FAAC 415 L LS 24V User Manual

Page 1
Swing Gate Operator
FAAC International Inc. Headquarter & East Coast Operations 5151 Sunbeam Road Suites 9-11 Jacksonville, FL 32257 Tel. 866 925 3222 www.faacusa.com
FAAC International Inc. West Coast Operations
357 South Acacia Avenue
Unit 357
Fullerton, CA 92831
Tel. 800 221 8278
415 L LS 24V
UL325 - UL991
Page 2
2
FAAC Model 415 L LS 24V Swing Gate Operator
CONTENTS
FAAC Model 415 L LS 24V - Rev: 02 - JUN 2012
Read this instruction manual before you begin installing the product.
= Information regarding personal safety and proper maintanence of the product.
IMPORTANT SAFETY INFORMATION 3
Important Safety Instructions 3
Important Installation Instructions 3
General Safety Precautions 4
UL325 Gate Operator Classications 5
Installing the Warning Signs 5
1. DESCRIPTION 6
2. DIMENSIONS 6
3. TECHNICAL SPECIFICATIONS 7
4. INSTALLATION 7
4.1 Electrical Set-up (Standard System) 7
4.2 Preliminary Checks 7
4.3 Installation Dimensions 8
4.4 Installing the Operator 9
4.5 Wiring the Operator 10
4.6 Adjusting the Limit Switches 11
4.7. Start-up 12
5. MANUAL OPERATION 12
6. MAINTENANCE 13
7. REPAIRS 13
8. 415 L LS PARTS DIAGRAM 14
E024U CONTROL BOARD AND LIMITED WARRANTY A2 - A18
Page 3
3
FAAC Model 415 L LS 24V Swing Gate Operator
1. Install the gate operator only when the following condi­tions have been met:
The operator is appropriate for the type and usage
class of the gate.
All openings of a horizontal slide gate have been
guarded or screened from the bottom of the gate to a minimum of 4 feet (1.25 m) above the ground to prevent a 2.25 inch (55 mm) diameter sphere from passing through openings anywhere in the gate or through that portion of the adjacent fence that the gate covers when in the open position.
All exposed pinch points are eliminated or guarded.
Guarding is supplied for exposed rollers.
2. The operator is intended for installation on gates used by vehicles only. Pedestrians must be provided with a separate access opening.
3. To reduce the risk of entrapment when opening and closing, the gate must be installed in a location that allows adequate clearance between the gate and adjacent structures. Swinging gates shall not open outward into public access areas.
4. Before installing the gate operator, ensure that the gate has been properly installed and that it swings freely in both directions. Do not over-tighten the operator clutch or pressure relief valve to compensate for a damaged gate.
5. User controls must be installed at least 6 feet away from any moving part of the gate and located where the user is prevented from reaching over, under, around or through the gate to operate the controls. Controls located outdoors or those that are easily accessible shall have security features to prevent unauthorized use.
6. The Stop and/or Reset buttons must be located within line-of-sight of the gate. Activation of the reset control shall not cause the operator to start.
7. All warning signs and placards must be installed and easily seen within visible proximity of the gate. A minimum of one warning sign shall be installed on each side of the gate.
8. For gate operators that utilize a non-contact sensor (photo beam or the like):
See instructions on the placement of non-contact
sensors for each type of application.
Exercise care to reduce the risk of nuisance tripping,
such as when a vehicle trips the sensor while the gate is still moving.
Locate one or more non-contact sensors where the
risk of entrapment or obstruction exists, such as at the reachable perimeter of a moving gate or barrier.
Use only FAAC “Photobeam” photoelectric eyes to
comply with UL325.
Important Installation Instructions
WARNING: TO REDUCE THE RISK OF SEVERE INJURY OR DEATH:
READ AND FOLLOW ALL INSTRUCTIONS.
Never let children operate or play with the gate
controls. Keep remote controls away from children.
Always keep people and objects away from the
gate. NO ONE SHOULD CROSS THE PATH OF A MOVING GATE.
Test the gate operator monthly. The gate MUST
reverse on contact with a rigid object or when an object activates a non-contact sensor. If necessary, adjust the force or the limit of travel and then retest the gate operator. Failure to properly adjust and retest the gate operator can increase the risk of injury or death.
Use the manual release mechanism only when the
gate is not moving.
KEEP GATE PROPERLY MAINTAINED. Have a qualied service person make repairs to gate
hardware.
The entrance is for vehicles only. Pedestrians must use a separate entrance.
SAVE THESE INSTRUCTIONS.
IMPORTANT SAFETY INFORMATION
Important Safety Instructions
Page 4
4
FAAC Model 415 L LS 24V Swing Gate Operator
Gate Construction
Vehicular gates should be constructed and installed in accordance with ASTM F2200: Standard Specica­tion for Automated Vehicular Gate Construction.
For more information, contact ASTM at: www.astm.org
Installation
If you have any questions or concerns regarding the
safety of the gate operating system, do not install the operator and consult the manufacturer.
The condition of the gate structure itself directly
affects the reliability and safety of the gate operator.
Only qualied personnel should install this equipment.
Failure to meet this requirement could cause severe injury and/or death, for which the manufacturer cannot be held responsible.
The installer must provide a main power switch that
meets all applicable safety regulations.
It is extremely unsafe to compensate for a damaged
gate by increasing hydraulic pressure.
Install devices such as reversing edges and photo
beams to provide better protection for personal property and pedestrians. Install reversing devices that are appropriate to the gate design and application.
Before applying electrical power, ensure that voltage
requirements of the equipment correspond to the supply voltage. Refer to the label on your gate operator system.
Usage
Use this equipment only in the capacity for which it
was designed. Any use other than that stated should be considered improper and therefore dangerous.
The manufacturer cannot be held responsible
for damage caused by improper, erroneous or unreasonable use.
If a gate system component malfunctions, disconnect
the main power before attempting to repair it.
Do not impede the movement of the gate, you may
injure yourself or damage the gate system as a result.
This equipment may reach high thermal temperatures
during normal operation, therefore use caution when touching the external housing of the gate operator.
Use the manual release mechanism according to the
procedures presented in this manual.
Before performing any cleaning or maintenance
operations, disconnect power to the equipment.
All cleaning, maintenance or repair work must performed by qualied personnel.
General Safety Precautions
9. For gate operators that utilize a contact sensor (edge sensor or similar):
Locate one or more contact sensors where the risk
of entrapment or obstruction exists, such as at the leading edge, trailing edge, and post mounted both inside and outside of a vehicular horizontal slide gate
Locate one or more contact sensors at the bottom
edge of a vehicular vertical lift gate.
Locate one or more contact sensors at the bottom
edge of a vertical barrier (arm).
Locate one or more contact sensors at the pinch
point of a vehicular vertical pivot gate.
Locate hard-wired contact sensors and wiring so
that communication between sensor and gate operator is not subjected to mechanical damage.
Locate wireless contact sensors, such as those
that transmit radio frequency (RF) signals, where the transmission of signals are not obstructed or impeded by building structures, natural landscaping or similar hindrances. Wireless contact sensors shall function under their intended end-use conditions.
Use only FAAC MSE MO, CN60 or M60 edge
sensors.
Important Installation Instructions (continued)
Page 5
5
FAAC Model 415 L LS 24V Swing Gate Operator
RESIDENTIAL VEHICULAR GATE OPERATOR CLASS I
A vehicular gate operator system intended for use in a single family dwelling, garage or associated parking area.
