Fire-Lite DACT-UD2 User Manual

PN: 53037:B ECN 08-188
Digital Alarm Communicator/Transmitter
DACT-UD2
Document #53037 4/01/08 Revision:
B
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise follow­ing the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These docu­ments can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Manage­ment Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens­ing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flam­ing fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.). Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com­prehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmis­sion systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the require­ments of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso­ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room tempera­ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Notes
4 DACT-UD2 Communicator PN 53037:B 4/01/08
Table of Contents
Product Description .................................................... .................................... ........................................................8
Product Features ................................................................................................................................................8
Compatible Panel ..............................................................................................................................................8
Specifications ....................................................................................................................................................8
Digital Communicator ..................................... ..................................................................................................9
Telephone Requirements and Warnings ............................................................................................................10
Telephone Circuitry - PH1 & PH2 .............................................................................................................10
Digital Communicator ....................................................... ..................................... ....................................10
T elephone Company Rights and Warnings ................................................................................................11
For Canadian Applications .........................................................................................................................12
DACT-UD2 Installation .........................................................................................................................................13
Installation in MS-9600LS FACP .....................................................................................................................13
DACT-UD2 Installation .............................................................................................................................14
Programming for DACT-UD2 ..............................................................................................................................18
Programming the MS-9600LS Fire Alarm Control Panel .................................................................................18
On-Board DACT ........................................................................................................................................19
DACT-UD2 DACT Enable ................................................. ..................................... ...........................19
Primary Phone .....................................................................................................................................19
Secondary Phone .................................................................................................................................20
Service Terminal .................................................................................................................................20
Ring Count ..........................................................................................................................................20
Central Station .....................................................................................................................................21
Reporting Enable .................................................................................................................................21
Backup Reporting ...............................................................................................................................22
Trouble Call Limit (Dialer Runaway Prevention) ..............................................................................22
Central Station Primary and Secondary Phone Numbers ..................................... ..............................23
Supervised Phone Line ........................................................................................................................29
Central Station Communications ..........................................................................................................................30
Transmittal Priorities .........................................................................................................................................31
Remote Site Upload/Download ............................ ..................................................................................................33
Remote Download .............................................................................................................................................33
Transferring a Program ................................................................ ......................................................................35
Security Features ........................................................................................................................................35
Default Programming .............................................................................................................................................37
Ademco Contact ID Format Event Code Descriptions .......................................................................................38
Transmission Format Between DACT and Receiver .................................................................................
....... 38
Ademco Contact ID Typical Printout ................................................................................................................38
Central Station Points ............................................................................................................................................43
DACT-UD2 Communicator P/N: 53037:B 4/01/08 5
Notes
6 DACT-UD2 Communicator PN 53037:B 4/01/08
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
• Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected Premises Unit
• Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems
• Proprietary Fire Alarm Systems (Protected Premises Unit) NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems ANSI/UL 864, Control Units and Accessories for Fire Alarm Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
FM Approved to ANSI/UL 864 Other: EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 MS-9600(UD)LS(E) Manual Document #52646
This product has been certified to comply with the requirements in the ANSI/UL 864, Standard for Control Units and Acces­sories for Fire Alarm Systems, 9th Edition. Operation of this product with products not tested for ANSI/UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
DACT-UD2 Communicator PN 53037:B 4/01/08 7
Product Description

SECTION 1 Product Description

The DACT-UD2 (Digital Alarm Communicator/Transmitter) transmits system status to UL listed Central Station Receivers via the public switched telephone network. The communicator mounts to the FACP main circuit board inside the panel cabinet and is capable of reporting 636 points or 99 zones. The DACT -UD2 is supplied standard with the MS-9600UDLS/E and is optional for the MS-9600LS/E.

1.1 Product Features

Dual supervised telephone lines
Mounts inside the control panel
Extensive transient protection
Communicates vital system status including:
Independent zone/point alarmIndependent zone/point troubleIndependent zone/point supervisoryAC power lossLow/No battery Battery charger troubleEarth faultSystem off normal12 or 24 hour test signal with alternating phone linesAbnormal test signalAnnunciation at control panel of DACT troubles including loss of phone lines,
communication failure with either Central Station, total communication failure
NAC faultsSLC faultsAnnunciator/option faults

1.2 Compatible Panel

The DACT-UD2 has been designed to be compatible with the following control panel:
MS-9600LS
MS-9600UDLS

1.3 Specifications

DC Power - J1 Connector
Current draw in standby and alarm:
U Standby = 0.0193 amps max. U Alarm = 0.0335 amps max. (communicating)
8 DACT-UD2 Communicator PN 53037:B 4/01/08

1.4 Digital Communicator

T wo modular phone jacks allow easy connecti on to telephone lines. Modular jacks are labeled PRI and SEC for the Primary and Secondary phone lines. The digital communicator provides the following functions:
Line Seizure - takes control of phone lines disconnecting any premises phones
Off/On Hook - performs on and off-hook status to the phone lines
Listen for dial tone - 440 hertz tone typical in most networks
Dialing Central Station(s) number - default is Touch-Tone®, programmable to rotary
For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and ‘Kissoff’ tone(s) - the frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
Communicate in the following formats:
Ademco Contact IDSIA
Product Description
DACT-UD2 Communicator PN 53037:B 4/01/08 9
Product Description

1.5 Telephone Requirements and Warnings

1.5.1 Telephone Circuitry - PH1 & PH2

Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line connection for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.

1.5.2 Digital Communicator

Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equip ment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: DACT-UD2 FCC Registration Number: 1W6AL00B9600LS Ringer Equivalence: 0.0B
Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the DACT-UD2 module IC is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to installation of this equipment.
Figure 2.6 on page 17 for an illustration of the proper
-
Important! The DACT-UD2 must not be used to dial a phone number that is call­forwarded.
10 DACT-UD2 Communicator PN 53037:B 4/01/08
Product Description

1.5.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notifica tion will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND ST ART , OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. T wo separate phone lines are r equir ed. Do not connect both telephone interfaces to the
same telephone line. The control panel must be connected to the public switched telephone network
upstream (as first device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or pre mises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
-
-
DACT-UD2 Communicator PN 53037:B 4/01/08 11
Product Description

1.5.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5: “NOTICE: The Industry Canada (IC) label identifies certified equipm ent. This
certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician.
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed
5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.”
Representative: NOTIFIER/FIRE-LITE, CANADA
10 Whitmore Rd. Woodbridge, Ontario L4L 7Z4 Phone: (905) 856-8733 FAX: (905) 856-9687
IC Certificate Number: 2132A-9600LS Ringer Equivalence Number (REN): 0.0B
12 DACT-UD2 Communicator PN 53037:B 4/01/08

SECTION 2 DACT-UD2 Installation

2.1 Installation in MS-9600LS FACP

WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
FACP Keypad/Display Removal
Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to replace the keypad/display, access the auxiliary trouble bus connectors at J16 and J17 or install the DACT-UD2 option module on J2, the Keypad/Display can be removed by inserting a Phillips screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and loosening the three mounting screws. Note that it is not necessary to disconnect the cables between the Keypad/Display and the main circuit board unless the unit itself is being replaced. Carefully lift the Keypad/ Display and rest the unit at the bottom of the main circuit board.
Note: When installing the DACT-UD2, the main motherboard must be removed from the chassis. Unplug the power supply cable from J1 before proceeding.
Keypad/Display Mounting
Screw Access Hole
standoff
standoff
TB3
JP10
4XTM OPT BD
TB4
TB1
JP6
TB5
TB7
TB6
JP5
DACT-UD2 Installation
screw
screw
TB8
MAINTENANCE
AC POWER
ALARM
FIRE ALARM
SILENCED
DISABLED
SUPERVISORY
TROUBLE
BATTERY
J2
OPT DACT
ACK/STEP
ALARM SILENCE
J8
HOLD 2 SEC
RESET
GROUND
DRILL
OPT SLC
96dact1.cdr
JP4
1 2 3
J3
J7
screw
REMOVE
JP2
TO DISABLE LOCAL CHARGER
JP3
J1
DISABLE GND FLT
2
1
ABC
4
5
JKL
GHI
J17
J16
78 9
TUV WXY
PRS
0
*
QZ
RECALL
screw screw
3
JP8
DEF
6
CUT TO
MNO
MONITOR 4XTM
JP6
LCD DISPLAY
#
TB1
-/.
st
1
EVENT
CLR
ESC
MODE
+BATTERY-
JP7
TB2
ENTER
J6
KEYPAD I/F
screw
Keypad/Display Mounting
Screw Access Holes
Figure 2.1 Keypad/Display Removal
DACT-UD2 Communicator PN 53037:B 4/01/08 13
DACT-UD2 Installation

