While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
Product Features ................................................................................................................................................8
Digital Communicator ..................................... ..................................................................................................9
Telephone Requirements and Warnings ............................................................................................................10
Digital Communicator ....................................................... ..................................... ....................................10
T elephone Company Rights and Warnings ................................................................................................11
For Canadian Applications .........................................................................................................................12
Programming for DACT-UD2 ..............................................................................................................................18
Programming the MS-9600LS Fire Alarm Control Panel .................................................................................18
Service Terminal .................................................................................................................................20
Ring Count ..........................................................................................................................................20
Central Station .....................................................................................................................................21
Central Station Primary and Secondary Phone Numbers ..................................... ..............................23
Supervised Phone Line ........................................................................................................................29
Central Station Communications ..........................................................................................................................30
Remote Site Upload/Download ............................ ..................................................................................................33
Transferring a Program ................................................................ ......................................................................35
Security Features ........................................................................................................................................35
Ademco Contact ID Format Event Code Descriptions .......................................................................................38
Transmission Format Between DACT and Receiver .................................................................................
....... 38
Ademco Contact ID Typical Printout ................................................................................................................38
Central Station Points ............................................................................................................................................43
DACT-UD2 Communicator P/N: 53037:B 4/01/08 5
Notes
6DACT-UD2 Communicator PN 53037:B 4/01/08
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
•CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
• Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected
Premises Unit
• Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm
Systems
• Proprietary Fire Alarm Systems (Protected Premises Unit)
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
ANSI/UL 864, Control Units and Accessories for Fire Alarm Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
FM Approved to ANSI/UL 864
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 9th Edition. Operation of this product with products not tested for ANSI/UL 864, 9th Edition
has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
DACT-UD2 Communicator PN 53037:B 4/01/087
Product Description
SECTION 1Product Description
The DACT-UD2 (Digital Alarm Communicator/Transmitter) transmits system status to
UL listed Central Station Receivers via the public switched telephone network. The
communicator mounts to the FACP main circuit board inside the panel cabinet and is
capable of reporting 636 points or 99 zones. The DACT -UD2 is supplied standard with
the MS-9600UDLS/E and is optional for the MS-9600LS/E.
1.1 Product Features
•Dual supervised telephone lines
•Mounts inside the control panel
•Extensive transient protection
•Communicates vital system status including:
Independent zone/point alarm
Independent zone/point trouble
Independent zone/point supervisory
AC power loss
Low/No battery
Battery charger trouble
Earth fault
System off normal
12 or 24 hour test signal with alternating phone lines
Abnormal test signal
Annunciation at control panel of DACT troubles including loss of phone lines,
communication failure with either Central Station, total communication failure
The DACT-UD2 has been designed to be compatible with the following control panel:
•MS-9600LS
•MS-9600UDLS
1.3 Specifications
DC Power - J1 Connector
Current draw in standby and alarm:
U Standby = 0.0193 amps max.
U Alarm = 0.0335 amps max. (communicating)
8DACT-UD2 Communicator PN 53037:B 4/01/08
1.4 Digital Communicator
T wo modular phone jacks allow easy connecti on to telephone lines. Modular jacks are
labeled PRI and SEC for the Primary and Secondary phone lines. The digital
communicator provides the following functions:
•Line Seizure - takes control of phone lines disconnecting any premises phones
•Off/On Hook - performs on and off-hook status to the phone lines
•Listen for dial tone - 440 hertz tone typical in most networks
•Dialing Central Station(s) number - default is Touch-Tone®, programmable to
rotary
•For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and
‘Kissoff’ tone(s) - the frequency and time duration of the tone(s) varies with the
transmission format. The control panel will adjust accordingly
•Communicate in the following formats:
Ademco Contact ID
SIA
Product Description
DACT-UD2 Communicator PN 53037:B 4/01/089
Product Description
1.5 Telephone Requirements and Warnings
1.5.1 Telephone Circuitry - PH1 & PH2
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line connection for 2 minutes
The REN is used to determine the quantity of devices which may be connected to
the telephone line. Excessive RENs on the telephone line may result in the devices
not ringing in response to an incoming call. In most, but not all areas, the sum of
the RENs should not exceed five (5.0). To be certain of the number of devices that
may be connected to the line, as determined by the total RENs, contact the
telephone company to determine the maximum REN for the calling area.
