Fire-Lite CHG-75 User Manual

PN: 51315:A ECN 01-437
Battery Charger
CHG-75
Document #51315
08/01/01 Revision:
A
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warn­ing devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke detectors may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede­termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power.
cated, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibil­ity to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized pro­fessional fire alarm installers only. Adequate written records of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, ad­dition or deletion of system components, or after any modifica­tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for operation at 0-49° C/32-120° F condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi­nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LimWarLg.p65 01/10/2000
Notes
4 CHG-75 PN 51315:A 08/01/01
Table of Contents
SECTION 1: Product Description ........................................................................................................................7
1.1: Features .......................................................................................................................................................7
1.2: Specifications ..............................................................................................................................................8
1.3: LED Indicators ............................................................................................................................................9
1.4: Charger Maintenance ..................................................................................................................................9
SECTION 2: Installation and Configuration .......................................................................................................10
2.1: Precautions ..................................................................................................................................................10
2.2: Charger Connections, Jumpers and Switches..............................................................................................10
2.3: Charger Configuration.................................................................................................................................11
2.3.1: SW2 & SW3 SLC Addressing Switches...........................................................................................11
2.3.2: SW1 SLC Communication Enable Switch .......................................................................................11
2.3.3: AC Loss Reporting Delay - Central Station Applications ................................................................11
2.3.4: Ground Fault Detection Disable........................................................................................................12
2.3.5: AM-1 Ammeter Enable.....................................................................................................................12
2.4: Mounting the Charger .................................................................................................................................12
2.4.1: Mounting the Charger in an FACP....................................................................................................12
2.4.2: Mounting the Charger in a BB-55F Battery Box..............................................................................13
2.4.3: Mounting Charger in BB-26 Battery Box.........................................................................................13
2.5: UL Power-limited Wiring Requirements.....................................................................................................14
2.6: Optional Voltmeter/Ammeter Installation ...................................................................................................15
2.7: Connecting AC Power to the Charger .........................................................................................................16
2.8: Connecting Batteries to the Charger ...........................................................................................................17
2.8.1: Connecting Two Batteries .................................................................................................................17
2.8.2: Connecting Four Batteries.................................................................................................................18
2.9: Connecting the Charger to a Load...............................................................................................................19
2.9.1: Connecting the Charger to a Single Load .........................................................................................19
2.9.2: Connecting the Charger to an MS-9200............................................................................................20
2.9.3: Connecting the Charger to an MS-9600............................................................................................21
2.9.4: Connecting the Charger to Multiple Loads.......................................................................................22
2.10: Trouble Monitoring ...................................................................................................................................23
SECTION 3: Operation .........................................................................................................................................25
3.1: Powering the Charger..................................................................................................................................25
3.2: LED Status Indicators .................................................................................................................................25
3.3: Normal Operation........................................................................................................................................26
CHG-75 P/N: 51315:A 08/01/01
5
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems
Other:
EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
6 CHG-75 PN 51315:A 08/01/01
Features
Product Description
SECTION 1
1.1 Features
Product Description
The CHG-75 battery charger is designed to charge lead-acid batteries that provide emergency standby power for an FACP (Fire Alarm Control Panel) and related equipment. Two 12 volt batteries are used in series to supply a nominal 24VDC. The battery charger is compatible with any FACP that uses lead-acid batteries with a rating of 25 AH (Amp Hours) to 75 AH. The FACP must have a feature that allows the disabling of the control panel battery charger.
The CHG-75 can be configured for 120 VAC operation or 220/240 VAC operation via jumper selection.
120 VAC or 220/240 VAC operation via JP1 jumper selection
Charger capacity of 25 AH to 75 AH
Mounts in a BB-26, BB-55F, MS-9600 and MS-9200 enclosure
Screw terminal connection for battery
F2, 15 amp replaceable fuse provides battery current-limiting, short circuit and overload protection
Screw terminal connection for battery backup to other equipment
F3, 15 amp replaceable fuse provides current-limiting and overload protection for output to connected equipment
Fail-safe Form-C trouble relay rated for 2 amps @ 30 VDC (resistive)
Ground fault detection circuit which can be disabled by cutting jumper JP2
Battery and charger voltage supervision
AC voltage supervision
AC loss reporting delay option, jumper selectable for 8 or 16 hour delay
Connectors for trouble input and trouble output which direct CHG-75 troubles to FACP and allows daisy-chaining of external troubles through the charger without affecting charger operation
Master trouble input allows monitoring of another device or zone
Connectors for optional AM-1 ammeter and VM-1 voltmeter
LEDs for monitoring charger condition
Screw terminal connection for SLC loop
Direct SLC interface for charger trouble and/or AC loss reporting to the FACP
CHG-75 PN 51315:A 08/01/01 7
Product Description
1.2 Specifications
Specifications
Primary (AC) Power - TB1, Terminals 1 (Hot), 2 (Neutral) & 3 (Earth)
120 VAC, 60 Hz, 2.05 amps maximum 220/240 VAC, 50 Hz, 1.14 amp maximum (JP1 cut) Fuse F1 - 6.25 amp (slow blow 3AG) Wire size: minimum 14 AWG with 600 volt insulation
Secondary Power (Battery) Charging Circuit - TB2, Terminals 1 (+) & 2 (-)
Supports lead-acid batteries only Float Charge Voltage: 27.6 VDC Maximum Charge Current: 4.5 amps (peak) Maximum Battery Capacity: 75 AH Supervised and Current-limited: F2 - 15 amp replaceable fuse
24 VDC Secondary (Battery) Input Power
The CHG-75 current consumption from the battery is as follows:
• During AC Loss: 60 mA
• With AC Present: 0 mA
Note: use these values in battery calculations for host FACP
Battery Output - TB2, Terminals 3 (+) & 4 (-)
Provides battery backup connection to other loads Current-limited: F3 - 15 amp replaceable fuse
SLC (Signal Line Circuit) Connector - TB3, Terminals 1(B+), 2(A+), 3(B-) & 4(A-)
Provides connection to an addressable FACP (Fire Alarm Control Panel) SLC loop. A built-in addressable monitor module can be used to indicate a charger trouble condition or loss of AC by programming the FACP to monitor the address assigned to the charger. Voltage: 24 VDC nominal, 27.6 VDC maximum Maximum Loop Current: 400 mA (short circuit) or 100 mA (normal) Maximum Loop Resistance: 40 ohms Supervised and Power-limited
Trouble Contact Rating - TB4, Terminals 1 (C), 2 (NO) & 3 (NC)
Fail-safe Form-C Relay Contacts: rated for 2 amps @ 30 VDC (resistive)
Trouble In and Out Connectors - J1 (In) & J2 (Out)
Trouble In is an open collector circuit which can be used to monitor trouble conditions on other equipment. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector circuits.
