4.3.1 Examining a Problem ..................................................................141
4.3.2 Problems and Countermeasures................................................. 143
4.3.3 Procedures for Examining Possible Causes ............................... 144
viii Fieldbus I/O Rev.6
Table of Contents
5. Maintenance Parts List ................................................ 151
Appendix A applicomIO Upgrade.................................... 153
Fieldbus I/O Rev.6 ix
Table of Contents
x Fieldbus I/O Rev.6
1. Introduction
1.1 Overview of Fieldbus I/O
The Fieldbus I/O option is an integrated I/O system that supports DeviceNet, PROFIBUS DP,
and EtherNet/IP fieldbuses.
A fieldbus is a standard of signal communications between field devices operating in a
factory (sensor, actuator, robot controller, etc.) and controller (PLC or robot controller) using
serial communications. Compared to signal communications using analog signals, a fieldbus
has the following features:
• Access to signals from multiple devices and multiple data from each device using
one cable.
1. Introduction
• Precise signal transmission since there is no need for A/D conversion and D/A
conversion.
• Less wiring costs, including signal relay board costs and installation area due to
several dozen (or a hundred) devices connected on one fieldbus.
• More flexible modification and expansion of a system because multiple devices are
simply added to one fieldbus without additional wiring.
• Slave devices can transmit self-diagnostics information.
For each fieldbus on the RCxxx controller, there is at least one board installed. You can use
more that one fieldbus type on the same controller. You can also use multiple boards for the
same fieldbus type. The EPSON RC+ software key Fieldbus I/O Option must be enabled to
use this option.
Response times for Fieldbus I/O can vary and depend on several factors, including baud rate,
scan rate, number and types of devices, number of SPEL+ tasks, etc. When the fastest and
most consistent response times are required, please use EPSON standard digital I/O, which
incorporates interrupt driven inputs and outputs.
1. Introduction
1.2 DeviceNet
Overview of DeviceNet
DeviceNet is a fieldbus network that provides easy interconnection between control devices
(PLC, PC, sensor, actuator, etc.).
DeviceNet was developed by Allen-Bradley as an open communication standard to connect
various field devices (sensor, actuator, robot controller, etc.). Because of the open
communication standard, DeviceNet users can easily construct a multi-vendor system with
various devices developed around the world.
Controller
DeviceNet Network
Motor Driver
from Company A
Analog Device
from Company G
Motor Driver
from Company B
Intelligent I/O
from Company C
Intelligent I/O
from Company D
Photo Sensor
from Company E
HMI Device
from Company F
Features of DeviceNet
Reduced Wiring
Compared with parallel wiring, DeviceNet employs a dedicated 5-wire cable (signal wires
and power wires) which substantially reduces the number of necessary wires, wiring time and
cost.
Detachable communication connectors provide you with simple wiring between nodes and
easy network separation or reconstruction.
Specified environment-resistance cables allow you to construct an environment-resistant
system at low cost.
Open Standard (Multi-vendor)
Due to an open communication standard, various devices from many manufacturers are
available. Standardized communication connectors provide you with easy network
construction.
The maintenance spare parts stored on site (factory, etc.) can be reduced because different
manufacturers’ devices are used in case of a breakdown. Similar products are available
around the world due to a global standard DeviceNet.
Large Numbers of Inputs/Outputs
For EPSON RC+ standard I/O and expansion I/O, the number of inputs/outputs is limited to
512 inputs and 512 outputs. When configuring a device to be a master of fieldbus I/O, you
can control more than 16,000 total inputs and outputs.
For a slave device, 2,040 inputs (255 bytes) and 2,040 outputs (255 bytes) are available.
2 Fieldbus I/O Rev.6
1. Introduction
Different Connection Types
There are two messaging connections: I/O messaging connection and explicit messaging
connection. The I/O messaging connection includes polling, strobe, cyclic, and change of
state. I/O messaging connections are explained below:
Polling: First, a master device sends output data to a slave device and then the slave device
responds. Data is normally exchanged in every communication cycle. The
communication frequency can be changed by setting. This connection type is the
most often used.
