Faber CADRA NOVA, WHISPER, SPECTRA NOVA, FEELING, SILENCE User Manual

...
installation guide and user manual
room-sealed built-in gas-fireplace
40 010 527
02 37
SILENCE
FEELING
WHISPER
CADRA NOVA
MISTY
Saturnus 8 NL-8448 CC Heerenveen Postbus 219 NL-8440 AE Heerenveen T. +31(0)513 656500 F. +31(0)513 656501
“Log Burner Technology”
1
CONTENTS
1. INTRODUCTION 2
2. SAFETY INSTRUCTIONS 3
3. INSTALLATION REQUIREMENTS 5
3.1 Builders opening and surround 5
3.2 Requirements outlet and exhaust 8
4. INSTALLATION-INSTRUCTIONS 17
4.1 Gas connection 17
4.2 Preparation of the appliance 17
4.3 Fitting the firebox 24
4.4 Placing of the wood set 26
5. INSTALLATION OF THE FLUE 27
5.1 Connection of the flue 27
5.2 Placing through existing chimney 28
5.3 Remote control 30
6. COMMISIONING 32
6.1 Check pilot ignition 32
6.2 Functional burner check 32
6.3 Functional balanced flue check 33
6.2 Check reference pressure 33
7. HANDING OVER 34
8. SERVICING 35
8.1 Routine annual servicing 35
USER GUIDE 45
9. SAFETY INSTRUCTIONS FOR THE USER 46
10. CONTROLING THE APPLIANCE 48
11. CLEANING AND SERVICE INSTRUCTIONS 54
12. DISPOSAL OF THE PACKAGING AND THE APPLIANCE 55
INDEX 1 LIST OF SPARE PARTS 40
INDEX 2 TECHNICAL DATA 41
UK/IRL
UK/IRL
2
UK/IRL
3
1. INTRODUCTION
Note: these instructions should be read carefully and retained for
future reference. Please leave these instructions with the user.
This guide is concerning the following types of appliances:
Widescreen interior: Types Silence and Feeling Roundscreen interior: Type Misty MV100 interior: Type Whisper MV110 interior: Types Spectra Nova and Cadra Nova
Special features:
- Realistic flame and glow effect because of the "Log burner" technology.
- Room sealed appliance, inlet and outlet are led to the outside using a natural draught concentric pipe system (100 mm/150 mm) (no power fan required). No additional ventilation required.
- Air supply and flue-gases go to outside atmosphere through wall or roof. A maximum horizontal extension of 6 meters is possible.
- Remote Control option on all appliances.
- Meets the essential requirements of the European Gas Appliance Directive (GAD) and carries the CE mark.
2. SAFETY AND GENERAL
INFORMATION
Before installation, ensure that the local distribution conditions (identification of the type of gas and pressure) and the adjustment of the appliance are compatible.
This gas appliance is factory set and shall not be adjusted by the installer.
This appliance does not contain any component manufactured from asbestos or any asbestos related products.
The pilot and flame sensing device fitted to this fire is also a safety device. If for any reason any part of the pilot assembly is to be replaced the entire assembly including the pilot burner, thermocouple, electrode and injector must be exchanged complete for a pilot assembly from the original manufacturer only.
Ventilation This appliance is room-sealed and doesn't require purpose provided ventilation.
2.1 General safety
It is the law in the UK that all gas appliances, are installed by a competent person in accordance with the Gas Safety (Installation and Use) Regulations (as amended), the relevant British Standards for Installation work, Building Regulations, Codes of Practice and the manufacturers instructions. The installation should also be carried out in accordance with the following where relevant:
BS5871 Part1 BS5440 Parts 1 & 2 BS1251.
Building Regulations Document J (as applicable).
UK/IRL
5
UK/IRL
4
Building Regulations and Standards issued as relevant by the Department of the Environment or the Scottish Development Department.
