Fire-Lite DACT-UD2 User Manual

PN: 53037:B ECN 08-188
Digital Alarm Communicator/Transmitter
DACT-UD2
Document #53037 4/01/08 Revision:
B
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise follow­ing the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These docu­ments can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Manage­ment Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens­ing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flam­ing fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.). Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com­prehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmis­sion systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the require­ments of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso­ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room tempera­ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Notes
4 DACT-UD2 Communicator PN 53037:B 4/01/08
Table of Contents
Product Description .................................................... .................................... ........................................................8
Product Features ................................................................................................................................................8
Compatible Panel ..............................................................................................................................................8
Specifications ....................................................................................................................................................8
Digital Communicator ..................................... ..................................................................................................9
Telephone Requirements and Warnings ............................................................................................................10
Telephone Circuitry - PH1 & PH2 .............................................................................................................10
Digital Communicator ....................................................... ..................................... ....................................10
T elephone Company Rights and Warnings ................................................................................................11
For Canadian Applications .........................................................................................................................12
DACT-UD2 Installation .........................................................................................................................................13
Installation in MS-9600LS FACP .....................................................................................................................13
DACT-UD2 Installation .............................................................................................................................14
Programming for DACT-UD2 ..............................................................................................................................18
Programming the MS-9600LS Fire Alarm Control Panel .................................................................................18
On-Board DACT ........................................................................................................................................19
DACT-UD2 DACT Enable ................................................. ..................................... ...........................19
Primary Phone .....................................................................................................................................19
Secondary Phone .................................................................................................................................20
Service Terminal .................................................................................................................................20
Ring Count ..........................................................................................................................................20
Central Station .....................................................................................................................................21
Reporting Enable .................................................................................................................................21
Backup Reporting ...............................................................................................................................22
Trouble Call Limit (Dialer Runaway Prevention) ..............................................................................22
Central Station Primary and Secondary Phone Numbers ..................................... ..............................23
Supervised Phone Line ........................................................................................................................29
Central Station Communications ..........................................................................................................................30
Transmittal Priorities .........................................................................................................................................31
Remote Site Upload/Download ............................ ..................................................................................................33
Remote Download .............................................................................................................................................33
Transferring a Program ................................................................ ......................................................................35
Security Features ........................................................................................................................................35
Default Programming .............................................................................................................................................37
Ademco Contact ID Format Event Code Descriptions .......................................................................................38
Transmission Format Between DACT and Receiver .................................................................................
....... 38
Ademco Contact ID Typical Printout ................................................................................................................38
Central Station Points ............................................................................................................................................43
DACT-UD2 Communicator P/N: 53037:B 4/01/08 5
Notes
6 DACT-UD2 Communicator PN 53037:B 4/01/08
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
• Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected Premises Unit
• Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems
• Proprietary Fire Alarm Systems (Protected Premises Unit) NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems ANSI/UL 864, Control Units and Accessories for Fire Alarm Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
FM Approved to ANSI/UL 864 Other: EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 MS-9600(UD)LS(E) Manual Document #52646
This product has been certified to comply with the requirements in the ANSI/UL 864, Standard for Control Units and Acces­sories for Fire Alarm Systems, 9th Edition. Operation of this product with products not tested for ANSI/UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
DACT-UD2 Communicator PN 53037:B 4/01/08 7
Product Description

SECTION 1 Product Description

The DACT-UD2 (Digital Alarm Communicator/Transmitter) transmits system status to UL listed Central Station Receivers via the public switched telephone network. The communicator mounts to the FACP main circuit board inside the panel cabinet and is capable of reporting 636 points or 99 zones. The DACT -UD2 is supplied standard with the MS-9600UDLS/E and is optional for the MS-9600LS/E.

