A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other
connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Communication symbols
SymbolMeaning
Wireless Local Area Network (WLAN)
Communication via a wireless, local network.
LED
Light emitting diode is off.
LED
Light emitting diode is on.
LED
Light emitting diode is flashing.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Visual inspection.
4Endress+Hauser
Page 5
Proline Promass X 500
1.
-
.
213
Symbols in graphics
SymbolMeaning
1, 2, 3, ...Item numbers
, 2., 3., …Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
Hazardous area
Safe area (non-hazardous area)
Flow direction
Function and system design
Measuring principle
The measuring principle is based on the controlled generation of Coriolis forces. These forces are
always present in a system when both translational and rotational movements are superimposed.
Fc = 2 · ∆m (ν · ω)
Fc = Coriolis force
∆m = moving mass
ω = rotational velocity
ν = radial velocity in rotating or oscillating system
The amplitude of the Coriolis force depends on the moving mass ∆m, its velocity ν in the system and
thus on the mass flow. Instead of a constant rotational velocity ω, the sensor uses oscillation.
In the sensor, two sets of two parallel measuring tubes containing flowing fluid oscillate in
antiphase, acting like a tuning fork. The Coriolis forces produced at the measuring tubes cause a
phase shift in the tube oscillations (see illustration):
• At zero flow (when the fluid is at a standstill) the two tubes oscillate in phase (1).
• Mass flow causes deceleration of the oscillation at the inlet of the tubes (2) and acceleration at the
outlet (3).
A0028850
The phase difference (A-B) increases with increasing mass flow. Electrodynamic sensors register the
tube oscillations at the inlet and outlet. System balance is ensured by the antiphase oscillation of the
two measuring tubes. The measuring principle operates independently of temperature, pressure,
viscosity, conductivity and flow profile.
Endress+Hauser5
Page 6
Proline Promass X 500
Density measurement
The measuring tube is continuously excited at its resonance frequency. A change in the mass and
thus the density of the oscillating system (comprising measuring tube and fluid) results in a
corresponding, automatic adjustment in the oscillation frequency. Resonance frequency is thus a
function of medium density. The microprocessor utilizes this relationship to obtain a density signal.
Volume measurement
Together with the measured mass flow, this is used to calculate the volume flow.
Temperature measurement
The temperature of the measuring tube is determined in order to calculate the compensation factor
due to temperature effects. This signal corresponds to the process temperature and is also available
as an output signal.
6Endress+Hauser
Page 7
Proline Promass X 500
2
3
1
A
B
1
2
3
Measuring system
The measuring system consists of a transmitter and a sensor. The transmitter and sensor are
mounted in physically separate locations. They are interconnected by connecting cables.
Transmitter
Two versions of the transmitter are available.
Proline 500 – digitalProline 500
For use in applications not required to meet special requirements due to
ambient or operating conditions.
ANon-hazardous area or Zone 2; Class I, Division 2
BNon-hazardous area or Zone 2; Class I, Division 2 or Zone 1; Class I,
Division 1
1Transmitter
2Connecting cable: cable, separate, standard
3Sensor connection housing with integrated ISEM
• Flexible and cost-effective separate installation.
• A standard cable can be used as the connecting cable.
• Electronics in the transmitter housing, ISEM (intelligent sensor
electronics module) in the sensor connection housing
• Signal transmission: digital
Order code for "Integrated ISEM electronics", option A "Sensor"
Connecting cable (can be ordered in various lengths)→ 102
• Length:
• Zone 2; Class I, Division 2: max. 300 m (1000 ft)
• Zone 1; Class I, Division 1: max. 150 m (500 ft)
• Standard cable with common shield (pair-stranded)
Hazardous area
Use in: Zone 2; Class I, Division 2
Mixed installation is possible:
• Sensor: Zone 1; Class I, Division 1
• Transmitter: Zone 2; Class I, Division 2
Device versions and materials
• Transmitter housing
• Aluminum, coated: aluminum, AlSi10Mg, coated
• Material: polycarbonate
• Material of window in transmitter housing
• Aluminum, coated: glass
• Polycarbonate: plastic
Configuration
• External operation via 4-line, backlit, graphic local display with touch control and guided menus ("Make-it-run" wizards) for application-specific
commissioning.
• Via service interface or WLAN interface:
• Operating tools (e.g. FieldCare, DeviceCare)
• Web server (access via Web browser, e.g. Microsoft Internet Explorer, Microsoft Edge)
For use in applications required to meet special requirements due to
ambient or operating conditions.
Non-hazardous area or Zone 2; Class I, Division 2 or Zone 1; Class I,
Division 1
1Transmitter with integrated ISEM
2Connecting cable: cable, separate
3Sensor connection housing
Application examples for sensors without electronics:
• Strong vibrations at the sensor.
• Sensor in underground installations.
• Electronics and ISEM (intelligent sensor electronics module) in the
transmitter housing
• Signal transmission: analog
Order code for "Integrated ISEM electronics", option B "Transmitter"
• Length: max. 20 m (65 ft)
• Cable with a common shield and individual shielded cores (3 pairs)
Use in: Zone 1; Class I, Division 1 or Zone 2; Class I, Division 2
• Transmitter housing
Cast, stainless: cast, stainless steel, 1.4409 (CF3M) similar to 316L
• Window material: glass
Endress+Hauser7
Page 8
Equipment architecture
2
1
6
5
7
4
3
3
Proline Promass X 500
Sensor connection housing
Order code for "Sensor connection housing", option L, "Cast, stainless":
1.4409 (CF3M) similar to 316L
Sensor
Promass X• Compact, bent four-tube system for measuring maximum flow rates,
suitable for offshore applications and highly accurate
• Simultaneous measurement of flow, volume flow, density and
temperature (multivariable)
• Nominal diameter range: DN 300 to 400 (12 to 16")
• Process connections: stainless steel, 1.4404 (F316/F316L)
1Possibilities for integrating measuring devices into a system
1Control system (e.g. PLC)
2Connecting cable (0/4 to 20 mA HART etc.)
3Fieldbus
4Coupler
5Non-hazardous area
6Hazardous area: Zone 2; Class I, Division 2
7Hazardous area: Zone 1; Class I, Division 1
SafetyIT security
Our warranty is valid only if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any inadvertent
changes to the settings.
IT security measures, which provide additional protection for the device and associated data transfer,
must be implemented by the operators themselves in line with their security standards.
Device-specific IT security
The device offers a range of specific functions to support protective measures on the operator's side.
These functions can be configured by the user and guarantee greater in-operation safety if used
correctly. An overview of the most important functions is provided in the following section.
8Endress+Hauser
A0027512
Page 9
Proline Promass X 500
Function/interfaceFactory settingRecommendation
Write protection via hardware write
protection switch → 9
Access code
(also applies for Web server login or
FieldCare connection) → 9
WLAN
(order option in display module)
WLAN security modeEnabled (WPA2-
WLAN passphrase
(password) → 9
WLAN modeAccess PointOn an individual basis following risk
Web server→ 10Enabled.On an individual basis following risk
CDI-RJ45 service interface → 10–On an individual basis following risk
Not enabled.On an individual basis following risk
assessment.
Not enabled
(0000).
Enabled.On an individual basis following risk
PSK)
Serial numberAssign an individual WLAN passphrase during
Assign a customized access code during
commissioning.
assessment.
Do not change.
commissioning.
assessment.
assessment.
assessment.
Protecting access via hardware write protection
Write access to the device parameters via the local display, Web browser or operating tool (e.g.
FieldCare, DeviceCare) can be disabled via a write protection switch (DIP switch on the
motherboard). When hardware write protection is enabled, only read access to the parameters is
possible.
Hardware write protection is disabled when the device is delivered.
Protecting access via a password
Different passwords are available to protect write access to the device parameters or access to the
device via the WLAN interface.
• User-specific access code
Protect write access to the device parameters via the local display, Web browser or operating tool
(e.g. FieldCare, DeviceCare). Access authorization is clearly regulated through the use of a userspecific access code.
• WLAN passphrase
The network key protects a connection between an operating unit (e.g. notebook or tablet) and the
device via the WLAN interface which can be ordered as an option.
• Infrastructure mode
When the device is operated in infrastructure mode, the WLAN passphrase corresponds to the
WLAN passphrase configured on the operator side.
User-specific access code
Write access to the device parameters via the local display, Web browser or operating tool (e.g.
FieldCare, DeviceCare) can be protected by the modifiable, user-specific access code.
WLAN passphrase: Operation as WLAN access point
A connection between an operating unit (e.g. notebook or tablet) and the device via the WLAN
interface, which can be ordered as an optional extra, is protected by the network key. The WLAN
authentication of the network key complies with the IEEE 802.11 standard.
When the device is delivered, the network key is pre-defined depending on the device. It can be
changed via the WLAN settings submenu in the WLAN passphrase parameter.
Infrastructure mode
A connection between the device and WLAN access point is protected by means of an SSID and
passphrase on the system side. Please contact the relevant system administrator for access.
Endress+Hauser9
Page 10
Proline Promass X 500
General notes on the use of passwords
• The access code and network key supplied with the device should be changed during
commissioning.
• Follow the general rules for generating a secure password when defining and managing the access
code or network key.
• The user is responsible for the management and careful handling of the access code and network
key.
Access via Web server
The device can be operated and configured via a Web browser with the integrated Web server. The
connection is via the service interface (CDI-RJ45) or the WLAN interface. For device versions with
the EtherNet/IP and PROFINET communication protocols, the connection can also be established via
the terminal connection for signal transmission with EtherNet/IP or PROFINET (RJ45 connector).
The Web server is enabled when the device is delivered. The Web server can be disabled if necessary
(e.g. after commissioning) via the Web server functionality parameter.
The device and status information can be hidden on the login page. This prevents unauthorized
access to the information.
For detailed information on device parameters, see:
The "Description of Device Parameters" document → 105
Access via OPC-UA
The "OPC UA Server" application package is available in the device version with the HART
communication protocol → 102.
The device can communicate with OPC UA clients using the "OPC UA Server" application package.
The OPC UA server integrated in the device can be accessed via the WLAN access point using the
WLAN interface - which can be ordered as an optional extra - or the service interface (CDI- RJ45) via
Ethernet network. Access rights and authorization as per separate configuration.
The following Security Modes are supported as per the OPC UA Specification (IEC 62541):
• None
• Basic128Rsa15 – signed
• Basic128Rsa15 – signed and encrypted
Access via service interface (CDI-RJ45)
The device can be connected to a network via the service interface (CDI-RJ45). Device-specific
functions guarantee the secure operation of the device in a network.
The use of relevant industrial standards and guidelines that have been defined by national and
international safety committees, such as IEC/ISA62443 or the IEEE, is recommended. This includes
organizational security measures such as the assignment of access authorization as well as technical
measures such as network segmentation.
Transmitters with an Ex de approval may not be connected via the service interface (CDI-RJ45)!
