While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
Product Features ................................................................................................................................................8
Digital Communicator ..................................... ..................................................................................................9
Telephone Requirements and Warnings ............................................................................................................10
Digital Communicator ....................................................... ..................................... ....................................10
T elephone Company Rights and Warnings ................................................................................................11
For Canadian Applications .........................................................................................................................12
Programming for DACT-UD2 ..............................................................................................................................18
Programming the MS-9600LS Fire Alarm Control Panel .................................................................................18
Service Terminal .................................................................................................................................20
Ring Count ..........................................................................................................................................20
Central Station .....................................................................................................................................21
Central Station Primary and Secondary Phone Numbers ..................................... ..............................23
Supervised Phone Line ........................................................................................................................29
Central Station Communications ..........................................................................................................................30
Remote Site Upload/Download ............................ ..................................................................................................33
Transferring a Program ................................................................ ......................................................................35
Security Features ........................................................................................................................................35
Ademco Contact ID Format Event Code Descriptions .......................................................................................38
Transmission Format Between DACT and Receiver .................................................................................
....... 38
Ademco Contact ID Typical Printout ................................................................................................................38
Central Station Points ............................................................................................................................................43
DACT-UD2 Communicator P/N: 53037:B 4/01/08 5
Notes
6DACT-UD2 Communicator PN 53037:B 4/01/08
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
•CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
• Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected
Premises Unit
• Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm
Systems
• Proprietary Fire Alarm Systems (Protected Premises Unit)
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
ANSI/UL 864, Control Units and Accessories for Fire Alarm Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
FM Approved to ANSI/UL 864
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 9th Edition. Operation of this product with products not tested for ANSI/UL 864, 9th Edition
has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
DACT-UD2 Communicator PN 53037:B 4/01/087
Product Description
SECTION 1Product Description
The DACT-UD2 (Digital Alarm Communicator/Transmitter) transmits system status to
UL listed Central Station Receivers via the public switched telephone network. The
communicator mounts to the FACP main circuit board inside the panel cabinet and is
capable of reporting 636 points or 99 zones. The DACT -UD2 is supplied standard with
the MS-9600UDLS/E and is optional for the MS-9600LS/E.
1.1 Product Features
•Dual supervised telephone lines
•Mounts inside the control panel
•Extensive transient protection
•Communicates vital system status including:
Independent zone/point alarm
Independent zone/point trouble
Independent zone/point supervisory
AC power loss
Low/No battery
Battery charger trouble
Earth fault
System off normal
12 or 24 hour test signal with alternating phone lines
Abnormal test signal
Annunciation at control panel of DACT troubles including loss of phone lines,
communication failure with either Central Station, total communication failure
The DACT-UD2 has been designed to be compatible with the following control panel:
•MS-9600LS
•MS-9600UDLS
1.3 Specifications
DC Power - J1 Connector
Current draw in standby and alarm:
U Standby = 0.0193 amps max.
U Alarm = 0.0335 amps max. (communicating)
8DACT-UD2 Communicator PN 53037:B 4/01/08
1.4 Digital Communicator
T wo modular phone jacks allow easy connecti on to telephone lines. Modular jacks are
labeled PRI and SEC for the Primary and Secondary phone lines. The digital
communicator provides the following functions:
•Line Seizure - takes control of phone lines disconnecting any premises phones
•Off/On Hook - performs on and off-hook status to the phone lines
•Listen for dial tone - 440 hertz tone typical in most networks
•Dialing Central Station(s) number - default is Touch-Tone®, programmable to
rotary
•For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and
‘Kissoff’ tone(s) - the frequency and time duration of the tone(s) varies with the
transmission format. The control panel will adjust accordingly
•Communicate in the following formats:
Ademco Contact ID
SIA
Product Description
DACT-UD2 Communicator PN 53037:B 4/01/089
Product Description
1.5 Telephone Requirements and Warnings
1.5.1 Telephone Circuitry - PH1 & PH2
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line connection for 2 minutes
The REN is used to determine the quantity of devices which may be connected to
the telephone line. Excessive RENs on the telephone line may result in the devices
not ringing in response to an incoming call. In most, but not all areas, the sum of
the RENs should not exceed five (5.0). To be certain of the number of devices that
may be connected to the line, as determined by the total RENs, contact the
telephone company to determine the maximum REN for the calling area.
1.5.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the
installation of two RJ31X jacks is necessary. If trouble is experienced with this equip
ment, for repair or warranty information, please contact:
Manufacturer:Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Note: This equipment complies with Part 68 of the FCC rules and the
requirements adopted by the ACTA. On the DACT-UD2 module IC is a
label that contains, among other information, a product identifier in the
format US:AAAEQ##TXXXX. If requested, this number must be
provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an
emergency situation. It must be able to do this even if other equipment (telephone,
answering system, computer modem, etc.) already has the telephone line in use. To do
so, alarm dialing equipment must be connected to a properly installed RJ31X jack that
is electrically in series with and ahead of all other equipment attached to the same
telephone line. If there are any questions concerning these instructions, consult the
telephone company or a qualified installer about installing the RJ31X jack and alarm
dialing equipment. Refer to
installation of this equipment.
Figure 2.6 on page 17 for an illustration of the proper
-
Important! The DACT-UD2 must not be used to dial a phone number that is callforwarded.
10DACT-UD2 Communicator PN 53037:B 4/01/08
Product Description
1.5.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue
services and/or make changes in its facilities, services, equipment or procedures which
may affect the operation of this control panel. However, the telephone company is
required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company
reserves the right to temporarily discontinue service. Advance notification will be
provided except in cases when advance notice is not practical. In such cases, notifica
tion will be provided as soon as possible. The opportunity will be given to correct any
problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND ST ART , OR
PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
T wo separate phone lines are r equir ed. Do not connect both telephone interfaces to the
same telephone line.
The control panel must be connected to the public switched telephone network
upstream (as first device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements adopted
by ACTA. This equipment is designed to be connected to the telephone network or pre
mises wiring using a compliant RJ31X male modular plug and compatible modular
jack that is also compliant.
-
-
DACT-UD2 Communicator PN 53037:B 4/01/0811
Product Description
1.5.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipm ent. This
certification means that the equipment meets certain telecommunications network
protective, operational and safety requirements as prescribed in the appropriate
Terminal Equipment Technical Requirements document(s). The Department does not
guarantee the equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be
connected to the facilities of the local telecommunications company. The equipment
must also be installed using an acceptable method of connection. The customer should
be aware that compliance with the above conditions may not prevent degradation of
service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alterations made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company
cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of
the power utility, telephone lines and internal metallic water pipe system, if present, are
connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the
appropriate electric inspection authority, or electrician.
