 1/2W)
• Analog input : External voltage or current input
(Reversible
operation)
(Inverse operation)
• UP/DOWN control : Output frequency increases when UP signal is ON, and decreases when DOWN signal is ON.
• Multistep frequency selection :
Up to 16 different frequencies can be selected by digital input signal.
• Pulse train input : 0 to 100kp/s
• Digital signal (parallel) :
• LINK operation : RS-485 (standard) (RS-485FGABus)
Programmed PATTERN operation : Max. 7 stages
This operation can be performed by KEYPAD opration (
key) or digital input signal (FWD or REV).
REV
Transistor output : RUN, FAR, FDT, OL, LU, TL, etc.
(4 points) (4 output types are selectable)
Relay output : • Same as transistor output.
(2 points) • Alarm output (for any fault)
Analog output : Output frequency, Output current,
(1 point) Output voltage, Output torque, etc.
Pulse output : Output frequency, Output current,
(1 point) Output voltage, Output torque, etc.
0.01 to 3600s
Four kinds of acceleration and deceleration times can be set independently, and the desired time is selected by combining digital input signal (2 points).
Selects acceleration/deceleration pattern from the following 4 types.
• Linear
• S-curve (weak)
• S-curve (strong)
• Non-linear (for variable torque load)
When the acceleration time reaches 60s, the motor output torque is automatically reduced to rated torque. Then the motor operation mode is changed to torque limiting operation.
High and Low frequency limiters can be preset.
key
STOP
∨
0 to +10Vdc (0 to +5Vdc) 4 to 20mAdc
: Reversible operation by polarized signal can be
selected.
0 to ± 10Vdc (0 to ± 5Vdc)
: Inverse mode operation can be selected by
digital input signal (IVS).
0 to +10Vdc 10 to 0Vdc (terminal 12) 4 to 20mAdc 20 to 4mAdc (terminal C1)
12-bit parallel (12-bit binary) signal can be input.
(Option) • T-Link (FUJI private link)
• Profibus-DP
• Interbus-S
• Modbus Plus
• Devicenet
or
FWD
or ∨ key
REV
key
,
Option card (PG/Hz) required. Switching between KEYPAD operation and
digital input signal operation is enabled by pressing STOP key and RESET key at the same time.
(LE)
• Connect to terminals 13, 12, and 11.
• Set Function code at ”F01: 1".
• Potentiometer is required separately. 0 to +5Vdc, 0 to ± 5Vdc input is enabled
when Func. code 17 (Gain for frequency setting) is set at 200.0%.
(UP, DOWN)
(SS1, SS2, SS4, SS8)
Option card (PG/SY) required. Option card (DIO) required. (LE)
Option card for open networks
<STG1, STG2, STG4, TU, TO>
• To enter jogging operation mode:
•Press same time.
•Digital input signal : (JOG)
* During jogging operation, an indicator at
“JOG” is lit on the LCD monitor.
Coast-to-stop is selectable by Function code “H11”. (RT1, RT2)
The acceleration time is automatically extended up to 3 times.
STOP
key and
∨
key at the
F42, A09
H30 to H39
C05 to C19
H31 to H39
F01 C21 to C28
F02
F36 E24, E25
F31
F35
H07
Chapter 1
∨
2. Common Specifications
Item Explanation Remarks Func. code
Control Bias frequency F18
Gain for frequency F17 setting
Jump frequency control C01 to C04
Rotating motor pick up H09 (Flying start)
Auto-restart after F14 momentary power failure
Line/Inverter changeover operation
Slip compensation P09
Droop operation H28
Torque limiting F40, F41
Torque control H18
PID control H20 to H25
Automatic deceleration F41, E17
Second motor's setting A01 to A18
Energy saving operation H10
Fan stop operation H06
Universal DI Universal DO
Bias frequency can be preset.
Gain for frequency setting can be preset. (0.0 to 200.0%)
ex.) Analog input 0 to +5Vdc with 200% gain results in
Maximum frequency at 5Vdc.
Jump frequency (3 points) and its common jump hysteresis width (0 to 30Hz) can be preset.
A rotating motor(including inverse rotating mode) can be smoothly picked up without stopping the motor. (speed search method)
Automatic restart is available without stopping motor after a momentary power failure. (speed search method) When "Smooth recovery" mode is selected, the motor speed drop is held minimum.
Controls switching operation between line power and inverter. The inverter has sequence function inside.
• The inverter output frequency is controlled according to the load torque to keep motor speed constant.
When the value is set at "0.00" and "Torque-vector" is set at "active", the
compensation value automatically selects the Fuji standard motor.
Slip compensation can be preset for the second motor. The motor speed droops in proportional to output torque.(-9.9 to
0.0Hz) ...G11S only
When the motor torque reaches a preset limiting level, this function automatically adjusts the output frequency to prevent the inverter from tripping due to an overcurrent.
To rque limiting 1 and Torque limiting 2 can be individually set, and are selectable with a digital input signal.
Output torque (or load factor ) can be controlled with an analog input signal (terminal 12).
This function can control flowrate, pressure, etc. (with an analog feedback signal.)
••
Reference signal
••
• KEYPAD operation (
Setting freq. / Maximum freq. X 100 [%]
•Voltage input (terminal 12 and V2) : 0 to 10Vdc / 0 to 100%
•Current input (terminal C1) : 4 to 20mAdc / 0 to 100%
• Reversible operation with polarity (terminal 12) :
0 to ± 10Vdc / 0 to ±100%
•Reversible operation with polarity (terminal 12 + V1) :
0 to ± 10Vdc / 0 to ± 100%
•Inverse mode operation (terminal 12 and V2) : 10 to 0Vdc / 0 to 100%
• Inverse mode operation (terminal C1) : 20 to 4mAdc / 0 to 100%
• PATTERN operation : Setting freq. / Maximum freq. X 100 [%]
•DI option input : • BCD...Setting freq. / Maximum freq. X 100 [%]
• Multistep frequency setting :
• RS-485 : Setting freq. / Maximum freq. X 100 [%]
••
Feedback signal
••
Terminal 12 (0 to 10Vdc / 0 to 100%, or 10 to 0Vdc / 0 to 100% )
Terminal C1 (4 to 20mAdc / 0 to 100%, or 20 to 4mAdc / 0 to 100%)
Torque limiter 1 (Braking) is set at "F41: 0".
• In deceleration :
The deceleration time is automatically extended up to 3 times for tripless operation even if a braking resistor is not used.
• In constant speed operation :
Based on regenerative energy, the frequency is increased, and tripless operation is active.
This function is used for two motors switching operation.
The second motor's V/f characteristics (base and maximum frequency),
rated current, torque boost, electronic thermal relay, etc. can be preset.
• The second motor's circuit parameter can be preset, and torque­vector control can be applied to both motors.
This function minimizes inverter and motor losses at light load.
• This function detects temperature inside inverter to stop cooling fans for silent operation and extending the fans' lifetime.
•On/off status of cooling fans is output.
Transmits to main controller of LINK operation Outputs command signal from main controller of LINK operation.
∨
or
• Binary...Full scale / 100%
(Setting of Torque limiter 2 (Braking) is same.)
key) :
Setting freq. / Maximum freq. X 100
NOTE : ( ) or < > in the “Remarks” column indicates the abbreviation of terminal function assigned to digital input terminals X1 to X9 and
transistor (relay) output terminals Y1 to Y4 (Y5A, Y5C).
When the sum of setting frequency and bias frequency is minus value, the output frequency rise can be delayed. (No reverse running is performed.)
(STM)
The inverter searches the motor speed, and smoothly returns to setting frequency.
Even if the motor circuit is temporarily opened, the inverter operates without a hitch.
(SW50, SW60) <SW88, SW52-1, SW52-2>
Slip compensation value can be manually set from 0.01 to 5.00Hz instead of 0.0 for FUJI standard motor.
P11S series doesn't have this function.
(TL2/TL1)
• Torque polarity selectable. (Hz/TRQ)
• P11S series doesn't have this function.
PID control is selected by "H20". (Hz/PID).
Reference signal selection is made by "F01". In "F01", "8: UP/DOWN control 1", "9: UP/ DOWN control 2", and "11: Pulse train input" cannot be used for the reference signal of PID control.
• Terminal V1 is optional.
• Terminal V2: EN only
[%
]
Feedback signal selection is made by "H21".
When the deceleration time is extended to longer than three times the setting time, the inverter trips.
(M2/M1) <SWM2>
<FAN> (U-DI) <U-DO>
H13 to H16
E01 to E09 E20 to E24, H13
A18
E16, E17
F01
C05 to C19
H21
1
1-7
Chapter 1
2. Common Specifications
Item Explanation Remarks Func. code
Control Zero speed control
Positioning control
Synchronized operation
Protection Overload
Overvoltage Surge protection
Undervoltage
Input phase loss Overheating Short-circuit Ground fault
Motor overload F10 to F12
(Overload early warning) E33 to E35
DB resistor overheating F13
Output phase loss detection
Motor protection by H26, H27 PTC thermistor
Auto reset H04, H05
Condition Installation location
(Installation and operation)
Storage condition
Ambient temperature
Ambient humidity Altitude
Vibration
The stopped motor holds its rotor angle. For a rotating motor, the rotor angle is held after deceleration.
