We thank you very much for purchasing Fuji’s ultrasonic flowmeter.
The instruction manual concerns the installation, operation, checkup and maintenance of the Flow transmitter (FLR) and
Detector (FLS) of ultrasonic flowmeter. Read it carefully before operation.
Before using, be sure to read this instruction manual carefully to ensure correct installation, operation and
z
maintenance of the flowmeter. Note that incorrect handling may lead to trouble or personal injury.
The specifications of this flowmeter are subject to change for improvement without prior notice.
z
Do not attempt to modify the flowmeter without permission. Fuji is not responsible for any trouble caused by
z
modification without permission. If it becomes necessary to modify the flowmeter, contact our office in
advance.
This instruction manual should always be kept on hand by the operator.
z
After reading, be sure to keep this manual in a place where it can easily be seen by the operator.
z
Make sure that this manual is presented to the end user.
z
If the instruction manual has been lost, request another one (with charge) to our local business office.
z
Manufacturer: Fuji Electric Instruments Co., Ltd.
Type: Shown on nameplate of Flowmeter
Date of manufacture: Shown on nameplate of Flowmeter
Product nationality: Japan
Fuji Electric Instruments Co.,Ltd. 2002
It is srictly prohibited to reproduce any part or the whole of this
z
instruction manual.
The contents of this manual may be changed without prior notice.
Before using, read the following safety precaution to ensure correct handling of the flowmeter.
●
The following items are important for safe operation and must be fully observed. These items are classified
into "DANGER" and "CAUTION".
Warning & Symbol Meaning
DANGER
CAUTION
●
The items noted under "
●
All the items are important and must be fully observed.
Incorrect handling may lead to a risk of death or heavy injury.
Incorrect handling may lead to a risk of medium or light injury, or to a risk of
physical damage.
CAUTION
" may also result in serious trouble depending on circumstances.
Caution on Installation and Piping
z
This product has not an explosion-proof structure. Do not use it in a place
with explosive gases, otherwise, it can result in serious accidents such as
DANGER
CAUTION
explosion, fire, etc.
z
The unit should be installed in a place conforming with the installation
requirements noted in this instruction manual. Installation in an improper
location may lead to a risk of electric shocks, fire, malfunction, etc.
z
The unit should be installed as noted in the manual. Improper installation
will cause falling, trouble or malfunction of the unit.
z
During installation, make sure that the inside of the unit is free from cable
chips and other foreign objects to prevent fire, trouble, malfunction, etc.
z
The items under "Caution on Installation" noted in the manual must be fully
observed; careless installation may result in trouble or malfunction of the
unit.
Caution on Wiring
z
When performing wiring termination to prevent output trouble caused by
CAUTION
moisture, dew condensation or water leak, follow “Section 3.3 Flow
transmitter wiring” described in this manual
z
Before performing the wiring work, be sure to turn OFF the main power to
prevent elect ric shocks.
z
Do not perform wiring work outdoors in rainy days to prevent insulation
deterioration and dew condensation; otherwise, it can result in trouble,
malfunction, etc.
z
Be sure to connect a power source of correct rating. Connection of a
power source of incorrect rating may lead to a risk of fire.
z
The unit must be earthed as specified to prevent electric shocks or
malfunction.
z
The analog output signal cable should be wired as far away as possible
from high-voltage lines to prevent entry of noise signals as it will cause
malfunction of the unit.
z
To prevent malfunction of the unit, the analog output signal cable and
power cable should be wired using separate conduits.
- ii -
INF-TN1FLRS-E
Caution on Maintenance/Inspection
z
The unit should be inspected everyday to always obtain good results of
CAUTION
measurements.
z
When measuring the insulation resistance between the power/output
terminal and the case, follow “Section 5.2.3 How to measure the
insulation resistance” described in this manual.
z
If the fuse is blown, detect and eliminate the cause , and then replace the
fuse with a spare. if there are no spares, replace the fuse with the one
specified in this manual (that must be prepared by customer). Use of a
fuse other than specified or its short-circuit may cause an electric shock or
fire. The fuse should be replaced according to “Section 5.3 How to
replace the fuse” described in this manual.
INF-TN1FLRS-E
- iii -
CAUTION ON INSTALLATION LOCATION
CAUTION
(1) Sufficient space for d aily inspection, wiring, etc.
(2) A place not exposed to direct sunshine nor weathering.
(3) Isolation from vibration, dust and moisture
(4) A place not subjected to radiated heat from a heating furnace etc.