In the Republic of Ireland installation should be carried out in accordance with IS813, ICP3, IS327, Building Regulations, Codes of Practice, the manufacturers instructions and any other rules in force.
Failure to comply with the above could leave the installer liable to prosecution and invalidate the appliance warranty.
Safety instructions for the user: see chapter 9.
3. INSTALLATION REQUIREMENTS
Note:
Since the appliance is a source of heat, circulation of air occurs. Therefore it is of importance that you do not use the appliance shortly after a renovation of the home. Because of the natural circulation of air, moist and volatile components from paint, building materials, carpet etc. will be attracted. These components can settle themselves down onto cold surfaces in the form of soot.
As on all heat producing appliances, soft furnishings such as blown vinyl wallpaper placed too near to the appliance may become scorched or discoloured. This should be born in mind when installing the appliance.
3.1 Builders opening and surround
The appliance can be installed in the following situations:
In a non-combustible fireplace or builders opening. This could be either an existing builders opening or a new made prefab builders opening. For the measurements, see figure 1 and index.
Although the appliance is tested for installation without a hearth, the appliance must not stand on combustible materials or carpets. If the appliance is placed on a combustible floor then a fibrelux or similar heatproof board of 12 mm thickness should be placed under it. Any under floor vents or openings within the builders opening should be sealed off.
Do not place the lintel, surround or marble stone directly onto the appliance. If possible, apply a lintel made of cement or something similar.
Isolate the appliance with a ceramic blanket (25 mm). See also chapter 4: Installation instructions. Preferred choice for insulation is unbound insulation wool (at 1000 °C gives no smell).
Builders opening (mm) Feeling Silence Whisper Spectra Cadra Misty
Nova Nova
A Opening width* 960 960 780 780 680 710 B Opening height* 649 649 705 698 798 890 C Opening depth* 385 385 430 430 430 370
Shelf dimensions (combustible)
D Min. height shelf from
top frame 350 350 350 350 350 350
E Depth shelf max. 150 150 150 150 150 150
Dimensions (mm)
F Box width 880 880 750 750 650 698 G Box depth 366 366 397 375 375 338 H Box height 636 636 714 715 815 879 I Frame width 1064 1064 815 794 694 740 J Frame height 678 678 720 703 803 905 K Frame thickness 47 20 16 30 30 144 L Position flue
(behind frame) 255 255 257 235 235 196
M Position flue (from the
back side box) 111 111 140 140 140 142
UK/IRL
7
UK/IRL
6
3.1 Builders opening and surround (continuing)
If the builders' opening is constructed out of non-combustible composition board (Fibrelux) and you install the appliance without a mantel then:
- Ventilate the space above the appliance (min. 1000 mm
2
).
- Always fit the DC convection set.
- The plaster of the outside has to be resistant to a high temperature. Use therefore the plaster materials especially made for this, to prevent discoloring (min. 100 °C temperature resistant).
If the appliance is to be fitted against a wall with combustible cladding, the cladding must be removed from the area covered by the surround.
The minimum height from the top surface of the fire to the underside of any shelf made from wood or other combustible materials is as follows:
- For a shelf up to 150 mm deep – Minimum height = 350 mm (fig. 1).
- If the shelf depth is greater than 150 mm add 50 mm to the upper­clearance height for every 25 mm increase in shelf depth.
- Side clearance = Minimum distance from the side of the fire frame to combustible material = 150 mm.
fig. 1
table 1
*the points A until C applies a tolerance from: – 0 mm and + 5 mm.
F
G
E
D
B
C
A
K
I
J
M
L
H
UK/IRL
9
UK/IRL
8
3.2 Flue requirements
The appliance is of the type C11/C31. The appliance will need to be supplied with the approved flue pipes and terminal, it is not possible to supply your own.
The minimum effective height of the flue system must be 0.5 or 1 meter, depending on the appliance.
Terminal locations, through the wall as well as through the roof. See
figure 3.