2.1.1 DACT-UD2 Installation

WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.
Secondary Phone Line
SEC
J5 Connector (located on back of module) plugs into J2 on FACP main circuit board
Figure 2.2 DACT-UD2 Module
PRI Primary Phone Line
DIALX.CDR
J4 USB Connector
The following steps must be followed when installing the DACT-UD2 module:
1. Remove all power (AC and DC) from FACP before proceeding with installation
2. Remove all main circuit board mounting screws (6 locations) and the 4XTMF module standoffs (2 locations), unplug the power supply cable from J1 and lift the main circuit board assembly off the chassis (refer to
Figure 2.1)
3. Remove the Keypad/Display from the main circuit board as described in the beginning of this section
4. Remove and discard the Keypad/Display support standoff that presently occupies DACT-UD2 standoff location #3 (refer to
Figure 2.3)
5. Install the supplied DACT-UD2 female/female standoffs in the three locations shown in
Figure 2.3 and secure with the three supplied screws, inserted from the
bottom side of the main circuit board. Be sure to tighten them fully.
6. Carefully plug connector J5 on back of the DACT-UD2 module into connector J2 on the FACP main circuit board, being careful not to bend any pins
14 DACT-UD2 Communicator PN 53037:B 4/01/08
DACT-UD2 Installation
7. Align the mounting holes in the DACT-UD2 module with the newly installed standoffs on the FACP main circuit board
Standoff 1
Standoff 2
Standoff 3
J2
J5
J1 Connector located on back of DACT-UD2 module
Figure 2.3 DACT-UD2 J1 Connector to FACP J2 Connector
8. Secure the module to the standoffs on the main circuit board with two of the screws supplied with the DACT-UD2 and the supplied male/female standoff which becomes the new Keypad/Display support in that location (see Figure 2.4)
Note: It is important that the supplied hardware be used to secure the module in order to help protect against electrical transients.
Mounting Screw
Mounting Screw
male/female standoff
96dialx2.CDR
96dialx3.CDR
Figure 2.4 DACT-UD2 Installation on Standoffs
9. Reinstall Keypad/Display on the main circuit board by positioning the unit over the appropriate standoffs and securing with screws which were loosened in step 3
10. Remount the main circuit board assembly to the chassis using screws and standoffs in their original locations. Plug in the power supply cable at J1 on the main circuit board
11. Make certain to program the control panel for DACT-UD2 operation
12. Refer to "Digital Communicator" on page 10, before proceeding with this step. Connect the premises primary and secondary phone lines to the DACT-UD2 as illustrated in
DACT-UD2 Communicator PN 53037:B 4/01/08 15
Figure 2.5 and test the system for correct operation
DACT-UD2 Installation
Important! The DACT-UD2 must not be used to dial a phone number that is call­forwarded.
Secondary Lines Incoming Telco Phone Lines
Green Wire
Tip
Red Wire
Ring
Secondary Phone Line SEC
IMPORTANT: Improper use of correct cable connector will void Warranty!
Green Wire
Ring
Red Wire
Ring
To premises phones
Tip
Note: Shorting bars inside RJ31X Jack removed during male plug insertion
7 foot cable (MCBL-7) order separately
Male Plug Connectors
Female Connectors
Tip
CAUTION: It is critical that the DACT-UD2 be located as the first device on the incoming telephone circuit to properly function
Primary Lines Incoming Telco Phone Lines
Ring
To premises phones
Tip
Primary Phone Line PRI
DACT-UD2
Figure 2.5 Wiring Phone Jacks
16 DACT-UD2 Communicator PN 53037:B 4/01/08
DACT-UD2 Installation
It is critical that the DACT be located as the first device on the incoming telephone circuit to properly function.
Customer Premises Equipment and Wiring
Network
Service
Provider’s
Facilities
Telephone
Line
Network
Demarcation
Point
RJ31X
Jack
Telephone
Unused
RJ-11 Jack
MS-9600LS with DACT-UD2
Fax Machine
Answering
System
Figure 2.6 DACT-UD2 Installation
Computer
Telephone
Unused
RJ-11 Jack
Telephone
DACT-UD2 Communicator PN 53037:B 4/01/08 17
Programming for DACT-UD2

SECTION 3 Programming for DACT-UD2

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, certain programming features or options must be lim­ited to specific values or not used at all as indicated below:
Program feature
or option
Trouble Call Limit N
Remote Download Y
Permitted in
ANSI/UL 864?
(Y/N)
Possible settings
Refer to "Trouble Call Limit (Dialer Runaway Prevention)" on page 22.
Trouble Call Limit = 0 (factory default): unlimited calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble to from 1 to 99 within a 24 hour period Refer to
Remote Download - Proprietary No Remote Download - Proprietary Yes
Settings permitted
in ANSI/UL 864
Trouble Call Limit = 0 for unlimited Central Station trouble calls
Remote Download Proprietary Yes for Proprietary Installations Only

3.1 Programming the MS-9600LS Fire Alarm Control Panel

Refer to the MS-9600LS Manual programming section for general programming information. To program the MS-9600LS FACP for use with the DACT-UD2:
1. Press the Enter or Mode key to display the Read Status/Programming screen
2. Press 2 to access Programming
3. Enter the Master level password
4. Press the down arrow key twice to view the screen with the Option Modules choice
5. Press 3 for Option Modules to access the Option Modules screen as shown to the left
6. Program the FACP for use with the DACT-UD2 using the following procedure
18 DACT-UD2 Communicator PN 53037:B 4/01/08
Programming for DACT-UD2
OPTION MODULES 1=ANNUNCIATORS/UDACT 2=ON BOARD DACT 3=PRINTER/PC
Option Module Screen