UL325 Gate Operator Classications
COMMERCIAL / GENERAL ACCESS VEHICULAR GATE OPERATOR CLASS II
A vehicular gate operator system intended for use in commercial locations or buildings such as multi-family housing
units (ve or more single family units), hotels, parking garages, retail stores or other buildings that service the general
public.
INDUSTRIAL / LIMITED ACCESS VEHICULAR GATE OPERATOR CLASS III
A vehicular gate operator system intended for use in industrial locations or buildings such as factories, loading docks or other locations not intended to service the general public.
RESTRICTED ACCESS VEHICULAR GATE OPERATOR CLASS IV
A vehicular gate operator system intended for use in guarded industrial locations or buildings such as airport security areas or other restricted access locations that do not service the general public, and in which unauthorized access is prevented via supervision by security personnel.
This FAAC swing gate operator is supplied with two warning signs to alert people that a possible hazard exists and that appropriate actions should be taken to avoid the hazard or to reduce exposure to it.
Permanently install one warning sign on each side of the gate so they are fully visible to
trafc and pedestrians.
Use appropriate hardware such as metal screws (not supplied) to permanently install each warning sign.
Installing the Warning Signs
Page 6
Model 415 L LS 24V Swing Gate Operator
1. DESCRIPTION
2. DIMENSIONS
Built-in security and anti-crushing measures of the 415 Operator include built in reverse on contact and a torque adjustment that controls the force transmitted to the gate leaf through the 415 Operator.
The Manual Release mechanism is a key accessed device that disengages (or engages) the cylinder on the 415 Opera­tor. When the drive is disengaged, you can manually open and close the gate leaf by hand.
Such manual operation of the gate is necessary during installation and useful during prolonged power failures. The torque of the 415 Operator is set using the Control Panel.
Reversing devices (such as inductive loops and photocells) should be installed to provide non-contact reversing opera­tion.
The 415 Operator automated system was designed and built for controlling vehicle access. Avoid any other use what so ever.
NOTES:
Use suitable conduit to lay electric cables.
To avoid any kind of interference, always use individual
sheaths to separate low-voltage accessories and control cables from 115V~ power supply cables.
6
FAAC Model 415 L LS 24V Swing Gate Operator
Fig. 2
The FAAC 415 is an automatic gate operator for swinging gate leafs. The 415 Operator is useful in residential applica­tions and can accommodate gate leafs up to 14 ft long. The self-contained 415 Operator consists of an electric motor that drives a worm screw housed in an aluminum casing.
The locking provided by the 415 Operator (in the fully opened and fully closed positions) is a service device rather than a security device.
Also, for the protection and proper operation of the 415 Op­erator, each operator has built in limit switches, so positive stops are not needed.
Pos. Description
1 Operator
2 Release Device
3 Rod
4 Front Bracket
5 Rear Bracket
6 Rear Fitting
7 Rear Fitting Pin
8 Terminal Board Cover
Fig. 1
37
* Measurements in Inches
Page 7
3. TECHNICAL SPECIFICATIONS
4. INSTALLATION
Pos. Description Cables
1 Operators 2 x AWG 14 (max 30’)
AWG 12 (max 50’) AWG 10 (max 100’)
1 Limit Switches 3 x AWG 20
2 Control Unit 3 x AWG 14 (AC power)
3 TX Photocells 4 x AWG 20
4 RX Photocells 2 x AWG 20
5 Key-operated Switch 2 x AWG 20
6 Flashing Lamp 2 x AWG 14
7 Receiver 3 x AWG 20
8 Mechanical Stops -
SPECIFICATION 415 L LS 24V
Power Supply 24 VDC
Power (W) 70
Current (A) 3
Thrust (lbf) 630
Effective Stroke (inches) 15
Rod Extension Speed (inches/sec) 0.5
Max Leaf Length (feet) 15
Cycle per hour at 68˚F (approx) 75
Class or Operation Residential
Ambient Operating Temperature
Range (˚F)
-4 to +131
Operator Weight (lbs) 17.5
Protection Class IP 54
4.2 Preliminary Checks
The condition of the gate structure directly affects the reliabil­ity and safety of the automated system. Before installing the 415 Operator, prepare the gate for the operator by performing the following:
Make sure that the gate structure is solidly built. Add rein-
forcing crosspieces to the gate leaves if necessary.
Make sure that the gate moves smoothly on its hinges
without excessive friction by swinging it opened and closed by hand. If necessary, lubricate all the gate’s moving parts.
Positive stops are not needed with the 415 operator, the built limit switches can be used to limit the rod travel
4.1 Electrical Set-up (Standard System)
4.3 Installation Dimensions
Determine the mounting position of the operator with reference to Fig. 4.
Ensure that the distance between the open leaf and any obstacles (walls, fences etc.) is greater than the dimensions of the operator.
* Dimensions
in Inches
7
FAAC Model 415 L LS 24V Swing Gate Operator
Fig. 3
Fig. 4
MODEL 415 L LS 24V
90° 110°
A 7⅝ 6⅝
B 7⅝ 6⅝
D
(1)
5 4⅜
Z
(2)
L 50¾ 50¾
E
(2)
(1)
max. dimension
(2)
min. dimension
Page 8
Guidelines for Determining Installation Dimensions
For 90° leaf openings: A+B=L
For leaf openings exceeding 90°: A+B<L
Smaller A and B dimensions provide higher periph-
eral leaf speed.
Limit the difference between A and B dimensions to
less than 1.5 inches. Greater differences may cause
speed variations during gate opening and closing movements.
Maintain a Z dimension that ensures that the operator
does not strike the pillar.
In LS models, limit switches are triggered during the
rst and last 1.25 inches of gate travel. Therefore select A and B dimensions that utilize the entire opera­tor travel. Short travel ranges can restrict or cancel the limit switch adjustment range.
If pillar dimensions or hinge position do not allow installa­tion of the operator, cut a niche into the pillar (as shown in Fig. 5) in order to maintain the A dimension as determined. The dimensions of the niche should enable easy installa­tion, rotation and operation of the release device.
4.4. Installing the Operator
1. Fix the rear bracket in the position you previously deter­mined in Section 4.3.1.
For iron pillars, carefully weld the bracket directly onto
the pillar (Fig. 6).
For masonry pillars, use a suitable plate (optional) for
which to attach the unit (Fig. 7). Make use of a suitable fastening system. Then carefully weld the bracket to the plate.
While fastening the bracket, use a level to ensure that it is perfectly horizontal.
2. Assemble and attach the rear tting to the operator (Fig.
8).
3. Set the 415 Operator to manual operation (see Section 6).
4. Completely extend the rod until it reaches the limit stop (Fig. 9, Ref. 1).
5. Re-lock the operator (see Section 6.1).
8
FAAC Model 415 L LS 24V Swing Gate Operator
Fig. 5
Fig. 7
Fig. 6
Fig. 8
Page 9
6. Turn the rod one half revolution clockwise (Fig. 9, Ref. 2).
7. Assemble the front bracket as shown in Fig. 10.
8. Fix the operator to the rear bracket by means of the sup­plied pins as shown in Fig. 11.
Attention: allow the bracket to cool before fastening the operator to it.