Flue routing;
- a horizontal extension with elbows is allowed for a maximum of
6 meters (depending on the type and situation).
- vertical max. 12 meters.
Determine on the base of the table 2 and 3, depending on the type and terminal position, if the desired situation is possible.
To establish this you will need to calculate:
- The effective height (this is the real difference in height between the upper side of the appliance and the terminal).
- The total horizontal extension. This is the total horizontal flue length where:
• each elbow, which is in the horizontal area, counts for 2 meters.
• each 45-degree bend, which is in the horizontal area, counts for 1 meter.
• elbows and bends at the transition of horizontal to vertically are not to be counted.
• the wall mounted terminal counts for 1 meter.
Flue restrictor
If applicable, in the table is also stated the size of a flue restrictor. This restrictor needs to be fitted in the combustion chamber when placing the appliance ( see chapter 4.2). Normally the smallest flue restrictor is fitted.
UK/IRL
Table Silence and Feeling with interior Widescreen
Determine according to the table 2 the right total horizontal- and vertical length. When meeting an X, and when the values are outside the table, the combination is not allowed. Normally the 30 mm flue restrictor is preinstalled.
Table Whisper and Spectra Nova with interior MV100
Determine according to the table 3 the right total horizontal- and vertical length. When meeting an X, and when the values are outside the table, the combination is not allowed. Normally the 30 mm flue restrictor is preinstalled.
table 2 interior Widescreen
table 3 interior MV100
UK/IRL
10
fig. 2a
fig. 2b
Example calculation 1
Calculati0n horizontal extension fig. 2a:
Flue lenght C + E = 1m + 1m 2 m Elbows D = 2m 2 m
Total horizontal extension 4 m
Measure or calculate ef fective height (Hvert)
Flue lenght A 1 m Roof mounted terinal 1 m
Total effective height 2 m
When calculating on basis of the Widescreen table nr. 2: It is allowed. Remove the flue restrictor!
When calculating on basis of the MV100 table nr. 3: Allowed but without flue restrictor. Remove the flue restrictor!
When calculating on basis of the MV150 table nr. 4: Allowed but without flue restrictor. Remove the flue restrictor!
When calculating on basis of the Roundscreen table nr. 5: Allowed but without flue restrictor. Remove the flue restrictor!
11
* at propane not allowed
Example calculation 2
Calculati0n horizontal extension fig. 2b
:
Flue lenght J + L = 0,5 + 0,5 1 m Elbows K + M = 2m + 2m 4 m Terminal 1 m
Total horizontal extension 6 m
Vertical
Flue lenght
H1 m
When calculating on basis of the Widescreen table nr. 2: Combination not allowed.
When calculating on basis of the MV100 table nr. 3: Allowed but without flue restrictor. Remove the flue restrictor!
When calculating on basis of the MV150 table nr. 4: Combination not allowed.
When calculating on basis of the Roundscreen table nr. 5: Combination not allowed.
Hvert.
0
G
1 00
1,5 0 0 0 0
F
B
C
E
D
2303000000 345453030000 4 45453030 30 0 0 5 505045303030 0 6 505045303030 0
A
7 606050454530 8 6060605050
Effective height
965 10 65 65 65 11 65 65 12 65
Horizontal extension
0123456 XXXXXXX
XXXXX
XXX
X combination
0 remove flue restrictor
X
XX
65 60 60
XXX
XXXX
XXXXX
XXXXXX
not allowed
Number is size in mm of the flue restrictor
Hvert.
M
I
H
L
J
K
N
Horizontal extension
0123456
0
XXXXXXX 1 30 0 0 0 0 0 0/X* 23030 0 0 0 0 0 3 454530 0 0 0 0 4 454530 0 0 0 0 5 5050454530 0 0 6 5050454530 0 0 7 606060505045 8 6060606050 9 65656060
Effective height
10 65 11 65 65 12 65
65 65
XXXX
XXXXX
XXXXXX
XX
XXX
X combination
not allowed
0 remove flue restrictor
Number is size in mm of the flue restrictor
X
UK/IRL
13
3.2 Flue requirements (continuing)
3.2.1 Terminal position
Verify if the required terminal position meets the local installation regulations regarding disturbance, good functioning and ventilation. (Also see: safety requirements).