3.1.1 On-Board DACT

The DACT-UD2 (Digital Alarm Communicator/Transmitter) is an optional module which installs directly on the FACP main circuit board for communication to a central station. Pressing 2 while viewing the Option Module Screen will cause the following screens to be displayed:
ON BOARD DACT 1=ENABLED YES 2=PRIMARY PHONE 3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=SUPERV PHONE LINE
On Board DACT Screen #2
3.1.1.1 DACT-UD2 DACT Enable
To enable the on-board DACT-UD2 module, press 1 while viewing On Board DACT Screen #1 until the display reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press of the key.
3.1.1.2 Primary Phone
Press 2 while viewing On Board DACT Screen #1 to program the type of primary phone line being connected to the DACT-UD2. The following screen will be displayed:
ON BOARD DACT PRIMARY PHONE LINE 1=TYPE TOUCHTONE
Primary Phone Line Screen
To select the type, press 1 while viewing the Primary Phone Line screen. The following screen will be displayed:
PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 60/40
Primary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
DACT-UD2 Communicator PN 53037:B 4/01/08 19
Programming for DACT-UD2
ON BOARD DACT 1=ENABLED 2=PRIMARY PHONE 3=SECONDARY PHONE
On Board DACT Screen #1
3.1.1.3 Secondary Phone
Press 3 while viewing On Board DACT Screen #1 to program the type of secondary phone line being connected to the DACT-UD2. The following screen will be displayed:
ON BOARD DACT SECONDARY PHONE LINE 1=TYPE TOUCHTONE
Secondary Phone Line Screen
To select the type, press 1 while viewing the Secondary Phone Line screen. The following screen will be displayed:
PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 60/40
ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=SUPERV PHONE LINE
On Board DACT Screen #2
Secondary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
3.1.1.4 Service Terminal
The MS-9600LS can be programmed remotely from a PC using a modem and telephone line. Information can also be retrieved from the F ACP using the same method. The Upload/Download option allows an operator to set the necessary parameters to allow the uploading and downloading of data between the FACP and PC. The Service Terminal selection provides the means for entering these parameters.
Pressing 1 while viewing On Board DACT Screen #2 will cause the following screen to appear:
SERVICE TERMINAL 1=RING COUNT 0
Service Terminal Screen
3.1.1.4.1 Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an incoming call from a service terminal. The factory default is 0 which means the control panel will not answer any incoming calls. This entry may be programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2.
20 DACT-UD2 Communicator PN 53037:B 4/01/08
Programming for DACT-UD2
The following screen will be displayed:
RING COUNT
0-25 RANGE
Ring Count Screen
A flashing cursor will appear in the lower left corner of the display. Enter the two­digit ring count which can be a value between 00 and 25. After the second digit is entered, the display will return to the Service Terminal screen.
ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=SUPERV PHONE LINE
On Board DACT Screen #2
3.1.1.5 Central Station
Central Station programming configures the control panel DACT-UD2 for contacting the central station. Pressing 2 while viewing On Board DACT Screen #2 will cause the following screens to be displayed:
CENTRAL STATION 1=REPORTING DISABLED 2=REPORT BACKUP 3=CALL LIMIT 0
Central Station Screen #1
CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE
Central Station Screen #2
3.1.1.5.1 Reporting Enable
T o enable the DACT-UD2 for reporting FACP activity to the central station, press 1 while viewing Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will toggle the display between Reporting Disabled and Reporting Enabled.
DACT-UD2 Communicator PN 53037:B 4/01/08 21
Programming for DACT-UD2
3.1.1.5.2 Backup Reporting
The DACT-UD2 can be programmed to transmit reports to primary and/or secondary central station phone numbers as a backup. Press 2 while viewing Central Station Screen #1 to display the following screen:
BACKUP REPORTING 1=BACKUP ONLY 2=FIRST AVAILABLE
Backup Reporting Screen
Press 1 to have all reports transmitted to the central station secondary phone number as a backup only if the primary phone line fails or 2 to send reports to the first available phone number.
3.1.1.5.3 Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT-UD2 trouble calls to the Central Station, to a programmed amount between 0 and 99, for each unique trouble within a 24 hour period. Separate limit counters keep track of each unique type of trouble. Note that the number of phone line (communication) faults called to the Central Station are not limited by this feature. No subsequent restoral message is sent to the Central Station(s) for a particular trouble whose call limit has been reached. Local DACT-UD2 annunciation will still track the particular trouble and restoral.
T o set the T rouble Call Limit, press 3 while viewing Central Station Screen #1. The following screen will be displayed.
TROUBLE CALL LIMIT
00-99 RANGE *
Backup Reporting Screen
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
Note: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT-UD2 to call the Central Station an unlimited number of times. This is the factory default setting.
22 DACT-UD2 Communicator PN 53037:B 4/01/08
CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE
Central Station Screen #2
Programming for DACT-UD2
3.1.1.5.4 Central Station Primary and Secondary Phone Numbers
Pressing 1 for Primary or 2 for Secondary will cause the following screens to be displayed.
CENTRAL STATION 1=TEST TIME INT 24 2=ACCOUNT CODE 0000 3=24HR TST TIME 0000
Primary/Secondary Screen #1
CENTRAL STATION 1=PHONE NUMBER
Primary/Secondary Screen #2
CENTRAL STATION 1=COMM FORMAT ADEMCO-CONTACT-ID
Primary/Secondary Screen #3
CENTRAL STATION 1=EVENT CODES
Primary/Secondary Screen #4
DACT-UD2 Communicator PN 53037:B 4/01/08 23
Programming for DACT-UD2
CENTRAL STATION 1=TEST TIME INT 2=ACCOUNT CODE 3=24HR TST TIME
Primary/Secondary Screen #1
Test Time Interval
Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be displayed:
TEST TIME INTERVAL 1=24 HOURS 2=12 HOURS 3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL 1=6 HOURS
Test Time Interval Screen #2
The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24 hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens shown above.
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed:
ACCOUNT CODE
4 CHAR RANGE 0-F
Account Codes Screen
The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen will have a flashing cursor in the lower left corner . Enter the supplied account code using 0 - 9 and A- F keys.
Note: If the Account Code being entered is a three digit number, enter the three digits first and then add a 0 (zero) as the fourth digit.
24 DACT-UD2 Communicator PN 53037:B 4/01/08
CENTRAL STATION 1=TEST TIME INT 2=ACCOUNT CODE 3=24HR TST TIME
Primary/Secondary Screen #1
Programming for DACT-UD2
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed:
24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen
Use the 24 Hour Test Time screen to program the time that the DACT-UD2 will transmit the 24 Hour Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen. Enter a four digit number representing the test time using military time (0000 = midnight and 2359 = 11:59PM).
CENTRAL STATION 1=PHONE NUMBER
Primary/Secondary Screen #2
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen
The Phone Number screen is used to enter the Central Station phone number that the DACT-UD2 will be contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9 and A - F where A = *, B = #, C = 2 second pause, D = 3 second pause and E = 5 second pause.