(5) A place not subjected to corrosi ve atmosphere
(6) A place not to be subm erged
(7) A place remote from electrical devices (motor, transformer, etc.) which generate electromagnetic
induction noise, electrostatic noise, etc.
(8) A place not subjected to excessive fluid pulsation (pump discharge side)
(9) A place that provides enough place for the length of the straight pipe.
(10) A place whe re ambient temperature and humidity are -20 to +50°C and 90% RH or less for flow
transmitter (FLR), and -20 to +60°C and 90% RH or less for detector (FLS).
- iv -
INF-TN1FLRS-E
CONTENTS
PREFACE ·········································································································································· i
SAFETY PRECAUTION ················································································································· ii
CAUTION ON INSTALLATION LOCATION··············································································· iv
6.4. Scope of delivery ··················································································································98
6.5. Items to be specified at order ································································································98
6.6. Piping data ····························································································································99
INF-TN1FLRS-E
-vii-
1. OUTLINE OF PRODUCT
1.1. Outline
This instrument is a clamp-on ultrasonic flowmeter which carries out measurements according to the transit time method.
Compact and lightweight design and easy handling have been drastically pursued, and building in machines and equipment
is facilitated. This excellent cost performance flowmeter is usable for small to medium piping size of 25 to 225 mm.
1.1.1. Measuring principle
Measuring principle
Ultrasonic pulses are propagated aslant from the upstream and downstream sides, and the time difference caused by the
flow is detected to measure the flow rate.
Detector
Upstream sensor
θ
Flow velocity
Downstream sensor
t
2
t
1
D
Flow
transmitter
Output signal
Mounting the detector
Configuration diagram
Ultrasonic transducerPipe
Plastic wedge
Lining
(1) Single-path system (V method)
Special signal cable
(2) When synchronizing
INF-TN1FLRS-E
Detector
Detector
Detector
Special signal cable
Synchronizing
signal wiring
Special signal cable
Flow
transmitter
Power supply
Power supply
Flow
transmitter
(master)
Flow
transmitter
(slave)
Power supply
4 to 20mA DC
Contact
4 to 20mA DC
Contact
4 to 20mA DC
Contact
-1-
1.2. Checking the received products
Flow transmitter (FLR)
•
Flow transmitter unit ·····································································1 set
Waterproof gland···········································································1 set (mounted on main unit)
Wall mounting fixture····································································1 set (mounted on main unit)
Pipe mounting fixture (option) ······················································1 set
(U bolt, support fixture, 2 wing nuts, 2 spring washers, 2 plain washers)
Detector (FLS)
•
Frame····························································································1 pc
Sensor unit ····················································································1 set (2 pcs)
Stainless steel belt ·········································································1 set (FLSE12: 2 pcs. FLSE22: 4 pcs.)
Spring fixture ················································································2 pcs
Silicone rubber or silicone-free compound (option)·······················1 pc
Signal cable (FLY: length designated) ············································1 set (2 pcs)
Belt tightening tool (option)···························································As ordered
•
Flow transmitter (FLR)
Wall mounting fixture
Flow transmitter
unit
Detector (FLS)
Frame for middle size
(FLSE22)
Frame for small size
(FLSE12)
Sensor unit
Waterproof gland
Pipe mounting fixture (option)
U bolt
Support fixture
Plain washer
Spring washer
Wing nut
Signal cable (FLY)
Spring fixture
Stainless steel belt
Silicone rubber
(option)
Silicone-free
grease
(option)
- 2 -
INF-TN1FLRS-E
1.3. Checking the type and specifications
The type and specifications of product are indicated on the specifications plate mounted on the flow transmitter and
detector frame. Make sure the types are as ordered referring to the type diagrams given below.
<Flow transmitter>
12345678 91011
2
3
4
Y
A
B
C
11Y
Y
A
1
1
A
B
Type (4th digit)
Standard for exports
Power Supply (5th digit)
100 to 120Vac, 50/60Hz
200 to 240Vac, 50/60Hz
20 to 30V DC
small
3 Indication and setting unit Indicates and sets the flow rate, etc.
4 Received wave diagnostic
Indicates whether received wave is normal (green) or abnormal (red).
indication
5 Escape key Return to the next-higher layer or cancels the set status.
6 UP key Selects items, numeric values and symbols.
7 Shift key Moves the cursor and selects decimal place.
8 Entry key Enters a selection or registers a setting.
9 LCD indication Indicates the flow rate or setting.
10 Power terminals Power cable are connected.
11 Input/output terminals Special signal cable, analog output and DO output cables are connected.
12 Communication board
Communication cable is connected (communication board is optional).
