FAAC 800IOL User Manual

Page 1
BYAN SYSTEMS, INC. OF LUSK, WYOMING, DEMANDS THAT YOU AS AN INSTALLER
INFORM YOUR CUSTOMER OF ALL SAFETY EQUIPMENT THAT SHOULD BE INSTALLED
ON EACH JOB SITE. THIS IS IN ACCORDANCE WITH YOUR LEGAL LIABILITY TO YOUR
CUSTOMER. ENSURE THAT THE PROTECTION AND WARNING SIGNALING DEVICES ARE
OPERATIONAL AND VISIBLE. THESE STEPS WILL AID IN YOUR DEFENSE SHOULD YOU
P.O. BOX 1384 FAX (307) 334-2028
INSTALLATION AND TECHNICAL MANUAL
BECOME INVOLVED IN LITIGATION REGARDING INJURY OR DAMAGE.
ATTENTION: ALL INSTALLERS EXPERIENCED OR NOT PLEASE REVIEW
PAGES 4 AND 9 BEFORE YOU INSTALL THIS ACTUATOR.
BYAN SYSTEM, INC.
413 LINDEN
LUSK, WY 82225
(800) 223-2926
MODEL 800A/900B SERIES
VEHICULAR SWING
Page 2
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
TABLE OF CONTENTS
DESCRIPTION PAGE NO.
USAGE CLASSES FOR VEHICULAR GATE OPERATOR 2
TECHNICAL DATA ABOUT THE OPERATOR 3
BEFORE YOU INSTALL 4
DURING INSTALLATION PROCEDURES 4
INSTALLATION COMPLETION/FOLLOW UP 5
INSTALLING THE OPERATOR 6
PURGING THE OPERATOR 7
PRESSURE ADJUSTMENTS 8
HYDRAULIC FLUID 8
MANUAL BYPASS 9
MOUNTING GEOMETRY 10
MOUNTING BRACKET LOCATION 11
FRONT MOUNTING DETAIL 12
WIRING THE CONTROL AND ACCESSORIES 13
CONNECTING THE OPERATOR 19
LOOP CONNECTORS 21
WARRANTY 26
END USER SAFETY 27
CUSTOMER ACKNOWLEDGMENT 29
413 Linden • Lusk, WY 82225 • (800) 223-2926
1
Page 3
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
USAGE CLASSES FOR
VEHICULAR GATES
CLASS I – RESIDENTIAL VEHICULAR GATE OPERATOR
A VEHICULAR GATE OPERATOR (OR SYSTEM) INTENDED FOR USE IN A HOME OF ONE TO FOUR SINGLE FAMILY DWELLING, OR A GARAGE OR PARKING AREA ASSOCIATE THEREWITH.
CLASS II – COMMERCIAL/GENERAL ACCESS VEHICULAR GATE OPERATOR
A VEHICULAR GATE OPERATOR (OR SYSTEM) INTENDED FOR USE IN A COMMERCIAL LOCATION OR BUILDING SUCH AS A MULTI-FAMILY HOUSING UNIT (FIVE OR MORE SINGLE FAMILY UNITS), HOTEL, GARAGES, RETAIL STORES, OR OTHER BUILDING SERVICING THE GENERAL PUBLIC.
CLASS III – INDUSTRIAL/LIMITED ACCESS VEHICULAR GATE OPERATOR
A VEHICULAR GATE OPERATOR (OR SYSTEM) INTENDED FOR USE IN AN INDUSTRIAL LOCATION OR BUILDING SUCH AS A FACTORY OR LOADING DOCK AREA OR OTHER LOCATION NOT INTENDED TO SERVICE THE GENERAL PUBLIC.
CLASS IV – RESTRICTED ACCESS VEHICULAR GATE OPERATOR
A VEHICULAR GATE OPERATOR (OR SYSTEM) INTENDED FOR USE IN A GUARDED INDUSTRIAL LOCATION OR BUILDING SUCH AS AN AIRPORT SECURITY AREA OR OTHER RESTRICTED ACCESS LOCATION NOT SERVICING THE GENERAL PUBLIC, IN WHICH UNAUTHORIZED ACCESS IS PREVENTED VIA SUPERVISION BY SECURITY PERSONNEL.
413 Linden • Lusk, WY 82225 • (800) 223-2926
2
Page 4
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
800A/900A SERIES TECHNICAL DATA
MODEL 800A: 220 VAC SINGLE PHASE MODEL 900B: 115 VAC SINGLE PHASE ELIMINATOR SERIES BUILT-IN THERMAL OVERLOAD
CAPACITOR RATING: 10UF FOR THE 800A
35UF FOR THE 900A
STANDARD WORKING PRESSURE: 1350 PSI MAXIMUM WORKING PRESSURE: 1750 PSI
PUMP: SPUR GEAR 1.0 LTR/MIN.
MOTOR: 1/6 HORSE POWER
OPERATOR LENGTH WITH PISTON 754 TO 904 MILLIMETERS RETRACTED AND REAR BRACKET AND 29-11/16 TO 35-5/8 INCHES SWIVEL INSTALLED
OPERATOR LENGTH EXTENDED WITH REAR 1004 TO 1304 MILLIMETERS BRACKET AND SWIVEL JOIN INSTALLED 39 TO 51 5/16 INCHES
OPERATOR WIDTH: 3-3/8 X 3-3/8 INCHES 4-5/16 WITH LOCK
OPERATOR SPEED TO 90 DEGREES: 13 SEC. FOR 800A 13 SEC. FOR 900A
PISTON STROKE: 250 MM OR 9-7/8 INCHES 400 MM OR 15-3/4 INCHES
AMBIENT OPERATOR TEMPERATURE RANGE: -60 TO 220 DEGREES F
HYDRAULIC FLUID: SHELL TELLUS T-15
THIS PATENTED NEW CONCEPT IN LINEAR ACTUATOR DESIGN ELIMINATES THE NEED FOR PHYSICAL STOPS. THE VALVE DESIGN CUSHIONS THE LAST HALF INCH OR ABOUT THE LAST 5 TO 10 DEGREES OF PISTON TRAVEL ALLOWING THE PISTON TO REACH END OF STROKE IN BOTH DIRECTIONS AND PREVENT INTERNAL DAMAGES.
OPERATOR BODY FABRICATED IN ANODIZED ALUMINUM FRONT AND REAR FLANGES ARE CAST ALUMINUM ALL INTERNAL COMPONENTS ARE CAST AND MACHINED INTERNAL COMPONENTS BATHED IN OIL SO VIRTUALLY NO MAINTENANCE REQUIRED.