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press the right arrow key to move the cursor to the right one position. Enter the second digit and repeat the process until all digits are entered. Press the Enter key to store the phone number in memory.
Enter the digits as you would like the number to be dialed. For example, if it’s necessary to dial 9 before dialing a number outside the building, you may wish to pause after dialing 9. Enter 9 followed by D for a three second pause or E for a five second pause then the phone number followed.
DACT-UD2 Communicator PN 53037:B 4/01/08 25
Programming for DACT-UD2
CENTRAL STATION 1=COMM FORMAT
Primary/Secondary Screen #3
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be displayed:
COMM FORMAT 1=ADEMCO CONTACT ID 2=SIA 8 3=SIA 20
Comm Format Screen
The Communication Format is determined by the type of receiver that the DACT-UD2 is transmitting to. Consult your Central Station for proper selection or
consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the appropriate Comm Format screen. The following table describes each format:
Table 3.1 Communication Formats
Screen Selection Communication Format Description
ADEMCO CONTACT ID Contact ID, DTMF, 1400/2300 ACK SIA 8 Security Industry Association, 8 messages per call SIA 20 Security Industry Association, 20 messages per call
CENTRAL STATION 1=EVENT CODES
Primary/Secondary Screen #4
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following screen to be displayed:
EVENT CODES 1=PULL STATION 2=MON-USER-DEF-1 3=WATERFLOW
Event Code Screen
Pressing the down arrow key allows viewing of all Events associated with the selected Communication Format. Pressing the number corresponding to the event displayed in each screen will display its default event code which can be customized by the programmer. For example, pressing 1 for Pull Station will display a screen similar to the following which allows the Event Code to be changed from the default value.
PULL STATION 115
Event Code Screen
The tables on the following pages list all of the Events and their default Event Codes for the various Communication Formats.
26 DACT-UD2 Communicator PN 53037:B 4/01/08
Programming for DACT-UD2
Ademco Contact ID & SIA Formats
The information shown in Table 3.1 is automatically programmed for the Central Station phone number Event Codes when the Ademco Contact ID or SIA Format is selected. Enter 0s for an Event Code Setting to disable the report.
Table 3.1 Event Codes
Event Description Ademco Contact ID SIA
Active Active Restoral
PULL STATION 115 FA FH MON-USER-DEF-1 115 FA FH WATERFLOW 113 SA SH MON-USER-DEF-2 113 SA SH SMOKE (PHOTO) 111 FA FH DET-USER-DEF-1 111 FA FH SMOKE (ION) 111 FA FH DET-USER-DEF-2 111 FA FH HEAT DETECT 114 KA KH DET-USER-DEF-3 114 KA KH SMOKE DUCT-P 116 FA FH DET-USER-DEF-4 116 FA FH PHOTO W/HEAT 111 FA FH DET-USER-DEF-5 111 FA FH DUCT SUPERV ISORY 200 FS FV DET-USER-DEF-6 200 FS FV PHOTO SUPERV 200 FS FV DET-USER-DEF-7 200 FS FV PHOTO ADAPT 111 FA FH DET-USER-DEF-8 111 FA FH PHOTO BEAM 111 FA FH DET-USER-DEF-9 111 FA FH not used 000 00 00 not used 000 00 00 not used 000 00 00 not used 000 00 00 not used 000 00 00 not used 000 00 00 not used 000 00 00 not used 000 00 00 not used 000 00 00 not used 000 00 00 MONITOR 110 FA FH MON-USER-DEF-3 110 FA FH not used 000 00 00 not used 000 00 00 SMOKE CONVEN 111 FA FH MON-USER-DEF-5 111 FA FH HEAT CONVENTIONAL 114 KA KH MON-USER-DEF-6 114 KA KH MEDIC ALERT 100 MA MH MON-USER-DEF-7 100 MA MH HAZARD ALERT 150 PA PH MON-USER-DEF-8 150 PA PH TORNADO ALRT 150 PA PH MON-USER-DEF-9 150 PA PH not used 000 00 00 not used 000 00 00 TAMPER 144 TA TH MON-USER-DEF-11 144 TA TH MON SUPERVISORY 200 FS FV MON-USER-DEF-12 200 FS FV
DACT-UD2 Communicator PN 53037:B 4/01/08 27
Programming for DACT-UD2
MON SUPERV AUTO 200 FS FV MON-USER-DEF-13 200 FS FV HVAC OVRRIDE 200 FS FV POWER MON 330 AT AR MON-USER-DEF-14 330 AT AR TROUBLE MON POINT_FAULT code will always be transmitted MON-USER-DEF-15 POINT_FAULT code will always be transmitted PROCESS MON 000 00 00 MON-USER-DEF-16 000 00 00 PROCMON AR 000 00 00 MON-USER-DEF-17 000 00 00 not used 000 00 00 not used 000 00 00 POINT_F AULT 380 FT FJ POINT_DISABLE 570 FB FU AC_FAIL 301 AT AR DRILL 604 FI FK SLC 1 OPEN FAULT 371 ET ER SLC 1 SHORT FAULT 372 ET ER SLC 2 OPEN FAULT 371 ET ER SLC 2 SHORT FAULT 372 ET ER GROUND FAULT 310 ET ER LOW BATTERY 302 YT YR NO_BATTERY 311 YT YR TELCO LINE 1 351 LT LR TELCO LINE 2 352 LT LR COMM FAULT 1 354 YC YK COMM FAULT 2 354 YC YK TOTAL COMM FLT 000 00 00 PRINTER FAULT 336 VT VR NAC 1 FAULT 321 YA YR NAC 2 FAULT 322 YA YR NAC 3 FAULT 326 YA YR NAC 4 FAULT 327 YA YR 24V FAULT 300 YP YQ VOICE EVAC FAULT 330 ET ER ACS/ANN-BUS FAULT 333 EM EN LCD_80F FAULT 330 EM EN NAC 1 DISABLE 521 ET ER NAC 2 DISABLE 522 ET ER NAC 3 DISABLE 526 ET ER NAC 4 DISABLE 527 ET ER CS CALC FAULT 304 YF CHARGER F AULT 300 YP YQ OPTION CARD 1 FAULT 331 ET ER OPTION CARD 2 FAULT 332 ET ER SLC 2 FAULT 370 ET ER ZONE DISABLE 570 FB FU NAC_KEY_FLT 300 ET ER NO_DEVICES_INSTLLD 380 ET ER OFF_NORMAL_MESSAGE 308 LB LX 24_HOUR_TEST 602 RP 24 HOUR ABNORMAL TES 608 RY UPDOWN REQUEST 411 RB UPLOAD SUCCESS 416 RS DOWNLOAD SUCCESS 412 RS UPDOWN FAILURE 413 RR GENERAL_ALARM 110 FA FH GENERAL_SUPERVISORY 200 FS FV
Table 3.1 Event Codes (Continued)
28 DACT-UD2 Communicator PN 53037:B 4/01/08
CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE
Central Station Screen #2
Programming for DACT-UD2
Report Style
Pressing 3 while viewing Central Station Screen #2 will cause the Report Style display to toggle between Point and Zone. Setting the Report Style to Point will program the DACT-UD2 to report individual point status to the Central Station. The control panel is capable of monitoring a total of 636 addressable devices. Setting the Report Style to Zone will program the DACT-UD2 to report zone status to the Central Station. The control panel is capable of monitoring a total of 99 individual zones.
CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE POINT
Central Station Screen #2
Notes on Central Station Repo rting:
1. SLC Loop 1, Detector Address 01 will be reported to the Central Station as
Point 01, Detector Address 02 as Point 02, with reports continuing in a similar fashion all the way up to Detector Address 159 which will be reported as Point
159.
ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=SUPERV PHONE LINE
On Board DACT Screen #2
2. SLC Loop 1, Module Address 01 will be reported to the Central Station as
Point 160, Module Address 02 will be reported to the Central Station as Point 161, with reports continuing in a similar fashion all the way up to Module Address 159 which will be reported as Point 318.
3. SLC Loop 2, Detector Address 01 will be reported to the Central Station as
Point 319, Detector Address 02 as Point 320, with reports continuing in a similar fashion all the way up to Detector Address 159 which will be reported as Point 477.
4. SLC Loop 2, Module Address 01 will be reported to the Central Station as
Point 478, Module Address 02 as Point 479, with reports continuing in a similar fashion all the way up to Module Address 159 which will be reported as Point 636.
3.1.1.5.5 Supervised Phone Line
The Supervised Phone Line feature allows the user to disable or enable the supervision of Phone Line 2 by the DACT. The factory default setting is Phone Line 2 supervised.
Pressing 3 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the following screen to be displayed:
SUPERVISE PHONE LINE 1=PHONE LINE 2 YES
Panel ID Screen
Each press of the 1 key while viewing this screen will toggle the option between Supervise Phone Line 2 Yes and No.
DACT-UD2 Communicator PN 53037:B 4/01/08 29
Central Station Communications

