EV9326 Digital controller with 6 outputs for electric bread ovens, with cooking timer and rapid heating
functionsversion 3.00
E ENGLISH
1IMPORTANT
1.1Important
Read these instructions carefully before installation and use and fol-
low all warnings regarding installation and for the electric connec-
tion. Keep these instructions with the instrument for future reference.
The instrument must be disposed of in compliance with
local Standards relative to the collection of electrical and
electronic appliances.
1.2Dimensions and installation
Panel with supplied brackets with screws; dimensions in mm (in).
DIMENS.MINIMUMTYPICALMAXIMUM
A92.0 (3.622)92.0 (3.622)92.8 (3.653)
B92.0 (3.622)92.0 (3.622)92.8 (3.653)
Installation recommendations:
• the thickness of the panel must not exceed 4.0 mm (0.157 in)
• position the brackets as indicated in the drawing in this paragraph,
moderate the coupling torque
• make sure that the working conditions (temperature of use, humid-
ity, etc.) lie within the limits indicated in the technical data
• do not install the instrument in proximity of heat sources (resistances,
hot air pipes, etc.), appliances with strong magnets (large diffusers,
etc.), places subject to direct sunlight, rain, humidity, excessive dust,
mechanical vibrations or jerks
• in compliance with Safety Standards, protection against any contact
with electrical parts must be assured via correct installation of the
instrument. All parts that ensure protection must be fixed in a way
that they cannot be removed without the aid of a tool.
1.3Electric connection
With reference to the wiring diagram: the serial port is the port for the
communication with the supervising system (through a serial inter-
face, via TTL, with MODBUS communication protocol) or with the
programming key;
same time.
the port must not be used for two purposes at the
Recommendations for the electric connection:
• do not operate on the terminal boards using electric or pneumatic
• if the instrument has been taken from a cold place to a hot place, the
humidity could condense inside; wait for about one hour before
applying power
• check that the power supply voltage, the frequency and the electric
operational power of the instrument correspond with those of the
local power supply
• disconnect the power supply before performing any type of maintenance
• supply the probes with protection able to isolate them from any
contact with metal parts or use isolated probes
• do not use the instrument as a safety device
• for repairs and information regarding the instrument, contact the
Evco sales network.
2PRELIMINARY CONSIDERATIONS
2.1Preliminary considerations
The instrument can be configured to function with 1 measurement
input (default, chamber probe) or with 2 measurement inputs (top
probe and floor probe). If functioning with 1 measurement input it is
however possible to enable a second probe (steam probe) to subordinate the injection of steam at the temperature of the same.
Functioning with 1 measurement input allows to independently set
the power distributed to the top to that distributed to the floor. Functioning with 2 measurement inputs allows to independently set the
top and floor work temperatures.
The utilities managed by the digital outputs (i.e. relays K1 ... K6) are the
following:
RELAY MANAGED UTILITY
K1top
K2floor
K3can be set (default chamber light)
K4airhole
K5steam injection
K6can be set (default steam generator)
To set the type of functioning (with 1 measurement input rather than
2) see paragraph 4.1. However, to set the utility managed by relay K3
and relay K6 see paragraph 4.2.
2.2Management of the utilities
Top.
If functioning with 1 measurement input:
• the output is switched on in cyclical mode, preferably when the
floor output is off (the parameter c1 establishes the cycle time. The
procedure given in paragraph 4.4 can be used to set the duration
of output switch-on, intended as a percentage of the time established with parameter c1)
• the cyclical activity is subject to the chamber temperature (chamber
probe), to the work set-point and parameter r0.
If functioning with 2 measurement inputs:
• the output activity depends mainly on the top temperature (top
probe), the top set-point and parameter r0.
Floor.
If functioning with 1 measurement input:
• the output is switched on in cyclical mode, preferably when the top
output is off (the parameter c1 establishes the cycle time. The procedure given in paragraph 4.4 can be used to set the duration of
output switch-on, intended as a percentage of the time established
with parameter c1)
• the cyclical activity is subject to the chamber temperature (chamber
probe), to the work set-point and parameter r0.
If functioning with 2 measurement inputs:
• the output activity depends mainly on the floor temperature (floor
probe), the floor set-point and parameter r6.
Chamber light.
The output is activated in manual mode.
Through the multifunction input it is also possible to activate the out-
put in remote mode.
Airhole.
The output is activated in the following conditions:
• before the conclusion of the cooking timer count (of the time estab-
lished with the parameter c5), for the time established with param-
eter c6
• in manual mode, for the time established for parameter c7.
Steam injection.
The output activity depends mainly on parameter t0.
Through the multifunction input it is also possible to activate the out-
put in remote mode.
Steam generator.
If functioning with 1 measurement input:
• if the steam probe is not enabled, the output is activated in manual
mode
• if the steam probe is enabled, the output is enabled in manual mode,
after which the activity of the same will depend on the temperature
of the steam (steam probe), the steam set-point and parameter t3.
If functioning with 2 measurement inputs, the output is activated in
manual mode.