413 Linden • Lusk, WY 82225 • (800) 223-2926
3
Page 5
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
BEFORE INSTALLATION
1. VERIFY THE GATE POST IS PLUM AND GATE LEAF SWINGS FREELY.
2. PERFORM ANY REQUIRED MAINTENANCE BEFORE CONTINUING.
3. VERIFY THE COMMERCIAL POWER CIRCUIT BREAKERS ARE ISOLATED AND RATED FOR
THE SPECIFIC LOAD. VISUALLY ENSURE THE CIRCUIT BREAKERS ARE IN THE “OFF” POSITION AND MARK THE BREAKER USED.
4. IF ANY PRE-CONSTRUCTION WIRING HAS BEEN INSTALLED, VISUALLY INSPECT AND
CONFIRM PROPER SIZING AND COMPLIANCE TO CODE.
5. AUTOMATIC VEHICULAR GATES ARE NOT APPROVED FOR PEDESTRIAN TRAFFIC,
HOWEVER, THEY CAN CREATE HAZARDS TO UNSUSPECTING PEDESTRIANS AND DOMESTIC ANIMALS. ANY GATE, CONSTRUCTED WITH REACHABLE PINCH POINTS, OR HAS A SURFACE AREA THAT ALLOWS ARMS OR LEGS TO PASS THROUGH, IS A POTENTIAL HAZARD. RECOMMEND AND PROVIDE SAFE GUARDS AGAINST THESE HAZARDS
6. REMOVE THE “END USER SAFETY ADVISORY HANDOUT” FROM THIS MANUAL. REQUEST
THE END USER REVIEW THE MATERIAL AND SIGN IT. COLLECT THE HANDOUT WHEN THE JOB IS COMPLETE.
.
DURING INSTALLATION
1. LOCATE THE ELECTRONIC CONTROLS FAR ENOUGH FROM THE GATE SO THE END USER
CAN OBSERVE, BUT NOT TOUCH, THE GATE WHILE OPERATING THE CONTROLS.
2. WHEN CONNECTING THE WIRING FROM THE COMMERCIAL POWER SOURCE TO THE
CONTROL PANEL, MAKE SURE YOU HAVE PROVIDED A PROPER EARTH GROUND. IF USING A METAL ENCLOSURE, CONNECT THE GROUND TO THE ENCLOSURE BEFORE CONNECTING TO THE GATE OPERATORS. NO GROUND IS TO CONNECTING TO THE GATE OPERATORS. NO GROUND IS TO CONNECT DIRECTLY TO THE MICROPROCESSOR CONTROL.
3. OBSERVE ALL WIRING REQUIREMENTS ESTABLISHED BY THE NATIONAL ELECTRICAL
CODE AND/OR THE AUTHORITY HAVING JURISDICTION.
4. MOUNT HE LINEAR ACTUATOR AS CLOSE TO THE CENTER OF THE GATE LEAF AS
POSSIBLE. THIS WILL HELP BALANCE THE WHIPPING MOTION OF THE GATE WHEN THE OPERATOR REACHES END OF THE PISTON STROKE.
5. ISOLATE THE LINEAR ACTUATOR WHEN WELDING TO PREVENT ANY CURRENT FROM
PASSING THROUGH THE OPERATOR AND DAMAGING THE MOTOR OR OTHER COMPONENTS.
413 Linden • Lusk, WY 82225 • (800) 223-2926
4
Page 6
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
INSTALLATION COMPLETION
1. INSTALL PLACARDS AND SAFETY EQUIPMENT AND TEST.
2. “REMOVE” ALL DEBRIS AND OBSTRUCTIONS FROM THE TRAVEL PATH OF THE GATE
LEAF(S).
3. TURN ON AND LABEL THE COMMERCIAL POWER CIRCUIT BREAKER AND REMOVE THE
“USED” TAG YOU INSTALLED AT THE BEGINNING OF THE PROJECT.
4. USING THE MANUAL BYPASS, POSITION THE GATE LEAF AT 45 DEGREES. PRESS THE
TEST BUTTON ON THE G2M CONTROL BOARD. THE FIRST SIGNAL WILL ALWAYS BE TO OPEN. IF THE OPERATOR RUNS TO THE CLOSED POSITION, TURN OFF THE COMMERCIAL POWER AND REVERSE THE MOTOR CONNECTIONS ON PINS 1 AND 3.
5. OPERATE THE ACTUATOR SEVERAL TIMES UNTIL YOU CAN DETECT A RISE IN THE
FLUID TEMPERATURE. PLACING YOUR HAND ON THE TOP OF THE OPERATOR AT THE REAR CAN DO THIS.
6. PURGE AND ADJUST THE OPERATOR AS DESCRIBED IN THE PURGING AND ADJUSTMENT
SECTION.
7. INSTRUCT THE END USER HOW TO MANUALLY RELEASE THE GATE IN THE EVENT OF A
POWER FAILURE.
8. INSTRUCT THE END USER HOW TO PROPERLY OPERATE THE GATE AUTOMATION AND
SAFETY FEATURES THEREOF.
9. COLLECT THE “SIGNED” END USER SAFETY HAND OUT. BY THEIR SIGNATURE, THE END
USER ACKNOWLEDGES THEIR UNDERSTANDING OF THEIR RESPONSIBILITIES OF OWNING, OPERATING, AND MAINTAINING A VEHICULAR AUTOMATIC GATE OPERATING SYSTEM.
413 Linden • Lusk, WY 82225 • (800) 223-2926
5
Page 7
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
INSTALLING THE OPERATOR
! ADVISORIES!
A. THIS LINEAR ACTUATOR MUST ME MOUNTED SO THE PISTON FULLY EXTENDS
AND FULLY RETRACTS. WHEN FULLY RETRACTED THERE SHOULD BE 1/8 INCH PISTON LEFT OUT OF THE FRONT.
B. THIS LINEAR ACTUATOR HAS AN OFFSET BETWEEN THE FRONT AND REAR
MOUNTING BRACKET. THE FRONT BRACKET IS ABOUT 5/8 OF AN INCH LOWER THAN THE FRONT BRACKET; REVIEW THE BRACKET ALIGNMENT DETAIL FOR THE OFFSET DIMENSION. THE FRONT BRACKET HAS THE TALLER SHOULDER.
1. SCRIBE A LINE FROM THE HORIZONTAL SUPPORT OR DESIRED HEIGHT FOR THE
OPERATOR ON THE GATE LEAF ONTO THE GATE POST.
