Fire-Lite D350RP Installation And Maintenance Manual

F300-11-00 8 I56-0047-005R
[10.2] Power Board Replacement
1. Disconnect wiring from the terminal block.
2. Remove the two power board mounting screws.
3. Pull gently on the board to remove it.
4. To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.
5. Secure board with the two mounting screws.
[12] Model D350RP Air Duct Smoke Detector Specifications
Operating Temperature Range +32° to +131°F (0° to +55°C) Storage Temperature Range –22° to +158°F (–30° to +70°C) Humidity Range 10% to 93% (non-condensing) Air Velocity 500 to 4000 ft/min (2.54 to 20.32 m/sec) Dimensions 14
3
⁄8
L x 5
1
⁄2″ W x 23⁄4″ D (37 cm L x 14 cm W x 7 cm D)
Programming Specifications/Requirements for Intelligent System Control Panels
There are a limited number of devices that can have their LEDs programmed to illuminate. The actual number of devices is determined by the control panel and its ability to supply LED current. Refer to the Control Panel Installation Manual for details.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Note:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interfer­ ence will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.
To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component of that system which fails shall be repaired or replaced as soon as possible.
Current Requirements (using no accessories)
Power supply voltage: 20-30 VDC 24 VAC, 50-60 Hz 120 VAC, 50-60Hz 220/240 VAC, 50-60Hz
Max. standby current: 26 mA 65 mA RMS 44 mA RMS 25 mA RMS
Max. alarm current: 87 mA 182 mA RMS 52 mA RMS 30 mA RMS
Alarm resonse time: 3 to 10 Sec. 3 to 10 Sec. 3 to 10 Sec. 3 to 10 Sec.
Power up time: 2 Sec. 2 Sec. 2 Sec. 2 Sec.
Accessories Part No. Remote LED RA400Z Magnetic Remote Test RTS451 Key-Activated Remote Test RTS451KEY Replacement Filters F36-09-11 Replacement Test Magnet M02-04-00
Accessories Part No.
Replacement Photo Insect Screen S08-39-01 Replacement End Cap for Plastic Sampling Tube P48-61-00 Replacement End Cap for Metal Sampling Tubes P48-21-00 Replacement Photoelectric Sensor Board A5053FL Replacement Power Board (w/relay) A5060
Accessory Current Loads at 24 VDC
Device Standby Alarm
PA400 0 mA 15 mA Max.
RA400Z 0 mA 12 mA Max.
RTS451/RTS451KEY 0 mA 10 mA Max.
Contact Ratings
Alarm auxiliary contacts* (DPDT) 10 A @ 30 VDC 10 A @ 277 VAC (.75 power factor) 240 VA @ 249 VAC (0.4 power factor) 1/8 HP @ 120 VAC 1/4 HP @ 240 VAC
Supervisory contact (SPST) 2.0 A @ 30 VDC (resistive)
*Minimum switching current for auxiliary contact must be 100 mA DC minimum @ 5 VDC.
F300-11-00 1 I56-0047-005R
Fire•Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472, 203-484-7161
Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from NEMA (National Electrical Manufacturers Association, 2101 L Street NW, Washington, DC
20037). NFPA Standards 72 and 90A should also be referenced for detailed information.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.
GENERAL DESCRIPTION
An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct system is distributed to the entire building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct.
The D350RP air duct smoke detector is a photoelectric detector. This smoke detection method combines with an efficient housing design that samples air passing through a duct and allows detection of a developing hazardous condition. When sufficient smoke is sensed, an alarm signal is initiated at the fire control panel monitoring the detector, and appropriate action can be taken to shut off fans, blowers and change over air handling systems, etc. This can prevent the distribution or it can isolate toxic smoke and fire gases throughout the areas served by the duct system.
Two LEDs on each detector may illuminate, if programmed by the system control panel, to provide a local alarm indica­tion. There is also a remote alarm output for use with auxiliary devices. The D350RP has remote test capability with the RTS451/RTS451KEY Remote Test Station.
The D350RP incorporates a cover tamper feature. When the cover is removed for more than 20 minutes, the unit loses communication at the panel, a trouble is indicated at the panel and the alarm relay switches states thereby shutting down fans, dampers and blowers. In the case when the sensor is removed or when there is no power to the unit, only a trouble is indicated at the panel (alarm relay does not work any longer).
Figure 1. Exploded view of duct smoke detector components:
CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT
The D350RP Duct Smoke Detector consists of the following items (See Figure 1.):
D350RP INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR
INSTALLATION AND MAINTENANCE INSTRUCTIONS
NOTE: For ducts over 1
1
⁄2 feet, longer sampling tubes must be ordered to complete the installation. They must be the
correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.
Contents Of The Duct Smoke Detector
1. Complete duct smoke detector assembly with sensor
2. Two #10 x 1
1
/
4
sheet metal screws
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the sampling tube and optional exhaust tube extension
8. One sampling tube end cap
9. One plastic sampling tube
10. One #8 self-tapping screw for plastic sampling tube
NOTE: A detector sensor board DOES NOT need to be ordered separately.



