SECTION 4 Central Station Communications

The DACT-UD2 transmits zone and system status reports to Central Stations via the public switched telephone network. Two supervised telephone line connections are made to interface the DACT to the telephone lines. Two optional 7 foot telephone cords are available for this purpose and can be purchased separately.
The control panel supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound, the yellow trouble LED will blink, the display will show a DACT communication trouble and the trouble condition will be reported to the Central Station over the remaining operational phone line.
The DACT-UD2 comes with line seizure capability provided for both the primary and secondary telephone line interfaces. Any time that the control panel needs to make a call to a Central Station, line seizure will disconnect any local premises phones sharing the same telephone line.
All transmissions to the Central Stations will be sent over the primary phone line. In the event of noisy phone lines, transmissions will be sent over the backup secondary phone line.
Two phone numbers must be programmed, the primary Central Station phone number and the secondary Central Station phone number. All system reports will be transmitted to the primary Central Station phone number. Reports will automatically be sent to the secondary Central Station phone number if attempts to transmits to the primary Central Station phone number are unsuccessful. Note that as an option, all reports may also be sent to the secondary Central Station phone number.
The DACT-UD2 installed on the MS-9600LS meets NFPA 72 National Fire Code reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting premises. The general priority reporting structure is:
1. Zone Alarms and Restores
2. Zone Troubles and Restores
3. System Troubles and Restores
4. 24-hour Test
30 DACT-UD2 Communicator PN 53037:B 4/01/08