Order code for "Approval transmitter + sensor", options (Ex de): BA, BB, C1, C2, GA, GB, MA,
MB, NA, NB
The device can be integrated in a ring topology. The device is integrated via the terminal
connection for signal transmission (output 1) and the connection to the service interface (CDIRJ45) .
10Endress+Hauser
Page 11
Proline Promass X 500
Input
Measured variableDirect measured variables
• Mass flow
• Density
• Temperature
Calculated measured variables
• Volume flow
• Corrected volume flow
• Reference density
Measuring rangeMeasuring range for liquids
DNMeasuring range full scale values
[mm][in][t/h][tn. sh./h]
300120 to 41000 to 4520
350140 to 41000 to 4520
400160 to 41000 to 4520
min(F)
to
Measuring range for gases
The full scale value depends on the density and the sound velocity of the gas used and can be
calculated with the formula below:
= minimum (
max(G)
max(G)
max(F)
<
max(G)
ρ
G
xConstant dependent on nominal diameter
c
G
d
i
max(F)
· ρG : x ; ρG · cG · π/2 · (di)2 · 3600)
max(F)
Maximum full scale value for gas [kg/h]
Maximum full scale value for liquid [kg/h]
can never be greater than
max(G)
Gas density in [kg/m³] at operating conditions
Sound velocity (gas) [m/s]
Measuring tube internal diameter [m]
max(F)
max(F)
DNx
[mm][in][kg/m3]
30012200
35014200
40016200
To calculate the measuring range, use the Applicator sizing tool → 104
Calculation example for gas
• Sensor: Promass X, DN 350
• Gas: Air with a density of 60.3 kg/m³ (at 20 °C and 50 bar)
• Measuring range (liquid): 70000 kg/h
• x = 200 kg/m³ (for Promass X, DN 350)
Maximum possible full scale value:
Flow rates above the preset full scale value do not override the electronics unit, with the result that
the totalizer values are registered correctly.
Input signalInput and output versions
→ 14
External measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow for
gases, the automation system can continuously write different measured values to the measuring
device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure
measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow for gases
Various pressure transmitters and temperature measuring devices can be ordered from Endress
+Hauser: see "Accessories" section → 104
It is recommended to read in external measured values to calculate the corrected volume flow.
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Current input
The measured values are written from the automation system to the measuring device via the
current input → 12.
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS DP
• PROFIBUS PA
• Modbus RS485
• EtherNet/IP
• PROFINET
Current input 0/4 to 20 mA
Current input0/4 to 20 mA (active/passive)
Current span• 4 to 20 mA (active)
• 0/4 to 20 mA (passive)
Resolution1 µA
Voltage dropTypically: 0.6 to 2 V for 3.6 to 22 mA (passive)
Maximum input voltage≤ 30 V (passive)
Open-circuit voltage≤ 28.8 V (active)
Possible input variables• Pressure
• Temperature
• Density
•
12Endress+Hauser
Page 13
Proline Promass X 500
Status input
Maximum input values• DC –3 to 30 V
• If status input is active (ON): Ri >3 kΩ
Response timeConfigurable: 5 to 200 ms
Input signal level• Low signal: DC –3 to +5 V
• High signal: DC 12 to 30 V
Assignable functions• Off
• Reset the individual totalizers separately
• Reset all totalizers
• Flow override
Endress+Hauser13
Page 14
Output
Proline Promass X 500
Output and input variants
Depending on the option selected for output/input 1, different options are available for the other
outputs and inputs. Only one option can be selected for each output/input 1 to 4. The following
tables must be read vertically (↓).
Example: If the option BA "4–20 mA HART" was selected for output/input 1, one of the options A, B,
D, E, F, H, I or J is available for output 2, and one of the options A, B, D, E, F, H, I or J is available for
output 3 and 4.
Output/input 1 and options for output/input 2
Options for output/input 3 and 4
Order code for "Output; input 1" (020) →Possible options
Current output 4 to 20 mA HARTBA
Current output 4 to 20 mA HART Ex i passive↓ CA
Current output 4 to 20 mA HART Ex i active↓ CC
FOUNDATION Fieldbus↓ SA
FOUNDATION Fieldbus Ex i↓ TA
PROFIBUS DP↓ LA
PROFIBUS PA↓ GA
PROFIBUS PA Ex i↓ HA
Modbus RS485↓ MA
EtherNet/IP 2-port switch integrated↓ NA
PROFINET 2-port switch integrated↓ RA
Order code for "Output; input 2" (021) →↓↓↓↓↓↓↓↓↓↓↓
Not assignedAAAAAAAAAAA
Current output 4 to 20 mABBBBBBB
Current output 4 to 20 mA Ex i passiveCCCC
User-configurable input/output
Pulse/frequency/switch outputEEEEEEE
Double pulse output
Pulse/frequency/switch output Ex i passiveGGGG
Relay outputHHHHHHH
Current input 0/4 to 20 mAIIIIIII
Status inputJJJJJJJ
2)
1)
DDDDDDD
FF
1)A specific input or output can be assigned to a user-configurable input/output → 21.
2)If double pulse output (F) is selected for output/input 2 (021), only the double pulse output (F) option is available for selection for output/input 3
(022).
14Endress+Hauser
Page 15
Proline Promass X 500
Output/input 1 and options for output/input 3 and 4
Options for output/input 2 → 14
Order code for "Output; input 1" (020) →Possible options
Current output 4 to 20 mA HARTBA
Current output 4 to 20 mA HART Ex i passive↓ CA
Current output 4 to 20 mA HART Ex i active↓ CC
FOUNDATION Fieldbus↓ SA
FOUNDATION Fieldbus Ex i↓ TA
PROFIBUS DP↓ LA
PROFIBUS PA↓ GA
PROFIBUS PA Ex i↓ HA
Modbus RS485↓ MA
EtherNet/IP 2-port switch integrated↓ NA
PROFINET 2-port switch integrated↓ RA
Order code for "Output; input 3" (022), "Output; input 4" (023) →↓↓↓↓↓↓↓↓↓↓↓
Not assignedAAAAAAAAAAA
Current output 4 to 20 mABBBBB
Current output 4 to 20 mA Ex i passive
User-configurable input/outputDDDDD
Pulse/frequency/switch outputEEEEE
Double pulse output (slave)
2)
Pulse/frequency/switch output Ex i passive
Relay outputHHHHH
Current input 0/4 to 20 mAIIIII
Status inputJJJJJ
1)
CC
FF
3)
GG
1)For output/input 4 the current output 4 to 20 mA Ex i passive (C) is not available.
2)The double pulse output (F) option is not available for input/output 4.
3)For output/input 4 the pulse/frequency/switch output Ex i passive (G) is not available.
Endress+Hauser15
Page 16
Output signalCurrent output 4 to 20 mA HART
Order code"Output; Input 1" (20):
Option BA: current output 4 to 20 mA HART
Signal modeCan be set to:
• Active
• Passive
Current rangeCan be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA (only with signal mode active)
• Fixed current value
Open-circuit voltageDC 28.8 V (active)
Maximum input voltageDC 30 V (passive)
Load250 to 700 Ω
Resolution0.38 µA
DampingConfigurable: 0 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
Proline Promass X 500
The range of options increases if the measuring device has one or more
application packages.
Current output 4 to 20 mA HART Ex i
Order code"Output; Input 1" (20) can be set to:
• Option CA: current output 4 to 20 mA HART Ex i passive
• Option CC: current output 4 to 20 mA HART Ex i active
Signal modeDepending on the ordered variant.
Current rangeCan be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA (only with signal mode active)
• Fixed current value
Open-circuit voltageDC 21.8 V (active)
Maximum input voltageDC 30 V (passive)
Load• 250 to 400 Ω (active)
• 250 to 700 Ω (passive)
Resolution0.38 µA
16Endress+Hauser
Page 17
Proline Promass X 500
DampingConfigurable: 0 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
FOUNDATION Fieldbus
FOUNDATION FieldbusH1, IEC 61158-2, galvanically isolated
Data transfer31.25 kbit/s
Current consumption10 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
PROFIBUS DP
Signal encodingNRZ code
Data transfer9.6 kBaud…12 MBaud
PROFIBUS PA
PROFIBUS PAIn accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically
isolated
Data transmission31.25 kbit/s
Current consumption10 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
Modbus RS485
Physical interfaceRS485 in accordance with EIA/TIA-485 standard
Terminating resistorIntegrated, can be activated via DIP switches
EtherNet/IP
StandardsIn accordance with IEEE 802.3
PROFINET
StandardsIn accordance with IEEE 802.3
Endress+Hauser17
Page 18
Proline Promass X 500
Current output 4 to 20 mA
Order code"Output; Input 2" (21), "Output; Input 3" (022) or "Output; Input 4" (023):
Option B: current output 4 to 20 mA
Signal modeCan be set to:
• Active
• Passive
Current rangeCan be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA (only with signal mode active)
• Fixed current value
Maximum output values22.5 mA
Open-circuit voltageDC 28.8 V (active)
Maximum input voltageDC 30 V (passive)
Load0 to 700 Ω
Resolution0.38 µA
DampingConfigurable: 0 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Current output 4 to 20 mA Ex i passive
Order code"Output; Input 2" (21), "Output; Input 3" (022):
Option C: current output 4 to 20 mA Ex i passive
Signal modePassive
Current rangeCan be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• Fixed current value
Maximum output values22.5 mA
Maximum input voltageDC 30 V
Load0 to 700 Ω
Resolution0.38 µA
18Endress+Hauser
Page 19
Proline Promass X 500
DampingConfigurable: 0 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionOpen collector
Can be set to:
• Active
• Passive
• Passive NAMUR
Ex-i, passive
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Voltage dropFor 22.5 mA: ≤ DC 2 V
Pulse output
Maximum input valuesDC 30 V, 250 mA (passive)
Maximum output current22.5 mA (active)
Open-circuit voltageDC 28.8 V (active)
Pulse widthConfigurable: 0.05 to 2000 ms
Maximum pulse rate10000 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Maximum input valuesDC 30 V, 250 mA (passive)
Maximum output current22.5 mA (active)
Open-circuit voltageDC 28.8 V (active)
Output frequencyAdjustable: end value frequency 2 to 10000 Hz (f
DampingConfigurable: 0 to 999 s
Pulse/pause ratio1:1
• Mass flow
• Volume flow
• Corrected volume flow
= 12500 Hz)
max
Endress+Hauser19
Page 20
Proline Promass X 500
Assignable measured
variables
Switch output
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Switching behaviorBinary, conductive or non-conductive
Switching delayConfigurable: 0 to 100 s
Number of switching
cycles
Assignable functions• Off
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Unlimited
• On
• Diagnostic behavior
• Limit value
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1-3
• Flow direction monitoring
• Status
• Partially filled pipe detection
• Low flow cut off
The range of options increases if the measuring device has one or more
application packages.
