Forney DR6101E User Manual

FLAME DETECTORS
DR6101E DUAL RANGE AMPLIFIER
S
IMULTANEOUS PROCESSING OF BOTH ULTRAVIOLET AND INFRARED
FLAME DETECTION
.
The Forney DR6101E is a microprocessor based, dual-range
flame amplifier. This two-range design allows the DR6101E to independently monitor and
vides a separate flame signal output for each flame detector connected. The DR6101E
is compatible with any two IDD-II, IDD-UV, or UV-4; or one DR 6.1 (a UV and IR in
one package).
The DR6101E measures frequency and amplitude across the entire spec-
trum sensed by the detector(s) and converts input data into an easy-to-read
pulse-per-second output. Flame-on and flame-off setpoints can be precisely
and discretely programmed with Forney’s SMARTDisplay™(a hand-held ter-
minal). The microprocessor within the DR6101E also stores diagnostic infor-
mation and error messages that can be downloaded to the SMARTDisplay.
The Forney DR6101E is available as a panel mount (PM) or rack mount
(RM) amplifier. The DR6101E can be mounted inside a local or remote con-
trol cabinet. Field wiring terminations can be made directly to the removable
card edge connectors.
• DUAL-RANGE OPERATION–
with
simultaneous processing of ultraviolet
and infrared detector inputs, the
DR6101E can do the work of two
amplifiers.
• ANALOG INTENSITY–
flame intensity
output of 0-10 vdc, or 4-20 mA are
available for each detector input.
• ENHANCED DISCRIMINATION of
flame-on/flame-off conditions–
unique pulse-per-second output allows
precise tuning and programming to
optimize system performance.
• ELECTRONIC SELF-CHECKING
FUNCTION–
periodically checks the
flame sensor to ensure that detector
circuits respond to an actual loss-of-
flame condition.
• DETECTOR COMPATIBILITY–
with all
versions of IDD-II, IDD-UV, UV-4, and
DR-6.1 detectors. The DR6101E can
replace most previous Forney flame
amplifiers in any application with
complete compatibility.
• LED STATUS DISPLAYS–
indicate
status of amplifier operating functions.
RM DR6101E Amplifier
PM DR6101E Amplifier
Forney Corporation
3405 Wiley Post Road Carrollton, TX 75006 USA Tel: 972.458.6100 Fax: 972.458.6650 www.forneycorp.com
TECHNICAL BULLETIN
PUBLICATION #404005-07 REV 03/03
DR6101E Dual Range Flame Amplifier
FLAME DETECTORS
PRODUCTS AND ACCESSORIES
PM-DR6101E Amplifier
Part #38879801 RM-DR6101E Amplifier Card Part #38805601 Amp Rack (8 slot) Part #40432502 SMARTDisplay™ Part #36483901 Tuning Software Part #39847400
Runs with PCMCIA Card AD converter Part #9196200 Cable 40’ (for IDD-II, IDD-UV, UV-4) Part #39985404 Cable 40’ (for DR 6.1) Part #39985604
SPECIFICATIONS
Temperature: 0° to 55°C (32° to 131°F) Humidity: 5% to 95% noncondensing P
anel Mount Power Requirements: 110/220 VAC, 50/60 Hz @ 12 VA Dimensions: 26.2 cm x 20.7 cm x 10.2 cm (10.3” x 8.3” x 4.0”) Weight 2.5 kg (5lbs. 8oz.) R
ack Mount Dimensions: PC card - 12” x 6.5” x 1.75”
Amp Rack - 17.5” H x 19” W x 8.3” D Weight 0.47 kg (1lb 3.2oz) Output Relay Rating: Form C SPDT(3)
5A at 125vac or 250vac
5A at 30vdc Minimum Pickup Time: 1.0 sec Nonvolatile RAM: 10-year battery Compatible Flame Detectors: IDD-IIL, Infrared Detector for Lignite
IDD-II, Filtered, Infrared Detector
IDD-IIU, Unfiltered, Infrared Detector
IDD-UV, Solid State UV Detector
UV-4, UV Tube Detector DR-6.1, IDD/UV Infrared/Ultraviolet Detector
Loading...