Most facilities have grounded electrical systems, so that in the event of a lightning strike
or utility overvoltage, current will find a safe path to earth. A ground electrode provides
the contact between the electrical system and the earth. To ensure a reliable connection to earth, electrical codes, engineering standards, and local standards often specify
a minimum impedance for the ground electrode. The International Electrical Testing
Association specifies ground electrode testing every three years for a system in good
condition with average up-time requirements. This application note explains earth/ground
principles and safety in more depth and then describes the principle testing methods: 3
and 4 pole Fall-of-Potential testing, selective testing, stakeless testing and 2 pole testing.
Why Ground?
The US National Electrical Code (NEC) gives two
principle reasons for grounding a facility.
• Stabilize the voltage to earth during normal
operation.
• Limit the voltage rise created by lightning,
line surges or unintentional contact with
higher-voltage lines.
Current will always find and travel the leastresistance path back to its source, be that a utility
transformer, a transformer within the facility or a
generator. Lightning, meanwhile, will always find a
way to get to the earth.
In the event of a lighting strike on utility lines
or anywhere in the vicinity of a building, a lowimpedance ground electrode will help carry the
energy into the earth. The grounding and bonding
Figure 1: A grounding system combining reinforcing steel and
a rod electrode
Application Note
systems connect the earth near the building with
the electrical system and building steel. In a lightning strike, the facility will be at approximately the
same potential. By keeping the potential gradient
low, damage is minimized.
If a medium voltage utility line (over 1000 V)
comes in contact with a low voltage line, a
drastic overvoltage could occur for nearby facilities. A low impedance electrode will help limit the
voltage increase at the facility. A low impedance
ground can also provide a return path for utilitygenerated transients.
system for a commercial building.
Ground Electrode Impedance
The impedance from the grounding electrode
to the earth varies depending on two factors: the
resistivity of the surrounding earth and the structure
of the electrode.
Resistivity is a property of any material and it
defines the material’s ability to conduct current.
The resistivity of earth is complicated, because it:
• Depends on composition of the soil (e.g. clay,
gravel and sand)
• Can vary even over small distances due to the
mix of different materials
• Depends on mineral (e.g. salt) content
• Varies with compression and can vary with time
due to settling
• Changes with temperature, freezing (and
thus time of year). Resistivity increases with
decreasing temperature.
• Can be affected by buried metal tanks, pipes,
re-bar, etc.
• Varies with depth
Since resistivity may decrease with depth, one
way to reduce earth impedance is to drive an electrode deeper. Using an array of rods, a conductive
ring or a grid are other common ways of increasing
the effective area of an electrode. Multiple rods
Figure 1 shows a grounding
F r o m t h e F l u k e D i g i t a l L i b r a r y @ w w w . f l u k e . c o m / l i b r a r y
should be outside of each other’s “areas of influence” to be most effective (see Figure 2). The rule
of thumb is to separate the elements by more than
their length. For example: 8-foot rods should be
spaced more than 8 feet apart to be most effective.
The NEC specifies 25 ohms as an acceptable limit
for electrode impedance. The IEEE Standard 142
Recommended Practice for Grounding of Industrial
and Commercial Power Systems (“Green Book”)
suggests a resistance between the main grounding electrode and earth of 1 to 5 ohms for large
commercial or industrial systems.
Local authorities including the authority having
jurisdiction (AHJ) and plant managers are responsible for determining acceptable limits for ground
electrode impedance.
Note: Power distribution systems deliver alternating
current and ground testers use alternating current
for testing. So, you’d think we would talk about
impedance, not resistance. However, at power line
frequencies, the resistive component of the earth
impedance is usually much bigger than the reactive
component, so you will see the terms impedance and
resistance used almost interchangeably.
How do ground impedance
testers work?
There are two types of ground impedance testers.
Three and four point ground testers and clamp-on
ground testers. Both types apply a voltage on the
electrode and measure the resulting current.
A three or four-pole ground tester combines
a current source and voltage measurement in a
“lunch box” or multimeter-style package. They use
multiple stakes and/or clamps.
Ground testers have the follwing characteristics:
AC test current. Earth does not conduct dc
•
very well.
Test frequency that is close to, but distinguish-
•
able from the power frequency and its harmonics. This prevents stray currents from interferring
with ground impedance measurements.
Separate source and measure leads to compen-
•
sate for the long leads used in this measurement.
Input filtering designed to pick up its own signal
•
and screen out all others.
Clamp-on ground testers resemble a large clamp
meter. But they are very different because clampon ground testers have both a source transformer
and a measurement transformer. The source
transformer imposes a voltage on the loop under
test and the measurement transformer measures
the resulting current. The clamp-on ground tester
uses advanced filtering to recognize its own signal
and screen out all others.
