Fire-Lite DACT-UD User Manual

PN: 51899:B1 ECN 05-044
Digital Alarm Communicator/Transmitter
DACT-UD Module
Document #51899
B
1/25/05 Revision:
1
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, com­munications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medi­cation. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A main­tenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized profes­sional fire alarm installers only. Adequate written records of all inspections should be kept.
PrecauLarge.PMD 01/10/2005
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for indoor dry opera­tion at 0-49° C/32-120° F RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the elec­tronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recom­mended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of 93 ±2%
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is com­pletely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or out-
side aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are antici­pated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can ra-
diate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause in­terference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environ­ment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
PrecauLarge.PMD 01/10/2005
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Notes
4 DACT-UD PN 51899:B1 1/25/05
Table of Contents
SECTION 1: Product Description ........................................................................................................................8
1.1: Product Features..........................................................................................................................................8
1.2: Compatible Panel ........................................................................................................................................8
1.3: Specifications ..............................................................................................................................................8
1.4: Digital Communicator.................................................................................................................................9
1.5: Telephone Requirements and Warnings ......................................................................................................10
1.5.1: Telephone Circuitry - PH1 & PH2....................................................................................................10
1.5.2: Digital Communicator.......................................................................................................................10
1.5.3: Telephone Company Rights and Warnings.......................................................................................11
SECTION 2: DACT-UD Installation ....................................................................................................................13
2.1: Installation in MS-9600 FACP....................................................................................................................13
2.1.1: MS-9600 Keypad/Display Removal .................................................................................................13
2.1.2: DACT-UD Installation ......................................................................................................................14
SECTION 3: Programming for DACT-UD .........................................................................................................17
3.1: Programming the MS-9600 Fire Alarm Control Panel ...............................................................................17
3.1.1: On-Board DACT...............................................................................................................................17
3.1.1.1 DACT-UD Enable ...................................................................................................................17
3.1.1.2 Primary Phone .........................................................................................................................18
3.1.1.3 Secondary Phone .....................................................................................................................18
3.1.1.4 Service Terminal .....................................................................................................................19
3.1.1.4.1 Panel ID ................................................................................................................................19
3.1.1.4.2 Terminal 1 and Terminal 2 ...................................................................................................20
3.1.1.4.3 Ring Count ...........................................................................................................................21
3.1.1.5 Central Station .........................................................................................................................21
3.1.1.5.1 Reporting Enable ..................................................................................................................21
3.1.1.5.2 Backup Reporting ................................................................................................................22
3.1.1.5.3 Trouble Call Limit (Dialer Runaway Prevention) ...............................................................22
3.1.1.5.4 Central Station Primary and Secondary Phone Numbers ....................................................23
3.1.1.6 Manual Dial Mode ..................................................................................................................35
3.2: Remote Site Upload/Download...................................................................................................................36
3.2.1: Downloading Program: General .......................................................................................................36
3.2.2: Security Features...............................................................................................................................37
3.3: Downloading Initiated at a Service Terminal..............................................................................................39
3.4: Uploading Initiated at a Service Terminal...................................................................................................39
3.5: Simultaneous Data Transfers.......................................................................................................................40
SECTION 4: Central Station Communications ..................................................................................................41
4.1: Transmittal Priorities...................................................................................................................................44
APPENDIX A: Default Programming .................................................................................................................46
APPENDIX B: Ademco Contact ID Format
...................................................................................................................................................................................
Event Code Descriptions ........................................................................................................................................47
APPENDIX C: Central Station Points ................................................................................................................52
DACT-UD P/N: 51889:B1 1/25/05 5
Notes
6 DACT-UD PN 51899:B1 1/25/05
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
• Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected Premises Unit
• Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems
• Proprietary Fire Alarm Systems (Protected Premises Unit) NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired
Other:
EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 MS-9600 Manual Document #51335
DACT-UD PN 51899:B1 1/25/05 7
Product Description Product Features
SECTION 1 Product Description
The DACT-UD Digital Alarm Communicator/Transmitter transmits system status to UL listed Central Station Receivers via the public switched telephone network. The communicator mounts to the FACP main circuit board inside the panel cabinet and is capable of reporting 636 points or 99 zones.