Double pulse output
FunctionDouble pulse
VersionOpen collector
Can be set to:
• Active
• Passive
• Passive NAMUR
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Voltage dropFor 22.5 mA: ≤ DC 2 V
Output frequencyConfigurable: 0 to 1000 Hz
DampingConfigurable: 0 to 999 s
20Endress+Hauser
Page 21
Proline Promass X 500
Pulse/pause ratio1:1
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
The range of options increases if the measuring device has one or more
application packages.
Relay output
FunctionSwitch output
VersionRelay output, galvanically isolated
Switching behaviorCan be set to:
• NO (normally open), factory setting
• NC (normally closed)
Maximum switching
capacity (passive)
Assignable functions• Off
• DC 30 V, 0.1 A
• AC 30 V, 0.5 A
• On
• Diagnostic behavior
• Limit value
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1-3
• Flow direction monitoring
• Status
• Partially filled pipe detection
• Low flow cut off
The range of options increases if the measuring device has one or more
application packages.
User-configurable input/output
One specific input or output is assigned to a user-configurable input/output (configurable I/O)
during device commissioning.
The following inputs and outputs are available for assignment:
• Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Pulse/frequency/switch output
• Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Status input
The technical values correspond to those of the inputs and outputs described in this section.
Signal on alarm
Depending on the interface, failure information is displayed as follows:
HART current output
Device diagnosticsDevice condition can be read out via HART Command 48
Endress+Hauser21
Page 22
PROFIBUS PA
Proline Promass X 500
Status and alarm
messages
Failure current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
PROFIBUS DP
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
EtherNet/IP
Device diagnosticsDevice condition can be read out in Input Assembly
PROFINET
Device diagnosticsAccording to "Application Layer protocol for decentralized periphery", Version 2.3
FOUNDATION Fieldbus
Status and alarm
messages
Failure current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-891
0 mA
Modbus RS485
Failure modeChoose from:
• NaN value instead of current value
• Last valid value
Current output 0/4 to 20 mA
4 to 20 mA
Failure modeChoose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
0 to 20 mA
Failure modeChoose from:
• Maximum alarm: 22 mA
• Freely definable value between: 0 to 20.5 mA
22Endress+Hauser
Page 23
Proline Promass X 500
Pulse/frequency/switch output
Pulse output
Failure modeChoose from:
• Actual value
• No pulses
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value (f
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
Relay output
Failure modeChoose from:
• Current status
• Open
• Closed
2 to 12500 Hz)
max
Local display
Plain text displayWith information on cause and remedial measures
BacklightRed backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
• HART protocol
• FOUNDATION Fieldbus
• PROFIBUS PA
• PROFIBUS DP
• Modbus RS485
• EtherNet/IP
• PROFINET
• Via service interface
• CDI-RJ45 service interface
• WLAN interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 85
Web browser
Plain text displayWith information on cause and remedial measures
Endress+Hauser23
Page 24
Light emitting diodes (LED)
Status informationStatus indicated by various light emitting diodes
Ex connection dataSafety-related values
Proline Promass X 500
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• EtherNet/IP network available
• EtherNet/IP connection established
• PROFINET network available
• PROFINET connection established
• PROFINET blinking feature
Order code for
Output typeSafety-related values
"Output; input 1"
Option BACurrent output
4 to 20 mA HART
UN = 30 V
UM = 250 V
Option GAPROFIBUS PAUN = 30 V
UM = 250 V
Option LAPROFIBUS DPUN = 30 V
UM = 250 V
Option MAModbus RS485UN = 30 V
UM = 250 V
Option SAFOUNDATION FieldbusUN = 30 V
UM = 250 V
Option NAEtherNet/IPUN = 30 V
UM = 250 V
Option RAPROFINETUN = 30 V
UM = 250 V
Order code for
"Output; input 2";
"Output; input 3"
Output typeSafety-related values
Output; input 2Output; input 3Output; input
"Output; input 4"
24 (+)25 (–)22 (+)23 (–)20 (+)21 (–)
Option BCurrent output
4 to 20 mA
Option DUser-configurable input/
output
Option EPulse/frequency/switch
output
Option FDouble pulse outputUN = 30 V
UN = 30 V
UM = 250 V
UN = 30 V
UM = 250 V
UN = 30 V
UM = 250 V
DC
DC
DC
DC
UM = 250 V
Option HRelay outputUN = 30 V
DC
IN =100 mADC/500 mA
UM = 250 V
Option ICurrent input
4 to 20 mA
Option JStatus inputUN = 30 V
UN = 30 V
UM = 250 V
DC
DC
UM = 250 V
"Output; input 1"
26 (+)27 (–)
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
AC
AC
AC
AC
AC
AC
AC
AC
1)
4
1)The order code "Output; input 4" is only available for the Proline 500 – digital transmitter.
24Endress+Hauser
Page 25
Proline Promass X 500
Intrinsically safe values
Order code for
Output typeIntrinsically safe values
"Output; input 1"
Option CACurrent output
4 to 20 mA HART Ex i
passive
Option CCCurrent output
4 to 20 mA HART Ex i
active
Option HAPROFIBUS PA Ex i
(FISCO Field Device)
Option TAFOUNDATION Fieldbus
Ex i
"Output; input 1"
26 (+)27 (–)
Ui = 30 V
li = 100 mA
Pi = 1.25 W
Li = 0 µH
Ci = 6 nF
Ui = 32 V
li = 570 mA
Pi = 8.5 W
Li = 10 µH
Ci = 5 nF
4)
Ex ic
Ui = 32 V
li = 570 mA
Pi = 8.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
1)Only available for the Zone 1; Class I, Division 1 version
2)Only available for the Zone 2; Class I, Division 2 version and only for the Proline 500 – digital transmitter
3)Only available for the Zone 1; Class I, Division 1 version
4)Only available for the Zone 2; Class I, Division 2 version and only for the Proline 500 – digital transmitter
Order code for
"Output; input 2";
"Output; input 3";
"Output; input 4"
Option CCurrent output
Output typeIntrinsically safe values or NIFW values
Output; input 2Output; input 3 Output; input 4
24 (+)25 (–)22 (+)23 (–)20 (+)21 (–)
Ui = 30 V
4 to 20 mA Ex i
li = 100 mA
Pi = 1.25 W
Li = 0
Ci = 0
Option GPulse/frequency/switch
output Ex i
Ui = 30 V
li = 100 mA
Pi = 1.25 W
Li = 0
Ci = 0
1)The order code "Output; input 4" is only available for the Proline 500 – digital transmitter.
The switch points for low flow cut off are user-selectable.
The outputs are galvanically isolated from one another and from earth (PE).
1)
Endress+Hauser25
Page 26
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x3B
HART protocol revision7
Device description files
(DTM, DD)
HART loadMin. 250 Ω
System integrationInformation on system integration: Operating Instructions → 105.
FOUNDATION Fieldbus
Manufacturer ID0x452B48 (hex)
Ident number0x103B (hex)
Device revision1
DD revisionInformation and files under:
CFF revision
Interoperability Test Kit (ITK) Version 6.2.0
ITK Test Campaign NumberInformation:
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Proline Promass X 500
Information and files under:
www.endress.com
• Measured variables via HART protocol
• Burst Mode functionality
• www.endress.com
• www.fieldbus.org
• www.endress.com
• www.fieldbus.org
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
• Set to OOS
• Set to AUTO
• Read trend data
• Read event logbook
26Endress+Hauser
Page 27
Proline Promass X 500
Max. response delay16
System integrationInformation regarding system integration: Operating Instructions → 105.
• Cyclic data transmission
• Description of the modules
• Execution times
• Methods
PROFIBUS DP
Manufacturer ID0x11
Ident number0x156F
Profile version3.02
Device description files (GSD,
DTM, DD)
Supported functions• Identification & Maintenance
Configuration of the device
address
Compatibility with
earlier model
System integrationInformation regarding system integration: Operating Instructions → 105.
Information and files under:
• www.endress.com
On the product page for the device: Documents/Software → Device drivers
• www.profibus.org
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
• DIP switches on the I/O electronics module
• Via operating tools (e.g. FieldCare)
If the device is replaced, the measuring device Promass 500 supports the
compatibility of the cyclic data with previous models. It is not necessary to
adjust the engineering parameters of the PROFIBUS network with the
Promass 500 GSD file.
Previous model:
Promass 83 PROFIBUS DP
• ID No.: 1529 (hex)
• Extended GSD file: EH3x1529.gsd
• Standard GSD file: EH3_1529.gsd
Description of the function scope of compatibility:
Operating Instructions → 105.
• Cyclic data transmission
• Block model
• Description of the modules
PROFIBUS PA
Manufacturer ID0x11
Ident number0x156D
Profile version3.02
Device description files (GSD,
DTM, DD)
Information and files under:
• www.endress.com
• www.profibus.org
Endress+Hauser27
Page 28
Proline Promass X 500
Supported functions• Identification & Maintenance
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
Configuration of the device
address
Compatibility with
earlier model
System integrationInformation regarding system integration: Operating Instructions → 105.
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e.g. FieldCare)
If the device is replaced, the measuring device Promass 500 supports the
compatibility of the cyclic data with previous models. It is not necessary to
adjust the engineering parameters of the PROFIBUS network with the
Promass 500 GSD file.
Earlier models:
• Promass 80 PROFIBUS PA
• ID No.: 1528 (hex)
• Extended GSD file: EH3x1528.gsd
• Standard GSD file: EH3_1528.gsd
• Promass 83 PROFIBUS PA
• ID No.: 152A (hex)
• Extended GSD file: EH3x152A.gsd
• Standard GSD file: EH3_152A.gsd
Description of the function scope of compatibility:
Response times• Direct data access: typically 25 to 50 ms
• Auto-scan buffer (data range): typically 3 to 5 ms
Device typeSlave
Slave address range1 to 247
Broadcast address range0
Function codes• 03: Read holding register
• 04: Read input register
• 06: Write single registers
• 08: Diagnostics
• 16: Write multiple registers
• 23: Read/write multiple registers
Broadcast messagesSupported by the following function codes:
• 06: Write single registers
• 16: Write multiple registers
• 23: Read/write multiple registers
Supported baud rate• 1200 BAUD
• 2400 BAUD
• 4800 BAUD
• 9600 BAUD
• 19200 BAUD
• 38400 BAUD
• 57600 BAUD
• 115200 BAUD
Data transfer mode• ASCII
• RTU
28Endress+Hauser
Page 29
Proline Promass X 500
Data accessEach device parameter can be accessed via Modbus RS485.
For Modbus register information
Compatibility with
earlier model
System integrationInformation on system integration: Operating Instructions → 105.
If the device is replaced, the measuring device Promass 500 supports the
compatibility of the Modbus registers for the process variables and the
diagnostic information with the previous model Promass 83. It is not
necessary to change the engineering parameters in the automation system.
Description of the function scope of compatibility:
Operating Instructions → 105.
