Current clamp set
20 A/200 A 1-, 3-phase
and 3-phase+N
These current clamp sets have been
designed for applications with Fluke
1735 and Fluke 1740 series products for
accurate non intrusive measurement of
ac currents. Using latest technologies
(integrated memory for calibration data)
provides current ranges from 0.5 A up to
200 A in a frequency range of 40 Hz to
5 kHz. The clamps are approved for the
required installation category.
Technical Data
Electrical specifications
Nominal current | n 20 / 200 A ac r.m.s.
Overload Up to 260 A ac r.m.s.
Max. non-destructive current 300 A ac r.m.s.
Conductor position influence < 0.5 % of range at 50/60 Hz
Error due to adjacent conductor ≤ 15 mA/A at 50 Hz
Phase shift at 2 kHz at 200 A < ± 1 degree
Frequency range 40 Hz to 5 kHz (- 3 dB)
Temperature coefficient 0.015 % of range/°C
Working voltage (see section safety) 600 V ac r.m.s. or dc
Accuracy (at 50 Hz)
Primary current 0.5 A to 10 A 10 A to 50 A 50 A to 100 A 100 A to 200 A
Operating error in % of reading ± 2.5 % ± 1.5 % ± 0.5 % ± 0.5 %
Phase shift Not specified < 2° < 0.5° < 1°
General specifications
Maximum conductor size 15 mm diameter, bus bar 15 mm x 17mm
Cable length 2 m
Operating temperature range -10 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Operating humidity 15 % to 85 % r.h. (non-condensing)
Weight (per clamp) 175 g
Environment temperature range +18 °C to +26 °C
Humidity 20 % to 75 % r.h.
Current Sinusoidal waveform, 48 Hz to 65 Hz, distortion factor: < 1 % , no dc
Safety standards IEC/EN61010-1: 2001
EMC standards IEC/EN 61326-1:2006
Safety 600 V CAT III, pollution degree 2
The current clamps are designed for use on insulated conductors. For using it with uninsulated conductors you have to
switch off before attaching the clamp. T he application of the clamps on unin sulated conduc tors is limited to 600 V ac r.m.s.
or dc to ground and frequencies below 1 kHz.
Dimensions (in mm)
component
IEC/EN61010-2-032:2002
IEC/EN61010-031:2002
Symbols
Do not apply around or remove from HAZARDOUS LIVE conductors.
Product is protected by double insulation.
Risk of Danger. Important information. See Instruction Sheet.
Risk of Electric Shock.
Canadian Standards Association has certified that the product meets
applicable U.S. and Canadian Standards.
Conforms to relevant European Union directives.
Ordering information
3-phase: 3024451 I20/200A Clamp PQ3
3-phase+N: 3024460 I20/200A Clamp PQ4
2 Fluke Corporation Current clamp set 20 A/200 A 1-, 3-phase and 3-phase+N
Fluke. Keeping your world
up and running.
Fluke Corporation
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2009 Fluke Corporation.
Specifications subject to change without notice.
Printed in U.S.A. 11/2009 3564620A D-EN-N
Modification of this document is not permitted
without written permission from Fluke Corporation.
®