Strobe: First, a master device requests slave devices to send data with multicast messages,
and then, each slave device responds separately.
Data from many sensors on the system can be effectively gathered. When the master
does not receive responses from all requested slave devices, a timeout error occurs.
Change Of State:
A device sends data whenever it changes. Signals for device diagnosis are sent
regularly in the background. This connection type is useful for remedying DeviceNet
communication traffic.
Cyclic: A slave device transfers data regularly according to its internal timer. This
connection type is typically used for communicating with a temperature controller.
The data transfer frequency is defined by master configuration.
NOTE
)
For Change of State and Cyclic, you can disable the ACK that is for verifying that
communication is completed. Never disable ACK, since communication errors cannot be
detected.
Functions of Master
The Master device gathers and controls all nodes on one network.
A DeviceNet master can control up to 64 nodes (max. 2 kbytes) on one network.
A PLC is typically configured as a master and controls all nodes in factory automation system,
but EPSON RC+ is also capable of being a master.
DeviceNet network configuration is specified by configuration management software. This
software is normally provided by a master device manufacturer. The configuration
management software determines parameters for each slave device via an Electronic Data
Sheet (EDS).
Available connection types are Polling, Strove, Cyclic, Change Of State, and explicit
messaging.
Available baud rates are 125 kbps, 250 kbps, and 500 kbps.
Functions of Slave
A slave can exchange data with a master device.
The configuration management software identifies parameters of each slave device via
Electronic Data Sheet (EDS) where the parameters are registered.
Available connection types are Polling, Strobe, Cyclic, and Change of State.
Available baud rates are 125 kbps, 250 kbps, and 500 kbps.
Fieldbus I/O Rev.6 3
1. Introduction
General Specifications
Electrical Specifications
Item Specification
Supply Voltage 5 V DC (supplied from a controller)
Power Consumption 7 W
Ambient Temperature 5-40 deg C
Relative Humidity 20-80%
DeviceNet Communication Specifications
Item Specification
Supported Connection - I/O messaging connection
(Polling, Strove, Cyclic, Change of State)
- Explicit messaging connection
All connections are conformed to DeviceNet communication
protocol.
Baud Rates 125 kbps, 250 kbps, 500 kbps
Transfer Distance
Maximum Nodes 64 (including master unit)
Data Length / Frame 8 byte (The data can be divided and transferred.)
Bus Access CSMA/NBA
Error Detection CRC error / Duplicate node address check
Cable 5-wire cable dedicated to DeviceNet (2 wires for signal,
Communications
Power Supply Voltage
Baud Rates
500 kbps
250 kbps
125 kbps
2 wires for power supply, 1 shield wire)
24 V DC (supplied from a connector)
Max. Network
Length
100 m
250 m *
500 m *
Drop Length
6 m or under
6 m or under
6 m or under
Total Drop
Line Length
39 m or under
78 m or under
156 m or under
* When thin cable is used for trunk line, the maximum network length is 100 m.
4 Fieldbus I/O Rev.6
A
1.3 PROFIBUS DP
Overview of PROFIBUS DP
PROFIBUS DP is one of fieldbus networks that provide easy interconnection between control
devices (PLC, PC, sensor, actuator, etc.).
PROFIBUS DP was co-developed by Siemens, Bosch, and ABB as an open communication
standard to connect various field devices (sensor, actuator, robot controller, etc.). Because of
the open communication standard, PROFIBUS DP can easily construct multi-vendor system
with various devices developed around the world.
PROFIBUS DP Network
1. Introduction
Controller
Motor Driver
from Company A
nalog Device
from Company G
Motor Driver
from Company B
Intelligent I/O
from Company C
Intelligent I/O
from Company D
Photo Sensor
from Company E
HMI Device
from Company F
Features of PROFIBUS DP
Reduced Wiring
Compared with a parallel wiring, PROFIBUS DP employing dedicated 2-wire cable
substantially reduces the number of necessary wires, wiring time and cost.
Detachable communication connector provides you a simple wiring between devices
(stations) and an easy network separation or reconstruction.
