Frymaster M3000 User Manual

LOV
FRYER Generation II
TECHNICAL REFERENCE MANUAL
Introducing the LOV™ Fryer 1
FRYER Generation II
LOV
FEB 2010
The LOV M3000 12 RTI-equipped Systems 31 Board Replacement 38 Wiring Diagrams 41 Pin Positions 44
Frymaster and Dean Technical Service
TECHNICAL REFERENCE MANUAL
8700 Line Ave, Shreveport, LA 71106 Service Hotline: 800-551-8633 Website: www.frymaster.com
Systems 2
*8196506*
LOV™ Generation II Technical Reference
M3000 Computer
Replace JIB Light
Diagnostic LED Screen
Filter Light
JIB (behind right door)
The LOV™ fryer.
Introducing the Low Oil Volume Fryer
The Low Oil Volume (LOV™) fryer is a McDonald’s-only, feature-laden version of the electric RE
fryer or gas H55 fryer. The enhancements found on the LOV
Low volume frypot — 30 pounds (15 liters) rather than 50 pounds (25 liters) of oil.
Automatic top-off — the fryer automatically maintains an optimal oil level with a reservoir in the cabinet.
M3000 computer — a sophisticated controller with multiple levels of programming.
Automatic ltration — the fryer performs hands-free fi ltering at prescribed cook cycle counts or at prescribed times.
fryer include:
Oil savings — The combination of a low-volume fry vat and oil automatically kept at a optimal level, reducing oil usage.
1
LOV™ Generation II Technical Reference
ATO Sensor
AIF Sensor
Temperature RTD
Oil Return Sensor
Ports and sensors inside a gas frypot. Oil return/ top off is at bottom rear of cool zone.
High limit
The LOV™ Systems
Auto Top Off
The core of the system is the automatic top-off board, which senses when the oil level is low and lls the pot to the top line.
The oil level is monitored by an R TD (Resistance Temperature Detector) sensor in the frypot at the upper oil level. The oil is moved to the pot from a reservoir, called a JIB (Jug In Box), to the frypot with a pump.
A circuit board, the AT O (Automatic Top Off), is located inside a box behind the JIB. It monitors the oil-level R TD and activates the pump when it senses an oil temperature drop of 60°F (33°C) below set­point, indicating the oil has moved away from the sensor. The AT O sends a signal to the MIB (Manual Interface Board), which then sends a signal to the AIF to open the actuator on the return valve of the frypot to be topped off.
Once the actuator has opened the return valve, oil is pumped into the vat for a specifi ed amount of time (approximately 60 seconds). When the ATO RTD detects a temperature within 55°F (30°C) of set­point, it is satisfi ed and the actuator closes the valve.
ATO Sensor
High limit
AIF Sensor
Oil Return/Top Off Slots
Ports and sensors inside an electric frypot.
T op of f will continue on the next vat if needed. The system is not suited to fi lling the frypot when it is empty and there are safeguards to prevent it from activating when the fryer is cold and the oil is rest­ing at the lower position.
The system is not active until the oil in the frypot reaches setpoint. That temperature is monitored by the temperature probe. The activation of the system is handled by the fryer’s computer , the M3000. The automatic top off system is also inactive during lter dispose cycles.
The system works the same in McDonald’s gas and electric LOV
The level of the reservoir, or JIB, is monitored by the ATO and the M3000 computer. If a low oil condition is not rectifi ed with two top off attempts or within 6 minutes, the low JIB light is illuminated on the front of the fryer. It will stay illuminated until the JIB is replaced and the orange button has been pressed and held to reset the light (see page 34).
systems.
Oil Defl ector
The ATO board positioned underneath the LON gateway controls the top off of the fry pots.
The pump that moves oil from the reser­voir to the frypots is visible above.
2
LOV™ Generation II Technical Reference
ATO Board
The reservoir, or JIB, rests behind the right door of the fryer. A light on the front of the fryer illuminates when the jug is empty.
The ATO board is positioned under the LON gateway in a box with a transformer that provides power to the board. The LON gateway must be removed to access the ATO board.
Troubleshooting the Top Off System
Problem Probable Causes Corrective Action
Frypot tops off cold. Incorrect setpoint. Ensure setpoint is correct.
A. J5 connection unplugged.
No power to ATO board.
B. Fuse blown.
C. Transformer malfunction.
Transformer
A. Check to ensure J5 on front of
ATO board is fully locked into connector.
B. Ensure fuse below right control
box is not blown.
C. Check that proper voltage is
present at transformer. See charts on pages 43-47.
The yellow JIB low light
won’t illuminate.
A. Loose wire connection.
B. Power in the component box is not
present.
C. Failed transformer.
3
A. Ensure the yellow LED is
securely attached to plug J6 on the ATO board.
B. Ensure power is present in the
component box.
C. If power is present in component
box, check the transformer for correct voltage.
LOV™ Generation II Technical Reference
change filter pad YES/ NO
Problem Probable Causes Corrective Action
A. Check to see that fryer is heating.
Fryer temperature must be at setpoint. Check ATO probe resistance. If probe is bad, replace the probe.
B. Ensure that the oil in the JIB is
above 70°F (21°C).
C. With the computer OFF, press
TEMP button and ensure the
ATO version appears. If not, the connection between the AIF and the ATO board may be bad. Ensure the 6-pin CAN connectors are tight between AIF (J4 and J5) and ATO (J10) boards.
D. Power to the ATO board has been
cut off. Restore power to the board and clear any service required errors.
E. Ensure transformer in ATO box is
functioning properly. Check power from transformer to ATO board. Ensure all harnesses are plugged securely into place.
F. Ensure pump is operational.
Check voltage to pump. Replace the pump if defective.
G. Check for proper voltages using the
pin position charts found on pages 43-47. If ATO found defective, replace ATO board and clear any errors.
Frypots won’t top off.
A. Probe temperature lower than
setpoint.
B. Oil is too cold.
C. Bad Connection.
D. ATO board power loss.
E. Failed transformer/harness.
F. ATO pump failed.
G. Failed ATO board.
One vat tops off but other
vats fail to top off.
Incorrect vat tops off.
One vat doesn’t top off.
A. Loose wire connection.
B. Actuator issue.
A. Wired incorrectly.
B. Flexlines connected to wrong vat.
A. Filter error exists.
B. Actuator, pump, loose connection,
RTD or ATO issue.
4
A. Ensure all wiring harnesses are
securely connected to ATO board and solenoids.
B. Check return actuator to ensure
actuator is functional.
A. Check wiring. B. Switch fl exlines to correct vat.
A. Clear fi lter error properly. When
change filter pad YES/ NO is displayed, do NOT press
any button until the pan has been removed for at least thirty seconds. After thirty seconds have elapsed, the computer returns to OFF or last display.
B. Check actuator, ATO pump, wire
connections, RTD and ATO board.
LOV™ Generation II Technical Reference
Auto Filtration (MIB and AIF)
The auto fi ltration system is controlled by the M3000 computer, the AIF (Automatic Intermittent
Filtration) board and the MIB (Manual Interface Board). The ltration is made hands-off by
actuators operating the drain and return valves.
The computer is programmable, and it allows fi lter cycles to be launched after a set number of cook cycles and a prescribed elapsed time.
The system can be set to lock out automatic ltration during busy times, such as the lunch rush.
The fryer prompts for fi ltration by illuminating a blue LED on the front and a text prompt on the computer. The operator can say no; cooking can continue.
An AIF board is mounted under each fry vat.
Responding “yes” leads to communication between the MIB and the AIF boards. The MIB controls and oversees the fi ltration; the AIF board operates the actuators, which open and close the valves.
The MIB is in the fryer cabinet. It is partially covered by a sheet metal cover and the LED display is visible. Buttons behind the cover allow limited manual operation of the system and its valves. The cover should be reinstalled after service.
The LED displays codes that can be used to diagnose failures (see chart on page 45).
(1) Responding to the Blue LED fi lter prompt with “yes” starts a fi lter cycle that lasts about as long as a cook cycle (approx. 4 minutes). Communication between the M3000 computer, the manual interface (MIB board), and the automatic intermittent fi ltration (AIF board) handle the process.
(2) Actuators open and close the drain valve and return valve, (3) emptying and refi lling the frypot.
1
2
3
5
LOV™ Generation II Technical Reference
Mode Display
Shows status (auto or manual) vat number (when operating valves manuals) and dis­plays error codes.
Vat Selection
Selects vat for manual operation of valves.
Manual/Auto
Switches fryer from auto to manual operation.
The MIB board.
Reset
Resets system, ensures all valves are closed.
Drain
Opens and closes drain valves in manual mode.
Return
Opens and closes return valves and turns on fi lter pump in manual mode.
Manual — Used to toggle between automatic and manual fi ltration mode. The unit must be
in manual mode for the other MIB buttons to operate.
Select — Used to scroll through the vats,
which are shown numerically in the LED.
Drain — Used to open and close the drain valve of the vat indicated on the display. When pressed an LED on the button indicates activity: slow blink, awaiting response from AIF; LED illuminated constantly, drain open; no illumination, drain closed.
Return — Used to open and close the return valve on the vat indicated on the display. It also controls the pump. When pressed an LED on the button indicates activity:
blink: awaiting response from AIF,
• LED illuminated constantly: drain open,
• no illumination: drain closed.
The MIB is mounted behind the left door. See arrow.
The pump operates with a momentary switch. Pressing and holding the return button after the valve is open activates the fi lter pump. Releasing the button deactivates the pump.
The mode display on the face of the MIB board displays a range of letters, which indicate activity or an error. These codes are listed on
the next page.
6
2
1
3
Error Codes
LOV™ Generation II Technical Reference
1L, 1r - 5L, 5r — Numbers correspond to vats: “L” indicates the left side of a split vat. “r”
indicates a full vat or the right side of a split vat.
A — Auto mode: auto ltration enabled.
E — Drain or return valve not in desired state: display alternates between E and vat
number. (Ensure actuator is plugged in and in the home position.)
n — Network Error: An “n” displays for 10 seconds if no communication is received from the cooking computer within ten seconds after a power on.