The SY option card can be used for positioning control by differential counter method.
This function controls the synchronized operation between 2 axes with PGs. Protects the inverter by electronic thermal and detection of inverter temperature.
Detects DC link circuit overvoltage, and stops the inverter. Protects the inverter against surge voltage between the main
circuit power line and ground. Detects DC link circuit undervoltage, and stops the inverter.
Phase loss protection for power line input Protects the inverter by detection of inverter heat sink temperature. Short-circuit protection for inverter output circuit
• Ground fault protection for inverter output circuit (3-phase current
• Zero-phase current detection method
• The inverter trips, and then protects the motor.
• Electronic thermal overload relay can be selected for standard
• The second motor's electronic thermal overload relay can be
• Before the inverter trips, outputs OL(Overload early warning)
• Prevents DB resistor overheating by internal electronic thermal
•Prevents DB resistor overheating by external thermal overload
When the inverter executes auto-tuning, detects each phase impedance imbalance (and stops the inverter).
When the motor temperature exceeds allowable value, the inverter trips automatically.
When the inverter is tripped, it resets automatically and restarts.
• Indoor use only.
• Free from corrosive gases, flammable gases, oil mist, dusts, and
-10 to +50˚C (14 to +122˚F) (For inverters of 30HP or smaller, remove the ventilation covers when operated at temperature of 40˚C (104˚F)or above.)
5 to 95%RH (non-condensing) 33ft (1000m) or less. Applicable to 9800ft (3000m) with power
derating (-10% / 33ft (1000m))
3mm (vibration amplitude) at 2 to less than 9Hz
9.8m/s 2m/s2 at 20 to less than 55Hz (2m/s2 at 9 to less than 55Hz : G11S 125HP, P11S 150HP or more) 1m/s
• Temperature : -25 to +65°C (-13 to +149°F)
• Humidity : 5 to 95%RH (No-condensing)
detection method)
motor or inverter motor
preset for 2-motor changeover operation.
signal at a preset level.
overload relay. (10HP or smaller for G11S, 15HP or smaller for P11S)
relay attached to DB resistor. (15HP or larger for G11S, 20HP or larger for P11S)
direct sunlight.
2
at 9 to less than 20Hz
2
at 55 to less than 200Hz
A motor with PG and option card (OPC­G11S-PG) are necessary. (ZERO) P11S series doesn't have this function.
Option card (PG/SY) required
Option card is required.
230V : 400Vdc, 460V : 800Vdc
• Line voltage : 5kV
Between power line and ground : 7kV (1.2/50µs)
230V : 200Vdc, 460V : 400Vdc
Operation details are selected by Function code F14.
• 30HP or smaller inverter
• 40HP or larger inverter
• Thermal time constant (0.5 to 75.0 minutes) can be preset for a special motor.
• External singnal is used for changeover.
Related transistor output : OL <OL1, OL2>
• The inverter stops electricity discharge operation, to protect the DB resistor.
Then, usually inverter displays "OU trip".
• Connects the relay output to the terminal THR, to protect the DB resistor.
Then, usually the inverter displays "OH trip".
Number of Auto reset times and reset interval can be preset.
Pollution degree 2 when complying with Low Voltage Directive is needed.
*
When altitude is 6600ft (2000m) or higher, interface circuit should be isolated from main power lines, to comply with Low Voltage Directive.
F14
A06 to A08
1-8
Item Explanation Remarks Func. code Explanation Func. code
Indication Operation mode
(Running)
LED monitor
The following items can be displayed by function setting.
• Output frequency 1 (Before slip compensation) [Hz]
• Output frequency 2 (After slip compensation) [Hz]
• Setting frequency [Hz]
• Output current [A]
• Output voltage [V]
• Motor synchronous speed [r/min]
• Line speed [m/min]
• Load shaft speed [r/min]
• Torque calculation value [%]
• Input power [kW]
• PID reference value
• PID reference value (remote)
• PID feedback value
• Trip history Cause of trip of the last 4 trips can be retained and displayed. (Even when main power is off, data is retained.)
• PG feedback value is displayed when PG option is used.
E43
F01 C30
LCD monitor
Languages for the LCD monitor are selectable. English, German, French, Spanish, Italian, Japanese
Operation monitor & Alarm monitor
• Operation monitor
Two types of monitoring is selectable by "E45".
• Displays operation guidance
• Bargraph
• Output frequency (before slip compensation) [%]
• Output current [A]
• Output torque [%]
• Alarm monitor
When the inverter trips, displays the alarm.
E46
E45
Chapter 1
2. Common Specifications
Indication Stopping
Item Explanation Remarks Func. code Explanation Func. code
Tri p mode
Charge lamp When the DC link circuit voltage is higher than 50V, the charge lamp is ON.
LED monitor
Selected setting value or output value
Displays the cause of trip by codes as follows.
• OC1 (Overcurrent during acceleration)
• OC2 (Overcurrent during deceleration)
• OC3 (Overcurrent running at constant speed)
• EF (Ground fault)
• Lin (Input phase loss)
• FUS (Fuse blown)
• OU1 (Overvoltage during acceleration)
• OU2 (Overvoltage during deceleration)
• OU3 (Overvoltage running at constant speed)
• LU (Undervoltage)
• OH1 (Overheating at heat sink)
• OH2 (External thermal relay tripped)
• OH3 (Overtemperature at inside air)
• dBH (Overheating at DB circuit)
• OL1 (Motor1 overload)
• OL2 (Motor2 overload)
• OLU (Inverter unit overload)
• OS (Overspeed)
• PG (PG error)
• Er1 (Memory error)
• Er2 (KEYPAD panel communica­tion error)
• Er3 (CPU error)
• Er4 (Option communication error)
• Er5 (Option error)
• Er6 (Operation procedure error)
• Er7 (Output phase loss error, impedance imbalance)
• Er8 (RS-485 error)
• Trip history
Cause of trip of the last 4 trips can be retained and displayed. (Even when main power is off, data are retained.)
E44
LCD monitor
Function setting & monitor
Selectable from the following 7 indications.
••
Function setting
••
Displays function codes and its data or data code.
• Changes the data value.
••
Operation condition monitoring
••
Output frequency (before slip compensation)
• Output current [A]
• Output voltage [V]
• Torque calculation value [%]
• Setting frequency [Hz]
• Operation condition
FWD or REV (Forward or reverse running)
• IL (Current limiting)
• VL or LU (Voltage limiting or stopped by undervoltage)
• TL (Torque limiting)
• Motor synchronous speed [r/min]
• Load shaft speed [r/min]
• Line speed [m/min]
• PID reference value
• PID feedback value
Driving torque limiter setting value [%]
Braking torque limiter setting value [%]
••
Tester function (I/O check)
••
Displays on/off status of digital input and output signals, level of analog input and pulse output signals.
•Digital I/O : (ON), ■ (OFF)
• Analog I/O: [V] , [mA], [H], [p/s]
••
Maintenance data
••
• Operation time [h]
• DC link circuit voltage [V]
• Temperature at inside air [°C]
• Temperature at heat sink [°C]
• Maximum current [A]
• Main circuit capacitor life [%]
• Control PC board life [h]
• Cooling fan operation time [h]
• Communication error times (KEYPAD)
• Communication error times (RS-485)
• Communication error times (Option)
• ROM version (Inverter)
• ROM version (KEYPAD)
• ROM version (Option)
••
Load factor calculation
••
• Measurement time [s]
• Maximum current [A]
• Effective current [A]
• Average braking power [%]
••
Alarm data
••
Dispalys operation data immediately before a trip occurs.
Output frequency (before slip compensation)
• Output current [A]
• Output voltage [V]
• Torque calculation value [%]
• Setting frequency [Hz]
• Operation condition
• FWD or REV (Forward or reverse running)
• IL (Current limiting)
• VL or LU (Voltage limiting or stopped by undervoltage)
• TL (Torque limiting)
• Operation time [h]
• DC link circuit voltage [V]
• Temperature at inside air [°C]
• Temperature at heat sink [°C]
• Communication error times (KEYPAD)
• Communication error times (RS-485)
• Communication error times (Option)
• Digital input terminal condition (Remote) Digital input terminal condition (Communication)
• Transistor output terminal condition
• Trip history code
• Multiple alarm exist
••
Data copy
••
• Function code (data and data code) is stored in one inverter and is copied to another inverter *.
* Copying is only available to the inverter
of the same series, same voltage class, and same capacity .