9. Close the leaf and, while keeping the operator perfectly horizontal, determine the fastening point of the front bracket (Fig.12).
10. Temporarily x the front bracket with two welding spots
(Fig.12).
Note: if the gate structure does not allow a xed bracket
fastening it is necessary to create a sturdy supporting base in the gate structure.
11. Release the operator (see Section 6) and manually check that the gate moves regularly without friction or hin­drances. Ensure that it opens completely and stops at the mechanical travel stops.
12. Perform the necessary corrective measures and repeat from Step 11.
13. Temporarily release the operator from the front bracket and permenantly weld the bracket.
If the leaf structure prevents the bracket from being welded, screw it to the leaf with adequate securing hardware.
Note: Grease all fastening pins of the ttings.
4.5. Wiring the Operator
IMPORTANT : Use the supplied cable or a similar UL ap­proved cable for outdoor use.
A terminal block is available in the lower part of the operator to connect the motor and the limit switches
Motor Wiring Instructions:
1. Open one of the pre­drilled holes in the sup­plied cover (Fig.13).
2. Fit the supplied cable gland.
3. Connect the motor (refer to Fig.14 and accompany­ing table)
9
FAAC Model 415 L LS 24V Swing Gate Operator
Fig. 9
Fig. 11
Fig. 10
Fig. 12
Fig. 13
Page 10
Limit Switches wiring in­structions:
Limit switches are wired in the same terminal block where the motor wiring has been in­stalled. Wire the limit switches as follows:
1. Open the second pre­drilled hole in the cover, see Fig. 15.
2. Fit the supplied cable gland, see Fig. 15.
3. Insert the cable and con­nect it to the terminals, following the connections
specied in Figure 16
Table.
Close and secure the cover with the four supplied screws
(Fig. 17).
4.6 Adjusting the Limit Switches
Note: Limit switches are triggered during the rst and the last
1.25 inches of travel. Therefore, the operator should utilize the entire available length of travel during the opening phase. Shorter travels can limit or completely cancel the limit switch adjustment range.
Limit switches adjustment is carried out as follows:
1. Unscrew the upper fastening screw, Fig.18 Ref.A, and remove the cap, Fig.18 Ref.B.
2. To adjust the closing limit switch FCC, turn the adjust-
ing screw clockwise (Fig.19 Ref.A) to increase rod stroke and counter-clockwise to reduce it.
3. To adjust the opening limit switch FCA, turn the adjust-
ing screw counter-clockwise (Fig. 20 Ref. A) to in­crease rod stroke and clockwise to reduce it.
4. Perform a pair of test cycles to check the correct posi-
tion of the limit switch. If the limit switch needs ad­ditional adjustment, repeat the operation starting from Step 2.
10
FAAC Model 415 L LS 24V Swing Gate Operator
Fig. 14
Figure 14 Table
415 (24 VDC)
POS. COLOR DESCRIPTION
1 White Motor Lead 1
- Not used -
2 Brown Motor Lead 2
Fig. 15
Fig. 16
Figure 16 Table
POS. COLOR DESCRIPTION
1 Blue Common
2 Brown Closing Limit Switch (FCC)
3 Black Opening Limit Switch (FCA)
Fig. 18
Fig. 19
Fig. 17
Page 11
5. Reposition the cap (Fig. 18 Ref. B) and tighten the fastening screw (Fig. 18 Ref. A).
4.7. Start-up
ATTENTION: Cut power before performing any work on the system or operator.
Carefully observe the GENERAL SAFETY RULES.
Following the indications in Fig. 3, lay the proper cable conduits and make the electrical connections of the control board and chosen accessories.
1. Power up the system and determine the status of the LEDs (as shown in the table of the control board instructions).
2. Program the control board according to your needs by following the control board instructions.
3. Test the system, carefully checking the operating ef- ciency of the motor and of all the accessories connect­ed to it, paying special attention to the safety devices
If the gate system needs to be moved manually due to lack of power or to an operator malfunction, proceed as follows:
1. Cut power by means of the safety circuit breaker (even in the event of a power outage).
2. Slide the protective cap, Fig. 21, Ref. 1.
3. Insert the key and turn it 90°, Fig .21, Ref. 2.
4. To release the operator, turn the control lever 180° in the direction indicated by the arrow on the release system, Fig.21, Ref. 3.
5. Open and close the leaf manually.
7. REPAIRS
For any repairs, contact an authorized FAAC repair center.
Fig. 21 Ref. 2
Note: To keep the operator in manual operation, the control
lever should be left in its current position (turned 180˚) and
power should be cut to the system.
Restoring Normal Operation
To restore normal operating conditions, proceed as follows:
1. Turn the release system’s control lever 180° in the op­posite direction of the arrow.
2. Turn the release key 90° and remove it.
3. Close the protection cover.
4. Power up the system and perform a complete cycle of movement to check that the automated system is cor­rectly restored.
Fig. 21 Ref. 3
5. MANUAL OPERATION
To ensure safety and trouble-free operation, an overall check of the system should be carried out every 6 months.
6. MAINTENANCE
11
FAAC Model 415 L LS 24V Swing Gate Operator
Fig. 20
Fig. 21 Ref. 1
Page 12
12
FAAC Model 415 L LS 24V Swing Gate Operator
8. 415 L LS PARTS DIAGRAM
POS. P/N DESCRIPTION
01 72200165 REAR MOUNTING BRACKET
02 72840065 REAR MOUNTING PLATE
03 718366 LONG PIN
04 7182075 SHORT PIN
05 N/A
HEX NUT
06 7221115 REAR FORK
07 716148 UPPER BODY
08 428403 MANUAL RELEASE ASSEMBLY
09 60202145 MANUAL RELEASE CAM
10 60202155 MANUAL RELEASE LEVER
11 716151 PROTECTIVE COVER
12 490108 LIMIT SWITCH ASSEMBLY
13 718354 FRONT PIN WITH SEEGER
14 N/A 4.2X13mm SELF TAPPING SCREW
15 728271 FRONT MOUNTING BRACKET
16 711027 LIMIT SWITCH ADJUSTERS COVER
17 490104 CYLINDER
POS. P/N DESCRIPTION
18 718367 SCREW DRIVE PIN WITH SEEGER
19 499399 LOCKING LOWER FLANGE
20 N/A 6.3X19mm SELF TAPPING SCREW
21 60202225 GEAR (piston)
22 N/A 4.8X13mm SELF TAPPING SCREW
23 60202165 BUSHING
24 60202215 GEAR (motor)
25 60202205 24V MOTOR
26 709324 GASKET
27 60202175 ELECTRIC CABLE COVER
28 716149 LOWER HALF BODY
29 490106 415 LS SKIN PACK
31 7120885 LOCK KEY
Page 13
SETTING
+
J24
DL19 DL20 DL21 DL22DL14 DL15 DL16 DL17 DL18
Main power supply
115/230 V~ 50/60 Hz switchable
Secondary power supply
24 Vdc - 16 A max.
(min. 20 Vdc. - max. 36 Vdc.)
Power consumption
stand-by = 4W max. = 400 W
Max load per motor
7 A
Accessory power supply
24 Vdc - 500 mA
Battery charge current
150 mA
Operating temperature
-4 °F.........+131 °F
Protection fuses
All self-resetting
Main power fuse
2.5 A Timed
Operating Logics
E, A, S, EP, AP, SP, B, C
Operating time out
10 min.