Manual Draining, Filling, Filtering with MIB
P — Pan switch: fi lter pan is not in place or not
sensed. Auto Filtration disabled.
r — Reset: r alternating with a vat number indicates that the MIB board is resetting. If r is displayed without alternating with a vat number, a problem may exist with the MIB board itself.
Three horizontal lines — temperature sensor: sensor did not detect that the vat
was full during auto fi ltration.
1
Press the M button, which switches the board to manual. The display becomes
1. the number of the vat to be controlled manually.
Press the vat selector button until the desired vat number is displayed.
2. Press the drain button to drain the oil or the press and hold the return button to
3. return oil to the vat displayed. Opening the drain and pressing and holding the return button after valve is open allows fi ltration.
Pressing the M button again returns the board to automatic mode.
4.
2
7
3
LOV™ Generation II Technical Reference
Troubleshooting the Manual Interface Board (MIB)
Problem Probable Cause Corrective Action
Filter pan out of position.
Auto fi ltration won’t start.
1. Oil Level is too low.
2. Ensure MIB board is not in
3. manual mode. Ensure MIB cover is not
4. damaged and pressing against buttons. Filter relay has failed.
5. AIF disable is set to YES,
6. blue light doesn’t light. Filter motor thermal switch
7. is tripped. AIF clock enabled.
8.
Ensure fi lter pan is fully inserted into fryer.
1. Ensure oil level is above the oil level sen-
2. sor. Ensure MIB board is in “A” automatic
3. mode. Remove and replace cover and see if fi ltra-
4. tion will start. Replace fi lter relay with part number 807-
5. 4482 24VDC relay. Set AIF disable in Level 1 to NO.
6. Press fi lter motor thermal switch.
7. Ensure AIF clock is set to disabled.
8.
MIB display shows something other than an “A” or vat number.
No power present at the MIB board
MIB will not clear error.
MIB indicates in­correct number of vats.
An error has occurred and displayed character indicates error.
Transformer has failed in left component box.
Error remains in non-volatile memory.
See MIB display diagnostics on page 46 for explanation.
Check output on the left transformer in left component box; should read 24VAC. If not replace transformer.
Press and hold reset button in top right cor­ner for fi ve seconds. The drain, return and manual/auto LEDS will illuminate and the MIB will reset and clear any remaining errors from memory. Allow 60 seconds to reset. If an error still exists, then another issue exists.
Ensure the CAN bus system is terminated at
BOTH ENDS (on the M3000 connector J6 and
on the ATO board connector J9) with a resistor equipped 6-pin connector.
Unplug and reseat all wiring harnesses in
• CAN system. Resistance between pins 2 and 3 on the CAN network connectors should be 120 ohms. Check software version numbers on all
• M3000 computers and ensure all display an AIF version. If an AIF version is miss­ing, the AIF board may be missing power. Check pins 5 and on J4 and J5 of the af­fected AIF board for proper voltage. The locator pin in J2 of the AIF board is
• either loose or in the incorrect position. See the chart on pages 47 of this manual for proper pin position.
8
LOV™ Generation II Technical Reference
Problem Probable Cause Corrective Action
Ensure the CAN bus system is terminated
A.
at BOTH ENDS (on the M3000 connector J6 and on the ATO board connector J10) with a resistor equipped 6-pin connector.
With the computer OFF, press TEMP but-
B.
ton and ensure the AIF version appears. If not, the 24V to the AIF boards may be missing. Ensure all 6-pin CAN connectors are tight between the M3000 (J6 and J7), MIB (J1 and J2), AIF (J4 and J5) and ATO (J10) boards. With the computer OFF, press TEMP but-
C.
ton and ensure the ATO version appears. If not, check the CAN wire harness between the AIF board J4 or J5 and the ATO board J9 or J10. The ATO fuse on the right side of the ATO box may be loose or blown; the 110V to the ATO transformer may be missing or bad. The J4/J5 connector may be loose. Check to see if MIB has 24V on pins 5 and
D.
MIB board alternat­ing “E” and “vat number and side.”
Network error on the CAN bus communication.
6 of J2. Check to see if 24V is present on pins 5 and 6 of wire harness plugging into J4 or J5 of the fi rst AIF board. If 24V miss- ing, check the pins. Replace the harness if necessary. Check continuity between each color wire
E.
on the CAN connectors into J7 on the far right computer and J10 on back of the ATO board (black to black, white to white, and red to red) and ensure there is no continu­ity between different color wires (black to red, red to white, and white to black). Ensure black computer locator wires are
F.
connected from ground to correct pin posi­tion (see pages 43-47). Ensure all boards have the corner ground
G.
wire attached and tightened. Check for loose locator pin or incorrect
H.
positioning in J2 of the AIF board. See the charts on pages 43-47 of this manual for proper pin position. Bad MIB and/or AIF board.
I.
Broken resistor lead. Unwrap the resistor
J.
leads and check ends.
9
LOV™ Generation II Technical Reference
Troubleshooting the AIF System (AIF)
Problem Probable Cause Fix
Ensure the actuator is plugged into the correct
1. connection (J1 for FV return, J3 for DV return; J6 for FV drain, J7 for DV drain). Ensure the locator pin is in the proper position
2. in plug J2. (See charts on pages 43-47 of this manual for proper pin position.)
Check pins 5 and 6 of J2 at the MIB board.
1. Should read 24VDC. Check voltage on pins 5 and 6 at the other end of the harness and ensure 24VDC is present. Check pins 5 and 6 for 24VDC on plugs J4 and J5 on AIF boards. Ensure actuator leads are plugged into AIF
2. board (J1 for FV return, J3 for DV return; J6 for FV drain, J7 for DV drain). Check the power on the connector of the
3. problem actuator while manually opening or closing the actuator. Pins 1 (black) and 4 (white) should produce +24VDC when the actuator is opening; -24VDC should be read from Pins 2 (red) and 4 (white) when the actuator is closing. If either voltage is missing, the AIF board is likely bad. Test the actuator by plugging into another connector to open or close. If the actuator operates, replace the board. Check resistance of the potentiometer
4. between pin 2 (purple wire) and pin 4 (gray/ white wire). Closed should read 0-560Ω. Open should read 3.8KΩ - 6.6KΩ. If proper voltages are seen at the connector
5. and the actuator doesn’t operate, replace the actuator.
Wrong vat opens.
Actuator doesn’t function.
Actuator is plugged into wrong
1. connector. Locator pin is in wrong position.
2.
No power to AIF board.
1. Actuator unplugged.
2. AIF board failure.
3. Actuator readings are out of
4. tolerance. Actuator is bad.
5.
Oil Return Sensor Troubleshooting (Gas LOV™ Fryers)
The oil return sensor is a device that is used to prevent dry fi ring of the burners. The sensor looks similar to a high limit. The sensors are energized when the computer is powered on with a soft on. The sensor heats up and detects the oil around it. During fi ltration when the oil is drained, it senses the difference between the oil and air. It is controlled with a board located next to the interface board (right) and a separate egg shaped plastic device (far right) that contains additional electronics. Use care when working with the sensor as temperatures may reach as high as 500°F (260°C).
The oil return sensor is controlled by a small green board and the electronics inside the plastic, egg-shaped device shown above to prevent dry fi ring.
10
LOV™ Generation II Technical Reference
IS VAT FULL?
IS DRAIN CLEAR?
If oil is surrounding the heater, the oil will prevent the heater from ever reaching its setpoint. Once oil is removed during fi ltration, the heater reaches setpoint and cycles a thermostat every four seconds. Since the cycle is only four seconds long, the seven second delay is not made and the gas valve won’t open.
The 120VAC is on T2 in the control box traveling in on pin 11 of J3 and out pin 7 on J1 (DV) or pin 7 on J3 (FV).
Typical sensor-related failures:
Low temp but no call for heat (heat light),
Stuck in melt cycle with no call for heat,
Filter error (
If the computer doesn’t exit melt cycle or continues to display low temp and does not heat, ensure that the gas supply, gas valve, and other components are working properly. If no heat lamp illuminates because no call for heat is initiated, check the following (see diagram below):
Power to oil sensor (from previous basket lift relay on interface board K1(DV) or K4 (FV)). Check
• pin 7 on J1 (DV) or pin 7 on J3 (FV) for 120VAC. Power to heater/relay coil on relay board. Check voltage to the coil on pins 8 and 1 to ensure that
• 120VAC is present with oil in the vat. If the vat is empty, the power will cycle 4 seconds on, 4 seconds off. Check between pin 3 and 2; 5VDC for air and 0VDC for oil. A common message for a shorted
• harness or issue is Check ground on pin 2 on relay board to stud for a secure ground.
• Check AIF communication harness. Interrupted communication will prevent the fryer from
• heating. If the oil level sensor is cycling 4 sec. on/off and oil is surrounding the sensor , the sensor may have
• a carbon build up that is self insulating the sensor. Use a no scratch pad to remove carbon build up.
IS VAT FULL?) with oil in the lter pan (no oil in the vat).
IS DRAIN CLEAR? with oil in the lter pan.
Black
(To J1 Pin 7 (DV)
or J3 Pin 7 (FV))
120V
White
(To T2 Terminal Block
Line Voltage In From
Oil Level Sensor
(Basket Lift) Relay on
Interface Board
24VAC from Interface Board
through High Limit (Ign. Module
Call for Heat)
To (optional Drain
Switch) and Gas
Valve
Fixed Setpoint Temp. Control
120V
120V (US) 230V (Intl) 40W
Heater w/ Thermocouple
WhiteBlack
C
NO
NC
1
2
3
Green
Red
8
7
Black
6
Black
5 4
Time Delay Relay Board
DPDT 7sec. Delay on Make
11
Thermocouple
Heater
(350 ohms US)
(1325 ohms Intl)
To AIF Board J2 Pin 9 DV
or 10 FV (AIF Oil Signal)
LOV™ Generation II Technical Reference
FR FRIES
----
mcchick
mcchick
M3000 Computer
Overview
Cook Cycle and
Selection Buttons
ON/OFF ON/OFFProduct Buttons
LED Display
Filter, Temp, Info, Programming
and Navigation Buttons
Heat Indicator
Lamp
LED Display
The M3000 computer retains the one-button ease of the M2000 and M100B, combining it with the utility of 40-product menu capability. It will operate with electric and gas fryers, both full- and split­vat.