Fast Communication
PROFIBUS DP communication speed can be set up to 12Mbps. This is faster than
DeviceNet, another communication standard supported by the fieldbus I/O.
Open Standard (Multi-vendor)
Due to an open communication standard, various devices from many manufacturers are
available. Standardized communication connectors allow you to reconstruct your network
easily.
The sort of maintenance parts stored on site (factory, etc.) can be reduced because different
manufacturers’ devices are used in case of a breakdown. Similar products are available
around the world due to a global standard PROFIBUS DP.
Large Numbers of Inputs/Outputs
For the standard I/O and expansion I/O, the number of inputs/outputs is limited to up to 512
inputs and 512 outputs. When configuring a device to be a master of fieldbus I/O, you can
control more than 16,000 total inputs and outputs.
For a slave device, 1,952 inputs (244 bytes) and 1,952 outputs (244 bytes) are available.
Fieldbus I/O Rev.6 5
1. Introduction
Functions of Master
There are two types of PROFIBUS DP master: DPM1 and DPM2. DPM1 (DP Master Class
1) gathers and controls all stations on one PROFIBUS DP network. DPM2 (DP master Class
2) operates network configurations, network maintenance, and diagnosis.
PROFIBUS DP master can control up to 126 stations (max. 2 kbytes) on one network.
A PLC is typically configured as a master and controls all devices in factory automation
system, but EPSON RC+ is also capable of being a master.
PROFIBUS DP network configuration is specified by configuration management software.
This software is normally provided by a master device manufacturer. The configuration
management software determines parameters for each slave device via an Electronic Data
Sheet (GSD).
The connection type is token passing procedure and master-slave communication. The token
passing procedure is applied to the PROFIBUS DP network with more than two master
devices to transfer network control between masters. The master-slave communication is
applied to the communication between the master device with network control and its slave
devices.
Available baud rates are 9.6 kbps, 19.2 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1500 kbps, 3
Mbps, 6 Mbps, and 12 Mbps.
Functions of Slave
A slave can exchange data with a master device.
The configuration management software identifies parameters of each slave device via an
electronic data sheet (GSD) file where the parameters are registered.
The communication type is a cyclic master-slave communication.
The input/output data of each station is up to 244 bytes.
Available baud rates are 9.6 kbps, 19.2 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1500 kbps, 3
Mbps, 6 Mbps, and 12 Mbps.
6 Fieldbus I/O Rev.6
1. Introduction
General Specifications
Electrical Specifications
Item Specification
Supply Voltage 5 V DC (supplied from a controller)
Power Consumption 5.5 W
Ambient Temperature during Operation5-40 deg C
Relative Humidity during Operation 20-80%
PROFIBUS DP Communication Specifications
Item Specification
Connection MethodHybrid
(token passing procedure and master-slave communication)
9.6 kbps
Maximum Stations 126 (including master unit and repeater)
Data Length / Frame244 bytes
Cable 2-wire cable dedicated to PROFIBUS (2 wires for signal)
100 m
100 m
100 m
200 m
400 m
1000 m
1200 m
1200 m
1200 m
Fieldbus I/O Rev.6 7
1. Introduction
1.4 EtherNet/IP
Overview of EtherNet/IP
EtherNet/IP is a fieldbus network that provides easy interconnection between control devices
(PLC, PC, sensor, actuator, etc.).
EtherNet/IP was developed by Allen-Bradley as an open communication standard to connect
various field devices (sensor, actuator, robot controller, etc.). Because of the open
communication standard, EtherNet/IP users can easily construct a multi-vendor system with
various devices developed around the world.
Controller
Ethernet/IP Network
Motor Driver
from Company A
NOTE
)
Analog Device
from Company G
Motor Driver
from Company B
Intelligent I/O
from Company C
Intelligent I/O
from Company D
Photo Sensor
from Company E
HMI Device
from Company F
Features of EtherNet/IP
Reduced Wiring
Compared with parallel wiring, EtherNet/IP employs a standard Ethernet cable which
substantially reduces the number of necessary wires, wiring time and cost.
