Fluke 345 Catalog Page

Power Quality Clamp Meter
Specifications
Fluke 345
View waveforms for equipment checking and setup
Log parameters over time to track down intermittent faults
345
The ideal troubleshooting tool for modern electrical loads
The Fluke 345 measures a wide range of electrical parameters for troubleshooting power disturbances in single- and three-phase electrical loads. With a bright color display to see waveforms and trends, a low-pass  lter to remove high frequency noise, and a high EMC immunity design, the Fluke 345 is ideal for measurements on switching loads such as variable speed drives, electronic lighting and UPS systems.
Current measurement
DC, DC rms, AC rms All measurements DC and 15 Hz to 1 kHz.
Measuring range 0 – 2000 A DC or 1400 AC rms Harmonics All measurements up to 30th harmonic (40th harmonic for 15 Hz to 22 Hz); Frequency
Voltage measurement
DC, DC rms, AC rms All measurements DC and 15 Hz to 1 kHz. Maximum overload 1,000 V rms. Volts rms is a
Measuring range 0 – 825 V DC or AC rms Harmonics All measurements up to 30th harmonic; Frequency range F0 : 15 Hz to 22 Hz and 45 Hz
Watts measurement (single- and three-phase)
Measuring range 0 – 1650 kW DC or 1200 kW ac VA measurement (single- and three-phase) DC, DC rms, AC rms Measuring range 0 -1650 kVA DC or 1200 kVA ac
VAR measurement (single- and three-phase)
Measuring range 0 – 1250 kVAR
Power factor (single- and three-phase)
Measuring range 0.3 cap…1.0… 0.3 ind (72.5° cap…0°… 72.5° ind)
Displacement power factor
Measuring range 0.3 cap … 1.0 … 0.3 ind (72.5° cap ... 0° ... 72.5° ind)
Kilowatt Hour (kWHr)
Measuring range 40,000 kWHr
Scope function
Time base 2.5 ms, 5 ms, 10 ms, 25 ms, 50 ms/div Current management: Ranges 10 A / 20 A / 40 A / 100 A / 200 A / 400 A / 1000 A / 2000 A Voltage measurement: Ranges 4 V / 10 V / 20 V / 40 V / 100 V / 200 V / 400 V / 1000 V Inrush current function All measurements DC and 15 Hz to 1 kHz Ranges 40, 400 and 2000 A Memory Up to 50 screen shots and over 150,000 individual measurement values
Maximum overload 10,000 A or RMS x frequency < 400,000. Amps rms is a true rms measurement (AC + DC).
range F0 : 15 Hz to 22 Hz and 45 Hz to 65 Hz; Iacrms > 10A
true-rms measurement (AC + DC).
to 65 Hz; Vacrms > 1V
DC, DC rms, AC rms
High safety rating: 600V CAT IV / 1000V CAT III rated for use at the service entrance
ac/dc current measurements: Clamp­on measurement of AC peak and DC current up to 2000 A without breaking the circuit
Harmonic analysis: Analyze, display and log harmonics up to the 30th harmonic (40th harmonic for 15 Hz to 22 Hz)
Verify batteries: Direct measurement of DC ripple (%) for battery and DC systems
(Check the Fluke web for detailed specifications)
106
Included Accessories
Soft carrying case, Power Log software, Test probes, Test leads, Alligator clips, International AC adapter / battery eliminator, Printed English User manual, Multi-language manual on CD
Ordering Information
Fluke 345 Power Quality Clamp Meter
Power supply: 1.5 V Alkaline AA MN 1500 or IEC LR6 x 6 Batter y Battery life (typical): >10 hours (backlight on f ull); >12 hours (backlight reduced) Safety: IEC 61010 -1 600 V CAT IV, 1000V CAT III (maximum input phase-phase 825V rms) double or reinforced insulation, pollution degree 2
Protection: IP40; EN60529 Operating temperature: 0 °C to 50 °C
TLK291
See page 146
TP220-1
See page 146
Display: Color transmissive LCD 320 x 240 pixels (70 mm diagonal) with 2 level backlight
Digital out put: USB interface to a PC Size (HxWxD): 300 mm x 98 mm x 52 mm Jaw opening: 60 mm Jaw capacity: 58 mm diameter Weight (including batteries): 0.82 kg Two Year Warranty