While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before reaching
the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system,
crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local
manufacturer's representative. Maintenance should be
scheduled monthly or as required by National and/or local
fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of
all inspections should be kept.
PrecauLarge.PMD 01/10/2005
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F
RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the
useful life of the system's standby batteries and the electronic components may be adversely affected by extreme
temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in
an environment with a nominal room temperature of 15-27°
C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of 93 ±2%
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is completely immune from lightning transients and interferences,
proper grounding will reduce susceptibility. Overhead or out-
side aerial wiring is not recommended, due to an increased
susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can ra-
diate radio frequency energy and if not installed and used
in accordance with the instruction manual, may cause interference to radio communications. It has been tested
and found to comply with the limits for class A computing
device pursuant to Subpart B of Part 15 of FCC Rules,
which is designed to provide reasonable protection against
such interference when operated in a commercial environment. Operation of this equipment in a residential area is
likely to cause interference, in which case the user will be
required to correct the interference at his own expense.
PrecauLarge.PMD 01/10/2005
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
1.4: Digital Communicator.................................................................................................................................9
1.5: Telephone Requirements and Warnings ......................................................................................................10
2.1: Installation in MS-9600 FACP....................................................................................................................13
3.3: Downloading Initiated at a Service Terminal..............................................................................................39
3.4: Uploading Initiated at a Service Terminal...................................................................................................39
3.5: Simultaneous Data Transfers.......................................................................................................................40
SECTION 4: Central Station Communications ..................................................................................................41
APPENDIX C: Central Station Points ................................................................................................................52
DACT-UD P/N: 51889:B1 1/25/05 5
Notes
6DACT-UD PN 51899:B1 1/25/05
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
• Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected
Premises Unit
• Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm
Systems
• Proprietary Fire Alarm Systems (Protected Premises Unit)
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
The DACT-UD Digital Alarm Communicator/Transmitter transmits system status to
UL listed Central Station Receivers via the public switched telephone network. The
communicator mounts to the FACP main circuit board inside the panel cabinet and is
capable of reporting 636 points or 99 zones.
1.1 Product Features
•Dual telephone lines
•Dual telephone line voltage detect
•Mounts inside the control panel
•Extensive transient protection
•Individual LEDs for
Kissoff - green LED
Primary Phone Line Active - red LED
Secondary Phone Line Active - red LED
•Communicates vital system status including:
Independent zone/point alarm
Independent zone/point trouble
Independent zone/point supervisory
AC power loss
Low battery
Earth fault
System off normal
12 or 24 hour test signal
Abnormal test signal per UL requirements
Annunciation at control panel of DACT troubles including loss of phone lines,
communication failure with either Central Station, total communication failure
1.2 Compatible Panel
The DACT-UD has been designed to be compatible with the following control panel:
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are
labeled PH1 and PH2 for the Primary and Secondary phone lines. Telephone line
Primary Active and Secondary Active red LEDs are provided as well as a green Kissoff
LED> The digital communicator provides the following functions:
•Line Seizure - takes control of phone lines disconnecting any premises phones
•Off/On Hook - performs on and off-hook status to the phone lines
•Listen for dial tone - 440 hertz tone typical in most networks
•Dialing Central Station(s) number - default is Touch-Tone®, programmable to
rotary
•For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and
‘Kissoff’ tone(s) - the frequency and time duration of the tone(s) varies with the
transmission format. The control panel will adjust accordingly
•Communicate in the following formats:
12 Tone Burst Types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
3 Touchtone Types:
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
DACT-UD PN 51899:B1 1/25/059
Product DescriptionTelephone Requirements and Warnings
1.5 Telephone Requirements and Warnings
1.5.1 Telephone Circuitry - PH1 & PH2
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to
the telephone line. Excessive RENs on the telephone line may result in the devices
not ringing in response to an incoming call. In most, but not all areas, the sum of
the RENs should not exceed five (5.0). To be certain of the number of devices that
may be connected to the line, as determined by the total RENs, contact the
telephone company to determine the maximum REN for the calling area.
1.5.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the
installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer:Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Product Model Number: DACT-UD
FCC Registration Number: US:1W6AL00BDACTUD
Ringer Equivalence: 0.0B
Note: This equipment complies with Part 68 of the FCC rules and the
requirements adopted by the ACTA. On the DACT-UD module IC is a
label that contains, among other information, a product identifier in the
format US:AAAEQ##TXXXX. If requested, this number must be
provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an
emergency situation. It must be able to do this even if other equipment (telephone,
answering system, computer modem, etc.) already has the telephone line in use. To do
so, alarm dialing equipment must be connected to a properly installed RJ31X jack that
is electrically in series with and ahead of all other equipment attached to the same
telephone line. If there are any questions concerning these instructions, consult the
telephone company or a qualified installer about installing the RJ31X jack and alarm
dialing equipment. Refer to Figure 2.6 on page 16 for an illustration of the proper
installation of this equipment.
10DACT-UD PN 51899:B1 1/25/05
Telephone Requirements and WarningsProduct Description
1.5.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue
services and/or make changes in its facilities, services, equipment or procedures which
may affect the operation of this control panel. However, the telephone company is
required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company
reserves the right to temporarili discontinue service. Advance notification will be
provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any
problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR
PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the
same telephone line.
The control panel must be connected to the public switched telephone network
upstream (as first device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements adopted
by ACTA. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular
jack that is also compliant.
DACT-UD PN 51899:B1 1/25/0511
Notes
This Page Left Intentionally Blank
12DACT-UD PN 51899:B1 1/25/05
Installation in MS-9600 FACPDACT-UD Installation
A
SECTION 2DACT-UD Installation
2.1 Installation in MS-9600 FACP
WARNING! Disconnect all sources of power (AC and DC) before installing or
removing any modules or wiring.
2.1.1 MS-9600 Keypad/Display Removal
DACT-UD (Digital Alarm Communicator/Transmitter) Module installation requires the
removal of the MS-9600 Keypad/Display unit from the main circuit board. To remove
the Keypad/Display, insert a Phillips screwdriver into each of the three holes located in
the flexible covering of the Keypad/Display and loosen the three mounting screws.
Note that it is not necessary to disconnect the cables between the Keypad/Display and
the main circuit board. Carefully lift the Keypad/Display and rest the unit at the bottom
of the main circuit board.
Mounting Screw Access Hole
TB3
JP3
REMOVE
TO DISABLE
LOCAL
CHARGER
JP10
JP2
2
1
DISABLE
GND
FLT
4
5
GHIJKL
J17
J16
78 9
PRS
0
*
QZ
RECALL
HOT
CB1
4XTM OPT BD
ABCDEF
CUT TOMONITOR 4XTM
TUVWXY
LCD DISPLAY
NEUT E ARTH
TB4 TB5
JP6
AC POWER
FIRE ALARM
SUPERVISORY
st
3
1
JP8
EVENT
JP7
CLR
6
MNO
JP6
ESC
MODE
#
TB1
-/.
+BATTERY-
TB2
ENTER
J6
KEYPAD I/F
TROUBLE
J2
OPT DACT
J8
CK/STEP
ALARM
SILENCE
JP5
MAINTENANCE
ALARM
SILENCED
DISABLED
BATTERY
GROUND
DRILL
HOLD 2 SEC
RESET
Mounting Screw Access Holes
Figure 2.1 Keypad/Display Removal
TB6TB7
JP4
123
J7
TB8
OPT SLC
J3
DACT-UD PN 51899:B1 1/25/0513
DACT-UD InstallationInstallation in MS-9600 FACP
2.1.2 DACT-UD Installation
WARNING! Disconnect all sources of power (AC and DC) before installing or
removing any modules or wiring.
The DACT-UD module plugs into connector J2 on the MS-9600 main circuit board.