Trouble Out can be used to send the Trouble In signal and/or charger trouble signal to a monitoring circuit on an FACP (daisy chain).
Trouble In Master - J3
Circuit monitors trouble from other devices by looking for a ground condition. When input is brought to ground potential, charger will operate trouble relay
8 CHG-75 PN 51315:A 08/01/01
LED Indicators
1.3 LED Indicators
LEDs are provided on the battery charger circuit board to monitor various conditions:
AC LED - green LED indicates AC power is present
Trouble LED - yellow LED turns on for charger troubles or trouble indication from the Master Trouble Input
Low Battery LED - yellow LED turns on when the battery voltage drops too low
Charging LED - yellow LED indicates battery is being charged, turns off when the CHG-75 is trickle charging
Ground Fault LED - yellow LED turns on to indicate ground fault on the charger
SLC Communication LED - green LED indicates SLC communication with FACP
1.4 Charger Maintenance
The charger does not require regular maintenance. While installing the charger, however, do not cut any jumpers when power is applied and make sure to maintain proper polarity when connecting power leads and battery connections. To ensure optimal operation of the charger, observe the following:
Product Description
Overload and reverse-polarity protection
12057) provide overload and reverse-polarity protection. Replace a blown fuse with a fuse that has the same rating and type. Determine the cause of the blown fuse.
Periodic Inspection
make sure that corrosive effects to the batteries do not affect the charger or cabinet.
Troubleshooting
loose connections. If you encounter problems, inspect the charger, the batteries and all connections for loose wiring or short circuits.
Replacing Batteries
capacity as the other batteries in the set. For example, if replacing one of four 25 AH batteries, make sure the replacement battery has the same charge rate and capacity as the other three batteries.
- periodically inspect the batteries for corrosion and
- most problems with a charger are due to faulty batteries or
- replace batteries only with the same charge rate and
- fuses F2 and F3 (15 A, P/N:
CHG-75 PN 51315:A 08/01/01 9
Installation and Configuration
Precautions
SECTION 2
Installation and Configuration
2.1 Precautions
Battery and Charger Precautions
!
When installing the CHG-75 battery charger, observe the following precautions:
cut any jumpers when power is applied to the charger
Do not
Observe polarity when making connections
Do not connect the Battery Interconnect Cable until instructed
Mounting batteries requires proper mounting hardware. Follow the battery manufacturer’s installation instructions
Be careful when lifting and handling batteries: batteries are heavy
Batteries, although sealed, contain sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention
Charging batteries can cause flammable hydrogen gas
2.2 Charger Connections, Jumpers and Switches
The following figure illustrates all connections, jumpers and switches needed to maintain, configure and operate the charger:
CAUTION!
DO NOT
Cut any Jumpers
if power is applied!
JP1 - In for 120VAC Cut for 240VAC
JP1
CUT FOR 240VAC
F1
Ground Fault - Yellow LED
SLC Communication - Green LED
SLC Addressing Switches
SW2 Tens Switch
TB1
HOT
SW3 Ones Switch
EARTHNEUT
Earth - TB1 Terminal 3 AC Neutral - TB1 Terminal 2 AC Hot - TB1 Terminal 1 (supervised)
*Relay is fail-safe and contact designations are shown with power applied and no troubles on the charger.
Figure 2.1 Charger Components
- Battery, supervised (TB2 Terminal 2)
+ Battery, supervised (TB2 Terminal 1)
J4 Connector for AM-1 Ammeter
JP4 - Cut for 16 Hour AC Reporting Delay
JP5 - Cut to Install AM-1
JP3 - Cut for 8 or 16 Hour AC Reporting Delay
SW1 - On = SLC Communication Enabled Off = SLC Communication Disabled
Low Battery - Yellow LED
Charging - Yellow LED
Trouble - Yellow LED
AC Power - Green LED
TENS
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
ONES
SLC A- (TB3 Terminal 4)
SLC B- (TB3 Terminal 3) SLC A+ (TB3 Terminal 2) SLC B+ (TB3 Terminal 1)
(supervised & power-limited)
Normally Closed (TB4 Terminal 3)
Normally Open (TB4 Terminal 2)
Common (TB4 Terminal 1)
- Out to FACP (TB2 Terminal 4)
+ Out to FACP (TB2 Terminal 3)
AM-1 ENABL E
ENABLE AC DELAY
JP4
JP5
F2
15
15
F3
J1 J2
JP2
J3
ADDRESS
SW1
ON OFF
TB3
A- B- A+ B+
JP3
16 HR DELAY
TB4
NC NO C
Relay*
J4
AM-1
TB2
+
-
BATT
-
+
OUT TO FA CP
GND FLT DISABLE
chg75brd.cdr
JP2 - Cut to Disable Ground Fault Detection
J3 - Master Trouble In J2 - Trouble Out J1 - Trouble In
10 CHG-75 PN 51315:A 08/01/01
Charger Configuration
2.3 Charger Configuration
2.3.1 SW2 & SW3 SLC Addressing Switches
An addressable monitor module has been incorporated into the circuitry of the CHG-75 to allow a host FACP (Fire Alarm Control Panel) to monitor the charger condition via its SLC. This monitor module will create an open circuit condition when any local charger trouble occurs. If AC power is lost, the monitor module will create a short condition which will be seen by the FACP immediately, even if AC delay is enabled. By addressing and connecting the charger to an addressable control panel’s SLC, the panel can be programmed to monitor this module for activation.