• Modbus RS485 information
• Function codes
• Register information
• Response time
• Modbus data map
EtherNet/IP
Protocol• The CIP Networks Library Volume 1: Common Industrial Protocol
• The CIP Networks Library Volume 2: EtherNet/IP Adaptation of CIP
Communication type• 10Base-T
• 100Base-TX
Device profileGeneric device (product type: 0x2B)
Manufacturer ID0x11
Device type ID0x103B
Baud ratesAutomatic ¹⁰⁄₁₀₀ Mbit with half-duplex and full-duplex detection
PolarityAuto-polarity for automatic correction of crossed TxD and RxD pairs
Supported CIP connectionsMax. 3 connections
Explicit connectionsMax. 6 connections
I/O connectionsMax. 6 connections (scanner)
Configuration options for
measuring device
Configuration of the EtherNet
interface
Configuration of the device
address
Device Level Ring (DLR)Yes
System integrationInformation regarding system integration: Operating Instructions
• DIP switches on the electronics module for IP addressing
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• Electronic Data Sheet (EDS) integrated in the measuring device
• Speed: 10 MBit, 100 MBit, auto (factory setting)
• Duplex: half-duplex, full-duplex, auto (factory setting)
• DIP switches on the electronics module for IP addressing (last octet)
• DHCP
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• EtherNet/IP tools, e.g. RSLinx (Rockwell Automation)
→ 105.
• Cyclic data transmission
• Block model
• Input and output groups
PROFINET
ProtocolApplication layer protocol for decentral device periphery and distributed
automation, Version 2.3
Communication type100 MBit/s
Endress+Hauser29
Page 30
Proline Promass X 500
Conformity classConformance Class B
Netload ClassNetload Class II
Baud ratesAutomatic 100 Mbit/s with full-duplex detection
Cycle timesFrom 8 ms
PolarityAuto-polarity for automatic correction of crossed TxD and RxD pairs
Media Redundancy Protocol
(MRP)
System redundancy supportSystem redundancy S2 (2 AR with 1 NAP)
The terminal assignment depends on the specific device version ordered → 14.
Input/output
2
Input/output
3
Input/output
4
EtherNet/IP
Supply voltageInput/output
1
1 (+)2 (–)EtherNet/IP
(RJ45 connector)
Input/output
2
24 (+)25 (–)22 (+)23 (–)20 (+)21 (–)
The terminal assignment depends on the specific device version
Input/output
3
ordered → 14.
Input/output
4
PROFINET
Supply voltageInput/output
1
1 (+)2 (–)PROFINET
(RJ45 connector)
Input/output
2
24 (+)25 (–)22 (+)23 (–)20 (+)21 (–)
The terminal assignment depends on the specific device version
Input/output
3
ordered → 14.
Input/output
4
Endress+Hauser31
Page 32
Proline Promass X 500
Transmitter and sensor connection housing: connecting cable
The sensor and transmitter, which are mounted in separate locations, are interconnected by a
connecting cable. The cable is connected via the sensor connection housing and the transmitter
housing.
Terminal assignment and connection of the connecting cable:
• Proline 500 – digital→ 35
• Proline 500 → 35
Device plugs available
Device plugs may not be used in hazardous areas!
Device plugs for fieldbus systems:
Order code for "Input; output 1"
• Option SA "FOUNDATION Fieldbus" → 32
• Option GA "PROFIBUS PA" → 32
• Option NA "EtherNet/IP" → 32
• Option RA "PROFINET" → 32
Device plug for connecting to the service interface:
Order code for "Accessory mounted"
option NB, adapter RJ45 M12 (service interface) → 34
Order code for "Input; output 1", option SA "FOUNDATION Fieldbus"
Order code forCable entry/connection → 35
"Electrical connection"23
M, 3, 4, 57/8" connector–
Order code for "Input; output 1", option GA "PROFIBUS PA"
Order code forCable entry/connection → 35
"Electrical connection"23
L, N, P, UConnector M12 × 1–
Order code for "Input; output 1", option NA "EtherNet/IP"
Order code forCable entry/connection → 35
"Electrical connection"23
L, N, P, UConnector M12 × 1–
1) 2)
1) 2)
1) 2)
R
, S
, T
1)Cannot be combined with an external WLAN antenna (order code for "Enclosed accessories", option P8) of
an RJ45 M12 adapter for the service interface (order code for "Accessories mounted", option NB) or of the
remote display and operating module DKX001
2)Suitable for integrating the device in a ring topology.
, V
1) 2)
Connector M12 × 1Connector M12 × 1
Order code for "Input; output 1", option RA "PROFINET"
Order code forCable entry/connection → 35
"Electrical connection"23
L, N, P, UConnector M12 × 1–
1) 2)
1) 2)
1) 2)
R
, S
, T
1)Cannot be combined with an external WLAN antenna (order code for "Enclosed accessories", option P8) of
an RJ45 M12 adapter for the service interface (order code for "Accessories mounted", option NB) or of the
remote display and operating module DKX001.
2)Suitable for integrating the device in a ring topology.
, V
1) 2)
Connector M12 × 1Connector M12 × 1
32Endress+Hauser
Page 33
Proline Promass X 500
1
2
4
3
1
2
4
3
3
2
4
3
2
4
Order code for "Accessory mounted", option NB "Adapter RJ45 M12 (service interface)"
Order codeCable entry/coupling → 35
"Accessory mounted"Cable entry
NBPlug M12 × 1–
Pin assignment, device plugFOUNDATION Fieldbus
PROFIBUS PA
Cable entry
2
PinAssignmentCodingPlug/socket
1+Signal +APlug
2-Signal –
3Grounding
4Not assigned
PinAssignmentCodingPlug/socket
1+PROFIBUS PA +APlug
2Grounding
3-PROFIBUS PA –
4Not assigned
3
PROFINET
PinAssignment
1+TD +
2+RD +
3-TD –
4-RD –
A0032047
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
CodingPlug/socket
DSocket
EtherNet/IP
PinAssignment
1+Tx
2+Rx
3-Tx
4-Rx
A0032047
CodingPlug/socket
DSocket
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
Endress+Hauser33
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
Page 34
Proline Promass X 500
3
2
4
Service interface
Order code for "Accessories mounted", option NB: Adapter RJ45 M12 (service interface)
PinAssignment
1+Tx
2+Rx
3-Tx
4-Rx
A0032047
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
CodingPlug/socket
DSocket
Supply voltage
Order code for
"Power supply"
Option DDC24 V±20%–
Option EAC100 to 240 V –15…+10%50/60 Hz
Option I
Power consumptionTransmitter
Max. 10 W (active power)
switch-on currentMax. 36 A (<5 ms) as per NAMUR Recommendation NE 21
Current consumptionTransmitter
• Max. 400 mA (24 V)
• Max. 200 mA (110 V, 50/60 Hz; 230 V, 50/60 Hz)
Power supply failure
• Totalizers stop at the last value measured.
• Depending on the device version, the configuration is retained in the device memoryor in the
pluggable data memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.
Terminal voltageFrequency range
DC24 V±20%–
AC100 to 240 V –15…+10%50/60 Hz
34Endress+Hauser
Page 35
Proline Promass X 500
+–AB
61 62 63 64
+–AB
61 62 63 64
4
2
1
4
3
5
6
4
56
7
8
111241
42
S1S1S2S2GNDTMTMTTTT
++++
++++
S1S1S2S2GNDTMTMTTTT
2
ER
+
+
ER
ER
ER
5
1
10
9
4567891011124142
3
4
X3
X4
X3X4
+
TM
2
TM
2
+
TM
2
TM
2
6
6
Electrical connectionConnection of connecting cable: Proline 500 – digital
1Cable entry for cable on transmitter housing
2Protective ground (PE)
3Connecting cable ISEM communication
4Grounding via ground connection; on device plug versions grounding is through the plug itself
5Cable entry for cable or connection of device plug on sensor connection housing
6Protective ground (PE)
A0028198
Connection of the connecting cable: Proline 500
The connecting cable is connected via terminals.
A0033694
1Protective ground (PE)
2Cable entry for connecting cable on transmitter connection housing
3Connecting cable
4Cable entry for connecting cable on sensor connection housing
5Protective ground (PE)
6Terminals X3, X4: temperature sensor; only for device version with order code for "Test, certificate", option JQ
Endress+Hauser35
Connecting the transmitter
• Terminal assignment → 31
• Device plug pin assignment → 33
Page 36
Proline Promass X 500
12 3456
2
Connecting the Proline 500 – digital transmitter
A0028200
1Terminal connection for supply voltage
2Terminal connection for signal transmission, input/output
3Terminal connection for signal transmission, input/output
4Terminal connection for connecting cable between sensor and transmitter
5Terminal connection for signal transmission, input/output or terminal for network connection (DHCP client)
via service interface (CDI-RJ45); optional: terminal connection for external WLAN antenna
6Protective ground (PE)
An adapter for RJ45 and the M12 connector is optionally available:
Order code for "Accessories", option NB: "Adapter RJ45 M12 (service interface)"
The adapter connects the service interface (CDI-RJ45) to an M12 connector mounted in the
cable entry. Therefore the connection to the service interface can be established via an M12
connector without opening the device.
Network connection (DHCP client) via service interface (CDI-RJ45) → 90
Connecting the Proline 500 transmitter
A0026781
1Terminal connection for supply voltage
2Terminal connection for signal transmission, input/output
3Terminal connection for signal transmission, input/output or terminal for network connection (DHCP client)
via service interface (CDI-RJ45); optional: terminal connection for external WLAN antenna
4Protective ground (PE)
An adapter for RJ45 and the M12 connector is optionally available:
Order code for "Accessories", option NB: "Adapter RJ45 M12 (service interface)"
The adapter connects the service interface (CDI-RJ45) to an M12 connector mounted in the
cable entry. Therefore the connection to the service interface can be established via an M12
connector without opening the device.
Network connection (DHCP client) via service interface (CDI-RJ45) → 90
36Endress+Hauser
Page 37
Proline Promass X 500
12 3456
2
Connecting in a ring topology
Device versions with EtherNet/IP and PROFINET communication protocols can be integrated into a
ring topology. The device is integrated via the terminal connection for signal transmission (output 1)
and the connection to the service interface (CDI-RJ45).
Transmitters with an Ex de approval may not be connected via the service interface (CDI-RJ45)!
Order code for "Approval transmitter + sensor", options (Ex de):
BA, BB, C1, C2, GA, GB, MA, MB, NA, NB
Integrating the transmitter into a ring topology:
• EtherNet/IP
• PROFINET
Transmitter: Proline 500 – digital
1Terminal connection for supply voltage
2Terminal connection for signal transmission, input/output
2Terminal connection for signal transmission: PROFINET or EtherNet/IP (RJ45 connector)
4Terminal connection for connecting cable between sensor and transmitter
5Terminal connection to service interface (CDI-RJ45)
6Protective ground (PE)
Transmitter: Proline 500
1Terminal connection for supply voltage
2Terminal connection for signal transmission: PROFINET or EtherNet/IP (RJ45 connector)
3Terminal connection to service interface (CDI-RJ45)
4Protective ground (PE)
If the device has additional inputs/outputs, these are routed in parallel via the cable entry for
connection to the service interface (CDI-RJ45).