Note:
The terminal must be located so that the outlet is not obstructed. If the flue terminal is located within 2 meters of a footway, path or where people could come into contact with it then a suitable terminal guard must be fitted.
Terminals located close to shared walkways, footpaths etc. could be subject to legal constraints and this should be pointed out to the customer before installation. If in any doubt about flue location advice should be sought from local building control, or if appliance­related, from the manufacturer including wherever possible a dimensioned sketch.
Avoid locating the terminal in close proximity to plastic materials such as gutters or other combustibles. If this is unavoidable then a suitable deflector should be made.
Some important requirements for a good functioning are:
The wall-mounted terminal has to be at a distance of at least
0.5 meters off:
- Corners of the building.
- Below eaves.
- Balcony's etc. unless the duct is dragged to the front side of the overhanging part.
The roof mounted terminal has to be at a distance of at least
0.5 meters of the sides of the roof, excluded the ridge.
UK/IRL
12
Table Cadra Nova with interior MV150
Determine according to the table 4 the right total horizontal- and vertical length. When meeting an X, and when the values are outside the table, the combination is not allowed. Normally the 30 mm flue restrictor is preinstalled.
Misty with roundscreen
Determine according to the table 5 the right total horizontal- and vertical length. When meeting an X, and when the values are outside the table, the combination is not allowed. Normally the 30 mm flue restrictor is preinstalled.
0123456
0
XXXXXXX
XXXXXX
XXXXX
XXXX
XXX
XX
X
XXXXX
0XX
0,5 X 0
1 X 30 0 0
000
1,5 40 30 0 0
2403000000 34040300000 4 50404030 0 0 0 5 505040403030 0 6 505050404030 0 7 605050404040 8 6060505050 960
60 60 50 10 65 60 60 11 65 65 12 65
X combination
not allowed
0 remove flue restrictor
Horizontal extension
Effective height
Number is size in mm of the flue restrictor
table 5 interior Roundscreen
0123456
0
XXXXXXX
XXXXX
60
XX
XX
50
X
XX
50 X X
40
X
0
0,5
X
0 X X X X X 1 30 0 0 0 0 X 240300 0 0 0 0 3 40 40 30 0 0 0 0 4 50404030 0 0 0 5 50 50 40 40 30 30 0 6 505050404030 7 6050504040 8 60605050 960
60 60
10 65 60
65
11 65
65
Horizontal extension
Effective height
X combination
not allowed
0 remove flue restrictor
Number is size in mm of the flue restrictor
X
12
XX
X
X
X
X
table 4 interior Cadra Nova
Table 6
UK/IRL
15
UK/IRL
14
Dimension Terminal position Balanced flue room sealed
(kW input 7.5 kW expressed in net) Natural draught
A Direct below an opening, airbrick, 300 mm
opening windows, etc.
B Above an opening, airbrick, 300 mm
opening window ect.
C Horizontally to an opening, airbrick, 300 mm
opening window etc. D Below gutters, soil pipes or drain pipes 500 mm E Below eaves 500 mm F Below balconies or car port roof 600 mm G From a vertical drain pipe or soil pipe 300 mm H From an internal or external corner 600 mm I Above ground roof or balcony level 300 mm J From a surface facing the terminal 600 mm K From a terminal facing the terminal 600 mm L From an opening in the carport (e.g. 1200 mm
window) into the dwelling M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm P From a vertical structure on the roof 600 mm Q Above intersection with roof 500 mm
Flue terminal positions
fig. 3
Loading...
+ 20 hidden pages