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an
indication of the maximum number of terminals allowed to be connected to a telephone
interface. The termination of an interface may consist of any combination of devices
subject only to the requirement that the sum of the REN of all devices does not exceed
5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio
noise emissions from digital apparatus set out in the Radio Interference Regulations of
the Canadian Department of Communications.”
IC Certificate Number: 2132A-9600LS
Ringer Equivalence Number (REN): 0.0B
12DACT-UD2 Communicator PN 53037:B 4/01/08
SECTION 2DACT-UD2 Installation
2.1 Installation in MS-9600LS FACP
WARNING! Disconnect all sources of power (AC and DC) before installing or
removing any modules or wiring.
FACP Keypad/Display Removal
Removal of the keypad/display is normally not necessary. If, however, it becomes
necessary to replace the keypad/display, access the auxiliary trouble bus connectors at
J16 and J17 or install the DACT-UD2 option module on J2, the Keypad/Display can be
removed by inserting a Phillips screwdriver into each of the three holes located in the
flexible covering of the Keypad/Display and loosening the three mounting screws.
Note that it is not necessary to disconnect the cables between the Keypad/Display and
the main circuit board unless the unit itself is being replaced. Carefully lift the Keypad/
Display and rest the unit at the bottom of the main circuit board.
Note: When installing the DACT-UD2, the main motherboard must be removed from
the chassis. Unplug the power supply cable from J1 before proceeding.
Keypad/Display Mounting
Screw Access Hole
standoff
standoff
TB3
JP10
4XTM OPT BD
TB4
TB1
JP6
TB5
TB7
TB6
JP5
DACT-UD2 Installation
screw
screw
TB8
MAINTENANCE
AC POWER
ALARM
FIRE ALARM
SILENCED
DISABLED
SUPERVISORY
TROUBLE
BATTERY
J2
OPT DACT
ACK/STEP
ALARM
SILENCE
J8
HOLD 2 SEC
RESET
GROUND
DRILL
OPT SLC
96dact1.cdr
JP4
123
J3
J7
screw
REMOVE
JP2
TO DISABLE
LOCAL
CHARGER
JP3
J1
DISABLE
GND
FLT
2
1
ABC
4
5
JKL
GHI
J17
J16
78 9
TUVWXY
PRS
0
*
QZ
RECALL
screwscrew
3
JP8
DEF
6
CUT TO
MNO
MONITOR 4XTM
JP6
LCD DISPLAY
#
TB1
-/.
st
1
EVENT
CLR
ESC
MODE
+BATTERY-
JP7
TB2
ENTER
J6
KEYPAD I/F
screw
Keypad/Display Mounting
Screw Access Holes
Figure 2.1 Keypad/Display Removal
DACT-UD2 Communicator PN 53037:B 4/01/0813
DACT-UD2 Installation
2.1.1 DACT-UD2 Installation
WARNING! Disconnect all sources of power (AC and DC) before installing or
removing any modules or wiring.
The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.
Secondary Phone Line
SEC
J5 Connector (located on back
of module) plugs into J2 on
FACP main circuit board
Figure 2.2 DACT-UD2 Module
PRI
Primary Phone Line
DIALX.CDR
J4
USB Connector
The following steps must be followed when installing the DACT-UD2 module:
1. Remove all power (AC and DC) from FACP before proceeding with installation
2. Remove all main circuit board mounting screws (6 locations) and the 4XTMF
module standoffs (2 locations), unplug the power supply cable from J1 and lift
the main circuit board assembly off the chassis (refer to
Figure 2.1)
3. Remove the Keypad/Display from the main circuit board as described in the
beginning of this section
4. Remove and discard the Keypad/Display support standoff that presently occupies
DACT-UD2 standoff location #3 (refer to
Figure 2.3)
5. Install the supplied DACT-UD2 female/female standoffs in the three locations
shown in
Figure 2.3 and secure with the three supplied screws, inserted from the
bottom side of the main circuit board. Be sure to tighten them fully.
6. Carefully plug connector J5 on back of the DACT-UD2 module into connector J2
on the FACP main circuit board, being careful not to bend any pins
14DACT-UD2 Communicator PN 53037:B 4/01/08
DACT-UD2 Installation
7. Align the mounting holes in the DACT-UD2 module with the newly installed
standoffs on the FACP main circuit board
Standoff 1
Standoff 2
Standoff 3
J2
J5
J1 Connector located on back
of DACT-UD2 module
Figure 2.3 DACT-UD2 J1 Connector to FACP J2 Connector
8. Secure the module to the standoffs on the main circuit board with two of the
screws supplied with the DACT-UD2 and the supplied male/female standoff
which becomes the new Keypad/Display support in that location (see Figure 2.4)
Note: It is important that the supplied hardware be used to secure the module in
order to help protect against electrical transients.
Mounting Screw
Mounting Screw
male/female standoff
96dialx2.CDR
96dialx3.CDR
Figure 2.4 DACT-UD2 Installation on Standoffs
9. Reinstall Keypad/Display on the main circuit board by positioning the unit over
the appropriate standoffs and securing with screws which were loosened in step 3
10. Remount the main circuit board assembly to the chassis using screws and
standoffs in their original locations. Plug in the power supply cable at J1 on the
main circuit board
11. Make certain to program the control panel for DACT-UD2 operation
12. Refer to "Digital Communicator" on page 10, before proceeding with this step.
Connect the premises primary and secondary phone lines to the DACT-UD2 as
illustrated in
DACT-UD2 Communicator PN 53037:B 4/01/0815
Figure 2.5 and test the system for correct operation
DACT-UD2 Installation
Important! The DACT-UD2 must not be used to dial a phone number that is callforwarded.
Secondary Lines
Incoming Telco Phone Lines
Green Wire
Tip
Red Wire
Ring
Secondary Phone Line SEC
IMPORTANT: Improper use
of correct cable connector
will void Warranty!
Green Wire
Ring
Red Wire
Ring
To premises phones
Tip
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
7 foot cable
(MCBL-7)
order separately
Male Plug
Connectors
Female
Connectors
Tip
CAUTION: It is critical that the DACT-UD2
be located as the first device on the incoming
telephone circuit to properly function
Primary Lines
Incoming Telco Phone Lines
Ring
To premises phones
Tip
Primary Phone Line PRI
DACT-UD2
Figure 2.5 Wiring Phone Jacks
16DACT-UD2 Communicator PN 53037:B 4/01/08
DACT-UD2 Installation
It is critical that the DACT be located as the first device on the incoming telephone circuit to properly function.