[Hz]
[Hz]
1
1-9
Chapter 1
2. Common Specifications

2.2 Protective functions

Function Description
Overcurrent protection
(Short-circuit) (Ground fault)
Overvoltage protection
Incoming surge protection
Undervoltage protection
Input phase loss protection
Overheat protection
Electronic thermal overload relay (Motor protection)
Fuse blown Stall prevention
(Momentary overcurrent limitation)
Active drive
External alarm input
Overspeed protection
PG error Alarm output
(for any fault)
Alarm reset command
Alarm history memory
Storage of data on cause of trip
Memory error
KEYPAD panel communication error
CPU error
Option communication error
Option error Operation
procedure error Output phase loss
error
RS-485 communication error
*) ▲ : By function code setting, alarm output can be disabled. NOTES :
1) Retaining alarm signal when auxiliary controll power supply is not used :
2) To issue the RESET command, press the
3) Fault history data is stored for the past four trips.
1-10
• Stops running to protect inverter from an overcurrent resulting from overload.
• Stops running to protect inverter from an overcurrent due to a short-circuit in the output circuit.
• Stops running to protect inverter from an overcurrent due to a ground fault in the output circuit.
Stops running to protect inverter from an overcurrent resulting from ground fault
in the output circuit by detecting zero-phase current. (30kW or larger model only)
• The inverter stops when it detects an overvoltage in the DC link circuit. (230V : 400Vdc or more, 460V : 800Vdc or more)
Protection is not assured if excess AC line voltage is applied inadvertently.
• Protects the inverter against surge voltage between the main circuit power line and ground.
• Protects the inverter against surge voltage in the main circuit power line.
• The inverter may be tripped by some other protective function.
Stops the inverter when the DC link circuit voltage drops below undervoltage level. (230V series : 200V DC or less, 460V series : 400V DC or less)
• Alarm signal is not output even if the DC link circuit voltage drops, when “F14 : 3 to 5” is selected.
• The inverter is protected from being damaged when open-phase fault occurs.
• Stops the inverter when it detects excess heat sink temperature in case of cooling fan failure or overload.
• Stops the inverter when it detects an abnormal rise in temperature in the inverter unit caused by insufficient ventilation in cubicles or an abnormal ambient temperature.
• Stops the inverter when it detects an abnormal rise in temperature inside the inverter.
• When the built-in or external braking resistor overheats, the inverter stops discharging and running.
Function data appropriate for the resistor type (built-in/external) must be set. (G11S: 10HP or smaller only)
• This function stops the inverter by detecting an inverter overload.
• This function stops the inverter by detecting an overload in a standard motor or inverter motor.
When a blown fuse is detected, the inverter stops running. (40HP or larger model only)
• When an output current exceeds the limit during acceleration, this function lowers output frequency to prevent the occurrence of an OC1 trip.
• The stall prevention function can be disabled.
• During running in which acceleration is 60s or longer, this function increases the acceleration time to prevent the occurrence of an OLU trip.
• The acceleration time can be prolonged up to three times the preset time.
• The inverter stops on receiving external alarm signals.
• Use THR terminal function (digital input).
• Stops the inverter when the output frequency exceeds the rated maximum frequency by 20%.
If disconnection occurs in pulse generator circuits, the inverter issues an alarm.
• The inverter outputs a relay contact signal when the inverter issued an alarm and stopped.
• An alarm-stop state of the inverter can be cleared with the RESET key or by a digital input signal (RST).
• Store up to four instances of previous alarm data.
• The inverter can store and display details of the latest alarm history data.
• The inverter checks memory data after power-on and when the data is written. If a memory error is detected, the inverter stops.
• If an error is detected in communication between the inverter and KEYPAD when the Keypad panel is being used, the inverter stops.
• When operated by external signals, the inverter continues running. The alarm output (for any fault) is not output. Only Er2 is displayed.
• If the inverter detects a CPU error caused by noise or some other factor, the inverter stops.
• If a checksum error or disconnection is detected during communication, the inverter issues an alarm.
If a linkage error or other option error is detected, the inverter issues an alarm.
Er6 is indicated only when the inverter is forcedly stopped by [STOP1] or [STOP2] operation in E01 to E09 (Set value: 30 or 31)
If an unbalance of output circuits is detected during auto-tuning, this function issues an alarm (and stops the inverter).
• If an RS-485 communication error is detected, the inverter issues an alarm.
If the inverter power supply is cut off while an internal alarm signal is being output, the alarm signal cannot be retained.
LED monitor
During acceleration
During deceleration
While running at constant speed
Groung fault
During acceleration During deceleration While running at constant speed
Motor 1 overload Motor 2 overload
• Output terminals: 30A, 30B, and 30C
• Use the RST terminal function for signal input.
• Even if main power input is turned off, alarm history and trip-cause data are retained.
key on the KEYPAD panel or connect terminals RST and CM and disconnect them afterwards.
RESET
Alarm output Func. code
(30Ry) *)
F14
F13
F10 to F12 A06 to A08
F40, F41 E16, E17
H12
F36
F02
Chapter 1
∨
2. Common Specifications
2.3 Function settings
The function marked can be set while the inverter is running. Other functions must be set while the inverter is stopped.
Fundamental Functions
Function Code Name LCD monitor unit 30HP 40HP
F00 Data protection F00 DATA PRTC 0:Data change enable
F01 Frequency command 1 F01 FREQ CMD 1 0 : KEYPAD operation (∨ or
F02 Operation method F02 OPR METHOD 0 : KEYPAD operation (
F03 Maximum frequency 1 F03 MAX Hz-1 G11S : 50 to 400Hz
F04 Base frequency 1 F04 BASE Hz-1 G11S : 25 to 400Hz
F05 Rated voltage 1 F05 RATED V-1 0V : The output voltage in proportion to the power
(at Base frequency 1 ) 80 to 240V : AVR active (230V)
F06 Maximum voltage 1 F06 MAX V-1 80 to 240V : AVR active (230V)
(at Maximum frequency 1) 320 to 480V : AVR active (460V)
F07 Acceleration time 1 F07 ACC TIME1 0.01 to 3600s F08 Deceleration time 1 F08 DEC TIME1 0.01 to 3600s
F09 Torque boost 1 F09 TRQ BOOST1 0.0 : Automatic (for constant torque load)
F10 Electronic (Select) F10 ELCTRN OL1 0 : Inactive
thermal 1 : Active (for 4-pole standard motor) overload relay 2 : Active (for 4-pole inverter motor)
F11 for motor 1 (Level) F11 OL LEVEL1 Approx. 20 to 135% of rated current of the inverter
F12 (Thermal time constant) F12 TIME CNST1 0.5 to 75.0 min
F13 Electronic thermal F13 DBR OL G11S [10HP or smaller]
overload relay 0 : Inactive (for braking resistor) 1 : Active (for built-in braking resistor)
F14 Restart mode (Select) F14 RESTART 0 : Inactive (Trip and alarm when power failure occurs.)
after momentary 1 : Inactive (Trip, and alarm when power recovers.) power failure 2 : Inactive (Deceleration stop, and alarm)
F15 Frequency (High) F15 H LIMITER G11S : 0 to 400Hz P11S : 0 to 120Hz
limiter (Low) F16 L LIMITER G11S : 0 to 400Hz P11S : 0 to 120Hz
F16 F17 Gain (for frequency F17 FREQ GAIN 0.0 to 200.0%
F18 Bias frequency F18 FREQ BIAS G11S : -400.0 to 400.0Hz P11S : -120.0 to 120.0Hz
F20 DC brake(Starting freq.) F20 DC BRK Hz 0.0 to 60.0Hz F21 (Braking level) F21 DC BRK LVL G11S : 0 to 100% P11S : 0 to 80% F22 (Braking time) F22 DC BRK t 0.0 (DC brake inactive), 0.1 to 30.0s
setting signal)
1:Data protection
Voltage input (terminal 12) (0 to 10Vdc, 0 to 5Vdc)
1: 2:Current input (terminal C1) (4 to 20mAdc) 3:Voltage and current input (terminals 12 and C1) 4:Reversible operation with polarity
(terminal 12) (0 to ± 10Vdc)
5:Reversible operation with polarity
(terminal 12 and V1) (0 to ± 10Vdc)
6:Inverse mode operation (terminal 12)
(+10 to 0Vdc)
7:Inverse mode operation (terminal C1)
(20 to 4mAdc) 8:UP/DOWN control 1 (initial freq. = 0Hz) 9:UP/DOWN control 2 (initial freq. = last value) 10 : PATTERN operation 11 : DI option or Pulse train input
1:External signal input (digital input)
(Operation by FWD or REV command)
P11S : 50 to 120Hz
P11S : 25 to 120Hz
supply voltage is set.