A0028200
A0026781
Endress+Hauser37
Page 38
Proline Promass X 500
4
4...20 mA
5
2
1
3
6
2
3
4...20 mA
41
5
Connection examples
Current output 4 to 20 mA HART
2Connection example for 4 to 20 mA HART current output (active)
1Automation system with current input (e.g. PLC)
2Cable shield provided at one end. The cable shield must be grounded at both ends to comply with EMC
requirements; observe cable specifications → 46
3Connection for HART operating devices → 85
4Resistor for HART communication (≥ 250 Ω): observe maximum load → 16
5Analog display unit: observe maximum load → 16
6Transmitter
A0029055
3Connection example for 4 to 20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Power supply
3Cable shield provided at one end. The cable shield must be grounded at both ends to comply with EMC
4Connection example for HART input with a common negative (passive)
1Automation system with HART output (e.g. PLC)
2Active barrier for power supply (e.g. RN221N)
3Cable shield provided at one end. The cable shield must be grounded at both ends to comply with EMC
requirements; observe cable specifications
4Analog display unit: observe maximum load → 16
5Pressure measuring device (e.g. Cerabar M, Cerabar S): see requirements
6Transmitter
PROFIBUS PA
5Connection example for PROFIBUS PA
1Control system (e.g. PLC)
2PROFIBUS PA segment coupler
3Cable shield provided at one end. The cable shield must be grounded at both ends to comply with EMC
4T-box
5Measuring device
6Local grounding
7Bus terminator
8Potential matching line
requirements; observe cable specifications
A0028768
Endress+Hauser39
Page 40
Proline Promass X 500
2
1
A
B
3
4
4
A
B
A
B
1
2
4
3
5
5
PROFIBUS DP
6Connection example for PROFIBUS DP, non-hazardous area and Zone 2/Div. 2
1Control system (e.g. PLC)
2Cable shield provided at one end. The cable shield must be grounded at both ends to comply with EMC
1Control system (e.g. PLC)
2Ethernet switch
3Observe cable specifications → 46
4Transmitter
5Connecting cable between the two transmitters
A0028767
A0027544
Endress+Hauser41
Page 42
PROFINET: system redundancy S2
1
2
555
4
3
2134
78
66
6
6
5
6
6
5
9Connection example for system redundancy S2
1Control system 1 (e.g. PLC)
2Synchronization of control systems
3Control system 2 (e.g. PLC)
4Industrial Ethernet Managed Switch
5Transmitter
Proline Promass X 500
A0039553
FOUNDATION Fieldbus
A0028768
10Connection example for FOUNDATION Fieldbus
1Control system (e.g. PLC)
2Power Conditioner (FOUNDATION Fieldbus)
3Cable shield provided at one end. The cable shield must be grounded at both ends to comply with EMC
12Connection example for 4-20 mA current output (active)
1Automation system with current input (e.g. PLC)
2Analog display unit: observe maximum load → 16
3Transmitter
A0028759
13Connection example for 4-20 mA current output (passive)
1Automation system with current input (e.g. PLC)
2Active barrier for power supply (e.g. RN221N)
3Analog display unit: observe maximum load → 16
4Transmitter
Endress+Hauser43
Page 44
Pulse/frequency output
1
2
3
12345
1
2
3
1
2
3
4
14Connection example for pulse/frequency output (passive)
1Automation system with pulse/frequency input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 19
Switch output
Proline Promass X 500
A0028761
15Connection example for switch output (passive)
1Automation system with switch input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 19
Double pulse output
16Connection example for double pulse output (active)
1Automation system with relay input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 21
Current input
A0028760
A0028915
19Connection example for 4 to 20 mA current input
1Power supply
2Terminal box
3External measuring device (to read in pressure or temperature, for instance)
4Transmitter
Endress+Hauser45
Page 46
Status input
1
2
3
20Connection example for status input
1Automation system with status output (e.g. PLC)
2Power supply
3Transmitter
Potential equalizationRequirements
No special measures for potential equalization are required.
Please consider the following to ensure correct measurement:
• Same electrical potential for the fluid and sensor
• Company-internal grounding concepts
Proline Promass X 500
A0028764
terminals
Spring-loaded terminals: Suitable for strands and strands with ferrules.
Conductor cross-section 0.2 to 2.5 mm2 (24 to 12 AWG).
Cable entries
• Cable gland: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
• NPT ½"
• G ½"
• M20
• Device plug for digital communication: M12
Only available for certain device versions → 32.
Cable specificationPermitted temperature range
• The installation guidelines that apply in the country of installation must be observed.
• The cables must be suitable for the minimum and maximum temperatures to be expected.
Power supply cable
Standard installation cable is sufficient.
Protective ground cable
Cable ≥2.08 mm2 (14 AWG)
The grounding impedance must be less than 1 Ω.
Signal cable
Current output 4 to 20 mA HART
A shielded cable is recommended. Observe grounding concept of the plant.
PROFIBUS PA
Twisted, shielded two-wire cable. Cable type A is recommended .
For further information on planning and installing PROFIBUS networks see:
• Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning"
(BA00034S)
• PNO Directive 2.092 "PROFIBUS PA User and Installation Guideline"
• IEC 61158-2 (MBP)
46Endress+Hauser
Page 47
Proline Promass X 500
PROFIBUS DP
The IEC 61158 standard specifies two types of cable (A and B) for the bus line which can be used for
every transmission rate. Cable type A is recommended.
Cable typeA
Characteristic impedance135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance< 30 pF/m
Wire cross-section
Cable typeTwisted pairs
Loop resistance≤110 Ω/km
Signal dampingMax. 9 dB over the entire length of the cable cross-section
ShieldCopper braided shielding or braided shielding with foil shield. When grounding
> 0.34 mm2 (22 AWG)
the cable shield, observe the grounding concept of the plant.
For further information on planning and installing PROFIBUS networks see:
• Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning"
(BA00034S)
• PNO Directive 2.092 "PROFIBUS PA User and Installation Guideline"
• IEC 61158-2 (MBP)
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a cable
used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to the
"Media Planning and Installation Manual. EtherNet/IP" of ODVA Organization
PROFINET
Standard IEC 61156-6 specifies CAT 5 as the minimum category for a cable used for PROFINET. CAT
5e and CAT 6 are recommended.
For more information on planning and installing PROFINET networks, see: "PROFINET Cabling
and Interconnection Technology", Guideline for PROFINET
FOUNDATION Fieldbus
Twisted, shielded two-wire cable.
For further information on planning and installing FOUNDATION Fieldbus networks see:
• Operating Instructions for "FOUNDATION Fieldbus Overview" (BA00013S)
• FOUNDATION Fieldbus Guideline
• IEC 61158-2 (MBP)
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used
for every transmission rate. Cable type A is recommended.
Cable typeA
Characteristic impedance135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance< 30 pF/m
Wire cross-section
Cable typeTwisted pairs
Loop resistance≤110 Ω/km
Signal dampingMax. 9 dB over the entire length of the cable cross-section
ShieldCopper braided shielding or braided shielding with foil shield. When grounding
> 0.34 mm2 (22 AWG)
the cable shield, observe the grounding concept of the plant.
Endress+Hauser47
Page 48
Current output 0/4 to 20 mA
2
3
C
1
3
B
1
3
A
1
3
A
1
3
B
2
3
C
4
5
6
Standard installation cable is sufficient.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Double pulse output
Standard installation cable is sufficient.
Relay output
Standard installation cable is sufficient.
Current input 0/4 to 20 mA
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
Choice of connecting cable between the transmitter and sensor
Depends on the type of transmitter and the installation zones
Proline Promass X 500
1Proline 500 digital transmitter
2Proline 500 transmitter
3Sensor Promass
4Non-hazardous area
5Hazardous area: Zone 2; Class I, Division 2
6Hazardous area: Zone 1; Class I, Division 1
AStandard cable to 500 digital transmitter → 49
BStandard cable to 500 digital transmitter → 49
CSignal cable to 500 transmitter → 51
Transmitter installed in the non-hazardous area or hazardous area: Zone 2; Class I, Division 2 / sensor
installed in the hazardous area: Zone 2; Class I, Division 2
Transmitter installed in the hazardous area: Zone 2; Class I, Division 2 / sensor installed in the hazardous
area: Zone 1; Class I, Division 1
Transmitter and sensor installed in the hazardous area: Zone 2; Class I, Division 2 oder Zone 1;
Class I, Division 1
48Endress+Hauser
A0032476
Page 49
Proline Promass X 500
A: Connecting cable between sensor and transmitter: Proline 500 – digital
Standard cable
A standard cable with the following specifications can be used as the connecting cable.
Design4 cores (2 pairs); uninsulated stranded CU wires; pair-stranded with common
The outputs have the following base accuracy specifications.
Current output
Accuracy±5 µA
Pulse/frequency output
o.r. = of reading
AccuracyMax. ±50 ppm o.r. (over the entire ambient temperature range)
o.r. = of reading; 1 g/cm3 = 1 kg/l; T = medium temperature
Base repeatability
Design fundamentals → 54
52Endress+Hauser
Page 53
Proline Promass X 500
[kg/m ]
3
[°C]
-40 0-8040 80 120 160 200 240 280 320 360 400
[°F]
-50050100150200
0
2
4
6
8
10
2
1
Mass flow and volume flow (liquids)
±0.025 % o.r. (PremiumCal, for mass flow)
±0.05 % o.r.
Mass flow (gases)
±0.25 % o.r.
Density (liquids)
±0.00025 g/cm
3
Temperature
±0.25 °C ± 0.0025 · T °C (±0.45 °F ± 0.0015 · (T–32) °F)
Response time
Influence of ambient
temperature
Influence of medium
temperature
The response time depends on the configuration (damping).
Current output
Temperature coefficientMax. 1 μA/°C
Pulse/frequency output
Temperature coefficientNo additional effect. Included in accuracy.
Mass flow and volume flow
o.f.s. = of full scale value
When there is a difference between the temperature for zero point adjustment and the process
temperature, the additional measured error of the sensor is typically ±0.0002 % o.f.s./°C (±0.0001 %
o. f.s./°F).
The effect is reduced if zero point adjustment is performed at process temperature.
Density
When there is a difference between the density calibration temperature and the process
temperature, the typical measured error of the sensor is
±0.00005 g/cm3 /°C (±0.000025 g/cm3 /°F). Field density calibration is possible.