1.5.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the
installation of two RJ31X jacks is necessary. If trouble is experienced with this equip
ment, for repair or warranty information, please contact:
Manufacturer:Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Note: This equipment complies with Part 68 of the FCC rules and the
requirements adopted by the ACTA. On the DACT-UD2 module IC is a
label that contains, among other information, a product identifier in the
format US:AAAEQ##TXXXX. If requested, this number must be
provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an
emergency situation. It must be able to do this even if other equipment (telephone,
answering system, computer modem, etc.) already has the telephone line in use. To do
so, alarm dialing equipment must be connected to a properly installed RJ31X jack that
is electrically in series with and ahead of all other equipment attached to the same
telephone line. If there are any questions concerning these instructions, consult the
telephone company or a qualified installer about installing the RJ31X jack and alarm
dialing equipment. Refer to
installation of this equipment.
Figure 2.6 on page 17 for an illustration of the proper
-
Important! The DACT-UD2 must not be used to dial a phone number that is callforwarded.
10DACT-UD2 Communicator PN 53037:B 4/01/08
Product Description
1.5.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue
services and/or make changes in its facilities, services, equipment or procedures which
may affect the operation of this control panel. However, the telephone company is
required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company
reserves the right to temporarily discontinue service. Advance notification will be
provided except in cases when advance notice is not practical. In such cases, notifica
tion will be provided as soon as possible. The opportunity will be given to correct any
problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND ST ART , OR
PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
T wo separate phone lines are r equir ed. Do not connect both telephone interfaces to the
same telephone line.
The control panel must be connected to the public switched telephone network
upstream (as first device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements adopted
by ACTA. This equipment is designed to be connected to the telephone network or pre
mises wiring using a compliant RJ31X male modular plug and compatible modular
jack that is also compliant.
-
-
DACT-UD2 Communicator PN 53037:B 4/01/0811
Product Description
1.5.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipm ent. This
certification means that the equipment meets certain telecommunications network
protective, operational and safety requirements as prescribed in the appropriate
Terminal Equipment Technical Requirements document(s). The Department does not
guarantee the equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be
connected to the facilities of the local telecommunications company. The equipment
must also be installed using an acceptable method of connection. The customer should
be aware that compliance with the above conditions may not prevent degradation of
service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alterations made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company
cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of
the power utility, telephone lines and internal metallic water pipe system, if present, are
connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the
appropriate electric inspection authority, or electrician.
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an
indication of the maximum number of terminals allowed to be connected to a telephone
interface. The termination of an interface may consist of any combination of devices
subject only to the requirement that the sum of the REN of all devices does not exceed
5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio
noise emissions from digital apparatus set out in the Radio Interference Regulations of
the Canadian Department of Communications.”
IC Certificate Number: 2132A-9600LS
Ringer Equivalence Number (REN): 0.0B
12DACT-UD2 Communicator PN 53037:B 4/01/08
SECTION 2DACT-UD2 Installation
2.1 Installation in MS-9600LS FACP
WARNING! Disconnect all sources of power (AC and DC) before installing or
removing any modules or wiring.
FACP Keypad/Display Removal
Removal of the keypad/display is normally not necessary. If, however, it becomes
necessary to replace the keypad/display, access the auxiliary trouble bus connectors at
J16 and J17 or install the DACT-UD2 option module on J2, the Keypad/Display can be
removed by inserting a Phillips screwdriver into each of the three holes located in the
flexible covering of the Keypad/Display and loosening the three mounting screws.
Note that it is not necessary to disconnect the cables between the Keypad/Display and
the main circuit board unless the unit itself is being replaced. Carefully lift the Keypad/
Display and rest the unit at the bottom of the main circuit board.
Note: When installing the DACT-UD2, the main motherboard must be removed from
the chassis. Unplug the power supply cable from J1 before proceeding.
Keypad/Display Mounting
Screw Access Hole
standoff
standoff
TB3
JP10
4XTM OPT BD
TB4
TB1
JP6
TB5
TB7
TB6
JP5
DACT-UD2 Installation
screw
screw
TB8
MAINTENANCE
AC POWER
ALARM
FIRE ALARM
SILENCED
DISABLED
SUPERVISORY
TROUBLE
BATTERY
J2
OPT DACT
ACK/STEP
ALARM
SILENCE
J8
HOLD 2 SEC
RESET
GROUND
DRILL
OPT SLC
96dact1.cdr
JP4
123
J3
J7
screw
REMOVE
JP2
TO DISABLE
LOCAL
CHARGER
JP3
J1
DISABLE
GND
FLT
2
1
ABC
4
5
JKL
GHI
J17
J16
78 9
TUVWXY
PRS
0
*
QZ
RECALL
screwscrew
3
JP8
DEF
6
CUT TO
MNO
MONITOR 4XTM
JP6
LCD DISPLAY
#
TB1
-/.