320 to 480V : AVR active (460V)
0.1 to 0.9 : Manual (for variable torque load)
1.0 to 1.9 : Manual (for proportional torque load)
2.0 to 20.0 : Manual (for constant torque load)
rated current, in Ampere
2 : Active (for external braking resistor) [15HP or larger]
0 : Inactive
P11S [15HP or smaller]
0 : Inactive 2 : Active (for external braking resistor)
[20HP or larger] 0 : Inactive
Active (Smooth recovery by continuous operation mode)
3: 4:Active (Momentarily stops and restarts at output
frequency of before power failure)
5:Active (Momentarily stops and restarts at
starting frequency)
Setting range Unit
key)
or
or
FWD
REV
STOP
key)
Min. Factory setting
-- 0
-- 0
-- 0
Hz 1 60
Hz 1 60
V1
230:(230V class)
V1230:(230V class)
s 0.01 6.0 20.0
s 0.01 6.0 20.0
- 0.1 G11S : 2.0
-- 1
A 0.01 Motor rated
min 0.1 5.0 10.0
-- 1
-- 0
-- 0
-- 0
-- 0
Hz 1 70 Hz 1 0
% 0.1 100.0
Hz 0.1 0.0 Hz 0.1 0.0
% 1 0
s 0.1 0.0
460:(460V class)
460:(460V class)
P11S : 2.0
current
Remarks
Setting can be made so that a set value cannot be easily changed by KEYPAD panel operation.
Sets the operation command input method.
Sets the maximum output frequency for motor 1.
Sets the base frequency for motor 1.
Sets the output voltage at the Base frequency 1 “F04”.
Sets the output voltage at the Maximum frequency 1 “F03”.
During deceleration, Coast­to-stop can be selected by setting of “H11”.
Torque boost for motor 2 can also be set by “A05”.
Selection fo motor 2 can also be made by “A06”.
Level setting for motor 2 can also be made by “A07”.
Setting for motor 2 can also be made by “A08”.
Not provided with models 15HP or larger.
Not provided with models 20HP or larger.
For detailed setting procedure, see “H13” to “H16”.
Minus bias setting is possible.
1
1-11
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is stopped.
Function Code Name LCD monitor unit 30HP 40HP
Setting range Unit
F23 Starting frequency (Freq.) F23 START Hz 0.1 to 60.0Hz F24 (Holding time) F24 HOLDING t 0.0 to 10.0s F25 Stop frequency F25 STOP Hz 0.1 to 6.0Hz F26 Motor sound (Carrier freq.) F26 MTR SOUND 0.75-15kHz 0.75-10kHz 0.75-6kHz
G11S -75HP 100HP P11S -30HP 40-100HP 125HP
F27 (Sound tone) F27 MTR TONE 0 : Level 0
1: Level 1 2: Level 2 3: Level 3
F30 FMA (Voltage adjust) F30 FMA V-ADJ 0 to 200% F31 (Function) F31 FMA FUNC 0 : Output frequency 1 (Before slip compensation)
1: Output frequency 2 (After slip compensation) 2: Output current 3: Output voltage 4: Output torque 5: Load factor 6: Input power 7: PID feedback value 8: PG feedback value 9: DC link circuit voltage
10 : Universal AO F33 FMP (Pulse rate) F33 FMP PULSES 300 to 6000 p/s (at full scale) F34 (Voltage adjust) F34 FMP V-ADJ 0% : Pulse rate output (50% duty)
F35 (Function) F35 FMP FUNC 0 : Output frequency 1 (Before slip compensation)
F36 30RY operation mode F36 30RY MODE 0 : The relay(30) excites on trip mode
F40 To rque limiter 1 (Driving) F40 DRV TRQ 1 G11S : 20 to 200, 999% (999: No limit) *2)
F41 (Braking) F41 BRK TRQ 1 G11S : 0 (Automatic deceleration control),
F42 Torque vector control 1 F42 TRQVECTOR1 0 : Inactive
1 to 200% : Voltage adjust : 2670 p/s (duty adjust)
1: Output frequency 2 (After slip compensation)
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback value
8: PG feedback value
9: DC link circuit voltage
10 : Universal AO
1: The relay(30) excites on normal mode
P11S : 20 to 150, 999% (999: No limit)
20 to 200, 999% (999: No limit) *2)
P11S : 0 (Automatic deceleration control),
20 to 150, 999% (999: No limit)
1: Active
Min. Factory setting
Hz 0.1 0.5
s 0.1 0.0
Hz 0.1 0.2
kHz 1 2
-- 0
% 1100
-- 0
p/s 1 1440
% 1 0
-- 0
-- 0
% 1999
% 1999
-- 0
Remarks
Sets the frequency at stopping. * In case of VT use, carrier
frequency should be adjusted depending on capacity
Four types of tone can be selected.
This setting is effective when the carrier frequency "F26" is set at 7kHz or lower.
This selection can be made at 7kHz or higher, but the tone does not change.
About 0 and 1
1:Output frequency 2 0:Output frequency 1
Setting value
KEYPAD panel
Slip compensation amount
Percent indication based on inverter rated voltage
About 0 and 1
1:Output frequency 2 0:Output frequency 1
Setting value
KEYPAD panel
Slip compensation amount
M
Inverter
M
Inverter
1-12
Extension Terminal Functions
Function Code Name LCD monitor unit 30HP 40HP
Setting range Unit
E01 X1 terminal function E01 X1 FUNC Selects from the following items. E02 X2 terminal function E02 X2 FUNC E03 X3 terminal function E03 X3 FUNC E04 X4 terminal function E04 X4 FUNC E05 X5 terminal function E05 X5 FUNC E06 X6 terminal function E06 X6 FUNC E07 X7 terminal function E07 X7 FUNC E08 X8 terminal function E08 X8 FUNC E09 X9 terminal function E09 X9 FUNC
0: [SS1]
 
1:Multistep freq. select (1 to 4bit) [SS2]
2:(16 steps) [SS4]
 
3: [SS8]
4:4 steps of ACC/DEC time [RT1]
 
5:selectioin (1 to 2bit) [RT2]
6: 3-wire operation stop command [HLD]
7: Coast-to-stop command [BX]
8: Alarm reset [RST]
9: Trip command (External fault) [THR]
10 : Jogging operation [JOG]
11 : Freq. set. 2 / Freq. set. 1 [Hz2/Hz1]
12 : Motor 2 / Motor 1 [M2/M1] 12: Switches motor
Min. Factory setting
-- 0
-- 1
-- 2
-- 3
-- 4
-- 5
-- 6
-- 7
-- 8
Remarks
parameters to motor 2 when this signal is on.
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is stopped.
Function Code Name LCD monitor unit 30HP 40HP
13 : DC brake command [DCBRK] 14 : Torque limiter 2 / Torque limiter 1
15 : Switching operation between line and inverter
(50Hz) [SW50]
16 : Switching operation between line and inverter
(60Hz) [SW60]
17 : UP command [UP] 18 : DOWN command [DOWN] 19 : Write enable for KEYPAD [WE-KP]
20 : PID control cancel [Hz/PID] 21 : Inverse mode changeover (terminals 12 and C1)
22 : Interlock signal for 52-2 [IL] 23 : TRQ control cancel [Hz/TRQ] 24 : Link enable (Bus, RS-485) [LE] 25 : Universal DI [U-DI] 26 : Pick up start mode [STM] 27 : SY-PG enable [PG/Hz] 28 : Synchronization command [SYC] 29 : Zero speed command [ZERO] 30 : Forced stop command [STOP1] 31 : Forced stop command with Deceleration time 4
32 : Pre-exciting command [EXITE] E10 Acceleration time 2 E11 Deceleration time 2 E11 DEC TIME2 E12 Acceleration time 3 E12 ACC TIME3 E13 Deceleration time 3 E13 DEC TIME3 E14 Acceleration time 4 E15 Deceleration time 4 E15 DEC TIME4 E16 Tor que limiter 2 (Driving) E16 DRV TRQ 2 G11S: 20 to 200%, 999% (999: No limit) *2)
E17 (Braking) E17 BRK TRQ 2 G11S : 0 (Automatic deceleration control),
E20 Y1 terminal function E21 Y2 terminal function E21 Y2 FUNC E22 Y3 terminal function E22 Y3 FUNC E23 Y4 terminal function E23 Y4 FUNC E24 Y5A,Y5C terminal function
E25 Y5 RY operation mode
E10 ACC TIME2 0.01 to 3600s
E14 ACC TIME4
P11S : 20 to 150%, 999% (999: No limit)
20 to 200%, 999% (999: No limit) *2)
P11S : 0 (Automatic deceleration control),
20 to 150%, 999% (999: No limit)
E20 Y1 FUNC Selects from the following items.
