Supplied By www.heating spares.co Tel. 0161 620 6677
DOMIcondens F 28
196
85
330
115200
400
3540S920
cod. 3540S920 — 05/2009 (Rev. 00)
INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE
700
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
EN
1. GENERAL INSTRUCTIONS
•Carefully read the instructions contained in this instruction booklet.
•After boiler installation, inform the use r reg ardi ng its op erat ion an d give him this man ual , which is
an integral and essential part of the product and must be kept with care for future reference.
•Installation and maintenance mu st be carr ied out by p rofessio nally qua lified p erson nel, accord ing
to current regulations and the manufacturer's instructions. Do not carry out any operation on the
sealed control parts.
•Incorrect installation or inadequa te maintenance ca n result in damag e or injury. The Manufacturer
declines any liability for damage du e to errors in installation and use or failu re to follow the instructions.
•Before carrying out any cleaning or maintenance operation, disconnect the unit from the power
supply using the system switch and/or the special cut-off devices.
•In case of a fault and/or poor operation, de activate the unit and do not attempt to repair it or directl y
intervene. Contact professionally qualified personnel. Repair/replacement of the products must
only be carried out by professionally qualified using original spare parts. Failure to comply with the
above could affect the safety of the unit.
•This unit must only be used for its intended purpose. Any other use is considered improper and
therefore dangerous.
•The packing materials are potentially hazar dous and must not be lef t withi n the reach of chi ldre n.
•The images given in this ma nual are a simpli fi ed repr ese ntat ion o f the produc t. I n this repres entation there may be slight and insignificant differences with respect to the product supplied.
2. OPERATING INSTRUCTIONS
2.1 Introduction
Dear Customer,
DOMIcondens F 28 is a high-efficiency sealed chamber condensing heat generator for
heating and hot water production running on natural gas or LPG, and equipped with a
microprocessor control system.
2.2 Control panel
15
1
10
11
12
9
eco
comfort
75
16
reset
DOMIcondens F 28
Boiler lighting and shutdown
Press the on/off button (detail 7 - fig.1) for 5 seconds.
fig. 2 - Turning the boiler off
When the boiler is turned off, the PCB is still powered. Domestic hot water and heating
are disabled. The antifreeze system remains activated. To relight the boiler, press the
on/off button (detail 7 fig. 1) again for 5 seconds.
fig. 3
The boiler will be immediately ready to operate whenever domestic hot water is drawn
or in case of a room thermostat demand.
The antifreeze system does not work when the power and/or gas to the unit are
turned off. To avoid damage caused by freezing during long idl e periods in win-
B
ter, it is advisable to drain all water from the boiler, DHW circuit and system; or
drain just the DHW circuit and add a suitable antifreeze to the heating system,
complying with that prescribed in sec. 3.3.
2.4 Adjustments
Summer/Winter Switchover
Press the summer/winter button (detail 6 - fig.1) for 2 seconds.
The display activates the Summer symbol (detail 10 - fig. 1): the boiler will only deliver
domestic hot water. The antifreeze system remains activated.
To deactivate the Summer mode, press the summer/winter button (detail 6 - fig. 1)
again for 2 seconds.
Heating temperature setting
Use the heating buttons (detail 3 - fig.1) to adjust the temperature from a min. of 30°C
to a max. of 85°C; it is advisable not to operate the boiler below 45°C.
36
Key
1 =Domestic hot water temperature setting
3 =Heating system temperature setting
5 =Display
6 =Summer/Winter mode selection - Reset button
7 =Unit On/Off - Eco/Comfort mode selection button
9 =DHW mode
10 =Summer mode
11 =Temperature or faults
12 =Eco (Economy) mode
13 =Heating
15 =Burner On and actual power
16 =Clock prearrangement
Indication during operation
Heating
A heating demand (generated by the Room Thermostat or Remote Timer Control) is indicated by flashing of the hot air above the radiator on the display.
Domestic hot water (DHW)
A DHW demand (generated by drawing domestic hot water) is indicated by flashing of
the hot water under the tap on the display.
2.3 Lighting and turning off
Connection to the power supply
•During the first 5 seconds the display shows the card software version.
•Open the gas cock ahead of the boiler.
•The boiler is now ready to operate automatically whenever hot water is drawn or in
case of a room thermostat demand.
