Fuji Electric FRC Service Manual

INSTRUCTION MANUAL
FRC
TEMPERATURE TRANSMITTER
(HART communication, intrinsically safe/flameproof)
POWER INPUT RATING

BEFORE USE ....

Thank you very much for your purchase of the Fuji FRC Transmitter. Before use, please check contents of the pack­age you received as outlined below. If you have any problems or questions with the product, please contact Fuji's Sales Office or representatives.
Transmitter .................................................................(1)
Short bar ..................................................................... (1)
Outdoor enclosure (FRC1) .......................................... (1)
Mounting screws (FRC1) ............................................(4)
2-inch pipe mounting bracket (FRC1) ................. (1) set
MODEL NO.
Check that model No. described on the specification label is exactly what you ordered.
SAFETY PRECAUTIONS
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures. Information that potentially raises safety issues is indicated by a warning symbol ( messages before performing an operation preceded by this symbol.
). Please refer to the following safety

POINTS OF CAUTION

The following are general precautions when using this unit. The safety features and precautions specific to the hazardous locations are explained in Page 10.
• Use a stable power source. The FRC restarts with a power interruption for longer than 1 millisecond.
ENVIRONMENT
• The model FRC0 is for indoor use.
• When heavy dust or metal particles are present in the air, install the unit inside an outdoor enclosure.
• Environmental (non-hazardous location) temperature must be within -40 to +85°C (-40 to 185°F) in order to ensure adequate life span and operation.
• For installing the FRC0 in an environment with a high relative humidity exceeding 0 to 95% RH or in a condensing atmosphere, install the unit inside an outdoor enclosure.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• For use in a hazardous location, be sure that the environ­mental temperature is within the temperature class required for the area.
WIRING
• Do not install cables (input and output) close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind the unit's cables together with cables where high noise levels are present. Do not install them in the same duct.
AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
MODEL
FRC

COMPONENT IDENTIFICATION

Figure 1. FRC0 exploded view and component identification
Transmitter Module
Mounting Screws (Not Included)
Screw
LCD Module
NEXT Key
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
ENTER Key
Sales Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo 191-8502, Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng
Specification Label
Safety Label
Terminal Cover
Lever
TNFRCA-EP. 1 / 8
Figure 2. FRC1 exploded view component identification
• Case Details
Cable Entry Conduit
Internal Earthing Screw
Fastener (ATEX flameproof)
External Earthing Screw
Transmitter Module
FRC
Specification Label
Case
Gasket
Cover
LCD Module
Terminal Cover
Screw
Screw
Lever
ENTER Key
NEXT Key
TNFRCA-EP. 2 / 8
EXTERNAL DIMENSIONS mm (inch)
Figure 3. FRC0 external dimensions
FRC
59 (2.32) dia.
33 (1.30)
3214
123
Without LCD Module
(Terminal Assignments)
4
+
2–5 (.197) dia. MTG HOLE
24.5 (.965) deep
LCD MODULE CONNECTOR
HHC TERMINAL
63 (2.48) max.
With LCD Module
48 (1.89)
34.5 (1.36)
24.5 (.96)
27.5 (1.08)
TNFRCA-EP. 3 / 8
Loading...