Primary Active LED
Kissoff LED
PH1
Primary
Phone Line
PH2
Secondary
Phone Line
Secondary Active LED
9600DACT.CDR
J1 Connector (located on back
of module) plugs into J2 on
MS-9600 main circuit board
Figure 2.2 DACT-UD Module
The following steps must be followed when installing the DACT module:
1. Remove all power (AC and DC) from the FACP before proceeding with the
installation
2. Remove the Keypad/Display from the main circuit board as described in the
beginning of this section
14DACT-UD PN 51899:B1 1/25/05
Installation in MS-9600 FACPDACT-UD Installation
3. Insert the supplied plastic snap-in standoff into mounting hole located at the
bottom center of the DACT-UD module (insert into back of board)
4. Carefully plug connector J1 on the back of the DACT-UD module into connector
J2 on the MS-9600 main circuit board, being careful not to bend any pins and at
the same time, insert plastic snap-in standoff into mounting hole in main board
5. Align the mounting holes in the DACT module with the premounted standoffs on
the FACP main circuit board
Standoff
Standoff
Standoff
J2
Standoff (snap-in)
J1
J1 Connector located on
back of DACT module
Figure 2.3 DACT J1 Connector to FACP J2 Connector
6. Secure the module to the standoffs on the main circuit board with the three
screws supplied with the DACT-UD. It is important that the supplied screws be
used to secure the module to the metal standoff in order to help protect against
electrical transients.
Mounting Screw
Mounting Screws
96dact2.CDR
Snap-in Standoff
96dact3.CDR
Figure 2.4 DACT Installation on Standoffs
7. Reinstall the Keypad/Display on the main circuit board by positioning the unit
over the appropriate standoffs and securing with the screws which were loosened
in step 2
8. Make certain to program the control panel for DACT operation
DACT-UD PN 51899:B1 1/25/0515
DACT-UD InstallationInstallation in MS-9600 FACP
9. Refer to "Digital Communicator" on page 10, before proceeding with this step.
Connect the premises primary and secondary phone lines to the DACT as
illustrated in Figure 2.5 and test the system for correct operation
Primary Lines
Incoming Telco Phone Lines
Tip
Ring
Primary Phone Line PH-1
Green Wire
Red Wire
1 2 3 4 5 6 7 8
RJ3 1-X
Jack
PH1
Ring
Red Wire
Ring
Tip
To premise phones
Tip
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
7 foot cable
(MCBL-7)
order separately
Male Plug
Connectors
Female
Connectors
J3
J2
CAUTION: It is critical that the DACT-UD
be located as the first device on the incoming
telephone circuit to properly function
PH2
Green Wire
1 2 3 4 5 6 7 8
RJ31 -X
Jack
Secondary Lines
Incoming Telco Phone Lines
Ring
To premise phones
Tip
Secondary Phone Line PH-1
DACT-UD
Figure 2.5 Wiring Phone Jacks
It is critical that the DACT be located as the first device on the incoming telephone circuit to properly function.
Customer Premises Equipment and Wiring
M
S
2
9
0
0
U
Network
Service
Provider’s
Facilities
RJ31X
Jack
D
Computer
Unused
RJ-11 Jack
MS-9600 with DACT-UD
Telephone
Line
Telephone
Network
Demarcation
Fax Machine
Unused
RJ-11 Jack
Point
Telephone
Answering
System
Telephone
Figure 2.6 DACT Installation
16DACT-UD PN 51899:B1 1/25/05
Programming the MS-9600 Fire Alarm Control PanelProgramming for DACT-UD
SECTION 3Programming for DACT-UD
3.1 Programming the MS-9600 Fire Alarm Control Panel
Refer to the MS-9600 Manual programming section for general programming
information. To program the MS-9600 FACP for use with the DACT-UD:
1. Press the Enter or Mode key to display the Read Status/Programming screen
2. Press 2 to access Programming
3. Enter the Master level password
4. Press the down arrow key twice to view the screen with the Option Modules
choice
5. Press 3 for Option Modules to access the Option Modules screen as shown to the
left
6. Program the FACP for use with the DACT-UD using the following procedure
3.1.1 On-Board DACT
The DACT-UD (Digital Alarm Communicator/Transmitter) is an optional module
which installs directly on the FACP main circuit board for communication to a
central station. Pressing 2 while viewing the Option Module Screen will cause the
following screens to be displayed:
ON BOARD DACT
1=ENABLED YES
2=PRIMARY PHONE
3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=MANUAL DIAL MODE
On Board DACT Screen #2
3.1.1.1 DACT-UD Enable
To enable the on-board DACT module, press 1 while viewing On Board DACT
Screen #1 until the display reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press of the key.
DACT-UD PN 51899:B1 1/25/0517
Programming for DACT-UDProgramming the MS-9600 Fire Alarm Control Panel
3.1.1.2 Primary Phone
Press 2 while viewing On Board DACT Screen #1 to program the type of primary
phone line being connected to the DACT. The following screen will be displayed:
ON BOARD DACT
PRIMARY PHONE LINE
1=TYPE TOUCHTONE
Primary Phone Line Screen
To select the type, press 1 while viewing the Primary Phone Line screen. The
following screen will be displayed:
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 62/38
ON BOARD DACT
1=ENABLED
2=PRIMARY PHONE
3=SECONDARY PHONE
On Board DACT Screen #1
Primary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break
ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
3.1.1.3 Secondary Phone
Press 3 while viewing On Board DACT Screen #1 to program the type of secondary
phone line being connected to the DACT. The following screen will be displayed:
ON BOARD DACT
SECONDARY PHONE LINE
1=TYPE TOUCHTONE
Secondary Phone Line Screen
To select the type, press 1 while viewing the Secondary Phone Line screen. The
following screen will be displayed:
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 62/38
Secondary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break
ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
18DACT-UD PN 51899:B1 1/25/05
Programming the MS-9600 Fire Alarm Control PanelProgramming for DACT-UD
3.1.1.4 Service Terminal
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=MANUAL DIAL MODE
On Board DACT Screen #2
The MS-9600 can be programmed remotely from a PC using a modem and
telephone line. Information can also be retrieved from the FACP using the same
method. The Upload/Download option allows an operator to set the necessary
parameters to allow the uploading and downloading of data between the FACP and
PC. The Service Terminal selection provides the means for entering these
parameters.
Pressing 1 while viewing On Board DACT Screen #2 will cause the following
screens to appear:
SERVICE TERMINAL
1=PANEL ID
2=TERMINAL 1
3=TERMINAL 2
Service Terminal Screen #1
SERVICE TERMINAL
1=RING COUNT 3
Service Terminal Screen #2
3.1.1.4.1 Panel ID
The Panel Identification Number is a 4-digit code (valid digits being 0 - 9 and A - F)
that is used to identify the installed FACP. It is important to program this code into
the FACP the first time that downloading is performed so that the called Service
Terminal can identify the control panel. The factory default is 0000.
To program the Panel ID, press 1 while viewing Service Terminal Screen #1. The
following screen will be displayed:
PANEL ID
4 CHARACTER 0-F
Panel ID Screen
A flashing cursor will appear in the lower left corner of the display. Enter a 4-digit
code using the digits 0 - 9 and/or the letters A - F by entering the first character.
Press the right arrow key to move the cursor to the second position and enter the
second character. Follow the same procedure to enter the remaining characters.
After entering the fourth character, press the right arrow key and then press the
Enter key to store the Panel ID number.
DACT-UD PN 51899:B1 1/25/0519
Programming for DACT-UDProgramming the MS-9600 Fire Alarm Control Panel
3.1.1.4.2 Terminal 1 and Terminal 2
Service Terminal #1 is generally designated as the FACP primary phone line used
for receiving phone calls from the service terminal (PC) being used for remote
programming. Service Terminal 2 is referred to as the secondary phone line.