Customer Premises Equipment and Wiring
Network
Service
Provider’s
Facilities
Telephone
Line
Network
Demarcation
Point
RJ31X
Jack
Telephone
Unused
RJ-11 Jack
MS-9600LS with DACT-UD2
Fax Machine
Answering
System
Figure 2.6 DACT-UD2 Installation
Computer
Telephone
Unused
RJ-11 Jack
Telephone
DACT-UD2 Communicator PN 53037:B 4/01/0817
Programming for DACT-UD2
SECTION 3Programming for DACT-UD2
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in ANSI/UL
864, Standard for Control Units and Accessories for Fire Alarm Systems, certain programming features or options must be limited to specific values or not used at all as indicated below:
Program feature
or option
Trouble Call LimitN
Remote DownloadY
Permitted in
ANSI/UL 864?
(Y/N)
Possible settings
Refer to "Trouble Call Limit (Dialer Runaway Prevention)"
on page 22.
Trouble Call Limit = 0 (factory default): unlimited
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Refer to
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Settings permitted
in ANSI/UL 864
Trouble Call Limit =
0 for unlimited
Central Station
trouble calls
Remote Download
Proprietary Yes for
Proprietary
Installations Only
3.1 Programming the MS-9600LS Fire Alarm Control Panel
Refer to the MS-9600LS Manual programming section for general programming
information. To program the MS-9600LS FACP for use with the DACT-UD2:
1. Press the Enter or Mode key to display the Read Status/Programming screen
2. Press 2 to access Programming
3. Enter the Master level password
4. Press the down arrow key twice to view the screen with the Option Modules
choice
5. Press 3 for Option Modules to access the Option Modules screen as shown to the
left
6. Program the FACP for use with the DACT-UD2 using the following procedure
The DACT-UD2 (Digital Alarm Communicator/Transmitter) is an optional module
which installs directly on the FACP main circuit board for communication to a
central station. Pressing 2 while viewing the Option Module Screen will cause the
following screens to be displayed:
ON BOARD DACT
1=ENABLED YES
2=PRIMARY PHONE
3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
3.1.1.1 DACT-UD2 DACT Enable
To enable the on-board DACT-UD2 module, press 1 while viewing On Board
DACT Screen #1 until the display reads Enabled Yes. The display will toggle
between Enabled Yes and Enabled No with each press of the key.
3.1.1.2 Primary Phone
Press 2 while viewing On Board DACT Screen #1 to program the type of primary
phone line being connected to the DACT-UD2. The following screen will be
displayed:
ON BOARD DACT
PRIMARY PHONE LINE
1=TYPE TOUCHTONE
Primary Phone Line Screen
To select the type, press 1 while viewing the Primary Phone Line screen. The
following screen will be displayed:
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 60/40
Primary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break
ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
DACT-UD2 Communicator PN 53037:B 4/01/0819
Programming for DACT-UD2
ON BOARD DACT
1=ENABLED
2=PRIMARY PHONE
3=SECONDARY PHONE
On Board DACT Screen #1
3.1.1.3 Secondary Phone
Press 3 while viewing On Board DACT Screen #1 to program the type of secondary
phone line being connected to the DACT-UD2. The following screen will be
displayed:
ON BOARD DACT
SECONDARY PHONE LINE
1=TYPE TOUCHTONE
Secondary Phone Line Screen
To select the type, press 1 while viewing the Secondary Phone Line screen. The
following screen will be displayed:
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 60/40
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
Secondary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break
ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
3.1.1.4 Service Terminal
The MS-9600LS can be programmed remotely from a PC using a modem and
telephone line. Information can also be retrieved from the F ACP using the same
method. The Upload/Download option allows an operator to set the necessary
parameters to allow the uploading and downloading of data between the FACP and
PC. The Service Terminal selection provides the means for entering these
parameters.
Pressing 1 while viewing On Board DACT Screen #2 will cause the following
screen to appear:
SERVICE TERMINAL
1=RING COUNT 0
Service Terminal Screen
3.1.1.4.1 Ring Count
The ring count designates the number of rings allowed on the phone line prior to
answering an incoming call from a service terminal. The factory default is 0 which
means the control panel will not answer any incoming calls. This entry may be
programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2.
20DACT-UD2 Communicator PN 53037:B 4/01/08
Programming for DACT-UD2
The following screen will be displayed:
RING COUNT
0-25 RANGE
Ring Count Screen
A flashing cursor will appear in the lower left corner of the display. Enter the twodigit ring count which can be a value between 00 and 25. After the second digit is
entered, the display will return to the Service Terminal screen.
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
3.1.1.5 Central Station
Central Station programming configures the control panel DACT-UD2 for
contacting the central station. Pressing 2 while viewing On Board DACT Screen #2
will cause the following screens to be displayed:
CENTRAL STATION
1=REPORTING DISABLED
2=REPORT BACKUP
3=CALL LIMIT 0
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
3.1.1.5.1 Reporting Enable
T o enable the DACT-UD2 for reporting FACP activity to the central station, press 1
while viewing Central Station Screen #1 so the display reads Reporting Enabled.
Each press of the 1 key will toggle the display between Reporting Disabled and
Reporting Enabled.
DACT-UD2 Communicator PN 53037:B 4/01/0821
Programming for DACT-UD2
3.1.1.5.2 Backup Reporting
The DACT-UD2 can be programmed to transmit reports to primary and/or
secondary central station phone numbers as a backup. Press 2 while viewing
Central Station Screen #1 to display the following screen:
BACKUP REPORTING
1=BACKUP ONLY
2=FIRST AVAILABLE
Backup Reporting Screen
Press 1 to have all reports transmitted to the central station secondary phone number
as a backup only if the primary phone line fails or 2 to send reports to the first
available phone number.
The Call Limit option limits the number of DACT-UD2 trouble calls to the Central
Station, to a programmed amount between 0 and 99, for each unique trouble within
a 24 hour period. Separate limit counters keep track of each unique type of trouble.
Note that the number of phone line (communication) faults called to the Central
Station are not limited by this feature. No subsequent restoral message is sent to the
Central Station(s) for a particular trouble whose call limit has been reached. Local
DACT-UD2 annunciation will still track the particular trouble and restoral.
T o set the T rouble Call Limit, press 3 while viewing Central Station Screen #1. The
following screen will be displayed.
TROUBLE CALL LIMIT
00-99 RANGE
*
Backup Reporting Screen
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
Note: Entering a value of 00 will disable the Trouble Call Limit allowing the
DACT-UD2 to call the Central Station an unlimited number of times. This is the
factory default setting.