Detachable communication connectors provide you with simple wiring between nodes and
easy network separation or reconstruction.
Specified environment-resistance cables allow you to construct an environment-resistant
system at low cost.
You can use the generic Ethernet hub or Ethernet switch for the EtherNet/IP. However, be
sure to a use product complying with the industrial standards or noise resistant Ethernet
cable (STP cable). If you use an office use product or UTP cable, it may causes
communication errors and may not offer the proper performance.
Open Standard (Multi-vendor)
Due to an open communication standard, various devices from many manufacturers are
available. Standardized communication connectors provide you with easy network
construction.
The maintenance spare parts stored on site (factory, etc.) can be reduced because different
manufacturers’ devices are used in case of a breakdown. Similar products are available
around the world due to a global standard EtherNet/IP.
8 Fieldbus I/O Rev.6
NOTE
)
1. Introduction
Large Numbers of Inputs/Outputs
For EPSON RC+ standard I/O and expansion I/O, the number of inputs/outputs is limited to
512 inputs and 512 outputs. When configuring a device to be a master of fieldbus I/O, you
can control more than 16,000 total inputs and outputs.
For a slave device, 4,040 inputs (505 bytes) and 4,072 outputs (509 bytes) are available.
Different Connection Types
There are two messaging connections: I/O messaging connection and explicit messaging
connection. The I/O messaging connection includes cyclic and change of state. I/O
messaging connections are explained below:
Change Of State:
A device sends data whenever it changes. Signals for device diagnosis are sent
regularly in the background. This connection type is useful for remedying
EtherNet/IP communication traffic.
Cyclic: A slave device transfers data regularly according to its internal timer. This
connection type is typically used for communicating with a temperature controller.
The data transfer frequency is defined by master configuration.
For Change of State and Cyclic, you can disable the ACK that is for verifying that
communication is completed. Never disable ACK, since communication errors cannot be
detected.
Functions of Master
The Master device gathers and controls all nodes on one network.
A EtherNet/IP master can control up to 127 nodes (max. 14 kbytes) on one network.
A PLC is typically configured as a master and controls all nodes in factory automation system,
but EPSON RC+ is also capable of being a master.
EtherNet/IP network configuration is specified by configuration management software. This
software is normally provided by a master device manufacturer. The configuration
management software determines parameters for each slave device via an Electronic Data
Sheet (EDS).
Available connection types are Cyclic, Change Of State, and explicit messaging.
Available baud rates are 100 Mbps and 10 Mbps. (auto-detect)
Functions of Slave
A slave can exchange data with a master device.
The configuration management software identifies parameters of each slave device via
Electronic Data Sheet (EDS) where the parameters are registered.
Available connection type is Cyclic.
Available baud rates are 100 Mbps and 10 Mbps. (auto-detect)
Fieldbus I/O Rev.6 9
1. Introduction
General Specifications
Electrical Specifications
Item Specification
Supply Voltage 5 V DC (supplied from a controller)
Power Consumption 5.5 W
Ambient Temperature 5-40 deg C
Relative Humidity 20-80%
EtherNet/IP Communication Specifications
Item Specification
Supported Connection - I/O messaging connection
(Cyclic, Change of State)
- Explicit messaging connection
All connections are conformed to EtherNet/IP communication
protocol.
Baud Rates 100 Mbps, 10 Mbps
Maximum Nodes 128 (including master unit)
Data Length / Frame 244 bytes
Access Control Type CSMA/CD
Cable Universal Ethernet cable
10 Fieldbus I/O Rev.6
2. Installation
This chapter contains procedures for installing a DeviceNet, PROFIBUS DP, or EtherNet/IP
network. Refer to the sections that correspond to the type of network you are installing.
2.1 How to Setup a DeviceNet Network
The following is a basic procedure for setting up a DeviceNet network:
1. Choose node distribution and distribution route on your network.
For details, refer to the following section 2.2 DeviceNet Network Construction.
2. Choose power supply method for communication.
For details, refer to the following section 2.2 DeviceNet Network Construction.
