TSP-LPGF Float
Installation Instructions with Tank Isolation Sleeve
The TSP-LPGF oat must be installed before securing the
customer supplied isolation sleeve into the LPG storage
vessel.
1. Remove the retaining ring from the end of the
isolation sleeve.
2. Orient the oat on the shaft so that the “M” is on the
top. Slide the TSP-LPGF over the end of the isolation
sleeve.
3. Re-install the retaining ring.
Franklin Fueling Systems
TSP-LL2 probe
Apply sealant here
(Step 6)
4. Using the isolation sleeve manufacturer’s installation
instructions, carefully install the isolation sleeve into
the opening in the LPG storage vessel making sure
the oat is not damaged in the process. Puncturing
the oat may impede its function.
5. After completing the installation of the isolation
sleeve according to the manufacturer’s installation
instructions, slide a Franklin Fueling Systems TSPLL2 probe into the isolation sleeve.
6. Seal the area between the isolation sleeve and the
TSP-LL2 probe using silicone RTV or equivalent
outdoor sealant.
Refer to Franklin Fueling Systems TSP-LL2 Probe
Installation Instructions for probe installation and operation
information.
Customer-supplied tank
isolation sleeve
“M” marks location of
magnets
Franklin Fueling Systems
TSP-LPGF oat
Customer-supplied tank
isolation sleeve retaining ring
©2008 FFS 000-0094 Rev. B