On single product vats, press any of the cook cycle buttons to begin cooking. On multi-product vats, press a product button, and then a cook cycle button under the display showing the desired product name.
For example, a typical M3000 computer on a 3-vat fry station will display
FR FRIES. Pressing
one of the cook cycle buttons will begin a cook cycle for French fries.
The chicken/fi llet station will usually display dashed lines [ assigned to McChicken, for example, will cause cycle button beneath the word
---- ----
mcchick to start a cook cycle for McChicken.
---- ----
mcchick to be displayed. Then, press a cook
----]. Pressing the product button
MCC HICK MCC HICK
Product Buttons Cook Cycle Buttons
12
LOV™ Generation II Technical Reference
RECOVERY FAULT
RECOVERY FAULT CALL SERVICE
Navigation
The M3000 uses  and  buttons to navigate the various menus and submenus.
When programming, the left screen shows the menu or submenu item. The right screen is for data entry. Data is entered with alpha-numeric characters, scrolling through lists or by toggling between choices (see diagrams on previous page).
During programming, if a button is not pushed within one minute, the computer returns to operation mode.
Cook Cycle and Selection Buttons
The 9 and 8 buttons are dual-function buttons shared with the number 1 and 2 buttons. They are located directly below the LED displays (see diagrams on previous page). Use these buttons to select or cancel functions. The 8 button is used to back out of and quit submenus.
Filter, Temperature, and Info Buttons
The < FLTR and FLTR > buttons (see diagram) are used to fi lter the left and right vats of a split vat fryer on demand, while the right FLTR > button is used to fi lter a full vat on demand. If pressed once, the FLTR buttons will display the number of cook cycles remaining until a fi ltration prompt. When a FLTR button is pressed twice, the date and time of the last fi lter will be displayed.
Temp Button
The TEMP button, if pressed once while the fryer is on, displays current vat temperature on both sides. If the TEMP button is pressed twice while the fryer is on, it shows the setpoint temperatures of the vats. If the fryer is off, the display shows the current versions of software.
Info Button
The INFO button, if pressed once when the fryer is on, shows the recovery time for each vat from the last test. Recovery displays the time required for the fryer to raise the temperature of the oil 50°F (28°C) between 250°F (121°C) and 300°F (149°C). Maximum recovery time should not exceed 1:40 for electric or 2:25 for gas.
If recovery time exceeds these times, the computer will display can be cleared and alarm silenced by pressing the 9 button. The second consecutive time it will display cleared by pressing the 9 button. However, each time the fryer is started up and the test performed, the error will continue to appear until code 0042 is entered in tech mode (see page 27).
RECOVERY FAULT CALL SERVICE. The error can be silenced and temporarily
RECOVERY FAULT. The error
If the INFO button is pressed and held for three seconds it shows information such as usage, fi lter statistics and last cook cycles.
13
LOV™ Generation II Technical Reference
Cook Channel
and Selection Buttons
Basic Operation
Filter, Temp, Info,
Programming and Navigation Buttons
ON/OFF
Turn Fryer ON
Press right key for full pot; press key on desired side on a split pot.
Turn Fryer OFF
Press right key for full pot; press key on desired side on a split pot.
Check Frypot Temperature
Press Temp key once. Displays show frypot temperatures.
Check Frypot Setpoint
Press Temp key twice. Displays show frypot setpoint temperatures.
Cancel Duty or Remove
Press key under active display.
Start One-Button Cook Cycle (Dedicated Mode)
Press key under display showing desired item.
Alarm
TEMP
TEMP
2
1
Product Buttons
Start Two-Button Cook Cycle (Multi-Product Mode)
Press product key bearing icon for desired product. Press cook channel button to begin cook cycle
Change From Dedicated
Press and hold Cook Channel button under displayed menu item for approximately 3 seconds until beep is heard. Display changes to dashed lines.
Change From Multi-Product
Press product key bearing icon for desired product. Press cook channel button under display showing desired item until beep is heard (approx 3 seconds).
.
to Multi-Product Mode
Mode to Dedicated Mode
ON/OFF
2
2
2
14
LOV™ Generation II Technical Reference
y
K
4
Cooking With Multi-Product Display
Dashed lines appear
1
in both displays.
Press a product
2
button.
Vat with appropriate
3
setpoint displays: MC CHICK. Skip to step 5.
Vat with inappropriate
4
setpoint displays:
If this occurs, change setpoint by pressing the button assigned to the product. When the chevrons appear, immediately press and hold the cook button until a beep is heard (approximately three seconds) and then release it.
Press a cook channel
5
button to begin cook cycle.
- - - - - - - -
McCK
Mc chick
<<<<>>>>
McCK
<<<<>>>>
1
1
Display alternates
6
between MCCK and remaining cook time
If a duty is required for
7
this menu item displayed when it is time to perform a duty, such as shake.
Press cook
8
channel button under duty display to cancel alarm.
Pull is displayed
9
when the cook time is complete; an alarm sounds.
Press cook
10
channel button under pull display to cancel alarm.
Dashed lines reappear
11
under active display at the end of the cook cycle.
.
, duty is
Mc c
2:3
dut
2
pull
2
- - - - - - -
NOTE:
If error Remove Discard Product appears, press the cook channel button under the message to cancel alarm and remove error message.
15
LOV™ Generation II Technical Reference
s
4
y
Cooking With Dedicated Display
A menu item, such as
1
FR FRIES shows in display
Press a cook channel
2
button to begin the cook cycle.
Display alternates
3
between abbreviated product name and remaining cook time.
Duty is displayed
4
when itis time to shake the fry basket.
Press cook channel
5
button to cancel alarm
Pull is displayed
6
when the cook cycle is complete.
fr
FRY
.
fries
1
2:3
dut
1
pull
Fr fries
Q7 is displayed and
8
alternates with FRY. As the quality time counts down.
Pressing the cook
9
channel button now will launch a cook cycle and end the
quality countdown.
QUAL is displayed
0
1
when the quality time has elapsed.
Pressing the cook
1
1
channel button restores the display to FR FRIES unit is ready for cooking
.
Q7 Fry
Q1 Fry
1
Qual
1
and the
FR FRie
Press cook channel
7
button to cancel alarm.
1
16
LOV™ Generation II Technical Reference
s
Changing from Breakfast Setup to Lunch
Hash brn Hash brn
Press and quickly
1
release product button for french fries.
Computer will change
2
from Hash Brn to
<<<<<>>>>>; an
alarm will sound.
Perform these steps on both sides to change both displays to FR FRIES.
FFRY
hash brn
<<<<<>>>>>
Press and hold the cook
3
channel button under the display until a beep is heard (approximately three seconds) and release.
Display changes to FR
4
Fries..
1
fr frie
17
LOV™ Generation II Technical Reference
r
s
Changing from Lunch Setup to Breakfast
Fr
Computer displays
1
FR FRIES.
Press and quickly
2
release product button for hash browns.
Computer display
3
will change from FR Fries to <<<<<>>>>>; an alarm sounds.
fries
FRFRie
f
<<<<<>>>>>
Hash
brn
fries
Fr
Press and hold the cook
4
channel button under the display until a beep is heard (approximately
three seconds) and release.
Display changes to
5
Low Temp until setpoint is reached.
Display changes to
6
Hash Brn.
fries
1
LOW temp
hash brn
Perform these steps on both sides to change both displays to FR FRIES.
18
LOV™ Generation II Technical Reference
A
r
The following chart maps the menu options available in the M3000 computer and indicates the location of more information on each menu item within the LOV™ Fryer Installation and Operation Manual. For more information, consult the indicated section.
M3000 Menu Items
Location in IO manual
Adding New Menu Items See section 4.10.2 Storing Menu Items in Product Buttons See section 4.10.3 Draining, Refi lling, and Disposing of Oil See section 4.10.4
Filter Menu
Programming
………………………………………………………………………………………………………….. 4.11
[Press and hold FLTR or FLTR ►]
Auto Filter Maint Filter Dispose Drain to Pan Fill Vat from Drain Pan Fill Vat from Bulk (Bulk Only) Pan to Waste (Bulk Only)
Level 1 Program
[Press and hold TEMP and INFO buttons, 2 beeps, displays Level 1, enter 1234]
Product Selection
…….……………….....………………………………………………………….. 4.12
..…….....………………………………………………………….. 4.10.2
Name Cook Time Te mp Cook ID Duty Time 1 Duty Time 2 Qual Tmr AIF Disable Assign Btn
IF Clock
..………………………………………………………………………………… 4.12.1
Disabled Enabled
Deep Clean Mode
High-Limit Test
Fryer Setup
……..……………………...…………………………………….. 4.12.2
…………….…………………….…………………………………….. 4.12.3
…………………….……………………………………………………………….. 4.9
Level 2 Program (Manager Level)
[Press and hold TEMP and INFO buttons, 3 beeps, displays Level 2, enter 1234]
Prod Comp E-Log
Password Setup
Sensitivity for product Log of last 10 error codes
Change passwords Setup [enter 1234] Usage [enter 4321] Level 1 [enter 1234] Level 2 [enter 1234]
Alert Tone Volume and Tone
Volume 1-9
Ton e 1 - 3 Filter Afte Filter Time
Tech Mode
[Press and hold and for 10 seconds, 3 beeps, displays TECH MODE, enter
1650]
Sets number of cooks before filter prompt
Sets amount of time between filter cycles
Clear Passwords Filter Pad Time
Info Mode
………………...………………………...………………………………………..……………………….. 4.14
[Press and hold INFO for 3 seconds, displays Info Mode]
Full/Split Vat Configuration
Filter Stats Review Usage Last Load
..……………….……………………………………………………………….. 4.14.1
………….……………………………………………………………….. 4.14.2
………………….……………………………………………………………….. 4.14.3
……………………………………………….. 4.13
…………………………………….. 4.13.1
…………………………….. 4.13.2
……………………………… 4.13.3
...………………………………………….. 4.13.4
………….. 4.13.5 ………….. 4.13.6
19
LOV™ Generation II Technical Reference
OFF
UPGRADE IN PROGRESS
WAIT
CC UPDATING
BOOT
UPGRADE IN PROGRESS
WAIT
COOK HEX
mib HEX
aif HEX
aTO HEX
REMOVED SD CARD
100
CYCLE POWER
M3000 CAN TX FULL
SERVICE REQUIRED
BOOT
OFF
YES
SYSTEM ERROR FIXED?
