E-T-A EM12D-TMB Instruction Manual

Page 1
Instruction manual
Controller EM12D-TMB
Page 2
Contents
1 Contents .................................................................................................................................................... 2
2 General information ..................................................................................................................................4
2.1 Safety instructions ................................................................................................................................ 4
2.2 Qualified personnel ............................................................................................................................... 4
2.3 Use .......................................................................................................................................................4
2.4 Delivery state ........................................................................................................................................ 4
3 General description .................................................................................................................................. 5
3.1 Design of the entire system .................................................................................................................. 6
3.2 Dimensions bus controller EM12D-TMB .............................................................................................. 7
3.3 Status indication and terminals ............................................................................................................ 7
3.3.1 Picture 3: status indicators and terminals EM12D-light emitting diode “CE/CM” ...................... 7
4 Mounting and installation ........................................................................................................................8
4.1 Mounting of the system ........................................................................................................................ 8
4.2 Power supply of the Modbus RTU controller .......................................................................................8
4.3 Terminals for the voltage supply and the ELBus
4.3.1 Communications for the Modbus RTU communication, connector socket X81/ X82 ................ 8
®
............................................................................... 8
5 Operating modes of the device EM12D-TMB ........................................................................................9
5.1 Operating mode: (system start) ............................................................................................................ 9
5.2 Operating mode: (critical failure) ...........................................................................................................9
5.3 Operating mode: (non-critical failure) ...................................................................................................9
5.4 Operating mode: (independent operation) .........................................................................................10
5.5 Operating mode: (faultless operation) ................................................................................................10
5.8 Signalling of operating conditions on circuit protector REX12D ........................................................11
6 Basic functions of the entire system .................................................................................................... 11
6.1 Internal cycle times .............................................................................................................................11
6.2 Hot swap of circuit protectors ............................................................................................................11
7 Communication via Modbus RTU .........................................................................................................12
7.1 ControlPlex
®
Controller model ......................................................................................................... 12
7.1.1 Error with faulty population ....................................................................................................... 13
7.1.2 Error device addressing ............................................................................................................13
7.2 Physical interface ...............................................................................................................................13
7.3 Setting the communication parameters .............................................................................................13
2
Page 3
8 Overview of Modbus registers ..............................................................................................................15
8.1 Voltage, current, status and control of channels ................................................................................ 15
8.2 Values and parameters per channel and of the supply module .........................................................16
8.3 Explanation of the individual regusters which are received ...............................................................20
8.3.1 Load voltage circuit protector ...................................................................................................20
8.3.2 Load current circuit protector ...................................................................................................20
8.3.3 Status of interfaces module ...................................................................................................... 20
8.3.4 Status circuit protector .............................................................................................................21
8.3.5 Control of circuit protectors ......................................................................................................22
8.3.6 System commands EM12D ......................................................................................................22
8.3.7 Diagnostic information of the intelligent interface module EM12D ........................................... 23
8.3.8 Configuration data of the EM12D intelligent supply module ....................................................24
8.3.9 Configure controllability of the channels via PLCLock in the EM12D supply module ..............25
8.3.10 Device type of EM12D supply module .................................................................................... 25
8.3.11 Serial number EM12D ............................................................................................................. 26
8.3.12 Hardware version EM12D .......................................................................................................26
8.3.13 Softwareversion EM12D .........................................................................................................26
8.3.14 Application Specific Tag EM12D ............................................................................................. 27
8.3.15 Current rating REX12D ............................................................................................................ 27
8.3.16 Limit value load current REX12D ............................................................................................27
8.3.17 Channel diagnosis REX12D ....................................................................................................28
8.3.18 Error memory REX12D ............................................................................................................ 29
8.3.19 Trip counter REX12D ............................................................................................................... 29
8.3.20 Trip reason REX12D ................................................................................................................ 29
8.3.21 Voltage average REX12D ........................................................................................................30
8.3.22 Maximum voltage REX12D .....................................................................................................30
8.3.23 Minimum voltage REX12D ......................................................................................................31
8.3.24 Current average REX12D ........................................................................................................31
8.3.25 Maximum current REX12D ...................................................................................................... 32
8.3.26 Minimum current REX12D ....................................................................................................... 32
8.3.27 Channel type REX12D .............................................................................................................32
8.3.28 Hardware version REX12D ......................................................................................................33
8.3.29 Software version REX12D ....................................................................................................... 33
8.3.30 Serial number REX12D............................................................................................................34
8.3.31 Action commands channel REX12D ....................................................................................... 35
9 Appendix .............................................................................................................................................. 36
9.1 List of pictures....................................................................................................................................36
3
Page 4
2 General information
2.1 Safety instructions
This manual points out possible danger for your personal safety and gives instruction how to avoid property damage. The following safety symbols are used to draw the reader's attention to the safety instructions in­cluded in this manual.
Danger!
Danger to life and limb unless the following safety precautions are taken.
Warning
Danger to machinery, materials or the environment unless the following safety precautions are taken.
Note
Information is provided to allow a better understanding.
2.2 Qualified personnel
This user manual must exclusively be used by qualified personnel, who are able – based on their training and experience – to realise arising problems when handling the product and to avoid related hazards. These persons have to ensure that the use of the product described here meets the safety requirements as well as the requirements of the presently valid directives, standards and laws.
2.3 Use
The product is part of a continuous enhancement process. Therefore there might be deviations between the product in hand and this documentation. These deviations will be remedied by a regular review and resulting corrections in future editions. The right to make changes without notice is reserved. Error and omissions excepted.
2.4 Delivery state
The product is supplied with a defined hardware and software configuration. Any changes in excess of the documented options are not permitted and lead to liability exclusion.
