WARN ING - S ev eral diff erent sources of power can
be connected to the fire alarm control panel.
Disconnect all sources of power before servicing.
Control unit and associated equipment may be
damaged by removing and/or i nserting cards, modules or inte rconnect ing ca bles w hile t he un it is e nergized. Do not attempt to inst all, service or operate
this unit until this manual is read and understood.
CAUTION - Sy stem Reacceptance Test after Soft-
ware Changes: To ensure proper system operation,
this product must be tested in accordance with NFPA
72 Chapter 7 after any programming operation or
change in site-specific software. Reacceptance testing is required a fter any c hange, additi on or del etion
of system components or after any modification,
repair or adjustment to system ha rd ware or wir ing.
All components, circuits, system operations or
software functions known to be affected by a change
must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at
least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50
devices, must be tested and proper syst em operation
verifie d.
This system meets NFPA requirements for operation
o
at 0 - 49
(noncondensing) @ 3 0
of the system's standby batteries and the electronic
components may be adversely affected by extreme
temperature ranges and humidity. Therefore, it is
recommended tha t this system and its peri pherals be
installed in an environment with a nominal room
temperature of 60 - 80
Ve rify that wire sizes are adequate for all initiating
and indicating device loops. Most devices cannot
tolerate more than a 10% I.R. drop fr o m the specified
device voltage.
C and at a relative humidity o f 85% RH
o
C. However, the useful life
o
F.
Fi re Alarm System Limitations
An auto matic fire a larm sys tem - typically made
up of smoke detectors, heat de tectors, manual pull
stations, audible warning devices and a fire alarm
control with remote not ification capability, can provide early warning of a developing fire. Such a
system, however, does not assure protection against
property damage or loss of life resu lti ng from a fire.
Any fire alarm system may fail for a variety of
reasons:
Smoke detectors may not sense fire where
smoke cannot reach the detectors such as in
chimneys, in walls, in roo fs, or on the other side
of closed doors. Smoke detect ors also may not
sense a fire on another level or floor of a building.
A second floor detector, for example, may not
sense a first floor or basement fire. Fur therm ore,
all types of smoke de tectors, both ionization an d
photoelectric types, have sensing limita tions. No
type of smoke detector can sen se every kind of
fire caused by carelessness and safety hazards
like smoking in bed, violent explosions, escaping
gas, improper storage of flammable materials,
overloaded electrical circuits, children playing
with matches or arson.
IMPORTANT! Smoke detectors must be
installed in the same room as the control panel
and in room s used by the sy stem f or the connection of alarm transmission w iring, com munications, signaling and/or po wer. If detectors are not
so located, a developing fire may damage the
alarm system, cripp ling its ability to report a fire.
Adherence to the following will aid in problem-free
installation with long-term reliability:
While insta lling a fire a la rm system may make lower insura nc e
rates possible, it is not a substitute for fire insura nce
Like all solid state electronic devices, this
system may operate erratical ly or c an be da maged
when subjected to lightning induced transients.
Although no system is comple tely immune from
lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or
outside aerial w iring is not recomm ended, du e to
an increased susceptibility to nearby lightning
strikes. Consult with the Technical Services
Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to
removing or inserting circuit boards. Failure to do
so can damage circuits.
Remove all electronic assemblies prior to any
drilling, filing, reaming or punching of the
enclosure. When possible, make all cable entries
from the sides or rear. Before making modifications, verify that they will not interfere with
battery, transformer and printed circuit board
location.
Do not ti ghte n sc rew terminal s mo re than 9 inlbs. Over tightening may damage threads,
resulting in reduced terminal contact pressure and
difficulty with screw terminal removal.
This system contains static-sensitive
components. Always ground yourself with a
proper wrist strap before handl ing any circuits so
that static charges are removed from the body.
Use static suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation,
operating and programming manuals. These
instructions must be followed to avoid dama ge to
the control panel and associated equipment.
FACP operation and reliability depend upon
proper installation.
A udible warni ng de vic es such as bells m ay
not alert people if these devices are located on
the other side of closed or partly open doors or
are located on another floor of a building.
A fire alarm system will not operate without
any electrical power. If AC power fails, the
system will operate from standby batteries
only for a specified time.
Rate-of-Rise heat de tectors may be subject
to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector
should be tested at least onc e per yea r by a
qualified fire protection specia list.