2. MEASURE FOR THE OFFSET DESCRIBED IN THE ADVISORY #B AND SCRIBE
ANOTHER LINE.
3. CUT THE REAR MOUNTING BRACKET IN ACCORDANCE WITH THE DIMENSIONS
SPECIFIED ON THE MOUNTING GEOMETRY DETAIL.
4. WELD THE REAR MOUNTING BRACKET TO THE GATE POST.
5. DETERMINE THE “C” DIMENSION AND CUT THE FRONT MOUNTING BRACKET TO
THE PROPER LENGTH.
6. EXTEND THE PISTON TO FULLY EXTENDED POSITION FOR INWARD SWING
GATES. THIS CAN BE ACHIEVED BY TEMPORARILY CONNECTING THE CONTROL PANEL TO THE OPERATOR AND USING THE MOTOR TO EXTEND THE PISTON, PRODUCING 9 7/8” OF PISTON. IT IS VERY IMPORTANT WITH THE “800A/900A” THAT THE PISTON “BOTTOMS OUT IN BOTH DIRECTIONS”.
7. SCREW THE “I” BOLT INTO THE END OF THE PISTON 1/2 TO 3/4 OF THE LENGTH OF
THE THREADS. ATTACH THE FRONT BRACKET TO THE OPERATOR.
8. ATTACH THE OPERATOR TO THE REAR MOUNTING BRACKET.
9. WITH THE GATE IN THE FULL CLOSED POSITION, LEVEL THE OPERATOR AND
SCRIBE THE LOCATION FOR THE FRONT MOUNTING BRACKET.
10. REMOVE THE FRONT MOUNTING BRACKET FROM THE FRONT OF THE GATE
OPERATOR AND WELD IT TO THE GATE LEAF AT THE SCRIBED LOCATION.
11. ATTACH THE OPERATOR TO THE FRONT MOUNTING BRACKET.
413 Linden • Lusk, WY 82225 • (800) 223-2926
6
Page 8
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
12. CONNECT THE CORD PER THE ELECTRICAL CONNECTION DETAILS.
NOTE: IT IS HELPFUL TO INSTALL A SINGLE GANG WEATHER PROOF BELL BOX ON THE GATE POST ACROSS FROM THE OPERATOR. THEN WIRE FROM THE CONTROL BOX CAN BE PULLED TO THIS POINT AND CONNECTED TO THE S.O. CORD INSIDE THE BELL BOX.
PURGING THE OPERATOR
SOMETIMES DURING SHIPPING, THE “800A/900A” SERIES OPERATOR GETS TURNED UPSIDE DOWN AND REQUIRES THE VALVE SYSTEM TO BE PURGED AFTER YOU HAVE COMPLETED THE INSTALLATION. THIS CAN BE NOTICED IF THE OPERATOR IS JERKING OR RUNS UNEVEN.
TIGHTEN THE BYPASS VALVE WITH THE ALLEN WRENCH AND GIVE THE OPERATOR A SIGNAL TO RUN. WHILE THE MOTOR IS RUNNING, OPEN AND CLOSE THE BYPASS VALVE PAUSING BETWEEN OPEN AND CLOSE. DO THIS 10 TO 12 TIMES. THEN REMOVE THE FILL CAP TO EXPEL ANY AIR IN THE OPERATOR. REPLACE THE OIL FILLER CAP SCREW AND TIGHTEN ONLY SNUG.
ADJUSTING THE OPERATOR
THE PRESSURES ON THE OPERATOR ARE PRESET AT BYAN SYSTEMS PRIOR TO SHIPMENT. IF THE PRESSURES DO NEED TO BE ADJUSTED, WHETHER HIGHER OR LOWER, YOU MUST ADJUST BOTH DIRECTIONS THE SAME NUMBER OF TURNS (i.e. 1/4 TURN, 1/2 TURN ETC.)
THE PRESSURE ADJUSTMENT SCREWS ARE FOUND UNDER THE LOCKING CAP ON THE TOP OF THE OPERATOR. LOOKING FROM THE REAR TO THE FRONT OF THE OPERATOR, THE LEFT VALVE IS FOR RETRACTING PRESSURE AND THE RIGHT VALVE IS FOR EXTENDING PRESSURE. WITH THE MOTOR RUNNING DECREASE THE PRESSURES EQUALLY UNTIL THE OPERATOR STOPS MOVING IN BOTH DIRECTIONS. BEGIN INCREASING PRESSURE ON BOTH VALVES WITH THE MOTOR RUNNING. ADJUST THE PRESSURE TO WHERE YOU HAVE TO PHYSICALLY STOP THE GATE. AT THIS POINT, EITHER INCREASE THE RETRACTING PRESSURE  TURN OR DECREASE THE EXTENDING PRESSURE  TURN. RETRACTING HAS TO BE A LITTLE HIGHER.
413 Linden • Lusk, WY 82225 • (800) 223-2926
7
Page 9
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
HYDRAULIC FLUID
BYAN SYSTEMS OPERATORS US A “SHELL OIL PRODUCTS” TELLUS T-15, THIS FLUID HAS A RELATIVELY LOW VISCOSITY SO IT WILL START TO FLOW QUICKLY ON COLD DAYS. WHEN THE FLUID RISES TO OPERATING TEMPERATURE, THERE IS NO RUSH OF THIN FLUID CAUSING POOR HYDRAULIC PERFORMANCE, OR WORSE YET, EXCESSIVE PUMP WEAR, FAILURE AND EXPENSIVE DOWNTIME.
TELLUS FLUIDS MINIMIZE THE EFFECT TEMPERATURE HAS ON VISCOSITY, AND RESISTS THE SHEARING ACTION OF HIGH SPEED PUMPS BY MAINTAINING THEIR STABLE VISCOSITY LONGER.
THERE IS A ZINC TYPE ADDITIVE IN THE FLUID TO HELP IMPEDE WEAR AND PREMATURE REPLACEMENT. IT HELPS PREVENT CORROSION TO METALS AND IS DESIGNED TO BE COMPATIBLE WITH HOSES, SEALS AND OTHER ELASTOMER PRODUCTS.
TELLUS T-15 READILY SEPARATES AIR AND WATER TO PREVENT FOAMING, KEEPING THE FLUID FIT AND DIELECTRIC STRENGTH HIGH.
WHERE TO BUY SHELL TELLUS FLUIDS
AT YOUR NEAREST SHELL DISTRIBUTOR, BYAN SYSTEMS DISTRIBUTOR, OR AT BYAN SYSTEMS WAREHOUSE.