4
Page 5
3 General description
Requirements in plant engineering and construction and in building automation are growing and growing. In the context of increasing efficiency and reducing costs, the transparency of systems, remote maintenance and remote access are getting more and more important. Early notification in the event of any disturbances and a fast response to current problems will increase system availability, save costs and improve the overall stability of the production process.
5
Page 6
3.1 Design of the entire system
HMI HMI
CPU
EM12D-TMB
CPU
EM12D­TMB-xxx
Modbus
0V
LINE + 1
RTU
X81
X82
Modbus RTU
REX12D-
REX12D-
TA2-100
TA2-100
DC24V
DC24V
COM COM COM
2A 4A
2A
4A
REX12D­TA2-100
DC24V
6A
6A
fig. 1: System overview
The Modbus controller EM12D-TMB is the centre of the ControlPlex® system. It collects all information of the REX12D electronic circuit protectors and forwards it to the superordinate Modbus server and thus to the superordinate control unit.
®
of the ControlPlex
system to the Modbus server, thus enabling display and analysis of the individual measuring values as well as diagnosis and control of the individual electronic circuit protectors. The user has unrestricted access to the safety-relevant functions in the event of a system disruption. Any occurring failures will be detected quickly and can be remedied without delay. The ControlPlex® system effectively reduces system downtimes and significantly increases the productivity.
6
Page 7
3.2 Dimensions bus controller EM12D-TMB
view X
12,4
Label, e.g. from Phoenix Contact, ZBF-12
LED CE/CM
EM12D-
TMB-000
A B
G N D
X81
A B
G N D
X82
0V
LINE +1
98
91,5
GERMANY
Entrance Module EM12D-TMB-000-DC24V-40A Modbus-RTU
x10 x1 Baudrate Bus-Address parity
E-T-A D-90518 Altdorf Made in Germany xxxx · xxx x
3-pole plus
view X
snap-on socket for rail mounting EN 60715-35x7,5
fig. 2: EM12D-TMB
3.3 Status indication and terminals
view X
Modbus
RTU
A B
G N D
A B
G N D
0V
LINE +1
X81
X82
LED CE/CM
Modbus RTU X81/ -X82 COM interface RS485 communication A communication B communication GND
0 V DC
LINE+ DC
snap-on socket for rail mounting EN 60715-35x7,5
GERMANY
Entrance Module EM12D-TMB-000-DC24V-40A Modbus-RTU
7,5
80
x10 x1 Baudrate Bus-Address parity
E-T-A D-90518 Altdorf Made in Germany xxxx · xxx x
3-pole plus
view X
fig. 3: status indicators and terminals EM12D light emitting diode “CE/CM”
3.3.1 Picture 3: status indicators and terminals EM12D-light emitting diode “CE/CM”
The LED CE/CM shows the status of the communication unit. Available LED colours are red, green and yellow/orange. For further details please see fig. 7. Illustration of operating modes.
7
Page 8
4 Mounting and installation
4.1 Mounting of the system
The preferred mounting position of the EM12D-TMB is horizontal.
fig. 4: Mounting position
4.2 Power supply of the Modbus RTU controller
Power supply of the Modbus controller is via the line entry terminals LINE+ and 0V.
4.3 Terminals for the voltage supply and the ELBus
®
The operating voltage of the device is 24V DC. Faultless operation of the device is ensured in a voltage range of 18V to 30V. The max. current of the supply module is 40A.
Using a supply voltage outside the indicated operating range can cause malfunctions or destruction of the device.
4.3.1 Connector sockets for the Modbus RTU communication, connector socket X81/ X82
These connector sockets serve for connection of the Modbus controller EM12D-TMB with the superordinate control unit. This connection is a one-to-one wiring.
1. communication A
2. communication B
3. communication GND
fig. 5: Modbus RTU connection
Preferably, the connection should be effected with a three-pole shielded cable. The cable length between the Modbus controller EM12D-TMB and the Modbus server has to comply with the benchmarks.
8
Page 9
Benchmarks:
cable length of RS485 approx. 1200 m approx. 110 Ohm cable length of RS485 approx. 600 m approx. 220 Ohm cable length of RS485 approx. 300 m approx. 330 Ohm
Use of the terminals for applications not provided for in the operation manual or improper connection
can lead to malfunction or destruction of the device.
4.3.2 Marking of the manufacturing date, the Device ID and revision status of the software
GERMANY
Entrance Module EM12D-TMB-000-DC24V-40A Modbus-RTU
x10 x1 Baudrate Bus-Address parity
E-T-A D-90518 Altdorf Made in Germany xxxx · xxx x
date code
Device ID of the unit
revision index of firmware
fig. 6: Marking of date code
5 Operating modes of the Device EM12D-TMB
5.1 Operating mode: (system start)
The Modbus controller is initialised by applying the supply voltage. The device will carry out implemented programme memory tests and self test routines. During this time a communication via the interfaces is not possible.
5.2 Operating mode: (critical failure)
If a failure is detected during the self test routines, the Modbus controller will change into operating mode “critical failure”. In the event of a critical failure, the device will also change into this operating mode. This operating mode can only be discontinued by way of re-starting the device and it prevents the data exchange via the interfaces. If the Modbus controller is in this operating mode, no communication is possible with the superordinate control unit. The electronic circuit protectors cannot be controlled by it and remain OFF.
5.3 Operating mode: (non-critical failure)
If there are no valid or invalid configuration data available in the Modbus controller, it will change into this operating mode. This operating mode will be left upon receipt of the correct module and slot parameters and configuration data. The circuit protectors remain OFF.