OFF
Loading and Updating Software Procedures
Updating the software takes approximately 20 minutes. To update the software, follow these steps:
1. Switch all computers to version.
2. Remove the two screws on the left side cover plate of the M3000 board.
3. With the computer folded down, insert the SD card into the slot on the left side of the M3000. The contacts on the card should face down and the notch should appear on the bottom right (see pictures below).
4. Once inserted,
5. The display then changes to right. The display counts up to 100 on the right, changing to a fl ashing THE CARD UNTIL THE DISPLAY PROMPTS TO DO SO IN STEP 8.
6. Then,
7. The display then changes to
8. Remove the SD card using the fi ngernail slot on the top of the SD card.
9. Once the SD card is removed the display changes to
UPGRADE IN PROGRESS is displayed on the left display and followed by the percentage complete on the right.
UPGRADE IN PROGRESS appears on the left display and
COOK HEX,
OFF. Press the TEMP button to check current M3000/MIB/AIF/ATO software
WAIT on the right.
CC UPDATING on the left and the percentage completed appears on the
BOOT. DO NOT REMOVE
WAIT on the right again,
mib HEX,
REMOVED SD CARD on the left and
aif HEX ending with
CYCLE POWER.
aTO HEX displayed on the left and
100 on the right.
10. Cycle the control power using the hidden reset switch behind the right control box (see page 38). HOLD THE SWITCH FOR 10 SECONDS ENSURING THE MIB BOARD HAS POWERED FULLY DOWN.
11.
M3000 CAN TX FULL (a rebooting. Press YES at the prompt to cancel alarm. A fl ashing computers while the program is transferred.
12. When the update is complete, the M3000 displays software is loading, changing to show the vat numbers. Once the LEDs stop blinking, press SYSTEM ERROR FIXED? Enter 1111. The MIB board will display A.
13. Cycle the control power using the hidden reset switch behind the right control box again. ENSURE
THE SWITCH IS HELD FOR 10 SECONDS. WAIT ANOTHER 20 SECONDS UNTIL THE MIB BOARD HAS FULLY RESET BEFORE CONTINUING.
14. With the computer displaying updated M3000/MIB/AIF/ATO version on each computer. IF ANY BOARDS DID NOT UPDATE, REPEAT THE PROCESS STARTING WITH STEP 3.
Insert the SD card
with contacts fac-
ing down.
SERVICE REQUIRED error) may appear while computers are
BOOT is displayed on the remaining
OFF. The MIB display will remain blank while
YES to
OFF, VERIFY software update by pressing the TEMP button to check
Remove the SD card using the fi ngernail slot on the top of the card.
20
LOV™ Generation II Technical Reference
filter busy
.
FILL VAT FROM DRAIN
PAN
M3000 Troubleshooting
Problem Probable Causes Corrective Action
No display on computer.
A. Computer not turned on.
B. No power to the fryer.
C. Power switch turned off.
D. Loose fuse holder.
E. Computer has failed.
F. Damaged computer wiring
harness.
G. Power supply component or
interface board has failed.
A. Press the ON/OFF switch to turn
the computer on.
B. This fryer may have two cords: a
computer power cord and a main power cord. If the computer cord is not plugged in, the computer will not activate. Verify computer power cord is plugged in and that circuit breaker is not tripped.
C. Some fryers have a rocker power
switch inside the cabinet below the computer. Ensure the switch is turned on.
D. Ensure fuse holder is screwed in
properly.
E. Swap the computer with a computer
known to be good. If computer functions, replace the computer.
F. Swap with a harness known to
be good. If computer functions, replace the harness.
G. If any component in the power
supply system (including the transformer and interface board) fail, power will not be supplied to the computer and it will not function.
Computer locks up. Computer error.
A. Another fi ltration cycle is still in
process.
M3000 display shows
filter busy
B. Computer error.
C. Computer error.
Remove and restore power to the computer.
A. Wait until the previous fi ltration
cycle ends to start another fi ltration cycle.
B. A computer has an error. Using
the fi lter menu, try to perform a
FILL VAT FROM DRAIN
PAN on each vat (see Chapter 4
of the BIELA14 IO manual). Only computers with errors can perform this function with a fi lter busy error. Computer should clear and return to normal operation once complete.
C. If fi lter busy is still displayed with
no activity, ensure the fi lter pan is
empty and remove and restore ALL
power to the fryer.
21
LOV™ Generation II Technical Reference
RECOVERY FAULT
CALL SERVICE.
ENERGY
MISCONFIGURED
EXCEPTION ERROR
SERVICE
REQUIRED
SYSTEM
ERROR FIXED? YES/NO.
ENTER
CODE
CHANGE
FILTER PAD
CHANGE FILTER
PAD
INSERT pan
INSERT
pan
hot-hi-1
HI-
LIMIT
.
Problem Probable Causes Corrective Action
M3000 display shows
RECOVERY FAULT
CALL SERVICE.
M3000 display
shows
MISCONFIGURED
M3000 display shows
EXCEPTION ERROR
with the description on the
M3000 displays
REQUIRED followed by
ENERGY
SERVICE
the error.
right.
Recovery time exceeded maximum time limit for two or more cycles.
Wrong energy type selected in setup.
An error has occurred.
An error has occurred.
Silence the alarm by pressing the 9 button. Clear the error using the code on page 25. Maximum recovery for electric is 1:40.
Press 1234 to enter setup and set energy type for electric.
Press 1234 to enter setup and reconfi gure the computer.
Press YES to silence alarm. The error is displayed three times. See list of issues on page 26. Fix issue. The computer displays
ERROR FIXED? YES/NO. Press
YES. Computer displays
CODE.. Enter 1111 to clear error
code. Pressing NO will allow the fryer to cook, but error will be redisplayed every 15 minutes.
SYSTEM
ENTER
M3000 display is in
wrong temperature scale
(Fahrenheit or Celsius).
M3000 displays
M3000 display shows
M3000 display shows
CHANGE
FILTER PAD.
INSERT pan.
hot-hi-1.
Incorrect display option programmed.
Filter error has occurred, fi lter pad clogged, 24 hour fi lter pad change prompt has occurred, or change lter pad was ignored on a prior prompt.
A. Filter pan is not fully inserted into
fryer. B. Missing fi lter pan magnet. C. Defective fi lter pan switch.
Frypot temperature is more than 410ºF (210ºC) or, in CE countries, 395ºF (202ºC).
See page 28 to change temperature scale.
Change the fi lter pad and ensure the lter pan has been removed from the
fryer for a minimum of 30 seconds. Do NOT ignore
PAD prompts.
A. Pull fi lter pan out and fully reinsert
into fryer.
B. Ensure the fi lter pan magnet is in
place and replace if missing.
C. If the fi lter pan magnet is fully
against the switch and computer continues to display pan, switch is possibly defective.
This in an indication of a malfunction in the temperature control circuitry, including a failure of the high-limit thermostat.
CHANGE FILTER
INSERT
M3000 display shows
LIMIT
HI-
Computer in high-limit test mode.
This is displayed only during a test of the high-limit circuit and indicates that the high-limit has opened properly.
22
LOV™ Generation II Technical Reference
low temp
with MLT-CYCL
EXIT
MELT
YES
ERROR RM SDCRD
TEMP PROBE
FAILURE.
MAINT FILTER
MAINT FILTER.
REMOVE DISCARD
HEATING FAILURE
.
HI
2 BAD.
HELP HI-2
HIGH
LIMIT FAILURE
Problem Probable Causes Corrective Action
M3000 display shows
low temp alternating
with MLT-CYCL.
Frypot temperature is between 180°F (82°C) and 315°F (157°C).
This display is normal when the fryer is fi rst turned on while in the melt cycle mode. To bypass the melt cycle press and hold either #1 or #2 product button under the LCD display until a chirp is heard. The computer displays MELT alternating with Press the #1 YES button to exit melt. If the display continues, the fryer is not heating.
YES and NONO.
EXIT
M3000 display shows
ERROR RM SDCRD
M3000 display shows
TEMP PROBE
FAILURE.
MAINT FILTER (Manual
Filter) won’t start.
M3000 display shows
REMOVE DISCARD.
M3000 display shows
HEATING FAILURE
Defective SD card. Replace card with another card.
A. This indicates a problem within the
A. Problem with the temperature
measuring circuitry including the
probe.
B. Damaged computer wiring
harness or connector.
Temperature too low.
In non-dedicated mode, a product is dropped that has a different setpoint that the current vat temperature.
Failed computer, failed interface board, open high-limit thermostat.
temperature measuring circuitry. Check resistance of probe, if faulty replace probe.
B. Swap the computer wiring harness
with one known to be good. If problem is corrected, replace the harness.
Ensure fryer is at setpoint before starting
MAINT FILTER.
Remove and discard product. Press a cook button under the display with the error to remove the error. Reset the setpoint of the vat before trying to cook product.
Turn off the vat with the problem. This error is displayed if the fryer loses its ability to heat oil. It is also displayed when the oil temperature is above 450°F (232°C) and the high-limit thermostat has opened, halting the heating of the oil.
Computer will not go into
program mode or some
buttons do not actuate.
M3000 display shows
M3000 display shows
HELP HI-2 or
LIMIT FAILURE.
HI
2 BAD.
HIGH
Failed computer. Replace computer
This is displayed during a test of the
Computer in high-limit test mode.