22DACT-UD2 Communicator PN 53037:B 4/01/08
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
Programming for DACT-UD2
3.1.1.5.4 Central Station Primary and Secondary Phone Numbers
Pressing 1 for Primary or 2 for Secondary will cause the following screens to be
displayed.
CENTRAL STATION
1=TEST TIME INT 24
2=ACCOUNT CODE 0000
3=24HR TST TIME 0000
Primary/Secondary Screen #1
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
CENTRAL STATION
1=COMM FORMAT
ADEMCO-CONTACT-ID
Primary/Secondary Screen #3
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
DACT-UD2 Communicator PN 53037:B 4/01/0823
Programming for DACT-UD2
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
Test Time Interval
Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following
screens to be displayed:
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
The test report sent to the Central Station phone number may be sent once every 6,
8, 12 or 24 hours. Select the desired Test Time Interval by pressing the
corresponding digit in the screens shown above.
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following
screen to be displayed:
ACCOUNT CODE
4 CHAR RANGE 0-F
Account Codes Screen
The Account Code, which is assigned by a Central Station, depends on the
communication format being used. The Account Code screen will have a flashing
cursor in the lower left corner . Enter the supplied account code using 0 - 9 and A- F
keys.
Note: If the Account Code being entered is a three digit number, enter the three
digits first and then add a 0 (zero) as the fourth digit.
24DACT-UD2 Communicator PN 53037:B 4/01/08
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
Programming for DACT-UD2
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following
screen to be displayed:
24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen
Use the 24 Hour Test Time screen to program the time that the DACT-UD2 will
transmit the 24 Hour Test to the Central Station. A flashing cursor will appear in the
lower left corner of the screen. Enter a four digit number representing the test time
using military time (0000 = midnight and 2359 = 11:59PM).
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following
screen to be displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen
The Phone Number screen is used to enter the Central Station phone number that
the DACT-UD2 will be contacting. A maximum of 20 characters can be entered
with valid entries being 0 - 9 and A - F where A = *, B = #, C = 2 second pause, D =
3 second pause and E = 5 second pause.
A flashing cursor will appear in the lower left corner of the screen. Enter the first
digit then press the right arrow key to move the cursor to the right one position.
Enter the second digit and repeat the process until all digits are entered. Press the
Enter key to store the phone number in memory.
Enter the digits as you would like the number to be dialed. For example, if it’s
necessary to dial 9 before dialing a number outside the building, you may wish to
pause after dialing 9. Enter 9 followed by D for a three second pause or E for a five
second pause then the phone number followed.
DACT-UD2 Communicator PN 53037:B 4/01/0825
Programming for DACT-UD2
CENTRAL STATION
1=COMM FORMAT
Primary/Secondary Screen #3
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following
screen to be displayed:
COMM FORMAT
1=ADEMCO CONTACT ID
2=SIA 8
3=SIA 20
Comm Format Screen
The Communication Format is determined by the type of receiver that the
DACT-UD2 is transmitting to. Consult your Central Station for proper selection or
consult our factory representatives. For any format chosen, the control panel
automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while
viewing the appropriate Comm Format screen. The following table describes each
format:
Table 3.1 Communication Formats
Screen SelectionCommunication Format Description
ADEMCO CONTACT IDContact ID, DTMF, 1400/2300 ACK
SIA 8Security Industry Association, 8 messages per call
SIA 20Security Industry Association, 20 messages per call
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following
screen to be displayed:
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Event Code Screen
Pressing the down arrow key allows viewing of all Events associated with the
selected Communication Format. Pressing the number corresponding to the event
displayed in each screen will display its default event code which can be customized
by the programmer. For example, pressing 1 for Pull Station will display a screen
similar to the following which allows the Event Code to be changed from the
default value.
PULL STATION 115
Event Code Screen
The tables on the following pages list all of the Events and their default Event
Codes for the various Communication Formats.
26DACT-UD2 Communicator PN 53037:B 4/01/08
Programming for DACT-UD2
Ademco Contact ID & SIA Formats
The information shown in Table 3.1 is automatically programmed for the Central
Station phone number Event Codes when the Ademco Contact ID or SIA Format is
selected. Enter 0s for an Event Code Setting to disable the report.
Table 3.1 Event Codes
Event DescriptionAdemco Contact IDSIA
ActiveActiveRestoral
PULL STATION115FAFH
MON-USER-DEF-1115FAFH
WATERFLOW113SASH
MON-USER-DEF-2113SASH
SMOKE (PHOTO)111FAFH
DET-USER-DEF-1111FAFH
SMOKE (ION)111FAFH
DET-USER-DEF-2111FAFH
HEAT DETECT114KAKH
DET-USER-DEF-3114KAKH
SMOKE DUCT-P116FAFH
DET-USER-DEF-4116FAFH
PHOTO W/HEAT111FAFH
DET-USER-DEF-5111FAFH
DUCT SUPERV ISORY200FSFV
DET-USER-DEF-6200FSFV
PHOTO SUPERV200FSFV
DET-USER-DEF-7200FSFV
PHOTO ADAPT111FAFH
DET-USER-DEF-8111FAFH
PHOTO BEAM111FAFH
DET-USER-DEF-9111FAFH
not used0000000
not used0000000
not used0000000
not used0000000
not used0000000
not used0000000
not used0000000
not used0000000
not used0000000
not used0000000
MONITOR110FAFH
MON-USER-DEF-3110FAFH
not used0000000
not used0000000
SMOKE CONVEN111FAFH
MON-USER-DEF-5111FAFH
HEAT CONVENTIONAL114KAKH
MON-USER-DEF-6114KAKH
MEDIC ALERT100MAMH
MON-USER-DEF-7100MAMH
HAZARD ALERT150PAPH
MON-USER-DEF-8150PAPH
TORNADO ALRT150PAPH
MON-USER-DEF-9150PAPH
not used0000000
not used0000000
TAMPER144TATH
MON-USER-DEF-11144TATH
MON SUPERVISORY200FSFV
MON-USER-DEF-12200FSFV
DACT-UD2 Communicator PN 53037:B 4/01/0827
Programming for DACT-UD2
MON SUPERV AUTO200FSFV
MON-USER-DEF-13200FSFV
HVAC OVRRIDE200FSFV
POWER MON330ATAR
MON-USER-DEF-14330ATAR
TROUBLE MONPOINT_FAULT code will always be transmitted