9
Page 10
5.4 Operating mode: (independent operation)
If no connection to the superordinate control unit is recognised after the supply voltage was applied, the module will change into the operating mode “independent operation”. The circuit protectors will adopt the condition specified by the configuration. If there is a connection between the Modbus controller and the superordinate control unit and there is no critical failure, the operating mode “independent operation” will be quitted. Should the connection between the Modbus controller and the superordinate control unit be interrupted during operation, the Modbus controller will automatically change into the operating mode “independent operation”.
Should the connection between the Modbus controller and the superordinate control unit be interrupted and the non-cyclical parameter “UNFREEZE” be set, all circuit protectors will be switched off before changing into the operating mode “independent operation”.
Should the connection between the Modbus controller and the superordinate control unit be interrupted and the non-cyclical parameter “FREEZE” be set, the condition of the circuit protectors will remain unchanged before changing into the operating mode “independent operation”.
By means of the non-cyclical parameter, the behaviour of the Modbus controller can be defined in the event of an interruption of the communication to the superordinate control unit.
Should the connection between the Modbus controller and the superordinate control unit be restored after a previous interruption, the operating mode “independent operation” will be quitted.
5.5 Operating mode: (Faultless operation) If there is neither a critical nor a non-critical failure and if there is a connection to the superordinate control
unit, the Modbus controller will change into the operating mode “faultless operation”. The parameters will be transmitted from the superordinate control unit to the Modbus controller and will be saved there. Subsequent­ly they will be forwarded to the electronic circuit protectors. The slot configuration data and slot parameters will be exchanged over Modbus Register between the superordinate control unit and the Modbus controller.
5.6 Operating mode: (bootloader)
®
ControlPlex
Views tool allows putting the Modbus Controller into the bootloader mode and to load a new
firmware. The actual procedure is described in a separate document.
5.7 Signalling of the various operating modes
The different operating modes of the Modbus controller are indicated as follows:
Operating mode Indication of operating mode Modbus communication
LED CE/CM system start of supply module independent operation faultless operation critical failure detected uncritical failure detected uncritical failure detected Bootloader active
green blinking not available
green available
red not available
yellow available
yellow blinking not available
red blinking not available
not defined
fig. 7: Available operating modes
10
Page 11
5.8 Signalling of operating conditions on circuit protector REX12D
The different operating modes of the REX12D are indicated as follows:
Operating condition LED for signalling Condition of
load output
channel switched off by momentary
dark OFF
switch channel switched on by momentary
orange OFF
switch and switched off by communication
channel switched on by momentary
green ON
switch and by communication selected threshold value exceeded overload detected tripped by short circuit
blinking green/orange ON
orange ON
red OFF
or overload low voltage detected
fig. 8: Signalling of operating conditions of circuit protector REX12D
red OFF
6 Basic functions of the entire system
6.1 Internal cycle times
®
The cycle time via the ELBus
is 530ms. During the aforementioned period the status and the load current of
each circuit protector is cyclically transmitted to Controller EM12D-TMB.
fig. 9: Cycle times of the system
6.2 Hot swap of circuit protectors
The electronic circuit protector REX12D can at any time be mounted side by side with a supply module or an existing system. By closing the connector arm a voltage supply of the device is available. Also, the device is
®
connected to the internal ELBus
.
Opening the connector arm is only permitted in the OFF condition. Opening under load can damage the device or cause undefined system conditions.
After plugging in a circuit protector, it will automatically be identified and parameterised if parameters are available for the slot in question. During this procedure the cyclical data will intermittently be marked as
unvalid.
11
Page 12
7 Communication via Modbus RTU
REX12D- TA2-100
DC24V
REX12D- TA2-100
DC24V
REX12D- TA2-100
2A
2A 4A
4A
DC24V
REX12D- TA2-100
2A
COM COM COM
X81
X82
0V
LINE + 1
Modbus
RTU
EM12D- TMB-xxx
7.1 ControlPlex® controller model
®
The EM12D-TMB has an internal ELBus protector REX12D. Up to 16 channels of the REX12D electronic circuit protectors (single channeled, multi­channeled or a mixed population) can be connected to the supply module.
REX12D-
EM12D­TMB-xxx
Modbus
RTU
X81
X82
0V
REX12D­TA2-100
DC24V
COM COM COM
2A 4A
2A
TA2-100
DC24V
4A
REX12D­TA2-100
DC24V
2A
2A
interface enabling the communication with the electronic circuit
REX12D-
REX12D­TA2-100
DC24V
COM COM COM
4A 2A
4A
TA2-100
DC24V
2A
REX12D­TA2-100
DC24V
4A
4A
REX12D­TA2-100
DC24V
COM COM
2A
2A
REX12D­TA2-100
DC24V
4A
4A
LINE + 1
fig. 10: ControlPlex® Controller: Model fitted with 8x 2-channeled REX12D-TA2-xx results in 16 channels
EM12D­TMB-xxx
Modbus
RTU
X81
X82
0V
LINE + 1
REX12D-
REX12D-
TA2-100
TA2-100
DC24V
DC24V
COM COM COM
2A 4A
2A
4A
REX12D­TA2-100
DC24V
2A
REX12D-
REX12D-
TA2-100
TA2-100
DC24V
DC24V
COM COM COM
4A
4A
2A
REX12D­TA2-100
DC24V
4A
4A
REX12D­TA2-100
DC24V
COM COM
2A
2A
REX12D­TA2-100
DC24V
4A
4A
fig. 11: ControlPlex® Controller: Model fitted with a mixture e.g. with 2x REX12D-TA1-xx and 7x REX12D-TA2-xx also results in 16 channels
12
Page 13
7.1.1 Error with faulty population
If a double channel device is connected as channel 16/17, the control unit will receive the information that a device is available at channel 16.