FLUID AND YOUR OPERATOR
THE OPERATOR HOLDS APPROXIMATELY 1 QUART OF FLUID. THE PROPER LEVEL CAN BE OBSERVED THROUGH THE OIL FILLER TUBE, LOCATED ON THE TOP OF THE REAR FLANGE OF THE OPERATOR, WITH THE PISTON IN THE RETRACTION POSITION, THE FLUID SHOULD BE VISIBLE AT THE BOTTOM OF THE TUBE, LEVEL WITH THE CURVED SECTION OF THE TUBE. THE 500 SERIES OPERATOR HAS A PRESSURED CHAMBER SO DO NOT OVERFILL. THE PUMP WILL INTERMITTENTLY FAIL TO DRAW FLUID AND WILL FAIL TO RUN IN ONE DIRECTION OR THE OTHER.
413 Linden • Lusk, WY 82225 • (800) 223-2926
8
Page 10
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
MANUAL BYPASS
THE MANUAL BYPASS VALVE IS FOR THE ABILITY TO RELEASE THE OPERATOR IN THE EVENT OF A POWER FAILURE OR MALFUNCTION. IT IS LOCATED UNDER THE KEYED CAP ON TOP OF THE OPERATOR. A METRIC ALLEN WRENCH IS SUPPLIED IN THE CAP TO RELEASE THE BYPASS VALVE. TURN THE VALVE COUNTER CLOCKWISE UNTIL THE OPERATOR RELEASES. WHEN TIGHTENING THE BYPASS VALVE IT MUST BE TIGHT IN ORDER TO PREVENT FLUID OR PRESSURE ESCAPING BACK INTO THE CHAMBER.
PLACARDS AND SAFETY EQUIPMENT
THE PLACARDS SHOULD BE INSTALLED (ONE ON EACH SIDE OF THE GATE) SO THAT THEY ARE VISIBLE AS ANYONE THAT APPROACHES THE GATE. THE SAFETY EQUIPMENT SHOULD BE TESTED BEFORE LEAVING THE GATE SITE.
413 Linden • Lusk, WY 82225 • (800) 223-2926
9
Page 11
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
413 Linden • Lusk, WY 82225 • (800) 223-2926
10
Page 12
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
MOUNTING DIMENSIONS
800A/900A I/O SERIES GATE OPERATOR
4” GATE W/ 2” GATE LEAF
INWARD SWING
DON’T USE THESE DIMENSION FOR LONG OPERATORS PLEASE CALL FOR
CORRECT DIMENSIONS
DEGREE A B C
70 7-1/4 2-1/4 2-3/4 75 6-7/8 2-1/4 2-3/4 80 6-3/8 3 2-3/4 85 6 4-1/4 2-3/4 90 5-5/8 4-1/8 2-3/4
95 5-3/8 4-1/2 2-3/4 *100 4-3/4 4-3/4 2-3/4 *105 4-1/8 4-3/8 2-3/4
110 N/A N/A N/A
6” GATE W/ 2” GATE LEAF
INWARD SWING
DON’T USE THESE DIMENSION FOR LONG OPERATORS PLEASE CALL FOR
CORRECT DIMENSIONS
DEGREE A B C
70 7-1/4 2-1/4 2-3/4
75 6-7/8 2-1/4 2-3/4
80 6-3/8 3 2-3/4
85 6 4 2-3/4
90 5-5/8 4-1/2 2-3/4
95 5-3/8 4-1/2 2-3/4 *100 5-1/8 4-3/4 2-3/4 *105 4-3/8 4-3/8 2-3/4
110 N/A N/A N/A
OUTWARD SWING
DON’T USE THESE DIMENSION FOR LONG OPERATORS PLEASE CALL FOR
CORRECT DIMENSIONS
DEGREE A B C
70 7-1/2 3-1/2 3
75 6-3/4 4 3
80 6 4-1/2 3
85 5-1/2 4-1/2 3
90 4-3/4 5 2-3/4
95 4-1/2 4-3/4 2-3/4
100 4-3/8 4-1/2 2-3/4 105 3-1/8 4-1/2 2-1/2
*110 3-1/4 4-7/8 2-1/2
*WITH THE GATE MOUNTED ON THE CENTERLINE OF THE GATE POST THESE MOUNTING
DIMENSIONS WILL BE VERY CLOSE TO THE GATE POST.
FOR OTHER DIMENSIONS PLEASE CALL BYAN SYSTEMS.
413 Linden • Lusk, WY 82225 • (800) 223-2926
11
Page 13
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
413 Linden • Lusk, WY 82225 • (800) 223-2926
12
Page 14
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
RECOMMENDED WIRE SIZES
HIGH VOLTAGE A.C.
14 AWG TO 400 FEET 12 AWG TO 650 FEET 10 AWG TO 1000 FEET 8 AWG TO 1650 FEET 6 AWG TO 2650 FEET
LOW VOLTAGE A.C.
18 AWG TO 100 FEET 16 AWG TO 170 FEET 14 AWG TO 270 FEET 12 AWG TO 430 FEET 10 AWG TO 690 FEET 8 AWG TO 1100 FEET
LOW VOLTAGE D.C.
20 AWG TO 400 FEET 18 AWG TO 700 FEET 16 AWG TO 1100 FEET 14 AWG TO 1700 FEET 12 AWG TO 2800 FEET 10 AWG TO 4500 FEET
NOTE: THESE WIRE SIZES ARE ONLY GENERAL RECOMMENDATIONS. FEDERAL, STATE
AND LOCAL CODES ALWAYS TAKE PRECEDENCE. CONSULT THE N.E.C. OR LOCAL AUTHORITY HAVING JURISDICTION IF YOU HAVE WIRING CONCERNS
.
413 Linden • Lusk, WY 82225 • (800) 223-2926
13
Page 15
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
G2M CONTROL BOARD DESCRIPTION
G2M-115V/220V SINGLE PHASE
MICRO CONTROLLED BOARD
THIS ELECTRONIC CONTROL UNIT IS SUITABLE FOR SINGLE-PHASE MOTORS, AND CAN DRIVE UP TO TWO DIFFERENT MOTORS. THERE IS LEAF DELAY INCORPORATED WITH THE USE OF A PLUG IN CARD. 9 DIP SWITCHES CAN SELECT SOME DIFFERENT OPTIONS OF THE CONTROL UNIT. THERE ARE THREE POSSIBLE TIMING POTENTIOMETERS: OPENING TIME, AUTOMATIC CLOSING TIME, AND THE CLOSING TIME. A DIP SWITCH CAN DOUBLE THE OPENING AND CLOSING TIME.