terminals
13 Fuse holder Houses a fuse.
14 Relay For DO2 output
15 Communication board Mounted if communication synchronization is optionally designated.
16 Arrester board Board for output mounted if arrester is optionally designated.
17 Frame Fastens the sensor unit on pipe.
18 Sensor unit Sends and receives an ultrasonic wave.
19 Stainless steel belt Fastens the frame on pipe.
20 Spring fixture Removes the play of stainless steel belt.
21 Scale For reading the sensor mounting spacing
22 Fastening hole For positioning and fastening the sensor units
23 Special signal cable Transmits send/receive signals.
11
10
INF-TN1FLRS-E
-5-
2. SELECTION OF INSTALLATION PLACE
Select an installation place taking into account the following matters from the viewpoint of easiness of maintenance and
checkup, instrument life and securing the reliability.
(1) A place where ambient temperature and humidity are -20 to +50°C and 90% RH or less for flow
transmitter (FLR), and -20 to +60°C and 90% RH or less for detector (FLS).
(2) A place not exposed to direct sunshine nor weathering.
(3) Sufficient space for daily inspection, wiring, etc.
(4) A place not subjected to radiated heat from a heating furnace, etc.
(5) A place not subjected to corrosive atmosphere.
(6) A place not to be submerged.
(7) A place free from excessive vibration, dust, dirt and moisture.
2.1. Flow transmitter
CAUTION
Secure at least 100 mm of space between the flow
transmitter and nearby wall. Also secure a space
of opening the front cover for maintenance.
Secure a cable wiring space under the case.
N
E
P
O
133100133
370 min.
Top view of mounting
min.
- 6 -
INF-TN1FLRS-E
2.2. Detector
The measuring accuracy is considerably affected by the detector mounting place, i.e., status of piping for measuring a flow
rate. Select a place which clears the condition in section 2.2.1. (Length of straight pipe). Also, sufficiently secure a
space for installation and maintenance referring to the following diagram.
2000min.
Note
200min.200min.
D + 1200 min.600min.D600min.
D: Pipe diameter
Necessary space for detector mounting place
INF-TN1FLRS-E
-7-
2.2.1. Length of straight pipe
The length of upstream and downstream straight pipe of the ultrasonic detector should be long enough to ensure accurate
measurements.
(D: Nominal diameter of pipe)
NameStraight length of upstream pipingStraight length of downstream piping
L≥5D
L≥10D
90° bend
Tee
Diffuser
Reducer
10D min.
0.5D min.
10D min.
10D min.
1.5D min.
Detector
L≥50D
L≥30D
D
L≥10D
L≥10D
L≥5D
L≥5D
Valve
Pump
Note: Quoted from JEMIS-032
L≥30D
Flow controlled upstream
Check valve
Stop valve
P
L≥10D
Flow controlled downstream
L≥50D
- 8 -
INF-TN1FLRS-E
2.2.2. Mounting posture
The detector can be installed vertical, horizontal or at any posture provided that attention is paid to the following things.
(1) The piping must completely be filled with fluid when it flows.
Air tends to accumulate.
May not
completely be
filled with liquid.
May not completely be filled with liquid.
Good
Pump
Good
(2) In case of horizontal piping, mount the detector within ±45° from the horizontal plane. Otherwise, the measurement
could be impossible if bubbles stay in the upper part of piping or if deposits are accumulated in the lower part of
piping. In case of vertical piping, the detector may be mounted at any position on its periphery provided that the
flow is upward.
Pipe
45°
Horizontal
45°
(3) Do not mount the detector on a distorted part, flange or welding.
Weldment
Weldment
INF-TN1FLRS-E
Welding is included.
Welding is partly involved.Avoid Welding.
Off the Welding.
-9-
3. INSTALLATION AND PROCEDURE PRIOR
TO RUNNING
3.1. Outline of installation procedure
(1) Select the flow transmitter and detector installation places.
(2) Install and wire the flow transmitter.
(3) Turn on power.
(4) Set the piping parameters, and calculate the sensor unit spacing (* if with parameter setting, check the sensor unit
spacing).
(5) Mount the frame on the piping to measure on.
(6) Mount the sensor unit.
(7) Set the measurement range (* unnecessary if with parameter setting and if measurement range is designated).
(8) Adjust zero point.
(9) Start a measurement.