13
fig. 1 - Control panel
fig. 4
Hot water temperature adjustment
Use the DHW buttons (detail 1 - fig. 1) to adjust the temperature from a min. of 40°C to
a max. of 55°C.
fig. 5
Room temperature adjustment (with optional room thermostat)
Using the room thermostat, set the temperature required in the rooms. If the room thermostat is not installed, the boiler will keep the system at the set system deliver y setpo int
temperature.
Room temperature adjustment (with optional remote timer control)
Using the remote timer control, set the required temperature in the rooms. The boiler will
adjust the system water according to the required room temperature. For operation with
remote timer control, please refer to the relevant instruction manual.
ECO/COMFORT selection
The unit has a function that ensures a high domestic hot wat er deliver y sp eed a nd ma ximum comfort for the user. When the device is activated (COMFORT mode), the water
contained in the boiler is kept hot, therefore ensuring immediate availability of hot water
on opening the tap, without waiting times.
The device can be deactivated by the user (ECO mode) by pressing the eco/comfort
button (detail 7 - fig. 1) with the boiler in standby mode. In ECO mode the display activates the ECO symbol (detail 12 - fig. 1). To activate COMFORT mode, press the eco/comfort button (detail 7 - fig. 1) again.
2
EN
cod. 3540S920 - 05/2009 (Rev. 00)
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
DOMIcondens F 28
Adjustments from Remote Timer Control
If the Remote Timer Control (optional) is connected to the boiler, the above ad-
A
justments are managed according to that given in table 1.
Table. 1
Heating temperature setting
Hot water temperature adjustment
Summer/Winter Switchover
Eco/Comfort selection
Water system pressure regulation
The filling pressure read on the boiler water gauge with the system cold must be approx
1.0 bar. If the system pressure falls to values below minimum, the boiler stops and fault
F37 is displayed.
3. INSTALLATION
3.1 General Instructions
This unit must only be used for its intended purpose. This unit is designed to
heat water to a temperature below boiling point and must be connected to a
B
heating system and/or a water supply system for domestic use, compatible wit h
its performance, characteristics and its heating capacity. Any other use is
deemed improper.
BOILER INSTALLATION MUST ONLY BE CARRIED OUT BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL
MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF THE
TECHNICAL STANDARDS (BS), ANY LOCAL REGULATIONS AND THE RULES OF
PROPER WORKMANSHIP.
Incorrect installation can cause damage or injury for which the manufacturer declines
any responsibility.
Installation of this unit must be carried out in strict compliance with the present
instructions and the following regulations applicable in Great Britain.
Gas Safety Regulations (Installations & Use).
Local Building Regulations..
The Building Regulations (Part L).
The Buildings Standards (Scotland - Consolidated) Regulations. British Standards
Codes of Practice (BSI):
Adjustment can be made from the Remote Timer Control menu and the
boiler control panel.
Adjustment can be made from the Remote Timer Control menu and the
boiler control panel.
Summer mode has priority over a possible Remote Timer Control heating demand.
Adjustment can only be made from the boiler control panel.
3.2 Place of installation
The combustion circuit is sealed with respect to the place of installation room, therefore
the unit can be installed in any room. However, the place of installation must be adequately ventilated to prevent the creation of dangerous conditi ons in case of even small
gas leaks. This safety regulation is laid down by EEC Directive no. 90/396 for all gas
units, including those with sealed chamber.
The unit is suitable for operation in a partially prot ected place in conf ormity wit h EN 297/
A6, with minimum temperature -5°C. If equipped with the special antifreeze kit, it can be
used with minimum temperatures to -15°C. The boiler must be installed is a protected
place, e.g. under the slope of a roof, inside a balcony or in a sheltered recess.
The place of installation must in any case be free of dust, flammable materials or objects
or corrosive gases.
The boiler is arranged for wall mounting and comes standard with a hooking bracket. The
wall fixing must ensure a stable and effective support for the generator.
If the unit is enclosed in a cabinet or mounted alongside, a space must be pro-
A
vided for removing the casing and for normal maintenance operations
3.3 Water connections
Important
The heating capacity of the unit must be previously established by calculating the building's heat requirement according to the current regulations. To ensure proper operation
and long boiler life, the plumbing system must be adequatel y sized and complete with all
the necessary accessories, including a room thermostat, a thermostattable valve (TRV)
etc. The system delivery and return pipes must have a diameter of at least 22 mm for the
first 3 m of length from the unit.