4.1 Transmittal Priorities

The DACT-UD2 transmits highest priority events first. Events, in terms of priority, are listed below in descending order:
1. Alarms (highest priority level)
Pull stationsWaterflowSmoke detectorOther alarm types
2. Supervisory Zone
3. System Troubles
Zone disabledFire drillAC fail (after delay)Zonal faultsEarth faultLow battery/no batteryTelephone line faultNotification Appliance Circuits faultCommunication troubleAnnunciator troubleSystem off normal
4. Restoral Reports
Zone alarmSupervisoryZone(s) enabledFire drillACZone faultEarthBatteryTelephone lineNotification Appliance CircuitsCommunicationAnnunciator troubleSystem off normal
5. 24 Hour Test (lowest priority)
Central Station Communications
DACT-UD2 Communicator PN 53037:B 4/01/08 31
Central Station Communications
The table below shows UL listed receivers which are compatible with the DACT -UD2.
Table 4.1 Compatible UL Listed Receivers
Format
0 SIA-DCS-8 1 SIA-DCS-20 2 Ademco Contact ID
Ademco
685 (1)
Ademco
MX8000 (2)
Silent Knight
9500 (3)
Silent Knight
9800 (4)
Osborne Hoffman
2000E (5)
Radionics
6600 (6)
SurGard
MLR2 (7)
SurGard
System III (8)
SurGard
MLR-2000 (9)
FBI
1. With 685-8 Line Card with Rev. 4.4d software
2. With 124060V206B and 124063 Line Card Rev. B
3. With version V2.4 Receiver and 126047 Line Card Rev. G
4. With 124077V2.00 Receiver and 126047 Line Card Rev. M
5. With V.7301 Receiver S/W
6. With 01.01.03 Receiver S/W and Line Card 01.01.03
7. With software V1.86
8. With software V1.72
9. With DSP4016 and V1.6 Line Card
10. With software V3.9
IMPORTANT! It is the installer’s responsibility to ensure that the Digital Alarm Communicator/Transmitter is compatible with the Central Station Receiver, utilized by the monitoring service, prior to installation. The Compatibility Table provides a list of compatible receivers and associated software versions for the receivers. Changes in the hardware and/or software by the receiver manufacturers may affect the receiver compatibility with the FACP DACT. After completing the installation, communication between the DACT and Central Station Receiver must be tested and verified.
CP220FB (10)
32 DACT-UD2 Communicator PN 53037:B 4/01/08
Remote Site Upload/Download

SECTION 5 Remote Site Upload/Download

Important! The FACP will automatically reset 2 minutes after completion of a user program download via the PS-Tools programming utility. To prevent program corruption, the operator must wait until this panel reset occurs before performing any panel operations.
The control panel may be programmed or interrogated off-site via the public switched telephone network or locally using the USB connection at J4 on the DACT-UD2. Any personal computer with Windows modem and Upload/Download software PS-Tools, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status, system voltages, time and date.
The control panel may also communicate to a local PC at the job-site. The PC must be connected to the USB connector J4 on the DACT-UD2. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.
XP or NEWER, with a 2400 baud compatible
"Remote Download" on page 33). Remote
CAUTION: After successfully downloading a program, make certain to perform the following steps:
1. Print out all programmed data via Print Mode or manually view programmed
2. Test all affected panel operations
3. Immediately correct any problems found

5.1 Remote Download

NFPA 72 requirements state that a technician be on-site and at the control panel whenever the PK-Plus Programming Utility is used to download any information to the FACP. This applies to local and remote programming. For this reason, a new option has been added to the FACP which allows an individual at the FACP to enter a password and either enable the proprietary mode where downloading will be allowed at any time or access a specific password protected screen where downloading will be allowed regardless of the current proprietary setting. The Remote Download option can be selected from the main menu screen as shown below:
entries and compare to intended program data
1=READ STATUS MODE 2=PROGRAMMING MODE 3=REMOTE DOWNLOAD
DACT-UD2 Communicator PN 53037:B 4/01/08 33
Remote Site Upload/Download
Pressing 3 for Remote Download while viewing the main menu will cause the following screen to be displayed:
REMOTE DOWNLOAD ENTER PASSWORD *****
The Remote Download password (default 00000) must be entered to access the Remote Download feature. Note that the default password can be changed using the Password Change option (refer to the FACP manual programming section). Entering the correct password will cause the following screen to be displayed:
REMOTE DOWNLOAD 1=PROPRIETARY NO 2=ACCEPT DOWNLOAD
Pressing 1 for Proprietary No (factory default setting), while viewing the Remote Download screen, will cause the display to toggle from Proprietary No to Proprietary Yes. Each press of the 1 key will cause the display to toggle between Proprietary No and Proprietary Yes. Selecting Proprietary Yes will program the FACP to allow remote programming downloads from the PK-Plus programming utility at all times without the need to access the Remote Download screen.
Pressing 2 for Accept Download will cause the following screen to be displayed:
*ALLOWING DOWNLOADS* IF YOU EXIT THIS SCREEN DOWNLOADS WILL BE DISABLED!
While this screen is displayed, remote programming downloads are allowed regardless of the Proprietary setting. Exiting this screen will disable any further downloads to the FACP. Also, following 30 minutes of inactivity (including up/downloading), the Accept Download screen will time-out, causing the display to return to the System All Normal screen.
34 DACT-UD2 Communicator PN 53037:B 4/01/08

5.2 Transferring a Program

The first time that the control panel is downloaded (whether initiated at the jobsite or remotely), a secret code is loaded in by a Service Terminal. Future upload or download requests cause verification of the secret code by the control panel before processing of data is allowed. If the secret code is not verified, the control panel will terminate the request.
While the control panel is communicating with the Service Terminal, one of the DACT’s red phone line active LEDs and the green Kissoff LED will turn on steady.
In order to download the panel (whether initiated at the jobsite or remotely), the following must be true:
The control panel must be in the Normal Mode of operation. Downloading is
not possible if the panel is in any other mode
There cannot be any active communications ongoing with a Central Station
receiver
All active events must be successfully 'kissed-off' by the Central Station(s).
The communicator must be in a standby state with no new information waiting to be transmitted to a Central Station
Remote Site Upload/Download

5.2.1 Security Features

Upload and download with the control panel have been carefully designed to include key security features to ensure proper functionality. Any time a transfer is initiated, the control panel and the Service Terminal will communicate and transfer data before contacting a Central Station. When the data transfers are completed and the control panel disconnects from the Service Terminal, the control panel will call the Central Station and report one of the following conditions:
Upload/Download request received
Upload and/or Download request successful
Upload/Download failed
The key features are listed and explained in the following sections.
Secret Code Verification
A secret code is stored in the control panel by a Service Terminal to prevent unauthorized access. The secret code is created at the Service Terminal by the master user and cannot be viewed or changed by anyone other than a master user. Viewing of the secret code is prohibited at the control panel. Prior to allowing an upload or download of data, the control panel will verify the secret code transmitted by the Service Terminal.
Time-out at Control Panel
Upon answering an incoming call on either the primary or secondary Central Station phone line, the control panel will listen for a modem connection signal. If this signal is not received within 50 seconds, the control panel will disconnect the call. Upon successful connection (secret code verified), if no communication occurs within 30 minutes, the panel will disconnect the call. Upon time-out, transfer activity will be reported to the Central Station (if enabled) and the connection will be terminated.
DACT-UD2 Communicator PN 53037:B 4/01/08 35
Remote Site Upload/Download
Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If an error is detected, the block is retransmitted until correct, up to a maximum of four times. If the Secret Code is not verified and four errors occur, the call is disconnected and the report that the upload/download was not successful is called to the Central Station(s).
Central Station Data Protection
The primary and secondary Central Station phone numbers, communications format, account code, test time and programmable event codes are vital Central Station information. These blocks of data are protected from partial programming due to faulty phone connections, line noise and other errors. This prevents the panel from being confused due to a wrong phone number, account code, test time and most critical formatting errors.
36 DACT-UD2 Communicator PN 53037:B 4/01/08