Failed high-limit.
high-limit circuit to indicate if the high­limit has failed.
This is displayed to indicate the high­limit has failed.
23
LOV™ Generation II Technical Reference
low temp
IS
VAT FULL? YES NO.
Problem Probable Causes Corrective Action
M3000 display shows
software for only M3000
or MIB but not all boards.
Loose or damaged harness.
Check that all harnesses between M3000’s, MIB, AIF and ATO are secure. Ensure 24VDC is present on pins 5 & 6 of J2 on MIB board and on J4 or J5 of AIF board. Check for loose or broken pins/wires. If the problem persists, swap out computer from one bank to another and cycle power on the fryer.
M3000 display shows
low temp,
indicator cycles on and
off normally but fryer
M3000 display shows
VAT FULL? YES NO.
Fryer fi lters after each
heating
does not heat.
IS
cook cycle.
A. Three phase power cord
unplugged or circuit breaker is
tripped. B. Failed computer. C. Damaged computer wiring
harness. D. Open connection in high-limit
circuit.
A fi lter error has occurred due to dirty or clogged fi lter pad or paper, clogged fi lter pump, fi lter pump thermal overload, improperly installed fi lter pan components, worn or missing O-rings, cold oil or an actuator problem.
Filter after setting incorrect or software update issue.
A. Ensure all cords are fully seated in
the receptacles, locked into place and that circuit breakers are not
tripped. B. Replace computer. C. Replace computer wiring harness. D. Check high limit circuit starting at
the control box connector working
to the high-limit.
Follow the steps in the fl owchart on page 30.
Overwrite the fi lter after setting by re- entering the fi lter after value in level two. Ensure that the down arrow is pressed after entering the value to save the setting (see Chapter 4 in the BIELA14 IO Manual for more information).
24
LOV™ Generation II Technical Reference
TECH MODE
0042
RECOVERY FAULT CALL SERVICE
1658
off
3322
COMPLETE
off
1650
1212
COMPLETE
off
0469
Filter Stat Data
1000
CALL TECH
1000
off
9988
BADCRC
9988
off
1111
SERVICE REQUIRED
1234
SETUP MODE
level 1
level 2
ENTER
Code
1234
4321
M3000 Useful Codes
To enter any of the following codes: Press and hold and simultaneously for TEN seconds; three chirps sounds. The computer displays
0042 – Reset
1658 Change from F° to C°. The computer displays
temperature to see the temperature scale. If the desired scale is not displayed, repeat.
3322 Reset Factory Menu. The computer displays
This will delete any hand-entered menu items.)
1650 Enter Tech Mode. See page 1-36 to reset passwords and change fi lter pad time.
1212 – Switch Between Domestic and International Menu. The computer displays
COMPLETE, and then
0469 – Reset
RECOVERY FAULT CALL SERVICE.
off. (NOTE: This will delete any hand-entered menu items.)
Filter Stat Data.
TECH MODE. Enter the codes below to perform this function.
off. Turn the computer on and check
COMPLETE, and then
off. (NOTE:
The following codes require the removal and reinsertion of the J3 locator plug on the rear of the computer before entering the code.
1000 – Reset
Enter
1000. Computer display switches to
using the 20-pin plug.
9988 – Reset
9988. Computer display switches to
the 20-pin plug. Replace the computer.
The following codes are entered when prompted to do so or from an energy misconfi gured exception error.
1111 – Reset
are prompted to enter.
1234 – Enter
ally can be done without pressing the fi lter buttons if an error is displayed.)
CALL TECH Message. Disconnect board locator plug (J10). Reinsert plug.
off. Remove and then restore power to the computer
BADCRC Message. Disconnect board locator plug (J10). Reinsert plug. Enter
off. Remove and then restore power to the computer using
SERVICE REQUIRED Message. Enter this when the issue is xed and you
SETUP MODE from energy miscon gured exception error. (This usu-
Passwords
To enter level one, level two passwords – Press and hold the TEMP and INFO buttons simultane-
ously until
level 1 or
level 2 is displayed. Release the buttons and
ENTER
Code appears.
1234 – Fryer Setup, Level One, and Level Two.
4321 – Usage Password.
25
LOV™ Generation II Technical Reference
SERVICE REQUIRED
YES
YES
SYSTEM ERROR FIXED?
YES/NO
yes
1111
SERVICE RE-
QUIRED
Service Required Errors
A
SERVICE REQUIRED error alternating with
pressed the alarm is silenced. The computer displays an error message from the list below three times with the location of the error. Then, the computer displays
YES/NO. If
yes is chosen, enter code
1111. If NONO is chosen, the system returns to cook
mode for 15 minutes then redisplays error until issue is fi xed.
YES displays on the computer. After
SYSTEM ERROR FIXED?
YES is
Pressing the MIB reset button during any fi lter function will generate a
QUIRED error.
SERVICE RE-
This is a list of the service required errors and cause.
ERROR MESSAGE EXPLANATION
Oil not returning to vat quickly. Possible problems: dirty pad, bad
PUMP NOT FILLING
DRAIN VALVE NOT OPEN Drain valve failed to open; the valve’s position is unknown. DRAIN VALVE NOT CLOSED Drain valve failed to close; the valve’s position is unknown. RETURN VALVE NOT OPEN Return valve failed to open; the valve’s position is unknown. RETURN VALVE NOT CLOSED Return valve failed to close; the valve’s position is unknown.
MIB BOARD
AIF BOARD MIB detects AIF missing; AIF board failure. ATO BOARD MIB detects ATO board connection lost; ATO board failure. HIGH LIMIT FAILURE High limit circuit has an issue. AIF PROBE AIF RTD reading out of range. ATO PROBE ATO RTD reading out of range. TEMP PROBE FAILURE TEMP Probe reading out of range. MIB SOFTWARE Internal MIB software error. INVALID CODE LOCATION SD card removed during update. MISCONFIGURED ENERGY
TYPE
RTC INVALID DATE
or missing O-rings, tripped or defective fi lter pump, actuators or linkage.
Problem with CAN communications; check for loose CAN connec­tions. MIB board failure.
Energy type in fryer setup is incorrect; set proper energy type gas or electric. Press 1234 to enter setup to properly confi gure fryer.
The date is invalid. Press 1234 to enter setup to properly confi g- ure fryer and set proper date.
26
LOV™ Generation II Technical Reference
CODE ERROR MESSAGE EXPLANATION
A product cook is started on the right side of a split vat
E01 REMOVE DISCARD (Right)
E02 REMOVE DISCARD (Left)
E03 ERROR TEMP PROBE FAILURE TEMP Probe reading out of range.
E04 HI 2 BAD High limit reading is out of range.
E05 HOT HI 1
E06 HEATING FAILURE
E07 ERROR MIB SOFTWARE Internal MIB software error.
E08 ERROR ATO BOARD
E09 ERROR PUMP NOT FILLING
E10 ERROR DRAIN VALVE NOT OPEN
E11 ERROR DRAIN VALVE NOT CLOSED
E12 ERROR RETURN VALVE NOT OPEN
E13 ERROR RETURN VALVE NOT CLOSED
E14 ERROR AIF BOARD MIB detects AIF missing; AIF board failure.
E15 ERROR MIB BOARD
E16 ERROR AIF PROBE AIF RTD reading out of range.
E17 ERROR ATO PROBE ATO RTD reading out of range.
E18 Not Used
E19 M3000 CAN TX FULL Connection between computers lost.
E20 INVALID CODE LOCATION SD card removed during update.
E21
E22 OIL IN PAN ERROR The MIB has detected oil may be in the pan.
E23 CLOGGED DRAIN (Gas) Vat did not empty during fi ltration.
E24
E25 RECOVERY FAULT Recovery time exceeded maximum time limit.
E26 RECOVERY FAULT CALL SERVICE
E27 LOW TEMP ALARM
FILTER PAD PROCEDURE ERROR (Change Filter Pad)
OIL RETURN (level) SENSOR FAILED (Gas)
or in a full vat that has a different setpoint other than the current vat temperature.
A product cook is started on the right side of a split vat or in a full vat that has a different setpoint other than the current vat temperature.
High limit temperature is past more than 410°F (210°C), or in CE countries, 395°F (202°C).
A component has failed in the high limit circuit such as computer, interface board, contactor or open-high limit.
MIB detects ATO board connection lost; ATO board failure.
Oil not returning to vat quickly. Possible problems: dirty pad, bad or missing O-rings, tripped or defective fi lter pump, actuators or linkage.
Drain valve failed to open; the valve’s position is unknown.
Drain valve failed to close; the valve’s position is unknown.
Return valve failed to open; the valve’s position is unknown.
Return valve failed to close; the valve’s position is unknown.
Cooking computer detects MIB connections lost; check software version on each computer. If versions are missing, check CAN connections between each computer; MIB board failure.
25 hour timer has expired or dirty fi lter logic has activated.
Oil return sensor may have failed.
Recovery time exceeded maximum time limit for two or more cycles.
Oil temperature has dropped lower than 15°F (8°C) in idle mode or 45°F (25°C) in cook mode.
27
LOV™ Generation II Technical Reference
TEN
CODE
1650
TECH MODE
CLEAR PASS-
WORDS
CLEAR PASSWORDS
COM-
PLETE
FILTER PAD TIME
OFF
OFF
LEVEL 1
ENTER
CODE
1234
level 1 program
Product selection
FRYER SETUP
Tech Mode
Tech mode allows technicians to reset all passwords set in Levels One and Two and change the time at which the fryer calls for a fi lter pad change. The default is 25 hours.
1. Press and hold and simultaneously for heard and
2. Enter
3. The computer displays WORDS.
4. Press the 9 (1) button to accept selection and clear the passwords.
5. The computer displays PLETE on the right. This clears any passwords set up under levels one and two.
6. Press the button to toggle to the right. (25 hours is the default time to change the pad.)
7. Press the 8 (2) button to accept changes and exit.
8. The computer displays
CODE is displayed.
1650.
TECH MODE and changes to
CLEAR PASSWORDS on the left and
FILTER PAD TIME on the left and 2525 on
OFF. Continue below to enter the setup mode.