- 10 -
INF-TN1FLRS-E
3.2. Installation of flow transmitter
The flow transmitter may be mounted on a wall or 2B pipe stand (option).
3.2.1. Wall mounting
For wall mounting, use two M8 bolts.
According to the mounting hole dimensions shown below, drill holes on the wall, and tighten M8 bolts.
Mounting
plate
130
70
Mounting hole 2-φ9
170
140
(197)
3.2.2. 2B pipe stand mounting
CAUTION
When mounting on 2B pipe, be sure to use a complete set of fixtures (U bolt, support fixture, plain washer,
spring washer, wing nut) furnished if optionally designated. Tighten the wing nut by hand. If any support
fixture is not used or if the altogether is excessively tightened by tool, the wall mounting fixture may be
deformed, thereby breaking the resin case.
Mount the instrument on 2B pipe stand as illustrated below.
2B pipe stand
U bolt
Support fixture
Plain washer
Spring washer
INF-TN1FLRS-E
Wing nut
-11-
3.3. Flow transmitter wiring
3.3.1. Precautions in wiring
CAUTION
(1) Use a special coaxial cable (FLY3) as a signal cable between the detector (FLS) and flow transmitter
(FLR). Do not provide a junction of the signal cable midway.
(2) Be sure to pass the signal cables through a metal conduit between the detector and flow transmitter.
Upstream and downstream signal cables may be put in the same conduit but, to avoid an interference, do
not put the power cable together.
(3) For output signal, use a shield cable, where possible.
(4) To avoid ingress of noise, do not put the cables together with heavy duty line or the like into the same
duct.
(5) If a ground wire is included in the power cable, connect it to ground as it is.
(6) A power switch is not provided on the instrument and must be mounted separately.
(7) Hermetically cover unused wiring ports by furnished caps.
3.3.2. Applied wiring
Use the following cables.
Power cable : 3 or 2 core cabtyre cable.
z
Nominal cross-sectional area 0.75 mm
Finish outer diameter ∅11 mm.
Output signal cable : 2 or, as required, multiple core cabtyre cable.
z
Finish outer diameter ∅11 mm.
Detector-flow transmitter cable : Special signal cable by type designation (heat-resisting high-frequency coaxial cable
z
having 50 Ω of characteristics impedance, provided on a side with waterproof BNC
connector).
Finish outer diameter ∅5 mm.
2
min.
3.3.3. Treatment of wiring ports
The outer case of flow transmitter is waterproof (IP65). However, if installed in a humid place, the wiring ports must be
made airtight to avoid ingress of moisture, condensation, etc. Be sure to use the waterproof glands furnished with the
instrument in order to ensure the waterproof means. Hermetically seal unused glands by furnished caps.
CAUTION
Do not install the instrument where there is a risk of inundation.
- 12 -
INF-TN1FLRS-E
3.3.4. Wiring to each terminal
Refer to the following diagram for carrying out wiring.
Communication board terminal block (option)
RS-232C
NC
GNDRXDTXD
RS-485 and synchronization
SYNC
SHILD TXDR2 TXDR1
Power cable
Output signal cable
(analog output, DO1, DO2,
communication synchronization)
Downstream
sensor cable
Power board terminal block
AC power source: 100 to 120 or 200 to 240 V AC,
50/60 Hz
LN
GNDGND
Upstream
sensor cable
Main board terminal block
Iout(+) DO1(+) DO2(+)GNDHF1
Iout(-) DO1(-) DO2(-)GNDHF2
Upstream sensor
Downstream sensor
Synchronization
RS-485
External ground terminal
Ground terminal
Red (upstream sensor)
DC power source: 20 to 30V DC
+−
GNDGND
Black (downstream sensor)
Special signal cable (FLY3)
Iout : Analog output
DO1: Transistor open collector
DO2: Relay contact
Notes
1. All screws are M3 on the terminal block. Use crimp-style terminals for M3 and whose outer diameter is ∅5.8 or
smaller.
2. Be sure to connect to ground the power board terminal block or external ground terminal (class D ground).
3. For output signal, use multiple core cable as required.
INF-TN1FLRS-E
-13-
3.4. Setting the piping parameters and calculating the
sensor unit spacing
After installation and wiring of the flow transmitter (sensor unit may not be wired), turn on power, input the piping
parameters below, and calculate the sensor unit installation spacing. (*When it is provided with parameter setting, the
following parameters have already been input. Check the installation spacing in this case.)