When reading out the Cominfo of the circuit protector, received the message that the circuit protector has wrong parameters.
The channels cannot be operated (cannot be switched on).
7.1.2 Error device addressing
Due to mechanical problems, there may be addressing errors. The LED on EM12D is permanently lighted orange. Possible causes are deformed or missing contacts in the connector arm. For putting the device into service again, the faulty circuit protector has to be removed and the supply voltage
has to be switched off and on again.
7.2 Physical interface
The physical interface used is RS485. Protocol used is the Modbus RTU protocol. It is unsusceptible to EMC disturbances and allows artless implementation of the bus communication.
7.3 Setting the communication parameters
The parameters for the communication to the Modbus server are realised by means of the switches on the device side.
1
0
x10 x1 busaddress
fig. 12: Potentiometers for the communication parameters
baudrate
parity
The address of the device is fixed in the bus structure by means of the potentiometers. The left rotary switch fixes the power of ten, the right one fixes the power of one.
x10 x1 busaddress
fig. 13: Potentiometers for the communication parameters
Bus address of the device in this example is 41.
13
Page 14
The communication speed and the parity bit are fixed by means of the DIP switches on the right side. For the definition of the switch please see the imprinted table.
fig. 14: Display of communication speed
The left DIP switch fixes the parity. The switching status is defined as follows:
Position “1”
Position “0”
fig. 15: Switching status of the DIP switches
In our example, the DIP switch is set to position “1” and the parity bit is set to “none”. The DIP switches 2 / 3 / 4 define the communication speed.
Stoppbit
For Stoppbit are two fix defined.
14
Page 15
8 Overview of Modbus registers
8.1 Voltage, current, status and control of channels
This list shows the various kinds of information and the corresponding registers.
Modbus register
47001 47002 47003
• 47016
47101 47102 47103
• 47116
47200
functional code
3 2 byte read 100 load voltage F1 3 2 byte read 100 load voltage F2 3 2 byte read 100 load voltage F3
3 2 byte status controller
data length write/read factor description
2 byte read 100 load voltage F16
2 byte read 100 load current F1 2 byte read 100 load current F2 2 byte read 100 load current F3
2 byte read 100 load voltage F16
47201 47202 47203
• 47216
47301 47302 47303
• 47316
fig. 16: Voltage, current, status and control of channels
3 1 byte read status F1 3 1 byte read status F2 3 1 byte read status F3
3 1 byte read status F16
6 & 16 2 byte write control F1 6 & 16 1 byte write control F2 6 & 16 1 byte write control F3
6 & 16 2 byte write control F16
15
Page 16
8.2 Values and parameters per channel and of the supply module
This list shows the various kinds of information and the corresponding registers.
Modbus register
functional code
write/read multiplication
factor
description
46001 6 write system commands 46002 3 read diagnosis controller 46003 6 & 3 read/write configuration controller 46004 16 & 6 & 3 read/write channels 1-16 controllable 46005 16 & 6 & 3 read/write channels 17-32 controllable 46006 16 & 6 & 3 read/write channels 33-48 controllable 46007 3 read product type 46008 3 read serial number 46009 46010 3 read hardware version 46011 3 read software version major.x.x 46012 3 read software version x.minor.x 46013 3 read software version x.x.build 460 (14..29) 16 & 3 read/write application specific tag
40101 6 & 3 read/write current rating F1 40201 6 & 3 read/write current rating F2 40301 6 & 3 read/write current rating F3
• 41601 6 & 3 read/write current rating F16
40102 6 & 3 read/write limit value load current F1 40202 6 & 3 read/write limit value load current F2 40302 6 & 3 read/write limit value load current F3
• 41602 6 & 3 read/write limit value load current F16
40109 6 & 3 read/write channel type (product type) F1 40209 6 & 3 read/write channel type (product type) F2 40309 6 & 3 read/write channel type (product type) F3
• 41609 6 & 3 read/write channel type (product type) F16
40110 3 read diagnosis channel F1 40210 3 read diagnosis channel F2 40310 3 read diagnosis channel F3
• 41610 3 read diagnosis channel F16
16
Page 17
Modbus register
40111 3 read error memory F1 40211 3 read error memory F2 40311 3 read error memory F3
• 41611 3 read error memory F16
40112 3 read trip counter F1 40212 3 read trip counter F2 40312 3 read trip counter F3
• 41612 3 read trip counter F16
40113 3 read trip reason F1 40213 3 read trip reason F2 40313 3 read trip reason F3
• 41613 3 read trip reason F16
functional code
write/read multiplication
factor
description
40116 3 read 100 Ø load voltage F1 40216 3 read 100 Ø load voltage F2 40316 3 read 100 Ø load voltage F3
• 41616 3 read 100 Ø load voltage F16
40117 3 read 100 max. load voltage F1 40217 3 read 100 max. load voltage F2 40317 3 read 100 max. load voltage F3
• 41617 3 read 100 max. load voltage F16
40118 3 read 100 min. load voltage F1 40218 3 read 100 min. load voltage F2 40318 3 read 100 min. load voltage F3
• 41618 3 read 100 min. load voltage F16
17
Page 18
Modbus register
functional code
write/read multiplication
factor
description
40119 3 read 100 Ø load current F1 40219 3 read 100 Ø load current F2 40319 3 read 100 Ø load current F3
• 41619 3 read 100 Ø load current F16
40120 3 read 100 max. load current F1 40220 3 read 100 max. load current F2 40320 3 read 100 max. load current F3
• 41620 3 read 100 max. load current F16
40121 3 read 100 min. load current F1 40221 3 read 100 min. load current F2 40321 3 read 100 min. load current F3
• 41621 3 read 100 min. load current F16
40122 3 read device type F1 40222 3 read device type F2 40322 3 read device type F3
• 41622 3 read device type F16
40123 3 read hardware version F1 40223 3 read hardware version F2 40323 3 read hardware version F3
• 41623 3 read hardware version F16
40124 3 read softwareversion major.x.x F1 40224 3 read software version major.x.x F2 40324 3 read software version major.x.x F3
• 41624 3 read software version major.x.x F16
18
Page 19
Modbus register
functional code
write/read factor description