MON-USER-DEF-15POINT_FAULT code will always be transmitted
PROCESS MON0000000
MON-USER-DEF-160000000
PROCMON AR0000000
MON-USER-DEF-170000000
not used0000000
not used0000000
POINT_F AULT380FTFJ
POINT_DISABLE570FBFU
AC_FAIL301ATAR
DRILL604FIFK
SLC 1 OPEN FAULT371ETER
SLC 1 SHORT FAULT372ETER
SLC 2 OPEN FAULT371ETER
SLC 2 SHORT FAULT372ETER
GROUND FAULT310ETER
LOW BATTERY302YTYR
NO_BATTERY311YTYR
TELCO LINE 1351LTLR
TELCO LINE 2352LTLR
COMM FAULT 1354YCYK
COMM FAULT 2354YCYK
TOTAL COMM FLT0000000
PRINTER FAULT336VTVR
NAC 1 FAULT321YAYR
NAC 2 FAULT322YAYR
NAC 3 FAULT326YAYR
NAC 4 FAULT327YAYR
24V FAULT300YPYQ
VOICE EVAC FAULT330ETER
ACS/ANN-BUS FAULT333EMEN
LCD_80F FAULT330EMEN
NAC 1 DISABLE521ETER
NAC 2 DISABLE522ETER
NAC 3 DISABLE526ETER
NAC 4 DISABLE527ETER
CS CALC FAULT304YF
CHARGER F AULT300YPYQ
OPTION CARD 1 FAULT331ETER
OPTION CARD 2 FAULT332ETER
SLC 2 FAULT370ETER
ZONE DISABLE570FBFU
NAC_KEY_FLT300ETER
NO_DEVICES_INSTLLD380ETER
OFF_NORMAL_MESSAGE308LBLX
24_HOUR_TEST602RP
24 HOUR ABNORMAL TES608RY
UPDOWN REQUEST411RB
UPLOAD SUCCESS416RS
DOWNLOAD SUCCESS412RS
UPDOWN FAILURE413RR
GENERAL_ALARM110FAFH
GENERAL_SUPERVISORY200FSFV
Table 3.1 Event Codes (Continued)
28DACT-UD2 Communicator PN 53037:B 4/01/08
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
Programming for DACT-UD2
Report Style
Pressing 3 while viewing Central Station Screen #2 will cause the Report Style
display to toggle between Point and Zone. Setting the Report Style to Point will
program the DACT-UD2 to report individual point status to the Central Station.
The control panel is capable of monitoring a total of 636 addressable devices.
Setting the Report Style to Zone will program the DACT-UD2 to report zone status
to the Central Station. The control panel is capable of monitoring a total of 99
individual zones.
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE POINT
Central Station Screen #2
Notes on Central Station Repo rting:
1. SLC Loop 1, Detector Address 01 will be reported to the Central Station as
Point 01, Detector Address 02 as Point 02, with reports continuing in a similar
fashion all the way up to Detector Address 159 which will be reported as Point
159.
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
2. SLC Loop 1, Module Address 01 will be reported to the Central Station as
Point 160, Module Address 02 will be reported to the Central Station as Point
161, with reports continuing in a similar fashion all the way up to Module
Address 159 which will be reported as Point 318.
3. SLC Loop 2, Detector Address 01 will be reported to the Central Station as
Point 319, Detector Address 02 as Point 320, with reports continuing in a
similar fashion all the way up to Detector Address 159 which will be reported
as Point 477.
4. SLC Loop 2, Module Address 01 will be reported to the Central Station as
Point 478, Module Address 02 as Point 479, with reports continuing in a
similar fashion all the way up to Module Address 159 which will be reported as
Point 636.
3.1.1.5.5 Supervised Phone Line
The Supervised Phone Line feature allows the user to disable or enable the
supervision of Phone Line 2 by the DACT. The factory default setting is Phone
Line 2 supervised.
Pressing 3 for Superv Phone Line while viewing Onboard DACT Screen 2 will
cause the following screen to be displayed:
SUPERVISE PHONE LINE
1=PHONE LINE 2 YES
Panel ID Screen
Each press of the 1 key while viewing this screen will toggle the option between
Supervise Phone Line 2 Yes and No.
DACT-UD2 Communicator PN 53037:B 4/01/0829
Central Station Communications
SECTION 4Central Station Communications
The DACT-UD2 transmits zone and system status reports to Central Stations via the
public switched telephone network. Two supervised telephone line connections are
made to interface the DACT to the telephone lines. Two optional 7 foot telephone
cords are available for this purpose and can be purchased separately.
The control panel supervises both telephone lines for proper voltage. A delay of two
minutes will occur before a fault in either phone line connection is reported as a trouble.
When a fault is detected, an audible trouble signal will sound, the yellow trouble LED
will blink, the display will show a DACT communication trouble and the trouble
condition will be reported to the Central Station over the remaining operational phone
line.
The DACT-UD2 comes with line seizure capability provided for both the primary and
secondary telephone line interfaces. Any time that the control panel needs to make a
call to a Central Station, line seizure will disconnect any local premises phones sharing
the same telephone line.
All transmissions to the Central Stations will be sent over the primary phone line. In
the event of noisy phone lines, transmissions will be sent over the backup secondary
phone line.
Two phone numbers must be programmed, the primary Central Station phone number
and the secondary Central Station phone number. All system reports will be transmitted
to the primary Central Station phone number. Reports will automatically be sent to the
secondary Central Station phone number if attempts to transmits to the primary Central
Station phone number are unsuccessful. Note that as an option, all reports may also be
sent to the secondary Central Station phone number.
The DACT-UD2 installed on the MS-9600LS meets NFPA 72 National Fire Code
reporting requirements for: (a) the type of signal, (b) condition and (c) location of the
reporting premises. The general priority reporting structure is:
1. Zone Alarms and Restores
2. Zone Troubles and Restores
3. System Troubles and Restores
4. 24-hour Test
30DACT-UD2 Communicator PN 53037:B 4/01/08
4.1 Transmittal Priorities
The DACT-UD2 transmits highest priority events first. Events, in terms of priority, are
listed below in descending order:
Zone disabled
Fire drill
AC fail (after delay)
Zonal faults
Earth fault
Low battery/no battery
Telephone line fault
Notification Appliance Circuits fault
Communication trouble
Annunciator trouble
System off normal
4. Restoral Reports
Zone alarm
Supervisory
Zone(s) enabled
Fire drill
AC
Zone fault
Earth
Battery
Telephone line
Notification Appliance Circuits
Communication
Annunciator trouble
System off normal
5. 24 Hour Test (lowest priority)
Central Station Communications
DACT-UD2 Communicator PN 53037:B 4/01/0831
Central Station Communications
The table below shows UL listed receivers which are compatible with the DACT -UD2.