E24 Y5 FUNC
0: Inverter running [RUN]
1: Frequency equivalence signal [FAR]
2: Frequency level detection [FDT1]
3: Undervoltage detection signal [LU]
4: Torque polarity [B/D]
5: Torque limiting [TL]
6: Auto-restarting [IPF]
7: Overload early warning [OL1]
8: KEYPAD operation mode [KP]
9: Inverter stopping [STP]
10 : Ready output [RDY]
11 : Line/Inv changeover (for 88) [SW88]
12 : Line/Inv changeover (for 52-2) [SW52-2]
13 : Line/Inv changeover (for 52-1) [SW52-1]
(11 to 13: For Line/Inverter changeover operation) 14 : Motor 2 / Motor 1 [SWM2] 15 : Auxiliary terminal (for 52-1) [AX] 16 : Time-up signal [TU] 17 : Cycle completion signal [TO] 18 : Stage No. indication 1 [STG1] 19 : Stage No. indication 2 [STG2] 20 : Stage No. indication 4 [STG4]
(16 to 20: For PATTERN operation) 21 : Alarm indication 1 [AL1] 22 : Alarm indication 2 [AL2] 23 : Alarm indication 4 [AL4] 24 : Alarm indication 8 [AL8]
(21 to 24: For Alarm signal output) 25 : Fan operation signal (for 40HP and above) [FAN] 26 : Auto-resetting [TRY] 27 : Universal DO [U-DO] 28 : Overheat early warning [OH] 29 : Synchronization completion signal [SY] 30 : Lifetime alarm [LIFE] 31 : 2nd Freq. level detection [FDT2] 32 : 2nd OL level early warning [OL2] 33 : Terminal C1 off signal [C1OFF] 34 : Speed existence signal [DNZS]
E25 Y5RY MODE 0 : Inactive (Y5 Ry excites at "ON signal" mode.)
1: Active (Y5 Ry excites at "OFF signal" mode.)
Setting range Unit
[TL2/TL1]
[IVS]
[STOP2]
Min. Factory setting
s 0.01 6.00 20.00 s 0.01 6.00 20.00 s 0.01 6.00 20.00 s 0.01 6.00 20.00 s 0.01 6.00 20.00 s 0.01 6.00 20.00
% 1999
% 1999
-- 0
-- 1
-- 2
-- 7
-- 10
--
0
Remarks
15, 16:
When 15 or 16 is turned on, the operation smoothly changes to commercial power operation at 50 or 60Hz, without stopping the
motor. From 50Hz power line : (SW50) From 60Hz power line : (SW60)
17, 18 : "F01" must be set at
"8: UP/DOWN
control 1" or "9: UP/
DOWN control 2".
20 :When this signal is on,
PID control is canceled and KEYPAD operation is effective.
23 :When this signal is on,
torque control is canceled.
27 : PG/Hz is option. 28 : SY is option. 29 : ZERO is option.
32 : EXITE is option.
F40, F41
29 : SY is option.
34: DNZS is option.
1
F07 F08
1-13
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is stopped.
Function Code Name LCD monitor unit 30HP 40HP
E30 FAR function (Hysteresis) E30 FAR HYSTR 0.0 to 10.0 Hz
signal
Setting range Unit
E31 FDT1 function (Level) E31 FDT1 LEVEL G11S : 0 to 400 Hz P11S : 0 to 120 Hz E32 signal (Hysteresis) E32 FDT HYSTR 0.0 to 30.0 Hz E33 OL1 function(Mode select) E33 OL1 WARNING 0 : Thermal calculation
signal 1 : Output current
E34 (Level) E34 OL1 LEVEL G11S : Approx. 5 to 200% of rated current
P11S : Approx. 5 to 150% of rated current E35 (Timer) E35 OL TIMER 0.0 to 60.0s E36 FDT2 function (Level) E36 FDT2 LEVEL G11S : 0 to 400Hz P11S : 0 to 120Hz E37 OL2 function (Level) E37 OL2 LEVEL G11S : Approx. 5 to 200% of rated current
P11S : Approx. 5 to 150% of rated current E40 Display coefficient A E40 COEF A -999.00 to 999.00 E41 Display coefficient B E41 COEF B -999.00 to 999.00 E42 LED Display filter E42 DISPLAY FL 0.0 to 5.0s E43 LED Monitor (Function) E43 LED MNTR 0 : Output frequency 1 (Before slip compensation)
E44 (Display at STOP mode) E44 LED MNTR2 0 : Setting value
E45 LCD Monitor (Function) E45 LCD MNTR 0 :Displays operation guidance
E46 (Language) E46 LANGUAGE 0 :Japanese
1: Output frequency 2 (After slip compensation)
2: Setting frequency [Hz]
3: Output current [A]
4: Output voltage [V]
5: Motor synchronous speed [r/min]
6: Line speed [m/min]
7: Load shaft speed [r/min]
8: Torque calculation value [%]
9: Input power [kW]
10 : PID reference value
11 : PID reference value (remote)
12 : PID feedback value
[Hz]
1: Output value
1 :Bar graph
(Output freq., Output current, and Output torque)
1 :English
2 :German
3 :French
4 :Spanish
5 :Italian E47 (Contrast) E47 CONTRAST 0 (Soft) to 10 (Hard)
Min. Factory setting
Hz 0.1 2.5
Hz 1 60 Hz 0.1 1.0
-- 0
A 0.01 Motor rated
current
s 0.1 10.0
Hz 1 60
A 0.01 Motor rated
current
- 0.01 0.01
- 0.01 0.00 s 0.1 0.5
-- 0
-- 0
-- 0
-- 1
-- 5
Remarks
E20 to E24: 1
E20 to E24: 2
E20 to E24: 7
About 0 and 1
1:Output frequency 2 0:Output frequency 1
Setting value
KEYPAD panel
Slip compensation amount
Selects items displayed on the LED monitor when inverter is stopping.
Indicates based on inverter rated current.
M
Inverter
Control Functions of Frequency
Function Code Name LCD monitor unit 30HP 40HP
Setting range Unit
C01 Jump (Jump freq. 1) C01 JUMP Hz 1 G11S : 0 to 400Hz P11S : 0 to 120Hz C02 frequency(Jump freq. 2) C02 JUMP Hz 2 C03 (Jump freq. 3) C03 JUMP Hz 3 C04 (Hysteresis) C04 JUMP HYSTR 0 to 30Hz C05 Multistep (Freq. 1) C05 MULTI Hz-1 G11S : 0.00 to 400.00Hz P11S : 0.00 to 120.00Hz C06 frequency (Freq. 2) C06 MULTI Hz-2 C07 setting (Freq. 3) C07 MULTI Hz-3 C08 (Freq. 4) C08 MULTI Hz-4 C09 (Freq. 5) C09 MULTI Hz-5 C10 (Freq. 6) C10 MULTI Hz-6 C11 (Freq. 7) C11 MULTI Hz-7 C12 (Freq. 8) C12 MULTI Hz-8 C13 (Freq. 9) C13 MULTI Hz-9 C14 (Freq.10) C14 MULTI Hz10 C15 (Freq.11) C15 MULTI Hz11 C16 (Freq.12) C16 MULTI Hz12 C17 (Freq.13) C17 MULTI Hz13 C18 (Freq.14) C18 MULTI Hz14 C19 (Freq.15) C19 MULTI Hz15 C20 JOG frequency C20 JOG Hz G11S : 0.00 to 400.00Hz P11S : 0.00 to 120.00Hz C21 PATTERN operation C21 PATTERN 0 : Active (Mono-cycle operation, and then stops.)
(Mode select) 1 : Active (Continuous cyclic operation during
operation command is effective.)
2: Active (Mono-cycle operation, and after
continues at the latest setting frequency.)
Min. Factory setting
Hz 1 0 Hz 1 0 Hz 1 0 Hz 1 3 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 0.00 Hz 0.01 5.00
-- 0
Remarks
1-14
Chapter 1
XM
X2+XM
X1+X2 x +Cable X
V/ ( 3 x I)
%X= x 100
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is stopped.