Pressing 2 for Terminal 1 or 3 for Terminal 2 while viewing Service Terminal
Screen #1 will display the following screen:
SERVICE TERMINAL #
1=PHONE NUMBER
Service Terminal # Screen
Phone Number (Service Terminal)
The Service Terminal Phone Number will be used by the control panel to contact
the service terminal. Pressing 1 while viewing the Service Terminal # Screen will
cause the following screen to be displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
Printer-PC Screen
A flashing cursor will appear in the lower left corner. Enter the phone number for
the service terminal by keying in the first digit, pressing the left arrow key and
entering the second digit. Continue this process until all desired numbers have been
entered (maximum of 20 characters). Press the Enter key to store the phone number
in memory and return the display to the Service Terminal # Screen.
Valid entries are 0 - 9 and A - F with the numeric digits as dialed numbers and
letters representing the following functions:
•A = * on a Touchtone phone keypad
•B = # on a Touchtone phone keypad
•C = look for secondary dial tone for up to two seconds (then dial anyway)
•D = three second pause
•E = five second pause
•F = end of phone number (F is automatically entered for unused entry positions)
20DACT-UD PN 51899:B1 1/25/05
Programming the MS-9600 Fire Alarm Control PanelProgramming for DACT-UD
3.1.1.4.3 Ring Count
The ring count designates the number of rings allowed on the phone line prior to
answering an incoming call from a service terminal. The factory default is 3 which
means the control panel will not answer an incoming call until 3 rings are detected.
This entry may be programmed for 1 to 25 rings. A setting of 00 prevents the panel
from answering incoming calls.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2.
The following screen will be displayed:
RING COUNT
0-25 RANGE
Ring Count Screen
A flashing cursor will appear in the lower left corner of the display. Enter the twodigit ring count which can be a value between 00 and 25. After the second digit is
entered, the display will return to the Service Terminal screen.
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=MANUAL DIAL MODE
On Board DACT Screen #2
3.1.1.5 Central Station
Central Station programming configures the control panel DACT for contacting the
central station. Pressing 2 while viewing On Board DACT Screen #2 will cause the
following screens to be displayed:
CENTRAL STATION
1=REPORTING DISABLED
2=REPORT BACKUP
3=CALL LIMIT
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
3.1.1.5.1 Reporting Enable
To enable the DACT for reporting FACP activity to the central station, press 1 while
viewing Central Station Screen #1 so the display reads Reporting Enabled. Each
press of the 1 key will toggle the display between Reporting Disabled and
Reporting Enabled.
DACT-UD PN 51899:B1 1/25/0521
Programming for DACT-UDProgramming the MS-9600 Fire Alarm Control Panel
3.1.1.5.2 Backup Reporting
The DACT can be programmed to transmit reports to primary and/or secondary
central station phone numbers as a backup. Press 2 while viewing Central Station
Screen #1 to display the following screen:
BACKUP REPORTING
1=BACKUP ONLY
2=BOTH
3=FIRST AVAILABLE
Backup Reporting Screen
Press 1 to have all reports transmitted to the central station secondary phone number
as a backup only if the primary phone line fails, 2 to transmit all reports to both the
primary and secondary phone numbers all of the time or 3 to send reports to the first
available phone number.
The Call Limit option limits the number of DACT trouble calls to the Central
Station, to a programmed amount between 0 and 99, for each unique trouble within
a 24 hour period. Separate limit counters keep track of each unique type of trouble.
Note that the number of phone line (communication) faults called to the Central
Station are not limited by this feature. No subsequent restoral message is sent to the
Central Station(s) for a particular trouble whose call limit has been reached. Local
DACT annunciation will still track the particular trouble and restoral.
To set the Trouble Call Limit, press 3 while viewing Central Station Screen #1. The
following screen will be displayed.
TROUBLE CALL LIMIT
00-99 RANGE
*
Backup Reporting Screen
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
22DACT-UD PN 51899:B1 1/25/05
Programming the MS-9600 Fire Alarm Control PanelProgramming for DACT-UD
3.1.1.5.4 Central Station Primary and Secondary Phone Numbers
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
Pressing 1 for Primary or 2 for Secondary will cause the following screens to be
displayed.
CENTRAL STATION
1=TEST TIME INT 24
2=ACCOUNT CODE 0000
3=24HR TST TIME 0021
Primary/Secondary Screen #1
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
CENTRAL STATION
1=COMM FORMAT
ADEMCO-CONTACT-ID
Primary/Secondary Screen #3
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
DACT-UD PN 51899:B1 1/25/0523
Programming for DACT-UDProgramming the MS-9600 Fire Alarm Control Panel
Test Time Interval
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following
screens to be displayed:
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
The test report sent to the Central Station phone number may be sent once every 6,
8, 12 or 24 hours. Select the desired Test Time Interval by pressing the
corresponding digit in the screens shown above.
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following
screen to be displayed:
ACCOUNT CODE
4 CHAR RANGE 0-F
Account Codes Screen
The Account Code, which is assigned by a Central Station, depends on the
communication format being used. The Account Code screen will have a flashing
cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F
keys.
Note: If the Account Code being entered is a three digit number, enter the three
digits first and then add a 0 (zero) as the fourth digit.
24DACT-UD PN 51899:B1 1/25/05
Programming the MS-9600 Fire Alarm Control PanelProgramming for DACT-UD
24 Hour Test Time
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following
screen to be displayed:
24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen
Use the 24 Hour Test Time screen to program the time that the DACT-UD will
transmit the 24 Hour Test to the Central Station. A flashing cursor will appear in the
lower left corner of the screen. Enter a four digit number representing the test time
using military time (0000 = midnight and 2359 = 11:59PM).
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following
screen to be displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen
The Phone Number screen is used to enter the Central Station phone number that
the DACT-UD will be contacting. A maximum of 20 characters can be entered with
valid entries being 0 - 9 and A - F where A = *, B = #, C = look for secondary dial
tone for up to 2 seconds (then dial anyway), D = 3 second pause, E = 5 second pause
and F = end of phone number (must be entered at end of phone number).
A flashing cursor will appear in the lower left corner of the screen. Enter the first
digit then press the right arrow key to move the cursor to the right one position.
Enter the second digit and repeat the process until all digits are entered. Press the
Enter key to store the phone number in memory.
Enter the digits as you would like the number to be dialed. For example, if it’s
necessary to dial 9 before dialing a number outside the building, you may wish to
pause after dialing 9. Enter 9 followed by D for a three second pause or E for a five
second pause then the phone number followed by an F to indicate the end of the
number.
DACT-UD PN 51899:B1 1/25/0525
Programming for DACT-UDProgramming the MS-9600 Fire Alarm Control Panel
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following
COMM FORMAT
1=3P1E C18 A23
2=3P1S C19 A14
3=3P1E C19 A14
Comm Format Screen #2
COMM FORMAT
1=4P1S C18 A23
2=4P1E C18 A23
3=4P1S C19 A14
Comm Format Screen #3
COMM FORMAT
1=4P1E C19 A14
2=4P2S C18 A23
3=4P2E C18 A23
Comm Format Screen #4
COMM FORMAT
1=4P2S C19 A14
2=4P2E C19 A14
3=ADEMCO CONTACT ID
Comm Format Screen #5
26DACT-UD PN 51899:B1 1/25/05
Programming the MS-9600 Fire Alarm Control PanelProgramming for DACT-UD
The Communication Format is determined by the type of receiver that the
DACT-UD is transmitting to. Consult your Central Station for proper selection or
consult our factory representatives. For any format chosen, the control panel
automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while
viewing the appropriate Comm Format screen. The following table describes each
format:
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following
screen to be displayed:
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Event Code Screen
Pressing the down arrow key allows viewing of all Events associated with the
selected Communication Format. Pressing the number corresponding to the event
displayed in each screen will display its default event code which can be customized
by the programmer. For example, pressing 1 for Pull Station will display a screen
similar to the following which allows the Event Code to be changed from the
default value.