CHARACTERISTICS:
BUTTONS:
REVERSING BUTTON:
THE FIRST ACTIVATION WILL MAKE THE GATE OPERATE. THE SECOND ACTIVATION WILL MAKE THE GATE STOP. THE THIRD ACTIVATION WILL REVERSE THE GATES DIRECTION WHILE DIP SWITCH 2 IS ON. WITH DIP SWITCH 2 OFF ON THE CLOSE CYCLE, THE GATE WILL AUTO REVERSE TO OPEN.
OPENING BUTTON:
USED ONLY TO OPEN AND HOLD OPEN THE GATE.
413 Linden • Lusk, WY 82225 • (800) 223-2926
14
Page 16
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
CLOSING BUTTON:
USED ONLY TO CLOSE THE GATE.
STOP BUTTON:
(NORMALLY CLOSE CONTACT), STOPS THE GATE IN OPENING/CLOSING.
THREE ADJUSTABLE TIMES
BLUE TIMER:
OPENING TIMER ONLY CONTROLS THE OPENING TIME BETWEEN 3 TO 30 SECONDS.
RED TIMER:
CLOSING TIMER ONLY CONTROLS THE CLOSE TIME BETWEEN 3 TO 30 SECONDS.
GREEN TIMER:
AUTOMATIC CLOSE TIMER WHEN THE GATE IS COMPLETELY OPEN THE TIMER IS ACTIVATED AND WILL AUTOMATICALLY CLOSE AFTER THE PROGRAMMED TIME.
NOTE: BUILT IN 2 SEC. TIMER TO STOP GATE BEFORE REVERSING OPERATION OCCURS.
OPEN/CLOSE LIMIT SWITCHES;
THEY STOP THE OPENING AND/OR CLOSING OPERATION. MUST REMOVE THE TWO JUMPER WIRES FROM TERMINAL 11 TO 12 AND 13 IF USED.
ENTRAPMENT SAFETY CONTACT:
IF ACTIVATED, THE RESULT IS REVERSING THE MOVEMENT IN BOTH OPENING AND CLOSING FOR 2 SECONDS. THEN STOPS, IF THE SAFETY CONTACT IS STILL ACTIVE THE ALARM WILL SOUND.
SAFETY REVERSING CONTACT:
THE RESULT IS REVERSING BACK TO OPEN WHILE THE GATE IS CLOSING, NOT ACTIVE WHEN OPENING.
POWER OUTPUT:
YOU CAN CONNECT MOTORS UP TO  HP
TIMER TABLE:
COLOR DESCRIPTION MINIMUM MAXIMUM GREEN AUTOMATIC CLOSING TIME 1 SECOND 2 MINUTES BLUE OPENING TIME 3 SECONDS 30 SECONDS RED CLOSING TIME 3 SECONDS 30 SECONDS
413 Linden • Lusk, WY 82225 • (800) 223-2926
15
Page 17
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
DIP SWITCH ASSEMBLY OPERATION MODE SELECTION;
No.
1 REVERSING STROKE FUNCTION
(OPERATOR FIRST WILL CLOSE FOR 1 SECOND)
2 STEP-BY-STEP FUNCTION* ACTIVE INACTIVE 3 AUTOMATIC CLOSING FUNCTION ACTIVE INACTIVE 4 REVERSING BUTTON IS NOT
OPERATIVE DURING OPENING 5 CLOSING ORDER BY CARS SAFETY CONTACT ACTIVE INACTIVE 6 SEE NOTE BELOW REF JP1 -------------- -------------­7 CARS SAFETY CONTACT IS
OPERATIVE DURING OPENING
*STEP-BY-STEP IS THAT EACH ACTIVATION OF THE REVERSE BUTTON WILL STOP THE GATE BEFORE CHANGING DIRECTION.
NOTE: THERE IS A JUMPER JP1 (BELOW THE REMOTE CONTROL CARD CONNECTOR) THAT CAUSES THE SELECTABLE OPTION No. 6 IN THE FOLLOWING MANNER:
JP1 OPEN: No. 6 ON IN THE POWER ON STATE, UNIT WILL DO A CLOSING
FUNCTION.
OFF IN THE POWER ON STATE, UNIT WILL DO AN OPENING
FUNCTION.
JP1 CLOSED: IN THE POWER ON STATE, THE DOOR REMAINS PAUSED. IN THIS CASE, THE SWITCH No. 6 CONTROLS THE FUNCTION OF
THE TRAFFIC LIGHTS. ON THE TRAFFIC LIGHTS CARD WILL ACT AS A FLASHING LIGHT CARD (UPPER RELAY) AND A GARAGE LIGHT CARD (LOWER RELAY). OFF THE TRAFFIC LIGHTS CARD WILL ACT AS GREEN AND RED LIGHTS.
OPTION ON OFF
ACTIVE INACTIVE
ACTIVE INACTIVE
ACTIVE INACTIVE
413 Linden • Lusk, WY 82225 • (800) 223-2926
16
Page 18
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
SELECTABLE OPTIONS SWITCH S3
No. OPTION ON OFF 1 EXTENDS RUN
TIME
2 REPOSITIONING
OPENING AND CLOSING TIME (30 SECONDS TO 1 MINUTE)
OPENING AND CLOSING TIME (3 SECONDS TO 30 SECONDS)
ACTIVE INACTIVE
THE DOOR *
* WITH THIS OPTION ACTIVE AND THE DOOR CLOSED THE DOOR IS CLOSED FOR 2 SECONDS EVERY HOUR, AND IF THE DOOR IS OPENED THE DOOR IS OPENED FOR 2 SECONDS EVERY HOUR.