Rotary switches SW2 & SW3 are used to address the CHG-75 for connection to the addressable control panel’s SLC. The switches must be set to a unique address which has not been programmed for any other device on the SLC
Installation and Configuration
To set the desired address, turn switch SW2 to the
ones
the
digit of the address. For example, to set the charger to address
tens
digit of the address and SW3 to
125
, position
SW2 so the arrow points to 12 and position SW3 so the arrow points to 5.
In the following example, the power supply has been set to address 68, with SW2 Tens switch pointing to 6 and SW3 Ones switch pointing to 8.
Figure 2.2 CHG-75 Addressing
SW2
SW3
12
12
14
13
14
13
10
15
10
15
11
TENS
11
9
9
0
5
3
4
0
5
3
4
ONES
7
8
1
6
2
7
8
1
6
2
chg75add.cdr
2.3.2 SW1 SLC Communication Enable Switch
Slide switch SW1 is used to enable and disable the SLC communication between the CHG-75 and the FACP. Positioning SW1 to the left (ON) will enable SLC communication while positioning the switch to the right (OFF) will disable communication. Refer to Figure 2.1 on page 10, for the location of switch SW1.
Note that if the FACP has been programmed to monitor the charger via the SLC, positioning SW1 to the right (OFF) position will disable SLC communication between the charger and control panel, causing the FACP to indicate a communication fault for the charger address.
2.3.3 AC Loss Reporting Delay - Central Station Applications
If a Digital Alarm Communicator (DACT) is being used, the reporting of an AC loss condition to a Central Station must be delayed. This will delay the activation of the trouble bus and Form-C trouble contacts when the AC fails. The charger can be configured for an 8-hour or 16-hour delay as follows:
JP3
1.
2.
Refer to Figure 2.1 on page 10, for location of the jumpers.
CHG-75 PN 51315:A 08/01/01 11
- Cut jumper JP3 to enable a delay in reporting AC loss
JP4
- Leave jumper JP4 in to delay AC loss reporting for 8 hours
Cut jumper JP4 to delay AC loss reporting for 16 hours
Installation and Configuration
2.3.4 Ground Fault Detection Disable
Cut jumper ground fault detection circuit might be disabled when the charger is connected to equipment with its own ground fault detection circuit to prevent the two circuits. Note that Ground Fault detection is required in Canada. Refer to Figure 2.1 on page 10, for location of the jumper.
2.3.5 AM-1 Ammeter Enable
Cut jumper CHG-75 charger. Refer to Figure 2.1 on page 10, for location of the jumper.
2.4 Mounting the Charger
2.4.1 Mounting the Charger in an FACP
The CHG-75 can be mounted in the bottom of the MS-9600 backbox, using the self­tapping screws included with the charger. In a similar fashion, the supplied nuts can be used to mount the charger to pem studs located in the bottom of the MS-9200 backbox. A separate battery box must be used to house the batteries when employing these configurations. Figure 2.3 illustrates the CHG-75 mounting location in the MS-9600. The pem studs are located in the same area in the MS-9200 backbox .
Note: The CHG-75 must be mounted in the same room and within 20 feet of the FACP
Mounting the Charger
JP2
to disable reporting of a local ground fault condition. The charger’s
competition
JP5
to enable the operation of the AM-1 Ammeter when installed on the
between
.
TB3
JP3
CUT TO DISABLE LOCAL CHARGER
DISABLE GND FLT
CUT TO MONITOR 4XTM
4XTM OP T BD
J10
JP2
J17
J16
LCD D ISPLAY
TB1
+BATTERY -
HOT
NEUT EARTH
CB1
mounting holes for CHG-75
MS-9600 FACP
TB5
TB4
JP6
J11
J2
J6
KEYPAD I/F
TB2
OPT DACT
J8
TB6 TB7
JP5
SW1
J7
J12
SECU RITY OPT BD
TB8
OPT SLC
J3
9600powr.cdr
Figure 2.3 MS-9600 Backbox
12 CHG-75 PN 51315:A 08/01/01
Mounting the Charger
Note: left and right side of backbox have same layout.
Installation and Configuration
2.4.2 Mounting the Charger in a BB-55F Battery Box
The CHG-75 can mount in a BB-55F Battery Box at the location indicated in Figure
2.4. Use the supplied self-tapping screws to secure the charger to the backbox.
mounting holes for CHG-75
mounting holes for AM-1 or VM-1
Figure 2.4 BB-55F Battery Box
2.4.3 Mounting Charger in BB-26 Battery Box
The CHG-75 can mount in a BB-26 Battery Box at the location indicated in Figure 2.5. Use the supplied nuts to secure the charger to the backbox mounting studs.
Note: left and right side of backbox have same layout.
bb55f.cdr
mounting hole for AM-1 or VM-1
mounting studs for CHG-75
bb26.cdr
Figure 2.5 BB-26 Battery Box
CHG-75 PN 51315:A 08/01/01 13
Installation and Configuration
789
2.5 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any nonpower­limited circuit wiring. Furthermore, all power-limited circuit wiring and nonpower­limited circuit wiring must enter and exit the cabinet through different conduits. Examples are shown in the following illustrations. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications, use of conduit is optional.
J8
nonpower-limited circuit
J6
TUV WXY
PRS
LCD DISPLAY
MODE
0 #
*
TB1
TB2
-/.