If the system delivery and return pipes follow a path where air pockets can fo rm in certain
places, it is advisable to install vent valves at these points. Also, type "A" drain cocks
must be installed at the lowest points in the system to allow complete emptying.
An automatic bypass with flow rate of at least 6 l/min. must be installed (connected as far away as possible from the boiler) if radiators with thermostatic
B
valves have been connected.
Hot water
Gas
B.S.
5440Detail 1 Flues
B.S.
5440Detail 2 Air supply and ventilation
B.S.
5449.........Systems for hot water production with forced circulation
B.S.
6798.........Installation of gas-fired boilers for hot water
B.S.
6891.........Gas systems
B.S.
7671.........IEE wiring system regulations
B.S.
4814.........Specifications for expansion ta n ks
B.S.
5482.........LPG systems
B.S.
7593.........Water treatment in central heating systems for domestic hot w a ter pr oduction
B.S.
5546.........Installation of systems for domestic hot water production
Model Water By-Laws
B.S.
5955-8.........Installation of plastic pipe s
For Northern Ireland, observe the current applicable regulations.
Safe handling of materials
Pay attention when handling the boiler insulation panels because the material they are
made of could irritate the skin. No part of the boiler contains asbestos, mercury or CFC's.
Advice for transport and handling
For lifting and transport always take suitable safety precautions: keep your back straig ht,
bend knees, do not turn your body, move feet, avoid bending forward or sideways and
keep the load as close as possible to your body.
If possible, use a trolley or other suitable means to carry the boiler.
Grip the boiler firmly and, before lifting it, try and find the point where t he load is concen-
trated in order to establish the centre of gravity and suitably reposition yourself.
Cold water mains
Additional expansion
vessel C.H. (if required)
Automatic
Bypass
fig. 6 - Automatic bypass connection
The temperature drop between the delivery manifold and the return to the boiler should
not exceed 20°C.
Do not use the water system pipes to earth electrical appliances.
Filling
point C.H.
B
3540S920
cod. 3540S920 - 05/2009 (Rev. 00)
EN
3
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
DOMIcondens F 28
Before installation, carefully wash all the pipes of the heating system to remove any residuals or impurities that could affect proper operation of the unit (as req uired by BS 7593
Building regs Doc L).
Carry out the connections to the unit as indicated in fig. 7.
13
524
6
39 6060
fig. 7 - Water connections
Shutoff valve kit
Make sure to install the shutoff valves (supplied) betwee n the boiler and the heating system, allowing the boiler to be isolated from the system if necessary.
The safety valve outlet must be connected to a copper pip e of 1 5 mm diameter
with continuous fall from the boiler to run off the system water in case of over-
B
pressure in the heating circuit. Otherwise, if the discharge valve cuts in and
floods the room, the boiler manufacturer cannot be held liable. The drain must
be run to the outside of the building to avoid the risk of damage or injury due to
the hot water in case of overpressure in the system.
Make the boiler connection in such a way that its internal pipes are free of stress. If a
non-return valve is installed also on the DHW circuit (if provided for), it is necessary to
install a safety valve between the boiler and the circuit (with the non- return valve at least
3 m from the boiler) or an expansion tank for domestic use.
For installation, follow the instructions contained in the kit.
Replenishing water
It is necessary to provide for replenishing of the water lost by the sealed system. Refer
to standard BS6798 for the methods of filling and replenishing water in sealed systems.
There must not be a direct connection between the central heating system of the boiler
and the water mains. For the use water coming from the water mains and direct pressurisation of the system, refer to the local water management by-laws. This connection,
if provided for, must be interrupted after use.
A connection example (filling loop) is shown in fig. 8.
1Filling point C. H. 15 mm isolation valve
2Temporary flexible connection
3Cold water supply 15 mm isolation valve
4Double check valve
8695
60
3.4 Gas connection
The gas must be connected to the relevant connect ion (see fig.7) in conformity with current standards, with a rigid metal pipe or with a continuous surface flexible s/steel tube,
installing a gas cock between the system and boiler. Make sure all the gas connections
are tight.