Item Input
method
Pipe outer diameter Value 10 to 300mm
Pipe material Menu PVC, PVDF, PEEK, PP, CARBON STEEL, STAINLESS STEEL, COPEER,
PIPE S.V (Note 1)
Pipe wall thickness Value 0.1 to 100mm
Lining presence and
material selection
Lining thickness Value 0.1 to 10mm
Fluid type Selection Water, sea water, FLUID S.V (Note 1)
Kinematic viscosity Value 0.00E-6m2/s to 999.999E-6m2/s (Note 1)
Note 1: In case of material or fluid not included in menus, input its sound velocity and kinematic viscosity of the
fluid. The sound velocity can be inputted within the range of 1000 to 3700 m/s for piping or lining
material, or 500 to 2500m/s for fluid. (Refer to section 6.6.)
The operating procedure is as follows (from measurement mode).
Note 2: If the parameter protection is set at "PROTECTION ON", change it to "PROTECTION OFF". If ID NO.
is set at this time, ID NO. must be inputted.
Keying
key pressed 3 times.
Menu NO LINING, TAR EPOXY, MORTAR, RUBER, TEFLON, PYREXGLASS,
Select the pipe material from menus. If there is no corresponding menu, input the
sound velocity of pipe material on sound velocity input screen whose menu is located
at the last. As necessary, see piping data in section 6.6.
Registered after [**COMPLETE**] is indicated about 1 second on 2nd line.
If pipe is not lined, press key to go to selection of next fluid to be measured.
Cursor blinks on 2nd line.
Select the lining material from menus. If there is no corresponding menu, input the
sound velocity of lining material on sound velocity input screen whose menu is located
at the last. As necessary, see lining data in section 6.6.
Registered after [**COMPLETE**] is indicated about 1 second on 2nd line.
1st line: [LINING THICKNESS]. 2nd line: [2.00 mm]. * As selected currently.
Note: Not indicated if lining material is set at [NO LINING].
Cursor blinks on 2nd line.
Input the lining thickness.
: Selects a numeric. : Shifts the place.
Registered after [**COMPLETE**] is indicated about 1 second on 2nd line.
1st line: [KIND OF FULID]. 2nd line: [WATER]. * As selected currently.
Cursor blinks on 2nd line.
Select [WATER] or [SEA WATER]. In case of other fluid, input the sound velocity of
fluid on sound velocity input screen whose menu is located at the last. As necessary,
see piping data in section 6.6.
Registered after [**COMPLETE**] is indicated about 1 second on 2nd line.
key pressed.
ENT
key pressed.
ENT
ENT
ENT
ESC
ESC
and
key pressed to enter.
key pressed twice.
key pressed.
key pressed.
key pressed to enter.
key pressed.
key pressed.
key pressed twice.
key pressed.
1st line: [KINEMATIC VISCO]. 2nd line: [1.0038E-6m2/s]. * As selected
currently. Kinematic viscosity of water is factory set. If fluid to be measured is
other than water, input the kinematic viscosity referring to piping data in section 6.6.
Cursor blinks on 2nd line.
Input the kinematic viscosity.
: Selects a numeric. : Shifts the place.
Registered after [**COMPLETE**] is indicated about 1 second on 2nd line.
Mount the frame carefully not to cut your fingers with stainless steel belt.
z
(1) Pass the spring fixture on the stainless steel belt as
shown in Fig. 3-2.
Spring fixtureStainless steel belt
Fig. 3-2
(2) Pass the stainless steel belt through 2 belt holes on
the frame as shown in Fig. 3-3.
Frame
Fig. 3-3
- 16 -
INF-TN1FLRS-E
(3) Make sure the obtained status is as shown in Fig. 3-4.
Fig. 3-4
(4) As shown in Fig. 3-5, apply the frame on the pipe
section subjected to a surface treatment.
(6) Adjust the frame so as to be in parallel with the pipe,
put the spring fixture to the side of the frame as
shown in Fig. 3-7, and tighten the stainless steel belt
so that the frame will tightly be fitted.
Second
stainless
steel belt
Spring fixture
Fig. 3-7
(7) After tightening both stainless steel belts, slide the
spring fixture to the opposite to the frame as shown in
Fig. 3-8.
Fig. 3-5
(5) Temporarily tighten the first stainless steel belt on the
pipe as shown in Fig. 3-6.
Spring fixture
Fig. 3-8
Note: When removing the frame set to the piping and
set it to a different position, use new stainless
steel belts.
INF-TN1FLRS-E
Fig. 3-6
-17-
Mounting on pipe whose diameter is 150A or larger
As shown in Fig. 3-9, connect 2 stainless steel belts.