TEN seconds until a third chirp is
CLEAR PASS-
COM-
Fryer Setup Mode
Fryer Setup Mode is used to setup the time, date, date format, language, fryer type, vat type, oil system type, and temperature scale in the fryer’s computer. These settings are needed for the fryer to function properly and should only be changed by a technician upon initial power up after installing a new computer or after accessing from Level 1.
With the computer displaying
1. Enter Level 1 programming mode by pressing the TEMP and INFO buttons simultaneously until CODE.
2. Enter
The computer displays Product selection .
3. Press the a button once to scroll to
1234.
LEVEL 1 is displayed. The computer displays
OFF:
ENTER
level 1 program for three seconds changing to
FRYER SETUP.
28
LOV™ Generation II Technical Reference
yes
ENTER CODE
1234
Language
english
yes
temp format
yes
time format
12 hr
12 hr
24 hr
yes
enter time
hh:MM
yes
DATE FORMAT
interntl
yes
enter date
MM-DD-YY
DD-MM-YY
4. Press the 9 (1
The computer displays
5. Enter
1234.
The computer displays
yes) button.
ENTER CODE.
Language on the left and
english on the
right.
6. Use the _ and ` buttons to scroll through the language menu.
7. With the desired language selection displayed, press the 9 (1
The computer displays
temp format on the left and f on the right.
yes) button.
8. Use the _ and ` buttons to toggle between f and c temperature scales.
NOTE: F is used for Fahrenheit, C is used for Celsius.
9. With the desired selection displayed, press the 9 (1 computer displays
time format on the left and
yes) button. The
12 hr on the right.
10. Use the _ and ` buttons to toggle between
12 hr and
11. With the desired selection displayed, press the 9 (1
The computer displays right in
hh:MM format. AMAM or PMPM is displayed if 12 hour system is chosen.
enter time on the left and current time on the
24 hr.
yes) button .
For example:
12 Hour Format – 7:30 AM is entered as 0730. 24 Hour Format – 2:30 is entered as 1430.
Change AMAM and PMPM – use the cd buttons.
12. Enter time in hours and minutes using the number buttons 0-9.
13. With the desired selection displayed, press the 9 (1
The computer displays
DATE FORMAT on the left and USUS on the right.
14. Use the _ and ` buttons to toggle between USUS and
15. With the desired selection displayed, press the 9 (1
yes) button.
interntl.
yes) button.
The computer displays DD-MM-YY on the right changing to the current date. For example:
US Format – Dec. 5, 2008 is entered as 120508.
International Format – 5 Dec. 2008 is entered as 051208.
enter date on the left and
MM-DD-YY or
29
LOV™ Generation II Technical Reference
yes
fryer type
Elec
elec
gas
yes
VAT
type
SPLIT
SPLIT
FULL
yes
OIl SYSTEM
JIB
JIB
BULK
JIB
BULK
yes
LANGUAGE
ENGLISH
SETUP COMPLETE
off
16. Enter the date using the number buttons 0-9.
17. With the desired selection displayed, press the 9 (1
The computer displays
18. Use the _ and ` buttons to toggle between
19. With the desired selection displayed, press the 9 (1
The computer displays
20. Use the _ and ` buttons to toggle between
21. With the desired selection displayed, press the 9 (1
The computer displays
22. Use the _ and ` buttons to toggle between
NOTE: A JIB system uses a disposable
system has large storage oil tanks that are connected to the fryer that lls a reservoir.
fryer type on the left and
elec and
VAT
OIl SYSTEM on the left and
type on the left and
SPLIT and
JIB and
JIB (Jug in a Box). A
SPLIT on the right.
yes) button.
Elec on the right.
gas.
yes) button.
FULL.
yes) button.
JIB on the right.
BULK.
BULK
23. With the desired selection displayed, press the 9 (1
The computer displays Use the cd buttons to scroll and edit any additional fi elds.
24. Press the 8 (2) button to exit.
The computer displays
LANGUAGE on the left and
SETUP COMPLETE changing to
yes) button.
ENGLISH on the right.
off.
30
LOV™ Generation II Technical Reference
Filter Error
SERVICE
REQUIRED
SYSTEM ERROR FIXED? YES
NO
YES
SYSTEM ERROR FIXED? YES NO
Filter Error Flow Chart
NORMAL
OPERATION
RESUMES
MESSAGE
DISPLAYED
Call an Authorized Repair Technician
SIXTH
CONSECUTIVE
FILTER ERROR
Change filter pad and
Fryer returns to
cook mode for 4
minutes or 15
minutes if pad
change expired.
ensure filter pan is
This chart follows the process of clearing a following occur:
TECH
ENTERS
CODE
pulled out for a minimum of 30
seconds.
Fryer returns to
cook mode for 15
minutes.
If the computer displays
REQUIRED, the fryer can be used in most
SERVICE
cases by answering NONO when the prompt for
SYSTEM ERROR FIXED? YES
NO is displayed. The message repeats every
15 minutes until the issue is repaired and error cleared by a technician. To clear the error, enter 1111 after answering
SYSTEM ERROR FIXED? YES NO
YES when
is displayed.
Filter Error prompt. The prompt is displayed when any of the
1. a clogged fi lter pad,
2. a tripped or defective fi lter pump,
3. a leaky O-ring on the pick up tube,
4. a clogged pressure switch (gas fryer),
5. a failed drain valve/actuator, or
6. a failed return valve/actuator.
It is cleared by following the prompts.
31
LOV™ Generation II Technical Reference
RTI-equipped Systems
Some stores may be equipped with RTI oil storage systems. If so, some of the settings, wiring, and troubleshooting may differ from normal LOV™ fryer systems. (See next page for bulk oil wiring.)
The LOV™ fryer will ONLY operate with RTI systems that have the new RTI updated three­pole fl oat switch. If the fl oat switch is the older two-pole switch, call RTI. These oat switches are
polarity specifi c and may short to ground and damage an MIB board.
Normal AC Voltage Measurements (MIB J6 8 pin connector with everything connected)
Pin 1 to Pin 2 - 24 VAC.
• Pin 2 to Pin 8 - 24 VAC when waste tank is full, 0 VAC when it is not full.
• Pin 2 to Pin 3 - 24 VAC when RTI fi ll pump is on, 0 VAC when it is off.
Troubleshooting
The valves and pump should be off while MIB is resetting. If any of the valves or pumps are on dur­ing reset then the MIB board is bad or wires are shorted.
If JIB valve is not opening, measure when JIB valve supposed to be open:
Voltage at MIB board from Pin 1 to Pin 2 should be 24 VAC; if not, check connections from
• RTI 24VAC transformer and check transformer.
JIB solenoid is not opening:
Take these readings when the JIB valve is in the open position:
Reset the power; wait 60 seconds and see if the valve opens.
1.
Check voltage at ATO board on J8. Pin 9 to Pin 16 should be 24 VAC.
2.
RTI pump is not operating or JIB is not fi lling:
1. Voltage at MIB board from Pin 1 to Pin 2 should be 24 VAC; if not, check connections from RTI 24VAC transformer and check transformer at RTI.
2. Voltage at MIB board from Pin 2 to Pin 3 should be 24 VAC; if not, check MIB board is bad or wires to pump relay are shorted or both.
3. Voltage at Add pump relay should be 24 VAC; if not, check wiring from MIB board. Relay located on top of RTI system.
Waste full signal: Pin 2 to Pin 8 should be 24 VAC when full, 0 VAC when not full; if no voltage level change, then the connection from RTI switch or MIB board is bad.
32
LOV™ Generation II Technical Reference
Bulk Oil LOV™ Wiring
DROP PLUG
BEHIND FR YER
GRAY 5-
CO NDUCT O R
123
RED
CA B L E
4
WHITE
BLACK
GREEN
5
12
4
3
3
4
12
5
TESTIN G BETW EEN PIN S 1 & 4 RTI
DROP PLUG SHOULD READ:
24VAC W HEN RTI TANK IS FULL
0 VAC WH EN R TI TANK IS EMPTY
BLAC K 24VAC IN FRO M R TI (HO T)
MIB J6
HIRS CHM ANN
REAR OF FRYER
CONNECTION ON
GREEN 24VAC OUT RTI PUMP
WHITE 24VAC IN FROM RTI(COM)
RED RTI DISPOSE TANK FULL
TESTING BETWEEN PINS 2 & 8 J6 MIB
SHOULD READ:
24VAC W HEN RTI TANK IS F ULL
0VACWHENRTITANKISNOTFULL
ADD
PUMP
LIN E
CONTROL
WASTE FULL
LINE
SENSE
33
LOV™ Generation II Technical Reference
Oil Disposal and Fill with RTI-equipped Systems
Bulk oil systems have large oil storage tanks, typically located in the rear of the restaurant, that are connected to the rear manifold on the fryer. Waste oil is pumped from the fryer, through the fi tting located on the left, and into the disposal tanks. Fresh oil is pumped from the tanks, through the fi tting located on the right, and into the fryer (as shown below).
LOV used for fi lling the jug and topping off the frypot.
An orange momentary switch located adjacent to the JIB allows the operator to fi ll the JIB from the bulk oil storage tank. To fi ll the JIB, press and hold the orange button until the JIB is full then release.
Using the fi lter menu scroll to DISPOSE and select to dispose using the RTI system. When prompt- ed, open the dispose valve by pulling the handle forward. To close push the handle towards the rear of the fryer until it stops. A key lock allows the store manager to control when oil is disposed.
fryers equipped for use with bulk oil systems have an onboard fresh oil jug. The same fi tting is
Warning: Do not add
HOT or USED oil to the
JIB.
The RTI JIB with fi tting.
Fresh Oil Connection
Waste Oil Connection
RTI Wiring Connection behind plate.
Fittings, LOV™ Fryer.
Orange JIB reset and momentary fi ll button.
Opening the RTI dis­pose valve.
34
Closing the RTI dispose valve.