TERMINAL BOARD
POWER TERMINALS (FROM TOP TO BOTTOM)
1. POWER SUPPLY
2. POWER SUPPLY
3. OPEN MOTOR 1
4. CLOSE MOTOR 1
5. COMMON MOTOR 1
6. OPEN MOTOR 2
7. CLOSE MOTOR 2
8. COMMON MOTOR 2
ACCESSORY TERMINALS FROM LEFT TO RIGHT ARE AS FOLLOWS:
1. OUTPUT PEOPLE OR ANIMALS ALARM CONTACT (N/O)
2. OUTPUT PEOPLE OR ANIMALS ALARM CONTACT (N/O)
3. 24V AC @ 1 AMP MAX. (COMMON)
4. 24V AC @ 1 AMP MAX. (POWER)
5. OUTPUT ELECTRIC LOCK 12VDC @ 1 AMP MAX.
6. OUTPUT ELECTRIC LOCK 12VDC @ 1 AMP MAX.
7. INPUT RESET ALARM (N/O)
8. INPUT SAFETY PEOPLE OR ANIMALS (N/C)
9. COMMON FOR SAFETY
10. INPUT SAFETY CAR (N/C)
11. COMMON LIMIT SWITCH
12. INPUT OPEN LIMIT SWITCH (N/C)
13. INPUT CLOSE LIMIT SWITCH (N/C)
14. INPUT STOP BUTTON (N/C)
15. COMMON FOR STOP BUTTON
16. COMMON TO COMMAND BUTTONS
17. INPUT CLOSE BUTTON
18. INPUT OPEN BUTTON
19. INPUT REVERSING BUTTON
413 Linden • Lusk, WY 82225 • (800) 223-2926
17
Page 19
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
CONTROL CONTACT
TERMINAL DESCRIPTION
1 ENTRAPMENT ALARM OUTPUT
2 ENTRAPMENT ALARM OUTPUT
3 24VAC OUTPUT @ 1 AMP MAX.
4 24VAC OUTPUT @ 1 AMP MAX.
5 ELECTRIC LOCK RELEASE 12VDC
6 ELECTRIC LOCK RELEASE 12VDC
7 ENTRAPMENT ALARM RESET
8 ENTRAPMENT SAFETY CONTACT
9 COMMON TO SAFETY CONTACT
10 REVERSING SAFETY CONTACT
11 COMMON TO LIMIT SWITCH
12 CLOSE LIMIT SWITCH
13 OPEN LIMIT SWITCH
14 STOP BUTTON
15 COMMON TO STOP BUTTON
16 COMMON TO CONTROL CONTACT
17 CLOSE COMMAND
18 OPEN COMMAND
19 REVERSE COMMAND
413 Linden • Lusk, WY 82225 • (800) 223-2926
18
Page 20
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
POWER & MOTOR CONNECTION
TERMINAL DESCRIPTION
1 COMMERCIAL POWER SUPPLY 115V NEUTRAL (WHITE)
[220V LINE (BLACK)]
2 COMMERCIAL POWER SUPPLY 115V LINE (BLACK)
[220V LINE (RED)]
3 MOTOR # 1 CLOSE DIRECTIONAL (BLACK)
4 MOTOR #1 OPEN DIRECTIONAL (BLACK
5 MOTOR #1 COMMON (WHITE)
6 MOTOR #2 CLOSE DIRECTIONAL (BLACK)
7 MOTOR #2 OPEN DIRECTIONAL (RED)
8 MOTOR #2 COMMON (WHITE)
413 Linden • Lusk, WY 82225 • (800) 223-2926
19
Page 21
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
SECOND MOTOR CARD T2M
CHARACTERISTICS:
THIS CARD IS SUITABLE FOR DRIVING A SECOND MOTOR THROUGH THE CONTROL UNIT, SELECTING THE OPENING DELAY TIME AND THE CLOSING DELAY TIME BETWEEN THE TWO MOTORS.
THE LIMIT SWITCHES OF THE SECOND MOTOR SHOULD BE CONNECTED TO THIS CARD. THESE SIGNAL INPUTS ARE OPT-COUPLED TO PREVENT MALFUNCTION DUE TO INTERFERENCE OR ATMOSPHERIC DISTURBANCES.
THE CONTROL UNIT POWERS THE CARD. THE CARD HAS TO BE INSERTED IN THE CONNECTOR MARKED AS “T.2 MOTOR” ON THE MAIN BOARD OF THE CONTROL UNIT.
IN THE OPENING OPERATION, MOTOR 1 ACTS FIRST AND IN THE CLOSING OPERATION, MOTOR 2 ACTS FIRST.
ADJUSTABLE TIMERS:
DESCRIPTION MINIMUM MAXIMUM
LEFT (MOTOR 1) 0 SECONDS 15 SECONDS
RIGHT (MOTOR 2) 0 SECONDS 15 SECONDS
TERMINAL BOARD:
OPERATION TERMINALS: (FROM TOP TO BOTTOM).
3 OPEN LIMIT SWITCH MOTOR 2 (NORMALLY CLOSED). 2 CLOSE LIMIT SWITCH MOTOR 2 (NORMALLY CLOSED). 1 COMMON LIMIT SWITCH MOTOR 2.
413 Linden • Lusk, WY 82225 • (800) 223-2926
20
Page 22
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
LOOP DETECTOR CONNECTIONS
THE MOLLEX CONNECTOR HAS 11 WIRE LEADS 12 INCHES LONG. THE PIN OUT IS AS FOLLOWS:
RED - POWER B+ BLACK - POWER B­BLUE - RELAY A COMMON (PULSE OR PRESENCE) ORANGE - RELAY A NORMALLY CLOSED (PULSE OR PRESENCE) YELLOW - RELAY A NORMALLY OPEN (PULSE OR PRESENCE) GREEN - RELAY B COMMON (PULSE ONLY) PURPLE - RELAY B NORMALLY OPEN (PULSE ONLY) BROWN - LOOP WIRE GRAY - LOOP WIRE WHITE - NOT USED
NOTE: LEADER WIRE FROM THE LOOP, WHETHER IT IS PREFORMED OR MANUFACTURED ON THE JOB SITE, MUST BE TWISTED A MINIMUM OF FIVE TURNS A FOOTS.
THE PROPER LOOP WIRE
WHY IS THE LOOP WIRE SO IMPORTANT? ONE OF THE MAIN CAUSES OF VEHICLE
LOOP DETECTOR FAILURES IS THE USE OF INFERIOR WIRE TYPES WHEN CONSTRUCTING THE LOOP. SINCE MOISTURE CAN CAUSE A SIGNIFICANT CHANGE IN THE DIELECTRIC CONSTANT OF THE INSULATION, WHICH RESULTS IN EXCESSIVE LOOP (FREQUENCY) DRIFT, YOU MUST CHOOSE A WIRE WITH AN INSULATION THAT IS MOST IMPERVIOUS TO MOISTURE. IT IS ALSO IMPORTANT TO CHOOSE A WIRE WITH A RUGGED, ABRASION RESISTANT INSULATION. REMEMBER THAT ALL PAVEMENTS ARE POROUS AND CONTAIN TRAPPED MOISTURE. WATER OR OTHER CHEMICALS WILL EVENTUALLY REACH THE INSULATION AND EITHER ATTACK THE INSULATION, BE ABSORBED BY IT, OR MIGRATE THROUGH TINY CRACKS IN THE INSULATION AND CHANGE THE DIELECTRIC OR BREAK DOWN THE INSULATION AND CAUSE SHORTS TO GROUND.