st
1
EVENT
CLR
ESC
MODE
+BATTERY-
JP7
TB2
ENTER
J6
KEYPAD I/F
screw
Keypad/Display Mounting
Screw Access Holes
Figure 2.1 Keypad/Display Removal
DACT-UD2 Communicator PN 53037:B 4/01/0813
DACT-UD2 Installation
2.1.1 DACT-UD2 Installation
WARNING! Disconnect all sources of power (AC and DC) before installing or
removing any modules or wiring.
The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.
Secondary Phone Line
SEC
J5 Connector (located on back
of module) plugs into J2 on
FACP main circuit board
Figure 2.2 DACT-UD2 Module
PRI
Primary Phone Line
DIALX.CDR
J4
USB Connector
The following steps must be followed when installing the DACT-UD2 module:
1. Remove all power (AC and DC) from FACP before proceeding with installation
2. Remove all main circuit board mounting screws (6 locations) and the 4XTMF
module standoffs (2 locations), unplug the power supply cable from J1 and lift
the main circuit board assembly off the chassis (refer to
Figure 2.1)
3. Remove the Keypad/Display from the main circuit board as described in the
beginning of this section
4. Remove and discard the Keypad/Display support standoff that presently occupies
DACT-UD2 standoff location #3 (refer to
Figure 2.3)
5. Install the supplied DACT-UD2 female/female standoffs in the three locations
shown in
Figure 2.3 and secure with the three supplied screws, inserted from the
bottom side of the main circuit board. Be sure to tighten them fully.
6. Carefully plug connector J5 on back of the DACT-UD2 module into connector J2
on the FACP main circuit board, being careful not to bend any pins
14DACT-UD2 Communicator PN 53037:B 4/01/08
DACT-UD2 Installation
7. Align the mounting holes in the DACT-UD2 module with the newly installed
standoffs on the FACP main circuit board
Standoff 1
Standoff 2
Standoff 3
J2
J5
J1 Connector located on back
of DACT-UD2 module
Figure 2.3 DACT-UD2 J1 Connector to FACP J2 Connector
8. Secure the module to the standoffs on the main circuit board with two of the
screws supplied with the DACT-UD2 and the supplied male/female standoff
which becomes the new Keypad/Display support in that location (see Figure 2.4)
Note: It is important that the supplied hardware be used to secure the module in
order to help protect against electrical transients.
Mounting Screw
Mounting Screw
male/female standoff
96dialx2.CDR
96dialx3.CDR
Figure 2.4 DACT-UD2 Installation on Standoffs
9. Reinstall Keypad/Display on the main circuit board by positioning the unit over
the appropriate standoffs and securing with screws which were loosened in step 3
10. Remount the main circuit board assembly to the chassis using screws and
standoffs in their original locations. Plug in the power supply cable at J1 on the
main circuit board
11. Make certain to program the control panel for DACT-UD2 operation
12. Refer to "Digital Communicator" on page 10, before proceeding with this step.
Connect the premises primary and secondary phone lines to the DACT-UD2 as
illustrated in
DACT-UD2 Communicator PN 53037:B 4/01/0815
Figure 2.5 and test the system for correct operation
DACT-UD2 Installation
Important! The DACT-UD2 must not be used to dial a phone number that is callforwarded.
Secondary Lines
Incoming Telco Phone Lines
Green Wire
Tip
Red Wire
Ring
Secondary Phone Line SEC
IMPORTANT: Improper use
of correct cable connector
will void Warranty!
Green Wire
Ring
Red Wire
Ring
To premises phones
Tip
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
7 foot cable
(MCBL-7)
order separately
Male Plug
Connectors
Female
Connectors
Tip
CAUTION: It is critical that the DACT-UD2
be located as the first device on the incoming
telephone circuit to properly function
Primary Lines
Incoming Telco Phone Lines
Ring
To premises phones
Tip
Primary Phone Line PRI
DACT-UD2
Figure 2.5 Wiring Phone Jacks
16DACT-UD2 Communicator PN 53037:B 4/01/08
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.