LOV™ Generation II Technical Reference
Frymaster LOV™ Fryer and RTI Bulk Oil System Plumbing Schematic
Valves
Drain Ball
Fryer
Filter
Pump
Built-in Filter BoxBuilt-in Filter Box
Fry Pots
Valve
Bypass Check
Pump
Top-off
Return
Valves
Jug
Top-off
Jug Valve
New Oil PumpNew Oil Pump
Valve
Dispose Manual
New Oil
Tank
Tank
Waste Oil
35
LOV™ Generation II Technical Reference
RTI LOV™ Test Quick Reference
DISPOSE TO WASTE, REFILL VAT FROM BULK:
1. Hold down “Filter” button until computer beeps twice.
2. Scroll down to “Dispose” using “Info” button then press “9” button.
3. “Dispose? Yes/No” is displayed.*
4. Press “9” to dispose of oil in pot.
5. “Draining” is displayed.
6. “Vat Empty? Yes” is displayed.
7. Press “9”.
8. “Cln Vat Complete? Yes” is displayed.
9. Press “9”.
10. “Open Dispose Valve” is displayed. Open dispose valve.
11. “Disposing” is displayed for fi ve minutes.
12. “Remove Pan” is displayed. Remove pan.
13. “Is Pan Empty? Yes No” is displayed.
14. Press “9” if fi lter pan is empty. Select “8” if pan still has oil in it.
15. “Close Dispose Valve” is displayed. Close dispose valve.
16. “Insert Pan” is displayed. Insert pan.
17. “Fill Vat From Bulk? Yes/No” is displayed.
18. Press “9”.
19. “Press and Hold Yes to Fill” alternating with “Yes” is displayed.
20. Hold down “9” to fi ll pot to desired level.
21. “Filling” is displayed while button is depressed.
22. “Continue Filling Yes/No” is displayed
23. Press “9” to continue fi lling or “8” to Exit program.
*NOTE: If the waste tank is full, the computer displays “RTI Tank Full.” Call RTI.
DISPOSE TO WASTE:
1. Hold down “Filter” button until computer beeps twice.
2. Scroll down to “dispose” using “Info” button and press “9” button.
3. “Dispose? Yes/No is displayed.
4. Press “9”.
5. “Draining” is displayed.
6. “Vat Empty? Yes is displayed.
7. Press “9”
8. “Cln Vat Complete? Yes” is displayed.
9. Press “9”.
10. “Open Dispose Valve” is displayed.
11. Open dispose valve by pulling completely forward to start disposal.
12. “Disposing” is displayed for four minutes.
13. “Remove Pan” is displayed.
14. Slide the fi lter pan slightly out of the fryer.
15. “Is Pan Empty? Yes/No” is displayed.
16. Press “9” if the fi lter pan is empty. Select “8” if pan still has oil in it.
17. “Close Dispose Valve” is displayed.
18. Close the dispose valve ensuring the handle is pushed completely towards the fryer.
19. “Insert Pan” is displayed.
20. “Fill Vat From Bulk? Yes/No” is displayed.
21. Press “8” if you wish to leave pot empty and exit.
36
LOV™ Generation II Technical Reference
FILTER NOW? YES/NO
CONFIRM YES/NO
SKIM VAT
FILTER NOW? YES/NO
CONFIRM YES/NO
SKIM VAT
FILL VAT FROM BULK:
1. Hold down “fi lter” button until computer beeps twice.
2. Scroll down to “Fill Vat from Bulk” using the Info button.
3. Press “9”.
4. “Fill Vat from Bulk? Yes/No” is displayed.
5. Press “9”.
6. “Press and Hold Yes to Fill / Yes” is displayed.
7. Press and hold down “9” to fi ll pot to desired level.
8. “Filling” is displayed during fi ll.
9. Release button to stop fi lling.
10. “Continue Filling? Yes/No” is displayed.
11. Press “8” to exit.
FILL JUG FROM BULK:*
1. When “Orange” indicator light is on, the top-off jug is empty.
2. To refi ll jug press and hold the orange reset button above the jug until the jug is full.
3. Release the button to stop fi lling.
*NOTE: The jug may not fi ll if any of the following are in progress:
If
FILTER NOW? YES/NO,
CONFIRM YES/NO, or
SKIM VAT is displayed, the ll jug
button is disabled until either a fi lter is complete or until no is chosen.
The system also checks these conditions. The following must be met before jug fi ll is allowed:
Solenoid closed –
Orange ll button pressed longer than 3 seconds.
Waste valve closed.
FILTER NOW? YES/NO,
CONFIRM YES/NO, or
SKIM VAT cannot be
displayed.
System power cycle (all boards – computers, MIB, AIF and ATO) after changing setup from JIB to Bulk (use momentary reset).
No fi ltration or other fi lter menu selection can be in process.
Other factors that may not allow fi ll jug from bulk –
Defective solenoid.
Defective switch.
RTI pump issue.
RTI relay stuck.
If using two fryer systems that are both attached to the RTI system, they may not be able to fi ll both units at the same time if they have an RTI unit with a single head. Some RTI units have dual heads which can fi ll simultaneously.
37
LOV™ Generation II Technical Reference
Board and Computer Replacement
Readdress All Boards
It is necessary to readdress any replaced boards by resetting all power to the entire fryer battery system.
The control power reset switch is a momentary rocker switch located behind the control box above the JIB that resets all power to all the computers and boards in the fryer. Press and hold the switch for at least 10 seconds when resetting the control power to ensure power has suffi ciently drained from boards. After releasing the momentary control power reset switch, wait at least 20 seconds until the MIB board has completely reset and all LEDs have stopped blinking before starting a function.
ATO Board, LON Gateway, ATO Pump Relay, and Transformer Replacement
The LON gateway and ATO board are located inside the box behind the JIB. The LON gateway covers the ATO board and must be removed to access it. Both are connected to single phase power from the control box.
1.
Disconnect the fryer from the electrical power supply .
2.
Locate the ATO box behind the JIB (Jug In Box).
3.
Remove the cover to expose the transformers, relay , and LON gateway (if installed; see image below , left).
4.
Mark and unplug any wires or harnesses.
5.
Once the LON gateway is removed, the ATO board is visible (see image below , right).
6.
Replace the defective component and reattach all wires or harnesses.
7.
Replace the cover.
8.
CYCLE POWER TO ENTIRE FR YER SYSTEM (see section above).
9.
Press the TEMP button on one of the M3000 computers to verify software version of the ATO. If the version is not visible, the ATO may not be connected properly .
ATO box interior, with LON gateway still installed.
38
ATO box interior, with LON gateway removed to expose ATO board.
LOV™ Generation II Technical Reference
MIB Replacement
The MIB controller is located inside the left cabinet (see image below). In normal operation, a cover hides the MIB controls. The LED display is visible.
1. Disconnect the fryer from the electrical power supply .
2. Remove the three torx screws from the MIB cover, exposing the MIB board (see image at right).
3. Remove the screw in the center top will allow the board to hinge down and expose the connections on the back of the board.
4. Disconnect the MIB board by carefully removing the plugs on the rear of the board (see image at right).
5. Replace with a new MIB board and reverse steps to reassemble.
6. Once replaced, reconnect the power.
7. Cycle all power to the unit to readdress the fryer using the steps on the previous page.
Cover
1 screw
MIB controller cover (three screws hold it in place).
2 screws
AIF Replacement
The AIF boards are located inside a protective housing underneath each frypot.
1. Disconnect the fryer from the electrical power supply.
2. Locate the AIF board to be replaced under a frypot.
3. Mark and unplug the harnesses.
4. Locate the screw on the front of the AIF assembly holding it in place.
5. Remove the screw and the front of the assembly drops down and the back tab slides out of the bracket attached to the frypot (see below).
6. Reverse steps to reassemble, ensuring that the new AIF assembly slides into the slot in the rear of the bracket.
7. Cycle all power to the unit to readdress the fryer using the steps on the previous page.
Remove this screw that secures the AIF board to the fryer.
After removing the screw, the AIF assembly drops down.
39
The bottom tab slides out of the bracket attached to the frypot.
LOV™ Generation II Technical Reference
M3000 Computer Replacement
The M3000 computer is located on the front of the fryer.
Disconnect the fryer from the electrical power supply.
1.
The controller bezel is held in place by tabs at the top and bottom. Slide the metal bezel
2.
up to disengage the lower tabs. Then slide the bezel down to disengage the upper tabs. Remove the two screws from the upper corners of the control panel. The control panel is
3.
hinged at the bottom and will swing open from the top. Unplug the wiring harnesses from the connectors on the back of the computer, marking
4.
their position for reassembly, and disconnect the grounding wires from the terminals. Re­move the computer assembly by lifting it from the hinged slots in the control panel frame.
Ground Wire
Terminal
Communication
Harnesses
Install the replacement computer. Reinstall the control panel assembly by reversing steps
5.
1 thru 4. Setup the computer following the instructions on page 4-9 in the Installation and Opera-
6.
tion manual. Setup MUST be performed after replacement. Cycle all power to the unit to readdress the fryer using the steps on page 37.
7.
ATO Pump Replacement
Disconnect the fryer from the electrical power supply .
1.
Locate the ATO pump, behind the ATO box. Mark and unplug any wires or harnesses.
2.
Press up from the bottom on the quick disconnects to release the plumbing. The plumbing can be
3.
pulled from the pump. Loosen the four nuts attaching the pump to the pump tray .
4.
Replace the defective component and reverse above steps, and then reconnect power.
5.
Ground Wire
Terminal
20-Pin Connector
Locator
Wire
ATO pump.
Quick disconnect.
40
LOV™ Generation II Technical Reference
Wiring Diagrams
LOV™ Electric Fryer
START OF 6-WIRE
DATA & POWER
41
LOV™ Generation II Technical Reference
LOV™ Gas Fryer
START OF 6-WIRE
DATA & POWER
42
LOV™ Generation II Technical Reference
Data Network Flow Chart
J7
120 Ω Pins 2 & 3
START OF 6-WIRE
DATA AND POWER
(24VDC) HARNESS
Right
M3000
J6
3-wire harness
J7
Middle
M3000
J6
3-wire harness
J7
Left
M3000
J6
3-wire harness
J1
MIB
J2
J4
Turn each computer to OFF. Press the TEMP button on each computer and verify ALL software versions are present (M3000, MIB, AIF, ATO and LON on US only). A missing version may indicate an open connection. Connections from the MIB to the AIF boards carry 24VDC on the gray cable.