APPENDIX A Default Programming

The following table provides a list of the programming options and their factory default settings.
Program Option Factory Default
ON Board DACT Disabled Service Terminal Primary Phone Line Type Touch Tone Service Terminal Secondary Phone Line Type Touch Tone Service Terminal Primary Phone Number all Fs Service Terminal Secondary Phone Number all Fs Service Terminal Phone Ring Count. 0 Central Station Reporting Disabled Central Station AC Loss Reporting Delay 2 Central Station Backup Reporting First A v ai lable Central Station Reporting Style Reporting by Point Central Station Trouble Call Limit 0 Central Station Primary Phone Line Test Time 0000 Central Station Secondary Phone Line Test Time 0000 Central Station Primary Phone Line Test Time Interval 24 Central Station Secondary Phone Line Test Time Interval 24 Central Station Primary Phone Line Account Code 0000 Central Station Secondary Phone Line Account Code 0000 Central Station Primary Phone Number Central Station Secondary Phone Number Central Station Primary Phone Communication Format Ademco Contact ID Central Station Secondary Phone Communication Format Ademco Contact ID
Default Programming
DACT-UD2 Communicator PN 53037:B 4/01/08 37
Ademco Contact ID Format Event Code Descriptions
APPENDIX B Ademco Contact ID Format
Event Code Descriptions
This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format.

B.1 Transmission Format Between DACT and Receiver

The transmission string for the Ademco Contact ID Format is as follows: SSSS 18 QXYZ GG CCC where
SSSS = Four digit Subscriber ID Account Code 18 = Identifies transmission as Contact ID to the receiver at the Central Station Q = Event Qualifier where 1 = New Event and 3 = New Restore XYZ = Event code GG = Group number CCC = Zone/Point number (refer to Table C.1 on page 43 )
Notes:
1. 18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the alarm and trouble report.
2. GG Group Number is fixed at '00' and cannot be changed.
3. CCC for Zone or Point Number:
Zone Number is transmitted as ‘001’ for zone 1 up to ‘099’ for zone 99Point Number is transmitted as ‘001’ for point/address 1 up to ‘636’ for point/
address 636

B.2 Ademco Contact ID Typical Printout

A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows:
Time Date Rcvr/Line ID SSSS QXYZ GG CCCC
11:28 03/25 11 7777 E110 00 C001 - general fire alarm on zone one 11:28 03/25 11 7777 E111 00 C002 - smoke detector alarm on zone two 11:28 03/25 11 7777 E380 00 C003 - fault on zone three 11:28 03/25 11 7777 E570 00 C009 - Zone nine disabled 11:28 03/25 11 7777 R110 00 C001 - Zone one alarm restored 11:28 03/25 11 7777 R111 00 C002 - smoke detector zone two restored 11:28 03/25 11 7777 R380 00 C003 - zone three fault restored 11:28 03/25 11 7777 R570 00 C009 - zone nine reenabled 11:28 03/25 11 7777 E158 00 C006 - high temperature, zone six 11:28 03/25 11 7777 E151 00 C007 - gas detected, zone seven
Notes:
1. 11 is an example of a Receiver/Line Card, showing which receiver and line card the message was transmitted to.
2. Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an
38 DACT-UD2 Communicator PN 53037:B 4/01/08
E for New Event or R for New Restore.
Ademco Contact ID Format Event Code Descriptions
EVENT CODE CLASSIFICATIONS
100
ALARMS
Medical Fire Panic Burglary General 24 Hour
200
SUPERVISORY
Fire
EVENT MESSAGE
Medical Alarms - 100 100 Medical EMERG - Personal Emergency - # 101 Pendant transmitter EMERG - Personal Emergency - # 102 Fail to report in EMERG Fail to Check- in #
Fire Alarms - 110 110 Fire Alarm FIRE - Fire Alarm - # 111 Smoke FIRE -Smoke Detector# 112 Combustion FIRE - Combustion - # 113 Waterfl ow FIRE - Waterflow - # 114 Heat FIRE - Heat Sensor - # 115 Pull station FIRE - Pull Station - # 116 Duct FIRE - Duct Sensor - # 117 Flame FIRE - Flame Sensor - # 118 Near Alarm FIRE - Near Alarm - #
300
TROUBLES
System Sounder/Relay System Peripheral Communication Protective Loop Sensor
400
OPEN/CLOSE
REMOTE ACCESS
Open/Close Remote Access Access Control
500
DISABLES/
BYPASSES
System Sounder/Relay System Peripheral Communication
600 TEST/ MISC.
Te st
Panic Alarms - 120 120 Panic Alarm PANIC - Panic - # 121 Duress PANIC - Duress 122 Silent PANIC -Silent Panic # 123 Audible PANIC -Audible Panic#
Burglar Alarms - 130 130 Burglary BURG - Burglary - # 131 Perimeter BURG - Perimeter - # 132 Interior BURG - Interior - # 133 24-Hour BURG - 24-Hour - # 134 Entry/Exit BURG - Entry/Exit - # 135 Day/Night BURG - Day/Night - # 136 Outdoor BURG - Outdoor - # 137 Tamper BURG - Tamper - # 138 Near Alarm BURG - Near Alarm - #
General Alarms - 140 140 General Alarm ALARM - General Alarm - # 141 Polling loop open ALARM - Polling Loop Open - # 142 Polling loop short ALARM - Polling Loop Short - # 143 Expansion module failure ALARM - Exp. Module Fail - # 144 Sensor tamper ALARM - Sensor Tamper - # 145 Expansion module tamper ALARM - Exp.Module Tamper - #
DACT-UD2 Communicator PN 53037:B 4/01/08 39
Ademco Contact ID Format Event Code Descriptions
EVENT MESSAGE
24 Hour Non-Burglary - 150 and 160 150 24-Hour Non-Burg ALARM - 24-Hr. Non-Burg - # 151 Gas detected ALARM - Gas Detected - # 152 Refrigeration ALARM - Refrigeration - # 153 Loss of heat ALARM - Heating System - # 154 Water leakage ALARM - Water Leakage - # 155 Foil break ALARM - Foil Break - # 156 Day trouble ALARM - Day Zone - # 157 Low bottled gas level ALARM - Low Gas Level - # 158 High temp ALARM - High Temperature - # 159 Low temp ALARM - Low Temperature - # 161 Loss of air flow ALARM - Air Flow - #
Fire Supervisory - 200 and 210 200 Fire supervisory S UPER. - Fire Supervisory - # 201 Low water pressure SUPER. - Low Water Pressure - # 202 Low CO2 SUPER. - Low CO2 203 Gate valve sensor SUPER. - Gate Valve - # 204 Low water level SUPER. - Low Water Level - # 205 Pump activated SUPER. - Pump Activation - # 206 Pump failure SUPER. - Pump Failure - #
System Troubles - 300 and 310 300 System trouble TROUBLE - System Trouble 301 AC loss TROUBLE - AC Power 302 Low system battery TROUBLE - System Low Battery 303 RAM checksum bad TROUBLE - Bad RAM Checksum (no restore) 304 ROM checksum bad TROUBLE - Bad ROM Checksum (no restore) 305 System reset TROUBLE - System Reset (no restore) 306 Panel program changed TROUBLE - Programming Changed (no restore 307 Self-test failure TROUBLE - Self Test Failure 308 System shutdown TROUBLE - System Shutdown 309 Battery test failure TROUBLE - Battery Test Failure 310 Ground fault TROUBLE - Ground Fault - # 311 No battery TROUBLE - No Battery
Sounder/Relay Troubles - 320 320 Sounder/Relay TROUBLE - Sounder Relay - # 321 Bell 1 TROUBLE - Bell/Siren #1 322 Bell 2 TROUBLE - Bell/Siren #2 323 Alarm relay TROUBLE - Alarm Relay 324 Trouble relay TROUBLE - Trouble Relay 325 Reversing TROUBLE - Reversing Relay 326 Bell 3 TROUBLE - Bell/Siren #3 327 Bell 4 TROUBLE - Bell/Siren #4
System Peripheral Troubles - 330 and 340 330 System peripheral TROUBLE - Sys. Peripheral - # 331 Polling loop open TROUBLE - Polling Loop Open 332 Polling loop short TROUBLE - Polling Loop Short 333 Expansion module failure TROUBLE - Exp. Module Fail - # 334 Repeater failure TROUBLE - Repeater Failure - # 335 Local printer paper out TROUBLE - Printer Paper Out 336 Local printer failure TROUBLE - Local Printer
40 DACT-UD2 Communicator PN 53037:B 4/01/08
Ademco Contact ID Format Event Code Descriptions
EVENT MESSAGE
Communication Troubles - 350 and 360 350 Communication TROUBLE - Communication Trouble 351 Telco 1 fault TROUBLE - Phone Line #1 352 Telco 2 fault TROUBLE - Phone Line #2 353 Long range radio xmitter fault TROUBLE - Radio Transmitter 354 Fail to communicate TROUBLE - Fail to Communicate 355 Loss of radio supervision TROUBLE - Radio Supervision 356 Loss of central polling TROUBLE - Central Radio Polling
Protection Loop Troubles - 370 370 Protection loop TROUBLE - Protection Loop - # 371 Protection loop open TROUBLE - Protection Loop Open - # 372 Protection loop short TROUBLE - Protection Loop Short - # 373 Fire Trouble TROUBLE - Fire Loop - #
Sensor Troubles - 380 380 Sensor trouble TROUBLE - Sensor Trouble - # 381 Loss of supervision - RF TROUBLE - RF Sensor Supervision - # 382 Loss of supervision - RPM TROUBLE - RPM Sensor Supervision - # 383 Sensor tamper TROUBLE - Sensor Tamper - # 384 RF transmitter low battery TROUBLE - RF Sensor Batt. - #
Open/Close - 400 400 Open/Close OPENING CLOSING 401 Open/Close by user OPENING - User # CLOSING - User # 402 Group Open/Close OPENING - GroupUser# CLOSING-GroupUser 403 Automatic Open/Close OPENING - Automatic CLOSING - Automatic 404 Late Open/Close OPENING - Late CLOSING - Late 405 Deferred Open/Close Opening not used Closing not used 406 Cancel OPENING - Cancel Closing not used 407 Remote arm/disarm OPENING - Remote CLOSING - Remote 408 Quick arm Opening not applicable CLOSING - Quick arm 409 Keyswitch Open/Close OPENING - Keyswitch CLOSING - Keyswitch
Remote Access - 410 411 Callback request made REMOTE - Callback Requested (no restore) 412 Success - download/access REMOTE - Successful Access (no restore) 413 Unsuccessful access REMOTE - Unsuccessful Access (no restore) 414 System shutdown REMOTE - System Shutdown 415 Dialer shutdown REMOTE - Dialer Shutdown 416 Success - upload/access REMOTE - Successful Access (no restore)
Access Control - 420 421 Access denied ACCESS - Access Denied - User # (no restore) 422 Access report by user ACCESS - Access Gained - User # (no restore)
System Disables - 500 and 510
DACT-UD2 Communicator PN 53037:B 4/01/08 41
Ademco Contact ID Format Event Code Descriptions
EVENT MESSAGE
Sounder/Relay Disables - 520 520 Sounder/Relay disable DISABLE - Sounder/Relay - # 521 Bell 1 disable DISABLE - Bell/Siren - #1 522 Bell 2 disable DISABLE - Bell/Siren - #2 523 Alarm relay disable DISABLE - Alarm Relay 524 Trouble relay disable DISABLE - Trouble Relay 525 Reversing relay disable DISABLE - Reversing Relay 526 Bell 3 disable DISABLE - Bell/Siren - #3 527 Bell 4 disable DISABLE - Bell/Siren - #4
System Peripheral Disables - 530 and 540
Communication Disables - 550 and 560 551 Dialer disabled DISABLE - Dialer Disable 552 Radio transmitter disabled DISABLE - Radio Disable
Bypasses - 570 570 Zone bypass BYPASS - Zone Bypass - # 571 Fire bypass BYPASS - Fire Bypass - # 572 24-Hour zone bypass BYPASS - 24-Hour Bypass - # 573 Burglar bypass BYPASS - Burg. Bypass - # 574 Group bypass BYPASS - Group Byp a ss - #
Test Misc. - 600 601 Manual trigger test TEST - Manually Triggered (no restore) 602 Periodic test report TEST - Periodic (no restore) 603 Periodic RF transmission TEST - Periodic Radio (no restore) 604 Fire test TEST - Fire Test (restore not used) 605 Status report to follow STATU S - Status Follows (no restore) 606 Listen-in to follow LISTEN - Listen-in Active (no restore) 607 Walk test mode TEST - Walk Test Mode 608 System abnormal test TEST - System Abnormal Test
42 DACT-UD2 Communicator PN 53037:B 4/01/08