PULL STATION
ALARM 000
Event Code Screen
The tables on the following pages list all of the Events and their default Event
Codes for the various Communication Formats.
DACT-UD PN 51899:B1 1/25/0527
Programming for DACT-UDProgramming the MS-9600 Fire Alarm Control Panel
3+1, 4+1 Express and 4+1 Standard
The information shown in Table 3.2 is automatically programmed for the Central
Station phone number Event Codes when any of these Formats are selected. Enter 0
for an Event Code Setting to disable the report.
The information shown in Table 3.3 is automatically programmed for the Central
Station phone number Event Codes when any of these Formats are selected. Enter
00 for an Event Code Setting to disable the report.
Programming for DACT-UDProgramming the MS-9600 Fire Alarm Control Panel
Ademco Contact ID Format
The information shown in Table 3.4 is automatically programmed for the Central
Station phone number Event Codes when Ademco Contact ID Format is selected.
Enter 000 for an Event Code Setting to disable the report.
Programming for DACT-UDProgramming the MS-9600 Fire Alarm Control Panel
Report Style
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
Pressing 3 while viewing Central Station Screen #2 will cause the Report Style
display to toggle between Point and Zone. Setting the Report Style to Point will
program the DACT to report individual point status to the Central Station. The
control panel is capable of monitoring a total of 636 addressable devices. Setting
the Report Style to Zone will program the DACT to report zone status to the Central
Station. The control panel is capable of monitoring a total of 99 individual zones.
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE POINT
Central Station Screen #2
Notes on Central Station Reporting:
1. SLC Loop 1, Detector Address 01 will be reported to the Central Station as
Point 01, Detector Address 02 as Point 02, with reports continuing in a similar
fashion all the way up to Detector Address 159 which will be reported as Point
159.
2. SLC Loop 1, Module Address 01 will be reported to the Central Station as
Point 160, Module Address 02 will be reported to the Central Station as Point
161, with reports continuing in a similar fashion all the way up to Module
Address 159 which will be reported as Point 318.
3. SLC Loop 2, Detector Address 01 will be reported to the Central Station as
Point 319, Detector Address 02 as Point 320, with reports continuing in a
similar fashion all the way up to Detector Address 159 which will be reported
as Point 477.
4. SLC Loop 2, Module Address 01 will be reported to the Central Station as
Point 478, Module Address 02 as Point 479, with reports continuing in a
similar fashion all the way up to Module Address 159 which will be reported as
Point 636.
34DACT-UD PN 51899:B1 1/25/05
Programming the MS-9600 Fire Alarm Control PanelProgramming for DACT-UD
3.1.1.6 Manual Dial Mode
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=MANUAL DIAL MODE
On Board DACT Screen #2
Pressing 3 while viewing On Board DACT Screen #2 will cause the following
screen to be displayed:
Pressing 1 for Primary Phone or 2 for Secondary Phone will display the following:
MANUAL DIAL MODE
1=GO OFF HOOK
2=DIAL DIGIT(S)
3=GO ON HOOK
Pressing 1 for Go Off Hook will cause the DACT to access the selected phone line
(similar to taking the phone handset off the cradle). The selected phone line’s red
Active LED will turn on.
Pressing 2 for Dial Digit(s) will display a screen which allows the user to key in the
phone number to be dialed. The first digit is keyed in and then the right arrow key
is pressed to move the cursor to the next position. The next digit is keyed in and the
process is repeated until all digits have been entered. Pressing the Enter key will
cause the number just entered to be dialed.
Pressing 3 for Go On Hook will cause the DACT to hang-up, deselecting the
previously selected phone line. The phone line’s red Active LED will turn off.
DACT-UD PN 51899:B1 1/25/0535
Programming for DACT-UDRemote Site Upload/Download
3.2 Remote Site Upload/Download
The control panel may be programmed or interrogated off-site via the public switched
telephone network. Any personal computer with Windows 95, a 1200 baud Hayes
compatible modem and Fire•Lite Upload/Download software P/N PK-CD may serve as
a Service Terminal. The Upload/Download software allows the following:
Download of the entire program
Download of an individual program item
Upload of the entire program
Upload of an individual program item
Upload of the entire program plus history file, walktest data, current status,
system voltages and time & date
Real-time upload, either continuous or ‘snapshot’ (one time) of current status
or system voltages
Execution of control panel functions such as Trouble Silence, Manual
Evacuate, Manual Evacuate Restore, Zone/NAC Disable, Zone/NAC Enable
and Set Time & Date
WA R NI N G : Changes to program entries occur as a result of the downloading process.
After successful downloading, make certain to perform the following steps:
1. Print out all programmed data via print mode or manually view programmed
entries and compare to intended program data
2. Test all affected panel operations
3. Immediately correct any problems found
3.2.1 Downloading Program: General
Any time that the control panel is downloaded, whether initiated at the jobsite or
remotely, a secret code (Factory Default 0000) is verified between the control panel and
the Service Terminal. Changing the Secret Code may only be accomplished at the
Service Terminal and subsequently loaded into the control panel. Future upload or
download requests cause verification of the secret code by the control panel before
processing of data is allowed. If the secret code is not verified, the control panel will
terminate the request immediately.
While the control panel is communicating with the Service Terminal, the DACT-UD’s
green Modem LED and one of the red Line Seize LEDs will remain on steady. At the
conclusion of a successful download transaction, the green Kissoff LED will come on
steady for one second. Upon termination of communication, the green Modem LED
will turn off and the red Line Seize LED will turn off.
In order to download the panel (whether initiated at the jobsite or remotely) the
following must be true:
The control panel may be in any mode of operation, including Disable, Enable
and Drill. Downloading is not possible if the communicator is active during
Central Station communications or while testing the phone lines while in
Troubleshoot mode
There cannot be any active communications ongoing with a Central Station
receiver
All active events must be successfully ‘Kissed-off’ by the Central Station(s)
The communicator must be in a standby state with no new information waiting
to be transmitted to a Central Station
36DACT-UD PN 51899:B1 1/25/05
Remote Site Upload/DownloadProgramming for DACT-UD
Two basic communication mechanisms are supported as follows:
•Download with Callback - the Service Terminal calls the control panel. The
control panel answers the call, confirms the calling party then hangs-up. The
Service Terminal then waits for a callback from the control panel. After the
control panel calls the Central Station and successfully reports that a request for
downloading has been received, the control panel calls the Service Terminal
back. Upon secret code verification, data transfers occur. When the data
transfers are completed and the Service Terminal disconnects from the control
panel, the panel calls the Central Station back to confirm either successful or
unsuccessful results
•Download with Callback Disabled - the Service Terminal calls the control panel.
No hang-up sequence occurs. Data transfers proceed.
Note: Callback enable/disable is controlled by the master user at the Service Terminal
on a per call basis.
Anytime a download with callback is initiated, the control panel will first contact the
primary Central Station or both the primary and secondary Central Stations or the first
available Central Station phone number (depending on which option has been
programmed into the control panel) to report a request for upload/download message.
Once the request is ‘Kissed-off’ by the Central Station(s), the control panel will then
call the appropriate Service Terminal and begin the downloading process.
Anytime a download without callback is initiated, the control panel and the Service
Terminal will communicate and transfer data without first contacting a Central Station.
When the data transfers are completed and the control panel disconnects from the
Service Terminal, the panel will call the Central Station and report the following:
•Upload/download request received
•Upload and/or download successful or
•Upload/download failed
To prevent the request for up/download message(s) from being reported to the Central
Stations(s), disable all upload/download reports back to both Central Stations.
During the downloading process, the fire protection remains active
trouble or alarm condition occur, the control panel immediately terminates
downloading and processes the trouble or alarm locally and transmits the information
to the Central Station(s).