3-wire harness
6-wire harness
6-wire
harness
NOTE: Pins 2 & 3 can
be tested on any plug throughout the system and should read 120Ω.
The data network plugs on the boards can be swapped. (ie. J4 and J5 on the AIF board.)
120 Ω Pins 2 & 3
J10
Left
AIF
J5
J4
Middle
AIF
J5
J4
Right
AIF
J5
J9
ATO
Oil Level
Sensor
(gas only)
6-wire
harness
Oil Level
Sensor
(gas only)
6-wire
harness
Oil Level
Sensor
(gas only)
6-wire
harness
For systems that have a LON Board and/
or 4 or 5 battery systems have an
additional ATO Board.
6-wire harness
J9
ATO
J10
6-wire harness
J9
nd
ATO board only
2 in 4 and 5 batteries
2nd ATO
J10
6-wire harness
J203
120 Ω Pins 2 & 3
LON
J202
43
LOV™ Generation II Technical Reference
Pin Positions
ATO (Automatic Top Off) Pin Positions and Harnesses
Connector From/To Harness # Pin # Function Voltage Wire Color
RTI Add Solenoid
ATO Pump Relay 4 24VAC Ret 24VAC Black
J8
J4 (Rear) /
J5 (Front)
J3 - Vat #3 J2
- Vat #2 J1
- Vat #1
J6 Orange LED 8074555
J7
J10
J9 AIF J5 8074546
JIB Reset Switch 8 JIB Low Reset 16VDC Black
RTI Add Solenoid 9 24VAC 24VAC Red
ATO Pump Relay 12 24VAC 24VAC Red
JIB Reset Switch 16 Ground 16VDC Red
Transformer 8074553
ATO RTD
Network Resistor
(pins 2 & 3)
or to next ATO Board
(4 & 5 vat units)
8074671
8074655 - Vat #1 8074654 - Vat #2 8074621 - Vat #3
8074552
1 24VAC Ret 24VAC Black 2 3
5 6 7
10 11
13 14 15
1 24VAC Ret 2 24VAC Blue 3 4 5 12VAC Ret 6 12VAC Brown 7 8 1 DV - Probe Ground 2 DV - Probe Red 3 FV - Probe Ground White 4 FV - Probe Red 1 16VDC 2 16VDC Ret Red 1 2 3 Ground 4 RB7/DATA 5 RB6/CLOCK 1 Ground Black 2 CAN Lo Red 3 CAN Hi White 4 5VDC+ 5VDC Black 5 24VDC 24VDC Red 6 Ground White 1 Ground Black 2 CAN Lo Red 3 CAN Hi White 4 5VDC+ 5VDC Black 5 24VDC 24VDC Red 6 Ground White
24VAC
12VAC
Ohm
16VDC
Orange
Red
White
Black
44
LOV™ Generation II Technical Reference
MIB (Manual Interface Board) Pin Positions and Harnesses
Connector From/To Harness # Pin # Function Voltage Wire Color
1 Ground Black 2 CAN Lo Red
J1 M3000 J7 8074546
J2 AIF J4 8074547
Transformer
Filter Relay
Blue LED
J5
J6
RTI Open Switch RTI Closed Switch
Pan Switch
RTI Open Switch 15 Ground - White
RTI Closed Switch 16 Ground - Green
To RTI connection in rear of
fryer
8074649 RTI
8074844
NON-RTI
8074760
3 CAN Hi White 4 5 6 1 Ground Black 2 CAN Lo Red 3 CAN Hi White 4 5VDC+ 5VDC Black 5 24VDC 24VDC Red 6 Ground White 1 24VAC 2 24VAC Ret White 3 Pump Motor 4 Pump Motor Green 5 Blue LED + 6 Blue LED - Black 7 Open Switch + Black 8 Closed Switch + Red
9 10 11 Pan Sw + 12 Pan Sw - Red 13 14
1 From RTI transformer 24VAC Black
2 Common White
3 To RTI “Add Pump” Relay 24VAC Green
4
5
6
7
From RTI “Waste Tank Full
8
Sensor” Test Pins 2 to 8
24VAC
24VDC
24VDC
24VDC
24VAC – Full
0VAC – Not
Full
Black
Red
Red
Black
Red
45
LOV™ Generation II Technical Reference
MIB (Manual Interface Board) Display Diagnostics
DISPLAY LED EXPLANATION
Drain
Vat # (The vat number is followed by an “L” to indicate left side of a split vat or an “r” to indicate the right side of a split vat or a full vat.)
Vat # (The vat number is followed by an “L” to indicate left side of a split vat or an “r” to indicate the right side of a split vat or a full vat.)
On Drain valve on vat # is open.
Off Drain valve on vat # is closed.
Vat # (The vat number is followed by an “L” to indicate left side of a split vat or an “r” to indicate the right side of a split vat or a full vat.)
Return
Vat # (The vat number is followed by an “L” to indicate left side of a split vat or an “r” to indicate the right side of a split vat or a full vat.)
Vat # (The vat number is followed by an “L” to indicate left side of a split vat or an “r” to indicate the right side of a split vat or a full vat.)
Vat # (The vat number is followed by an “L” to indicate left side of a split vat or an “r” to indicate the right side of a split vat or a full vat.)
Network
N
Resetting
r
Miscellaneous
E alternating with vat # (The vat number is followed by an “L” to indicate left side of a split vat or an “r” to indicate the right side of a split vat or a full vat.)
Blink
On Return valve on vat # is open.
Off Return valve on vat # is closed.
Blink
Blink
Drain valve on vat # is opening or closing or an error condition may exist.
Return valve on vat # is opening or closing or an error condition may exist.
Network error, displays for 10 seconds in no communications are received from the M3000 within 10 seconds after power on or MIB reset.
An “r” is displayed for ten seconds or until communication is received from the M3000 after a power on or MIB reset.
The circuit has an issue. Ensure the actuator is plugged in. Ensure the CAN connections are all securely plugged into the connectors.
A
Vat # (The vat number is followed by an “L” to indicate left side of a split vat or an “r” to indicate the right side of a split vat or a full vat.)
P
Manual LED off
Manual LED on
46
Indicates the AIF temperature sensor did not detect a full vat during fi ltration.
The system is in auto fi ltration mode.
The system is in manual mode.
This will only be displayed in auto ltration mode. Filter pan is improperly seated. Any auto fi ltration messages received at this time are ignored.
LOV™ Generation II Technical Reference
AIF (Auto Intermittent Filtration) Actuator Board Pin Positions
Connector From/To Harness PN Pin # Function Voltage
1 Ret + (Open) 24VDC Black
J1 FV Return N/A
FV AIF RTD
DV AIF RTD
J2
J3 DV Return N/A
J4
J5
J6 FV Drain N/A
J7 DV Drain N/A
Oil Level Sensor
(Gas)
Locator Pin
Locator 16 Locator Signal Black
8074547
MIB J2 or
AIF J5
AIF J4 or
ATO J10
AIF Board
Communication and
Power
8074547
AIF Board
Communication and
Power
2 Ret – (Closed) 24VDC Red 3 Ret Position Purple 4 Ground White 1 Ground White 2 FV - Temp Red 3 Ground White 4 DV - Temp Red 5 6 7 8
9 DV – OLS (Gas) Black 10 FV – OLS (Gas) Red 11 Locator Vat #5 12 Locator Vat #4 13 Locator Vat #3 14 Locator Vat #2 15 Locator Vat #1
1 Ret + (Open) 24VDC Black
2 Ret – (Closed) 24VDC Red
3 Ret Position Purple
4 Ground White
1 Ground Black
2 CAN Lo Red
3 CAN Hi White
4 5VDC+ 5VDC Black
5 24VDC 24VDC Red
6 Ground White
1 Ground Black
2 CAN Lo Red
3 CAN Hi White
4 5VDC+ 5VDC Black
5 24VDC 24VDC Red
6 Ground White
1 Drain + (Open) 24VDC Black
2 Drain – (Closed) 24VDC Red
3 Drain Position Purple
4 Ground White
1 Drain + (Open) 24VDC Black
2 Drain – (Closed) 24VDC Red
3 Drain Position Purple
4 Ground White
Wire
Color
Black
47
LOV™ Generation II Technical Reference
M3000 Board, Harnesses, and Pin Positions
Connector From/To Harness PN Pin # Function Voltage Wire Color
1 12VAC In 12VAC
2 Ground
3 12VAC In 12VAC
4 FV Heat Demand
5 V Relay 12VDC
6 DV Heat Demand
7 R/H B/L 12VDC
8 Analog Ground
807-4199
J2
J6
J7
J9 ONLY USED ON NON-AIF UNITS
J10
J11 SD Card
Interface Board
to Computer
Next M3000
J7 or Network
Resistor
MIB J1 or
previous
M3000 J6
Interface Board
Ground to Computer
SMT Computer to
Interface Board
Harness
807-4546
Computer Commu-
nication Harness
807-4546
Computer Commu-
nication Harness
807-4573
Computer Locator
Harness
9 L/H B/L 12VDC
10 ALARM
11 Sound Device 5VDC
12 ALARM
13 FV Probe
14 Common Probes
15 DV Probe
16
17
18
19
20
1 Ground Black
2 CAN Lo Red
3 CAN Hi White
4
5
6
1 Ground Black
2 CAN Lo Red
3 CAN Hi White
4
5
6
1 Vat #1
2 Vat #2
3 Vat #3
4 Vat #4
5 Vat #5
6
Black
Black
48
Frymaster L.L.C.
8700 Line Avenue, Shreveport, LA 71106
Service Center (800) 551-8633 or (318) 865-1711
Printed in the United States of America English © 2009 February 23, 2010
Loading...