2. Installation
3. Choose baud rate.
Choose the baud rate based on the network length. Select the fastest baud allowed
for the length. Increasing network load due to slow baud rate may cause trouble
including communication failure.
4. Lay cables.
For details, refer to the following section 2.2 DeviceNet Network Construction.
5. Configure nodes.
For details, refer to respective manuals of your desired nodes.
6. Turn ON the communications power supply and nodes.
Turn ON the communications power supply. After that or simultaneously, turn ON
the nodes to supply power. When the power to the nodes is supplied earlier than the
power to the communications power supply, communication with the nodes may fail.
7. Install the scanner board in your controller.
Refer to the section 2.7 DeviceNet Board Installation later in this chapter.
8. Configure a master and slaves.
Use the configuration management software for configuring a master and slaves
(scan list). For details, please refer to the configuration management software
manual.
To configure EPSON RC+ as a master, refer to the section 2.7 DeviceNet Board Installation later in this chapter.
9. Configure EPSON RC+.
Refer to the section 2.10 EPSON RC+ Fieldbus I/O Installation later in this chapter.
10. Operate the DeviceNet network.
Fieldbus I/O Rev.6 11
2. Installation
p
y
A
A
r
r
2.2 DeviceNet Network Construction
Network Configuration
A DeviceNet network is configured as shown in the following figure.
ttach a terminating
resistor on each end
of the trunk line.
Trunk Line
T-branch
Tap
Drop Line
Node
Drop
Line
Node
Node
There are two types of the node: master and slave. The master controls a network and gathers
data from its slaves. The slaves, including external I/O and other devices, output data in
response to the master’s output order and informs the master of its input status.
You can install masters anywhere in the network. You can connect up to 64 nodes (including
the master) on your network.
Ground to
100 Ω or less.
Trunk Line
Drop
Line
Communications
ower suppl
24 V DC
Trunk Line
T-branch
Tap
Drop Line
Node
Drop Line
Node
Use DeviceNet cables.
Power Supply Tap or
T-branch Tap
Trunk
T-branch Tap
Drop Line
Drop Line
Node
Node
T-branch
Connector
Line
T-branch Tap
Node
Trunk
Line
Drop
Line
Waterproof
slave
ttach a terminating
resistor on each end
of the trunk line.
T-branch
Connector
Connector with
Line
terminating
resistor
Waterproof
slave
Drop
Trunk Line and Drop Line
A trunk line is a backbone cable of DeviceNet network with a terminating resistor on the both
ends.
A drop line is a branch of the trunk line.
Terminating
resisto
Trunk Line
T-branch
These are all drop Lines.
Terminating
resisto
- No limits on the number of T-branch
- Limits on the length of drop lines
For DeviceNet, 5-wire cables are used for trunk lines and drop lines. The DeviceNet cables
on the market can be used for such cables. There are two types of the DeviceNet cable: Thick
cable and Thin cable. Environment-resistant cable and flexible cable are available. For
details of cables, see ODVA’s Web site (http://www.odva.org/).
12 Fieldbus I/O Rev.6
2. Installation
Thick Cable Thin Cable
11.2 to 12.1 mm outside diameter
Braid Shield
Signal Wire
(Blue/White)
Power Wire
Shield Wire
(Red/Black)
Shield Wire
6.9 mm outside diameter
Braid Shield
Signal Wire
(Blue/White)
Power Wire
(Red/Black)
Communication Cable Signal
Wire Type Color Details of Signal Wire Identity
Signal wire
Power wire
Blue Signal Low CAN L
White Signal High CAN H
Red Communications Power Positive V+
Black Communications Power Negative V
Shield wire - Shield S
Terminating Resistor
To reduce reflections of communication signal, terminating resistors should be attached on
both ends of the trunk line. For DeviceNet, nodes have no terminating resistor on the ends.
Attach 121 Ω +/-1%, 1/4W terminating resistors between the signal wires (CAN-H and CANL) of the trunk line cable. Some T-branch taps and connectors can accept terminal resistors.
Molded terminating resistors with connectors are also available to attach to environmentresistant T-branch taps and connectors.