. Should a system
3.2.2 Security Features
Remote site upload and download with the control panel has been carefully designed to
include key security features to ensure proper functionality. The key features are listed
and explained below.
Secret Code Verification
A secret code is stored in the control panel by a Service Terminal to prevent
unauthorized access. The secret code is created at the Service Terminal in Password
level 1 and cannot be viewed or changed by anyone other than a user with access to
level 1. Viewing of the secret code is prohibited at the control panel. Prior to allowing
an upload or download of data, the control panel will verify the secret code transmitted
by the Service Terminal.
Time-out at Control Panel
Upon answering an incoming call on either the primary or secondary Central Station
phone line, the panel will listen for a modem connection signal. If this signal is not
received within 30 seconds, the panel will disconnect the call.
Upon successful connection (secret code verified and callback complete, if applicable),
if no communication occurs within five minutes, the panel will disconnect the call.
DACT-UD PN 51899:B1 1/25/0537
Programming for DACT-UDRemote Site Upload/Download
Callback to Service Terminal
Anytime that the panel is remotely requested to allow an upload or download with
callback, it will confirm the source of the incoming call, hang-up and call back the
calling party (Service Terminal phone number).
Panel Identification Number
The panel identification number will be used to automatically identify the panel to the
Service Terminal (when the panel calls the Service Terminal).
Calls initiated at the panel must be coordinated a the Service Terminal manually. Note
that the Service Terminal will not pickup the incoming call unless operating on the
communications screen. The Service Terminal will not recognize a control panel
initiated call unless the secret code is at the factory default settings.
Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If an
error is detected, the block is retransmitted until correct, up to a maximum of four
times. If the Secret Code is not verified and four errors occur, the call is disconnected
and the report that the upload/download was not successful is called to the Central
Station(s).
Central Station Acknowledge
There is an option whereby the control panel will report to one or both Central Stations
that a request for uploading or downloading has been received prior to processing the
call. This is called the callback option. If the Central Station(s) does not acknowledge
receipt of this request, uploading or downloading is prohibited. If acknowledged by the
Central Station(s), another message is transmitted informing the Central Station(s) that:
(1) downloading was successful, (2) uploading was successful or (3) uploading/
downloading was not successful.
Data Protection/Integrity
Options allow programming of single data entries or the entire program. Use caution
when selecting programming choices and verify all entries via an upload or manual
check at the control panel. Data blocks containing user programming options are
protected from partial programming due to faulty phone connections, line noise and
other errors.
38DACT-UD PN 51899:B1 1/25/05
Downloading Initiated at a Service TerminalProgramming for DACT-UD
3.3 Downloading Initiated at a Service Terminal
Before initiating the Download procedure, make certain that the control panel is in the
standby state with the red Line Seize LED, green Modem and Kissoff LEDs off.
Once an incoming call is accepted/answered by the control panel, the panel will:
1. Establish basic modem connection
2. Verify secret code
3. Verify callback vs. no callback request from the Service Terminal. If callback is
requested then perform steps 4 through 10. If no callback is requested then
perform steps 9 and 10 only
4. Identify the Service Terminal location
5. Hang-up/disconnect call
6. Call the Central Station(s) and transmit a request for upload/download message
(if programmed to do so). If this message is accepted, the control panel will
proceed to the next step
7. Return call to Service Terminal
8. Verify secret code
9. Begin downloading
10. Upon completion of download, call Central Station(s) back and report a
successful download or failed upload/download status (if programmed to do so)
3.4 Uploading Initiated at a Service Terminal
Items that may be uploaded from the control panel to a Service Terminal are:
•All or portions of programmed data plus the real time clock, time and date
•Entire Walktest data file in real-time continuous or as a ‘snapshot’
•Troubleshoot system voltages in real-time continuous or as a ‘snapshot’
•Entire event History file
•Current system status in real-time continuous or a a ‘snapshot’
Uploading is possible at any time provided the following conditions are true:
The control panel may be in any mode of operation. Uploading is not possible
if the communicator is active or while testing the phone lines while in
troubleshoot mode
There cannot be any active communications ongoing with a Central Station
receiver
All active events must be successfully ‘Kissed-off’ by the Central Station(s).
The communicator must be in a standby state with no new information waiting
to be transmitted to a Central Station
DACT-UD PN 51899:B1 1/25/0539
Programming for DACT-UDSimultaneous Data Transfers
Once an incoming call is accepted/answered by the control panel, the panel will
1. Establish basic modem connection
2. Verify secret code
3. Verify callback vs. no callback request from the Service Terminal. If callback is
requested then perform steps 4 through 10. If no callback is requested then
perform steps 9 and 10 only
4. Identify the Service Terminal location
5. Hang-up/disconnect call
6. Call the Central Station(s) and transmit a request for upload/download message
(if programmed to do so). If this message is accepted, the control panel will
proceed to the next step
7. Return call to Service Terminal
8. Verify secret code
9. Begin uploading
10. Upon completion of upload, call Central Station(s) back and report a successful
upload or failed upload/download status (if programmed to do so)
During the uploading process, the fire protection remains active. Should a system
trouble or alarm condition occur, the control panel immediately terminates uploading
and processes the trouble or alarm locally and transmits the information to the Central
Station(s).
3.5 Simultaneous Data Transfers
Uploading and downloading may take place on a single telephone call. Control and
selection of the data transaction is coordinated at the Service Terminal. This eliminates
multiple phone calls, allows instant verification of downloaded data files and simplifies
the overall process.
40DACT-UD PN 51899:B1 1/25/05
Simultaneous Data TransfersCentral Station Communications
SECTION 4Central Station Communications
The DACT-UD transmits zone and system status reports to Central Stations via the public switched telephone network. Two supervised telephone line connections are made
to interface the DACT to the telephone lines. Two optional 7 foot telephone cords are
available for this purpose and can be purchased separately.
The control panel supervises both telephone lines for proper voltage. A delay of two
minutes will occur before a fault in either phone line connection is reported as a trouble.
When a fault is detected, an audible trouble signal will sound, the yellow trouble LED
will blink, the display will show a DACT communication trouble and the trouble
condition will be reported to the Central Station over the remaining operational phone
line.
The DACT-UD comes with line seizure capability provided for both the primary and
secondary telephone line interfaces. Any time that the control panel needs to make a
call to a Central Station, line seizure will disconnect any local premises phones sharing
the same telephone line.
All transmissions to the Central Stations will be sent over the primary phone line. In
the event of noisy phone lines, transmissions will be sent over the backup secondary
phone line.
Two phone numbers must be programmed, the primary Central Station phone number
and the secondary Central Station phone number. All system reports will be transmitted
to the primary Central Station phone number. Reports will automatically be sent to the
secondary Central Station phone number if attempts to transmits to the primary Central
Station phone number are unsuccessful. Note that as an option, all reports may also be
sent to the secondary Central Station phone number.
The DACT-UD installed on the MS-9600 meets NFPA 72 National Fire Code reporting
requirements for: (a) the type of signal, (b) condition and (c) location of the reporting
premises. The general priority reporting structure is:
1. Zone Alarms and Restores
2. Zone Troubles and Restores
3. System Troubles and Restores
4. 24-hour Test
DACT-UD PN 51899:B1 1/25/0541
Central Station CommunicationsSimultaneous Data Transfers
The control panel is capable of reporting detailed messages depending upon the format
in use. Table 4-1 shows the reporting structure for all formats.