Table 4.1 Compatible UL Listed Receivers
Format
0SIA-DCS-8
1SIA-DCS-20
2Ademco Contact ID
Ademco
685 (1)
Ademco
MX8000 (2)
Silent Knight
9500 (3)
Silent Knight
9800 (4)
Osborne Hoffman
2000E (5)
Radionics
6600 (6)
SurGard
MLR2 (7)
SurGard
System III (8)
SurGard
MLR-2000 (9)
FBI
1. With 685-8 Line Card with Rev. 4.4d software
2. With 124060V206B and 124063 Line Card Rev. B
3. With version V2.4 Receiver and 126047 Line Card Rev. G
4. With 124077V2.00 Receiver and 126047 Line Card Rev. M
5. With V.7301 Receiver S/W
6. With 01.01.03 Receiver S/W and Line Card 01.01.03
7. With software V1.86
8. With software V1.72
9. With DSP4016 and V1.6 Line Card
10. With software V3.9
IMPORTANT! It is the installer’s responsibility to ensure that the Digital Alarm
Communicator/Transmitter is compatible with the Central Station Receiver, utilized by
the monitoring service, prior to installation. The Compatibility Table provides a list of
compatible receivers and associated software versions for the receivers. Changes in
the hardware and/or software by the receiver manufacturers may affect the receiver
compatibility with the FACP DACT. After completing the installation, communication
between the DACT and Central Station Receiver must be tested and verified.
CP220FB (10)
32DACT-UD2 Communicator PN 53037:B 4/01/08
Remote Site Upload/Download
SECTION 5Remote Site Upload/Download
Important! The FACP will automatically reset 2 minutes after completion of a user
program download via the PS-Tools programming utility. To prevent program
corruption, the operator must wait until this panel reset occurs before performing any
panel operations.
The control panel may be programmed or interrogated off-site via the public switched
telephone network or locally using the USB connection at J4 on the DACT-UD2. Any
personal computer with Windows
modem and Upload/Download software PS-Tools, may serve as a Service Terminal.
This allows download of the entire program or upload of the entire program, history
file, walktest data, current status, system voltages, time and date.
The control panel may also communicate to a local PC at the job-site. The PC must be
connected to the USB connector J4 on the DACT-UD2. A standard USB cable with
male-A to male-B connectors, which must be purchased separately, is required.
Important: Remote modification of FACP programming requires that the panel be
enabled for remote download (refer to
interrogation of panel programming, history logs, detector status, etc., is possible
without enabling the remote download option.
™
XP or NEWER, with a 2400 baud compatible
"Remote Download" on page 33). Remote
CAUTION: After successfully downloading a program, make certain to perform the
following steps:
1. Print out all programmed data via Print Mode or manually view programmed
2. Test all affected panel operations
3. Immediately correct any problems found
5.1 Remote Download
NFPA 72 requirements state that a technician be on-site and at the control panel
whenever the PK-Plus Programming Utility is used to download any information to the
FACP. This applies to local and remote programming. For this reason, a new option
has been added to the FACP which allows an individual at the FACP to enter a
password and either enable the proprietary mode where downloading will be allowed at
any time or access a specific password protected screen where downloading will be
allowed regardless of the current proprietary setting. The Remote Download option
can be selected from the main menu screen as shown below:
entries and compare to intended program data
1=READ STATUS MODE
2=PROGRAMMING MODE
3=REMOTE DOWNLOAD
DACT-UD2 Communicator PN 53037:B 4/01/0833
Remote Site Upload/Download
Pressing 3 for Remote Download while viewing the main menu will cause the
following screen to be displayed:
REMOTE DOWNLOAD
ENTER PASSWORD
*****
The Remote Download password (default 00000) must be entered to access the Remote
Download feature. Note that the default password can be changed using the Password
Change option (refer to the FACP manual programming section). Entering the correct
password will cause the following screen to be displayed:
REMOTE DOWNLOAD
1=PROPRIETARY NO
2=ACCEPT DOWNLOAD
Pressing 1 for Proprietary No (factory default setting), while viewing the Remote
Download screen, will cause the display to toggle from Proprietary No to Proprietary Yes. Each press of the 1 key will cause the display to toggle between Proprietary No
and Proprietary Yes. Selecting Proprietary Yes will program the FACP to allow remote
programming downloads from the PK-Plus programming utility at all times without the
need to access the Remote Download screen.
Pressing 2 for Accept Download will cause the following screen to be displayed:
*ALLOWING DOWNLOADS*
IF YOU EXIT THIS
SCREEN DOWNLOADS
WILL BE DISABLED!
While this screen is displayed, remote programming downloads are allowed regardless
of the Proprietary setting. Exiting this screen will disable any further downloads to the
FACP. Also, following 30 minutes of inactivity (including up/downloading), the
Accept Download screen will time-out, causing the display to return to the System All
Normal screen.
34DACT-UD2 Communicator PN 53037:B 4/01/08
5.2 Transferring a Program
The first time that the control panel is downloaded (whether initiated at the jobsite or
remotely), a secret code is loaded in by a Service Terminal. Future upload or download
requests cause verification of the secret code by the control panel before processing of
data is allowed. If the secret code is not verified, the control panel will terminate the
request.
While the control panel is communicating with the Service Terminal, one of the
DACT’s red phone line active LEDs and the green Kissoff LED will turn on steady.
In order to download the panel (whether initiated at the jobsite or remotely), the
following must be true:
The control panel must be in the Normal Mode of operation. Downloading is
not possible if the panel is in any other mode
There cannot be any active communications ongoing with a Central Station
receiver
All active events must be successfully 'kissed-off' by the Central Station(s).
The communicator must be in a standby state with no new information waiting
to be transmitted to a Central Station
Remote Site Upload/Download
5.2.1 Security Features
Upload and download with the control panel have been carefully designed to include
key security features to ensure proper functionality. Any time a transfer is initiated, the
control panel and the Service Terminal will communicate and transfer data before
contacting a Central Station. When the data transfers are completed and the control
panel disconnects from the Service Terminal, the control panel will call the Central
Station and report one of the following conditions:
•Upload/Download request received
•Upload and/or Download request successful
•Upload/Download failed
The key features are listed and explained in the following sections.
Secret Code Verification
A secret code is stored in the control panel by a Service Terminal to prevent
unauthorized access. The secret code is created at the Service Terminal by the master
user and cannot be viewed or changed by anyone other than a master user. Viewing of
the secret code is prohibited at the control panel. Prior to allowing an upload or
download of data, the control panel will verify the secret code transmitted by the
Service Terminal.