Equipment used in the system may not be
technically compatible with the control panel.
It is essential to use only equ ipment listed for
service with your control panel.
Telephone lines needed to transmit alarm
signals from a pr emis e to a central m onitoring
station may be out of servi ce or temporarily
disabled.
The most common cause of fire alarm
malfunctions, however, is inadequate maintenance. All devices and system wiring should be
tested and maintain ed by professional fire alarm
installers following written procedures supplied
with each device. System inspection and testing
should be scheduled monthly or as required by
National and/or local fire codes. Adequate written
records of all inspections sh ould be kept
1.1: Main Features..............................................................................................................................................6
2.2: About Modems............................................................................................................................................10
2.6: Program Files ..............................................................................................................................................13
3.1: Initial Use of PK-411UD.............................................................................................................................14
3.1.1: Log-in as Master...............................................................................................................................15
FIGURE 4-1: Main Menu - Operator Setup........................................................................................16
FIGURE 4-2: Operator Information .............. ...... ..... ...........................................................................17
FIGURE 4-3: New Access.......................................................................... ...... ..... ..............................18
4.2: Default Directory and File...........................................................................................................................18
FIGURE 4-4: Main Menu - Configure Directories and Files..............................................................18
8.2: Detailed Vie w of Dif fer ences............... .......................................................................................................60
FIGURE 8-5: Detailed View of Compare............................................................................................60
9.5: Central Station Acknowledge......................................................................................................................63
The PK-411UD Off-Line Programming Utility
is a versatile utility program which allows
remote programming and communicator
interrogation of the Fire•Watch 411UD/
411UDAC over standard public telephone
lines. Using this utility, the communicator can
be programmed via modem using most IBM AT
or compatible computers, including laptops,
equipped with a Hayes
Program files can be created and stored on the
PC and then downloaded to the communicator.
Use of the PK-411UD software requires a full
understanding of the 411UD/411UDAC Digital
Communicator functionality prior to an y upload
or download activity. For information on the
digital communicator, refer to the Fire•Watch
411UD, manual P/N: 50759, or Fire•Watch
411UDAC, manual P/N: 51073. Each time a
new program is created or an existing program
is modified and entered into a 411UD/
411UDAC Digital Communicator, the communicator must be thoroughly tested.
P roduct Descr iption
®
compatible modem.
1.1Main Features
• Program runs under Microsoft®
Windows
Windows
• Password protect i on with fou r separat e
authority levels
• Modem option selection window
• Operator Identification Utility provides
operator information wh ich is st ored in a
database
• Customer File Utility allows customer
configuration using separate data files
for each customer
• Download file utility (Download to
Communicator) permits versatile
program setup for programming digital
communicators. Create and customize a
master default download program or edit
existing programs
®
3.1 or higher, including
®
95
6
Document #50802 Rev.B 1/5/99 P/N 50802:B
Main Features
• Upload file utility (Upload from Communicator) permits versatile examination of retrieved communicator
• Security Features:
• File Compare utility allows location by location comparison of separate upload and download files
• Print utility allows printing of upload and download file information
• On-line Help feature
• Escape (Esc) key feature which allows the recall of the last saved item in a program field
programs and information:
✓Panel program
✓Troubleshoot data and voltages
✓Current communicator time
✓Secret Code
✓Time-out at communicator
✓Callback (with Disable option)
✓Panel Identification Number
✓Error checking (with retry on error)
✓Central Station acknowledge
Document #50802 Rev. B 1/5/99 P/N 50802:B
7
Getting Started
CHAPTER 2
The PK-411UD software provides a
conv enient and po werful t ool which can be
used to program and manipulate the
411UD/411UD AC programm ing data from
a PC or laptop. This user friendly utility
has been designed to provide many features which will enhance the communicator's programmability. In order to take full
advantage of the available features, it is
important to become familiar with the
PK-411UD functions and the environment
in which the program was designed to
operate. This chapter pro vides information
on the minimum system requirements for
the computer in which the PK-411UD will
be installed.
Some computer literacy and a rudimentary
understanding of DOS and Windows
necessary to successfully use this utility.
Even if exposure to computers is limited,
the information in this chapter along with
DOS and Windows
should provide sufficient knowledge to use
the PK-411UD program. Take the time to
read and understand the installation as
presented in this chapter.