TABLE 4-1:Format Selection
Format Format Format Format
Report
AlarmSSS(S) A
Alarm RestoreSSS(S) RA
Zone Trouble
(Zone Open)
Zone Trouble RestoreSSS(S) RTZ
System TroubleSSS(S) TS
System Trouble RestoreSSS(S) RTS
Zone DisableSSS(S) DZ
Zone Disable RestoreSSS(S) RDZ
Low BatterySSS(S) L
Low Battery RestoreSSS(S) RL
AC LossSSS(S) P
AC Loss RestoreSSS(S) RP
Fire DrillSSS(S) FD
Fire Drill RestoreSSS(S) RFD
Supervisory ConditionSSS(S) V
Supervisory Condition
Restore
Test ReportSSS(S) XSSS(S) XSSSS XX2SSSS XX2
Upload or DownloadSSS(S) UDSSS(S) UDSSS UDUD2SSS UDUD2
3+1/4+1/Standard
4+1 Express
SSS(S) TZ
SSS(S) RV
3+1/4+1/Expanded
SSS(S) A
AAA(A) Z
SSS(S) RA
RARARA(RA) Z
SSS(S) TZ
TZTZTZ(TZ) Z
SSS(S) RTZ
RTZ RTZRTZ( RTZ ) Z
SSS(S) TS
TSTSTS(TS) Y
SSS(S) RTS
RTS RTSRTS( RTS) Y
SSS(S) DZ
DZDZDZ(DZ) Z
SSS(S) RDZ
RDZRDZRDZ(RDZ) Z
SSS(S) L
LLL(L) L2
SSS(S) RL
RLRLRL(RL) L2
SSS(S) P
PPP(P) P2
SSS(S) RP
RPRPRP(RP) RP2
SSS(S) FD
FDFDFD(FD) FD2
SSS(S) RFD
RFDRFDRFD(RFD) RFD2
SSS(S) V
VVV(V) Z
SSS(S) RV
RVRVRV ( RV) Z
4+2/Standard
4+2 Express
SSSS AA2SSSS AZ
SSSS RARA2SSSS RAZ
SSSS TZTZ2SSSS TZZ
SSSS RTZRTZ2SSSS RTZZ
SSSS TSTS2SSSS TSY
SSSS RTSRTS2SSSS RTSY
SSSS DZDZ2SSSS DZZ
SSSS RDZRDZ2SSSS RDZZ
SSSS LL2SSSS LL2
SSSS RLRL2SSSS RLRL2
SSSS PP2SSSS PP2
SSSS RPRP2SSSS RPRP2
SSSS FDFD2SSSS FDFD2
SSSS RFDRFD2SSSS RFDRFD2
SSSS VV2SSSS VZ
SSSS RVRV2SSSS RVZ
4+2/Expanded
Refer to Table 4-2 for an explanation of each letter code in Table 4-1 . Refer to Table
4-3 for a list of compatible receivers.
42DACT-UD PN 51899:B1 1/25/05
Simultaneous Data TransfersCentral Station Communications
B =Telco Secondary Line Fault
C =Main Bell Fault, Annunciator Bell
D =Communication Fault to Primary Number
E =Communication Fault to Secondary Number
F =System Off Normal Fault/System Fault (Slave Operation, see Chapter 6)
UD=Upload/download (1st digit)
UD2=Upload/download (2nd digit)
Note: For Expanded Reporting, the control panel automatically adds the digit corresponding to the
zone number and the second digit corresponding to any system trouble condition. Only the first
digit is programmable.
DACT-UD PN 51899:B1 1/25/0543
Central Station CommunicationsTransmittal Priorities
4.1 Transmittal Priorities
The DACT-UD transmits highest priority events first. Events, in terms of priority, are listed below
in descending order:
Zone disabled
Fire drill
AC fail (after delay)
Zonal faults
Earth fault
Low battery/no battery
Telephone line fault
Notification Appliance Circuits fault
Communication trouble
Annunciator trouble
System off normal
4. Restoral Reports
Zone alarm
Supervisory
Zone(s) enabled
Fire drill
AC
Zone fault
Earth
Battery
Telephone line
Notification Appliance Circuits
Communication
Annunciator trouble
System off normal
5. 24 Hour Test (lowest priority)
Red LEDs are provided on the DACT-UD circuit board to identify which telephone line is activated. Also, a green LED labeled 'kissoff' will turn on whenever the DACT-UD has successfully
transmitted reports to the Central Station. The 'kissoff' LED may turn on several times during communications with a Central Station.
44DACT-UD PN 51899:B1 1/25/05
Transmittal PrioritiesCentral Station Communications
The table below shows UL listed receivers which are compatible with the DACT-UD.
TABLE 4-3:Compatible UL Listed Receivers
Ademco
685 (1)
Silent Knight
9000 (2)
ITI
CS-4000 (3)
FBI
CP220FB
Osborne Hoffman
Models 1 & 2
Radionics
6000 (6)
Radionics
6500 (5)
Sescoa
Format #
4+1 Ademco Express
4+2 Ademco Express
3+1/Standard/1800/2300
3+1/Expanded/1800/2300
3+1/Standard/1900/1400
3+1/Expanded/1900/1400
4+1/Standard/1800/2300
4+1/Expanded/1800/2300
4+1/Standard/1900/1400
4+1/Expanded/1900/1400
4+2/Standard/1800/2300
4+2/Expanded/1800/2300
4+2/Standard/1900/1400
4+2/Expanded/1900/1400
Ademco Contact ID
Not Used
3000R (7)
(8)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
Surguard
MLR-2 (9)
1. With 685-8 Line Card with Rev. 4.4d software
2. With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software
3. Rev. 4.0 software
4. FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8
software
5. Model 6500 with Rev. 600 software
6. Mode 6000 with Rev. 204 software
7. With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software
8. Model 2 only
9. Version 1.62 software
DACT-UD PN 51899:B1 1/25/0545
Default ProgrammingDefault Programming
APPENDIX A Default Programming
The following table provides a list of the programming options and their factory default settings.
Program OptionFactory Default
ON Board DACTDisabled
Service Terminal Primary Phone Line TypeTouch Tone
Service Terminal Secondary Phone Line TypeTouch Tone
Service Terminal Panel ID0000
Service Terminal Primary Phone Numberall Fs
Service Terminal Secondary Phone Numberall Fs
Service Terminal Primary Phone Ring Count.03
Service Terminal Secondary Phone Ring Count03
Service Terminal Upload/Download ReportingBackup Only
Central Station ReportingDisabled
Central Station AC Loss Reporting Delay4
Central Station Backup ReportingFirst Available
Central Station Primary Phone Line Reporting StyleReporting by Point
Central Station Secondary Phone Line Reporting StyleReporting by Point
Central Station Trouble Call Limit10
Central Station Primary Phone Line Test Time0000
Central Station Secondary Phone Line Test Time0000
Central Station Primary Phone Line Test Time Interval24
Central Station Secondary Phone Line Test Time Interval24
Central Station Primary Phone Line Account Code0000
Central Station Secondary Phone Line Account Code0000
Central Station Primary Phone Numberall Fs
Central Station Secondary Phone Numberall Fs
Central Station Primary Phone Communication FormatAdemco Contact ID
Central Station Secondary Phone Communication FormatAdemco Contact ID
46DACT-UD PN 51899:B1 1/25/05
Ademco Contact ID Format Event Code DescriptionsAdemco Contact ID Format Event Code Descriptions
APPENDIX B Ademco Contact ID Format
Event Code Descriptions
This appendix describes the various Event Codes and their messages which are available for the
Ademco Contact ID Format.
The reporting structure for the Ademco Contact ID Format is as follows:
SSS 18 QXYZ GG CCC where
SSSS= Four digit Subscriber ID Account Code
18= Identifies transmission as Contact ID to the receiver at the Central Station
Q= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ= Event code (shown in Table 3.4 )
GG= Group number
CCC= Zone number
Notes:
1. GG Group Number is fixed at '00' and cannot be changed.
2. CCC for Zone or Point Number :
Zone Number is transmitted as '001' for zone 1 up to '099' for zone 99
Point Number is transmitted as ‘001’ for point 1 to ‘636’ for point 636
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
TimeDateRcvr/Line IDSSSSQXYZGGCCCC
11:2803/25117777E11000C001 - general fire alarm on zone one
11:2803/25117777E11100C002 - smoke detector alarm on zone two
11:2803/25117777E38000C003 - fault on zone three
11:2803/25117777E57000C009 - Zone nine disabled
11:2803/25117777R11000C001 - Zone one alarm restored
11:2803/25117777R11100C002 - smoke detector zone two restored
11:2803/25117777R38000C003 - zone three fault restored
11:2803/25117777R57000C009 - zone nine reenabled
11:2803/25117777E15800C006 - high temperature, zone six
11:2803/25117777E15100C007 - gas detected, zone seven
Notes:
1. 18
, which is used in the reporting structure to identify the transmission as Contact ID, is not
printed out in the alarm and trouble report.