40125 3 read software version minor.x.x F1 40225 3 read software version minor.x.x F2 40325 3 read software version minor.x.x F3
• 41625 3 read software version minor.x.x F16
40126 3 read software version built F1 40226 3 read software version built F2 40326 3 read software version built F3
• 41626 3 read software version built F16
40127 3 read serial number F1 40128 3 read 40227 3 read serial number F2 40228 3 read 40327 3 read serial number F3 40328 3 read
• 41627 3 read serial number F16 41628 3 read
40129 6 write action command F1 40229 6 write action command F2 40329 6 write action command F3
• 41629 6 write action command F16
45000 6 & 3 read/write history memory channel no. 45001 3 read history memory data
• 45400 3 read history memory data
fig. 17: Values and parameters per channel and of the supply module
19
Page 20
8.3 Explanation of the individual registers which are received
8.3.1 Load voltage circuit protector
Register 47001 – 47016 for channel 1-16, only readable, functional code 3. The load voltage is determined for each electronic circuit protector and transmitted cyclically to the interface
module. value range: 0-65535 (equals 0.0 – 655.35 V) data length: 1 word
The load voltage is made available as a standardised 16-bit-value with a solution of 10 mV. Example:
measuring value load voltage = 1025 ➞ real measuring value = 10.25 Volt.
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 18: load voltage circuit protector
8.3.2 Load current circuit protector
Register 47101 – 47116 for channel 1-16, only readable, functional code 3. Load current is determined for each electronic circuit protector and transmitted cyclically to the interface
module. value range: 0-65535 (equals 0.0 – 655.35 A) data length: 1 word
The load current is made available as a standardised 16-bit-value with a solution of 10 mA. measuring
value load current = 1025 ➞ real measuring value = 10.25 Ampere.
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 19: Load current circuit protector
8.3.3 Status of interface module
Register 47200, only readable, functional code 3. Status of interface module is determined and made available to the superordinate control unit. value range: 0 – 65535 data length: 1 word
20
Page 21
value
definition explanation
[dec.]
0 1
DEVICE IS OPERATING PROPERLY In all other events this value is transmitted MAINTENANCE REQUIRED This value is transmitted if one of the circuit protectors
tripped due to short circuit or overload
2
OUT OF SPECIFICATION This value is transmitted if one of the circuit protectors
detected an undervoltage
3 4
FUNCTIONAL CHECK Not supported DEVICE FAILURE This value is transmitted if one of the connected circuit
protectors has set the error-bit in the ELBus® Device Status.
fig. 20: Status of interface module
8.3.4 Status circuit protector
Register 47201 – 47216 for channel 1-16, only readable, functional code 3. Status for each electronic circuit protector is cyclically transmitted to the interface module. Individual status
information is shown in the following table. value range: 0 – 65535 data length: 1 word
Word bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 load output (ON/OFF) 0/1*
short circuit 0/1* overload 0/1*
reserve 0/1* reserve 0/1* reserve 0/1* limit value (reached/
0/1*
exceeded) hardware lock (OFF
0/1*
at the device itself)
Word bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1*
* status not set = 0 / status set = 1
fig. 21: status circuit protector
21
Page 22
8.3.5 Control of circuit protectors
Register 47301 – 47316 for channel 1-16, writable, functional codes 6 and 16. It is possible to access the circuit protectors from the superordinate control unit. Each channel of each
electronic circuit protector can be switched on or off or reset. Switch on or off is only possible if correspond­ing PLCLock Bit is set to false.
value range: 0–65535 data length: 1 word
Word bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 load output
0/1*
(ON/OFF) reset 0/1*
overload 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1*
Word bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1* reserve 0/1*
* status not set = 0 / status set = 1
fig. 22: Controlling the circuit protectors
8.3.6 System commands EM12D
Register 46001, writable, functional code 6. Depending to transmitted value one of following functions will be executed.
8.3.6.1 Reset to factory settings
Set Value 130 at Register load default Parameter at supply modul.
8.3.6.2 Reset statistical information
Set Value 250 at Register reset all Statisticinformation at all channels. It is equally possible to reset these pieces of information channel-wise. This is described in the chapter of the action commands.
22
Page 23
8.3.7 Diagnostic information of the intelligent interface module EM12D
Register 46002, readable, functional code 3. The following global errors and diagnostic messages are returned. Evaluation is bit-wise. value range: 0 – 65535 data length: 1 word (unsigned integer)
byte [0] bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
TN_SysNoConfig 0/1
TN_SysConfigMismatch 0/1
0/1
0/1
TN_SysQueueFull 0/1
0/1
0/1
TN_ELBusDown 0/1
byte [1] bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
0/1 TN_SysWatchdogReset 0/1 TN_SysHardwareError 0/1 (TN_SysBrownout) volt-
0/1
age dip
0/1
0/1
0/1
0/1
fig. 23: Diagnostic information of the intelligent interface module EM12D
23
Page 24
8.3.8 Configuration data of the EM12D intelligent supply module
Register 46003, readable, writable, functional code 6 and 3. This register holds the configuration data of the intelligent supply module EM12D. Evaluation is bit-wise. value range: Bit 0-15 Default value: power saving mode de-activated, freeze active data length: 1 word (unsigned integer)
byte [0] bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
0/1 offline behaviour
0/1
(unfreeze/freeze)
power saving mode 0/1
0/1
0/1
0/1
0/1
0/1
byte [1] bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
fig. 24: Configuration data of the EM12D intelligent supply module
Behaviour in the event of communication disruption: Bit 1 unfreeze = 0 all load outputs (channels) of the circuit protectors are switched off and the
EM12D-TMB changes into the operating mode “independent operation”.