QZ
RECALL
HOT
+BATTERY-
NEUT EARTH
CB1
KEYPAD I/F
JP4
HOLD 2 SEC
1 2
RESET
3
J7
UL Power-limited Wiring Requirements
J3
J12
chg7to96.cdr
nonpower-limited circuit
nonpower-limited circuit
nonpower-limited circuit
power-limited circuit
nonpower-limited circuit
power-limited circuit
power-limited circuit
JP1
CUT FO R 240VAC
F1
TB1
HOT
EARTHNEUT
CUT FOR 240VAC
HOT
EARTHNEUT
MS-9600 FACP
nonpower-limited circuit
AM-1 ENABLE
J4
ENABLE
JP5
JP3
AC DELAY
AM-1
F2
TB2
SW1
TB3
A- B- A+ B+
ADDRESS
ON OFF
15
+
BATT
-
JP4
16 HR
15
DELAY
-
F3
+
OUT TO FACP
JP2
GND FLT DISABLE
TB4
J1 J2
J3
NC NO C
nonpower-limited circuit
TENS
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
0
5
11
7
10
8
14
1
12 13
6
2
15
3
9
4
ONES
bb55fchg.cdr
BB-55F
JP1
F1
TB1
TENS
0
5
11
7
10
8
14
1
12 13
6
15
2
39
ADDRESS
4
SW1
0
5
11
7
ON OFF
10
8
14
1
12 13
6
15
2
39
4
ONES
TB3
A- B- A+ B+
J4
ENABLE
JP5
JP3
AC DELAY
AM-1
F2
TB2
15
+
-
BATT
JP4
15
-
F3
+
OUT TO FACP
JP2
TB4
J1 J2 J3
NC NO C
nonpower-limited circuit
GND FLT DISABLE
nonpower-limited circuit
BB-26
Figure 2.6 UL Power-limited Wiring Examples
14 CHG-75 PN 51315:A 08/01/01
chg7bb26.cdr
Optional Voltmeter/Ammeter Installation
2.6 Optional Voltmeter/Ammeter Installation
An ammeter (AM-1) or voltmeter (VM-1) can be installed for use with the CHG-75 charger. If installing an AM-1 or VM-1, mount the meter to a BB-26 or BB-55F battery box as illustrated below.
Figure 2.7 Mounting AM-1 or VM-1 on BB-55F Battery Box
Installation and Configuration
metertobb-55f.cdr
VM-1 Voltmeter Connections
- the VM-1 can be installed on the CHG-75 to provide a visual indication of the battery/charger voltage. When the battery is disconnected, the voltmeter measures charger voltage only. The VM-1 can mount to a BB-26 or BB-55F battery box. To connect the VM-1 to the CHG-75:
Connect the VM-1 positive lead to TB2 Out (+)
Connect the VM-1 negative lead to TB2 Out (-)
Mount the VM-1 into a mounting slot on the front of the battery box
AM-1 Ammeter Connections
- the AM-1 can be installed on the CHG-75 to provide a visual indication of the charger current. The AM-1 can mount to a BB-26 or BB-55F battery box. To connect the AM-1 to the CHG-75:
Cut jumper JP5 on the CHG-75
Connect the AM-1 harness to connector J4 on the CHG-75. Be sure to observe polarity
Mount the AM-1 into a mounting slot on the front of the battery box
- AM-1
AM-1 ENABLE
ENABLE AC DELAY
JP4
16 HR DELAY
TB4
chg75amvm.cd
J1 J2
NC NO C
JP5
F2
F3
J4
-
+
AM-1
TB2
15
+
-
BATT
15
-
+
OUT TO FAC P
JP2
GND FLT DISABLE
J3
+ AM-1
+ VM-1
- VM-1
+ Out
- Out
AM-1
VM-1
To Load/FACP
Figure 2.8 Wiring AM-1 or VM-1 to CHG-75
CHG-75 PN 51315:A 08/01/01 15
Installation and Configuration
2.7 Connecting AC Power to the Charger
Connecting AC Power to the Charger
CAUTION!
any jumpers or servicing the charger.
Disconnect all sources of power before making any connections, cutting
AC power connections are made to TB1 of the CHG-75 battery charger. Primary power source for the CHG-75 is 120 VAC, 60 HZ, 2.05 amps or, if JP1 is cut, 220/240 VAC, 50 Hz, 1.14 amps. Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB1. As per National Electric Code, use 14 AWG (1.6 mm O.D.) or heavier gauge wire with 600 volt insulation.
The following figure illustrates the steps for connecting the charger to the main AC power source.
HOT
NEUT
EARTH
TB1
HOT
NEUT
EARTH
TB1
Plastic insulating cover
Step 1:
Remove the plastic insulating
cover from TB1.
NEUTRAL (line in)
EARTH (ground)
HOT
NEUT
EARTH
TB1
HOT
NEUT
EARTH
TB1
EARTH (ground)
Step 2:
Connect the Earth ground line
to TB1 Terminal 3.
HOT (line in)
NEUTRAL (line in)
EARTH (ground)
Step 3:
Connect the Primary
Neutral line to TB1 Terminal 2
Figure 2.9 Connecting AC Power
Step 4:
Connect the Primary Hot line to TB1 Terminal 1. Check all connections, then replace the plastic insulating cover.
16 CHG-75 PN 51315:A 08/01/01
Connecting Batteries to the Charger
2.8 Connecting Batteries to the Charger
Batteries ranging from 25 AH to 75 AH can be connected to the charger. This section provides illustrations and instructions for connecting two or four batteries.
2.8.1 Connecting Two Batteries
The following steps must be followed when connecting two batteries to the charger:
1. Remove all power sources to the charger
2. Connect the battery negative (-) cable to TB2, Terminal 2 on the charger (labeled BATT -) as illustrated in Figure 2.10
3. Connect the battery positive cable to TB2, Terminal 1 on the charger (labeled BATT +) as illustrated in Figure 2.10
Do not connect the Battery Interconnect Cable at this time.