1.1 Product Features

Dual supervised telephone lines
Mounts inside the control panel
Extensive transient protection
Communicates vital system status including:
Independent zone/point alarmIndependent zone/point troubleIndependent zone/point supervisoryAC power lossLow/No battery Battery charger troubleEarth faultSystem off normal12 or 24 hour test signal with alternating phone linesAbnormal test signalAnnunciation at control panel of DACT troubles including loss of phone lines,
communication failure with either Central Station, total communication failure
NAC faultsSLC faultsAnnunciator/option faults

1.2 Compatible Panel

The DACT-UD2 has been designed to be compatible with the following control panel:
MS-9600LS
MS-9600UDLS

1.3 Specifications

DC Power - J1 Connector
Current draw in standby and alarm:
U Standby = 0.0193 amps max. U Alarm = 0.0335 amps max. (communicating)
8 DACT-UD2 Communicator PN 53037:B 4/01/08

1.4 Digital Communicator

T wo modular phone jacks allow easy connecti on to telephone lines. Modular jacks are labeled PRI and SEC for the Primary and Secondary phone lines. The digital communicator provides the following functions:
Line Seizure - takes control of phone lines disconnecting any premises phones
Off/On Hook - performs on and off-hook status to the phone lines
Listen for dial tone - 440 hertz tone typical in most networks
Dialing Central Station(s) number - default is Touch-Tone®, programmable to rotary
For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and ‘Kissoff’ tone(s) - the frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
Communicate in the following formats:
Ademco Contact IDSIA
Product Description
DACT-UD2 Communicator PN 53037:B 4/01/08 9
Product Description

1.5 Telephone Requirements and Warnings

1.5.1 Telephone Circuitry - PH1 & PH2

Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line connection for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.

1.5.2 Digital Communicator

Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equip ment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: DACT-UD2 FCC Registration Number: 1W6AL00B9600LS Ringer Equivalence: 0.0B
Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the DACT-UD2 module IC is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to installation of this equipment.
Figure 2.6 on page 17 for an illustration of the proper
-
Important! The DACT-UD2 must not be used to dial a phone number that is call­forwarded.
10 DACT-UD2 Communicator PN 53037:B 4/01/08
Product Description

1.5.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notifica tion will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND ST ART , OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. T wo separate phone lines are r equir ed. Do not connect both telephone interfaces to the
same telephone line. The control panel must be connected to the public switched telephone network
upstream (as first device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or pre mises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
-
-
DACT-UD2 Communicator PN 53037:B 4/01/08 11
Product Description

1.5.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5: “NOTICE: The Industry Canada (IC) label identifies certified equipm ent. This
certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician.
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed
5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.”
Representative: NOTIFIER/FIRE-LITE, CANADA
10 Whitmore Rd. Woodbridge, Ontario L4L 7Z4 Phone: (905) 856-8733 FAX: (905) 856-9687
IC Certificate Number: 2132A-9600LS Ringer Equivalence Number (REN): 0.0B
12 DACT-UD2 Communicator PN 53037:B 4/01/08

SECTION 2 DACT-UD2 Installation

2.1 Installation in MS-9600LS FACP

WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
FACP Keypad/Display Removal
Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to replace the keypad/display, access the auxiliary trouble bus connectors at J16 and J17 or install the DACT-UD2 option module on J2, the Keypad/Display can be removed by inserting a Phillips screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and loosening the three mounting screws. Note that it is not necessary to disconnect the cables between the Keypad/Display and the main circuit board unless the unit itself is being replaced. Carefully lift the Keypad/ Display and rest the unit at the bottom of the main circuit board.
Note: When installing the DACT-UD2, the main motherboard must be removed from the chassis. Unplug the power supply cable from J1 before proceeding.
Keypad/Display Mounting
Screw Access Hole
standoff
standoff
TB3
JP10
4XTM OPT BD
TB4
TB1
JP6
TB5
TB7
TB6
JP5
DACT-UD2 Installation
screw
screw
TB8
MAINTENANCE
AC POWER
ALARM
FIRE ALARM
SILENCED
DISABLED
SUPERVISORY
TROUBLE
BATTERY
J2
OPT DACT
ACK/STEP
ALARM SILENCE
J8
HOLD 2 SEC
RESET
GROUND
DRILL
OPT SLC
96dact1.cdr
JP4
1 2 3
J3
J7
screw
REMOVE
JP2
TO DISABLE LOCAL CHARGER
JP3
J1
DISABLE GND FLT
2
1
ABC
4
5
JKL
GHI
J17
J16
78 9
TUV WXY
PRS
0
*
QZ
RECALL
screw screw
3
JP8
DEF
6
CUT TO
MNO
MONITOR 4XTM
JP6
LCD DISPLAY
#
TB1
-/.
st
1
EVENT
CLR
ESC
MODE
+BATTERY-
JP7
TB2
ENTER
J6
KEYPAD I/F
screw
Keypad/Display Mounting
Screw Access Holes
Figure 2.1 Keypad/Display Removal
DACT-UD2 Communicator PN 53037:B 4/01/08 13
DACT-UD2 Installation