®
reference material
Getting Sta rted
®
are
An On-line Help feature has been
incorporated into the software. For
information about a window option, use
the mouse arrow to point to the window
option button or te xt block. Cl ick and hol d
the mouse button, and move the arrow off
the selected window button or block.
Release the mouse button and then press
the F1 keyboard key to dis play the Help
window for the selected option.
The keyboard Escape (Esc) key can be
used to recall the last saved item in a
program field. This can be particularly
useful if, while typing an entry into a
program field, the programmer decides to
delete the new entry before saving it.
Pressing the Escape (Esc) key will cause
the last saved entry to be displayed in the
program field in place of the recently typed
but not saved entry.
8
Document #50802 Rev.B 1/5/99 P/N 50802:B
Basic System R equireme n ts
2 . 1 Ba sic Syste m Re quire ments
The PK-411UD Program has been designed for a
specific computer en viro nment. Although most IBM AT
or compatible computers will accommodate the
PK-411UD software, specific computer requirements
and operating systems must be adhered to. In order to
ensure proper operation of the PK-411UD software, the
minimum requirements listed below must be met.
2.1.1 System Microprocessor
Most IBM AT or compatible computers with at least a
486-66MHz microprocessor may serve as a service
terminal and will accommodate the PK-411UD
software.
2.1.2 Memory and Drive Requirements
The service terminal must have a minimum of 4 megabytes of onboard RAM in order to run the PK-411UD
software. The program must be run from a hard drive
and requires a minimum of 4 megabytes of hard drive
space to store the program.
2.1.3 Monitor
A minimum of a VGA monitor is required for adequate
display of the PK-411UD menu screens.
2.1.4 Mouse
Any IBM compatible mouse or track ball should be us ed
to run the program. The program may also be run from a
standard 101-key keyboard, although certain features
will not be accessible.
2.1.5 Microsoft® Wind ow s® Envi ro nme nt
The PK-411UD software was developed to run in a
Windows
3.1 or higher or Windows
To take full advantage of the Windows
a basic understanding of Windows
be acquired from t he many excellent books and manual s
on Microsoft
manual to provide this training, however, some of the
terms used in reference to Windows
this section.
Document #50802 Rev. B 1/5/99 P/N 50802:B
®
environment. Microsoft® Windows® version
®
Windows®. It is not the intention of this
®
95 must be installed.
®
-based software,
®
is needed and may
®
are indicated in
9
About Mode ms
2 . 2About M ode ms
A modem (modulator/demodulator) conve rts the digital data signals of a computer to audio tones in order to transmit
the serial data over standard telephone lines. The modem also converts the incoming audio tones to digital data that
the computer can use.
Two basic types of modem have been designed for IBM PCs and compatibles:
• direct connect internal modems
• direct connect external modems
The internal modem is designed as an IBM P C compati ble e xpan sion card wh ich plugs i nto the comput er's e xpans ion
slot. The main advantage of the internal modem is the relatively low cost.
An external modem incorporates its own po wer supply and RS-232 interf ace into a single package. It connects to an
IBM compatible computer through an RS-232 serial cable. The main advantages of the external modem are the simplicity of connection to an IBM compatible computer with an RS-232 serial interface and the ease with which it can
be moved from one computer to another.
Using the Configure Modem windo w, the PK-411UD can be set to operate with either an internal or external modem
with a baud rate of 1200 or higher. The PK-411UD will set it to the proper baud rate. Baud rate refers to the speed of
transmission in bits per second. Most 1200 baud modems conform to Bell 212A North American standard. Baud
rate standards set guidelines for modem manufacturers to ensure comp atibility between modems operating at the
same baud rates.
2.2.1 Compatible Modems
The following internal and external modems are supported:
• Cardinal 14400
• Cardinal 28800
• Hayes Accura 14400
• Hayes Accura 28800
• Hayes Optima 9600
• Hayes 2400 Data/9600 FAX
• Hayes 1200 Smart Modem
• Identity ID-2400
• US Robotics Sportster 1200
• US Robotics Sportster 9600
• US Robotics Sportster 14400
• US Robotics Sportster 28800
• Zoom 14400 Data/FAX
• Zoom 960 0
10
Document #50802 Rev.B 1/5/99 P/N 50802:B
Ca ble Connections
2 . 3C able Conne ctions
Direct connect modems are connected to telephone lines using standard RJ11 modular jacks and plugs.