Function Code Name LCD monitor unit 30HP 40HP
C22 (Stage 1) C22 STAGE 1 • Operation time: 0.00 to 6000s C23 (Stage 2) C23 STAGE 2 • F1 to F4 and R1 to R4 C24 (Stage 3) C24 STAGE 3 Code FWD/REV ACC/DEC C25 (Stage 4) C25 STAGE 4 F1: FWD ACC1 / DEC1 C26 (Stage 5) C26 STAGE 5 F2: FWD ACC2 / DEC2 C27 (Stage 6) C27 STAGE 6 F3: FWD ACC3 / DEC3 C28 (Stage 7) C28 STAGE 7 F4: FWD ACC4 / DEC4
* Setting for R1: REV ACC1 / DEC1 operation time, R2: REV ACC2 / DEC2 FWD/REV rotation and R3: REV ACC3 / DEC3 ACC/DEC time select. R4: REV ACC4 / DEC4
C30 Frequency command 2 C30 FREQ CMD 2 0 : KEYPAD operation (
C31 Offset (Terminal 12) C31 OFFSET 12 -5.0 to +5.0% C32 Offset (Terminal C1) C32 OFFSET C1 -5.0 to +5.0% C33 Analog setting signal C33 REF FILTER 0.00 to 5.00s
filter
1: Voltage input (terminal 12) (0 to 10Vdc, 0 to 5Vdc) 2: Current input (terminal C1) (4 to 20mAdc) 3: Voltage and current input (terminals 12 and C1) 4: Reversible operation with polarity (terminal 12)
(0 to ± 10Vdc)
5: Reversible operation with polarity
(terminal 12 and V1) (0 to ± 10Vdc)
6: Inverse mode operation (terminal 12) (10 to 0Vdc) 7: Inverse mode operation (terminal C1) (20 to 4mAdc) 8: UP/DOWN control 1 (initial freq. = 0Hz) 9: UP/DOWN control 2 (initial freq. = last value) 10 : PATTERN operation 11 : DI option or Pulse train input
Setting range Unit
∨
or key)
Min. Factory setting
s 0.01 0.00 F1 s 0.01 0.00 F1 s 0.01 0.00 F1 s 0.01 0.00 F1 s 0.01 0.00 F1 s 0.01 0.00 F1 s 0.01 0.00 F1
-- 2
%0.1 0.0 %0.1 100.0
s 0.01 0.05
Remarks
F01, H30 F17,18 E01-09:11,20,23
Data 2, 3, and 7 are always inactive
E01-E09:21 E01-E09:21 E01-E09:17 E01-E09:18 C21-C28
1
Motor Parameters
Function Code Name LCD monitor unit 30HP 40HP
P01 Number of motor 1 poles P01 M1 POLES 2 to 14
P02 Motor 1 (Capacity) P02 M1-CAP 30HP or smaller : 0.01 to 45.00 kW
P03 (Rated current) P03 M1-Ir 0.00 to 2000 A
P04 (Tuning) P04 M1 TUN1 0 : Inactive
P05 (On-line Tuning) P05 M1 TUN2 0 : Inactive
P06 (No-load current) P06 M1-Io 0.00 to 2000 A
P07 (%R1 setting) P07 M1-%R1 0.00 to 50.00 %
P08 (%X setting) P08 M1-%X 0.00 to 50.00 %
40HP or larger : 0.01 to 500.00 kW
1: Active (One time tuning of %R1 and %X (on
motor stopping mode ))
2: Active (One time tuning of %R1, %X and Io (on
motor running mode ))
1: Active (Real time tuning of %R2)
Setting range Unit
Min. Factory setting
pole 2 4
kW 0.01 Motor Capacity
A 0.01
-- 0
-- 0
A 0.01 Fuji standard
% 0.01 Fuji standard
% 0.01 Fuji standard
Motor rated
current
rated value
rated value
rated value
Remarks
Sets the number poles of the motor 1.
Set the applied motor capacity. This setting automatically sets "P03" and "P06" to "P08". Frame must be from -2 to +1. When a frame is outside this range, take a special note.
Sets the motor rated current.
Measure %R1 of motor, and %X and Io at base frequency. When "1" is selected, data is stored in "P07" and "P08". When "2" selected, data is stored in "P06" to "P08".
Data in "P07" and "P08" is not updated.
Sets exciting current at torque-vector control.
Sets motor primary coil resistance manually.
R1+Cable R
%R1= x 100
V/( 3 x I)
R1: Motor primary resistance [Ω] Cable R : Resistance at output side cable V : Rated voltage [V] I : Motor rated current [A]
Sets motor leakage inductance at base frequency manually.
P09
NOTE: Percent shall be set according to Function code "P02" or "A09", motor capacity.
(Slip compensation control 1)
P09 SLIP COMP1 0.00 to +15.00 Hz
Torque referenced here may not be obtainable when "P02" or "A09" is set at "0".
Hz 0.01 0.00
X1 : Motor primary leakage reactance [Ω] X2 : Motor secondary leakage reacstance [Ω] XM : Excitation reactance [Ω] Cable X : Cable resctance (Primary conversion value) [Ω] V : Rated voltage [V] I : Motor rated current [A]
Sets the slip frequency.
1-15
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is stopped.
High Performance Functions
1-16
Function Code Name LCD monitor unit 30HP 40HP
H03 Data initializing H03 DATA INIT 0 : Manual set value
H04 Auto-reset (Times) H04 AUTO-RESET 0 (Inactive), 1 to 10 times H05 (Reset interval) H05 RESET INT 2 to 20s H06 Fan stop operation H06 FAN STOP 0: Inactive
H07 ACC/DEC (Mode select) H07 ACC PTN 0 : Linear
pattern 1 : S-curve (weak)
H08 Rev. phase sequence lock H08 REV LOCK 0 : Inactive 1 : Active H09 Start mode H09 START MODE 0 : Inactive
(Rotating motor pick up) 1 :
H10 Energy-saving operation H10 ENERGY SAV 0 : Inactive
H11 DEC mode H11 DEC MODE 0 : Normal (According to "H07" mode)
H12 Instantaneous H12 INST CL 0 : Inactive
overcurrent limiting 1 : Active
H13 Auto-restart (Restart time) H13 RESTART t 0.1 to 10.0s
H14 (Freq. fall rate) H14 FALL RATE 0.00 to 100.00 Hz/s H15 (Holding DC voltage) H15 HOLD V 200 to 300V (230V)
(OPR command selfhold time)
H16
H18 Torque control H18 TRQ CTRL G11S 0 : Inactive (Frequency control)
H19 Active drive H19 AUT RED 0 : Inactive
H20 PID control (Mode select) H20 PID MODE 0 : Inactive
H21 (Feedback signal) H21 FB SIGNAL 0 : Terminal 12 (0 to +10V)
H22 (P-gain) H22 P-GAIN 0.01 to 10.00 H23 (I-gain) H23 I-GAIN 0.0 : Inactive
H24 (D-gain) H24 D-GAIN 0.00 : Inactive
H25 (Feedback filter) H25 FB FILTER 0.0 to 60.0s
PTC thermistor (Mode select)
H26
H27 (Level) H27 PTC LEVEL 0.00 to 5.00V H28 Droop operation H28 DROOP G11S: -9.9 to 0.0Hz
H30 Serial link(Function select) H30 LINK FUNC (Code) (Monitor) (Frequency (Operation
H31 RS-485 (Address) H31 485ADDRESS 1 to 31 H32 (Mode select on no H32 MODE ON ER 0 : Trip and alarm (Er8)
H33 (Timer) H33 TIMER 0.0 to 60.0s H34 (Baud rate) H34 BAUD RATE 0 : 19200 bit/s
(Data reset) 1 : Return to factory set value
1: Active (Fan stops at low temperature mode (2HP
or larger)
2: S-curve (strong)
4: Non-linear (For variable torque load)
Active (Only Auto-restart after momentary power failure mode )
2: Active (All start mode)
1: Active (Only when torque boost "F09" is in
manual setting mode
1: Coast-to-stop
H16 SELFHOLD t 0.0 to 30.0s, 999s (999s: The operation command is
H26 PTC MODE 0 : Inactive
response error) 1 : Operation for H33 timer, and alarm (Er8)
400 to 600V (460V)
held during DC link circuit voltage is larger than 50V)
1: Active (Torque control by terminal 12 (Driving))
2: Active (Torque control by terminal 12 (Driving &
P11S 0 : Inactive (Fixed)
1: Active
1: Active
2: Active (inverse operation mode)
1: Ter minal C1 (4 to 20mA)
2: Ter minal 12 (+10 to 0V)
3: Ter minal C1 (20 to 4mA)
0.1 to 3600.0s
0.01 to 10.0s
1: Active
P11S : 0.0 (Fixed)
0 : X - ­1: X X ­2 : X - X 3 : X X X
2: Operation for H33 timer,and retry to communicate.
* If the retry fails, then the inverter trips("Er 8").
3: Continuous operation
1: 9600
2: 4800
3: 2400
4: 1200
Setting range Unit
(0 to +10V/0 to 200%)
Braking))
(0 to +10V/0 to 200%)
command) command)
(X: Valid -: Invalid)
Min. Factory setting
-- 0
-1 0 s1 5
-- 0
-- 0
-- 0
-- 0
-- G11S:0
-- 0
-- 1
s0.1 0.5
Hz/s 0.01 10.00
V 1 230V class : 235V
s0.1 999
-- 0
-- 0
-- 0
-- 0
-- 1
- 0.01 0.1 s 0.1 0.0
s 0.01 0.00
s 0.1 0.5
-- 0
V 0.01 1.60
Hz 0.1 0.0
-- 0
-1 1
-- 0
s 0.1 2.0
-- 1
P11S:1
460V class : 470V
Remarks
When data code is set at "1", all function data is returned to initial data (factory setting data). Automatically returns to "0" after initializing.
Time required until motor residual voltage reduces to zero.
P11S series does not have this function. Gain for frequency setting is disabled.
When the acceleration time is longer than 60s, this function prevents inverter trip due to overvurrent, to accelerates motor in a shortest time.
E01-E09:20 C33 E01-E09:21
P11S does not have this function.
Selects type of LINK operation in LINK operation mode. F01:11, C30:11, E01-E09:24,25, F02
Chapter 1
2. Common Specifications
The function marked can be set while the inverter is running. Other functions must be set while the inverter is stopped.