1.1 Product Features
Dual telephone lines
Dual telephone line voltage detect
Mounts inside the control panel
Extensive transient protection
Individual LEDs for
Kissoff - green LEDPrimary Phone Line Active - red LEDSecondary Phone Line Active - red LED
Communicates vital system status including:
Independent zone/point alarmIndependent zone/point troubleIndependent zone/point supervisoryAC power lossLow battery Earth faultSystem off normal12 or 24 hour test signalAbnormal test signal per UL requirementsAnnunciation at control panel of DACT troubles including loss of phone lines,
communication failure with either Central Station, total communication failure
1.2 Compatible Panel
The DACT-UD has been designed to be compatible with the following control panel:
MS-9600
1.3 Specifications
DC Power - J1 Connector
Current draw in standby and alarm:
Standby = 0.100 ampsAlarm = 0.132 amps (communicating)
8 DACT-UD PN 51899:B1 1/25/05
Digital Communicator Product Description
1.4 Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the Primary and Secondary phone lines. Telephone line Primary Active and Secondary Active red LEDs are provided as well as a green Kissoff LED> The digital communicator provides the following functions:
Line Seizure - takes control of phone lines disconnecting any premises phones
Off/On Hook - performs on and off-hook status to the phone lines
Listen for dial tone - 440 hertz tone typical in most networks
Dialing Central Station(s) number - default is Touch-Tone®, programmable to rotary
For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and ‘Kissoff’ tone(s) - the frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
Communicate in the following formats: 12 Tone Burst Types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
3 Touchtone Types:
4+1 Ademco Express 4+2 Ademco Express Ademco Contact ID
DACT-UD PN 51899:B1 1/25/05 9
Product Description Telephone Requirements and Warnings
1.5 Telephone Requirements and Warnings
1.5.1 Telephone Circuitry - PH1 & PH2
Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
1.5.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equip­ment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Product Model Number: DACT-UD
FCC Registration Number: US:1W6AL00BDACTUD
Ringer Equivalence: 0.0B
Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the DACT-UD module IC is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to Figure 2.6 on page 16 for an illustration of the proper installation of this equipment.
10 DACT-UD PN 51899:B1 1/25/05
Telephone Requirements and Warnings Product Description
1.5.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarili discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notifica­tion will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream (as first device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or pre­mises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
DACT-UD PN 51899:B1 1/25/05 11
Notes
This Page Left Intentionally Blank
12 DACT-UD PN 51899:B1 1/25/05
Installation in MS-9600 FACP DACT-UD Installation
A
SECTION 2 DACT-UD Installation
2.1 Installation in MS-9600 FACP
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
2.1.1 MS-9600 Keypad/Display Removal
DACT-UD (Digital Alarm Communicator/Transmitter) Module installation requires the removal of the MS-9600 Keypad/Display unit from the main circuit board. To remove the Keypad/Display, insert a Phillips screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and loosen the three mounting screws. Note that it is not necessary to disconnect the cables between the Keypad/Display and the main circuit board. Carefully lift the Keypad/Display and rest the unit at the bottom of the main circuit board.
Mounting Screw Access Hole
TB3
JP3
REMOVE TO DISABLE LOCAL CHARGER
JP10
JP2
2
1
DISABL E GND FLT
4
5
GHI JKL
J17
J16
78 9
PRS
0
*
QZ
RECALL
HOT
CB1
4XTM OPT BD
ABC DEF
CUT TO MONITOR 4XTM
TUV WXY
LCD DISPLAY
NEUT E ARTH
TB4 TB5
JP6
AC POWER
FIRE ALARM
SUPERVISORY
st
3
1
JP8
EVENT
JP7
CLR
6
MNO
JP6
ESC
MODE
#
TB1
-/.
+BATTERY-
TB2
ENTER
J6
KEYPAD I/F
TROUBLE
J2
OPT DACT
J8
CK/STEP
ALARM SILENCE
JP5
MAINTENANCE
ALARM SILENCED
DISABLED
BATTERY
GROUND
DRILL
HOLD 2 SEC
RESET
Mounting Screw Access Holes
Figure 2.1 Keypad/Display Removal
TB6 TB7
JP4
1 2 3
J7
TB8
OPT SLC
J3
DACT-UD PN 51899:B1 1/25/05 13
DACT-UD Installation Installation in MS-9600 FACP
2.1.2 DACT-UD Installation
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
The DACT-UD module plugs into connector J2 on the MS-9600 main circuit board.
Primary Active LED
Kissoff LED
PH1 Primary Phone Line
PH2 Secondary Phone Line
Secondary Active LED
9600DACT.CDR
J1 Connector (located on back of module) plugs into J2 on MS-9600 main circuit board
Figure 2.2 DACT-UD Module
The following steps must be followed when installing the DACT module:
1. Remove all power (AC and DC) from the FACP before proceeding with the installation
2. Remove the Keypad/Display from the main circuit board as described in the beginning of this section
14 DACT-UD PN 51899:B1 1/25/05
Installation in MS-9600 FACP DACT-UD Installation
3. Insert the supplied plastic snap-in standoff into mounting hole located at the bottom center of the DACT-UD module (insert into back of board)
4. Carefully plug connector J1 on the back of the DACT-UD module into connector J2 on the MS-9600 main circuit board, being careful not to bend any pins and at the same time, insert plastic snap-in standoff into mounting hole in main board
5. Align the mounting holes in the DACT module with the premounted standoffs on the FACP main circuit board
Standoff
Standoff
Standoff
J2
Standoff (snap-in)
J1
J1 Connector located on back of DACT module
Figure 2.3 DACT J1 Connector to FACP J2 Connector
6. Secure the module to the standoffs on the main circuit board with the three screws supplied with the DACT-UD. It is important that the supplied screws be used to secure the module to the metal standoff in order to help protect against electrical transients.