4. section titled "Powering the Charger" on page 25
JP1
CUT F OR 240VAC
F1
AC Power
Hot
Neutral
Earth
TB1
HOT
NEUT
EARTH
+
-
25 AH 12V
CHG-75
Battery
Interconnect
Cable *
TENS
0
5
11
7
10
8
14
1
12
13
6
15
2
3
9
4
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
ONES
-
25 AH 12V
Installation and Configuration
Proceed to the
AM-1 ENABLE
J4
JP5
AM-1
F2
TB2
BAT
+
15 15
BAT
J1 J2
-
OUT
+
OUT
-
F3
JP2
GND FLT DISABL E
J3
JP4
SW1
TB3
A- B- A+ B+
Out -
ADDRESS
ON OFF
Out +
ENABLE
JP3
AC DELAY
16 HR DELAY
TB4
NC NO C
Battery -
Battery +
+
chg7mp2f.cdr
TB1
+
-
POWER LIMITED
+24R COMMON +24 COMMON
BAT + BAT -
EARTH GND AC NEUTRAL AC HOT
TB2
Battery
F1CB1
Terminal
P2
P3
JP5
P4
R27
Power Supply
JP1
*Do not connect the Battery Interconnect Cable at this time.
!
Refer to "Powering the Charger" on page 25.
P7
MPS-24AE PCC R EV ___
MPS-24AP CC R EV __ _
MPS24A.
Figure 2.10 Connecting Two 25 AH Batteries
P5
JP2
CHG-75 PN 51315:A 08/01/01 17
Installation and Configuration
+
BAT + BAT -
TB1
EARTH GND AC NEUTRAL AC HOT
TB2
Battery
Terminal
Power Supply
Connecting Batteries to the Charger
2.8.2 Connecting Four Batteries
The following steps must be followed when connecting four batteries to the charger:
1. Remove all power sources to the charger
2. Connect the batteries in pairs by connecting the battery negative terminals and the battery positive terminals as illustrated in Figure 2.11
3. Connect the battery negative (-) cable to TB2, Terminal 2 on the charger (labeled BATT -) as illustrated in Figure 2.11
4. Connect the battery positive cable to TB2, Terminal 1 on the charger (labeled BATT +) as illustrated in Figure 2.11
Do not connect the Battery Interconnect Cable at this time.
5. section titled "Powering the Charger" on page 25
JP1
CUT FOR 240VAC
F1
AC Power
Hot
Neutral
Earth
TB1
HOT
EARTHNEUT
-
POWER LIMITED
+24R COMMON +24 COMMON
P2
P5
F1CB1
P3
JP5
P4
R27
-
25 AH 12V
-
25 AH 12V
CHG-75
+
+
TENS
0
5
11
7
10
8
14
1
12
13
6
15
2
3
9
4
SW1
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
ONES
TB3
A- B- A+ B+
Out -
Battery
Interconnect
Cable*
Battery
Interconnect
Cable*
Proceed to the
ENABLE
JP3
AC DELAY
JP4
16 HR DELAY
ADDRESS
ON OFF
TB4
NC NO C
Out +
-
25 AH 12V
-
25 AH 12V
AM-1 ENABLE
JP5
AM-1
F2
15 15
F3
JP2
GND FLT DISABLE
J1 J2
J3
Battery -
+
+
J4
TB2
BAT
+
BAT
-
OUT
+
OUT
-
Battery +
chg7m42f.cdr
JP2
JP1
*Do not connect the Battery Interconnect Cable at this time.
!
Refer to "Powering the Charger" on page 25
P7
MPS-24AEPCC REV ___
MPS-24APCC REV ___
MPS24A.
Figure 2.11 Connecting Four Batteries to the Charger
18 CHG-75 PN 51315:A 08/01/01
Connecting the Charger to a Load
2.9 Connecting the Charger to a Load
This section provides three applications for connecting a charger to a load. While connecting a charger to a load, observe the following precautions:
Make sure all power has been removed from the charger and the load
Observe polarity when making connections.
2.9.1 Connecting the Charger to a Single Load
The CHG-75 is designed to provide additional charging capability to an existing FACP power supply. The charger can be connected to a single power supply as illustrated in Figure 2.12.
To connect the charger to a single load:
1. Connect the Battery (+) and Battery (-) terminals of the power supply to the CHG-75 Output Circuit TB2, Terminal 3 (Out +) and Terminal 4 (Out -) as illustrated in Figure 2.12
2. Connect the batteries to the CHG-75 (refer to Figure 2.10 or Figure 2.11)
CHG-75
Installation and Configuration
AC Power
Hot
Neutral
Earth
TB1
JP1
CUT FO R 240VAC
F1
TB1
HOT
EARTHNEUT
EARTH GND AC NEUTRAL AC HOT
Battery +
BAT + BAT -
TB2
Battery
F1CB1
Terminal
Power Supply
Battery -
POWER L IMITED
+24R COMMON +24 COMMON
JP5
AM-1 ENABLE
JP4
J1 J2
JP5
J4
AM-1
F2
TB2
BAT
+
15 15
BAT
-
OUT
+
OUT
-
F3
JP2
GND FLT DISABLE
J3
chg7pwrs.cdr
ENABLE
JP3
AC DELAY
TENS
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
SW1
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
ONES
ON OFF
TB3
A- B- A+ B+
ADDRESS
TB4
16 HR DELAY
NC NO C
Out -
Out +
Battery -
Battery +
P2
P5
P3
P4
R27
JP2
JP1
P7
MPS-24AE PCC REV ___
MPS-24AP CC REV ___
MPS24A.
Figure 2.12 Typical Charger Wiring to Single Load
CHG-75 PN 51315:A 08/01/01 19
Installation and Configuration
Connecting the Charger to a Load
2.9.2 Connecting the Charger to an MS-9200
The charger can be connected to an FACP power supply, such as an MS-9200, by disabling the local charger. The MS-9200 charger is disabled by cutting jumper JP1.
WAR NI NG!
FACP main circuit board, which does not allow disabling of the FACP battery charger (no JP1 jumper). System damage will result.