Pause time Programmable (0 to 4 min)
with trimmer
Motor force, speed, obstacle sensitivity, closing delay
Programmable with
dedicated trimmer
Connector inputs
Power supply, Battery,
Radio receiver, USB
Terminal strip inputs Encoder, Open A, OpenB, Stop,
Open safety fotocell, Closing safety
fotocell, Limit switches
Terminal strip outputs Lamp, Buzzer, Motors, Lock,
Programmable OUT,
accessory power supply
Programming
With trimmers,
dipswitches
and pushbutton
RADIO
Connector for the radio receiver
BATTERY
Connector for the backup battery
J24 Jumper to disable battery charging
(With the jumper present the battery
is charged)
POWER SUPPLY
DC Power supply input
TR1 to TR6
Programming Trimmers
+24 LED
DC power indicator
SW1 - SETUP
Pushbutton for automatic setup
DS1 - DS2
Programming dipswitches
LED ERROR
Troubleshooting indicator
USB A
USB connection for software upgrade
On the radio connector it’s possible to plug in receivers RP and RP2. With a single channel radio RP it will be possible to activate only the OPEN A input, with a dual channel radio RP2 it will be possible to activate both OPEN A and OPEN B inputs. Plug in the radio board with the component side towards the internal part of the board.
Make sure you insert or disconnect the board ONLY with the power off.
1. E024U CONTROL BOARD DESCRIPTION & CHARACTERISTICS
1.1 TECHNICAL SPECIFICATIONS 1.2 LAYOUT AND COMPONENTS
1.3 RADIO CONNECTION
Fig. A1
A2
E024U CONTROL BOARD
Page 14
A B STP CL OP OPEN FSW
Fig. A2
PIN LABEL FUNCTION
2 EASY 2 EASY Input for bus 2easy accessories (encoder)
1 OPEN A N.O. Contact for total opening command
2 OPEN B /
CLOSE
OPEN B: N.O. Contact for opening of leaf 1 only
(with only one leaf the opening stops at 50% of traveling)
CLOSE (LOGIC B-C): N.O. Contact for closing command
3 STOP N.C. Contact for stop command
4 FSW CL N.C. Contact for closing safety
5 FSW OP N.C. Contact for opening safety
6 GND (-) 24 Vdc negative
7 GND (-) 24 Vdc negative
8 + 24 24 Vdc positive
9 OUT (-) Programmable output (See: DS1 SW 11-12)
10 FCA 1 Open limit switch Motor 1
11 GND (-) 24 Vdc negative
12 FCC 1 Close limit switch Motor 1
13 FCA 2 Open limit switch Motor 2
14 GND (-) 24 Vdc negative
15 FCC2 Close limit switch Motor 2
LAMP LAMP Audio alarm output (DS1 SW11=OFF)
Output for ashing light 24Vdc 15W max (DS1 SW11=ON)
LOCK LOCK Output for electrical lock, max 5A pulse (DS2 - SW 4=OFF) 12 Vac / 24Vdc
Always ON (maglock): max 1 A (DS2 - SW 4=ON) 24 Vdc
MOT1 MOT 1 Motor 1 output ( rst moving motor )
MOT2 MOT 2 Motor 2 output ( second moving motor )
USB A USB Firmware upgrade input
2. INPUT / OUTPUT DESCRIPTION
A3
E024U CONTROL BOARD
Page 15
FSW
STP CL OP
How to connect Normally Open contacts. (Connect them in parallel)
How to connect Normally Close contacts. (Connect them in series)
The photocells must be connected depending on which area they must protect. (See Fig. A5) Closing Safety D : These photocells protect the area covered by the gate during the closing movement. They have no effect during the opening movement. Opening Safety B-C : These photocells protect the area covered by the gate during the opening movement. They have no effect during the closing movement. Opening/Closing Safety A : These photocells protect the area covered by the gate both during the opening and the closing movements.
The E024U board allows the connection of several safety devices (for example photocells). With photocells you can activate the FAILSAFE function, which, before each movement of the ope­rator, tests each fotocells. In case the test fails the movement is inhibited. To activate this function set to ON the dip-switch N. 11 and 12 of DS1, and connect the negative of the transmitter
to the OUT pin (No.9).
Fig. A3
Fig. A5
Fig. A4
Connection of a pair of closing photocells and a pair of opening/closing photocells
To use the FAIL-SAFE mode connect the negative power supply of the transmitters to OUT (pin 9), and set dip-
switch 11 and 12 to ON on DS1
Fig. A6
RX= Photocell Receiver TX= Ptotocell Transmitter CL= Closing OP= Opening
3. PHOTOCELLS CONNECTIONS
3.1 CONNECTIONS TO NORMALLY CLOSE (N.C.) PHOTOCELLS
A4
E024U CONTROL BOARD
Page 16
FSW
STP CL OP
FSW
STP CL OP
Connection of two pairs of closing photocells
Connection of a pair of closing photocells, a pair of opening photcells and a pair of opening/closing photocells
Other optional safety devices to connect in series
Fig. A7
Fig. A8
To use the FAIL-SAFE mode connect the negative power supply of the transmitters to OUT (pin 9), and
set dip-switch 11 and 12 to ON on DS1
When using the FAIL-SAFE mode also the safety inputs not used (FSW CL , FSW OP) must be connected
to OUT (pin No. 9)
To use the FAIL-SAFE mode connect the negative power supply of the transmitters to OUT (pin 9),
and set dip-switch 11 and 12 to ON on DS1
RX= Photocell Receiver TX= Ptotocell Transmitter CL= Closing OP= Opening
RX= Photocell Receiver TX= Ptotocell Transmitter CL= Closing OP= Opening
A5
E024U CONTROL BOARD
Page 17
8
8
FSW
STP CL OP
FSW
STP CL OP
FSW
STP CL OP
FSW
STP CL OP
To use the FAIL-SAFE mode connect the negative power supply of the transmitters to OUT (pin 9), and set dip-
switch 11 and 12 to ON on DS1
Connection of a pair of closing photocells and a pair of opening photocells
Fig. A9
Connection of no safety or stop devices
(NOT RECOMMENDED)
Connection of one pair of opening photocells
Other optional safety devices to connect in series
Fig. A10
Fig. A11
Fig. A12
To use the FAIL-SAFE mode connect the ne-
gative power supply of the transmitters to OUT (pin 9), and set dip-switch 11 and 12 to ON on DS1
When using the FAIL-SAFE mode also the
safety inputs not used (FSW CL , FSW OP) must be connected to OUT (pin No. 9)
RX= Photocell Receiver TX= Ptotocell Transmitter CL= Closing OP= Opening
Connection of a generic closing safety device and a generic
open safety device
A6
E024U CONTROL BOARD
Page 18
4. PROGRAMMING
OPERATING LOGIC
DS 1: SW 1 - SW 2 - SW 3
LOGIC
SW 1SW 2SW 3PAUSE
TIME
DESCRIPTION
E (default)
Semiautomatic
OFF OFF OFF NO
One command opens, the next one closes. A command du-
ring opening stops the gate
A
Automatic
ON ON ON
0 - 4
min
One command opens, waits for the pause time an then closes
automatically
S
Security
OFF OFF ON
0-4
min
One command opens, waits for the pause time and then clo­ses automatically. If the closing safety is activated or another
command is given during the pause time it closes
EP
Semiautomatic
step by step
OFF ON OFF NO
One command opens, the next one closes. During the move-
ment a command stops the gate
AP
Automatic
step by step
OFF ON ON
0-4
min
One command opens, waits for the pause time and then clo-
ses automatically. A command during the pause time holds
the gate open
SP
Security
step by step
ON OFF OFF
0-4
min
One command opens, waits for the pause time and then
closes automatically. If the closing safety is activated during
pause time the gate closes in 5 s. A command during pause
time holds open the gate
B
Manned Pulsed
ON OFF ON NO
An open A command opens the gate, an open B command
closes the gate
C
Manned Constant
ON ON OFF NO
Holding open A active opens the gate, holding Open B active
closes the gate
For more details on the operating logics please refer to Chapter 12 - Function Logics
4.1 DIP SWITCH DS1 SETTINGS FOR OPERATING LOGIC
A7
E024U CONTROL BOARD
Page 19
6
TR 3 – SPEED ADJUSTMENT FOR MOTOR1 AND MOTOR 2
Turn clockwise to increase the opening and closing speed
TR 4 – SENSITIVITY ADJUSTEMENT FOR OBSTACLE DETECTION FOR MOTOR 1 AND MOTOR 2
Turn clockwise to increase the sensitivity for obstacle detection.