Alarm.
The output is activated during a temperature alarm.
Through the multifunction input it is also possible to activate the out-
put in remote mode.
Cooking timer.
The output is activated during the cooking timer count.
Acoustics.
The output is activated in the following conditions:
• before the conclusion of the cooking timer count (of the time estab-
lished with the parameter c9), for the time established with param-
eter c4
• during an alarm or an error, with continuous contribution.
On/Stand-by.
The output is activated during the “on” state (see paragraph 3.1).
In spite of the fact that the instrument can manage the 10
utilities stated in this paragraph, there are 6 digital out-
puts available. Make sure that the desired utility is man-
aged by the instrument (see paragraph 2.1).
3USER INTERFACE
3.1Preliminary considerations
The following functioning states exist:
• the “on” state (the instrument is powered and on: the regulators can
be on)
• the “stand-by” state (the instrument is powered but switched off via
software: the regulators are off)
• the “off” state (the instrument is not powered).
Successively, the term “switch-on” means the passage from the standby state to the on state. The term “switch-off” means the passage from
the on state to the stand-by state.
When powered, the instrument re-proposes the state that it was in
when the power supply was disconnected.
3.2Instrument switch-on/off
To pass from the stand-by state to the on state (and vice versa):
• make sure no procedure is in progress
• press
Through the on/stand-by input it is also possible to pass from the on
state to the stand-by state in remote mode.
To pass from the on to the stand-by state in remote mode:
• activate the on/stand-by input (the instrument remains in the stand-
If the on/stand-by input is active, it will not be allowed to pass from the
stand-by state to the on state by pressing the
3.3The display
If functioning with 1 measurement input, if the instrument is in the on
state:
• the upper part of the display will show the size established with
- if P5 = 0, the display will show the chamber temperature
- if P5 = 1, the display will show the work set-point
• the lower part of the display will show the size established with
- if P6 = 0, the display will show the chamber temperature
- if P6 = 1, the display will show the work set-point (in this case the
- if P6 = 2, the display will show the value of the cooking timer or its
See also paragraphs 3.5 and 3.7.
If functioning with 2 measurement inputs, if the instrument is in the on
state:
• the upper part of the display will show the size established with
- if P5 = 0, the display will show the top temperature
- if P5 = 1, the display will show the top set-point
for 1s.
by state for the entire duration of input activation).
key.
parameter P5:
parameter P6:
“set” LED will be on)
count if the timer is active (in this case the “timer” LED will be on); the
value of the cooking timer is displayed in the hours:minutes format.
parameter P5:
Page 2
Evco S.p.A. • Code 1049326E00 • page 2/6
- if P5 = 2, the display will show the floor temperature
- if P5 = 3, the display will show the floor set-point
• the lower part of the display will show the size established with
parameter P6:
- if P6 = 0, the display will show the top temperature
- if P6 = 1, the display will show the top set-point (in this case the “set”
LED and the “1” LED will be on).
- if P6 = 2, the display will show the value of the cooking timer or its
count if the timer is active (in this case the “timer” LED will be on); the
value of the cooking timer is displayed in the hours:minutes format
- if P6 = 3, the display will show the floor temperature
- if P6 = 4, the display will show the floor set-point (in this case the “set”
LED and the “2” LED will be on).
See also paragraphs 3.5 and 3.7.
If the instrument is in the stand-by state:
• the upper part of the display will be off
• the lower part of the display will be off
• the LED
will be on.
3.4Temporary setting of the quantity shown by the
upper part of the display during the on state
• make sure no procedure is in progress
• press
andfor 1s several times: the upper part of the display
will show one of the labels given in the tables in
paragraph 3.5 for 2 secs, after which it will show
the corresponding value.
Any power supply cut-off causes the display of the quantity estab-
lished with parameter P5 to be restored.
3.5Learning the quantity shown by the upper part of
the display during the on state
• make sure no procedure is in progress
• press
and: if functioning with 1 measurement input, the
upper part of the display will show one of the
labels given in the following table for 2 seconds:
LABEL MEANING
Pbchamber temperature
SPwork set-point
PbS steam temperature
If the steam probe is not enabled (parameter P4 = 0), the “PbS” label
will not be displayed.
if functioning with 2 measurement inputs, the upper part of the dis-
play will show one of the labels given in the following table for
2 seconds:
LABEL MEANING
Pb1 temperature of the top
SP1 top set-point
Pb2 temperature of the floor
SP2 floor set-point
3.6Temporary setting of the quantity shown by the
lower part of the display during the on state
• make sure no procedure is in progress
• press
andfor 1s several times: the lower part of the display
will show one of the labels given in the tables in
paragraph 3.7 for 2 secs, after which it will show
the corresponding value.
Any power supply cut-off causes the display of the quantity estab-
lished with parameter P6 to be restored.