To connect a charger to the MS-9200:
1. Disconnect all power (AC and DC) from the MS-9200 and CHG-75
2. Cut jumper JP1, which is located on the MS-9200 main circuit board, to disable
3. Disconnect the battery ends of the battery cable connected to J2 on the MS-9200.
4. Connect the stripped wire ends to the CHG-75 Output Circuit TB2, Terminal 3
5. Connect the batteries to the charger (refer to Figure 2.10 and Figure 2.11).
24V UNREG 24V NO NRS 24V RST BELL 2 POWER BELL 1 POWER SUPV
+ - + - + -
T B 4
B+ A+ A- B- B+ A+ A- B-
T B 2
MS-9200
T B 1
Do not
attempt to connect the CHG-75 to older versions of the MS-9200
the FACP battery charger
Cut off the battery connectors and strip the ends of the wire.
(Out +) and Terminal 4 (Out -) as illustrated in Figure 2.13.
proper polarity.
ALARM
TROUBLE
NO C NO NC C NO NC C
PC/PRINTER TERM CO MM
T
OUT+ IN+ OUT- IN-
B3T
SHIELD SLC SLC
ACS
1 COMM 2
A B B+ A+ B- A-
T B
B
5
7
T B 6
Be certain to observe
TRAN SFOR MER 1
J17
HIGH VOLTAGE
CAU TION!
TRANSFORMER 2
J19
CAUTION HIGH VOLTAGE
Cut JP1 for this application
J16
SW1
JP4
TB8
J3
JP1
- +
BATTER Y
+
-
JP3
GND FAULT
DISABLE
RS-232
RS-485
J6
PC/PRINTER
TERM. MODE
SW3
SW2
TROUBLE
chg79200.cdr
CHG-75
AC Power
Hot
Neutral
Earth
CUT FO R 240VAC
HOT
EARTHNEUT
JP1
F1
TB1
TENS
0
5
11
7
10
8
14
1
12 13
6
15
2
ADDRESS
3
9
4
SW1
0
11
5
7
10 14 12 13
15
9
ONES
ON OFF 8 1
6
2
3
4
TB3
A- B- A+ B+
Out -
Out +
Battery
Interconnect
-
25 AH 12V
+
Cable*
-
25 AH 12V
+
ENABLE
JP3
AC DELAY
JP4
16 HR DELAY
TB4
NC NO C
Battery -
Battery +
AM-1 ENABLE
JP5
F2
15 15
F3
J1 J2
J4
AM-1
TB2
BAT
+
+
BAT
-
-
OUT
+
+
OUT
-
-
JP2
GND FLT DISABLE
J3
Figure 2.13 CHG-75 Wiring to MS-9200
20 CHG-75 PN 51315:A 08/01/01
Connecting the Charger to a Load
2.9.3 Connecting the Charger to an MS-9600
The charger can be connected to an FACP power supply, such as an MS-9600, by disabling the local charger. The MS-9600 charger is disabled by cutting jumper JP3.
To connect a charger to the MS-9600:
1. Disconnect all power (AC and DC) from the MS-9600 and CHG-75
2. Cut jumper JP3, which is located on the MS-9600 main circuit board, to disable
3. Connect the CHG-75 Output Circuit TB2, Terminal 3 (Out +) to MS-9600
4. Connect the batteries to the charger (refer to Figure 2.10 and Figure 2.11).
Installation and Configuration
the FACP battery charger
battery connector TB2 (+) terminal and Terminal 4 (Out -) to MS-9600 battery connector TB2 (-) terminal as illustrated in Figure 2.13.
Be certain to observe
proper polarity.
Cut JP3 for this application
TB3
JP3
CUT TO DISABLE LOCAL CHARG ER
JP10
JP2
1
DISABLE GND FLT
2
ABC
4
5
JKL MNO
GHI
J17
J16
78 9
TUV WXY
PRS
0
*
QZ
RECALL
HOT
CB1
MS-9600
4XTM OPT BD
3
JP8
DEF
6
CUT TO MONITOR 4XTM
JP6
LCD D ISPLAY
#
TB1
-/.
NEUT EARTH
TB4
JP11
st
1
EVENT
JP7
CLR
ESC
J6
MODE
TB2
BATTERY
+-
+
AC Power
TB5
-
JP6
ENTER
KEYPAD I/F
Hot
Neutral
Earth
AC POWER
FIRE ALARM
SUPERVISORY
TROUBL E
J2
OPT DACT
JP1
CUT F OR 240VAC
F1
HOT
NEUT
EARTH
ACK/STEP
J8
TB1
JP5
MAINTENANCE
SILENCED
DISABLED
BATTERY
GROUND
SILENCE
DRILL
HOLD 2 SEC
RESET
TB6 TB7
JP4
1 2 3
J7
CHG-75
-
75 AH 12V
Battery
Interconnect
+
Cable*
J12
SECURITY O PT BD
TENS
0
5
11
7
10
8
14
1
12
13
6
15
2
3
9
4
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
ONES
-
75 AH 12V
OPT SLC
Out -
TB8
J3
SW1
TB3
A- B- A+ B+
+
ADDRESS
ON OFF
Out +
JP3
chg79600.cdr
16 HR DELAY
TB4
NC NO C
AM-1 ENABLE
ENABLE AC DELAY
JP4
J1 J2
Battery -
JP5
AM-1
F2
15 15
F3
JP2
GND FLT DISABL E
J3
Battery +
J4
TB2
BAT
+
+
BAT
-
-
OUT
+
+
OUT
-
-
Figure 2.14 CHG-75 Wiring to MS-9600
CHG-75 PN 51315:A 08/01/01 21
Installation and Configuration
AC Power
EARTH GND AC NEUTRAL AC HOT
TB1
Connecting the Charger to a Load
2.9.4 Connecting the Charger to Multiple Loads
The CHG-75 charger can be connected to multiple loads, such as a main power supply, auxiliary power supply, auxiliary devices, etc., as illustrated in Figure 2.15. To connect the charger to multiple loads:
1. Connect the Battery + and Battery - terminals of an optional external device to the charger Output Circuit TB2, Terminal 3 (Out +) and Terminal 4 (Out -)
2. Connect the Battery + and Battery - terminals of the power supply to the charger Battery Circuit TB2, Terminal 1 (Battery +) and Terminal 2 (Battery -)
3. Connect the batteries to the same charger Battery Circuit described in step 2, TB2, Terminal 1 (Battery +) and Terminal 2 (Battery -)
CHG-75
Hot
Neutral
Earth
+
BAT + BAT -
TB2
Battery
Terminal
F1CB1
CUT FO R 240VAC
F1
HOT
EARTHNEUT
JP1
TB1
-
JP5
Battery -
Battery +
POWER LIMITED
+2 4R C O M MO N + 2 4 C OM MO N
P3
TENS
0
5
11
7
10
8
14
1
12 13
6
15
2
3
9
4
0
5
11
7
10
14
12
13
15
2
3
9
4
ONES
ADDRESS
SW 1
ON OFF
8
1
6
TB3
A- B- A+ B+
To Auxiliary Devices
P2
P5
P4
R27
chg7pwrm.cdr
ENABLE
JP3
AC DELAY
16 HR DELAY
TB4
NC NO C
Battery -
Battery +
JP4
AM-1 ENABLE
JP5
F2
15 15
F3
J1 J2
Out -
Out +
J4
AM-1
TB2
JP2
GND FLT DISABLE
J3
Battery -
Battery +
BAT
+
BAT
-
OUT
+
OUT
-
Power Supply
JP2
JP1
P7
MPS-24AE PCC R EV ___
MPS-24AP CC REV ___
MPS24A.