Node Connection
Nodes can be connected to a DeviceNet network by the following topologies: tree, multi-drop,
T-branch, daisy chain. For tree topology, there is no limitation of daisy chain layer but drop
line length is limited. For details of drop line length, refer to the following section “Drop
Line Length”.
Terminating
Resistor
Tree
Trunk Line
Branch Tap
Multi-dropT-branch
Terminating
Resistor
Daisy Chain
Communications Power Supply
DeviceNet supplies 24V DC communications power to each node via 5-wire cables. You can
install the communications power supply at any location on the DeviceNet network. We
recommend providing a dedicated communications power supply on the network separately
even though it is possible to share power among the communications power supply, node
internal circuit power supply, and I/O power supply.
Shield Ground of Signal Wire
Ground the DeviceNet network at one point with 100 Ω or less.
As a noise countermeasure, you can leave the network ungrounded. For details, refer to the 4. Troubleshooting.
Fieldbus I/O Rev.6 13
2. Installation
Maximum Network Length (Maximum Trunk Length)
The maximum network length is the longest distance either between terminating resistors or
between the two most distant nodes on the network.
The longest distance is the maximum network length.
Trunk Line
Terminating
Resistor
Terminating
Resistor
The maximum network length is restricted by the type of cable and the baud rate.
Baud Rate
500 kbps
250 kbps
125 kbps
Thick Cable Thin Cable
Maximum Network Length
100 m
250 m
500 m
100 m
100 m
100 m
Both Thick Cable and Thin Cable can be combined and used for trunk lines. In this
case, the maximum network length is calculated using the following formulas.
The drop line length is the distance from a branch on the trunk line to the end of that branch.
2 m
3 m
Trunk Line
4 m
Node 3
1 m
1 m
Node 1 Node 2
In figure above, each drop line length is as follows:
Drop Line to Node 1: 4 m
Drop Line to Node 2: 6 m
Drop Line to Node 3: 6 m
One drop line length should be 6m or less.
14 Fieldbus I/O Rev.6
2. Installation
Total Drop Line Length
The total drop line length is the total distance of all drop lines on one network.
2 m
Trunk Line
Terminating
Resistor
4 m
Terminating
Resistor
1 m
1 m
3 m
2 m
4 m
In the figure above, the total drop line length is 17 m.
The maximum total drop line length is restricted by baud rate as shown in the table below.
The cable thickness is not related to the restriction.
Baud Rate Max. Total Drop Line Length
500 kbps
250 kbps
125 kbps
39 m
78 m
156 m
Cable Current Capacity
The current-carrying capacity of the DeviceNet network cable is restricted as shown below:
Thick CableThin Cable
Trunk Line
Drop Line (Unit: A)
Current Capacity 8A 3A 4.57 / Drop Line Length (m) ≤ 3A
The following figures illustrate power supply configuration examples.
When an external power supply is installed on the network as shown in the figure below, the
current capacity is 11A and it exceeds the permissible current of the cable.
Terminating
Resistor
External Power
Supply 24 V DC
Power Supply Tap
1A
1A
1A
2A
Trunk Line
2A2A
Terminating
Resistor
2A
If the location of the external power supply is changed on the network as shown in the figure
below, the power supply can be used on the network because the current capacity on the left
side of the power supply tap is 5 A and that on the right side is 6 A.
Terminating
Resistor
Power Supply Tap
1A
1A
1A
2A
External
Power Supply
24 V DC
Trunk Line
2A2A
Terminating
Resistor
2A
Fieldbus I/O Rev.6 15
2. Installation
Ω
A
If the current capacity consumed on the network exceeds the restriction of cable current
capacity, it is possible to install more than one power supply on the network. If you attempt
to install two or more power supplies on the network, take necessary measures (pulling out a
fuse on the power supply tap, etc.) to avoid conflicts between power outputs from multiple
power supplies.
CAUTION
Terminating
Resistor
1A 1A
Power Supply Tap
2A
1A
External
Power Supply
24 V DC
Trunk Line
2A2A
2A
Power Supply Tap
Terminating
Resistor
2A
1A
1A1A
The following figure illustrates a sample wiring. An OMRON power supply tap is shown in
the figure.