WHAT ABOUT THE WIRE? POLYVINYL CHLORIDE (PVC) INSULATION (TFFN, THHN,
AND THHN-THWN) SHOULD BE AVOIDED SINCE IT TENDS TO ABSORB MOISTURE AND CRACKS VERY EASILY. THE INSULATION IS THIN AND VERY SOFT, LEAVING IT VULNERABLE TO DAMAGE DURING INSTALLATION AND RAPID AGE CRACKING AFTER SEALING. ANY ONE OF THE ABOVE MENTIONED WIRE TYPES HAS ONLY 0.015” OF INSULATION FROM12 GA. TO 18 GA. IF THERE IS ANY DOUBT ABOUT IT’S VULNERABILITY, CRIMP THE INSULATION WITH A PAIR OF PLIERS AND SEE HOW IT CRACKS. SEE HOW EASY IT STRIPS WITH A POCKETKNIFE. WHAT WOULD AN UNNOTICED PIECE OF WIRE OR A SHARD OF GLASS BURIED IN THE PAVEMENT SLOT DO
413 Linden • Lusk, WY 82225 • (800) 223-2926
21
Page 23
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
TO THE INSULATION? THE OUTER DIAMETER IS 0.115” FOR 14 GA. WIRE AND 0.013” FOR 16 GA. WIRE. WHEN INSTALLED IN A ” (0.250) SLOT, AS IS OFTEN DONE, THE TURNS OF WIRE CAN LAY SIDE BY SIDE IN THE SLOT AND THE TURNS TWIST UNDER THE PRECEDING TURNS AND NOT STACK SNUGLY IN A SINGLE LAYER, AS THEY SHOULD BE. THIS WILL CAUSE REDUCED LOOP EFFICIENCY.
WHAT TYPE OF WIRE SHOULD I USE? CROSS LINKED POLYETHYLENE (XLPE) OR
POLYESTER INSULATION PROVIDES EXCELLENT PROTECTION FOR WIRE USED IN SAW CUT LOOP INSTALLATIONS. BOTH TYPES ARE ABRASION RESISTANT, MUCH HARDER (NOT IMPOSSIBLE) TO STRIP, AND VERY MOISTURE RESISTANT.
SUMMARY: THE USE OF THE CORRECT TYPE OF WIRE FOR THE JOB, AS WELL AS THE
PROPER INSTALLATION TECHNIQUES, WILL AVOID FREQUENT SERVICE CALLS BEGINNING SOON AFTER INSTALLATION AND RESULT IN YEARS OF TROUBLE FREE SERVICE AND IN SATISFIED CUSTOMERS.
COMPARISON CHART
INSULATION TYPE
RESISTANCE TO CHEMICALS XLPE THHN
ETHYL ALCOHOL HIGH GOOD ACETONE HIGH GOOD GASOLINE HIGH FAIR PHYSICAL CONDITIONS ABRASION RESISTANCE E F-G RESISTANCE TO DEGREASER SOLVENT E P-F LOW TEMPERATURE FLEXIBILITY E P-F ELECTRICAL F-O F-G WATER ABSORBENCY (% IN 24 HOURS) 0.01 0.75 SERVICE TEMPERATURE RANGE (CELSIUS) -65 TO +150 -55 TO +105 P=POOR F=FAIR G=GOOD E=EXCELLENT O=OUTSTANDING
413 Linden • Lusk, WY 82225 • (800) 223-2926
22
Page 24
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
413 Linden • Lusk, WY 82225 • (800) 223-2926
23
Page 25
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
413 Linden • Lusk, WY 82225 • (800) 223-2926
24
Page 26
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
413 Linden • Lusk, WY 82225 • (800) 223-2926
25
Page 27
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
FOUR YEAR LIMITED WARRANTY
This warranty pertains only to products manufactured for/or by Byan Systems, Inc. for gate operating systems, accessories, and equipment. These products are warranted against all defective material for forty-eight months from the date of sale.
Defective material returned must be prepaid and accompanied by a Byan Systems, Inc. return authorization number within the warranty period for repair or replacement at Byan Systems, Inc. option. Byan Systems, Inc. will return warranted item freight prepaid ground service via U.P.S.
The warranty extends only to wholesale customers who buy direct from Byan Systems, Inc. through normal distributor channels. Byan Systems, Inc. does not warranty its products to the end user/consumer. Consumer should inquire from their selling dealer as to the nature and extent of the dealer’s warranty, if any. There are no obligations or liabilities on the part of Byan Systems, Inc. for consequential damages arising out of or in connection with the use or performance of these products or other indirect damages with respect to loss of property, revenue or profit, cost of removal, original installation or reinstallation.
Warranty will be considered void if damage or malfunction was due to improper, inadequate or negligent installation or use of improper power source, or damage was caused by fire, flood, lightning, electrical power surge, explosion, windstorm or hail, aircraft or vehicles, vandalism, riot or civil commotion, or acts of god. All implied warranties for fitness are limited in duration to forty-eight months from date of sale. Some states do not allow how long an implied warranty lasts, so this limitation may not apply to you. This warranty by Byan Systems, Inc. is in lieu of all warranties expressed or implied.
Product delivery time is subject to availability. Byan Systems, Inc. is not responsible for any damages caused by delays in shipping or product availability.
413 Linden • Lusk, WY 82225 • (800) 223-2926
26
Page 28
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
END USER SAFETY
“THE GATE AUTOMATION AND ACCESS CONTROL MANUFACTURER” HAS NO CONTROL OVER THE GATE SYSTEM YOU HAVE AUTOMATED. THE WORD “SYSTEM” AUTOMATION EQUIPMENT, ACCESSORY DEVICES, THE CONSTRUCTION AND INSTALLATION THEREOF.
VEHICULAR GATE OPERATING SYSTEMS PROVIDE CONVENIENCE AND SECURITY TO THEIR USERS. BECAUSE THESE MACHINES PRODUCE SUCH HIGH LEVELS OF FORCE, ALL GATE SYSTEM DESIGNERS, INSTALLERS AND END USERS MUST BE AWARE OF THE POTENTIAL HAZARDS ASSOCIATED WITH IMPROPERLY DESIGNED, INSTALLED OR MAINTAINED SYSTEMS.