Figure 2.15 Typical Wiring of Charger to Multiple Loads
22 CHG-75 PN 51315:A 08/01/01
Trouble Monitoring
2.10 Trouble Monitoring
The CHG-75 charger has three connectors (J1, J2 & J3), a Form-C trouble relay (TB4) and an SLC (Signal Line Circuit - TB3) which can be used for trouble monitoring by an FACP. These connections are optional and, therefore, are not required for the proper operation of the charger. They are, however, necessary when the FACP is required to indicate a trouble condition for the charger. One or more of the following may be used to transmit the trouble condition to the FACP:
J1
- Trouble IN (2-pin connector) Open collector input allows connection to trouble bus from other devices which are compatible with open collector inputs. This connection allows daisy chaining of trouble signals through the charger without affecting the charger operation or activating the local trouble relay.
J2
- Trouble OUT (2-pin connector) Open collector output allows connection of trouble bus to other devices which are compatible with open collector outputs. This connection allows daisy chaining of trouble signals from the Trouble IN connector. A trouble on the charger will also be transmitted from this connector
J3
- Trouble IN Master (2-pin connector) This input can receive trouble signals from another device, such as a spare zone, and will in turn activate the local trouble relay. This input is compatible with an open collector output from another device
Installation and Configuration
TB4
Figure 2.16 on page 24 provides an illustration of CHG-75 connector locations and terminal connections.
- Trouble Relay This fail-safe Form-C Trouble relay will activate when the charger detects a local trouble, such as AC fail, ground fault (if enabled), low battery, etc., or when a trouble signal is received at the Trouble IN Master (J7)
TB3
- SLC Connector A built-in monitor module will create an open charger trouble occurs except for AC fail. If AC is lost, the monitor module will create a short delay is enabled. By addressing and connecting the charger to an addressable control panel’s SLC, the FACP can be programmed to monitor this built-in monitor module for activation. Refer to the SLC manual for information on wiring an SLC loop
condition which will be seen by the FACP immediately even if AC
circuit condition when any local
CHG-75 PN 51315:A 08/01/01 23
Installation and Configuration
JP1
CUT FOR 240VAC
F1
TB1
HOT
NEUT
EARTH
SLC In From Addressable FACP or Previous Addressable Device
Refer to SLC manual for information on wiring an SLC loop.
*Relay is fail-safe and contact designations are shown with power applied and no troubles on the charger.
To Trouble Input on main power supply, FACP or charger
INOUT
Trouble Monitoring
Trouble Monitoring Connections
The following figure illustrates the various connections which can be made to allow trouble monitoring of the CHG-75. Any one or more of these connections can be made, depending on the capabilities of the host FACP.
CHG-75
AM-1 ENABLE
J4
JP5
AM-1
F2
TB2
BAT
+
15
BAT
-
OUT
+
15
OUT
-
F3
JP2
GND FLT DISABLE
J3
chg75trb.cdr
Master Trouble IN
Open Collector Trouble OUT (from CHG-75)
TENS
11
10
14
12
13
15
9
11
10
14
12
13
15
9
SLC Out to Next Addressable Device
Trouble Relay*
Open Collector Trouble IN
IN
OUT IN
0
4
0
4
ONES
ENABLE
JP3
AC DELAY
5
7
8
1
6
2
3
5
7
8
1
6
2
3
-
+
NC
NO
SW1
TB3
-
+
ADDRESS
ON OFF
A- B- A+ B+
16 HR DELAY
TB4
NC NO C
JP4
J1 J2
C
OUT
FACP, Power Supply or Charger
Figure 2.16 Trouble and Form-C Relay Connections
FACP, Power Supply or Charger
FACP, Power Supply or Charger
24 CHG-75 PN 51315:A 08/01/01
Powering the Charger
Operation
SECTION 3
Operation
3.1 Powering the Charger
WAR NI NG
Follow the installation instructions described in the section titled "Installation and Configuration" on page 10
Verify the proper polarity on all connections between the charger and the batteries, loads and optional meters
Make sure there are no short circuits between leads and between battery terminals. Also, check to make certain that jumpers which have been cut are not shorting together or to other components on the circuit board
Make sure the Battery Interconnect Cable(s) is not
To power the charger, perform the following steps:
1. Apply AC power to the charger. The Trouble LED should turn on
2. Connect the batteries to the charger
3. Connect the Battery Interconnect Cable(s). The Trouble LED should turn off
4. Connect the charger to the load (such as a power supply, amplifier, FACP with local charger disabled, etc.)
3.2 LED Status Indicators
! Prior to applying power to the charger, perform the following check list:
connected
The CHG-75 provides six LED status indicators as illustrated in Figure 3.1.
