Fluke 360 AC Data Sheet

Fluke 360
AC Leakage Current Clamp Meter
The Fluke 360, a rugged and accurate solution for leakage current measurement
Ideally designed for non-invasive checks of insulation condition, the Fluke 360 allows you to perform tests without powering down the installation or disconnecting equipment ­saving you time, without compromising on quality or safety. The unique jaw design of the Fluke 360 eliminates the influence of adjacent current conductors, and minimizes the effects of external magnetic fields, even at low currents. This allows you to perform accurate and reliable tests in today’s crowded electrical environments. The tough and high-quality clamp design of the Fluke 360 guarantees high stability for long-term repeatability.
Technical Data
Measurement of leakage current with 3 mA range and 1 µA of
resolution, for accurate monitoring of insulation erosion
Broad range of measurement, from 1 µA up to 60 A, for all installation
needs
Advanced shielding to ensure accurate results when measuring near
The high durability clamp construction can withstand over 50,000
operations - added ruggedness that extends the life of your clamp.
Easy-to-carry, pocket-sized clamp with wide 40 mm (1.5 in) jaw size
Handy “Display-Hold” button for capturing readings in hard-
to-reach places
Auto power-off, with warning buzzer, saves battery life
Conformance to IEC1010 and EMC standard for confident
measurements
Meets all of the applications and performance classes in safety
standard VDE0404-4 and VDE0702 for leakage current and differential current measurement of electrical appliances
Special Features
IEC 61010 and EMC Conformance
IEC 61010 safety features including a tactile barrier and special jaw design provide the user with confidence when making measurements in hazardous voltage areas.
High Accuracy
Advanced jaw design means that the Fluke 360 accuracy is little affected by external magnetic fields even at low
currents. Typical external current rejection is 200,000:1. Conformance to EMC standards ensures high reliability through reduced susceptibility to electromagnetic interference. The Fluke 360 also meets the latest safety standard VDE0404-4 and the new VDE0702 requirements.
General Specification
Method of detection Mean value Display Digital display: 3200 counts
Bar-graph display: 32 segments, LCD
Measurement cycle 2 times/second (Digital display), 12 times/second (Bar-graph display) Range switching Auto-range Ambient temperature and humidity 0 °C to 50 °C, 80 % R
Temperature coefficient 0.05 % of range/°C or less (within the ranges of 0 °C to 18 °C and
28 °C to 50 °C for measurement of 0-50 A)
Influence of external magnetic field 0.0005 % typical 1 (on current value of adjacent cable) Influence of conductor position Within accuracy
Circuit voltage Safety standard EN 61010-1, EN 61010-2-032. 300 V CAT II, Pollution Degree 2 Withstanding voltage 3.7 kV ac for one minute Battery type 1 x 3 V Lithium battery (button cell) CR2032 Battery life Approx. 90 hours (when continuously used) Auto power-off Approx. 10 minutes Diameter of measurable conductor 40 mm max. Weight 200 g (0.441 lb) Dimension 176 mm x 70 mm x 25 mm (6.9 in x 2.8 in x 1 in) Operating altitude 2000 m (6,562 ft)
300 Vrms
or less (no condensation)
H
Electrical Specification
Specifications at 23 ± 5 °C. 80 % R
max
H
Accuracy: ± (% rdg + dgt) = ± (% readout + value of least significant digit)
AC Current Measurement
Measuring range Resolution Accuracy Max Permissible current
3 mA 0.001 mA
30 mA 0.01 mA
30 A 0.01 A 60 A 0.1 A
Mean value detection and rms-value calibration. Accuracy specified at 50/60 Hz Frequency range 15 Hz to 150 Hz
2 Fluke Corporation Fluke 360 AC Leakage Current Clamp Meter
1 % + 5
1 % + 5 (0~50 A)
5 % + 5 (50~60 A)
60 A rms
Fluke. The Most Trusted Tools in the World.
Fluke Corporation PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands
For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com
©2012, 2006 Fluke Corporation. All rights reserved. Specifications subject to change without notice. Printed in U.S.A. 10/2012 2791021 D-EN-N Rev B
Loading...