Figure 2: Ground electrodes have “areas of influence” that
surround them
Ground Testing Safety
Always use insulated gloves, eye protection and
other appropriate personal protective equipment
when making connections. It is not safe to assume
that a ground electrode has zero voltage or zero
amps, for reasons given below.
To perform a basic ground test (called Fall-ofPotential) on an electrode, the electrode must be disconnected from the building. New selective
methods allow accurate testing with the electrode
still connected. See “Selective Measurements.”
A ground fault in the system might cause significant current to flow through the ground conductor.
You should use a clamp meter to check for current
before performing any impedance testing. If you
measure above 1 amp you should investigate the
source of the current before proceeding.
If you must disconnect an electrode from an
electrical system, try to do so during a maintenance
shutdown when you can de-energize the system.
Otherwise, consider temporarily connecting a
backup electrode to the electrical system during
your test.
Never disconnect a ground electrode if there is a
chance of lightning.
A ground fault in the vicinity can cause voltage
rises in the earth. The source of the ground fault
may not even be in the facility you are testing, but
could cause voltage between the test electrodes.
This can be especially dangerous near utility
substations or transmission lines where significant
ground currents can occur. (Testing grounding
systems of transmission towers or substations
requires the use of special “Live Earth” procedures
and is not covered in this app note.)
Ground impedance testers use much higher
energy than your standard multimeter. They can
output up to 250 mA. Make sure everyone in the
area of the test is aware of this and warn them not
to touch the probes with the instrument activated.
2 Fluke Corporation Checking ground electrode impedance for commercial, industrial and residental buildings.
Checking Connection Resistance
Measured
Resistance
Distance of P2 from E
Current
Spike
Potential
Spike
Electrode
Under test
Electrode/Earth
Impedance
I
V
E
P2
C2
d1d2
C2
R
H
R
E
P2C1&P1
V
I
Leading Up to the Electrode
Before testing the electrode, start by checking its
connection to the facility bonding system. Most
Fall-of-Potential testers have the ability to measure
2-pole, low ohms and are perfect for the job. You
should see less than 1 ohm:
At the main bonding jumper
•
Between the main bonding jumper and the
•
ground electrode conductor
Between the ground electrode conductor and
•
the ground electrode
Along any other intermediate connection
•
between the main bonding jumper and the
ground electrode
The Fall-of-Potential Method
The Fall-of-Potential method is the “traditional”
method for testing electrode resistance. The procedure is specified in the IEEE-81 standard “Guide for
Measuring Earth Resistivity, Ground Impedance and
Earth Surface Potentials of a Ground System.” In it’s
basic form, it works well for small electrode systems
like one or two ground rods. We will also describe
the Tagg Slope Technique which can help you draw
accurate conclusions about larger systems.
Remember: for this method, the ground electrode must be disconnected from the building
electrical service.
The tricky part comes in determining where to
drive the stakes to get a true reading of the resistance between the electrode and the earth.
At what point does the dirt surrounding the
electrode stop being a contributor of resistance
and become the vast earth? Remember that we
are not interested in the resistance between the
electrode and our stakes. We are trying to measure
the resistance that a fault current would see as it
passes through the mass of the earth.
The current probe generates a voltage between
itself and the electrode under test. Close to the
electrode, the voltage is low and becomes zero
when the P stake and electrode are in contact.
How it works
The Fall-of-Potential method connects to the
Figure 3: 3-point measurement
earth at three places. It is often called the “threepole method.” You may want to use a fourth lead
for precise measurements on low-impedance
electrodes, but for our initial discussions we will
consider three leads.
The connections are made to:
E/C1 – the ground electrode being tested
•
S/P2 – A voltage (potential) measurement stake
•
driven into the earth some distance away from
the electrode. Sometimes called the potential
auxiliary electrode
H/C2 – A current stake driven into the earth a
•
further distance away. Sometimes called the
current auxiliary electrode
Figure 3 shows this schematically and Figure 4
shows the three connections made using a typical
ground tester.
The ground tester injects an alternating current
into the earth between the electrode under test
3 Fluke Corporation Checking ground electrode impedance for commercial, industrial and residental buildings.
(E) and the current stake (C2). The ground tester
measures the voltage drop between the P2 stake
and E. It then uses ohms law to calculate the
resistance between P2 and E.
some distance from the electrode under test. Then,
To perform the test you position the C2 stake at
keeping the C2 stake fixed, you move the P2 stake
along the line between E and C2, measuring the
impedance along the way.
Figure 4: A plot of measured impedances versus position of the
potential stake allows us to see the earth impedance
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.