Supplement to the MS-9600(UD)LS(C/E)
Fire-Lite Manual Document 52646 Revision B
dated 06/17/2008
Document 53587
03/20/09 Rev:
P/N 53587:A ECN 09-150
A

Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact T echnical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• T opic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
2 Supplement to the MS-9600(UD)LS(C/E) Manual Revision B P/N 53587:A 03/20/09

This Supplement provides updates to the MS-9600(UD)LS(C/E) FACP manual Revision B as indicated below:
1 Table 5.3: System Current Draw Calculations on page 177
The following table provides updated current draw values. The current draws that have changed are indicated by bold
text.
Calculation Column 1
Device Type
Main Circuit Board 1 X[0.160]= 0.160 1 X[0.253]= 0.253 1 X[0.103]= 0.103
ANN-80 [ ] X[0.037]= [ ] X[0.040]= [ ] X[0.015]=
ANN-(R)LED [ ] X[0.028]= [ ] X[0.068]= [ ] X[0.028]=
ANN-RLY [ ] X[0.015]= [ ] X[0.075]= [ ] X[0.015]=
ANN-I/O [ ] X[0.035]= [ ] X[0.200]= [ ] X[0.035]=
ANN-S/PG [ ] X[0.045]= [ ] X[0.045]= [ ] X[0.045]=
ACM-8RF [ ] X[0.030]= [ ]
ACM-16ATF
ACM-32AF
AEM-16ATF
AEM-32AF
AFM-16ATF
AFM-32AF
AFM-16AF [ ] X[0.025] [ ]
DACT-UD2 [ ] X[0.020] [ ] X[0.029]= [ ] X[0.017]=
LDM-32F [ ] X[0.040] [ ]
LDM-E32F [ ] X[0.002] [ ] X[0.018]= [ ] X[0.002]=
LCD-80F & LCD-80FC [ ] X[0.064] [ ] X[0.064]= [ ] X[0.025]=
4XTMF [ ] X[0.005]= [ ]
4-wire Detector Heads [ ]
Power Supervision
SLC-2LS Expander [ ] X[0.02500]= X[0.02600]= [ ] X[0.01900]=
SD350T & SD355T [ ] X[0.00030]= [ ] X[0.00030]=
AD350 & AD355 [ ] X[0.00030]= [ ] X[0.00030]=
H350R & H355R [ ] X[0.00030]= [ ] X[0.00030]=
D350P & D350PL [ ] X[0.00030]= [ ] X[0.00030]=
D350RP & D350RPL [ ] X[0.00030]= [ ] X[0.00030]=
B224RB Relay Base [ ] X[0.00050]= [ ] X[0.00050]=
B224BI Isolator Base [ ] X[0.00045]= [ ] X[0.00045]=
Current Draw from TB3
Sum each column
‡‡
Relays
CP350 & CP355 [ ] X[0.00030]=
SD350 & SD355 [ ] X[0.00030]= [ ] X[0.00030]=
H350 & H355 [ ] X[0.00030]= [ ] X[0.00030]=
H355HT [ ] X[0.00030]= [ ] X[0.00030]=
B501BH &
***
B501BHT
MMF-300 [ ] X[0.00040]= [ ] X[0.00040]=
MMF-300-10 [ ] X[0.00350]= [ ] X[0.00350]=
MDF-300 [ ] X[0.00075]= [ ] X[0.00075]=
MMF-301 [ ] X[0.000375]= [ ] X[0.000375]=
MMF-302 [ ] X[0.00027]= [ ] X[0.00027]=
MMF-302-6 [ ] X[0.00200]= [ ] X[0.00200]=
BG-12LX [ ] X[0.00030]= [ ] X[0.00030]=
CMF-300 [ ] X[0.00039]= [ ] X[0.00039]=
CMF-300-6 [ ] X[0.00225]= [ ] X[0.00225]=
CRF-300 [ ] X[0.00027]= [ ] X[0.00027]=
CRF-300-6 [ ] X[0.00145]= [ ] X[0.00145]=
I300 [ ] X[0.00040]= [ ] X[0.00040]=
†††
NAC #1
NAC #2 [ ] X[ ]=
NAC #3 [ ] X[ ]=
NAC #4 [ ] X[ ]=
‡‡‡
(nonalarm
for totals
)
Primary, Non-Fire Alarm Current
(amps)
Qty X[current draw]= Total Qty X [current draw] = Total Qty X[current draw]= Total
[ ] X[0.040] [ ]
[ ] X[0.002] [ ]
[ ] X[0.040] [ ]
††
X[ ]
[ ] X[0.025]= [ ] X[0.025]= [ ] X[0.025]=
[ ] X[0.001]= [ ] X[0.001]=
****
Primary Non-Alarm = Primary Alarm = Secondary Non-Alarm =
=
[ ]= [ ] [ ]= [ ] [ ]=
Calculation Column 2
Primary, Fire Alarm Current
(amps)
*
X[0.158]
=
†
X[0.056]
=
2
=
X[0.018]
2
X[0.056]
=
2
=
X[0.065]
‡
X[0.056]
=
**
[ ] X[ ]= [ ] X[ ]=
X[0.011]
maximum alarm draw
for all devices:
with one (1) SLC Loop
with two (2) SLC Loops
[ ] X[ ]=
=
0.400
0.800
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
[ ] X[0.030]=
[ ] X[0.040]=
[ ] X[0.002]=
[ ] X[0.040]=
[ ] X[0.025]=
[ ] X[0.040]=
[ ] X[0.005]=
[ ] X[0.00030]=
* All eight ACM-8RF relays activated on a single module.
† All annunciator LEDs on
‡ LDM-32F with LEDs on
** If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
†† Refer to the Device Compatibility Document for standby current.
‡‡ Must use compatible listed Power Supervision Relay.
***Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
†††Current limitation of Terminal TB4 circuits is 3.00 amps per NAC.
‡‡‡The total standby current must include both the resettable (TB3 Terminals 1 & 2) and nonresettable (TB3
T erminals 3 & 4, 5 & 6) power . Caution must be taken to ensure that current drawn from these outputs during
alarm does not exceed maximum ratings specified. Current limitations of TB3 circuits is 3.0 amps per output
****Total current draw listed above cannot exceed 7.0 amps in alarm.
Supplement to the MS-9600(UD)LS(C/E) Manual Revision B P/N 53587:A 03/20/09 3

2 Appendix G: Canadian Applications on page 201
Replace the first bulleted line with the following statement:
• The MS-9600LSC is supplied with the DP-9692 Dress Panel. The ANN-LED annunciator must be ordered
separately.
4 Supplement to the MS-9600(UD)LS(C/E) Manual Revision B P/N 53587:A 03/20/09