3.5 Electrical connections
The unit must be connected to an efficient earthing system in accordance with
current safety standards. Have the efficiency and suitability of the earthing sys-
B
tem checked by professionally qualified personnel; the Manufacturer declines
any liability for damage caused by failure to earth the system.
The boiler is prewired and provided with a "Y" type cable (without plug) for connection to the electric line. The connections to the grid must be made with a permanent connection and equipped with a double-pole switch with contact
opening of at least 3 mm, installing fuses of max. 3A b etween the boiler and the
line. Make sure to respect the polarities (LINE: brown wire / NEUTRAL: blue
wire / EARTH: yellow/green wire) in connections to the electric line.
The user must not replace the unit's power cable. If dama ged, switch off the unit
and have the cable replaced only by professionally qualified personnel. If re-
B
placing the power cable, only use "HAR H05 VV-F" 3x0.75 mm2 cable with
max. outside diameter of 8 mm.
Room thermostat (optional)
IMPORTANT: THE ROOM THERMOSTAT MUST HAVE VOLTAGE-FREE
CONTACTS. CONNECTING 230V TO THE ROOM THERMOSTAT TERMI-
B
NALS WILL PERMANENTLY DAMAGE THE PCB.
When connecting a time control or timer, do not take the power su pply for such
devices from their cutoff contacts. Th ei r po w e r supp l y m us t be ta ke n wi th a d irect connection from the mains or with batteries, depending on the type of device.
Accessing electrical terminal block
Follow the instructions given in fig. 9 to access the electrical connection terminal block.
The layout of the terminals for the various connections is also gi ven in the wirin g diagram
in fig. 21.
4
3
fig. 8 - Filling loop
Reference is made to the provisions contained in the water management by-laws.
Water treatment
If water treatment is necessary, Ferroli recommends the exclusive use of specific products such as Fernox or Sentinel to be applied according to the producer's instructions.
For further information, please contact:
If the boiler is installed in an existing system, any unsuitable additives must be
A
removed by thoroughly cleaning the system. Cleaning of all the systems must
be done in compliance with the requirements of standard B.S. 7593.
In areas with hard water, treatment may be necessary in orde r to prevent scale
A
from forming in the boiler.
Make sure to use the water treatment product in the right concentration, acco rd-
A
ing to the producer's instructions.
2
Sentinel Performance Solutions Ltd
The Heath Business & Technical Park
Runcorn, Cheshire WA7 4QX
Tel.: 0151 424 5351
1
fig. 9 - Accessing the terminal block
3.6 Fume ducts
Important
The unit is “type C” with sealed chamber and forced dra ught; the ai r inlet and fume o utlet
must be connected to one of the following extraction/suction systems. Before installation,
check and carefully observe the above prescriptions. Also, comply with the provisions
concerning the positioning of wall and/or roof termi nals and the mi nimum distance s from
windows, walls, vents, etc.
Expansion
For fume exhaust pipes longer than 1 metre, during installa tion take in a ccount
A
the natural expansion of the materials when the boiler is operating.
To prevent any deformation, leave an expansion space of approx. 2 ÷ 4 mm for
every metre of pipe.
4
EN
cod. 3540S920 - 05/2009 (Rev. 00)
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
DOMIcondens F 28
Baffles
Boiler operation requires fitting the baffles supplied wit h the un it, according t o th at given
in the following tables.
Before inserting the f ume exhaus t pipe, ch eck the pr esence of the right baffle ( when it is to
be used) and that it is correctly positioned. The boilers are fitted standard with the smallest
diameter baffle. To replace the baffle (ref. 1 - fig.10), proceed as indicated in fig.10.
1
fig. 10
Connection with coaxial pipes
Standard coaxial installation
010007X0
80
Rear outlet
Side view
196
Ø100
Drill the wall 10÷20 mm
Between
10 e 60 mm
125
1KWMA56W
more than the
pipe diameter
80
Side outlet
Front view
200200
Ø100
Between
10 e 60 mm
125
Connection with separate pipes
C
52
C
32
C
52
B
22
C
12
fig. 14 - Examples of connection with separate pipes ( = Air / = Fumes)
For the connection of separate ducts, fit the unit with the following starting accessory:
Ø 81Ø 81
Ø 65
Ø 87
Ø 65
fig. 15 - Starting accessory for separate ducts
Before proceeding with installation, check the baffle to be used and make sure the maximum permissible length has not been exceeded, by means of a simple calculation:
1. Completely establish the layout of the system of split flues, including accessories
and outlet terminals.