With this trimmer you can adjust the reaction time for the board to invert the motion of the gate in case of obstacle detection, or the complete stop in case the board is in the positive stop detection zone. If an obstacle is detected during the gate movement the board will invert the motor rotation until the gate goes back to the original starting position. If in the successive movement an obstacle is detected again the board will be put in alarm mode and won’t take any more commands until the STOP input is activated (Alarm Reset) or power is cycled
TR 5 – PAUSE TIME ADJUSTMENT ( 0 - 4 min. )
Turn clockwise to increase the pause time.
TR6 - CLOSING DELAY OF LEAF 1 OVER LEAF 2 ADJUSTMENT ( 0 - 15 sec )
Turn clockwise to increase the delay
TR1 – FORCE ADJUSTMENT MOTOR 1
Turn clockwise to increase the opening and closing force
1 min
2 min
3 min
4 min0 sec
30 sec
TR 2 – FORCE ADJUSTEMENT MOTOR 2
Turn clockwise to increase the opening and closing force
4.2 ADJUSTING TRIMMERS
Dip switches DS1: 1 to 3 need to be set for an operating mode with PAUSE time for this adjustment to have any effect
A8
E024U CONTROL BOARD
Page 20
BOARD SETUP
DS 1: SW 4 to SW 12
OPENING DELAY
SW 4
The opening of leaf 2 is delayed after the opening of leaf 1. This is to avoid that the gate’s leafs interfere with each other during the initial part of the movement. In case there is only one leaf is has no effect.
0 sec (default)
OFF
2 sec
ON
REVERSE AND LAST STROKE
SW 5
If active, before opening, while the gate is closed, the motors thrust to close for 2 s to facilitate the release of the electric lock. At closing the
motors are activated for a nal stroke after slowdown to facilitate locking
of the electric lock.
inactive (default)
OFF
active
ON
MAX THRUST AT STARTUP
SW 6
With this fuction active the motors work at maximum force at startup (regardless of the force setting) during the initial phase of the movement. Useful for heavy leafs
inactive (default)
OFF
active for 3 sec
ON
AUTOMATIC OPENING IN CASE OF
POWER FAILURE
SW 7
If active and with the optional backup battery installed, the board will open the gate after one minute from the power failure and keep it open. Within the minute wait it’s always possible to open and close the gate with a command. If the logic used has a pause time the board will close the gate when the power comes back.
inactive (default)
OFF
active
ON
CLOSING SAFETY LOGIC
SW 8
With this function you can choose the behaviour of the closing safety. With SW8 OFF the gate movement will be reversed as soon as the safety is active, with SW8 ON the gate will stop when the safety is active and it will reverse only when the safety is deactivated again.
immediate reverse (default)
OFF
reverse when cleared
ON
PREFLASHING
SW 9
This function activates the ashing lamp for 5s before the movement of
the gate
inactive (default)
OFF
active for 5 sec
ON
EXTRA SENSITIVITY TO
OBSTACLE DETECTION
SW 10
If active this function allows to have an immediate reverse in case the gate hits a rigid obstacle, while keeping the motor active in case of a gradual increment of resistance, like with wind pressure on the gate or increased friction
inactive (default)
OFF
active
ON
ORANGE TERMINAL FUNCTION
SW 11
If OFF after the second consecutive obstacle detection this output is activated until the STOP contact is open or the power is cycled if ON the output can be connected to a warning lamp. NOTE: for UL325 compliance this switch must be left OFF
Audio Alarm (default)
OFF
Warning Lamp
ON
OUT FUNCTION (pin 9)
max 100mA
SW 12
if OFF: use pin 9 as power supply negative for a warning lamp. The lamp will be active during opening, pause and stop. Flashing during close, off when the gate is closed
If ON: use pin 9 as power supply negative for the safety photocells. Before any movement the board will check for the presence of the safety photocells. If the test fails the gate will not move.
Lamp
OFF
Photocells FAIL SAFE active
ON
4.3 DIP SWITCH DS1 SETTINGS FOR BOARD SETUP
A9
E024U CONTROL BOARD
Page 21
DS2
SETTING
+
J24
1
2
3
4
5
6
7
8 9
10
DL19 DL20 DL21 DL22
DL14 DL15 DL16 DL17 DL18
DS 2
OPERATOR SELECTION
OPERATOR TYPE SW 1 SW 2 SW 3
S450H, S800H OFF OFF OFF
S418 OFF OFF ON
415, 390, 770 ON OFF OFF
DS 2
LOCK OUTPUT MODE
OUTPUT MODE SW 4
Active only for 3 sec. after an open impulse
OFF
Active always except 3 sec. before an opening
ON
+
IMPORTANT
BUS
DEVICE
4.4 DIP SWITCH DS2 SETTINGS FOR OPERATOR TYPE AND LOCK MODE
5. LED DIAGNOSTICS
A10
E024U CONTROL BOARD
Page 22
A11
L
E
D
DESCRIPTION
LED STATUS
In BOLD the normal state with gate closed and working
ON STEADY OFF BLINKING
1
LED BATTERY
Board working on AC
power
Board working on
battery power or ext
supply
Battery charging
2
LED +24 Main power present Main power OFF
3
LED SET-UP
Normal operation
SLOW BLINK
(1 sec. ON - 1 sec. OFF)
SET-UP needed
FAST BLINK
(0.5 sec. ON - 0.5 sec OFF)
SET UP in in progress
4
LED ERROR Board malfunction No errors Error conditions. See LED ERROR
DISPLAY table
5
LED BUS_MON Communication on
Bus “2easy” OK
Communication bus
“2Easy” inactive. Verify
the bus “2Easy” devices
for shorts
Bus 2Easy devices with the
Same address. Verify dip switch
Setting on photocells or
Encoder LEDs
6
LED USB
Software update done
or USB key not present
USB key inserted and software
Update in progress
(DON’T Remove the USB key)
7
RESERVED
8
LED DL 14
OPEN A INPUT (N.O.)
OPEN A active OPEN A not active
LED DL 15
OPEN B INPUT (N.O.)