Wide-range density specification (special density calibration)
If the process temperature is outside the valid range (→ 51) the measured error is
±0.00005 g/cm3 /°C (±0.000025 g/cm3 /°F)
1Field density calibration, for example at +20 °C (+68 °F)
2Special density calibration
Temperature
±0.005 · T °C (± 0.005 · (T – 32) °F)
Endress+Hauser53
A0016613
Page 54
Proline Promass X 500
ZeroPoint
BaseAccu
⋅ 100
³
± BaseAccu
ZeroPoint
BaseAccu
⋅ 100
<
ZeroPoint
MeasValue
⋅ 100
±
½ ⋅ ZeroPoint
BaseRepeat
⋅ 100
³
½ ⋅ ZeroPoint
BaseRepeat
⋅ 100
<
ZeroPoint
MeasValue
⋅ 100
½ ⋅±
E [%]
0102030405060
0
0.5
1.0
1.5
2.0
2.5
708090100
Q [%]
Influence of medium
pressure
Design fundamentals
The table below shows the effect on accuracy of mass flow due to a difference between calibration
pressure and process pressure.
o.r. = of reading
It is possible to compensate for the effect by:
• Reading in the current pressure measured value via the current input.
• Specifying a fixed value for the pressure in the device parameters.
Operating Instructions→ 105.
DN[% o.r./bar][% o.r./psi]
[mm][in]
30012–0.009–0.0006
35014–0.009–0.0006
40016–0.009–0.0006
o.r. = of reading, o.f.s. = of full scale value
BaseAccu = base accuracy in % o.r., BaseRepeat = base repeatability in % o.r.
MeasValue = measured value; ZeroPoint = zero point stability
Calculation of the maximum measured error as a function of the flow rate
Flow rateMaximum measured error in % o.r.
A0021332
A0021333
Calculation of the maximum repeatability as a function of the flow rate
Flow rateMaximum repeatability in % o.r.
A0021335
A0021336
Example for maximum measured error
A0021339
A0021334
A0021340
A0021337
EMaximum measured error in % o.r. (example with PremiumCal)
QFlow rate in % of maximum full scale value
54Endress+Hauser
A0028808
Page 55
Proline Promass X 500
1
2
3
4
5
Mounting location
Installation
No special measures such as supports etc. are necessary. External forces are absorbed by the
construction of the device.
A0028772
To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid
the following mounting locations in the pipe:
• Highest point of a pipeline.
• Directly upstream of a free pipe outlet in a down pipe.
Installation in down pipes
However, the following installation suggestion allows for installation in an open vertical pipeline.
Pipe restrictions or the use of an orifice with a smaller cross-section than the nominal diameter
prevent the sensor running empty while measurement is in progress.
21Installation in a down pipe (e.g. for batching applications)
1Supply tank
2Sensor
3Orifice plate, pipe restriction
4Valve
5Batching tank
A0028773
DNØ orifice plate, pipe restriction
Orientation
The direction of the arrow on the sensor nameplate helps you to install the sensor according to the
flow direction (direction of medium flow through the piping).
[mm][in][mm][in]
300122108.27
350142108.27
400162108.27
Endress+Hauser55
Page 56
Proline Promass X 500
12
OrientationRecommendation
AVertical orientation
A0015591
BHorizontal orientation, transmitter at
top
A0015589
→ 22, 56
CHorizontal orientation, transmitter at
bottom
A0015590
→ 22, 56
DHorizontal orientation, transmitter at
side
A0015592
1)This orientation is recommended to ensure self-draining.
2)Applications with low process temperatures may decrease the ambient temperature. To maintain the
minimum ambient temperature for the transmitter, this orientation is recommended.
3)Applications with high process temperatures may increase the ambient temperature. To maintain the
maximum ambient temperature for the transmitter, this orientation is recommended.
1)
2)
3)
→ 22, 56
Inlet and outlet runs
If a sensor is installed horizontally with a curved measuring tube, match the position of the sensor to
the fluid properties.
A0028774
22Orientation of sensor with curved measuring tube
1Avoid this orientation for fluids with entrained solids: Risk of solids accumulating.
2Avoid this orientation for outgassing fluids: Risk of gas accumulating.
No special precautions need to be taken for fittings which create turbulence, such as valves, elbows
or T-pieces, as long as no cavitation occurs → 65.
56Endress+Hauser
Page 57
Proline Promass X 500
ø 20…70
( 0.79…2.75)ø
~102 (~ 4.0)
4 x
SW 10
3 x
TX 25
149 (5.85)
211 (8.31)
=
5.8 (0.23)
17 (0.67)=
L
5.8 (0.23)
Mounting the transmitter
housing
Proline 500 – digital transmitter
Post mounting
A0029051
23Engineering unit mm (in)
Wall mounting
24Engineering unit mm (in)
LDepends on order code for "Transmitter housing"
Order code for "Transmitter housing"
• Option A, aluminum coated: L =14 mm (0.55 in)
• Option D, polycarbonate: L = 13 mm (0.51 in)
A0029054
Endress+Hauser57
Page 58
Proline Promass X 500
1
4 x
SW 13
!…(! 0.79 to 2.75)20 70
20 (0.79)
100 (3.94)
100 (3.94)
! 8.6 (0.39)
! 18 (0.71)
! 10 (0.39)
Proline 500 transmitter
Post mounting
WARNING
L
Order code for "Transmitter housing", option L "Cast, stainless": cast transmitters are very
heavy.
They are unstable if they are not mounted on a secure, fixed post.
Only mount the transmitter on a secure, fixed post on a stable surface.
‣
Special mounting
instructions
25Engineering unit mm (in)
Wall mounting
26Engineering unit mm (in)
Drainability
The measuring tubes can be completely drained and protected against solids build-up in vertical
orientation.
A0029057
A0029068
Sanitary compatibility
When installing in hygienic applications, please refer to the information in the "Certificates and
approvals/hygienic compatibility" section .
58Endress+Hauser
Page 59
Proline Promass X 500
RUPTURE DISK
i
2
3
1
Rupture disk
Information that is relevant to the process: → 64.
WARNING
L
Danger from medium escaping!
Medium escaping under pressure can cause injury or material damage.
Take precautions to prevent danger to persons and damage if the rupture disk is actuated.
‣
Observe information on the rupture disk sticker.
‣
Make sure that the function and operation of the rupture disk is not impeded through the
‣
installation of the device.
Do not use a heating jacket.
‣
Do not remove or damage the rupture disk.
‣
The position of the rupture disk is indicated on a sticker beside it.
The transportation guard must be removed.
The existing connecting nozzles are not intended for the purpose of rinsing or pressure monitoring,
but instead serve as the mounting location for the rupture disk.
In the event of a failure of the rupture disk, a discharge device can be screwed onto the internal
thread of the rupture disk in order to drain off any escaping medium.
A0029944
1Rupture disk label
2Rupture disk with 1/2" NPT internal thread with 1" width across flat
3Transportation guard
For information on the dimensions: see the "Mechanical construction" section (accessories)
Zero point adjustment
All measuring devices are calibrated in accordance with state-of-the-art technology. Calibration
takes place under reference conditions→ 51. Therefore, a zero point adjustment in the field is
generally not required.
Experience shows that zero point adjustment is advisable only in special cases:
• To achieve maximum measuring accuracy even with low flow rates.
• Under extreme process or operating conditions (e.g. very high process temperatures or very highviscosity fluids).
Endress+Hauser59
Page 60
Protective cover
213 (8.4)
39 (1.5)
243 (9.6)
203 (8.0)
146 (5.75)
48 (1.9)
12 (0.47)
280 (11.0)255 (10.0)
134 (5.3)
30 (1.18)
27Weather protection cover for Proline 500 – digital
Proline Promass X 500
A0029552
Ambient temperature range
28Weather protection cover for Proline 500
Environment
Measuring device• –40 to +60 °C (–40 to +140 °F)
• Order code for "Test, certificate", option JP:
–50 to +60 °C (–58 to +140 °F)
• Order code for "Test, certificate", option JQ:
• Sensor:–60 to +60 °C (–76 to +140 °F)
• Transmitter: –50 to +60 °C (–58 to +140 °F)
Readability of the
local display
‣
Dependency of ambient temperature on medium temperature→ 62
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
You can order a weather protection cover from Endress+Hauser. → 102.
–20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature
range.
A0029553
Storage temperature
–50 to +80 °C (–58 to +176 °F)
60Endress+Hauser
Page 61
Proline Promass X 500
Climate class
Degree of protection
Vibration- and shockresistance
DIN EN 60068-2-38 (test Z/AD)
Transmitter
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure
Sensor
• As standard: IP66/67, type 4X enclosure
• With the order code for "Sensor options", option CM: IP69 can also be ordered
External WLAN antenna
IP67
Vibration broad-band random, according to IEC 60068-2-6
Sensor: order code for "Meas. tube mat., wetted parts surface", option LA, SD, SE, SF, TH, TT, TU
• 2 to 8.4 Hz, 3.5 mm peak
• 8.4 to 2000 Hz, 1 g peak
Sensor: order code for "Meas. tube mat., wetted parts surface", option HA, SA, SB, SC
• 2 to 8.4 Hz, 7.5 mm peak
• 8.4 to 2000 Hz, 2 g peak
Transmitter
• 2 to 8.4 Hz, 7.5 mm peak
• 8.4 to 2000 Hz, 2 g peak
Vibration broad-band random, according to IEC 60068-2-64
Sensor: order code for "Meas. tube mat., wetted parts surface", option LA, SD, SE, SF, TH, TT, TU
• 10 to 200 Hz, 0.003 g2/Hz
• 200 to 2000 Hz, 0.001 g2/Hz
• Total: 1.54 g rms
Sensor: order code for "Meas. tube mat., wetted parts surface", option HA, SA, SB, SC
• 10 to 200 Hz, 0.01 g2/Hz
• 200 to 2000 Hz, 0.003 g2/Hz
• Total: 2.70 g rms
Transmitter
• 10 to 200 Hz, 0.01 g2/Hz
• 200 to 2000 Hz, 0.003 g2/Hz
• Total: 2.70 g rms
Shock half-sine, according to IEC 60068-2-27
• Sensor: order code for "Meas. tube mat., wetted parts surface", option LA, SD, SE, SF, TH, TT, TU
6 ms 30 g
• Sensor: order code for "Meas. tube mat., wetted parts surface", option HA, SA, SB, SC
6 ms 50 g
• Transmitter
6 ms 50 g
Rough handling shocks, according to IEC 60068-2-31
Electromagnetic
compatibility (EMC)
• As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
• Device version with PROFIBUS DP: Complies with emission limits for industry as per EN 50170
Volume 2, IEC 61784
The following applies for PROFIBUS DP: If baud rates > 1.5 MBaud, an EMC cable entry must be
used and the cable shield must continue as far as the terminal wherever possible.
Details are provided in the Declaration of Conformity.
Endress+Hauser61
Page 62
Process
T
a
T
m
B
A
Proline Promass X 500
Medium temperature range
–50 to +180 °C (–58 to +356 °F)
Dependency of ambient temperature on medium temperature
29Exemplary representation, values in the table below.
TaAmbient temperature range
TmMedium temperature
AMaximum permitted medium temperature Tm at T
require a reduced ambient temperature T
a
BMaximum permitted ambient temperature Ta for the maximum specified medium temperature Tm of the
sensor
= 60 °C (140 °F); higher medium temperatures T
a max
A0031121
m
Values for devices used in the hazardous area:
Separate Ex documentation (XA) for the device → 106.