APPENDIX C Central Station Points

The DACT -UD2 transmits Central St ation Reports in a numerical format which indicates the FACP addressable device address that is reporting and the SLC loop on which it resides. The following table indicates the Central Station Report (CS Report) number that will be transmitted and the addressable device address and SLC loop number it represents.
Table C.1 Addressable DETECTORS on SLC Loop 1
Central Station Points
CS
Report
001 001 033 033 065 065 097 097 129 129 002 002 034 034 066 066 098 098 130 130 003 003 035 035 067 067 099 099 131 131 004 004 036 036 068 068 100 100 132 132 005 005 037 037 069 069 101 101 133 133 006 006 038 038 070 070 102 102 134 134 007 007 039 039 071 071 103 103 135 135 008 008 040 040 072 072 104 104 136 136 009 009 041 041 073 073 105 105 137 137 010 010 042 042 074 074 106 106 138 138 011 011 043 043 075 075 107 107 139 139 012 012 044 044 076 076 108 108 140 140 013 013 045 045 077 077 109 109 141 141 014 014 046 046 078 078 110 110 142 142 015 015 047 047 079 079 111 111 143 143 016 016 048 048 080 080 112 113 144 144 017 017 049 049 081 081 113 113 145 145 018 018 050 050 082 082 114 114 146 146 019 019 051 051 083 083 115 115 147 147 020 020 052 052 084 084 116 116 148 148 021 021 053 053 085 085 117 117 149 149 022 022 054 054 086 086 118 118 150 150 023 023 055 055 087 087 119 119 151 151 024 024 056 056 088 088 120 120 152 152 025 025 057 057 089 089 121 121 153 153 026 026 058 058 090 090 122 122 154 154 027 027 059 059 091 091 123 123 155 155 028 028 060 060 092 092 124 124 156 156 029 029 061 061 093 093 125 125 157 157 030 030 062 062 094 094 126 126 158 158 031 031 063 063 095 095 127 127 159 159 032 032 064 064 096 096 128 128
Detector Address
Loop 1
CS
Report
Detector
Address
Loop 1
CS
Report
Detector Address
Loop1
CS
Report
Detector
Address
Loop 1
CS
Report
Detector
Address
Loop 1
DACT-UD2 Communicator PN 53037:B 4/01/08 43
Central Station Points
Table C.2 Addressable MODULES on SLC Loop 1
CS
Report
160 001 192 033 224 065 256 097 288 129 161 002 193 034 225 066 257 098 289 130 162 003 194 035 226 067 258 099 290 131 163 004 195 036 227 068 259 100 291 132 164 005 196 037 228 069 260 101 292 133 165 006 197 038 229 070 261 102 293 134 166 007 198 039 230 071 262 103 294 135 167 008 199 040 231 072 263 104 295 136 168 009 200 041 232 073 264 105 296 137 169 010 201 042 233 074 265 106 297 138 170 011 202 043 234 075 266 107 298 139 171 012 203 044 235 076 267 108 299 140 172 013 204 045 236 077 268 109 300 141 173 014 205 046 237 078 269 110 301 142 174 015 206 047 238 079 270 111 302 143 175 016 207 048 239 080 271 113 303 144
Module
Address
Loop 1
CS
Report
Module
Address
Loop 1
CS
Report
Module
Address
Loop1
CS
Report
Module
Address
Loop 1
CS
Report
Module
Address
Loop 1
176 017 208 049 240 081 272 113 304 145 177 018 209 050 241 082 273 114 305 146 178 019 210 051 242 083 274 115 306 147 179 020 211 052 243 084 275 116 307 148 180 021 212 053 244 085 276 117 308 149 181 022 213 054 245 086 277 118 309 150 182 023 214 055 246 087 278 119 310 151 183 024 215 056 247 088 279 120 311 152 184 025 216 057 248 089 280 121 312 153 185 026 217 058 249 090 281 122 313 154 186 027 218 059 250 091 282 123 314 155 187 028 219 060 251 092 283 124 315 156 188 029 220 061 252 093 284 125 316 157 189 030 221 062 253 094 285 126 317 158 190 031 222 063 254 095 286 127 318 159 191 032 223 064 255 096 287 128
44 DACT-UD2 Communicator PN 53037:B 4/01/08
Table C.3 Addressable DETECTORS on SLC Loop 2
Central Station Points
CS
Report
319 001 351 033 383 065 415 097 447 129 320 002 352 034 384 066 416 098 448 130 321 003 353 035 385 067 417 099 449 131 322 004 354 036 386 068 418 100 450 132 323 005 355 037 387 069 419 101 451 133 324 006 356 038 388 070 420 102 452 134 325 007 357 039 389 071 421 103 453 135 326 008 358 040 390 072 422 104 454 136 327 009 359 041 391 073 423 105 455 137 328 010 360 042 392 074 424 106 456 138 329 011 361 043 393 075 425 107 457 139 330 012 362 044 394 076 426 108 458 140 331 013 363 045 395 077 427 109 459 141 332 014 364 046 396 078 428 110 460 142 333 015 365 047 397 079 429 111 461 143 334 016 366 048 398 080 430 113 462 144 335 017 367 049 399 081 431 113 463 145 336 018 368 050 400 082 432 114 464 146 337 019 369 051 401 083 433 115 465 147 338 020 370 052 402 084 434 116 466 148 339 021 371 053 403 085 435 117 467 149 340 022 372 054 404 086 436 118 468 150 341 023 373 055 405 087 437 119 469 151 342 024 374 056 406 088 438 120 470 152 343 025 375 057 407 089 439 121 471 153 344 026 376 058 408 090 440 122 472 154 345 027 377 059 409 091 441 123 473 155 346 028 378 060 410 092 442 124 474 156 347 029 379 061 411 093 443 125 475 157 348 030 380 062 412 094 444 126 476 158 349 031 381 063 413 095 445 127 477 159 350 032 382 064 414 096 446 128
Detector Address
Loop 2
CS
Report
Detector
Address
Loop 2
CS
Report
Detector Address
Loop2
CS
Report
Detector
Address
Loop 2
CS
Report
Detector
Address
Loop 2
DACT-UD2 Communicator PN 53037:B 4/01/08 45
Central Station Points
Table C.4 Addressable MODULES on SLC Loop 2
CS
Report
478 001 510 033 542 065 574 097 606 129 479 002 511 034 543 066 575 098 607 130 480 003 512 035 544 067 576 099 608 131 481 004 513 036 545 068 577 100 609 132 482 005 514 037 546 069 578 101 610 133 483 006 515 038 547 070 579 102 611 134 484 007 516 039 548 071 580 103 612 135 485 008 517 040 549 072 581 104 613 136 486 009 518 041 550 073 582 105 614 137 487 010 519 042 551 074 583 106 615 138 488 011 520 043 552 075 584 107 616 139 489 012 521 044 553 076 585 108 617 140 490 013 522 045 554 077 586 109 618 141 491 014 523 046 555 078 587 110 619 142 492 015 524 047 556 079 588 111 620 143 493 016 525 048 557 080 589 113 621 144 494 017 526 049 558 081 590 113 622 145 495 018 527 050 559 082 591 114 623 146 496 019 528 051 560 083 592 115 624 147 497 020 529 052 561 084 593 116 625 148 498 021 530 053 562 085 594 117 626 149 499 022 531 054 563 086 595 118 627 150 500 023 532 055 564 087 596 119 628 151 501 024 533 056 565 088 597 120 629 152 502 025 534 057 566 089 598 121 630 153 503 026 535 058 567 090 599 122 631 154 504 027 536 059 568 091 600 123 632 155 505 028 537 060 569 092 601 124 633 156 506 029 538 061 570 093 602 125 634 157 507 030 539 062 571 094 603 126 635 158 508 031 540 063 572 095 604 127 636 159 509 032 541 064 573 096 605 128
Modules Address
Loop 2
CS
Report
Modules
Address
Loop 2
CS
Report
Modules Address
Loop2
CS
Report
Modules
Address
Loop 2
CS
Report
Modules
Address
Loop 2
46 DACT-UD2 Communicator PN 53037:B 4/01/08
Index
Numerics 24 Hour Test Time 25 A Account Code 24 Ademco
contact ID format 38 Alarm Current 8 B Backup
Reporting 22 C Central Station 21, 36
Communication 30
Phone Number 23, 25
point assignments 43 Central Station Communications 30 Central Station Reports 43 Communication
Central Station 30 Communication Format 26 Communication Formats 9 Compatible Panel 8 contact ID 38 Current
Alarm 8
Standby 8 D DACT
Installation 14
Programming 19 DACT-UD2
option module installation 14 DC Power 8 Default Programming 37 Description 8 dial tone 9 Digital Communicator 9 Downloading 35 E Enable
DACT 19
Reporting 21 Error Checking 36 event code classification 39 Event Codes 26 F Features 8 I Installation of DACT
MS-9600LS 13 K Keypad/Display
removal and installation 13 L Line Seizure 9 O Off/On Hook 9 On-Board DACT
Programming 19 P Panel Compatibility 8 Phone Number
Central Station 23, 25 point assignments 43 Point Reporting 29 Primary Phone 19 Priorities
Transmittal 31 Product Features 8 Programming
factory default 37
MS-9600LS for DACT-UD-2 18 Proprietary Yes
see also Remote Upload 34 R Receivers 32 receivers
UL listed 32 Remote Download 33 REN
see also Ringer Equivalence Number 10 Report Style 29 Reporting
Backup 22
Enable 21 Ring Count 20 Ringer Equivalence Number 10 Rotary dialing 19 S Secondary Phone 20 Secret Code 35 Security Features 35 Service Terminal 20 Specifications 8 Standby Current 8 T Telephone
Circuitry 10
DACT-UD2 Communicator PN 53037:B 4/01/08 47
Requirements 10
Telephone Company
Rights and Warnings 11 Telephone Connection 15 Test Time
24 Hour 25 Test Time Interval 24, 25 Time-out 35 tone burst 9 touchtone 9 Touchtone dialing 19 Transmittal
Priorities 31 Transmittal Priorities 31 U Upload/Download 33 W Warnings 10 Z Zone Reporting 29
Index
48 DACT-UD2 Communicator PN 53037:B 4/01/08
Notes
DACT-UD2 Communicator PN 53037:B 4/01/08 49
Notes
50 DACT-UD2 Communicator PN 53037:B 4/01/08
Limited Warranty
Honeywell International Inc. warrants products manufactured by it
to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufa cture. The sole and exclusive obligation of Honeywell International Inc. is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. Honeywell International Inc. does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than Honeywell
International Inc. or as expressly authorized by Honeywell International Inc. in writing, or is serviced by anyone other than Honeywell International Inc. or its authorized distributors. This
warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products. Honeywell International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Honeywell International Inc., is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE F ACE HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE HONEYWELL
INTERNATIONAL INC.’S PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by Honeywell International Inc. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
Warn-HL-05-2007.fm
World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.firelite.com
Loading...