2. Consult the table 4 and identify the losses in m
ponent, according to the installation position.
3. Check that the sum total of losses is less than or equal to the maximum permissible
length in table 3.
(equivalent metres) of every com-
eq
700
330
700
400
fig. 11 - Standard coaxial installation
Other connections coaxial
C
C
12
C
C
12
C
32
32
32
C
12
fig. 12 - Examples of connection with coaxial pipes ( = Air / = Fumes)
For coaxial connection, fit the unit with one of the following starting a ccessories. For t he
wall hole dimensions, refer to the figure on the cover. Anyhorizontal sections of the f ume
exhaust must be kept slopingslightly towards the outside, to prevent possible condensate from flowing back towards the unit.
125
80
60
100
60
45.6
123.5
100
118
68
Table. 3 - Baffles for separate ducts
Separate ducts
Max. permissible length
Baffle to use
0 ÷ 15 m
15 ÷ 35 m
35 ÷ 55 m
55 m
eq
eq
eq
eq
Ø 45
Ø 50
No baffle
Table. 4 - Accessories
Losses in m
eq
Air
inlet
PIPE
1 m M/F1KWMA83W1.01.62.0
BEND
45° M/F1KWMA65W1.21.8
Fume exhaust
VerticalHorizontal
90° M/F1KWMA01W1.52.0
Ø 80
PIPE SECTION
TERMINAL
with test point1KWMA70W0.30.3
air, wall1KWMA85A2.0fumes, wall with antiwind1KWMA86A-5.0
FLUE
Split air/fumes 80/801KWMA84U-12.0
3.7 Condensate drain connection
The boiler is equipped with an internal trap for condensate draining. Fit the inspection
union A and the flexible tube B, pressing it on about 3 cm. Fill the trap with approx. 0.5 l
of water and connect the flexible tube to the drainage system.
fig. 13 - Starting accessory for coaxial ducts
010014X0010006X0010007X0
Table. 2 - Baffles for coaxial ducts
Coaxial 60/100Coaxial 80/125
Max. permissible length6 m12 m
Reduction factor 90° bend1 m0.5 m
Reduction factor 45° bend0.5 m0.25 m
0 ÷ 2 mØ 450 ÷ 6 mØ 45
Baffle to use
2 ÷ 4 mØ 506 ÷ 12 mno baffle
4 ÷ 6 mno baffle
cod. 3540S920 - 05/2009 (Rev. 00)
fig. 16 - Condensate drain connection
EN
5
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
DOMIcondens F 28
4. SERVICE AND MAINTENANCE
4.1 Adjustments
Gas conversion
The unit can operate on natural gas or LPG and is factory-set for use with one of these
two gases, as clearly shown on the packing and on the dataplate. Whenever a different
gas to that for which the unit is preset has to be used, a conversion kit will be required,
proceeding as follows:
1. Replace the nozzles at the main burner, fitting the nozzles specified in the technical
data table in cap. 5, according to the type of gas used
2. Modify the parameter for the type of gas:
•put the boiler in standby mode
•press the reset button (detail 6 - fig.1) for 10 seconds: the display shows “TS“
flashing
•press the reset button (detail 6 - fig. 1): the display shows “P01“.
•Press the DHW buttons (detail 1 - fig. 1) to set parameter 00 (for operation with
natural gas) or 01 (for operation with LPG).
•Press the reset button (detail 6 - fig. 1) for 10 seconds.
•the boiler will return to standby mode
3. Adjust the minimum and maximum pressures at the burner (ref. relevant section),
setting the values given in the technical data table for the type of gas used
4. Apply the sticker contained in the conversion kit, near the dataplate as proof of the
conversion.
TEST mode activation
Press the heating buttons (detail 3 - fig. 1) at the same time for 5 seconds to activate the
TEST mode. The boiler lights at the maximum heating power set as de scribed in the following section.
The heating and DHW symbols (fig. 17) flash on the display; the heating power will be
displayed alongside.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
D
FHI
E
G
R
S
C
F
BA
L
+
N
B
M
fig. 17 - TEST mode (heating power = 100%)
To deactivate the TEST mode, repeat the activation sequence.
