Fisher Manual: Mounting Instructions for DVC6200/DVC2000 Digital Valve Controller on (Old NAMUR) Sliding Stem Actuator | Fisher Manuals & Guides

www.Fisher.com
may or may not
include all components shown for kit installation.
Mounting Instructions
DVC6200/DVC2000
Valve Controller on
(Old Namur) Sliding Stem Actuator
D103997X012 May 2014
Digital
Use these instructions to mount a FIELDVUE DVC6200 or DVC2000.
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before performing any maintenance operations:
Always wear protective clothing,
gloves, and eyewear.
Do not remove the actuator from the valve while the valve is still pressurized.
Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the actuator cannot suddenly open or close the valve.
Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure from both sides of the valve.
Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression.
Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
Refer to the appropriate actuator instruction manual for actuator installation, operation, maintenance, and parts identification as this manual
1. Isolate the control valve from the process line
pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
2. Install set screws into stem block.
3. Attach arm connector onto stem block set screws.
Two connecting arms are provided one suitable for use with large actuators and one for use with small actuators; select the appropriate one for the actuator being used.
DVC6200/DVC2000
Digital Valve Controller on
(Old Namur) Sliding Stem Actuator
4. Loosely (for later adjustment) attach washers and
nuts to set screws.
Mounting Instructions
D103997X012
May 2014
6. Connect array to extension arm with supplied
fasteners. Leave fasteners loose enough for fine adjustment.
7. Attach mounting bracket to actuator.
5. Attach extension arm to connector arm.
.
For Rib Actuator go to step 8a.
For Plane Actuator go to step 8b.
For Pillar Actuator go to step 8c.
DVC6200/DVC2000
(Old Namur) Sliding Stem Actuator
Mounting Instructions
D103997X012 May 2014
8a. Rib Actuator
Attach mounting bracket to actuator using supplied M8 hex head fastener.
Skip to step 9.
8b. Plane Actuator
Attach mounting bracket to actuator using supplied fasteners.
(4) M8X45 Hex Head Screws (4) External Tooth Lock Washer (4) M8 Hex Nuts
Digital Valve Controller on
8c. Pillar Actuator
Use hardware to attach mounting bracket to pillar. Ensure device mounting plane is perpendicular to array.
Hardware:
(2) M8 Round U Bolt
(4) External Tooth Lock Washer
(4) M8 Hex Nuts
Skip to Step 9
DVC6200/DVC2000
Digital Valve Controller on
(Old Namur) Sliding Stem Actuator
(Array Kit sold separately)
Ensure device mounting plane is perpendicular to array.
9. Attach alignment template to mounting bracket. Adjust array to line up with alignment template. If Actuator stroke is in the up position, use Step 10a. If Actuator stroke is in the down position, use Step 10b. Ensure that the index mark of the alignment tool will be in between the array index marks.
(Index Lines are shown below with arrows)
Mounting Instructions
D103997X012
May 2014
10a. Align array bottom index line with alignment template index line.
10b. Align array top index line with alignment template index line.