Internal modems, which plug into the PC computer's expansion slot, connect directly to the phone line using the RJ11
connectors. An RJ11 jack is built into the modem card allowing connection to the phone line. Power for the modem
is supplied by the computer.
External modems connect to the telephone line using the RJ11 jack and plug. The modem then connects to the PC's
RS-232 serial port. A DB-9 o r DB-25 RS-232 cable is used, dependi ng on t he com puter ser ial por t con nector. Power
must be supplied to the external modem.
Note that cables are not supplied with the PK-411UD.
2.4Inventory
The PK-411UD Off-Line Programing Utility Kit (P/N PK-411UD) contains the following:
• Four 3½" floppy disks
• PK-411UD Instruction Manual P/N 50802
FIGURE 2-1:
Windows® 3.1 Dialog Box
2 .5Loa ding Softwa re
The PK-411UD software, which is supplied on four 3½"
floppy disks, m ust be loaded onto the hard drive of t he
computer to be used for uploading and downloading to the
411UD/411UDAC Digital Communicator. The software
should be loade d using Windows
2.5 .1 U sin g Windows® To Load PK-411UD
With Windows® 3.1 or higher installed and the Program
Manager being displayed, insert the PK-411U D floppy disk
labeled 'Disk 1 of 4' into the computer floppy drive. Using
the mouse pointer, click 'File' in the Program Man ager menu
line. Using the mouse, click 'Run' to select it from the list of
options under 'File'. The window shown in Figure 2-1 will
be displayed with a cursor blinking in a box labeled
'Command Line'.
With Windows
the 'Start' button. The window shown in Figure 2-2 will be
displayed. Using the mouse pointer, click 'Run' to display
the dialog box shown in Figure 2-3. The cursor will be
blinking in the box labeled 'Open'.
®
95 installed, use the mouse pointer to click
®
.
FIGURE 2-2:
Windows® 95 Start
For Windows
®
3.1 or higher and Windows® 95, type the
following in the Command Line or Open Line:
A:\SETUP.EXE
Document #50802 Rev. B 1/5/99 P/N 50802:B
11
Loading Software
If a floppy drive other than A is used, replace A
with the floppy drive in which the PK-411UD
floppy disk is inserted. Click the OK button in this
window. The computer will begin loading the
software from the floppy disk to the hard drive.
Window prompts will appear, instructing when to
insert the remaining disks. The software will also
provide prompts as indicated in “PK-411UD
Installation Prompts” on page 12.
2.5.2 PK-411UD Installation Prompts
One of the first screens to be displayed during the
installation process is shown in Figure 2-4. This
window recommends closing any application programs which may be running, before continuing
with the PK-411UD installation. After closing all
applications, click the OK button.
The window displayed in Figure 2-5 indicates
the default path for loading the software to the
hard driv e. As shown in the prompt , the program
will be loaded on the C drive in a directory called
PK411UD when the button (see Figure 2-5
arrow) is clicked. If you wish to change this
default path, type in the new information after
clicking the 'Change Directory' button.
FIGURE 2-3:
FIGURE 2-4:
Windows® 95 Dialog Box
Insta lla tion to H ard Drive
For example, if you have a partitioned hard drive
containing a D drive, you may load the program
to the D drive partition. If you wish to call the
directory something other than P K411UD, type a
different name such as PROGRAM (limit is 11
characters). To use more than 8 characters, a
period followed by up to 3 characters may be
entered, such as PROGRAM.DIR. To designate
PROGRAM as the directory name, type the
following:
D:\PROGRAM
Click the Install button (indicated by the arrow
in Figure 2-5) to continue the installation. Note
that the last floppy disk, labeled 'Disk 4 of 4',
should remain in the disk drive until installation
is completed.
FIGURE 2-5:
Insta lla tion P ath
12
Document #50802 Rev.B 1/5/99 P/N 50802:B
Program Files
The last installation window, as shown in Figure 2-6,
provides an indication that the installation is completed. Use the mouse arrow to click the OK button
in this window. The final installation process is the
creation of the Upload/Download program ICON.
2.6Program Files
The PK-411UD Off-Line Programming Utility can
be used in two ways:
• Off-line - program files can be created or
modified for later use
• On-line - the PC is connected to the 411UD/
411UDAC via modem and program files can
be transferred between the two devices.