3.7Learning the quantity shown by the lower part of
the display during the on state
• make sure no procedure is in progress
• press
and: if functioning with 1 measurement input, the
lower part of the display will show one of the
labels given in the following table for 2 seconds:
LABEL MEANING
Pbchamber temperature
SPwork set-point
tine value of the cooking timer or its count if the timer is active
PbS steam temperature
If the steam probe is not enabled (parameter P4 = 0), the “PbS” label
will not be displayed.
if functioning with 2 measurement inputs, the lower part of the display will show one of the labels given in the following table for 2
seconds:
LABEL MEANING
Pb1 temperature of the top
SP1 top set-point
tine value of the cooking timer or its count if the timer is active
Pb2 temperature of the floor
SP2 floor set-point
3.8Chamber light switch on/off
• make sure no procedure is in progress
• press
Using the multifunction input, it is also possible to cause the same
effect caused by pressing the key
in remote mode.
If the chamber light is not managed by any digital output, pressing the
key will cause the display of the “no” indication for 1s in the lower
part of the display.
3.9Buzzer silencing
• make sure no procedure is in progress
• press a key (the first time the key is pressed, the associated effect is not
caused).
Pressing the key also causes the deactivation of the acoustic output
and the buzzer output.
Using the multifunction input, it is also possible to deactivate the buzzer,
the acoustic output and the buzzer output in remote mode.
4SETTINGS
4.1Setting the type of functioning (with 1 measure-
ment input rather than 2)
To access the procedure:
• make sure that the instrument is in stand-by state and that no proce-
dure is in progress
• press
andfor 4s: the upper part of the display will show
“PA”
• press
: the lower part of the display will show the correspond-
ing value
• press
orwithin 15s to set “743”
• press
• pressandfor 4s: the upper part of the display will show
“Pb”.
To modify the type of functioning:
• press
: the lower part of the display will show the correspond-
ing value.
The meaning of the values is the following:
VALUE MEANING
1functioning with 1 measurement input (default, chamber
probe)
2functioning with 2 measurement inputs (top probe and
floor probe)
• press
orwithin 15s
• press
To exit the procedure:
• press
andfor 4s.
The modification of the type of functioning does not cause
the configuration parameters default value to be restored.
4.2Setting the utility managed by the relay K3 and
the relay K6
To access the procedure:
• make sure that the instrument is in stand-by state and that no proce-
dure is in progress
• press
andfor 4s: the upper part of the display will show
“PA”
• press
: the lower part of the display will show the correspond-
ing value
• press
orwithin 15s to set “743”
• press
• pressandfor 4s: the upper part of the display will show
“Pb”
• press
orto select “do3” or “do6”.
The label meaning is the following:
LABEL MEANING
do3 utility managed by the third digital output (relay K3)
do6 utility managed by the sixth digital output (relay K6)
To modify the utility managed by an output:
• press
: the lower part of the display will show the correspond-
ing value.
The meaning of the values is the following:
VALUE MEANING
0not used
1chamber light
2steam generator
3alarm
4cooking timer
5acoustics
6on/stand-by
• press
orwithin 15s
• press
To exit the procedure:
• press
andfor 4s.
4.3.1 Setting the work set-point (only if functioning with
1 measurement input)
• make sure that the instrument is in on state and that no procedure is
in progress
• press
• press
• press
: the lower part of the display will show “SP”, the upper
part the corresponding value and the LED
will flash
orwithin 15s; see also parameters r1 and r2
3 times or do not operate for 15s: the LED will switch-
off, after which the instrument will exit the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
It is also possible to set the work set-point via the SP parameter.
4.3.2 Setting the top set-point and the floor set-point
(only if functioning with 2 measurement inputs)
To modify the top set-point:
• make sure that the instrument is in on state and that no procedure is
in progress
• press
• press
• press
: the lower part of the display will show “SP1”, the upper
part the corresponding value and the LED
will flash
orwithin 15s; see also parameters r1 and r2
2 times or do not operate for 15s: the LED will switchoff, after which the instrument will exit the procedure.
To modify the floor set-point:
• press
during the modification of the top set-point: the lower
part of the display will show “SP2”, the upper part the
• press
• press
corresponding value and the LED
orwithin 15s; see also parameters r7 and r8
: the LED will switch-off, after which the instrument
will flash
will exit the procedure.
To go back to previous levels:
• press
several times during the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
It is also possible to set the top set-point via parameter SP1 and the floor
set-point via parameter SP2.
4.4Setting the power distributed to the top and the
power distributed to the floor (only if functioning
with 1 measurement input)
To modify the power distributed to the top:
• press
during the modification of the work set-point: the lower
part of the display will show “Po1”, the upper part the
corresponding value and a proportioned number of bars
• press
orwithin 15s; see also parameters c0 and c1
• non operare per 15 s: the LED
of the LED
will flash
will switch-off, after which the
instrument will exit the procedure.
To modify the power distributed to the floor:
• press
during the modification of the power distributed to the
top: the lower part of the display will show “Po2”, the
upper part the corresponding value and a proportioned
• press
• press
number of bars of the LED
orwithin 15s; see also parameters c0 and c1
: the LED will switch-off, after which the instrument will
will flash
exit the procedure.
