CAUTION: The door of the pull station may detach from
the backplate and cannot be re-attached if backplate is
installed on an SB-10 surface backbox or an electrical box.
To re-attach the door----
Hold door (A) to the rear of the backplate (B) as shown in
the figure below. Bring door forward (1) to align pins with
holes. Slide door down (2) onto backplate. Close door
partially to lock into place.
BG12-Ffrontsak.cdr
BG-12SL Single Action Pull Station
Document: 51860 Revision: A ECN: 01-500 09/14/01
Patented, U.S. Patent No. Des. 428,351 Other Pantents Pending
Description
The BG-12SL Pull Station is a non-coded manual pull
station which provides a Fire Alarm Control Panel (FACP)
with a single alarm initiating input signal.
HOLE
A
PIN
B
2
1
BG12-doorattach.cdr
Operation
To activate the pull station, simply pull down the handle. The
word ‘ACTIVATED’ appears after the handle is pulled
down. This will remain until the pull station is reset.
The pull station is a single-action model equipped with a key
lock/reset. Pigtail wires are provided for connection to the
FACP Initiating Device Circuit.
It is UL listed and meets the ADA requirement of a 5-lb.
maximum pull force to activate. Operating instructions are
molded into the handle along with Braille text.
Switch Contact Rating
All Switch contacts are rated for 0.25 A at 30 volts (AC or
DC).
Installation
The pull station can be surface mounted to a Surface
Backbox (SB-10) or semi-flush mount to a standard doublegang, or 4-inch (10.16cm) square electrical box. An optional
Trim Ring (BG-TR) may be used when semi-flush mounting
the unit.
BG12-Factivsak.cdr
This pull station includes one Single Pole, Single Throw
(SPST) Normally Open (N/O) switch which closes upon
activation of the pull station.
Resetting the Pull Station
1. Insert the key into the lock and rotate 1/4 turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
Closing the door automatically resets the switch to the ‘Nor-
Note:
mal’ position. Opening the door will not activate or deactivate the
alarm switch.
Wiring Instructions for BG-12SL
Prior to wiring the pull station, pull all necessary wiring
through a mounted backbox and the optional trim ring.
Connect the field wiring from the FACP’s IDC, or previous
device on the IDC, to the pull station’s pigtail wires.
Caution
Install the pull station in accordance with the supplied
instructions, applicable NFPA standards, national and local
Fire and Electrical codes and the requirements of the
Authority Having Jurisdiction (AHJ). Conduct regular
testing of the devices using appropriate NFPA standards.
Fire•lite Alarms is not responsible for devices that have not
been properly installed, tested and maintained.
ADA Compliance
For ADA compliance, if the clear floor space only allows
forward approach to an object, the maximum forward reach
height allowed is 48-inches (121.92cm). If the clear floor
space allows parallel approach by a person in a wheelchair,
the maximum side reach allowed is 54-inches (137.16cm).
1. Connect the positive (+) FACP’s IDC wire to a red
pigtail wire and the negative (–) FACP’s IDC wire to
a black pigtail wire.
2. Connect the positive (+) wire going to the next
device, or an ELR, to the remaining red pigtail wire
and the negative (–) wire going to the next device, or
an ELR, to the remaining black pigtail wire.
3. Maintain consistent polarity with all connections
throughout the IDC.
RED
Positive
BLACK
Negative
Document: 51860 Revision: A ECN: 01-500 09/14/01
BG12-wiring3.cdr