SLC - green LED indicates SLC communication with FACP AC POWER - green LED indicates AC power present GND FLT - yellow LED indicates a ground fault on the charger TBL - yellow LED indicates a local charger trouble CHGING - yellow LED indicates batteries are being charged LOW BAT - yellow LED indicates a low battery condition
AM-1 EN ABLE
JP3
ENABLE AC DELAY
JP5
F2
TENS
0
5
11
7
10
15
15
9
4
0
11
9
4
ONES
8
1
6
2
3
5
7
8
1
6
2
3
ADDRESS
SW1
ON OFF
TB3
14 12 13
10
14
12
13
16 HR DELAY
TB4
JP4
15
15
F3
J1 J2
JP2
J4
AM-1
TB2
GND FLT DISABLE
J3
BAT
+
BAT
-
OUT
+
OUT
-
A- B- A+ B+
NC NO C
chg75led.cdr
Figure 3.1 LED Status Indicators
CHG-75 PN 51315:A 08/01/01 25
Operation
3.3 Normal Operation
While charging the batteries, the CHGING (charging) LED will turn on. When batteries are fully charged, the charger maintains a float charge of 27.6 VDC. The SLC LED and AC LED are the only other LEDs that should be on during normal operation if SLC communication is programmed at the FACP and the SLC enable switch SW1 is On.
Normal Operation
LED
SLC (if programmed and enabled)
AC Power On
Trouble
Ground Fault
Low Battery
Charging
= LED On (Note that Charge LED may blink on momentarily when switching to
Normal Operation
AC Fail
AC Fail
(with AC loss reporting delay enabled
Battery Fault
(low battery)
Disconnected Battery
Ground Fault
Short Circuit
✓✓✓✓ ✓ ✓✓ ✓
✓✓✓ ✓ ✓✓✓
✓✓
trickle charge. LED will extinguish if battery is disconnected)
Table 3.1 LED Status Indicators
System Trouble
(with Master Trouble In Connected
26 CHG-75 PN 51315:A 08/01/01
Index
A AC
LED 9
AC loss
reporting delay 7
AC loss reporting delay 11
jumper selection 10 time selection 11
AC power
see also primary power 16
addressing 11
example 11
addressing switches
SW2 & SW3 11
AM-1 ammeter
see also ammeter installation 15
ammeter 7
enable 12
installation 10, 15 B battery 7, 8
charger 8
connecting four batteries 18
connecting two batteries 17
connection to charger 17
interconnect cable 17, 18
lead-acid 7
output connector 8
replacement 9 battery cabinet 7 battery capacity 8 battery charger
AH rating 7
capacity 7
compatibility 7
FACP compatibility 7 battery protection
also see fuses 7 BB-26
see also battery cabinet 7 BB-26 battery box 13 BB-55F
see also battery cabinet 7 BB-55F battery box 13 C capacity 7 charge current 8 charge voltage 8 charger 8
connection to load 19 connection to MS-9200 20 connection to MS-9600 21 connection to multiple loads 22 connection to single load 19
charging
LED 9
communication enable
SLC 11 compatibility 7 components 10 configuration 10, 11 connections 10 contact rating 8 current
consumption 8 current consumption 8 D description 7 E equipment protection
also see fuses 7 F FACP
battery charger compatibility 7
mounting charger 12 fail-safe relay
also see trouble relay 7 features 7 fuse 8, 9 G ground fault
LED 9 ground fault detection 7, 10, 12
disabling 7
enable/disable 12 I illustration
charger 10 indicators
see also LED 9 inspection 9 installation 9, 10 J jumper
selections 7 jumpers 10 L LED
CHG-75 PN 51315:A 08/01/01 27
AC 9 AC power 25 charging 9, 25 ground fault 9, 25 low battery 9, 25 normal operation 26 see also indicators 9 SLC communication 9, 25 status indicators 25, 26 trouble 9, 25
low battery
LED 9 M maintenance
charger 9 monitor module 11 monitoring trouble 23 mounting 7, 12
in BB-26 battery box 13
in BB55F battery box 13
in FACP 12 MS-9200
connecting charger 20
connection precaution 20
disabling onboard charger 20 MS-9600
connection to charger 21
onboard charger disable 21 N normal operation 26 O operation 25, 26 P polarity 10 power application 25 powering the charger 25 power-limited wiring
BB-26 14
BB-55F 14
FACP 14 power-limited wiring requirements 14 precautions 10
battery 10
charger 10 primary current 8, 16 primary power 8
connections 16
jumper selection 10
voltage selection 16
wire size 8
primary voltage 7
selection jumper 8
protection
see also fuse 9 R relay 10
contact rating 7
trouble 7 replacing battery 9 S secondary power
see also battery 8 Signal Line Circuit
see also SLC 8 SLC 23
addressing 11
addressing switches 10
communication enable 11
communication enable/disable 10
see also Signal Line Circuit 8
specifications 8 SLC communication
enable/disable 11
LED 9 specifications 8 supervision 7
AC voltage 7
battery 7
charger 7 SW2
SLC communication enable/disable 11 SW2 & SW3
addressing switches 11 switches 10 T trouble
LED 9
monitoring 11, 23 trouble connectors 8, 23 trouble monitor
connections 24
via connectors J2 & J3 23
via SLC 23
via trouble relay 23 trouble relay 7, 8, 23
contact rating 8 troubleshooting 9
28 CHG-75 PN 51315:A 08/01/01
U UL power-limited wiring requirements 14 V VM-1 voltmeter
see also voltmeter installation 15 voltmeter 7 voltmeter installation 15
CHG-75 PN 51315:A 08/01/01 29
Notes
30 CHG-75 PN 51315:A 08/01/01
Limited Warranty
The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of original purchase by the manufacturer's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired, or serviced by anyone other than the manufacturer or its authorized distributors, or if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its products. The manufacturer does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
LimWarLg.p65 01/10/2000
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...