Bit 2 freeze = 1 all load outputs (channels) of the circuit protectors remain in their current
condition and the EM12D-TMB changes into the operating mode “Independent operation”.
Bit 2 power saving mode deactivated = 0 LEDs always have full illuminating power
power saving mode activated = 1 LEDs have reduced illuminating power in the
OK condition
24
Page 25
8.3.9 Configure controllability of the channels via PLCLock in the EM12D supply module
Register 46004, readable, writable, functional code 3, 6 and 16. The status PLCLock is fed back for all possible 16 channels via one word with one bit each representing the
status of a channel: value range: Bit 0-15 data length: 1 word (unsigned integer)
byte [0] bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
PLCLock channel 1 0/1 PLCLock channel 2 0/1 PLCLock channel 3 0/1
PLCLock channel 4 0/1 PLCLock channel 5 0/1 PLCLock channel 6 0/1 PLCLock channel 7 0/1 PLCLock channel 8 0/1
byte [1] bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
PLCLock channel 9 0/1 PLCLock channel 10 0/1 PLCLock channel 11 0/1 PLCLock channel 12 0/1 PLCLock channel 13 0/1 PLCLock channel 14 0/1 PLCLock channel 15 0/1 PLCLock channel 16 0/1
fig. 25: Configure controllability of the channels via PLCLock in the EM12D supply module
Setting the bit means that the channel cannot be switched on or off via the control unit. This means that volt­age is applied to the output of the channel when the supply voltage is switched on (provided the channel did not trip previously).
8.3.10 Device type of EM12D supply module
Register 46007, readable, functional code 3. The register holds information on the device type of the intelligent supply module EM12D. value range: 0 – 65535 data length: 1 word
Value Device type
1 EM12D-TMB
25
Page 26
8.3.11 Serial number EM12D
Register 46008 - 46009, readable, functional code 3. This two registers hold information on the serial no. of the intelligent supply module EM12D. value range: 0 – 4294967295 data length: 2 word
byte[1] (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte [2] bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte [3] bit 19 bit 18 bit 17 bit 16
description 524288 262144 131072 65536
value 0/1 0/1 0/1 0/1
byte [3] bit 23 bit 22 bit 21 bit 20
description 8388608 4194304 2097152 1048576
value 0/1 0/1 0/1 0/1
byte [4] (HIGH) bit 27 bit 26 bit 25 bit 24
description 134217728 67108864 33554432 16777216
value 0/1 0/1 0/1 0/1
byte [4] (HIGH) bit 31 bit 30 bit 29 bit 28
description 2147483648 1073741824 536870912 268435456
value 0/1 0/1 0/1 0/1
fig. 26: Serial number EM12D
8.3.12 Hardware version EM12D
Register 46010, readable, functional code 3. This register holds information on the hardware version of the intelligent supply module EM12D. value range: 0 – 65535 data length: 1 word
8.3.13 Software version EM12D
Register 46011 – 46013, readable, functional code 3. This register contain the software version of the intelligent supply module EM12D-TMB. value range: major.minor.build data length: 3 word
description format: register
major.x.x Word x1
software version
x.minor.x Word x2 x.x.build Word x3
fig. 27: software version EM12D
26
Page 27
8.3.14 Application Specific Tag EM12D
Register 46014 – 46029 for channel 1-16, writable, functional codes 3 and 16. A customer-specific text can be entered here. The text can hold up to 32 characters. One register holds two
characters. value range: text data length: 16 word
8.3.15 Current rating REX12D
Register 4(01..16)01 for channel 1-16, readable, writable, functional codes 3 and 6. The parameter returns the current rating of the channel in Amp, depending on the device type. This value is
both readable and writable. value range: 1-10 (integer) default value: 1 data length: 1 word
8.3.16 Limit value load current REX12D
Register 4(01..16)02 for channel 1-16, readable, writable, functional codes 3 and 6. The parameter determines at how many percent of the rated current the channel will signal "limit value
exceeded". This parameter is readable/writable. value range: 50 % - 100 % (whole numbers) default value: 80 % data length: 1 word
27
Page 28
8.3.17 Channel diagnosis REX12D
Register 4(01...16)01 for channel 1-16, readable, functional code 3. This register contains diagnosticinformation about connected protector channel. For the meaning of the
values please see the following table. value range: 0 – 255 data length: 1 word
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
Detected unsupported device. An
0 0 0 0 0 0 0 1 unsupported circuit protector was included in the system.
The transmitted device parameters
1 0 0 1 0 0 0 0 were rejected by the circuit protec­tor, because they are outside of the valid range.
Reserve 1 0 0 1 0 0 0 1 Channel locked. The channel was
1 0 0 1 0 0 1 0 locked out by actuating the integral momentary switch and cannot be switched on by the IO link master.
Low voltage detected.
1 0 0 1 0 0 1 1 The operating voltage is below the safe range.
Reserve 1 0 0 1 0 1 0 0 Device tripped. A reset command
1 0 0 1 1 0 0 0 has to be sent.
No error 0 0 0 0 0 0 0 0 The circuit protector is not
1 0 0 1 0 1 1 1 parameterised.