Time-out at Control Panel
Upon answering an incoming call on either the primary or secondary Central Station
phone line, the control panel will listen for a modem connection signal. If this signal is
not received within 50 seconds, the control panel will disconnect the call. Upon
successful connection (secret code verified), if no communication occurs within 30
minutes, the panel will disconnect the call. Upon time-out, transfer activity will be
reported to the Central Station (if enabled) and the connection will be terminated.
DACT-UD2 Communicator PN 53037:B 4/01/0835
Remote Site Upload/Download
Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If an
error is detected, the block is retransmitted until correct, up to a maximum of four
times. If the Secret Code is not verified and four errors occur, the call is disconnected
and the report that the upload/download was not successful is called to the Central
Station(s).
Central Station Data Protection
The primary and secondary Central Station phone numbers, communications format,
account code, test time and programmable event codes are vital Central Station
information. These blocks of data are protected from partial programming due to faulty
phone connections, line noise and other errors. This prevents the panel from being
confused due to a wrong phone number, account code, test time and most critical
formatting errors.
36DACT-UD2 Communicator PN 53037:B 4/01/08
APPENDIX A Default Programming
The following table provides a list of the programming options and their factory default
settings.
Program OptionFactory Default
ON Board DACTDisabled
Service Terminal Primary Phone Line TypeTouch Tone
Service Terminal Secondary Phone Line TypeTouch Tone
Service Terminal Primary Phone Numberall Fs
Service Terminal Secondary Phone Numberall Fs
Service Terminal Phone Ring Count.0
Central Station ReportingDisabled
Central Station AC Loss Reporting Delay2
Central Station Backup ReportingFirst A v ai lable
Central Station Reporting StyleReporting by Point
Central Station Trouble Call Limit0
Central Station Primary Phone Line Test Time0000
Central Station Secondary Phone Line Test Time0000
Central Station Primary Phone Line Test Time Interval24
Central Station Secondary Phone Line Test Time Interval24
Central Station Primary Phone Line Account Code0000
Central Station Secondary Phone Line Account Code0000
Central Station Primary Phone Number
Central Station Secondary Phone Number
Central Station Primary Phone Communication FormatAdemco Contact ID
Central Station Secondary Phone Communication FormatAdemco Contact ID
Default Programming
DACT-UD2 Communicator PN 53037:B 4/01/0837
Ademco Contact ID Format Event Code Descriptions
APPENDIX B Ademco Contact ID Format
Event Code Descriptions
This appendix describes the various Event Codes and their messages which are
available for the Ademco Contact ID Format.
B.1 Transmission Format Between DACT and Receiver
The transmission string for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC where
SSSS= Four digit Subscriber ID Account Code
18= Identifies transmission as Contact ID to the receiver at the Central Station
Q= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ= Event code
GG= Group number
CCC= Zone/Point number (refer to Table C.1 on page 43 )
Notes:
1. 18, which is used in the reporting structure to identify the transmission as Contact
ID, is not printed out in the alarm and trouble report.
2. GG Group Number is fixed at '00' and cannot be changed.
3. CCC for Zone or Point Number:
Zone Number is transmitted as ‘001’ for zone 1 up to ‘099’ for zone 99
Point Number is transmitted as ‘001’ for point/address 1 up to ‘636’ for point/
address 636
B.2 Ademco Contact ID Typical Printout
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm
and trouble reports in the Ademco Contact ID Reporting Structure follows:
TimeDateRcvr/Line IDSSSSQXYZGGCCCC
11:2803/25117777E11000C001 - general fire alarm on zone one
11:2803/25117777E11100C002 - smoke detector alarm on zone two
11:2803/25117777E38000C003 - fault on zone three
11:2803/25117777E57000C009 - Zone nine disabled
11:2803/25117777R11000C001 - Zone one alarm restored
11:2803/25117777R11100C002 - smoke detector zone two restored
11:2803/25117777R38000C003 - zone three fault restored
11:2803/25117777R57000C009 - zone nine reenabled
11:2803/25117777E15800C006 - high temperature, zone six
11:2803/25117777E15100C007 - gas detected, zone seven
Notes:
1. 11 is an example of a Receiver/Line Card, showing which receiver and line card
the message was transmitted to.
2. Q, which is the Event Qualifier for the reporting structure, is printed out in the
report as an
38DACT-UD2 Communicator PN 53037:B 4/01/08
E for New Event or R for New Restore.
Ademco Contact ID Format Event Code Descriptions
EVENT CODE CLASSIFICATIONS
100
ALARMS
Medical
Fire
Panic
Burglary
General
24 Hour
200
SUPERVISORY
Fire
EVENTMESSAGE
Medical Alarms - 100
100 MedicalEMERG - Personal Emergency - #
101 Pendant transmitterEMERG - Personal Emergency - #
102 Fail to report inEMERG Fail to Check- in #
24 Hour Non-Burglary - 150 and 160
150 24-Hour Non-BurgALARM - 24-Hr. Non-Burg - #
151 Gas detectedALARM - Gas Detected - #
152 RefrigerationALARM - Refrigeration - #
153 Loss of heatALARM - Heating System - #
154 Water leakageALARM - Water Leakage - #
155 Foil breakALARM - Foil Break - #
156 Day trouble ALARM - Day Zone - #
157 Low bottled gas levelALARM - Low Gas Level - #
158 High tempALARM - High Temperature - #
159 Low tempALARM - Low Temperature - #
161 Loss of air flowALARM - Air Flow - #
Fire Supervisory - 200 and 210
200 Fire supervisoryS UPER. - Fire Supervisory - #
201 Low water pressureSUPER. - Low Water Pressure - #
202 Low CO2SUPER. - Low CO2
203 Gate valve sensorSUPER. - Gate Valve - #
204 Low water levelSUPER. - Low Water Level - #
205 Pump activatedSUPER. - Pump Activation - #
206 Pump failureSUPER. - Pump Failure - #
System Troubles - 300 and 310
300 System troubleTROUBLE - System Trouble
301 AC lossTROUBLE - AC Power
302 Low system batteryTROUBLE - System Low Battery
303 RAM checksum badTROUBLE - Bad RAM Checksum (no restore)
304 ROM checksum badTROUBLE - Bad ROM Checksum (no restore)
305 System resetTROUBLE - System Reset (no restore)
306 Panel program changedTROUBLE - Programming Changed (no restore
307 Self-test failureTROUBLE - Self Test Failure
308 System shutdownTROUBLE - System Shutdown
309 Battery test failureTROUBLE - Battery Test Failure
310 Ground faultTROUBLE - Ground Fault - #
311 No batteryTROUBLE - No Battery
System Peripheral Troubles - 330 and 340
330 System peripheralTROUBLE - Sys. Peripheral - #