Mounting Screw
Mounting Screws
96dact2.CDR
Snap-in Standoff
96dact3.CDR
Figure 2.4 DACT Installation on Standoffs
7. Reinstall the Keypad/Display on the main circuit board by positioning the unit over the appropriate standoffs and securing with the screws which were loosened in step 2
8. Make certain to program the control panel for DACT operation
DACT-UD PN 51899:B1 1/25/05 15
DACT-UD Installation Installation in MS-9600 FACP
9. Refer to "Digital Communicator" on page 10, before proceeding with this step. Connect the premises primary and secondary phone lines to the DACT as illustrated in Figure 2.5 and test the system for correct operation
Primary Lines Incoming Telco Phone Lines
Tip
Ring
Primary Phone Line PH-1
Green Wire
Red Wire
1 2 3 4 5 6 7 8
RJ3 1-X
Jack
PH1
Ring
Red Wire
Ring
Tip
To premise phones
Tip
Note: Shorting bars inside RJ31X Jack removed during male plug insertion
7 foot cable (MCBL-7) order separately
Male Plug Connectors
Female Connectors
J3
J2
CAUTION: It is critical that the DACT-UD be located as the first device on the incoming telephone circuit to properly function
PH2
Green Wire
1 2 3 4 5 6 7 8
RJ31 -X
Jack
Secondary Lines Incoming Telco Phone Lines
Ring
To premise phones
Tip
Secondary Phone Line PH-1
DACT-UD
Figure 2.5 Wiring Phone Jacks
It is critical that the DACT be located as the first device on the incoming telephone circuit to properly function.
Customer Premises Equipment and Wiring
M
S
2
9
­0
0
U
Network
Service
Provider’s
Facilities
RJ31X
Jack
D
Computer
Unused
RJ-11 Jack
MS-9600 with DACT-UD
Telephone
Line
Telephone
Network
Demarcation
Fax Machine
Unused
RJ-11 Jack
Point
Telephone
Answering
System
Telephone
Figure 2.6 DACT Installation
16 DACT-UD PN 51899:B1 1/25/05
Programming the MS-9600 Fire Alarm Control Panel Programming for DACT-UD
SECTION 3 Programming for DACT-UD
3.1 Programming the MS-9600 Fire Alarm Control Panel
Refer to the MS-9600 Manual programming section for general programming information. To program the MS-9600 FACP for use with the DACT-UD:
1. Press the Enter or Mode key to display the Read Status/Programming screen
2. Press 2 to access Programming
3. Enter the Master level password
4. Press the down arrow key twice to view the screen with the Option Modules choice
OPTION MODULES 1=ANNUNCIATORS/UDACT 2=ON BOARD DACT 3=PRINTER/PC
Option Module Screen
5. Press 3 for Option Modules to access the Option Modules screen as shown to the left
6. Program the FACP for use with the DACT-UD using the following procedure
3.1.1 On-Board DACT
The DACT-UD (Digital Alarm Communicator/Transmitter) is an optional module which installs directly on the FACP main circuit board for communication to a central station. Pressing 2 while viewing the Option Module Screen will cause the following screens to be displayed:
ON BOARD DACT 1=ENABLED YES 2=PRIMARY PHONE 3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=MANUAL DIAL MODE
On Board DACT Screen #2
3.1.1.1 DACT-UD Enable
To enable the on-board DACT module, press 1 while viewing On Board DACT Screen #1 until the display reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press of the key.
DACT-UD PN 51899:B1 1/25/05 17
Programming for DACT-UD Programming the MS-9600 Fire Alarm Control Panel
3.1.1.2 Primary Phone
Press 2 while viewing On Board DACT Screen #1 to program the type of primary phone line being connected to the DACT. The following screen will be displayed:
ON BOARD DACT PRIMARY PHONE LINE 1=TYPE TOUCHTONE
Primary Phone Line Screen
To select the type, press 1 while viewing the Primary Phone Line screen. The following screen will be displayed:
PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 62/38
ON BOARD DACT 1=ENABLED 2=PRIMARY PHONE 3=SECONDARY PHONE
On Board DACT Screen #1
Primary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
3.1.1.3 Secondary Phone
Press 3 while viewing On Board DACT Screen #1 to program the type of secondary phone line being connected to the DACT. The following screen will be displayed:
ON BOARD DACT SECONDARY PHONE LINE 1=TYPE TOUCHTONE
Secondary Phone Line Screen
To select the type, press 1 while viewing the Secondary Phone Line screen. The following screen will be displayed:
PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 62/38
Secondary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
18 DACT-UD PN 51899:B1 1/25/05
Loading...
+ 42 hidden pages