Trunk Line
Pull out
the fuse.
Ground the
network at
only one point.
Ground 100
Ground 100 Ω or less.
If you cannot ground the network with 100 Ω or less,
do not connect V- and FG wires.
Carefully connect the wires. Incorrect wiring may cause node malfunction and
severe damage to the entire DeviceNet network.
V+ V+
L CAN L
S Shield
H CAN H
V- V-
or less.
Procedure for Modifying and Installing Communication Cables
Follow the steps described below to modify communication cables and connect them to
connectors.
Be careful not to injure your hands or fingers on any sharp blades or tools used
to modify the cable.
CAUTION
Use appropriate blades and/or other tools to modify the cable. Using
inappropriate blades and/or other tools may result in bodily injury and/or
equipment damage.
(1) Strip approx. 30 mm of the cable covering with extra
pprox. 30 mm
care so that you do not scratch on the braided shield
underneath. Do not strip the cable covering more than
necessary. Excess stripping may cause short-circuit
and/or make the cable more sensitive to noise.
16 Fieldbus I/O Rev.6
2. Installation
(2) Carefully expand the meshes of the braided shield.
Shield Wire
Under the braided shield, there is one exposed bare
twisted shield wire other than the signal wires and
power wires that are wrapped with aluminum tape. The
shield wire is slightly harder than the mesh.
(3) Cut off the expanded braided shield and remove the
aluminum tape around the signal wires and power
wires. Then, strip the insulation from the signal wires
and power wires for a length sufficient to connect them
to crimp terminals.
Twist each stripped signal wire and power wire.
(4) Set the crimp terminal on the stripped part of the wire
and crimp it with a crimp tool. The following crimping
Peel the coverings in enough
length to connect the wires to
crimping terminals.
Crimping
Te rm i na l
terminals are recommended products.
NICHIFU TC series
Model Number Specifications Special Tool
TMEV TC-0.5 For Thin Cable
TMEV TC-2-11 For Thick Cable (power wire)
MH-32
TMEV TC-1.25-11 For Thick Cable (signal wire)
Phoenix Contact AI series
Model Number Specifications Special Tool
AI 0.5-8WH For Thin Cable (power cable)
AI 0.25-8YE For Thin Cable (signal wire)
AI 2.5-8BU For Thick Cable (signal wire)
CRIMPFOX UD6
AI 1-8RD For Thick Cable (signal wire)
NOTE
)
(5) Wrap or cover the cable with vinyl tape or heat-shrink
Heat-shrinkable Tube, etc.
tubing.
Loosen the screws securing the cables on the connector. If the screws are not loosened, the
wires go into different openings on the rear of connector instead of the correct openings
and the wires cannot be secured.
(6) Ensure the correct connector orientation and insert the
signal wires and shield wire to their respective holes
on the connector.
As shown in the figure, insert the wires (black, blue,
shield, white, and red) into the holes in the order
named.
The following table shows the specified colors of the
cables.
Color Details of Signal Wire Identity
a Black Communications Power
V-
Supply (negative)
Insert wires in
this direction.
a
b
c
Insert the
connector
in this
direction.
e
d
b Blue Signal (Low) CAN L
c - Shield S
d White Signal (High) CAN H
e Red Communications Power
Supply (positive)
V+
Fieldbus I/O Rev.6 17
2. Installation
(7) Tighten each screw securing the wires on the connector.
Tighten the screw securing the wire at a correct tightening torque (0.25 to 0.3 N·m). To
prevent thick cable from coming out due to cable tension, install enough thick cable
length to allow for stretch.
Use a small flat blade screwdriver that has the correct
width and thickness. If you use a typical screwdriver
Thickness
Width
whose point is narrow, you cannot deeply insert it into
the hole on the connector.
Specific screwdriver for DeviceNet connector screw:
OMRON : XW4Z-00C
Phoenix Contact : SZF-1 0.6×3.5
0.6 mm 3.5 mm
18 Fieldbus I/O Rev.6
Loading...
+ 138 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.