To go back to previous levels:
• press
several times during the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
It is also possible to set the power distributed to the top through pa-
rameter Po1 and the power distributed to the floor through param-
eter Po2.
4.5Setting the configuration parameters
To access the procedure:
• make sure that the instrument is in stand-by state and that no proce-
dure is in progress
• press
andfor 4s: the upper part of the display will show
“PA”
• press
: the lower part of the display will show the correspond-
ing value
• press
• press
• press
orwithin 15s to set “-19”
or do not operate for 15s
andfor 4s: if functioning with 1 measurement input,
the upper part of the display will show “SP”; if
functioning with 2 measurement inputs, the
upper part of the display will show “SP1”.
To select a parameter:
• press
or
To modify a parameter:
• press
: the lower part of the display will show the correspond-
ing value
• press
• press
orwithin 15s
or do not operate for 15s.
To exit the procedure:
• press
andfor 4s or do not operate for 60s (any modifica-
tions will be saved).
Cut the instrument power supply off after modification of
the parameters.
4.6Restore the default value of the configuration pa-
rameters
• make sure that the instrument is in stand-by state and that no proce-
dure is in progress
• press
andfor 4s: the upper part of the display will show
“PA”
• press
: the lower part of the display will show the correspond-
ing value
• press
• press
• press
orwithin 15s to set “743”
or do not operate for 15s
andfor 4s: the upper part of the display will show
“Pb”
• press
• press
orto select “dEF”
: the lower part of the display will show the correspond-
ing value
• press
• press
orwithin 15s to set “149”
or do not operate for 15s: the upper part of the display
will show “dEF” flashing for 4s, after which “dEF” will
switch on
• cut the instrument power supply off.
To exit the procedure in advance:
• press
andfor 4s during the procedure (i.e. before setting
“149”: restore will not be carried out).
Make sure that the default value of the parameters is
appropriate.
5COOKING TIMER
5.1Preliminary considerations
The cooking timer allows to start the reverse count of a time.
The count is shown in the lower part of the display; during the count
the “timer” LED is on and the timer output is activated.
Before conclusion of the count (of the time established with parameter
c9) the buzzer and the acoustic output are activated, for the time estab-
lished with parameter c4.
Before conclusion of the count (of the time established with parameter
c5) the airhole is activated, for the time established with parameter c6.
Using the multifunction input, it is also possible to start/interrupt the
cooking timer in remote mode.
Page 3
Evco S.p.A. • Code 1049326E00 • page 3/6
5.2Setting the cooking timer
• make sure that the instrument is in the on state, that the cooking timer
count is not in progress and that no procedure is in progress
• press
and: the lower part of the display shows the value of
the cooking timer; the left part and the “timer”
LED will flash.
The value of the cooking timer is displayed in the hours:minutes for-
mat.
To modify the hour:
• press
• press
orwithin 15s
: the right part will flash.
To modify the minutes:
• press
orwithin 15s.
The cooking timer can be set between 00:00 and 24:00 h:min.
• press
: the “timer” LED will switch-off, after which the instru-
ment will exit the procedure.
To go back to previous levels:
• press
several times during the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
The cooking timer can also be set when the count is in progress (this
modification is temporary, i.e. any power supply cut-off causes the
value set with the procedure given at the start of this paragraph to be
restored). If the value is set at 00:00 h:min, the count will be inter-
rupted, the “timer” LED will switch-off and the buzzer will be activated
for 3 seconds.
5.3Starting the cooking timer
• press
during timer setting: the “timer” LED will switch on.
Alternatively:
• make sure that the instrument is in on state and that no procedure is
in progress
• press
: the “timer” LED will switch on.
5.4Cooking timer start and switch-off of the instru-
ment on conclusion of the count
• make sure that the instrument is in on state and that no procedure is
in progress
• press
for 4s: the “timer” LED switches-on and the LED will
flash; the instrument will switch-off when the count has
been concluded.
5.5Interrupting the cooking timer
• press
for 1s: the “timer” LED switches off and the buzzer will be
activated for 3s.
6STEAM GENERATOR
6.1Preliminary considerations
The steam generator allows to subordinate the steam injection to its
own state.
If functioning with 1 measurement input, if the steam probe is not
enabled, pressing the
and keys for 1s will cause the steam
generator to switch on and successive pressing causes its switch-off;
steam injection is allowed on condition that the steam generator is on.
If functioning with 1 measurement input, if the steam probe is not
enabled, pressing the
and keys for 1s will enable the steam
generator, after which the activity of the same will depend on the
temperature of the steam (steam probe), the steam set-point and pa-
rameter t3 (successive pressing of the keys causes the steam generator
to be disabled);
steam injection is allowed on condition that the tem-
perature of the steam is above that established with the steam set-point
or at the minimum. Once the steam set-point has been reached, above
the “steam set-point - t4”.
If functioning with 2 measurement inputs, pressing the
and
keys for 1s will cause the steam generator to switch on and successive
pressing causes its switch-off;
steam injection is allowed on condition
that the steam generator is on.