OPEN B active OPEN B not active
LED DL 16
STOP INPUT (N.C.)
STOP non active STOP active or
wiring error
LED DL 17
FSW CL INPUT (N.C.)
Closing safety
devices clear
Closing safety devices
triggered or wiring error
LED DL 18
FSW OP INPUT (N.C.)
Opening safety
devices clear
Opening safety devices triggered or wiring error
9
LED DL 19 FCA1
OPEN LIMIT SWITCH MO-
TOR1 (N.C.)
Limit switch
OFF or not used Limit Switch activated
LED DL 20 FCC1
CLOSE LIMIT SWITCH MO-
TOR1 (N.C.)
Limit switch
OFF or not used Limit Switch activated
10
LED DL 21 FCA2
OPEN LIMIT SWITCH MO-
TOR2 (N.C.)
Limit switch
OFF or not used Limit Switch activated
LED DL 22 FCC2
CLOSE LIMIT SWITCH MO-
TOR2 (N.C.)
Limit switch
OFF or not used Limit Switch activated
A11
E024U CONTROL BOARD
Page 23
WARNING: If the time learning setup is done automatically then the slow down points are set by the board on his own
Move the leafs to the mid position
Very important for a good result
1. Press and hold the SETUP button until the SETUP LED lights up, wait about 3 sec. until it turns off and then release it immediately. NOTE: If you wait too long to release it the manual set-up will start. The LED will blink during the setup procedure
2. Leaf 2 (if present) starts to move slowly in closing direction, stopping when it reaches the mechanical stop or FCC2.
3. Leaf 1 begins to move slowly in closing direction, stopping when it reaches the mechanical stop, or FCC1.
4. Leaf 1 starts to move slowly in opening direction, followed by leaf 2 (if present) still slowly.
5. When they both reach the open mechanical stop or FCA1 and FCA2 they stop and reverse, leaf 2 (if present) automatically starts closing at full speed followed by leaf 1.
After powering up the board for the rst time or when the board
will need it the setup LED will blink at a slow frequency to indicate that the setup procedure to learn the running times is needed.
The setup can be redone at any time by pressing and holding the setup button as indicated below.
After the setup rst movement, if the leafs are opening instead
of closing you need to reverse the wires going to the motor that moves in the wrong direction
LED ERROR DISPLAY
NUMBER OF
FLASHES
ERROR CONDITION SOLUTION
1
OBSTACLE DETECTION Remove the obstacle
2
BOARD IN SLEEP MODE
(Slow blinking means that the automatic open
in case of power failure function is active)
Verify the presence of AC power
3
MOTOR 1 FAILURE Replace motor 1
4
MOTOR 2 FAILURE Replace motor 2
5
ENCODER on motor 1 or motor 2 broken or
wiring error
Verify the encoder wiring and LED status. If they are correct replace
the encoder
6
FAIL SAFE FAILED Verify the photocells wiring and alignement
7
BOARD THERMAL PROTECTION ACTIVE Turn off the board and wait until the components cool down
8
MAX RUN TIME REACHED
WITHOUT FINDING THE
POSITIVE STOP (10 min. )
- Verify that the operator manual release is not engaged
- Verify that the board recognizes the mechanical stop, in case redo the setup procedure
The diagnostic LED shows only one error condition at a time, with the priority of the below table. In case there is more
than one error once one is eliminated the LED will show the next
6. When they reach the close mechanical stop or FCC1 and FCC2 both leafs stop and leaf 1 restarts automatically ope­ning at full speed followed by leaf 2 (if present).
7. If you selected an automatic logic the board will wait for the pause time and then closes the gate automatically. Other­wise you have to give an OPEN command to close the gate.
WARNING: If the manual time learning setup is done then the slow down points must be set by the installer during the procedure
Move the leafs to the mid position
Very important for a good result
1. Press and hold the SETUP button until the SETUP LED lights up, keep it pressed for about 3 sec. until it turns off and keep it pressed more until the leaf 2 (if present) starts mo­ving slowly. The LED will blink during the setup procedure
2. Leaf 2 will move in closing direction until it reaches the mechanical stop or FCC2
3. Leaf 1 starts moving slowly until it reaches the mechanical stop or FCC1
4. Leaf 1 starts moving in opening direction at the set speed (trimmer speed).
5. At the point where you want the slowdown to start give an OPEN A command with the push button or the remote that is already stored in memory. Leaf 1 starts to slow down and stops when it reaches the mechanical stop or FCA1.
6. Leaf 2 starts moving in opening direction at the set speed (trimmer speed)
6. TIME LEARNING (SET-UP)
6.1 AUTOMATIC TIME LEARNING
6.2 MANUAL TIME LEARNING
A12
E024U CONTROL BOARD
Page 24
The obstacle detection function is achieved by controlling the current absorption and / or through the encoder connected to the motors.
If the gate encounters an obstacle during the movement of opening or closing, the obstacle detection function is activated and the operator reverses the direction of the gate.
In case of a second consecutive obstacle the operator stops the gate right away and any further command is inhibited. To re-enable the automation, you must remove power or open the STOP contact input. Until this “reset” the Audio Alarm output will be active.
7. At the point where you want the slowdown to start give an OPEN A command with the push button or the remote that is already stored in memory. Leaf 2 starts to slow down and stops when it reaches the mechanical stop or FCA2.
8. Leaf 2 starts to close at the set speed (trimmer speed).
9. At the point where you want the slowdown to start give an OPEN A command with the push button or the remote that is already stored in memory. The leaf 2 starts to slow down and stops when it reaches the mechanical stop or FCC2.
10. Leaf 1 starts to close at the set speed (trimmer speed).
11. At the point where you want the slowdown to start give an OPEN A command with the push button or the remote that is already stored in memory. Leaf 1 starts to slow down and stops when it reaches the mechanical stop or FCC1.
12. The manual time learning procedure is complete.
15
15/32
6 7/32”
17 15/32
The E024U board is supplied on a panel that ts in a 16x14”
enclosure.
On the back panel are installed the control board, the power supply and additional accessories.
Power Supply
AC connection
Power outlet
and switch
Pushbutton
E24U board
DIN rail
Batteries
AC POWER GUIDELINES:
THE E024U control board and power supply uses a single phase AC power line to operate, charge the batteries, and power gate accessories. Use the following guidelines when installing the AC power:
1. Check the local wiring codes in all cases and follow all local building codes. Wiring and hookup should be performed by a
qualied electrician/installer only.
2. AC power should be supplied from a circuit breaker panel and must have its own dedicated circuit breaker. This supply must include a green ground conductor.
3. Use copper conductor wires with liquid tight exible conduit
UL listed for electric cable protection
14 AWG, 600V, 80°C
Terminal Block max Torque 2.1 Nm
4. Properly ground the gate operator to minimize or prevent damage from power surges and/or lightning. Use a grounding rod if necessary. A surge suppressor is recommended for ad­ditional protection.
6.3 OBSTACLE DETECTION FUNCTION
7. ENCLOSURE
8. POWER CONNECTION
A13
E024U CONTROL BOARD
Page 25
AC POWER CONNECTION
To connect AC power to the controller:
1. Turn the circuit breaker for the AC gate operator power OFF before connecting the AC input wires.
2. Turn OFF the Power Switch located on the left side of enclo­sure before connecting the AC input wires.
3. Connect the AC input wires to the AC terminal located on the top left of the control box. See diagram below.
4. Batteries must be installed after the AC power is on. See Battery Power Connection.
115V 60Hz 2.5A
The E024U board is powered by a high efciency switching power
supply that takes 115V or 230V in input and provides 36VDC to power the board. The power supply is preset for 115V at the fac­tory, consult with FAAC Tecnical Support for 230V wiring options.