2. Q
, which is the Event Qualifier for the reporting structure, is printed out in the report as an E
for New Event or R
DACT-UD PN 51899:B1 1/25/0547
for New Restore.
Ademco Contact ID Format Event Code DescriptionsAdemco Contact ID Format Event Code Descriptions
EVENT CODE CLASSIFICATIONS
1 0 0
ALARMS
M e d i c a l F i r e
Panic Burglary General 24
Hour
2 00
SUPERVISORY
Fire
3 00
TROUBLES
System Sounder/
Relay System
Peripheral Communication Protective
Loop Sensor
400
OPEN/CLOSE
REMOTE ACCESS
Open/Close Remote
Access Access Control
5 00
DISABLES/
BYPASSES
System Sounder/
Relay System
Peripheral Communication
600
TEST/
MISC.
Tes t
EVENTMESSAGE
Medical Alarms - 100
100 MedicalEMERG - Personal Emergency - #
101 Pendant transmitterEMERG - Personal Emergency - #
102 Fail to report inEMERG - Fail to Check-in - #
Ademco Contact ID Format Event Code DescriptionsAdemco Contact ID Format Event Code Descriptions
EVENTMESSAGE
24 Hour Non-Burglary - 150 and 160
150 24-Hour Non-BurgALARM - 24-Hr. Non-Burg - #
151 Gas detectedALARM - Gas Detected - #
152 RefrigerationALARM - Refrigeration - #
153 Loss of heatALARM - Heating System - #
154 Water leakageALARM - Eater Leakage - #
155 Foil breakALARM - Foil Break - #
156 Day trouble ALARM - Day Zone - #
157 Low bottled gas levelALARM - Low Gas Level - #
158 High tempALARM - High Temperature - #
159 Low tempALARM - Low Temperature - #
161 Loss of air flowALARM - Air Flow - #
Fire Supervisory - 200 and 210
200 Fire supervisorySUPER. - Fire Supervisory - #
201 Low water pressureSUPER. - Low Water Pressure - #
202 Lox CO2SUPER. - Low CO2
203 Gate valve sensorSUPER. - Gate Valve - #
204 Low water levelSUPER. - Low Water Level - #
205 Pump activatedSUPER. - Pump Activation - #
206 Pump failureSUPER. - Pump Failure - #
System Troubles - 300 and 310
300 System troubleTROUBLE - System Trouble
301 AC lossTROUBLE - AC Power
302 Low system batteryTROUBLE - System Low Battery
303 RAM checksum badTROUBLE - Bad RAM Checksum (Restore not applicable)
304 ROM checksum badTROUBLE - Bad ROM Checksum (Restore not applicable)
305 System resetTROUBLE - System Reset (Restore not applicable)
306 Panel program changedTROUBLE - Programming Changed (Restore not applicable)
307 Self-test failureTROUBLE - Self Test Failure
308 System shutdownTROUBLE - System Shutdown
309 Battery test failureTROUBLE - Battery Test Failure
310 Ground faultTROUBLE - Ground Fault - #
311 No batteryTROUBLE - No Battery
System Peripheral Troubles - 330 and 340
330 System peripheralTROUBLE - Sys. Peripheral - #
331 Polling loop openTROUBLE - Polling Loop Open
332 Polling loop shortTROUBLE - Polling Loop Short
333 Expansion module failureTROUBLE - Exp. Module Fail - #
334 Repeater failureTROUBLE - Repeater Failure - #
335 Local printer paper outTROUBLE - Printer Paper Out
336 Local printer failureTROUBLE - Local Printer
DACT-UD PN 51899:B1 1/25/0549
Ademco Contact ID Format Event Code DescriptionsAdemco Contact ID Format Event Code Descriptions
EVENTMESSAGE
Communication Troubles - 350 and 360
350 CommunicationTROUBLE - Communication Trouble
351 Telco 1 faultTROUBLE - Phone Line #1
352 Telco 2 faultTROUBLE - Phone Line #2
353 Long range radio xmitter faultTROUBLE - Radio Transmitter
354 Fail to communicateTROUBLE - Fail to Communicate
355 Loss of radio supervisionTROUBLE - Radio Supervision
356 Loss of central pollingTROUBLE - Central Radio Polling
Open/Close - 400
400 Open/CloseOPENINGCLOSING
401 Open/Close by userOPENING - User #CLOSING - User #
402 Group Open/CloseOPENING - Group User # CLOSING - Group User #
403 Automatic Open/CloseOPENING - Automatic CLOSING - Automatic
404 Late Open/CloseOPENING - LateCLOSING - Late
405 Deferred Open/CloseOpening not usedClosing not used
406 CancelOPENING - CancelClosing not used
407 Remote arm/disarmOPENING - RemoteCLOSING - Remote
408 Quick armOpening not applicable CLOSING - Quick arm
409 Keyswitch Open/CloseOPENING - Keyswitch CLOSING - Keyswitch
Remote Access - 410
411 Callback request madeREMOTE - Callback RequestedRestore not applicable
412 Success - download/accessREMOTE - Successful AccessRestore not applicable
413 Unsuccessful accessREMOTE - Unsuccessful AccessRestore not applicable
414 System shutdownREMOTE - System Shutdown
415 Dialer shutdownREMOTE - Dialer Shutdown
416 Success - upload/accessREMOTE - Successful AccessRestore not applicable
Access Control - 420
421 Access deniedACCESS - Access Denied - User # Restore not used
422 Access report by userACCESS - Access Gained - User # Restore not used
System Disables - 500 and 510
50DACT-UD PN 51899:B1 1/25/05
Ademco Contact ID Format Event Code DescriptionsAdemco Contact ID Format Event Code Descriptions
Communication Disables - 550 and 560
551 Dialer disabledDISABLE - Dialer Disable
552 Radio transmitter disabledDISABLE - Radio Disable
Bypasses - 570
570 Zone bypassBYPASS - Zone Bypass - #
571 Fire bypassBYPASS - Fire Bypass - #
572 24-Hour zone bypassBYPASS - 24-Hour Bypass - #
573 Burglar bypassBYPASS - Burg. Bypass - #
574 Group bypassBYPASS - Group Bypass - #
Test Misc. - 600
601 Manual trigger testTEST - Manually Triggered Restore not applicable
602 Periodic test reportTEST - Periodic Restore not applicable
603 Periodic RF transmissionTEST - Periodic Radio Restore not applicable
604 Fire testTEST - Fire Test Restore not used
605 Status report to followSTATUS - Status Follows Restore not applicable
606 Listen-in to followLISTEN - Listen-in Active Restore not applicable
607 Walk test modeTEST - Walk Test Mode
608 System abnormal testTEST - System Abnormal Test
DACT-UD PN 51899:B1 1/25/0551
Central Station PointsCentral Station Points
APPENDIX C Central Station Points
The DACT-UD transmits Central Station Reports in a numerical format which indicates the FACP
addressable device address that is reporting and the SLC loop on which it resides. The following
table indicates the Central Station Report (CS Report) number that will be transmitted and the
addressable device address and SLC loop number it represents.