First steel beltSecond steel belt
Fig. 3-9
Tightening tool
Use of an optional tool (Fig. 3-10) facilitates tightening
the stainless steel belt (Fig. 3-11).
Fig. 3-10
Fig. 3-11
- 18 -
INF-TN1FLRS-E
A
3.5.4. How to mount the sensor unit
(1) Mount both sensor units spaced at the SPACING value [S= **] (number of graduations on frame) indicated after
setting the piping parameters.
Mounting size (SPACING)
Pressing fixture
Frame
Fig. 3-12
(2) Before mounting the sensor unit into the frame, sufficiently
apply silicone filler (or silicone-free grease
entire transmission surface of the sensor unit, taking care not
to introduce bubbles (Fig. 3-13).
Note) When using silicon-free grease, pay attention to the
fluid temperature range. The fluid temperature range
is shown below.
Silicon rubber: −20 to 100°C
Silicon-free grease: 0 to 60°C
When using silicon-free grease, reapply it on the
transmission surface of the sensor unit approximately
once every 6 months. (Silicon rubber need not be
reapplied.)
(3) Then insert the sensor unit into the frame, align the slit
provided on the pressing fixture of the sensor unit with
graduations located on the frame top surface (see Fig. 3-14),
and press the sensor unit until the fixture claws are engaged
with the frame side square holes. Mount both sensor units
so as to be roughly symmetrical with respect to the frame
(see Fig. 3-15).
Graduations
Slit
Note
) over the
Fig. 3-13
Pressing fixture
INF-TN1FLRS-E
Position of the slit and the graduation
(Magnified view of section A)
Fig. 3-14
Fig. 3-15
-19-
CAUTION
Mount the sensor units so that their BNC connectors will face outward (Fig. 3-16a). If at least one is
mounted opposite, the measurement is impossible (Fig. 3-16b, c). The pressing fixture claws must
completely be engaged with square holes provided on sides of the frame. Otherwise, the sensor and pipe will
not correctly get in contact with each other, whereby the measurement will be impossible.
BNC connector (must face outward)
Mount the BNC connectors of sensor units
so as to face outward
Fig. 3-16 a
Do not mount the BNC connectors of sensor units
in the same direction
Fig. 3-16 b
Do not mount the BNC connectors of sensor units
so as to face inward
Fig. 3-16c
Fig. 3-16
(4) Engage the signal line with BNC connectors of the sensor units. At this time, do not mistake the upstream and
downstream sides for each other. Engage the red BNC connector upstream, and the black BNC connector
downstream (see Fig. 3-17).
RedBlack
- 20 -
Upstream
Downstream
Fig. 3-17
INF-TN1FLRS-E
(5) After connecting the signal line, make sure the red LED on the flow transmitter has turned green. It takes about
10 seconds until the color changes to green.
The green color indicates the received signal is normal. The red color indicates the received signal is abnormal. If
the LED remains red and does not turn green, examine the sensor installation status (sensor spacing, sensor
orientation, claw engagement, etc.) and parameter settings, and check whether the piping is filled with fluid.
LED (red " green)
Fig. 3-18
INF-TN1FLRS-E
-21-
3.5.5. How to remove the sensor unit
If the sensor unit has to be detached from the frame such as after mistaking the space between the sensor units, proceed as
follows.
(1) Loosen the wind bolt located at the middle of frame
by 3 to 4 turns (Fig. 3-19).
Note 1: Do not loosen the wing bolt completely.
(3) Likewise, disengage the opposite claws of the sensor
unit pressing fixture from the frame (Fig. 3-21).
Wing bolt
Fig. 3-19
(2) By hand, hold the frame near the pressing fixture for
a sensor unit to remove.
Press the resin section which stands out of the frame
of sensor unit just enough to open the frame a little
(about 1 mm). At this time, the claws of sensor unit
fixture are disengaged from the frame (Fig. 3-20).
Note 2: Do not open the frame excessively. Otherwise,
it may deform, and an accurate measurement
could be impossible or the sensor unit could
not be installed.
Fig. 3-21
(4) Making sure claws have been disengaged from both
sides, and pull out the sensor unit from the frame (Fig.
3-22).
- 22 -
Fig. 3-20
(5) In the same procedure, remove the other sensor unit
also.
Note 3: After removing both sensor units, tighten the
loosened wing bolt as before.
Fig. 3-22
INF-TN1FLRS-E
Loading...
+ 83 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.