Function Code Name LCD monitor unit 30HP 40HP
H35 (Data length) H35 LENGTH 0 : 8 bit 1 : 7 bit H36 (Parity check) H36 PARITY 0 : No checking
H37 (Stop bits) H37 STOP BITS 0 : 2 bit 1  : 1 bit H38 H39 (Response interval) H39 INTERVAL 0.00 to 1.00s
(No response error
detection time)
H38 NO RES t 0 (No detection), 1 to 60s
1: Even parity 2: Odd parity
Setting range Unit
Alternative Motor Parameters
Min. Factory setting
-- 0
-- 0
-- 0
s1 0
s 0.01 0.01
Remarks
1
Function Code Name LCD monitor unit 30HP 40HP
A01 Maximum frequency 2 A01 MAX Hz-2 G11S : 50 to 400Hz P11S : 50 to 120Hz
A02 Base frequency 2 A02 BASE Hz-2 G11S : 25 to 400Hz P11S : 25 to 120Hz A03 Rated voltage 2 A03 RATED V-2 0V (Free) : The output voltage in proporpion to the
80 to 240V : AVR active (230V) 320 to 480V : AVR active (460V)
A04 Maximum voltage 2 A04 MAX V-2 80 to 240V : AVR active (230V)
(at Maximum frequency 2) 320 to 480V : AVR active (460V)
A05 Torque boost 2 A05 TRQ BOOST2 0.0 : Automatic (for constant torque load)
A06 Electronic (Select) A06 ELCTRN OL2 0 : Inactive
thermal 1 : Active (for 4-pole standard motor) overload relay 2 : Active (for 4-pole inverter motor)
A07 for motor 2 (Level) A07 OL LEVEL2 Approx. 20 to 135% of the inverter rated current, in
A08 (Thermal time constant) A08 TIME CNST2 0.5 to 75.0 min A09 Torque vector control 2 A09 TRQVECTOR2 0 : Inactive
A10 Number of motor-2 poles A10 M2 POLES 2 to 14
A11 Motor 2 (Capacity) A11 M2-CAP 30HP or smaller : 0.01 to 45.00 kW
A12 (Rated current) A12 M2-Ir 0.00 to 2000 A
A13 (Tuning) A13 M2 TUN1 0 : Inactive
A14 (On-line Tuning) A14 M2 TUN2 0 : Inactive
A15 (No-load current) A15 M2-Io 0.00 to 2000 A
A16 (%R1 setting) A16 M2-%R1 0.00 to 50.00 %
A17 (%X setting) A17 M2-%X 0.00 to 50.00 %
(Slip compensation control 2)
A18
A18 SLIP COMP2 0.00 to +15.00 Hz
0.1 to 0.9 : Manual (for variable torque load)
1.0 to 1.9 : Manual (for proportional torque load)
2.0 to 20.0 : Manual (for constant torque load)
Ampere
1: Active
40HP or larger : 0.01 to 500.00 kW
1: Active (One time tuning of %R1 and %X (on
motor stopping mode ))
2: Active (One time tuning of %R1, %X and Io (on
motor running mode ))
1: Active (Real time tuning of %R1 and %X)
Setting range Unit
power supply voltage is set.(at Base frequency 2)
Min. Factory setting
Hz 1 60
Hz 1 60
V 1
220:(230V class) 380:(460V class)
V 1220:(230V class)
- 0.1 G11S : 2.0
-- 1
A 0.01 Motor rated
min 0.1 5.0 10.0
-- 0
- 24
kw 0.01 Motor Capacity
A 0.01 Motor rated
-- 0
-- 0
A 0.01 Fuji standard
% 0.01 Fuji standard
% 0.01 Fuji standard
Hz 0.01 0.00
380:(460V class)
P11S : 2.0
current
current
rated value
rated value
rated value
Remarks
Sets the maximum output frequency for motor 2.
Sets the output voltage at the Base frequency 2 "A02".
Sets the output voltage at the Maximum frequency 2 "A01".
Sets the number of poles of motor 2.
Set the applied motor capacity. This setting automatically sets "P03" and "P06" to "P08". Frame must be from -2 to +1. When a frame is outside this range, take a special note.
Sets the motor rated current.
Measure %R1 of motor, and %X and Io at base frequency. When "1" is selected, data is stored in "A16" and "A17". When "2" selected, data is stored in "A15" to "A17".
Data in "A16" and "A17" is not updated.
Sets exciting current at torque-vector control.
Sets motor primary coil resistance manually.
R1+Cable R
%R1= x 100
V/( 3 x I)
R1: Motor primary resistance [Ω] Cable R : Resistance at output side cable V : Rated voltage [V] I : Motor rated current [A]
Sets motor leakage inductance at base frequency manually.
%X= x 100
X1 : Motor primary leakage reactance [Ω] X2 : Motor secondary leakage reactance [Ω] XM : Excitation reactance [] Cable X : Cable resctance (Primary conversion value) [Ω] V : Rated voltage [V] I : Motor rated current [A]
Sets the slip frequency.
XM
X1+X2 x +Cable X
X2+XM
V/ ( 3 x I)
1-17
Chapter 1
2. Common Specifications
User Functions
Function Code Name LCD monitor unit 30HP 40HP
U01 Maximum compensation
frequency during braking torque limit
U02 1st S-shape level at
acceleration
U03 2nd S-shape level at
acceleration
U04 1st S-shape level at
deceleration
U05 2nd S-shape level at
deceleration
U08 Main DC link capacitor
U09 (Measured value) U10 PC board capacitor
powered on time
U11 Cooling fan operating
time
U13 Magnetize current
vibration damping gain
U15 Slip compensation filter
time constant
U23 Integral gain of
continuous operation at power failure
U24 Proportional gain of
continuous operation at power failure
U48 Input phase loss
protection
U49 RS-485 protocol
selection
U56 Speed agreement
U57 /PG error
U58 PG error selection U59 Braking-resistor
function select (up to 30HP) Manufacturer’s function (40HP or more)
U60 Regeneration
avoidance at deceleration
U61 Voltage detect offset
and gain adjustment
(Initial value)
(Detection width)
(Detection timer)
U01 USER 01 0 to 65535 - 1
U02 USER 02 1 to 50% % 1
U03 USER 03 1 to 50% % 1
U04 USER 04 1 to 50% % 1
U05 USER 05 1 to 50% % 1
U08 USER 08 0 to 65535 - 1
U09 USER 09 0 to 65535 - 1
U10 USER 10 0 to 65535h h 1
U11 USER 11 0 to 65535h h 1
U13 USER 13 0 to 32767 - 1
U15 USER 15 0 to 32767 - 1
U23 USER 23 0 to 65535 - 1
U24 USER 24 0 to 65535 - 1
U48 USER 48 0, 1, 2 - -
U49 USER 49 0, 1 - -
U56 USER 56 0 to 50% % 1
U57 USER 57 0.0 to 10.0s s 0.1
U58 USER 58 0, 1 - - U59 USER 59 00 to A8(HEX) - 1
U60 USER 60 0, 1 - -
U61 USER 61 Up to 30HP : F0(Fixed.) - -
40HP or more : F0, 1, 2
Setting range Unit
Min. Factory setting
75
10
10
10
10
xxxx
0 0
0
819 410
556 546
1738 1000
1024 1000
-75HP 100HP­0 1
0
10
0.5
1
00
0
0
Remarks
1-18
The information described in this document is for the purpose of selecting the
Caution
appropriate product only. Before actually using this product, be sure to read the Instruction Manual carefully to ensure proper operation.

3. Wiring Diagram

3.1 Wiring diagram before shipment from factory (1) 230V/460V FRENIC5000G11S: 1/4 to 1HP / 1/2, 1HP

Chapter 1
3. Wiring Diagram
Power supply ( *1) 3-phase 200 to 230V 50/60Hz
or 3-phase 400 to 480V 50/60Hz
Potentiometer power supply
Analog input
Analog output (analog monitor)
MCCB or
GFCI
(*2)
Grounding
Voltage input
Current input
MC
(*2)
Main circuit
Jumper wire (*3)
P1
L1/R
L2/S
L3/T
SR
73
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
+010Vdc
P(+)
+10Vdc
+24Vdc
DBR
0V
0V
DB
N(-)
30
U
V
W
( *4)
G
30C
30B
Alarm output (for any fault)
30A
NOTE: Common terminals [11], (CM), and <CME> for control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage matches the power supply voltage.
(*2) Use this peripheral device when necessary.
(*3) Terminals [P1] and [P(+)] are connected with a jumper wire before shipping.
(*4) Terminal for grounding the motor. Connect it, if necessary.
1
Motor
M
G
Digital input
Pulse output (frequency monitor)
(CM)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
RS-485
Pulse output
(DX-)
(DX+)
(SD)
Y5C
Y5A
Y4
Y3
Y2
Y1
CME
Relay output
Transistor output
1-19
Chapter 1
3. Wiring Diagram
The information described in this document is for the purpose of selecting the
Caution
(2) 230V/460V FRENIC5000G11S : 2 to 10HP
appropriate product only. Before actually using this product, be sure to read the Instruction Manual carefully to ensure proper operation.