EACH COMPONENT MUST WORK IN UNISON TO PROVIDE THE END USER, VISITORS AND SUBSEQUENT OWNERS WITH PROPER OPERATION OF ALL AUTOMATION, SAFETY AND ACCESS CONTROL EQUIPMENT.
IT IS THE RESPONSIBILITY OF THE DESIGNER, INSTALLER AND PURCHASER, THAT THE TOTAL SYSTEM IS SAFE FOR THE PARTICULAR APPLICATION.
THE END USERS RESPONSIBILITY IS ALWAYS PRESENT. ASSURANCE OF SAFETY RESTS WITH THE USER OF THE GATE SYSTEM, AT ANY PARTICULAR TIME.
GATE SYSTEMS SHOULD BE PROTECTED AS MAY BE NECESSARY FROM CHILDREN AND PETS BY WHATEVER MEANS NECESSARY. MOVING DEVICES ALWAYS PRESENT PEOPLE, PETS AND PROPERTY WITH CERTAIN RISKS AND HAVE POTENTIAL FOR HARM.
THE FOLLOWING LIST OF PRECAUTIONS HAS BEEN PREPARED FOR YOUR REVIEW. THIS LIST IS NOT ALL-INCLUSIVE NOR IS IT REPRESENTED AS SUCH. PLEASE ASK YOU INSTALLER ANY QUESTIONS YOU HAVE NOW, OR LATER, ABOUT THE INSTALLATION, OPERATION, OR SAFETY FEATURES OF YOUR GATE SYSTEM.
1. BE SURE THE OPERATING AND SAFETY INSTRUCTIONS ARE AVAILABLE TO
ALL PERSON THAT WILL OPERATE THE GATE SYSTEM.
2. KEEP GATE SYSTEM OPERATING AREA CLEAR OF ALL OBSTRUCTIONS. STAY
CLEAR OF THE OPERATING AREA WHEN THE GATE SYSTEM IS IN USE.
3. DO NOT ALLOW CHILDREN OR PETS NEAR THE GATE SYSTEM. IN A
RESIDENTIAL OR MULTIFAMILY DWELLING, IT MAY BE NECESSARY TO FENCE OFF PORTIONS OF THE SYSTEM. IT MAY BE NECESSARY TO MOUNT
HEREIN REFERS TO THE GATE POST, GATE LEAF, HINGING, ALL
413 Linden • Lusk, WY 82225 • (800) 223-2926
27
Page 29
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
PROTECTION DEVICES IN THE AREA, ON THE GATE, OR THE EQUIPMENT ITSELF.
4. “CAUTION!!!”
AROUND THE ELECTRICAL ENCLOSURES
5. NEVER OPERATE A GATE SYSTEM WITHOUT VISUAL CONTACT SO IT CAN BE
SUSPENDED IF NECESSARY.
6. SECURE AND LABEL POWER CABINETS OR EQUIPMENT COVERS.
7. IF THE GATE HAS AN OPEN ROLLER, EACH MUST HAVE A GUARD SUITABLE
TO PROTECT PERSONS, PETS AND CLOTHING, WHICH COULD BE ENTRAPPED, NO MATTER HOW UNLIKELY IT MAY APPEAR AT FIRST GLANCE.
8. ENSURE ALL SAFETY DEVICES ARE TESTED REGULARLY.
9. DO NOT TIGHTEN CLUTCHES OR INCREASE PRESSURES TO COMPENSATE FOR
A POOR GATE SYSTEM DESIGN AND/OR THE GATE LEAF.
10. INSTALL WARNING SIGNS ON BOTH SIDES OF THE GATE LEAF.
11. HAVE PROPER LIGHTING INSTALLED FOR NIGHT TIME USE.
12. NEVER BECOME COMPLACENT WITH THE OPERATION OF A GATE SYSTEM.
SCHEDULE PERIODIC INSPECTION AND/OR MAINTENANCE.
NEVER ALLOW CHILDREN TO RIDE ON THE GATE(S) OR PLAY
413 Linden • Lusk, WY 82225 • (800) 223-2926
28
Page 30
BYAN SYSTEMS, INC.
Automated Gate and Access Control Products
CUSTOMER ACKNOWLEDGMENT
DEAR _________________________________
(CUSTOMER/COMPANY NAME)
VEHICULAR GATE OPERATING SYSTEMS PROVIDE CONVENIENCE AND SECURITY TO THEIR USERS. BECAUSE THESE MACHINES PRODUCE SUCH HIGH LEVELS OF FORCE, ALL GATE OPERATING SYSTEM DESIGNERS, INSTALLER AND END USERS NEED TO BE AWARE OF THE POTENTIAL HAZARDS ASSOCIATED WITH IMPROPERLY DESIGNED, INSTALLED OR MAINTAINED SYSTEMS.
EACH COMPONENT MUST WORK IN UNISON TO PROVIDE THEIR END USER, VISITORS AND SUBSEQUENT OWNER WITH CONVENIENCE, SECURITY AND SAFETY.
“BYAN SYSTEMS” ROQUET HYDRAULIC GATE OPERATORS AND ACCESSORY EQUIPMENT ARE INTENDED TO BE PART OF A TOTAL OPERATING SYSTEM. WE HIGHLY ENDORSE AND RECOMMEND THE USE OF SAFETY ACCESSORIES AND VISUAL WARNING INDICATORS IN THE FORM OF LIGHTS, SOUNDERS AND PLACARDS PROPERLY PLACED.
IT IS THE RESPONSIBILITY OF THE PURCHASER, DESIGNER AND INSTALLER, THAT THE TOTAL SYSTEM IS SAFE FOR THE PARTICULAR APPLICATION.
WE ARE PLEASED YOU HAVE SELECTED “BYAN SYSTEMS” ROQUET OPERATORS FOR YOUR VEHICULAR GATE AUTOMATION. ON BEHALF OF OUR DISTRIBUTION AND DEALER NETWORK, MAY I EXTEND TO YOU OUR GRATITUDE AND COMMITMENT TO FUTURE SUPPORT.
THANK YOU FOR REVIEWING THIS INFORMATION. VERIFY WITH YOUR INSTALLER THAT YOU UNDERSTAND ALL THE OPERATING EQUIPMENT AND THE FUNCTIONS OF THE SAFETY ACCESSORIES.
PLEASE SIGN AND DATE THIS FORM ACKNOWLEDGING YOU HAVE READ, UNDERSTAND AND RATIFY THE INFORMATION HEREIN.
X_______________________________________ DATE:___/___/___
413 Linden • Lusk, WY 82225 • (800) 223-2926
29