Internal error detected. 1 0 0 1 1 0 0 0 Reserve 1 0 0 1 1 0 0 1 Reserve 1 0 0 1 1 0 1 1 Internal ELBus
®
error detected
1 0 0 1 1 0 1 1 (temporary disruption). This error can be caused by strong EMI.
Reserve 1 0 0 1 1 1 0 0 No device available. 0 0 0 0 0 0 1 0
fig. 28: Channel diagnosis REX12D
28
Page 29
8.3.18 Error memory REX12D
Register 4(01..16)11 for channel 1-16, readable, functional code 3. Parameters holds the internal error memory of the circuit protector. value range: 0 – 255 data length: 1 word
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
no parameters available 0/1* error parameter memory 0/1*
error programme memory 0/1* error data memory 0/1* error control unit 0/1*
reset through watchdog 0/1* reserve reserve
* error not available = 0 / error available = 1
fig. 29: Error memory REX12D
8.3.19 Trip counter REX12D
Register 4(01..16)12 for channel 1-16, readable, functional code 3. The number of all trippings occurred up to now are stored in this parameter. Each trip operation of the circuit
protector is stored and added. Thus the service personnel has an exact overview of the number of trip operations.
8.3.20 Trip reason REX12D
Register 4(01..16)13 for channel 1-16, readable, functional code 3. The parameter holds the latest trip reason of the channel. value range: 0, 1, 2, 4 data length: 1 word
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description
128 64 32 16 8 4 2 1 no reason for trip available (0) 0 0 0 0 0 0 0 0
short circuit (1) 0 0 0 0 0 0 0 1 overload (2) 0 0 0 0 0 0 1 0
internal failure (4) 0 0 0 0 0 1 0 0
fig. 30: Trip reason REX12D
29
Page 30
8.3.21 Voltage average REX12D
Register 4(01..16)16 for channel 1-16, readable, functional code 3. Contains the voltage average of the channel since the last reset. value range: 0-65535 (equals 0.0 – 655.35 V) data length: 1 word
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 31: Mean value voltage REX12D
The voltage average is made available as a standardised 16-bit-value with a resolution of 10 mV. Example: measuring value operating voltage = 2512 ➞ real measuring value = 25.12 Volt
8.3.22 Maximum voltage REX12D
Register 4(01..16)17 for channel 1-16, readable, functional code 3. Contains the highest measured voltage of the channel since the last reset. value range: 0-65535 (equals 0.0 – 655.35 V) data length: 1 word
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 32: Maximum voltage REX12D
The maximum voltage is made available as a standardised 16-bit-value with a resolution of 10 mV. Example: measuring value operating voltage = 2512 ➞ real measuring value = 25.12 Volt.
30
Page 31
8.3.23 Minimum voltage REX12D
Register 4(01..16)18 for channel 1-16, readable, functional code 3. Contains the highest measured voltage of the channel since the last reset. value range: 0-65535 (equals 0.0 – 655.35 V) data length: 1 word
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 33: Minimum voltage channel
The minimum voltage is made available as a standardised 16-bit-value with a resolution of 10 mV. Example: measuring value operating voltage = 2512 ➞ real measuring value = 25.12 Volt
8.3.24 Current average REX12D
Register 4(01..16)19 for channel 1-16, readable, functional code 3. Contains the current average of the channel since the last reset. value range: 0-65535 (equals 0.0 – 655.35 V) data length: 1 word
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 34: Current average channel
The current average is made available as standardised 16 bit value with a resolution of 10 mA (resolution of the channel is one decimal place, for simplification it is shown identically with the voltage with 2 decimal places). Example: measuring value operating voltage = 710
-> real measuring value = 7.10 Ampere
31
Page 32
8.3.25 Maximum current REX12D
Register 4(01..16)20 for channel 1-16, readable, functional code 3. Contains the highest current value of the channel since the last reset. value range: 0-65535 (equals 0.0 – 655.35 A) data length: 1 word
byte[9] (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte[10] (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 35: Maximum current channel
The maximum current is made available as standardised 16 bit value with a resolution of 10 mA (resolution of the channel is one decimal place, for simplification it is shown identically with the voltage with 2 decimal places). Example: measuring value operating voltage = 710
->➞ real measuring value = 7.10 Ampere
8.3.26 Minimum current REX12D
Register 4(01..16)21 for channel 1-16, readable, functional code 3. Contains the lowest current value of the channel since the last reset. value range: 0-65535 (equals 0.0 – 655.35 A) data length: 1 word
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 36: Minimum current channel
The minimum current is made available as standardised 16 bit value with a resolution of 10 mA (resolution of the channel is one decimal place, for simplification it is shown identically with the voltage with 2 decimal places). Example: measuring value operating voltage = 710
->➞ real measuring value = 7.10 Ampere
8.3.27 Channel type REX12D
Register 4(01..16)22 for channel 1-16, readable, functional code 3. The parameter indicates the type of device with which the interface module is communicating. The word contains information on the device type of circuit protector. value range: 0-65535 failure: Circuit protector type not available (255) data length: 1 word
32
Page 33
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 REX12D (144) 1 0 0 1 0 0 0 0
byte (HIGH) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 TA1 (9) 0 0 0 0 1 0 0 1 TA2 (10) 0 0 0 0 1 0 1 0 TA4 (11) 0 0 0 0 1 0 1 1 TE2 (14) 0 0 0 0 1 1 1 0
fig. 37: Channel type REX12D
8.3.28 Hardware version REX12D
Register 4(01..16)23 for channel 1-16, readable, functional code 3. Holds the hardware version of the corresponding channel: The hardware version is made available in whole
numbers. value range: 0…65535 error: Hardware version not available (65535) data length: 1 word
byte (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte (HIGH) bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
fig. 38: Device information channel: hardware version
8.3.29 Software version REX12D
Register 4(01..16)24 - 4(01..16)26 for channel 1-16, readable, functional code 3. Holds the software version version of the corresponding channel: The software version is made available
coded. It is coded as follows: value range: major.minor.build data length: 3 word
description format: register
major.x.x Word x24
software version
x.minor.x Word x25 x.x.build Word x26
fig. 39: device information channel: Software version
33
Page 34
8.3.30 Serial number REX12D
Register 4(01..16)27 - 4(01..16)28 for channel 1-16, readable, functional code 3. Holds the serial number of the corresponding channel: value range: 0…4294967295 error: Serial number not available (4294967295) data length: 2 word
byte[1] (LOW) bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte [2] bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
description 32768 16384 8192 4096 2048 1024 512 256
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
byte [3] bit 19 bit 18 bit 17 bit 16
description 524288 262144 131072 65536
value 0/1 0/1 0/1 0/1
byte [3] bit 23 bit 22 bit 21 bit 20