FRENIC5000P11S : 7.5 to 15HP
Main circuit
Jumper wire (*3)
Power supply ( *1) 3-phase 200 to 230V 50/60Hz
or 3-phase 400 to 480V 50/60Hz
Potentiometer power supply
Analog input
Analog output (analog monitor)
Digital input
MCCB or
GFCI
(*2)
Auxiliary control power supply (*4)
Grounding
Voltage input
Current input
Pulse output (frequency monitor)
MC
(*2)
P1
L1/R
L2/S
L3/T
(R0) (T0)
SR
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
+0 10Vdc
Pulse output
P(+)
+10Vdc
+24Vdc
(DX-)
DBR
(*5)
0V
0V
(DX+)
DB
(SD)
N(-)
30
W
G
30C
30B
30A
Y5C
Y5A
Y4
Y3
Y2
Y1
CME
U
V
(*6)
Alarm output (for any fault)
NOTE: Common terminals [11], (CM), and <CME> for control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage matches the power supply voltage.
(*2) Use this peripheral device when necessary. (*3) Terminals [P1] and [P(+)] are connected
with a jumper wire before shipping.
(*4) Even if these terminals are not powered, the inverter can be operated.
(*5) The built-in braking resistor (DBR) is not mounted on P11S models 7.5HP to 15HP (*6) Terminal for grounding the motor. Connect it, if necessary.
Relay output
Transistor output
Motor
M
G
1-20
RS-485
The information described in this document is for the purpose of selecting the
Caution
appropriate product only. Before actually using this product, be sure to read the Instruction Manual carefully to ensure proper operation.
(3) 230V/460V FRENIC5000G11S : 15 to 30HP
FRENIC5000P11S : 20 to 30HP
Main circuit
Jumper wire (*3)
Chapter 1
3. Wiring Diagram
1
Power supply ( *1) 3-phase 200 to 230V 50/60Hz
or 3-phase 400 to 480V 50/60Hz
Analog input
Digital input
Auxiliary control power supply (*4)
Potentiometer power supply
Analog output (analog monitor)
MCCB or
GFCI
(*2)
Pulse output (frequency monitor)
MC
(*2)
Grounding
Voltage input
Current input
P1
L1/R
L2/S
L3/T
(R0) (T0)
SR
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
+010Vdc
Pulse output
(DX-)
+10Vdc
+24Vdc
0V
0V
(DX+)
P(+)
(SD)
N(-)
30
U
V
W
G
30C
30B
30A
Y5C
Y5A
Y4
Y3
Y2
Y1
CME
Motor
M
G
(*5)
Alarm output (for any fault)
NOTE: Common terminals [11], (CM), and <CME> for control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage matches the power supply voltage.
(*2) Use this peripheral device when necessary. (*3) Terminals [P1] and [P(+)] are connected
with a jumper wire before shipping. (*4) Even if these terminals are not powered,
the inverter can be operated. (*5) Terminal for grounding the motor.
Connect it, if necessary.
Relay output
Transistor output
RS-485
1-21
Chapter 1
3. Wiring Diagram
The information described in this document is for the purpose of selecting the
Caution
(4) 230V/460V FRENIC5000G11S : 40 to 75HP
appropriate product only. Before actually using this product, be sure to read the Instruction Manual carefully to ensure proper operation.
FRENIC5000P11S : 40 to 75HP
Main circuit
Jumper wire (*3)
Power supply ( *1) 3-phase 200 to 230V 50/60Hz
or 3-phase 400 to 480V 50/60Hz
Analog input
Digital input
Auxiliary control power supply (*4)
Potentiometer power supply
Analog output (analog monitor)
MCCB or
GFCI
(*2)
Pulse output (frequency monitor)
MC
(*2)
Grounding
Voltage input
Current input
P1
L1/R
L2/S
L3/T
(R0) (T0)
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
Pulse output
SR
73
+10Vdc
+010Vdc
+24Vdc
(DX-)
P(+)
CNUX () U1 U2
0V
0V
(DX+)
(SD)
N(-)
30
U
V
W
G
30C
30B
30A
Y5C
Y5A
Y4
Y3
Y2
Y1
CME
Motor
M
G
(*5)
Alarm output (for any fault)
NOTE: Common terminals [11], (CM), and <CME> for control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage matches the power supply voltage.
(*2) Use this peripheral device when necessary. (*3) Terminals [P1] and [P(+)] are connected
with a jumper wire before shipping.
(*4) Even if these terminals are not powered, the inverter can be operated.
(*5) Terminal for grounding the motor. Connect it, if necessary.
Relay output
Transistor output
()
400 to 440V/50Hz, 440 to 480V/60Hz 380V/50Hz (398V or smaller),
380 to 415V/60Hz (430V or smaller)
Input voltage
CNUX connector
U1
U2
1-22
RS-485
The information described in this document is for the purpose of selecting the
Caution
appropriate product only. Before actually using this product, be sure to read the Instruction Manual carefully to ensure proper operation.
(5) 2300V/460V FRENIC5000G11S : 100, 125HP / 100 to 600HP
FRENIC5000P11S : 100 to 150HP / 100 to 800HP
DC REACTOR (DCR) (*3)
Main circuit
MCCB
Power supply ( *1) 3-phase 200 to 230V 50/60Hz
or 3-phase 400 to 480V 50/60Hz
Auxiliary control power supply (*4)
or GFCI
(*2)
Grounding
MC
(*2)
L1/R
L2/S
L3/T
(R0) (T0)
N(-)
P1
SR
73
G
P(+)
CNUX (∗) U1 U2
Chapter 1
3. Wiring Diagram
1
U
V
W
(*5)
G
Motor
M
G
Analog input
Digital input
Potentiometer power supply
Voltage input
Current input
Analog output (analog monitor)
Pulse output (frequency monitor)
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X1)
(X9)
(CM)
(FMP)
+010Vdc
Pulse output
+10Vdc
+24Vdc
(DX-)
0V
0V
(DX+)
(SD)
30
30C
30B
30A
Y5C
Y5A
Y4
Y3
Y2
Y1
CME
Alarm output (for any fault)
NOTE: Common terminals [11], (CM), and <CME> for control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage matches the power supply voltage.
(*2) Use this peripheral device when necessary.
(*3) A DC REACTOR (DCR) is provided as standard in JE version for inverters of 100HP or larger (separately installed). Be sure to connect the DCR properly. (*4) Even if these terminals are not powered, the inverter can be operated.
(*5) Terminal for grounding the motor. Connect it, if necessary.
Relay output
Transistor output
()
400 to 440V/50Hz, 440 to 480V/60Hz 380V/50Hz (398V or smaller),
380 to 415V/60Hz (430V or smaller)
Input voltage
CNUX connector
U1
U2
RS-485
1-23
Chapter 1
3. Wiring Diagram
The information described in this document is for the purpose of selecting the
Caution

3.2 Basic wiring diagram (1) 230V/460V FRENIC5000G11S : 1/4 to 1HP / 1/2, 1HP

appropriate product only. Before actually using this product, be sure to read the Instruction Manual carefully to ensure proper operation.
Power supply ( *1) 3-phase 200 to 230V 50/60Hz
or 3-phase 400 to 480V 50/60Hz
It is possible to input voltage signals (0 to +10Vdc or 0 to +5Vdc) to terminals [12]-[11] instead of the potentiometer.
Analog input
Analog frequency meter
Potentiometer power supply (*2)
Voltage input
0 to 10Vdc
Current input
4 to 20mAdc
0 to 60Hz
FM (*2)
MCCB or
GFCI
(*3)
Grounding
3
2
1
(+) (–)
MC
(*3)
Main circuit
Jumper wire (*4)
P1
L1/R
L2/S
L3/T
G
Control circuit
[13]
[12]
[11]
[C1]
[FMA]
(PLC)
(FWD)
(REV)
(CM)
P(+)
SR
73
+10Vdc
+010Vdc.
+24Vdc
DBR
0V
0V
DB
N(-)
30
U
V
W
(*5)
G
30C
30B
Alarm output (for any fault)
30A
NOTE: Common terminals [11], (CM), and <CME> for control circuits are isolated from one another.
(*1) Use the inverter whose rated input voltage matches the power supply voltage.
(*2) Use this optional device when necessary.
(*3) Use this peripheral device when necessary.
(*4) Terminals [P1] and [P(+)] are connected with a jumper wire before shipping.
(*5) Terminal for grounding the motor. Connect it, if necessary.
Motor
M
G
1-24
Digital input
Digital frequency meter
(pulse counter) (*2)
60Hz
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(X8)
(X9)
(CM)
(FMP)
RS-485
Pulse output
(DX-)
(DX+)
(SD)
Y5C
Y5A
Y4
Y3
Y2
Y1
CME
Relay output
Transistor output
Loading...
+ 206 hidden pages