H0106-00
Please refer to insert for the Limitations of Fire Alarm Systems
F300-11-00 7 I56-0047-005R
[9.2.2] Alarm Tests [9.2.2.1] M02-04-00 Magnet Test
1. Place the painted surface of the magnet onto the TEST locator on the bottom of the detector housing (Figure 13).
2. Verify system control panel alarm status and control panel execution of all intended auxiliary functions (i.e. fan shutdown, damper control, etc.)
3. The detector is self-restoring when the magnet is removed. Verify that the system control panel has reset; the panel may have to be reset.
[9.2.2.2] RTS451/RTS451KEY Remote Station Test
The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct smoke detector. These accessories provide the stimulus to initiate an alarm condition at the detector. The detector is self-restoring when the accessory test stimulus is removed. Verify that the system control panel has reset; the panel may have to be reset.
[9.2.3] Sensitivity Tests
Notify the proper authorities that the smoke detector system is undergoing maintenance, and that the system will temporarily be out of service. Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department.
[9.3] Maintenance of Duct Smoke Detectors [9.3.1] Air Filters
1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with new filters (p/n F36-09-11). If they are not heavily coated, use a vacuum cleaner or compressed air nozzle to remove dust, then reinstall the filters.
[9.3.2] Photo Detector Boards
1. Remove the screen by gently grasping on each side and pulling straight off.
2. Lift the photo chamber in the same fashion. Vacuum the screen and cover. Use clean, compressed air to loosen and blow out any remaining debris. Replacement screens (p/n S08-39-01) are available.
3. Vacuum photo chamber, then use clean compressed air to blow area clean.
4. Replace the chamber by pressing it onto the base. Press the screen into place. It should fit tightly on the chamber.
[10] Board Replacement [10.1] Sensor Board Replacement
1. Remove the two sensor board mounting screws.
2. Pull gently on the board to remove it.
3. To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.
4. Secure board with the two mounting screws.
Figure 13. Testing detector alarm:
5
7
PA400
5 = Alarm Signal 7 = Aux. Power (–)
Figure 11. Detector with optional PA400 Figure 12. Insulator car d for D350RP.
F300-11-00 2 I56-0047-005R
WARNING
LIMITATIONS OF DUCT DETECTORS
WARNING
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection system.
It is strongly recommended that the user read NFPA Standards 90A, 72, and 101.
WARNING
This device will not operate without electrical power. Fire situations may cause an interruption of power. The system safeguards should be discussed with your local fire protection specialist.
WARNING
This device will not sense smoke unless the ventilation system is operating.
WARNING
In order to function properly, this detector must be installed according to the instructions. Do not exceed the electrical or ambient specifications or the detector will not function properly. This detector must be protected from the elements.
INSTALLATION SEQUENCE
Step 1. Verify duct air flow direction and velocity.................................................................................................. 2
Step 2. Drill the mounting holes ........................................................................................................................... 2
Step 2.1 Install the sampling tube for ducts less than 1
1
⁄2
feet wide ..........................................................................2
Step 3. Secure the detector housing to the duct ..................................................................................................... 3
Step 4. Install the sampling tube for ducts greater than 1
1
⁄2
feet wide .................................................................... 3
Step 4.1 Installation for ducts greater than 1
1
⁄2
feet but less than 8 feet wide ..........................................................3
Step 4.2 Installation for ducts more than 8 feet wide ............................................................................................. 4
Step 5. Install the filters ....................................................................................................................................... 4
Step 6. Field wiring.............................................................................................................................................. 4
Step 7. Perform detector check .............................................................................................................................5
Step 8. Install the cover ....................................................................................................................................... 5
Step 9. Detector Maintenance and Test Procedures ................................................................................................5
[1] Verify Duct Air Flow Direction And Velocity
The D350RP duct smoke detector is designed to be used in air handling systems having air velocities of 500 to 4000 feet per minute. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If necessary, use a velocity meter to check the air velocity in the duct. See Air Flow Test, section 9.1.
[2] Drill The Mounting Holes
Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indi­cated on the template.
[2.1] Sampling Tube Installation for Ducts Less Than 1
1
⁄2 Feet Wide (see Figure 2)
1. Remove the front cover.
2. Slide the plastic sampling tube into the housing bushing.
3. Align the holes in the bushing with the holes in the sampling tube. Make sure there are 6 exposed holes on the plastic sampling tube. Secure with the #8 self-tapping screw into the bottom of the permanent tube (shown in Fig. 2).
NOTE: The sampling tube end cap is critical to the proper operation of the duct smoke detectors. The end cap is needed to create the proper air flow to the sensor of the duct smoke detector.
NOTE: For ducts greater than 1
1
⁄2 feet in width, refer to sections [4], [4.1] and [4.2].
Figure 2. Plastic sampling tube connected to duct smoke detector:
Loading...
+ 2 hidden pages