If the steam generator is not managed by any digital output , pressing
the
and keys will cause the display of the “no” indication for
1s in the lower part of the display.
In this case, steam injection is always
allowed.
7STEAM INJECTION
7.1Preliminary considerations
The functioning mode of the steam injection depends on parameter
t0.
If the parameter t0 is set at 0, pressing the
key causes the injection
of steam for the time established with parameter t2 or for the entire
duration that the key is pressed. The parameter t1 establishes the mini-
mum time that can pass between the two successive injections.
If the parameter t0 is set at 1, pressing the
key will enable the
automatic injection of the steam (in cyclical mode: parameter t2 estab-
lishes the duration of the injector switch-on and parameter t1 estab-
lishes the duration of switch-off).
Using the multifunction input, it is also possible to cause the same
effect caused by pressing the
key in remote mode.
Steam injection is subordinate to the steam generator state (see para-
graph 6.1).
7.2Quick setting of the parameter t2
• make sure that the instrument is in on state and that no procedure is
in progress
• press
and: the upper part of the display will show “t2”, the
lower part the corresponding value and the LED
will flash.
The parameter t2 can be set between 1 and 250 ds.
• press
orwithin 15s
• press
: the LED will switch-off, after which the instrument will
exit the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
7.3Activation of the injector in manual mode (only if
parameter t0 is set at 0)
• make sure that the instrument is in on state and that no procedure is
in progress
• press
: the LED will switch-on and the injector will be acti-
vated, both for the time established with parameter t2 or
for the entire duration that the key is pressed.
The injector must not be deactivated in manual mode.
7.4Enabling of automatic steam injection (only if pa-
rameter t0 is set at 1)
• make sure that the instrument is in on state and that no procedure is
in progress
• press
: the LED will switch-on and the injector will be acti-
vated in cyclical mode according to that established with
parameters t1 and t2 (until the key is pressed again).
8AIRHOLE
8.1Preliminary considerations
The airhole is activated in the following conditions:
• before the conclusion of the cooking timer count (of the time estab-
lished with the parameter c5), for the time established with param-
eter c6
• in manual mode, by pressing the
key for the time established
with parameter c7.
8.2Quick setting of the parameter c7
• make sure that the instrument is in on state and that no procedure is
in progress
• press
and: the upper part of the display will show “c7”, the
lower part the corresponding value the left part
and the LED
will flash.
The parameter c7 is visualised in the minutes:seconds format.
To modify the minutes:
• press
• press
orwithin 15s
: the right part will flash.
To modify the seconds:
• press
orwithin 15s.
The parameter c7 can be set between 00:00 and 60:00 min:s.
• press
: the LED will switch-off, after which the instrument will
exit the procedure.
To go back to previous levels:
• press
several times during the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
8.3Activation of the airhole in manual mode
• make sure that the instrument is in on state and that no procedure is
in progress
• press
: the LED will switch on and the airhole will be acti-
vated, both for the time established with parameter c7.
8.4Deactivation of the airhole in manual mode
• make sure no procedure is in progress
• press
: the LED will switch-off.
9ECONOMY
9.1Preliminary considerations
The economy allows to reduce the power supplied to the top and the
power supplied to the floor by switching an output on when the
other is off.
If functioning with 1 measurement input, when the function is in
progress the top output and the floor output are switched on for half
of the duration of the switch-on set using the procedure given in
paragraph 4.4 (intended as a percentage of the time established with
parameter c1).
If functioning with 2 measurement inputs, when the function is in
progress, the top output and the floor output are switched-on alter-
nately for half the time established with parameter c1.
When the time established with parameter c10 has passed, the func-
tion is interrupted.
Through the multifunction input it is also possible to activate the
economy function in remote mode.
If the rapid heating function is in progress, the economy function
cannot be activated.
9.2Economy activation
• make sure that the instrument is in the on state, that no procedure is
in progress and no rapid heating function is in progress
• press
When the function is in progress the LED
andfor 1s.
will flash for 1s every 4s.
9.3Economy interruption in manual mode
• make sure no procedure is in progress
• press
andfor 1s.
10RAPID HEATING (only if functioning with 1 meas-
urement input)
10.1 Preliminary considerations
The rapid heating allows to reach the work set-point as quickly as
possible, supplying 100% of the power both to the top and the floor
(i.e. excluding switch-on of the top and floor outputs in a cyclical way
with benefit to switch-on in continuous mode).
When the temperature of the chamber reaches the “work set-point -
temperature established with parameter c3” value, the function is in-
terrupted.
If the economy function is in progress, the rapid heating cannot be
activated.
10.2 Rapid heating activation
• causes the event established with parameter c2:
- if c2 = 1, press
for 1s (make sure that the instrument is in the on
state, that no procedure is in progress and the economy function is
not is progress)
- if c2 = 2, pass from the stand-by state to the on state
- if c2 = 3, press
for 1s (make sure that the instrument is in the on
state, that no procedure is in progress and the economy function is
not is progress) or pass from the stand-by state to the on state.