Not insulatedInsulated
ABAB
VersionT
a
T
m
TaT
m
T
a
T
m
T
a
Promass X 500 – digital60 °C (140 °F)180 °C (356 °F)––60 °C (140 °F)150 °C (302 °F)55 °C (131 °F)180 °C (356 °F)
Promass X 500
Density
Pressure-temperature
ratings
0 to 5000 kg/m3 (0 to 312 lb/cf)
The following pressure/temperature diagrams apply to all pressure-bearing parts of the device and
not just the process connection. The diagrams show the maximum permissible medium pressure
depending on the specific medium temperature.
T
m
62Endress+Hauser
Page 63
Proline Promass X 500
300[°F]350250200150100500-50
[°C]200150100500-50
400
0
10
20
30
40
50
70
60
80
90
[bar][psi]
200
400
600
800
0
100
1400
PN40
PN16
PN100
PN63
PN10
300[°F]350250200150100500-50
[°C]200150100500-50
400
0
10
20
30
40
50
70
60
80
90
[bar][psi]
200
400
600
800
0
100
1400
Cl.150
Cl.600
Cl.300
Flange connection according to EN 1092-1 (DIN 2501)
30With flange material 1.4404 (316/316L)
Flange connection according to ASME B16.5
A0029911-EN
A0029912-EN
Sensor housing
Endress+Hauser63
31With flange material 1.4404 (316/316L)
The sensor housing is filled with dry nitrogen gas and protects the electronics and mechanics inside.
If a measuring tube fails (e.g. due to process characteristics like corrosive or abrasive fluids), the
fluid will initially be contained by the sensor housing.
In the event of a tube failure, the pressure level inside the sensor housing will rise according to the
operating process pressure. If the user judges that the sensor housing pressure rating/burst pressure
does not provide an adequate safety margin, the device can be fitted with a rupture disk. This
prevents excessively high pressure from forming inside the sensor housing. Therefore, the use of a
rupture disk is strongly recommended in applications involving high gas pressures, and particularly
in applications in which the process pressure is greater than 2/3 of the sensor housing burst
pressure.
Page 64
Proline Promass X 500
If there is a need to drain the leaking medium into a discharge device, the sensor should be fitted
with a rupture disk. Connect the discharge to the additional threaded connection → 72.
If the sensor is to be purged with gas (gas detection), it should be equipped with purge connections.
Do not open the purge connections unless the containment can be filled immediately with a
dry, inert gas. Use only low pressure to purge. Maximum pressure: 5 bar (72.5 psi).
Sensor housing nominal pressure rating and burst pressure
The following sensor housing nominal pressure ratings/burst pressures are only valid for standard
devices and/or devices equipped with closed purge connections (not opened/as delivered).
If a device fitted with purge connections (order code for "Sensor option", option CH "Purge
connection") is connected to the purge system, the maximum nominal pressure is determined by the
purge system itself or by the device, depending on which component has the lower nominal pressure
classification.
If the device is fitted with a rupture disk (order code for "Sensor option", option CA "Rupture disk"), the
rupture disk trigger pressure is decisive for the maximum nominal pressure .
The sensor housing burst pressure refers to a typical internal pressure which is reached prior to
mechanical failure of the sensor housing and which was determined during type testing. The
corresponding type test declaration can be ordered with the device (order code for "Additional
approval", option LN "Sensor housing burst pressure, type test").
Pressure rating according to ASME BPVC.
Rupture disk
Flow limit
DNSensor housing nominal
pressure
(designed with a safety factor
≥ 4)
[mm][in][bar][psi][bar][psi]
3001268728406
3501468728406
4001668728406
Sensor housing burst pressure
For information on the dimensions: see the "Mechanical construction" section→ 68
To increase the level of safety, a device version with a rupture disk with a trigger pressure of
5.5 to 6.5 bar (80 to 94 psi) can be used (order code for "Sensor option", option CA "rupture disk").
For information on the dimensions: see the "Mechanical construction" section (accessories)
→ 72
Select the nominal diameter by optimizing between the required flow range and permissible pressure
loss.
For an overview of the full scale values for the measuring range, see the "Measuring range"
section → 11
• The minimum recommended full scale value is approx. 1/20 of the maximum full scale value
• In most applications, 20 to 50 % of the maximum full scale value can be considered ideal
• A low full scale value must be selected for abrasive media (such as liquids with entrained solids):
flow velocity < 1 m/s (< 3 ft/s).
• For gas measurement the following rules apply:
• The flow velocity in the measuring tubes should not exceed half the sound velocity (0.5 Mach).
• The maximum mass flow depends on the density of the gas: formula → 11
To calculate the flow limit, use the Applicator sizing tool → 104
Pressure loss
To calculate the pressure loss, use the Applicator sizing tool → 104
64Endress+Hauser
Page 65
Proline Promass X 500
System pressure
Thermal insulation
It is important that cavitation does not occur, or that gases entrained in the liquids do not outgas.
This is prevented by means of a sufficiently high system pressure.
For this reason, the following mounting locations are recommended:
• At the lowest point in a vertical pipe
• Downstream from pumps (no danger of vacuum)
In the case of some fluids, it is important to keep the heat radiated from the sensor to the
transmitter to a low level. A wide range of materials can be used for the required insulation.
The following device versions are recommended for versions with thermal insulation:
Version with extended neck:
Order code for "Measuring tube material", option SA with an extended neck length of
105 mm (4.13 in).
NOTICE
Electronics overheating on account of thermal insulation!
downwards.
Do not insulate the sensor connection housing.
‣
Maximum permissible temperature at the lower end of the sensor connection housing:
‣
80 °C (176 °F)
Thermal insulation with extended neck free: We recommend that you do not insulate the
‣
extended neck in order to ensure optimum dissipation of heat.
A0028777
A0034391
32Thermal insulation with extended neck free
Heating
Some fluids require suitable measures to avoid loss of heat at the sensor.
Heating options
• Electrical heating, e.g. with electric band heaters
• Via pipes carrying hot water or steam
• Via heating jackets
Under critical climatic conditions, in particular, it is important to ensure that the temperature
difference between the ambient temperature and the fluid temperature is not >100 K. Suitable
measures must be taken, such as heating or insulation.
NOTICE
Danger of overheating when heating
Ensure that the temperature at the lower end of the transmitter housing does not exceed
‣
80 °C (176 °F).
Ensure that sufficient convection takes place at the transmitter neck.
‣
Ensure that a sufficiently large area of the transmitter neck remains exposed. The uncovered part
‣
serves as a radiator and protects the electronics from overheating and excessive cooling.
When using in potentially explosive atmospheres, observe the information in the device-specific
‣
Ex documentation. For detailed information on the temperature tables, see the separate
document entitled "Safety Instructions" (XA) for the device.
Endress+Hauser65
Page 66
Proline Promass X 500
Vibrations
The high oscillation frequency of the measuring tubes ensures that the correct operation of the
measuring system is not influenced by plant vibrations.
66Endress+Hauser
Page 67
Proline Promass X 500
Custody transfer measurement
The measuring device is optionally tested in accordance with OIML R117 and has an
EU type evaluation certificate which authorizes the use in EU type-examination certificates according
to Measuring Instruments Directive 2014/32/EU for service subject to legal metrological control
("custody transfer") for liquids other than water(Annex VII).
The permitted fluid temperature in these applications is –10 to +90 °C (+14 to +194 °F).
The measuring device is optionally tested in accordance with OIML R137 and has an EU typeexamination certificate according to Measuring Instruments Directive 2014/32/EU for service as a
gas meter subject to legal metrological control ("custody transfer") (Annex IV). The permitted fluid
temperature in these applications is –25 to +55 °C (–13 to +131 °F).
The device is used with a legally controlled totalizer on the local display and optionally with legally
controlled outputs.
Measuring devices subject to legal metrological control totalize in both directions, i.e. all the outputs
consider flow components in the positive (forward) and negative (reverse) flow direction.
Generally a measuring device subject to legal metrological control is secured against tampering by
seals on the transmitter or sensor. These seals may normally only be opened by a representative of
the competent authority for legal metrology controls.
After putting the device into circulation or after sealing the device, operation is only possible to a
limited extent.
Detailed ordering information is available from your local Endress+Hauser sales center for national
approvals, which are based on the OIML certificates, for applications with liquids other than water or
gases.