The TEST mode is automatically disabled in any case after 15 minutes.
Adjustment of pressure at burner
Since this unit has flame modulation, there are two fixed pressure values: the minimum
and maximum, which must be those given in the technical data table according to the
type of gas.
•Connect a suitable pressure gauge to pressure point "B" downstream of the gas
valve.
•Disconnect the pressure compensation tube “N”.
•Remove the protection cap “D”.
•Operate the boiler in TEST mode.
•Adjust the maximum pressure by turning the screw “G” clockwise to increase the
pressure and anticlockwise to decrease it.
•Disconnect one of the two fastons "C" from the modureg "F" on the gas valve.
•Adjust the minimum pressure by turning the screw "E" clockwise to increase the
pressure and anticlockwise to decrease it.
•Turn the burner on and off, checking that the minimum pressure remains stable.
•Reconnect the faston "C" detached from the modureg "F" on the gas valve
•Check that the maximum pressure has not changed
•Reconnect the pressure compensation tube “N”.
•Refit the protection cap “D”.
•To end the TEST mode, repeat the activation sequence or wait 15 minutes.
After checking or adjusting the pressure, make sure to seal the adjust-
A
ment screw with paint or a specific seal.
fig. 18 - Gas valve
AUpstream pressure po i nt
BDownstream pressure point
CModureg electrical connection
DProtection cap
EMinimum pressure adjustment
FModureg
GMinimum pressure adjustment
HCompensation tube connection
IGas valve electrical connection
LSealed chamber
MPressure gauge
NCompensation tube
RGas outlet
SGas inlet
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons detail 3 - fig.1 to increase or decrease the power (min. = 00 - max. =
100). Press the reset button within 5 seconds and the max. power will remain that just
set. Exit TEST mode (see sec. 4. 1) .
Lighting power adjustment
To adjust the lighting power, switch the boiler to TEST mode (see sec. 4.1). Press the
DHW buttons (detail 1 - fig. 1) to increase or decrease the power (min. = 00 - max. = 60).
Press the reset button within 5 seconds and the lighting power will remain that just
set. Exit TEST mode (see sec. 4. 1) .
4.2 Startup
Before lighting the boiler
•Check the seal of the gas system.
•Check correct prefilling of the expansion tank.
•Fill the water system and make sure all air contained in the boiler and the system
has been vented.
•Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
•Check correct connection of the electrical system and efficiency of the earthing system.
•Make sure the gas pressure for heating is that required.
•Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
6
EN
cod. 3540S920 - 05/2009 (Rev. 00)
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
DOMIcondens F 28
Checks during operation
•Switch the unit on.
•Check the tightness of the fuel circuit and water systems.
•Check the efficiency of the flue and air/fume ducts while the boiler is working.
•Make sure the water is circulating properly between the boiler and the systems.
•Make sure the gas valve modulates correctly in the heating and domestic hot water
production stages.
•Check correct boiler lighting by performing various tests, turning it on and off with
the room thermostat or remote control.
•Make sure the fuel consumption indicated on the meter matches that given in the
technical data table in cap.5.
•Make sure that with no demand for heating, the burner lights correctly on opening a
hot water tap. Check that in heating mode, on opening a hot water tap, the heating
circulating pump stops and there is regular production of hot water.
•Make sure the parameters are programmed correctly and carry out any required
customisation (compensation curve, power, temperatures, etc.).
4.3 Maintenance
Periodical check
To ensure correct operation of the unit over time, have qualified personnel carry out a
yearly check, providing for the following:
•The control and safety devices (gas valve, flow meter, thermostats, etc.) must function correctly.
•The fume exhaust circuit must be perfectly efficient.
(Sealed chamber boiler: fan, pressure switch, etc. -The sealed chamber must be
tight: seals, cable glands, etc.)
(Open chamber boiler: anti-backflow device, fume thermostat, etc.)
•The air/fume terminal and ducts must be free of obstructions and leaks
•The burner and exchanger must be clean and free of deposits. Do not use chemical
products or wire brushes for cleaning.
•The electrode must be free of scale and properly positioned.
•The gas and water systems must be tight.
•The water pressure in the system when cold must be approx. 1 bar; otherwise bring
it to that value.