If parameter c2 is set at 0, the function cannot be activated.
When the function is in progress the upper part of the display shows
“F-F” alternately to the quantity established with parameter P5.
10.3 Interruption of rapid heating in manual mode
• make sure no procedure is in progress
• press
for 1s.
11SIGNALS
11.1 S ignals
LED MEANING
top and floor LED
if it is on, the to output and/or the floor output will be on
if it flashes, the modification of the work set-point, the top
set-point and the floor set-point is in progress (with the
procedures indicated in paragraphs 4.3.1 or 4.3.2)
power distributed to the top LED
supplies and indication regarding the power distributed
to the top
if it flashes, the modification of the power distributed to the
top is in progress (with the procedure indicated in para-
graph 4.4)
power distributed to the floor LED
supplies and indication regarding the power distributed
to the floor
if it flashes, the modification of the power distributed to the
floor is in progress (with the procedure indicated in para-
graph 4.4)
steam injection LED
if it is on:
• and the parameter t0 is set at 0, steam injection will be in
progress
• and the parameter t0 is set at 1, steam injection will be in
enabled
if it flashes:
• rapid setting of parameter t2 is in progress (see para-
graph 7.2)
• steam injection will not be available (parameter t4)
airhole LED
if it is on, the airhole will be activated in manual mode
if it flashes:
• the airhole will be activated due to the effect of the con-
clusion of the cooking timer count (parameter c6)
• rapid setting of parameter c7 is in progress (see para-
graph 8.2)
°Cdegrees Celsius LED
if it is on, the unit of measurement of the temperatures will
be degrees Celsius (parameterP2)
°Fdegrees Fahrenheit LED
if it is on, the unit of measurement of the temperatures will
be degrees Fahrenheit (parameter P2)
on/stand-by LED
if it is on, the instrument is in the stand-by state
if it flashes, the cooking timer count is in progress and on
conclusion of the count, the instrument will switch-off
if it flashes for 1s every 4s, the economy function will be in
progress
timer cooking timer LED
if it is on, the quantity shown by the lower part of the
display will be the value of the cooking timer or its count
if the timer will be activated
if it flashes:
• cooking timer setting is in progress
• the cooking timer count will be in progress but the lower
part of the display will be showing another quantity
setset-point LED
if it is on, the quantity shown by the lower part of the
display will be the work set-point value, the top set-point
or the floor set-point
1• the quantity displayed by the lower part of the display
will be the top set-point value
2• the quantity displayed by the lower part of the display
will be the floor set-point value
12INDICATIONS
12.1 Indications
INDICAT. MEANING
F-Falternately to the quantity established with parameter P5:
the rapid heating function will be in progress (only if func-
tioning with 1 measurement input)
decrease the time established with parameter c9 is missing... 1 second
time to the conclusion of the cooking timer count
c9
00:00 flashing: the cooking timer count has ended
Page 4
Evco S.p.A. • Code 1049326E00 • page 4/6
13ALARMS
13.1 Alarms
CODE MEANING
ALchamber temperature alarm (only if functioning with
1 measurement input)
Remedies:
• check the chamber temperature
• see parameters A1 and A3
Consequences:
• the alarm output will be activated
• the acoustics output and the buzzer output will be activated
AL1 top temperature alarm (only if functioning with 2 meas-
urement inputs)
Remedies:
• check the top temperature
• see parameters A1 and A3
Consequences:
• the alarm output will be activated
• the acoustics output and the buzzer output will be activated
AL2 floor temperature alarm (only if functioning with 2 meas-
urement inputs)
Remedies:
• check the floor temperature
• see parameters A5 and A7
Consequences:
• the alarm output will be activated
• the acoustics output and the buzzer output will be activated
idmultifunction input alarm (only if the parameter i5 is set at 5)
Remedies:
• check the causes that brought about the input activation
• see parameters i5 and i6
Main consequences:
• the top output will be deactivated
• the floor output will be deactivated
• steam injection will not be available
• the alarm output will be activated
• the acoustics output and the buzzer output will be activated
PF1 power supply cut-off alarm during the cooking timer count
Remedies:
• press a key to restore the normal display
• check the causes that brought about the power supply
cut-off
Main consequences:
• on power supply restore, the count will continue with
a maximum error of 3 min
• the acoustics output and the buzzer output will be activated
When the cause of the alarm disappears, the instrument restores normal functioning, except for the power supply cut-off alarm during the
cooking timer count (code “PF1”) which requires a key to be pressed.