2.1.1 DACT-UD2 Installation

WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.
Secondary Phone Line
SEC
J5 Connector (located on back of module) plugs into J2 on FACP main circuit board
Figure 2.2 DACT-UD2 Module
PRI Primary Phone Line
DIALX.CDR
J4 USB Connector
The following steps must be followed when installing the DACT-UD2 module:
1. Remove all power (AC and DC) from FACP before proceeding with installation
2. Remove all main circuit board mounting screws (6 locations) and the 4XTMF module standoffs (2 locations), unplug the power supply cable from J1 and lift the main circuit board assembly off the chassis (refer to
Figure 2.1)
3. Remove the Keypad/Display from the main circuit board as described in the beginning of this section
4. Remove and discard the Keypad/Display support standoff that presently occupies DACT-UD2 standoff location #3 (refer to
Figure 2.3)
5. Install the supplied DACT-UD2 female/female standoffs in the three locations shown in
Figure 2.3 and secure with the three supplied screws, inserted from the
bottom side of the main circuit board. Be sure to tighten them fully.
6. Carefully plug connector J5 on back of the DACT-UD2 module into connector J2 on the FACP main circuit board, being careful not to bend any pins
14 DACT-UD2 Communicator PN 53037:B 4/01/08
DACT-UD2 Installation
7. Align the mounting holes in the DACT-UD2 module with the newly installed standoffs on the FACP main circuit board
Standoff 1
Standoff 2
Standoff 3
J2
J5
J1 Connector located on back of DACT-UD2 module
Figure 2.3 DACT-UD2 J1 Connector to FACP J2 Connector
8. Secure the module to the standoffs on the main circuit board with two of the screws supplied with the DACT-UD2 and the supplied male/female standoff which becomes the new Keypad/Display support in that location (see Figure 2.4)
Note: It is important that the supplied hardware be used to secure the module in order to help protect against electrical transients.
Mounting Screw
Mounting Screw
male/female standoff
96dialx2.CDR
96dialx3.CDR
Figure 2.4 DACT-UD2 Installation on Standoffs
9. Reinstall Keypad/Display on the main circuit board by positioning the unit over the appropriate standoffs and securing with screws which were loosened in step 3
10. Remount the main circuit board assembly to the chassis using screws and standoffs in their original locations. Plug in the power supply cable at J1 on the main circuit board
11. Make certain to program the control panel for DACT-UD2 operation
12. Refer to "Digital Communicator" on page 10, before proceeding with this step. Connect the premises primary and secondary phone lines to the DACT-UD2 as illustrated in
DACT-UD2 Communicator PN 53037:B 4/01/08 15
Figure 2.5 and test the system for correct operation
DACT-UD2 Installation
Important! The DACT-UD2 must not be used to dial a phone number that is call­forwarded.
Secondary Lines Incoming Telco Phone Lines
Green Wire
Tip
Red Wire
Ring
Secondary Phone Line SEC
IMPORTANT: Improper use of correct cable connector will void Warranty!
Green Wire
Ring
Red Wire
Ring
To premises phones
Tip
Note: Shorting bars inside RJ31X Jack removed during male plug insertion
7 foot cable (MCBL-7) order separately
Male Plug Connectors
Female Connectors
Tip
CAUTION: It is critical that the DACT-UD2 be located as the first device on the incoming telephone circuit to properly function
Primary Lines Incoming Telco Phone Lines
Ring
To premises phones
Tip
Primary Phone Line PRI
DACT-UD2
Figure 2.5 Wiring Phone Jacks
16 DACT-UD2 Communicator PN 53037:B 4/01/08
Loading...
+ 36 hidden pages