
Instruction Manual Supplement
D103469X012
FIELDVUE Instruments
Using Fisher™ FIELDVUE™ HART® Digital Valve
April 2017
Controllers with the Smart Wireless THUM
™
Adapter and a HART Interface Module (HIM)
HART communicating FIELDVUE digital valve controllers can be used in conjunction with a HART Interface Module
(HIM) and a Smart Wireless THUM adapter from Emerson Automation Solutions (figure 1). This combination allows
multiple analog signals into a control system via the HIM and remote access to diagnostics with the THUM adapter.
The Smart HART Loop Interface and Monitor from Moore Industries (shown in figure 2), and ValveLink
AMS Suite: Intelligent Device Manager can be used with the THUM adapter to implement this solution.
Note
A THUM adapter should not be used with a FIELDVUE digital valve controller firmware 4 and lower in burst mode. Since the HIM is a
HART Master and polls the FIELDVUE digital valve controller, burst mode is not required.
If the HIM replaces a device that requires the digital valve controller to be in burst mode, be sure to disable burst mode in the
digital valve controller.
Figure 1. Smart Wireless THUM Adapter from Emerson and Moore Industries HART Loop Monitor
™
software or
WIRELESS THUM ADAPTER INSTALLED ON
DVC6200 DIGITAL VALVE CONTROLLER
www.Fisher.com
HART LOOP INTERFACE AND MONITOR (HIM)

FIELDVUE Instruments
April 2017
Instruction Manual Supplement
D103469X012
Figure 2. Example of FIELDVUE DVC6200 SIS Digital Valve Controller Installed with a Moore Industries HART Loop
Monitor, the Smart Wireless Thumb Adapter and the Smart Wireless Gateway
FIELDVUE DVC6200 SIS
Digital Valve Controller
HART
Digital
Communication
Smart HART Loop
Interface and Monitor
WirelessHART
Communications
Smart Wireless
THUM Adapter
4‐20 mA Valve Control Signal
with Superimposed
HART Digital Signal
Valve 90% Open
Valve Full Open
Valve Travel
Output Pressure
®
Relay #1
Relay #2
4-20 mA
4-20 mA
Ethernet
Communication
S
S
Control
System
AMS Device
Manager
ValveLink
Software
PC
Smart Wireless Gateway
Installation and Configuration Considerations
Refer to figures 2 and 3 for installation examples.
The HIM should be configured as the Primary Master and the THUM adapter as the Secondary Master. Both devices will
be transparent on the loop and poll the digital valve controller.
The HIM updates about 2 times per second. The THUM adapter updates as configured by the user and allows
communications with ValveLink software and AMS Device Manager.
2

Instruction Manual Supplement
D103469X012
FIELDVUE Instruments
Figure 3. Example HIM Smart HART Loop Interface and Monitor and Smart Wireless THUM Adapter
Installation with a FIELDVUE Digital Valve Controller
THUM ADAPTER
HAZARDOUS AREA NON‐HAZARDOUS AREA
FISHER HF340 HART
FILTER OR LC340 LINE CONDITIONER
+
-
INTRINSIC
SAFETY BARRIER
IF REQUIRED BY
APPLICATION
+
FLD
-
4-20 mA
+ HART
HART LOOP INTERFACE
AND MONITOR (HIM)
COMM
+INB
−INB
99.999
PERC
+
SYS
-
ANALOG
OUTPUT
+OUT
−OUT
+
ANALOG OUTPUT TO
FIELDVUE INSTRUMENT
-
CONTROLLER ANALOG
INPUT CHANNEL
CONTROLLER DISCRETE
INPUT CHANNEL
YELLOW
+
RED
BLACK
WHITE
-
FIELDVUE
DIGITAL VALVE
CONTROLLER
April 2015
CONTROL ROOM
DISCRETE
NOTE:
REFER TO SMART HART LOOP INTERFACE AND MONITOR USERS' MANUAL 224‐778‐00
AVAILABLE FROM MOORE INDUSTRIES FOR MORE DETAILED WIRING INFORMATION.
OUTPUT
24 VDC POWER
Additional Information
Refer to instruction manual supplement Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor
(HIM) (D103263X012
available from your Emerson sales offices, Local business Partner, or at Fisher.com
For additional information on the HIM, refer to Smart HART Loop Interface and Monitor documentation
Industries web site, at www.miinet.com.
For additional information on the THUM adapter refer to the Smart Wireless THUM Adapter quick installation guide
(00825‐0100‐4075
www.Emerson.com.
) for detailed information on connecting the HIM to a FIELDVUE instrument. This supplement is
.
or the Moore
) or reference manual (00809‐0100‐4075) available from your Emerson sales office or
3

FIELDVUE Instruments
April 2017
Instruction Manual Supplement
Related Fisher Documents
DVC6200 and DVC6200 SIS
D DVC6200 Series Digital Valve Controller Quick Start Guide (D103556X012)
D DVC6200 HW1 Digital Valve Controller Instruction Manual (D103409X012
D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103605X012
D DVC6200 SIS Digital Valve Controller Instruction Manual (D103557X012
DVC6000 HW2
D DVC6005 Series Remove Mount Digital Valve Controller Quick Start Guide (D103784X012)
D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103785X012
DVC2000
D DVC2000 Digital Valve Controller Quick Start Guide (D103203X012)
D DVC2000 Digital Valve Controller Instruction Manual (D103176X012
)
)
)
)
)
D103469X012
Miscellaneous
D HF340 Filter Instruction Manual (D102796X012)
D LC340 Line Conditioner instruction manual (D102797X012
D Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor (HIM) (D103263X012
)
)
DVC6000 and DVC6000 SIS (Supported)
D DVC6000 Digital Valve Controllers Instruction Manual (D102794X012)
D DVC6000 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutions Instruction Manual
(D103230X012
Documents are available from your Emerson sales office, Local Business Partner, or at Fisher.com
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, THUM, and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric
Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART and WirelessHART are
registered trademarks of FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
)
.
4
E 210, 2017 Fisher Controls International LLC. All rights reserved.