FIGURE 2-6:
Ins tallat ion Complet ed
Document #50802 Rev. B 1/5/99 P/N 50802:B
13
User Interface
CHAPTER 3
Following the completion of the PK-411UD
program installation, a window is created with the
PK-411UD ICON as shown in Figure 3-1. Run
Upload/Download program by placing the mouse
pointer on the ICON and double clicking.
The Copyright window, the first window displayed
when the PK-411UD program is run, is shown in
Figure 3-2. Read the information displayed before
proceeding with the PK-411UD Upload/Download
program. Clicking the OK button indicates agreement and compliance with this statement.
Note that from this point on, all subsequent menus
can be accessed and functions performed using the
keyboard. This is especially useful when a mouse
is not avai lable. Mo ve bet ween bu ttons or f ields v ia
the 'Tab' key, followed by pressing the 'Enter' key.
Note that all of the windows which appear while the
PK-411UD software is being used can be centered
on the PC (service terminal) screen by pressing and
holding the Control (Ctrl) key while pressing the
'C' key on the key boar d.
User Interfa ce
he
t
FIGURE 3-1:
FIGURE 3-2:
PK-411UD ICON
Copyright W indow
3.1Initial Use of PK-411UD
The window shown in Figure 3-3 will appear only
on initial use of the PK-411UD Upload/Download
program. The primary (mast er) program operat or is
assigned at this time. The flashing cursor will be in
the top box labeled Last Name. The primary or
master operator types in the last name and then
places the mouse cursor in the First Name box and
clicks. The cursor moves to the next field labeled
First Name where the operator types the first name.
The mouse cursor is placed in the Operator Password box and clicked. The cur sor now mo ves to the
Operator Password field. A user defined password
consisting of at least 1 but not more than 8
alphanumeric characters is typed in. The name and
password should be checked and confirmed for
accuracy. If satisfied with this data, position the
mouse pointer on the Update key and click to store
this information. The software is now registered to
the individual entering this data. This window will
not appear on subsequent start-ups of the
PK-411UD program.
FIGURE 3-3:
Initia lization Windo w
14
Document #50802 Rev.B 1/5/99 P/N 50802:B
Initial Use of PK-411UD
3.1.1 Log-in as Master
Following the Initialization window shown in Figure 3-3, or each time the Upload/Download program is run after
initialization, the window shown in Figure 3-4 will appear. The operator must type in the Last Name, the First Name
and the previously assigned password. Movement from one entry field to the next is accomplished by pressing the
Enter key, the Tab key or by us ing the mouse arrow to click the next field. Once the Password is keyed-in, click the
OK
button or press the Enter ke y twi ce.
It should be noted that for security reasons, the password is not displayed as it is typed (asterisks appear instead).
Make certain the password is typed correctly since there is no visual confirmation. Any incorrect entries during
Log-in will result in a message window stating 'Error With Log-in'.
FIGURE 3-4:
Log-in
Following a successful Log-in, the window shown in Fig. 3-5 will be displayed.
FIGURE 3-5:
Communica tor S election Window
After selecting the type of Communicat or, the Main Menu window shown in F igure 4-1 wil l be display ed. The menu
options are grouped under the headings of
Data Entry, Utilities, Communications, Setup
Secret Code
and
. Each
menu option is described in the sequence in which it would normally be used for an initial 411UD/411UDAC Digital
Communicator upload or download.
Document #50802 Rev. B 1/5/99 P/N 50802:B
15
Setup
CHAPTER 4
The Setup options include:
✓Operator setup, which allows the creation of new operators
✓Default Directory and File setup, which allows the configuration of a default program file and
directory
✓Modem setup, which allows PC and modem configuration
Setup
4.1Operator
This optional menu selection may be used to create new users and maintain existing operators. The individual
designated as the Master (Level 0 access) during the program initialization process, has access to all program o ptions
and features. The Master may, howeve r , designate an alter nate Master for Le v el 0 or limited access to Le ve ls 1, 2 and
3 as described in the following paragraph.
FIGURE 4-1:
Main Menu - Operator Setup
16
Document #50802 Rev.B 1/5/99 P/N 50802:B
Operator
Figure 4-2 shows the window which will be displayed by clicking the Oper ator button. The Name fields in this
display will contain the name of the individual who initially installed the PK-411UD program and is designated the
master. This window allows the master to create alternate masters and designate individuals with lower access levels.
