Fire-Lite CP355 User Manual

CP355 Plug-in Addressable Ionization Sensor
Installation and Maintenance Instructions
GENERAL DESCRIPTION
This sensor must be installed in compliance with the control panel system installation manual. The installation must meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with the National Fire Protection Association (NFPA); see NFPA 72.
Model CP355 intelligent ionization sensor uses a state-of-the-art sensing chamber. This sensor is designed to provide open area protection and is intend­ed for use with compatible control panels only.
The CP355 requires compatible addressable communications to function properly. Connect this sensor to listed-compatible control panels only.
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC Max. Avg. Standby Current: 300µA@ 24 VDC (one communication every 5 sec. with LED blink enabled) Max. Alarm Current (LED on): 6.5 mA @ 24 VDC Operating Humidity Range: 10% to 93% Relative Humidity, noncondensing Operating Temperature Range 0° to 49°C (32° to 120°F) Height: 1.7 inches (43 mm) installed in B350LP Base Diameter: 6.1 inches (155 mm) installed in B350LP Base Weight: 3.6 oz. (102 g)
SPACING
Fire•Lite recommends spacing sensors in compliance with NFPA 72. In low air flow applications with smooth ceilings, space sensors 30 feet apart. For specific information regard­ing sensor spacing, placement, and special applications, refer to NFPA72 or the System Smoke Detector Application Guide, available from Fire•Lite.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color­coded to limit wiring mistakes and ease system trouble-shoot­ing. Improper connections will prevent a system from respond­ing properly in the event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, see Figure 1.
2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling or construction.
6. Tamper-Resistance Model CP355 includes a tamper-resistant capability that prevents its removal from the bracket
without the use of a tool. Refer to the base manual for details on making use of this capability.
7. After all sensors have been installed, apply power to the system.
8. See Figure 3. Test the sensor by positioning a test magnet against the sensor plastic in the magnet test area. The alarm level should be recognized at the panel and the LED controlled by communication command from the panel.
9. Reset the sensor by communication command from the panel.
CAUTION
F300-23-00 1 I56-1970-00R
Fire•Lite, One Fire•Lite Place, Northford, CT 06472-1653, (203) 484-7161
Figure 1.
Figure 2.
CONTROL PANEL
UL LISTED COMPATIBLE
+
-
­+
REMOTE ANNUNCIATOR
+-
2
3
1
CAUTION: Do not loop wire under terminal 1 or 2. Break wire run to provide supervision of connections.
2
3
1
CLASS A OPTIONAL WIRING
2
3
1
6
5
4
3
2
1
Breakaway Stop
7
8
9
10
11 12
13
14
15
0
7
8
6
5
9
4
3
2
1
0
TESTING
Detectors must be tested after installation and following periodic mainte­nance. However, before testing, notify the proper authorities that the smoke detector system is undergoing maintenance and the system will be temporarily out of service. Disable the zone or system undergoing mainte­nance to prevent unwanted alarms.
Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when tested and maintained in com­pliance with NFPA72.
Test the sensors as follows: A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test magnet electronically simulates smoke in the sensing chamber, testing the sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel. Two LEDs on the sensor are controlled by the panel to indicate sen­sor status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel tech­nical documentation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry: Aerosol Generator (Gemini 501)
The GEMINI model 501 aerosol generator can be used for smoke entry testing. Set the generator to represent 4%/ft to 5%/ft obscuration as described in the GEMINI 501 manual. Using the bowl shaped applica­tor, apply aerosol until the panel alarms.
Asensor that fails any of these tests should be cleaned as described under CLEANING, and retested. If the sensor fails after cleaning, it must be replaced.
When testing is complete, restore the system to the normal operation and notify the proper authorities that the system is back in operation.
F300-23-00 2 I56-1970-00R
©2002 Fire•Lite
Figure 3. Test Magnet Positioning
Figure 4. Cleaning
CLEANING
Before cleaning, notify the proper authorities that the system is undergo­ing maintenance and will be temporarily out of service. Disable the system to prevent unwanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover. Press firmly on each of the four removal tabs that hold the cover in place.
3.
Vacuum the outside of the screen carefully. If further cleaning is required, continue with Step 4, otherwise skip to Step 5.
4. Use clean, compressed air to remove dust and debris from the sens­ing chamber.
5. Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place.
6. Reinstall the detector.
7. Test the detector as described in TESTING.
8. Reconnect disabled circuits.
9. Notify the proper authorities that the system is back on line.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interfer­ence will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.
A78-2737-01
Please refer to insert for the Limitations of Fire Alarm Systems
A78-2738-00
Magnet T est
Marker
Test Magnet
Position
Sensor Cover
Sensing
Cover Removal Tabs
Chamber and Screen
LED Status
Indicators
Magnet T est
Marker
Test Magnet
Position
Loading...