•The circulating pump must not be blocked.
•The expansion tank must be filled.
•The gas flow and pressure must match that given in the respective tables.
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdown (marked with the letter “A”): to restore
operation, press the RESET button (detail 6 - fig.1) for 1 second or RESET on the optional remote timer control if installed; if the boiler fails to start, it is necessar y to eliminate
the fault indicated by the operation LEDs.
Faults marked with the letter “F” cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
Table of faults
Table. 5 - Fault list
Fault
FaultPossible causeCure
code
No burner ignition
A01
Flame present signal with burner
A02
off
Overtemperature protection activa-
A03
tion
Air pressure switch (fails to close
contacts within 20 sec. of fan activation)
F05
Air pressure switch (fails to close
contacts within 20 sec. of fan activation) due to activation of the
fume thermostat
A06
No flame after the ignition stage
F10
Delivery sensor 1 fault
F11
DHW sensor fault
F14
Delivery sensor 2 fault
Air pressure switch (fails to close
contacts within 20 sec. of fan acti-
A15
vation)
Supply voltage under 170V.Electric mains trouble Check the electrical system
F34
F35
Faulty mains frequencyElectric mains trouble Check the electrical system
F37
Incorrect system water pressure
A41
Sensor positioning
F42
Heating sensor faultSensor damagedReplace the sensor
F43
Exchanger protection activation.
F50
Modureg faultWiring disconnectedCheck the wiring / Gas valve
Excessive condensate
level
No gas
Ignition/detection electrode fault
Faulty gas valve
Electrode faultCheck the ionisation electrode wiring
Card faultCheck the card
Heating sensor dam-
aged
No water circulation in
the system
Air in the systemVent the system
Air pressure switch
contact open
Incorrect air pressure
switch wiring
Wrong baffleCheck correct Ø
Flue obstructed or not
correctly sized
Exchangers dirty
(clogged on water
side)
Faulty water circulation
Low pressure in the
gas system
Burner minimum pres-
sure setting
Sensor damaged
Wiring disconnected
Sensor damaged
Wiring disconnected
Sensor damaged
Wiring disconnected
Fault
F05
generated 5
times in the last 24
hours
Pressure too lowFill the system
Water pressure switch
damaged or not connected
Delivery sensor or
DHW sensor detached
from the pipe
No system H
lation
Air in the systemVent the system
Empty / clean the trap
Check the regular gas flow to the boiler
and that the air has been eliminated
from the pipes
Check the wiring of the electrode and
that it is correctly positioned and free of
any deposits
Check the gas valve and replace it if
necessary
Check the correct positioning and operation of the heating sensor
Check the circulating pump
Check the pressure switch / Fan / Fan
socket
Check the wiring
Check the length of the flues / Clean the
flues
Clean the exchangers
Check the gas pressure
Check the gas pressures
Check the wiring or replace the sensorWiring shorted
Check the wiring or replace the sensorWiring shorted
Check the wiring or replace the sensorWiring shorted
See fault
F05
Check the sensor
Check the correct positioning and operation of the sensors
O circu-
2
Check the circulating pump
cod. 3540S920 - 05/2009 (Rev. 00)
EN
7
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
A = Boiler pressure losses - 1, 2 and 3 = Circulating pump speed
Important: Before connecting the room thermostat or the remote timer con-
A
trol, remove the jumper on the terminal block.