230V
115V
The E024U board allows the connection of a 24V backup bat­tery to provide power to operate the gate during blackouts. For more details about how the boards handles the loss of main
power and how to congure its behaviour please see par 4.3
and DS1 switch 7.
To connect the battery use the provided cable and plug it on the BATTERY connector on the board. Plug the other end of the cable to the batteries, red wire to +24 and black wire to GND.
+
J24
SETTING
+
DL 1
DL 2
DL 3
DL 4
DL 5
J24
+
J2 4
To disable the battery charger unplug jumper J24
J24 PRESENT = BATTERY CHARGING ACTIVE J24 NOT PRESENT = BATTERY CHARGING NOT ACTIVE
9. BACKUP BATTERY
8.1 POWER SUPPLY
9.1 DISABLE THE BATTERY CHARGER
A14
E024U CONTROL BOARD
Page 26
LOGIC “E” PULSES
SYSTEM STATUS
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED opens the leaves opens leaf 1 no effect
no effect
(OPEN disabled)
no effect
(OPEN disabled)
no effect
no effect
(OPEN disa-
bled)
OPENING
stops operation
(1)
stops operation
recloses
leaves
immediately
stops operation
immediately
reverses at
closing
no effect
stops and opens
at release (OPEN
stops - saves
CLOSE)
OPEN
recloses leaves
immediately (1)
recloses leaves
immediately
recloses
leaves
immediately
no effect
(OPEN/CLOSE
disabled)
no effect
no effect
(CLOSE disabled)
no effect
(OPEN/CLOSE
disabled)
CLOSING
reopens leaves
immediately
reopens leaves
immediately
no effect stops operation no effect
reverses at opening
stops and opens
at release (OPEN
stops - saves
CLOSE)
BLOCKED closes leaves closes leaves closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
(OPEN disabled)
no effect
(CLOSE disabled)
no effect
(OPEN stops -
saves CLOSE)
(1) if the cycle began with OPEN-B (leaf 1), both leaves are activated at opening
LOGIC “A” PULSES
SYSTEM STATUS
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED
opens and closes
after pause time
opens leaf 1 and
closes after pause
time
no effect
no effect
(OPEN disabled)
no effect
(OPEN disa-
bled)
no effect
no effect
(OPEN disa-
bled)
OPENING no effect (1) no effect
recloses leaves
immediately
stops operation
reverses at
closing
no effect
stops and
opens at
release (saves
CLOSE)
OPEN IN
PAUSE
reloads
pause time (1)
reloads
pause time of
released leaf
recloses leaves
immediately
stops operation no effect
recharges
pause time
(CLOSE disa-
bled)
recharges
pause time
(CLOSE disa-
bled)
CLOSING
reopens leaves
immediately
reopens leaves
immediately
no effect stops operation no effect
reverses at
opening
stops and
opens at
release (saves
CLOSE)
BLOCKED closes leaves closes leaves closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
(OPEN disa-
bled)
no effect
(CLOSE disa-
bled)
no effect
(OPEN/CLOSE
disabled)
(1) if the cycle began with OPEN-B (leaf 1), both leaves are activated at opening
SETTING
+
DL 1
DL 2
DL 3
DL 4
DL 5
J2 4
1. Disconnect the batteries if they are present.
2. Turn the AC power off and insert the Flash Drive into the USB A input on the board
3. Turn the AC power back on. The USB2 LED will start to ash to conrm the beginning of the software update. (WAR­NING: DON’T TURN THE POWER OFF OR REMOVE THE FLASH DRIVE UNTIL THE USB2 LED TURNS OFF.
4. Wait until the USB 2 LED turns off
5. Remove the USB Flash drive.
6. Cycle power, reconnect the batteries if needed and execute a new SETUP procedure (See chapter 6)
For the upgrade you need a USB Flash Drive, where you have
to copy the le supplied by FAAC. Then follow these steps:
WARNING: Only upgrade the rmware with the proper le
supplied by FAAC. otherwise the board could be damaged
The E024U board keeps the operating rmware in a eld pro­grammable memory, it can be easily upgraded through the on board USB port
10. FIRMWARE UPGRADE
11. FUNCTION LOGICS
A15
E024U CONTROL BOARD
Page 27
LOGIC “EP” PULSES
SYSTEM STATUS
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED opens the leaves opens leaf 1 no effect
no effect
(OPEN disabled)
no effect
(OPEN disabled)
no effect
no effect
(OPEN disabled)
OPENING stops operation (1) stops operation
recloses
leaves
immediately
stops operation
immediately
reverses at
closure
no effect
stops and opens
at release (OPEN stops - saves CLOSE)
OPEN
recloses leaves
immediately (1)
recloses leaves
immediately
recloses
leaves
immediately
no effect
(OPEN/CLOSE
disabled)
no effect
no effect
(CLOSE disa-
bled)
no effect
(OPEN/CLOSE
disabled)
CLOSING stops operation stops operation no effect stops operation no effect
reverses at
opening
stops and opens
at release (OPEN stops - saves CLOSE)
BLOCKED
restarts moving in
opposite direction.
Always closes
after STOP
restarts moving in
opposite direction.