Table C.1 Addressable DETECTORS on SLC Loop 1
CS
Report
001001033033065065097097129129
002002034034066066098098130130
003003035035067067099099131131
004004036036068068100100132132
005005037037069069101101133133
006006038038070070102102134134
007007039039071071103103135135
008008040040072072104104136136
009009041041073073105105137137
010010042042074074106106138138
011011043043075075107107139139
012012044044076076108108140140
013013045045077077109109141141
014014046046078078110110142142
015015047047079079111111143143
016016048048080080112113144144
017017049049081081113113145145
018018050050082082114114146146
019019051051083083115115147147
020020052052084084116116148148
021021053053085085117117149149
022022054054086086118118150150
023023055055087087119119151151
024024056056088088120120152152
025025057057089089121121153153
026026058058090090122122154154
027027059059091091123123155155
028028060060092092124124156156
029029061061093093125125157157
030030062062094094126126158158
031031063063095095127127159159
032032064064096096128128
Detector
Address
Loop 1
CS
Report
Detector
Address
Loop 1
CS
Report
Detector
Address
Loop1
CS
Report
Detector
Address
Loop 1
CS
Report
Detector
Address
Loop 1
52DACT-UD PN 51899:B1 1/25/05
Central Station PointsCentral Station Points
Table C.2 Addressable MODULES on SLC Loop 1
CS
Report
160001192033224065256097288129
161002193034225066257098289130
162003194035226067258099290131
163004195036227068259100291132
164005196037228069260101292133
165006197038229070261102293134
166007198039230071262103294135
167008199040231072263104295136
168009200041232073264105296137
169010201042233074265106297138
170011202043234075266107298139
171012203044235076267108299140
172013204045236077268109300141
173014205046237078269110301142
174015206047238079270111302143
175016207048239080271113303144
Module
Address
Loop 1
CS
Report
Module
Address
Loop 1
CS
Report
Module
Address
Loop1
CS
Report
Module
Address
Loop 1
CS
Report
Module
Address
Loop 1
176017208049240081272113304145
177018209050241082273114305146
178019210051242083274115306147
179020211052243084275116307148
180021212053244085276117308149
181022213054245086277118309150
182023214055246087278119310151
183024215056247088279120311152
184025216057248089280121312153
185026217058249090281122313154
186027218059250091282123314155
187028219060251092283124315156
188029220061252093284125316157
189030221062253094285126317158
190031222063254095286127318159
191032223064255096287128
DACT-UD PN 51899:B1 1/25/0553
Central Station PointsCentral Station Points
Table C.3 Addressable DETECTORS on SLC Loop 2
CS
Report
319001351033383065415097447129
320002352034384066416098448130
321003353035385067417099449131
322004354036386068418100450132
323005355037387069419101451133
324006356038388070420102452134
325007357039389071421103453135
326008358040390072422104454136
327009359041391073423105455137
328010360042392074424106456138
329011361043393075425107457139
330012362044394076426108458140
331013363045395077427109459141
332014364046396078428110460142
333015365047397079429111461143
334016366048398080430113462144
335017367049399081431113463145
336018368050400082432114464146
337019369051401083433115465147
338020370052402084434116466148
339021371053403085435117467149
340022372054404086436118468150
341023373055405087437119469151
342024374056406088438120470152
343025375057407089439121471153
344026376058408090440122472154
345027377059409091441123473155
346028378060410092442124474156
347029379061411093443125475157
348030380062412094444126476158
349031381063413095445127477159
350032382064414096446128
Detector
Address
Loop 2
CS
Report
Detector
Address
Loop 2
CS
Report
Detector
Address
Loop2
CS
Report
Detector
Address
Loop 2
CS
Report
Detector
Address
Loop 2
54DACT-UD PN 51899:B1 1/25/05
Central Station PointsCentral Station Points
Table C.4 Addressable MODULES on SLC Loop 2
CS
Report
478001510033542065574097606129
479002511034543066575098607130
480003512035544067576099608131
481004513036545068577100609132
482005514037546069578101610133
483006515038547070579102611134
484007516039548071580103612135
485008517040549072581104613136
486009518041550073582105614137
487010519042551074583106615138
488011520043552075584107616139
489012521044553076585108617140
490013522045554077586109618141
491014523046555078587110619142
492015524047556079588111620143
493016525048557080589113621144
494017526049558081590113622145
495018527050559082591114623146
496019528051560083592115624147
497020529052561084593116625148
498021530053562085594117626149
499022531054563086595118627150
500023532055564087596119628151
501024533056565088597120629152
502025534057566089598121630153
503026535058567090599122631154
504027536059568091600123632155
505028537060569092601124633156
506029538061570093602125634157
507030539062571094603126635158
508031540063572095604127636159
509032541064573096605128
Modules
Address
Loop 2
CS
Report
Modules
Address
Loop 2
CS
Report
Modules
Address
Loop2
CS
Report
Modules
Address
Loop 2
CS
Report
Modules
Address
Loop 2
DACT-UD PN 51899:B1 1/25/0555
Notes
56DACT-UD PN 51899:B1 1/25/05
Index
Numerics
24 Hour Test Time25
A
Account Code 24
Ademco
contact ID format 47
Alarm Current 8
B
Backup
Reporting 22
C
Callback to Service Terminal 38
Central Station 21
Communication 41
Phone Number 23, 25
point assignments 52
Central Station Acknowledge 38
Central Station Communications 41
Central Station Reports 52
Communication
Central Station 41
Communication Format 26, 27
Reporting Structure 42
Communication Formats 9
Compatible Panel 8
contact ID 47
Current
Alarm 8
Standby 8
D
DACT
Installation 14
Programming 17
Data Protection/Integrity 38
DC Power 8
Default Programming 46
Description 8
dial tone 9
Digital Communicator 9
Download
Off Hook 35
Off/On Hook 9
On Hook 35
On-Board DACT
Programming 17
P
Panel Compatibility 8
Panel ID 19
Panel Identification Number 38
Phone Number
Central Station 23, 25
Service Terminal 20
point assignments 52
Point Reporting 34
Primary Phone 18
Priorities
Transmittal 44
Product Features 8
Program
Download 36
Programming
factory default 46
MS-9600 for DACT 17
R
Receivers 45
receivers
UL listed 45
Remote Site
Upload/Download 36
REN
see also Ringer Equivalence
Number 10
Report Style 34
Reporting
Backup 22
Enable 21
Reporting Structure
Communication Format 42
Ring Count 21
Ringer Equivalence Number 10
Rotary dialing 18
S
Secondary Phone 18
Secret Code Verification 37
Security Features 37
Service Terminal 19
Phone Number 20
Simultaneous Data Transfers 40
Specifications 8
Standby Current 8
T
Telephone
Circuitry 10
Requirements 10
Telephone Company
Rights and Warnings 11
Telephone Connection 16
Telephone Line 9
Terminal 20
Test Time
24 Hour 25
Test Time Interval 24, 25
Time-out at Control Panel 37
tone burst 9
touchtone 9
Touchtone dialing 18
Transmittal
Priorities 44
Transmittal Priorities 44
U
Upload
Remote 36
Service Terminal 39
W
Warnings10
Z
Zone Reporting 34
DACT-UD PN 51899:B1 1/25/0557
Notes
58DACT-UD PN 51899:B1 1/25/05
Limited Warranty
The manufacturer warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service. Products
are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer
is to repair or replace, at its option, free of charge for parts and labor, any part which is
defective in materials or workmanship under normal use and service. For products not under
the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of
original purchase by the manufacturer's distributor unless the installation instructions or catalog
sets forth a shorter period, in which case the shorter period shall apply. This warranty is void
if the product is altered, repaired, or serviced by anyone other than the manufacturer or its
authorized distributors, or if there is a failure to maintain the products and systems in which
they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our customer service department. Return product, transportation
prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its
products. The manufacturer does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they are
installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes
no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse,
abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER
NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S
PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR
AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the
manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.