14INTERNAL DIAGNOSTICS
14.1 Internal diagnostics
CODE MEANING
Pr1
If functioning with 1 measurement input:
chamber probe error
Remedies:
• see parameter P0
• check probe integrity
• check the instrument-probe connection
• check the chamber temperature
Main consequences:
• the top output and the floor output will be deactivated
• the acoustics output and the buzzer output will be activated
If functioning with 2 measurement inputs:
top probe error
Remedies:
• the same as the previous case but relative to the top probe
Main consequences:
• the top output will be deactivated
• the acoustics output and the buzzer output will be activated
Pr2
If functioning with 1 measurement input:
steam probe error
Remedies:
• the same as the previous case but relative to the steam
probe
Main consequences:
• the steam generator output will be off
• steam injection will not be available
• the acoustics output and the buzzer output will be activated
If functioning with 2 measurement inputs:
floor probe error
Remedies:
• the same as the previous case but relative to the floor
probe
Main consequences:
• the floor output will be deactivated
• the acoustics output and the buzzer output will be activated
When the causes of the alarm have disappeared, the instrument will
go back to normal functioning.
15TECHNICAL DATA
15.1 Technical data
Container: grey self-extinguishing.
Front panel protection rating: IP 54.
Connections: removable terminal boards (power supply, inputs and
outputs), 6-pole connector (serial port).
Temperature of use: from 0 to 55 °C (from 32 to 131 °F,
10 ... 90% relative humidity without condensate).
Power supply: 115 ... 230 VAC, 50/60 Hz, 5 VA (approx) or 24 VAC,
50/60 Hz.
Alarm buzzer: incorporated.
Measurement inputs: can be configured:
• 1 (chamber probe) for J/K thermocouple
if functioning with 1 measurement input;
second input (steam probe) for J/K ther-
mocouple
• 2 (top probe and floor probe) for J/K ther-
mocouple if functioning with 2 measure-
ment inputs.
Digital inputs: 2 inputs:
• on/stand-by input in high voltage (230 VAC) with
configurable polarity
• multifunction input, for NO/NC contact (poten-
tial-free contact, 5 V 1 mA).
Range of measurement: from -99 to 800 °C (from -99 to 999 °F)
for J thermocouple, from -99 to 999 °C (from -99 to 999 °F) for
K thermocouple.
Resolution: 1 °C/1 °F.
Digital outputs: 6 relays:
• top (relay K1): 8 A res. @ 250 VAC (NO)
• floor (relay K2): 8 A res. @ 250 VAC (NO)
• utility that can be set (relay K3): 8 A res.
@ 250 VAC (contact in exchange)
• airhole (relay K4): 8 A res. @ 250 VAC (NO
contact)
• steam injection (relay K5): 8 A res. @
250 VAC (NO contact)
• utility that can be set (relay K6): 8 A res.
@ 250 VAC (contact in exchange).
The maximum current accepted on clamp 23 is 10 A.
To set the utility managed by relay K3 and relay K6, see paragraph 4.2.
Other outputs: buzzer output (12 V, max. 20 mA); the output is
activated during alarms and errors, with continuous contribution.
Serial port: port for the communication with the supervising system
(through a serial interface, via TTL, with MODBUS communication
protocol) or with the programming key.
PT • 35/09
Page 5
Evco S.p.A. • Code 1049326E00 • page 5/6
16WORK SET-POINT, POWER DISTRIBUTED AND CONFIGURATION PARAMETERS
temperature of the steam below which, once the steam set-point has been reached, the steam injection is no longer available (relative to the steam
set-point i.e. “steam set-point - t4”) (5)
PARAM. MIN. MAX. U.M.1 INPUT2 INPUTS
c002- - - -0not visible
VARIOUS
restraint between the power distributed to the top and power distributed to the floor
0 = no restraint
1 = the modification of the power supplied to an output automatically causes the supply of the maximum power to the other
2 = the modification of the power supplied to an output causes an automatic adaptation of the power supplied to the other such to guarantee that the
sum of the two percentages is always 100
c11999 s8080
with 1 measurement input, cycle time for the top output and floor output switch-on, see also Po1 and Po2
with 2 measurement inputs, cycle time for the top output and floor output switch-on, when economy function is in progress (7)
c203- - - -1not visible
event that causes the activation of the rapid heating function
0 = function cannot be activated
1 = press
for 1s (make sure that the instrument is in the on state, that no procedure is in progress and the economy function is not is progress)
2 = pass from stand-by state to on state
3 = press
for 1s (make sure that the instrument is in the on state, that no procedure is in progress and the economy function is not is progress) or
pass from the stand-by state to the on state
c309 9°C/°F (1)1 0not visible
c4-1120 s1515
temperature of the chamber over which the rapid heating function is interrupted (relative to the work set-point i.e. “work set-point - c3”)
duration of buzzer activation and of the acoustic output on conclusion of the cooking timer count; see also c9 (8) (9)
-1 = the buzzer and the acoustic output must be deactivated in manual mode by pressing a key
c5060min2020
c6060min2020
c700:00 60:00 min:s00:3000:30
c90120 s1010
c10 0999 min120120
PARAM. MIN. MAX. U.M.1 INPUT2 INPUTS
A10999 °C/°F (1)00
time that passes between the activation of the airhole and the conclusion of the cooking timer count, see also c6
duration of the activation of the airhole at conclusion of the cooking timer count, see also c5
