Read these instructions carefully before installing and using the instrument and follow all additional information for installation and electrical
connection; keep these instructions close to the interface for future consultations.
The interface must be disposed according to the local legislation about the collection for electrical and electronic equipment.
1.2. Available models for the programmable controllers of the family c-pro........................................................................................................ 5
1.3. Available models for the programmable controllers of the family c-pro 3..................................................................................................... 5
2.
SIZE AND INSTALLATION........................................................................................................................................................................ 6
2.3. Additional information for installation........................................................................................................................................................... 7
3.2. Additional information for electrical connection............................................................................................................................................ 9
4.2. Configuring the interface ............................................................................................................................................................................. 10
4.3. List of configuration parameters .................................................................................................................................................................. 11
4.4. Configuring a device through the interface.................................................................................................................................................. 14
6.1. Frontal plates CPVP* by Evco..................................................................................................................................................................... 16
1.1.1. Available models.................................................................................................................................................................................... 16
6.2. Support for wall mounting CPVW00........................................................................................................................................................... 16
1.1.3. Available models.................................................................................................................................................................................... 16
1.1.5. Available models.................................................................................................................................................................................... 17
Vgraph is a new and innovative user interface for the programmable controllers of the family c-pro that support the CAN bus and for the
programmable controllers of the family c-pro 3.
The main features of the interface are the possibility to communicate to the user a great deal of information and the remarkable ease of control; these
features are due to the use of a 128 x 64 pixel single colour LCD graphic display (black with rearlighting through white LED), to the 6 buttons (with
preset functions) membrane keyboard and to the CAN bus (for the connection to the controllers).
This last also allows the use of the interface in multimaster networks.
Thanks to its constructive features, Vgraph offers several mounting typologies; this is possible:
- by panel, at the front of units, of machines for refrigeration or for air conditioning, of electrical panels and as well as in all those
applications where a frontal protection degree IP65 is required
- built-in by wall, in traditional box (like "506" by BTicino)
- by wall, on the support CPVW00 by Evco (to order separately).
Also the necessity to customize the interface, in order to integrate it aesthetically in residential and commercial environments, is satisfied by Vgraph
since at the front of the interface one can apply both the plates CPVP* by Evco (to order separately, made in plastic material and available in two
different colorations, white and black) and the numerous plates series "Living" and "Light" by BTicino.
By request, Vgraph can be supplied with:
At the front of the interface one can apply the plates CPVP* by Evco (to order separately, made in plastic material and available in two different
colorations, white and black); look at chapter 6 (ACCESSORIES).
2.3. Additional information for installation
- working conditions (working temperature, humidity, etc.) must be between the limits indicated in the technical data
- do not install the interface close to heating sources (heaters, hot air ducts, etc.), devices provided with big magnetos (big speakers, etc.),
locations subject to direct sunlight, rain, humidity, dust, mechanical vibrations or bumps
- according to the safety legislation, the protection against electrical parts must be ensured by a correct installation of the interface; the parts
that ensure the protection must be installed so that you can not remove them if not by using a tool.
Position micro-switch 4 on position ON to plug in the termination of the CAN port; micro-switches 1, 2 and 3 are reserved.
The following tables show the meaning of the connectors.
Connector 1: CAN port.
Terminal Meaning
1 ground
2 signal +
3 signal -
The maximum length of the connecting cables of the CAN port of the interface depends on the baud rate of the CAN communication, as
follows:
- 1,000 m (3,280 ft) with baud rate 20,000 baud
- 500 m (1,640 ft) with baud rate 50,000 baud
- 250 m (820 ft) with baud rate 125,000 baud
- 50 m (164 ft) with baud rate 500,000 baud.
Connect the CAN port of the interface using a twisted pair.
According to the default settings, the interface recognizes the baud rate automatically, on condition that it is one of the those mentioned above;
hereinafter one suggests setting the same baud rate of the others devices in the network.
Connector 2: power supply (not isolated 24 VAC or 20 ... 40 VDC or isolated 12-24 VAC or 15 ... 40 VDC, according to the model).
The maximum length of the connecting cables of the power supply is 10 m (32.8 ft).
In the models with not isolated power supply, this must galvanically be isolated from the one of the other devices connected in the
network.