description 8388608 4194304 2097152 1048576
value 0/1 0/1 0/1 0/1
byte [4] (HIGH) bit 27 bit 26 bit 25 bit 24
description 134217728 67108864 33554432 16777216
value 0/1 0/1 0/1 0/1
byte [4] (HIGH) bit 31 bit 30 bit 29 bit 28
description 2147483648 1073741824 536870912 268435456
value 0/1 0/1 0/1 0/1
fig. 40: Device information channel: serial number
34
Page 35
8.3.31 Action commands channel REX12D
Register 4(01..16)29 for channel 1-16, readable, functional code 6. One byte is transmitted, which carries out the following functions depending on its value. value range: 115-120 data length: 1 byte (unsigned character)
byte [1] bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
description 128 64 32 16 8 4 2 1
value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 reset
error memory (115) reset
trip counter (116) reset minimum
statistics (117) reset maximum
statistics (118) reset medium
value statistics (119) reset all
statistical values (120)
0 1 1 1 0 0 1 1
0 1 1 1 0 1 0 0
0 1 1 1 0 1 0 1
0 1 1 1 0 1 1 0
0 1 1 1 0 1 1 1
0 1 1 1 1 0 0 0
fig. 41: Action commands channel REX12D
35
Page 36
9 Appendix
9.1 List of pictures
fig. 1: System overview ................................................................................................................................... 6
fig. 2: EM12D-TMB ..........................................................................................................................................7
fig. 3: Status indicators and terminals EM12D-light emitting diode “CE/CM” ..........................................7
fig. 4: mounting attitude .................................................................................................................................. 8
fig. 5: Modbus RTU connection ...................................................................................................................... 8
fig. 6: Marking of date code ............................................................................................................................9
fig. 7: List of the available operating modes ............................................................................................... 10
fig. 8: Signalling of operating conditions of REX12D .................................................................................11
fig. 10: ControlPlex
fig. 11: ControlPlex® Controller: population ................................................................................................ 12
fig. 12: Adjustment elements for the communication parameters ...........................................................13
fig. 13: Adjustment elements for the communication parameters ...........................................................13
fig. 14: Display of communication speed .................................................................................................... 13
fig. 15: Switching status of the DIP switches .............................................................................................14
fig. 16: Voltage, current, status and control of channels ........................................................................... 15
fig. 17: Values and parameters per channel and of the supply module ...................................................16
fig. 18: Load voltage circuit protector .........................................................................................................20
fig. 19: Load current circuit protector .........................................................................................................20
fig. 20: Status of interface module ............................................................................................................... 21
fig. 21: Status of circuit protector ................................................................................................................21
fig. 22: Controlling the circuit protectors ....................................................................................................22
fig. 23: Diagnostic information of the intelligent interface module EM12D .............................................23
fig. 24: Configuration data of the EM12D intelligent supply module ........................................................ 24
fig. 25: Controllability of the channels configure PLCLock of EM12D supply module ...........................25
fig. 26: Serial number EM12D ....................................................................................................................... 26
fig. 27: Software version EM12D .................................................................................................................. 26
fig. 28: Channel diagnosis REX12D..............................................................................................................28
fig. 29: Error memory REX12D .....................................................................................................................29
fig. 30: Trip reason REX12D .......................................................................................................................... 29
fig. 31: Mean value voltage REX12D ............................................................................................................ 30
fig. 32: Maximum voltage REX12D ............................................................................................................... 30
fig. 33: Minimum voltage channel ................................................................................................................31
fig. 34: Mean value current channel ............................................................................................................. 31
fig. 35: Maximum current channel ...............................................................................................................32
fig. 36: Minimum current channel ................................................................................................................32
fig. 37: Channel type REX ............................................................................................................................ 2D
fig. 38: Device information channel: hardware version ..............................................................................33
fig. 39: Device information channel: software version ............................................................................... 33
fig. 40: Device information channel: Serial number ...................................................................................34
fig. 41: Action commands channel REX12D ...............................................................................................35
®
Controller: population ................................................................................................ 12
9.2 Technical data For the technical data of EM12D-TMB please see relevant data sheet.
36
Page 37
37
Page 38
http://www.e-t-a.de/QR1033/
Bedienungsanleitung/Instruction manual B_CP_EM12D-TMB-xxx_e_140218 Bestell-Nr./Ref. number Y31274802 - Index: b Issue 11/2018 Alle Rechte vorbehalten / All rights reserved
E-T-A Elektrotechnische Apparate GmbH Industriestraße 2-8 . 90518 ALTDORF GERMANY Phone +49 9187 10-0 . Fax 09187 10-397 E-Mail: info@e-t-a.de . www.e-t-a.de
Loading...