TECHNICAL DATA
Fluke 1630-2 FC
Earth Ground Clamp
AC LEAKAGE CURRENT
MEASUREMENT
Identify ac leakage currents without disconnecting the earth ground stake from
the grounding system–ideal for system
troubleshooting.
Stakeless earth ground loop and ac leakage current
clamp for fast, safe indoor/outdoor earth ground
resistance and ac leakage current tests.
Test the grounding components of equipment in hard-to-reach
spaces, including areas that are indoors or fully paved and do not
permit driving auxiliary test stakes. Stay on line—identify ground
loop resistance without the need to disconnect then reconnect the
earth electrode from the system.
The Fluke 1630-2 FC Stakeless Earth Ground Clamp is the kind of
high-quality, rugged tool you expect from Fluke. Heavy-duty clamp
jaw stays in alignment and in calibration even in every day,
on-the-job industrial environments.
Stakeless measurement
The 1630-2 FC clamp measures earth ground loop resistances
for multi-grounded systems using the dual-clamp jaw. This test
technique eliminates the dangerous and time-consuming activity
of disconnecting parallel grounds, as well as the process of finding
suitable locations for auxiliary test stakes. You can also perform
ground tests in places that were previously difficult: inside buildings, on power pylons or anywhere you don’t have access to soil to
place auxiliary test stakes.
With this test method, a two-process measurement is made around
the earth ground wire or bus bar using the specially-designed jaw
of the 1630-2 FC clamp. Auxiliary test stakes are not used at all.
A known voltage is induced by the source in the clamp, and the
current is measured by the sensor in the clamp. The tester automatically determines the earth loop resistance for this section of
the earthing system.
RUGGED
Heavy-duty clamp jaw stays in alignment
and in calibration even in every day, onthe-job industrial environments.
LOGGING MEASUREMENTS
The ear th ground clamp saves time by
automatically recording data at pre-set
intervals and saves up to 32,760 measurements in memory at the set logging
interval. Saves time by recording and storing measured values.
ALARM THRESHOLD
User-defined high/low alarm limits, for rapid
measurement evaluation.
BAND-PASS FILTER
Selectable band-pass filter function
removes unwanted noise from the ac leakage current measurement.
FLUKE CONNECT© WIRELESS SYSTEM
The 1630-2 FC suppor ts the Fluke Connect© Wireless System
(may not be available in all regions). Fluke Connect© wirelessly
connects the clamp with an app on your smartphone or tablet.
The app shows the ground resistance measurements on your
smartphone or tablet display. You can save these measurements,
GPS location from your phone and images to Fluke Connect Cloud
storage and share with your team.
Specifications
Electrical specifications
Maximum voltage to earth ground 1000 V
Battery type 4 x 1.5 V AA alkaline IEC/EN LR6
Battery life More than 15 hours*
Frequency range 40 Hz to 1 kHz
Ingress protection IEC/EN 60529: IP30 with jaw closed
LCD Digital reading 9999 counts
Refresh rate 4/s
Temperature Operating -10 °C to +50 °C (14 °F to +122 °F)
Storage -20 °C to +60 °C (-4 °F to +140 °F)
Operating humidity Non condensing (<10 °C) (< 50 °F)
≤90 % RH (at 10 °C to 30 °C [50 °F to 86 °F])
≤75 % RH (at 30 °C to 40 °C [86 °F to 104 °F])
≤45 % RH (at 40 °C to 50 °C [104 °F to 122 °F])
(Non condensing)
Altitude Operating 2000 m (6561 ft.)
Storage 12,000 m (39370 ft.)
Reference temperature 23 °C ±5 °C (73 °F ±9 °F)
Temperature coefficient 0.15 % X (specified accuracy)/ °C (<18 °C or >28 °C ([<64.4 °F or >82.4 °F])
Overload indication OL
Display Reading Specification with
Loop Resistance Standard
Data logging capacity Minimum of 32,760 measurements
Data logging interval 1 second to 59 minutes and 59 seconds
Safety General IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1
Measurement IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V
Current clamp for leakage current
measurements
Resistance to Earth IEC/EN 61557-5
Effectiveness of the protective
measures
Electromagnetic
compatibility
(EMC)
* In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off
Wireless radio
Frequency range 2412 MHz to 2462 MHz
Output power <10 mW
Radio frequency certification FCC ID:T68-FBLE IC:6627A-FBLE
General specifications
Conductor size 40 mm (1.57 in) approximately
Dimensions (L x W x H) 283 mm x 105 mm x 48 mm (11.1 in x 4.1 in x 1.9 in)
Weight 880g (31 oz)
Warranty One year
International IEC/EN 61326-1: Portable Electromagnetic Environment
Korea (KCC) Class A equipment (Industrial Broadcast & Communications Equipment)
USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
IEC/EN 61557-13: Class 2, ≤30 A/m
IEC/EN 61557-16: cutoff frequency 20 kHz (-3 dB)
CISPR 11: Group 1, Class B, IEC/EN 61326-2-2
Input (Ω) Minimum Maximum
0.474 0.417 0. 531
0.5 0.443 0.558
10 9.55 10.4 5
100 96 104.0
2 Fluke Corporation Fluke 1630-2 FC Earth Ground Clamp