3.2. Additional information for electrical connection
- do not operate on the terminal blocks with electrical or pneumatic screwers
- if the interface has been moved from a cold location to a warm one, the humidity could condense on the inside; wait about an hour before
supplying it
- test the working power supply voltage, working electrical frequency and working electrical power of the interface; they must correspond
with the local power supply
- disconnect the local power supply before servicing the interface
- do not use the interface as safety device
- for repairs and information on the interface please contact Evco sales network.
ymd = year, month and day
mdy = month, day and year
dmy = day, month and year
Parameters TimeWithSec 0 1 - - - 1
Parameters Time AM/PM 0 1 - - - 0
Parameters Back Mode - - - - - - - - - TIME
Parameters BackTimeout 0 240 s 60
Parameters I/O Timeout 0 240 s 60
Showing the seconds in the real time
1 = yes
Time format
0 = 24 h (for example 15:20)
1 = 12 h (for example 3:20 PM)
Backlight mode
OFF = backlight is never lit
ON = backlight is always lit
TIME = backlight is lit the time one has
set with parameter BackTimeout
since the last operation with the
buttons
Backlight duration (only if parameter Back Mode
has value TIME)
Local (or of the interface) CAN communication
time-out (after this time without CAN
communication, the display will show
Checking . . . and the l’I/O of the interface will
be disabled)
CAN Network MyNode 1 127 - - - 99 Local (or of the interface) CAN node’s address
CAN Network Master - - - - - - - - - YES The interface always works as master
CAN communication baud rate
20K = 20,000 baud
50K = 50,000 baud
125K = 125,000 baud
CAN Network Baud - - - - - - - - - Auto
CAN Network Net Timeout 1 240 s 5
500K = 500.000 baud
Auto = the interface recognizes the baud
rate automatically, on condition
that it is one of the those
mentioned above
Remote (or of the devices in the network) CAN
communication time-out (after this time without
CAN communication with a device, this will be
excluded by the network)
118.0 x 111.0 x 26.7 mm (4.645 x 4.370 x 1.051 in).
Size refers to the interface with connector 1 and connector 2 properly plugged.
the installation is possible:
- by panel
- built-in by wall, in traditional box (like "506" by BTicino)
- by wall, on the support CPVW00 by Evco (to order separately); look at chapter
6 (ACCESSORIES).
Fixing screws are always supplied by the builder.
At the front of the interface one can apply the plates CPVP* by Evco (to order separately, made in
plastic material and available in two different colorations, white and black); look at chapter
6 (ACCESSORIES).
IP40 (IP65 for panel mounting with gasket 0027000007, to order separately); look at chapter
6 (ACCESSORIES).
Connections:
Working temperature:
Pollution situation:
extractable male + female terminal blocks (power supply and CAN port), 6 poles telephone connector
(programming port).
The maximum length of the connecting cables of the CAN port of the interface depends on the baud
rate of the CAN communication, as follows:
- 1,000 m (3,280 ft) with baud rate 20,000 baud
- 500 m (1,640 ft) with baud rate 50,000 baud
- 250 m (820 ft) with baud rate 125,000 baud
- 50 m (164 ft) with baud rate 500,000 baud.
According to the default settings, the interface recognizes the baud rate automatically, on condition
that it is one of the those mentioned above.
from 0 to 50 °C (32 to 120 °F, 10 ... 90% of relative humidity without condensate).
- 12-24 VAC (min. 11.4 VAC, max. 27.6 VAC), 50/60 Hz, 3 VA (approximate) isolated or
15 ... 40 VDC, 3 W (approximate) isolated
- 24 VAC (min. 20.4 VAC, max. 27.6 VAC), 50/60 Hz, 3 VA (approximate) non isolated or
20 ... 40 VDC, 2 W (approximate) non isolated
supplied from a class 2 circuit.
Power supply:
The maximum length of the connecting cables of the power supply is 10 m (32.8 ft).
In the models with not isolated power supply, this must galvanically be isolated from the one of the
other devices connected in the network.
Protect the power supply with an UL listed or recognized fuse rated:
- 80 mA-T if the user interface is powered with 15... 40 VDC
- 160 mA-T if the user interface is powered with 12... 19 VAC
- 125 mA-T if the user interface is powered with 19... 24 VAC.
Overvoltage category:
Real time clock data maintenance in
absence of power supply:
Battery charging time
Alarm buzzer:
Display:
Communication ports:
III.
2 days will battery fully charged; the real time clock is available by request.
2 min without interruptions (the battery is charged by the power supply of the interface).
by request.
128 x 64 pixel single colour LCD graphic display (black with rearlighting through white LED).
Hardware manual ver. 1.01
PT - January 2011
Code 114VGRAHWE01
This document belongs to Evco; unless you are authorized by Evco, you can not publish this document.
Evco does not take any responsibility about features, technical data and possible mistakes related in this document.
Evco does not take any responsibility about damages coming by the non-observance of additional information.
Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.