duration of the activation of the airhole in manual mode
time that passes between the activation of the buzzer and the acoustic output and the conclusion of the cooking timer count, see also c4
maximum duration of the economy function (10)
TEMPERATURE ALARMS
with 1 measurement input, temperature of the chamber above which the chamber temperature alarm is activated; with 2 measurement inputs, tempera-
ture of the top above which the top temperature alarm is activated; see also A3 (11)
A20240 min00
with 1 measurement input, chamber temperature alarm delay; with 2 measurement inputs, top temperature alarm delay
Page 6
Evco S.p.A. • Code 1049326E00 • page 6/6
A302- - - -00
with 1 measurement input, type of chamber temperature alarm delay; with 2 measurement inputs, type of top temperature alarm delay
0 = no alarm
1 = absolute (i.e. A1)
2 = with 1 measurement input, relative to the work set-point (i.e. “work set-point + A1”); with 2 measurement inputs, relative to the top set-point (i.e. “top
set-point + A1”)
A40999 °C/°F (1)not visible0
A5024 0 minnot visible0
A602- - - -not visible0
floor temperature above which the floor temperature alarm is activated, see also A6 (11)
floor temperature alarm delay
type of floor temperature alarm
0 = no alarm
1 = absolute (i.e. A4)
2 = relative to the floor set-point (i.e. “floor set-point + A4”)
PARAM. MIN. MAX. U.M.1 INPUT2 INPUTS
i101- - - -00
DIGITAL INPUTS
on/stand-by input polarity
0 = live input active
1 = non-live input active
i506- - - -00
effect caused by the activation of the multifunction input
0 = no effect
1=
START/INTERRUPTION OF THE COOKING TIMER - the activation of the input will cause the cooking timer to start and the successive activation will cause
its interruption
2=
CHAMBER LIGHT SWITCH-ON/OFF - the activation of the input will cause the chamber light to switch-on and the successive activation will cause its
switch-off
3=
BUZZER, ACOUSTIC OUTPUT AND BUZZER OUTPUT DEACTIVATION - the activation of the input will cause deactivation of the buzzer, the acoustic
output and the buzzer output (activate the input again to deactivate these utilities again)
4=
STEAM INJECTION - in this case:
• if t0 = 0, the activation of the input causes the injection of steam for the time established with parameter t2 or for the entire duration that the key is
pressed (parameter t1 establishes the minimum time that can pass between the two successive injections) (12)
• if t0 = 1, the activation of the input will enable automatic steam injection (in cyclical mode; parameter t2 establishes the duration of the switch-on
of the injector and parameter t1 establishes the duration of switch-off) until the input is activated again (12)
5=
DOOR MICRO SWITCH - the activation of the input causes the deactivation of the top output and the floor output, prevents steam injection, displays
the flashing “id” code in the upper part of the display and activates the buzzer until the input is deactivated; see also i7
6=
START/STOP OF THE ECONOMY FUNCTION - activation of the input causes the activation of the economy function and successive activation will cause
interruption
i601- - - -00
type of contact of the multifunction input
0 = NO (input active with closed contact)
1 = NC (input active with open contact)
i70120 min00
PARAM. MIN. MAX. U.M.1 INPUT2 INPUTS
LA1247 - - - -247247
Lb03- - - -22
multifunction input alarm signal delay (only if i5 = 5)
SERIAL NETWORK (MODBUS)
instrument address
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
LP02- - - -22
parity
0 = none (no parity)
1 = odd
2 = even
(1)the unit of measurement depends on parameter P2
(2)
set the parameters relative to the regulators appropriately after modification of parameter P2
(3)the value depends on the type of functioning (1 with 1 measurement input and 3 with 2 measurement inputs)
(4)the value depends on the type of functioning (2 with 1 measurement input and 4 with 2 measurement inputs)
(5)steam injection becomes available again when the temperature of the steam reaches the steam set-point again
(6)ds = tenths of second
(7)the top output and the floor output are switched-on alternately for half of the time established with parameter c1
(8)the buzzer and the acoustic output are activated before the conclusion of the cooking timer count (of the time established with the parameter c9), for the time established with parameter c4
(9)if the cooking timer is interrupted (with the procedure given in paragraph 5.4 or by activation of the malfunction input), the duration of buzzer activation and of the acoustic output and the flashing duration
of the 00:00 indication will be 3 seconds
(10)if the economy function is in progress, any instrument switch-off will cause interruption of the function. A power cut will not cause interruption of the function but the re-start of the time count established with
parameter c10
(11)the parameter differential is 10 °C/18 °F
(12)pressing the key
causes the associated effect.
EVCO S.p.A.This document belongs to Evco; unless you are authorized by Evco, you can not publish this document.
Via Mezzaterra 6, 32036 Sedico Belluno ITALYEvco does not take any responsibility about features, technical data and possible mistakes related in this document.
Phone +39-0437-852468 • Fax +39-0437-83648Evco does not take any responsibility about damages coming by the non-observance of additional information.
info@evco.it • www.evco.itEvco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.