FIGURE 4-2:
Operator Information
The Record Count displayed in the lower right corner of the window indicates the number of individuals with access
to the program. The count following initialization should be 1, since the program in staller (master) is the only one
with initial access.
In the window disp layed in F igure 4- 2, cli ckin g the Pr int button will allow printing of the current operator window or
the entire operator database. Clicking the New button adds new operators. Clicking the Update button allows modification of the current operator information. Clicking the Delete button deletes (with verification) the current opera-
tor. The remaining buttons (except the Exit button) allow navigation through the operator database, in order to view
the operators who have already been entered.
To add a new operator to the access list, click the New button. The window shown in Figure 4-3 will appear. Type
the Last Name, First Name, Password and access level for the new individual. Complete each entry by pressing the
Enter key or clicking on the next field with the mouse pointer. When the password has been entered and the Enter
key pressed, the cursor will move to the Access Level box. Typing the desired Access Level will automatically cause
the adjacent box to display the allowed function for the level. Available Access Levels are as follows:
0 = Master User (all functions)
1 = Upload/Download
2 = Upload Only
3 = View/Print Files
Document #50802 Rev. B 1/5/99 P/N 50802:B
17
De fa ult D ire ctor y a nd F ile
Clicking the Cancel button will clear all data entered in this window prior to Updating. Clicking the Update button
will store this information and increment the Record Count by 1. The fields will clear in preparation for new input
data. If no new user is to be added, click the Exit button to return to the Main Operator window. From this window
click Exit to Main Men u to return to the Main Menu selections.
FIGURE 4-3:
Ne w Acce ss
4.2Default Directory and File
Click the D efault Directory and File button on the Main Menu to customize default directories and program files.
FIGURE 4-4:
Ma in Menu - Configure Directories a nd Files
18
Document #50802 Rev.B 1/5/99 P/N 50802:B
De fa ult D ire ctor y a nd F ile
Clicking the De fault Directory and F ile button will cause the window shown in Figure 4-5 to appear.
FIGURE 4-5:
Defau lt Selections
4.2.1 Def ault Directory
The field which is labeled Default Directory displays the drive and directory name, selected by the program, which
will hold files created by the program. In this example, C:\PK411UD is the default path. The drive and/ or d irectory
name may be changed by clicking in the white text block. The window shown in Figure 4-6 will be displayed.
FIGURE 4-6:
Path Locator
This window allows the user to select an alternate path for saving program files by clicking the Down Arrow symbol
in the bottom text block and selecting from the av ailable choices. Clicking the OK button will save the selection and
close the Path Locator window, returning to the window shown in Figure 4-5.
4.2.2 Install Directory
The Install Directory field displays the drive and directory name where the PK-411UD program was installed. This
field is for informational purposes only and cannot be changed.
Document #50802 Rev. B 1/5/99 P/N 50802:B
19
De fa ult D ire ctor y a nd F ile
4.2.3 Us er Default Files
User Default File
The
future programming. Clicking in the
displayed.
field allows the user to select a file name which will be used as the default or template file for
User Default File
text block will cause the window shown in Figure 4-7 to be
FIGURE 4-7:
User Default Files
In order to view all av ailable user files, it may be necessary to expand the display en tries by clicking the plus (+) signs
preceding each entry. Click all plus (+) signs until only minus (-) signs appear. The available files follow the
customer and site names. In Figure 4-7, F0000001 is one of the available user files. Double click the file to be used
as the Default User File. The window will close and the selection will then appear in the Default User File text block.
T o exit the window illustrated in Figure 4-7 without selecting a file, double click any entry in the display except a user
file. The program will return to the window displayed in Figure 4-5. Save all selections by clicking the
To exit the window without saving the changes, click the
Exit
button.
Save
button.
20
Document #50802 Rev.B 1/5/99 P/N 50802:B
Modem
4.3Modem
The PK-411UD software must be configured for compatibility with the user's service terminal (PC) communications
ports and modem setup. Click the Modem button in the Main Menu to configure the service terminal for proper
modem operation.
FIGURE 4-8:
Ma in Menu - Configure Mode m
Clicking the Modem button will display the options window shown in Figure 4-9.
FIGURE 4-9:
Co nfig ure Modem
Document #50802 Rev. B 1/5/99 P/N 50802:B
21
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.