Always closes
after STOP
closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
(OPEN disabled)
no effect
(CLOSE disa-
bled)
no effect (OPEN stops - saves CLOSE)
LOGIC “AP” PULSES
SYSTEM STATUS
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED
opens and closes
after pause time
opens leaf 1 and
closes after pause
time
no effect
no effect
(OPEN disabled)
no effect
(OPEN disa-
bled)
no effect
no effect
(OPEN disabled)
OPENING
stops operation
(1)
stops operation
recloses
leaves
immediately
stops operation
reverses at
closing (saves
OPEN)
no effect
stops and opens
at release
(OPEN stops -
saves CLOSE)
OPEN IN PAUSE
stops operation
(1)
stops operation
recloses
leaves
immediately
stops operation no effect
recharges
pause time
(CLOSE disa-
bled)
recharges
pause time
(CLOSE disa-
bled)
CLOSING
reopens leaves
immediately
reopens leaves
immediately
no effect stops operation no effect
reverses at
opening
(see
DS1-SW8)
stops and opens
at release
(OPEN stops -
saves CLOSE)
BLOCKED closes leaves closes leaves closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
(OPEN disa-
bled)
no effect
(CLOSE disa-
bled)
no effect
(OPEN/CLOSE
disabled)
(1) if the cycle began with OPEN-B (leaf 1), both leaves are activated at opening
(1) if the cycle began with OPEN-B (leaf 1), both leaves are activated at opening
LOGIC “S” PULSES
SYSTEM STATUS
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED
opens and closes
after pause time
opens released leaf and closes
after pause time
no effect
no effect
(OPEN disa-
bled)
no effect
(OPEN disa-
bled)
no effect
no effect
(OPEN disabled)
OPENING no effect (1) no effect
recloses leaves
immediately
stops operation
reverses at
closure
continues
to open and
recloses
immediately
stops and opens
at release
(saves CLOSE)
OPEN IN
PAUSE
recloses leaves
immediately (1)
recloses leaves
immediately
recloses leaves
immediately
stops operation no effect
stops and, at
release, closes
stops and, at
release, closes
CLOSING
reopens leaves
immediately
reopens leaves
immediately
no effect stops operation no effect
reverses at opening
(see DS1-SW8) and closes imme-
diately at end
stops and opens after release and
closes immediately
at end
BLOCKED closes leaves closes leaves closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
(OPEN disa-
bled)
no effect
(CLOSE disa-
bled)
no effect
(OPEN/CLOSE
disabled)
(1) if the cycle began with OPEN-B (leaf 1), both leaves are activated at opening
A16
E024U CONTROL BOARD
Page 28
LOGIC “B” PULSES
SYSTEM STATUS
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED opens the leaves no effect no effect
no effect
(OPEN disabled)
no effect
(OPEN disabled)
no effect
no effect
(OPEN disa-
bled)
OPENING no effect closes leaves closes leaves stops operation
reverses at
closure
no effect
stops and, at
release, closes
(saves
OPEN/CLOSE)
OPEN no effect closes leaves closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
no effect
(CLOSE disa-
bled)
no effect
(OPEN/CLO-
SE disabled)
CLOSING opens the leaves no effect no effect stops operation no effect
reverses at
opening
stops and
opens at
release
(saves
OPEN/CLOSE)
BLOCKED opens the leaves closes leaves closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
(OPEN disabled)
no effect
(CLOSE disa-
bled)
no effect
(OPEN/CLO-
SE disabled)
LOGIC “C” CONTINUOS COMMANDS PULSES
SYSTEM STATUS
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED opens the leaves no effect no effect
no effect
(OPEN disabled)
no effect
(OPEN disabled)
no effect
no effect
(OPEN disa-
bled)
OPENING no effect closes leaves closes leaves stops operation
reverses at
closure
no effect
stops and, at
release, closes
(saves
OPEN/CLOSE)
OPEN no effect closes leaves closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
no effect
(CLOSE disa-
bled)
no effect
(OPEN/CLO-
SE disabled)
CLOSING opens the leaves no effect no effect stops operation no effect
reverses at
opening
stops and
opens at
release
(saves
OPEN/CLOSE)
BLOCKED opens the leaves closes leaves closes leaves
no effect
(OPEN/CLOSE
disabled)
no effect
(OPEN disabled)
no effect
(CLOSE disa-
bled)
no effect
(OPEN/CLO-
SE disabled)
LOGIC “SP” PULSES
SYSTEM STATUS
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED
opens and clo-
ses after pause
time
opens leaf 1 and
closes after pause
time
no effect
no effect
(OPEN disabled)
no effect
(OPEN disa-
bled)
no effect
no effect
(OPEN disa-
bled)
OPENING
stops operation
(1)
stops operation
recloses
leaves
immediately
stops operation
reverses at
closure
continues to open
and recloses
immediately
stops and opens
after release and
closes immediately
at end (OPEN stops
- saves CLOSE)
OPEN IN PAUSE
recloses
leaves
immediately (1)
recloses leaves
immediately
recloses
leaves
immediately
stops operation no effect
stops and, at
release, closes
stops and, at
release, closes
CLOSING stops operation stops operation no effect stops operation no effect
reverses at opening
stops and
opens at
release (saves
CLOSE)
BLOCKED
restarts moving
in opposite
direction. Always
closes after
STOP
restarts moving in opposite direction.
Always closes
after STOP
recloses
leaves
immediately
no effect
(OPEN/CLOSE
disabled)
no effect
(OPEN disa-
bled)
no effect
(CLOSE disabled)
no effect
(OPEN/CLOSE
disabled)
(1) if the cycle began with OPEN-B (leaf 1), both leaves are activated at opening
A17
E024U CONTROL BOARD
Page 29
A18
E024U CONTROL BOARD
To the original purchaser only:
FAAC International, Inc., warrants, for twenty­four (24) months from the date of invoice, the gate operator systems and other related systems and equipment manufactured by FAAC S.p.A. and distributed by FAAC International, Inc., to be free from defects in material and workmanship under normal use and service for which it was intended provided it has been properly installed and operated.
FAAC International, Inc.’s obligations under this warranty shall be limited to the repair or exchange of any part of parts manufactured by FAAC S.p.A. and distributed by FAAC International, Inc. Defective products must be returned to FAAC International, Inc., freight prepaid by purchaser, within the warranty period. Items returned will be repaired or replaced, at FAAC International, Inc.’s option, upon an examination of the product by FAAC International, Inc., which discloses, to the satisfaction of FAAC International, Inc., that the item is defective. FAAC International, Inc. will return the warranted item freight prepaid. The products manufactured by FAAC S.p.A. and distributed by FAAC International, Inc., are not
warranted to meet the specic requirements,
if any, of safety codes of any particular state, municipality, or other jurisdiction, and neither FAAC S.p.A. or FAAC International, Inc., assume any risk or liability whatsoever resulting from the use thereof, whether used singly or in combination with other machines or apparatus.
Any products and parts not manufactured by FAAC S.p.A. and distributed by FAAC International, Inc., will carry only the warranty, if any, of the manufacturer. This warranty shall not apply to any products or parts thereof which have been repaired or altered, without FAAC International, Inc.’s written consent, outside of FAAC International, Inc.’s workshop, or altered in any way so as, in the judgment of FAAC International, Inc., to affect adversely the stability or reliability of the product(s) or has been subject to misuse, negligence, or accident, or has not been operated in accordance with FAAC International, Inc.’s or FAAC S.p.A.’s instructions or has been operated under conditions more severe than, or otherwise exceeding, those set
forth in the specications for such product(s).
Neither FAAC S.p.A. nor FAAC International, Inc., shall be liable for any loss or damage whatsoever resulting, directly or indirectly, from the use or loss of use of the product(s). Without limiting the foregoing, this exclusion from liability embraces a
purchaser’s expenses for downtime or for making up downtime, damages for which the purchaser may be liable to other persons, damages to property, and injury to or death of any persons.
FAAC S.p.A. or FAAC International, Inc., neither assumes nor authorizes any person to assume for them any other liability in connection with the sale or use of the products of FAAC S.p.A. or FAAC International, Inc. The warranty herein above set forth shall not be deemed to cover maintenance parts, including, but not limited to,
hydraulic oil, lters, or the like. No agreement to
replace or repair shall constitute an admission by FAAC S.p.A. or FAAC International, Inc., of any legal responsibility to effect such replacement, to make such repair, or otherwise. This limited warranty extends only to wholesale customers who buy directly through FAAC International, Inc.’s normal distribution channels. FAAC International, Inc., does not warrant its products to end consumers.
Consumers must inquire from their selling dealer as to the nature and extent of that dealer’s warranty, if any. This warranty is expressly in lieu of all other warranties expressed or implied including the warranties of merchantability and
tness for use. This warranty shall not apply to
products or any part thereof which have been subject to accident, negligence, alteration, abuse, or misuse or if damage was due to improper installation or use of improper power source, or
if damage was caused by re, ood, lightning,
electrical power surge, explosion, wind storm, hail, aircraft or vehicles, vandalism, riot or civil commotion, or acts of God.
LIMITED WARRANTY
Loading...