7
4438
fig. 19 - General view
Q [l/h]
277
27
19
26
81
186
193
14
36
114
32
A
DataUnitDOMIcondens F 28
Max. heating capacitykW27.2(Q)
Min. heating capacitykW10.0(Q)
Max. Heat Output in heating (80/60°C)kW26.2(P)
Min. Heat Output in heating (80/60°C)kW9.2(P)
Max. Heat Output in heating (50/30°C)kW28.2
Min. Heat Output in heating (50/30°C)kW9.6
Max. heating capacity in hot water productionkW27.2
Min. heating capacity in hot water productionkW10.0
Max. Heat Output in hot water productionkW26.5
Min. Heat Output in hot water productionkW9.2
Gas supply pressure G20mbar20
Max. gas delivery G20
Min. gas delivery G20
Gas supply pressure G31mbar37
Max. gas delivery G31kg/h2.13
Min. gas delivery G31kg/h0.78
Efficiency class Directive 92/42 EECNOx emission class-3(NOx)
Max. working pressure in heatingbar3(PMS)
Min. working pressure in heatingbar0.8
Max. heating temperature°C90(tmax)
Heating water contentlitres1.5
Heating expansion tank capacitylitres8
Heating expansion tank prefilling pressurebar1
Max. working pressure in hot water productionbar9(PMW)
Min. working pressure in hot water productionbar0.25
DHW flowrate Dt 25°Cl/min15.2
DHW flowrate Dt 30°Cl/min12.7(D)
Protection ratingIPX5D
Power supply voltageV/Hz230V/50Hz
Electrical power inputW135
Electrical power input in hot water productionW135
Empty weightkg35
Type of unitC13-C23-C33-C43-C53-C63-C83-B23-B33
PIN CE0063BR3161
Key of figures cap. 5
5Sealed chamber
7Gas inlet
8Domestic hot water outlet
9Cold water inlet
10Syst em delivery
11System return
14Safety valve
16Fan
19Combustion chamber
20Burner assembly
21Main nozzle
22Burner
26Combustion chamber insulation
27Copper exchanger f or heating and hot water
32Heating circulating pump
36Automatic air vent
38Flow switch
42DHW temperatur e sensor
43Air pressure switch
44Gas valve
47Modureg
56Expansion tank
72Room thermostat
81Ignition and detection electrode
114Water pressure switch
126Contact fume thermostat
139Remote timer control
186Return sensor
193Trap
277Condensing recuperator
278Double sensor (Safety + Heating)
3
m
/h
3
/h
m
2.88
1.06
8
EN
cod. 3540S920 - 05/2009 (Rev. 00)
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
DOMIcondens F 28
DBM02.1B
193
278
TT
72
12
REMOVE TO CONNECT
THE
CLOCK
43
X4
22:00
X1
X5
X7
X6
11
10
9
1
8
2
7
3
6
4
5
5
4
6
3
7
2
1
4
3
2
1
81
N
230V
50 Hz
L
3
32
2
1
X3
44
114
42
T .
ON
DAY
04
47
38
126
16
139
fig. 21 - Wiring diagram
cod. 3540S920 - 05/2009 (Rev. 00)
EN
9
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
267
BENCHMARK
COLLECTIVE MARK
BENCHMARK No.
Please add the first 4 digits of the Boiler serial No to complete the BENCHMARK No.
GAS BOILER COMMISSIONING CHECKLIST
BOILER SERIAL No.NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATINGROOM T/STAT & PROGRAMMER/TIMERPROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATERCYLINDER T/STAT & PROGRAMMER/TIMER
HEATING ZONE VALVESFITTEDNOT REQUIRED
HOT WATER ZONE VALVESFITTEDNOT REQUIRED
THERMOSTATIC RADIATOR VALVESFITTED
AUTOMATIC BYPASS TO SYSTEMFITTEDNOT REQUIRED
COMBI BOILER
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATEft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE)mbar
CENTRAL HEATING FLOW TEMPERATURE°C
CENTRAL HEATING RETURN TEMPERATURE°C
m3/hr
N/A
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED? YES NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATEft3/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)mbar
COLD WATER INLET TEMPERATURE°C
HOT WATER OUTLET TEMPERATURE°C
WATER FLOW RATE
m
N/A
3
/hr
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER’S INSTRUCTIONS?YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
lts/min
THE HEATING AND HOT WATER SYSTEM COMPLIES
WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING?N/AYESCO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
COMMISSIONING ENG’S NAME PRINTCORGI ID No.
SIGNDATE
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SERVICE 1
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 3
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 5
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SERVICE 2
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 4
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 6
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SIGNATURE
SERVICE 7
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 9
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
SIGNATURE
SERVICE 8
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 10
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
FERROLI TECHNICAL HELPLINE - 08707 282 885
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
Should you require any assistance during the installation
Should you require a service engineer to visit
Phone numbers:
Installer
Service Engineer
call our Technical Service Helpline on
08707 282 885 option 1
call our service centre on
08707 282 885 option 2
BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS
MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.
ALL SPECIFICATIONS SUBJECT TO CHANGE
Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check
this is not caused by lack of electricity supply, gas supply or low water pressure before calling our