331 Polling loop openTROUBLE - Polling Loop Open
332 Polling loop shortTROUBLE - Polling Loop Short
333 Expansion module failureTROUBLE - Exp. Module Fail - #
334 Repeater failureTROUBLE - Repeater Failure - #
335 Local printer paper outTROUBLE - Printer Paper Out
336 Local printer failureTROUBLE - Local Printer
40DACT-UD2 Communicator PN 53037:B 4/01/08
Ademco Contact ID Format Event Code Descriptions
EVENTMESSAGE
Communication Troubles - 350 and 360
350 CommunicationTROUBLE - Communication Trouble
351 Telco 1 faultTROUBLE - Phone Line #1
352 Telco 2 faultTROUBLE - Phone Line #2
353 Long range radio xmitter faultTROUBLE - Radio Transmitter
354 Fail to communicateTROUBLE - Fail to Communicate
355 Loss of radio supervisionTROUBLE - Radio Supervision
356 Loss of central pollingTROUBLE - Central Radio Polling
Access Control - 420
421 Access deniedACCESS - Access Denied - User # (no restore)
422 Access report by userACCESS - Access Gained - User # (no restore)
Communication Disables - 550 and 560
551 Dialer disabledDISABLE - Dialer Disable
552 Radio transmitter disabledDISABLE - Radio Disable
Bypasses - 570
570 Zone bypassBYPASS - Zone Bypass - #
571 Fire bypassBYPASS - Fire Bypass - #
572 24-Hour zone bypassBYPASS - 24-Hour Bypass - #
573 Burglar bypassBYPASS - Burg. Bypass - #
574 Group bypassBYPASS - Group Byp a ss - #
Test Misc. - 600
601 Manual trigger testTEST - Manually Triggered (no restore)
602 Periodic test reportTEST - Periodic (no restore)
603 Periodic RF transmissionTEST - Periodic Radio (no restore)
604 Fire testTEST - Fire Test (restore not used)
605 Status report to followSTATU S - Status Follows (no restore)
606 Listen-in to followLISTEN - Listen-in Active (no restore)
607 Walk test modeTEST - Walk Test Mode
608 System abnormal testTEST - System Abnormal Test
42DACT-UD2 Communicator PN 53037:B 4/01/08
APPENDIX C Central Station Points
The DACT -UD2 transmits Central St ation Reports in a numerical format which indicates the FACP
addressable device address that is reporting and the SLC loop on which it resides. The following
table indicates the Central Station Report (CS Report) number that will be transmitted and the
addressable device address and SLC loop number it represents.
Numerics
24 Hour Test Time 25
A
Account Code 24
Ademco
contact ID format 38
Alarm Current 8
B
Backup
Reporting 22
C
Central Station 21, 36
Communication 30
Phone Number 23, 25
point assignments 43
Central Station Communications 30
Central Station Reports 43
Communication
Central Station 30
Communication Format 26
Communication Formats 9
Compatible Panel 8
contact ID 38
Current
Alarm 8
Standby 8
D
DACT
Installation 14
Programming 19
DACT-UD2
option module installation 14
DC Power 8
Default Programming 37
Description 8
dial tone 9
Digital Communicator 9
Downloading 35
E
Enable
DACT 19
Reporting 21
Error Checking 36
event code classification 39
Event Codes 26
F
Features 8
I
Installation of DACT
MS-9600LS 13
K
Keypad/Display
removal and installation 13
L
Line Seizure 9
O
Off/On Hook 9
On-Board DACT
Programming 19
P
Panel Compatibility 8
Phone Number
Central Station 23, 25
point assignments 43
Point Reporting 29
Primary Phone 19
Priorities
Transmittal 31
Product Features 8
Programming
factory default 37
MS-9600LS for DACT-UD-2 18
Proprietary Yes
see also Remote Upload 34
R
Receivers 32
receivers
UL listed 32
Remote Download 33
REN
see also Ringer Equivalence Number 10
Report Style 29
Reporting
Backup 22
Enable 21
Ring Count 20
Ringer Equivalence Number 10
Rotary dialing 19
S
Secondary Phone 20
Secret Code 35
Security Features 35
Service Terminal 20
Specifications 8
Standby Current 8
T
Telephone
Circuitry 10
DACT-UD2 Communicator PN 53037:B 4/01/0847
Requirements 10
Telephone Company
Rights and Warnings 11
Telephone Connection 15
Test Time
24 Hour 25
Test Time Interval 24, 25
Time-out 35
tone burst 9
touchtone 9
Touchtone dialing 19
Transmittal
Priorities 31
Transmittal Priorities 31
U
Upload/Download 33
W
Warnings 10
Z
Zone Reporting 29
Index
48DACT-UD2 Communicator PN 53037:B 4/01/08
Notes
DACT-UD2 Communicator PN 53037:B 4/01/0849
Notes
50DACT-UD2 Communicator PN 53037:B 4/01/08
Limited Warranty
Honeywell International Inc. warrants products manufactured by it
to be free from defects in materials and workmanship for eighteen
(18) months from the date of manufacture, under normal use and
service. Products are date stamped at time of manufa cture. The sole
and exclusive obligation of Honeywell International Inc. is to repair
or replace, at its option, free of charge for parts and labor, any part
that is defective in materials or workmanship under normal use and
service. All returns for credit are subject to inspection and testing at
the factory before actual determination is made to allow credit.
Honeywell International Inc. does not warrant products not
manufactured by it, but assigns to the purchaser any warranty
extended by the manufacturer of such products. This warranty is void
if the product is altered or repaired by anyone other than Honeywell
International Inc. or as expressly authorized by Honeywell
International Inc. in writing, or is serviced by anyone other than
Honeywell International Inc. or its authorized distributors. This
warranty is also void if there is a failure to maintain the products and
systems in which they operate in a proper and workable manner. In
case of defect, secure a Return Material Authorization form from our
Return Authorization Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products. Honeywell
International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases
provide the protection for which they are installed or intended. Buyer
acknowledges that Honeywell International Inc., is not an insurer
and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,
EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR
ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS
BEYOND THE DESCRIPTION ON THE F ACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC.
BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY,
DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF
THE USE OF, OR INABILITY TO USE HONEYWELL
INTERNATIONAL INC.’S PRODUCTS. FURTHERMORE,
HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE
COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL
OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only
warranty made by Honeywell International Inc. No increase or
alteration, written or verbal, of the obligation of this warranty is
authorized.
Warn-HL-05-2007.fm
World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.firelite.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.