Endress+Hauser67
Page 68
Mechanical construction
N
P
F
G
A
Q
T
G
A
B
C
Q
Q
F
Dimensions in SI unitsHousing of Proline 500 – digital transmitter
Non-hazardous area or hazardous area: Zone 2; Class I, Division 2
Proline Promass X 500
A0033789
Order code for "Transmitter housing", option A "Aluminum, coated" and order code for "Integrated ISEM
electronics", option A "Sensor"
A
[mm]
167232801872421
F
[mm]
G
[mm]
N
[mm]
P
[mm]
Q
[mm]
Order code for "Transmitter housing", option D "Polycarbonate" and order code for "Integrated ISEM
electronics", option A "Sensor"
A
[mm]
177234901971722
F
[mm]
G
[mm]
N
[mm]
P
[mm]
Q
[mm]
Housing of Proline 500 transmitter
Hazardous area: Zone 2; Class I, Division 2 or Zone 1; Class I, Division 1
Order code for "Transmitter housing", option A "Aluminum, coated" and order code for "Integrated ISEM
electronics", option B "Transmitter"
A
[mm]
18885103318217130239
B
[mm]
C
[mm]
F
[mm]
G
[mm]
Q
[mm]
[mm]
68Endress+Hauser
A0033788
T
Page 69
Proline Promass X 500
D
L
E
F
K
M
A
B
C
G
C
D
A
B
E
L
Order code for "Transmitter housing", option L "Cast, stainless" and order code for "Integrated ISEM
electronics", option B "Transmitter"
A
[mm]
18885103295217130239
B
[mm]
C
[mm]
F
[mm]
G
[mm]
Q
[mm]
T
[mm]
Sensor connection housing
Order code for "Sensor connection housing", option L "Cast, stainless"
DNA
[mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm]
3001458659140447587136102.2
3501458659140447587136102.2
4001458659140447587136102.2
1)
BCDEFGKLM
2)
2)
2)
A0033800
1227
1227
1227
1)Depending on the cable gland used: values up to + 30 mm
2)Dependent on the respective process connection
Fixed flange connections EN 1092-1, ASME B16.5
33Engineering unit mm (in)
A0015621
Length tolerance for dimension L in mm:
±4
Endress+Hauser69
Page 70
Proline Promass X 500
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN 10
1.4404 (F316/F316L)
Order code for "Process connection", option DAS
DN
[mm]
30044540012 × Ø2226309.71707
35050546016 × Ø2226341.41707
40056551516 × Ø2626392.21716
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 3.2 to 12.5 µm
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN 16
1.4404 (F316/F316L)
Order code for "Process connection", option D1S
DN
[mm]
30046041012 × Ø2628309.71727
35052047016 × Ø2630339.61734
40058052512 × Ø3032390.41741
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 3.2 to 12.5 µm
A
[mm]
A
[mm]
B
[mm]
B
[mm]
C
[mm]
C
[mm]
D
[mm]
D
[mm]
E
[mm]
E
[mm]
L
[mm]
L
[mm]
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN40
1.4404 (F316/F316L)
Order code for "Process connection", option D2S
DN
[mm]
30051545016 × Ø3342307.91800
35058051016 × Ø3646338.01818
40066058516 × Ø3950384.41836
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 3.2 to 12.5 µm
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN63
1.4404 (F316/F316L)
Order code for "Process connection", option D3S
DN
[mm]
30053046016 × Ø3652301.91844
35060052516 × Ø3956330.61863
40067058516 × Ø4260378.01880
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 3.2 to 12.5 µm
A
[mm]
A
[mm]
B
[mm]
B
[mm]
C
[mm]
C
[mm]
D
[mm]
D
[mm]
E
[mm]
E
[mm]
L
[mm]
L
[mm]
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN100
1.4404 (F316/F316L)
Order code for "Process connection", option D4S)
DN
[mm]
30058550016 × Ø4268295.51901
35065556016 × Ø4874323.61936
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
L
[mm]
70Endress+Hauser
Page 71
Proline Promass X 500
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN100
1.4404 (F316/F316L)
Order code for "Process connection", option D4S)
DN
[mm]
40071562016 × Ø4882.2364.91936
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 3.2 to 12.5 µm
Flange in accordance with ASME B16.5: Cl 150
1.4404 (F316/F316L)
Order code for "Process connection", option AAS
DN
[mm]
300482.6431.812 × Ø25.432.2304.81794
350533.4476.316 × Ø28.435.5336.51820
400596.9539.816 × Ø28.437.0387.31820
Surface roughness (flange): Ra 3.2 to 6.3 µm
A
[mm]
A
[mm]
[mm]
B
[mm]
B
C
[mm]
C
[mm]
D
[mm]
[mm]
E
[mm]
D
E
[mm]
L
[mm]
L
[mm]
Flange in accordance with ASME B16.5: Cl 300
1.4404 (F316/F316L)
Order code for "Process connection", option ABS
DN
[mm]
300520.7450.916 × Ø31.851.3304.81826
350584.2514.416 × Ø31.854.4336.51852
400647.7571.516 × Ø35.157.6387.31858
Surface roughness (flange): Ra 3.2 to 6.3 µm
Flange in accordance with ASME B16.5: Cl 600
1.4404 (F316/F316L)
Order code for "Process connection", option ACS
DN
[mm]
300558.8489.020 × Ø35.173.7288.81875
350603.3527.120 × Ø38.177.0317.51891
400685.8603.320 × Ø41.183.2363.31912
Surface roughness (flange): Ra 3.2 to 6.3 µm
A
[mm]
A
[mm]
B
[mm]
B
[mm]
C
[mm]
C
[mm]
D
[mm]
D
[mm]
E
[mm]
E
[mm]
L
[mm]
L
[mm]
Endress+Hauser71
Page 72
Proline Promass X 500
L
A
SW 1"
2
½" NPT
1
½" NPT
35 (1.38)ca. 75 (approx. 2.95)
213 (8.4)
39 (1.5)
243 (9.6)
203 (8.0)
Accessories
Rupture disk/purge connections
34
1Connection nipple for purge connections: order code for "Sensor options", option CH "Purge connection"
2Connection nipple with rupture disk: order code for "Sensor option", option CA "Rupture disk"
A0029972
DNAL
[mm][mm][mm]
300182547
350182547
400182547
Protective cover
A0029552
35Weather protection cover for Proline 500 – digital
72Endress+Hauser
Page 73
Proline Promass X 500
146 (5.75)
48 (1.9)
12 (0.47)
280 (11.0)255 (10.0)
134 (5.3)
30 (1.18)
105 (4.1)
A0029553
36Weather protection cover for Proline 500
External WLAN antenna
The external WLAN antenna is not suitable for use in hygienic applications.
Proline 500 – digital
External WLAN antenna mounted on device
A0033607
37Engineering unit mm (in)
External WLAN antenna mounted with cable
The external WLAN antenna can be mounted separately from the transmitter if the transmission/
reception conditions at the transmitter mounting location are poor.
Endress+Hauser73
Page 74
70 (2.8)
1500 (59.1)
72 (2.8)
38Engineering unit mm (in)
68 (2.7)105 (4.1)
173 (6.8)
70 (2.8)
1500 (59.1)
72 (2.8)
Proline 500
Proline Promass X 500
A0033606
External WLAN antenna mounted on device
A0028923
39Engineering unit mm (in)
External WLAN antenna mounted with cable
The external WLAN antenna can be mounted separately from the transmitter if the transmission/
reception conditions at the transmitter mounting location are poor.
74Endress+Hauser
40Engineering unit mm (in)
A0033597
Page 75
Proline Promass X 500
N
P
F
G
A
Q
T
G
A
B
C
Q
Q
F
Dimensions in US unitsHousing of Proline 500 – digital transmitter
Non-hazardous area or hazardous area: Zone 2; Class I, Division 2
Order code for "Transmitter housing", option A "Aluminum, coated" and order code for "Integrated ISEM
electronics", option A "Sensor"
A0033789
A
[in]
6.579.133.157.360.940.83
F
[in]
G
[in]
N
[in]
P
[in]
Q
[in]
Order code for "Transmitter housing", option D "Polycarbonate" and order code for "Integrated ISEM
electronics", option A "Sensor"
A
[in]
6.979.213.547.760.670.87
F
[in]
G
[in]
N
[in]
P
[in]
Q
[in]
Housing of Proline 500 transmitter
Hazardous area: Zone 2; Class I, Division 2 or Zone 1; Class I, Division 1
A0033788
Order code for "Transmitter housing", option A "Aluminum, coated" and order code for "Integrated ISEM
electronics", option B "Transmitter"
A
[in]
7.403.354.0612.58.545.129.41
[in]
B
C
[in]
F
[in]
G
[in]
Q
[in]
T
[in]
Endress+Hauser75
Page 76
Proline Promass X 500
D
L
E
F
K
M
A
B
C
G
C
D
A
B
E
L
Order code for "Transmitter housing", option L "Cast, stainless" and order code for "Integrated ISEM
electronics", option B "Transmitter"
A
[in]
7.403.354.0611.68.545.129.41
B
[in]
C
[in]
F
[in]
G
[in]
Q
[in]
Sensor connection housing
Order code for "Sensor connection housing", option L "Cast, stainless"
DNA
[in][in][in][in][in][in][in][in][in][in][in]
125.713.392.325.5117.623.115.354.02
145.713.392.325.5117.623.115.354.02
165.713.392.325.5117.623.115.354.02
1)
BCDEFGKLM
2)
2)
2)
T
[in]
A0033800
48.31
48.31
48.31
1)Depending on the cable gland used: values up to +1.18 in
2)Dependent on the respective process connection
Fixed flange connections ASME B16.5
41Engineering unit mm (in)
A0015621
Length tolerance for dimension L in inch:
±0.16
76Endress+Hauser
Page 77
Proline Promass X 500
Flange in accordance with ASME B16.5: Cl 150
1.4404 (F316/F316L)
Order code for "Process connection", option AAS
DN
[in]
1219.0017.0012 × Ø1.001.2712.0070.63
1421.0018.7516 × Ø1.121.4013.2571.65
1623.5021.2516 × Ø1.121.4615.2571.65
Surface roughness (flange): Ra 125 to 250 µin
Flange in accordance with ASME B16.5: Cl 300
1.4404 (F316/F316L)
Order code for "Process connection", option ABS
DN
[in]
1220.5017.7516 × Ø1.252.0212.0071.89
1423.0020.2516 × Ø1.252.1413.2572.91
1625.5022.5016 × Ø1.382.2715.2573.15
Surface roughness (flange): Ra 125 to 250 µin
A
[in]
A
[in]
B
[in]
B
[in]
C
[in]
C
[in]
D
[in]
D
[in]
E
[in]
E
[in]
L
[in]
L
[in]
Flange in accordance with ASME B16.5: Cl 600
1.4404 (F316/F316L)
Order code for "Process connection", option ACS
DN
[in]
1222.0019.2520 × Ø1.382.9011.3773.82
1423.7520.7520 × Ø1.503.0312.5074.45
1627.0023.7520 × Ø1.623.2814.3075.28
Surface roughness (flange): Ra 125 to 250 µin
A
[in]
B
[in]
C
[in]
D
[in]
E
[in]
L
[in]
Endress+Hauser77
Page 78
Proline Promass X 500
L
A
SW 1"
2
½" NPT
1
½" NPT
35 (1.38)ca. 75 (approx. 2.95)
213 (8.4)
39 (1.5)
243 (9.6)
203 (8.0)
Accessories
Rupture disk/purge connections
42
1Connection nipple for purge connections: order code for "Sensor options", option CH "Purge connection"
2Connection nipple with rupture disk: order code for "Sensor option", option CA "Rupture disk"
A0029972
DNAL
[in][in][in]
127.1721.54
147.1721.54
167.1721.54
Protective cover
A0029552
43Weather protection cover for Proline 500 – digital
78Endress+Hauser
Page 79
Proline Promass X 500
146 (5.75)
48 (1.9)
12 (0.47)
280 (11.0)255 (10.0)
134 (5.3)
30 (1.18)
105 (4.1)
A0029553
44Weather protection cover for Proline 500
External WLAN antenna
The external WLAN antenna is not suitable for use in hygienic applications.
Proline 500 – digital
External WLAN antenna mounted on device
A0033607
45Engineering unit mm (in)
External WLAN antenna mounted with cable
The external WLAN antenna can be mounted separately from the transmitter if the transmission/
reception conditions at the transmitter mounting location are poor.
Endress+Hauser79
Page 80
70 (2.8)
1500 (59.1)
72 (2.8)
46Engineering unit mm (in)
68 (2.7)105 (4.1)
173 (6.8)
70 (2.8)
1500 (59.1)
72 (2.8)
Proline 500
Proline Promass X 500
A0033606
External WLAN antenna mounted on device
A0028923
47Engineering unit mm (in)
External WLAN antenna mounted with cable
The external WLAN antenna can be mounted separately from the transmitter if the transmission/
reception conditions at the transmitter mounting location are poor.
80Endress+Hauser
48Engineering unit mm (in)
A0033597
Page 81
Proline Promass X 500
Weight
All values (weight exclusive of packaging material) refer to devices with ASME B16.5
Class 150 flanges.
Transmitter
• Proline 500 – digital polycarbonate: 1.4 kg (3.1 lbs)
• Proline 500 – digital aluminum: 2.4 kg (5.3 lbs)
• Proline 500 aluminum: 6.5 kg (14.3 lbs)
• Proline 500 cast, stainless: 15.6 kg (34.4 lbs)
Sensor
Sensor with cast connection housing version, stainless: see the information in the following table
Weight in SI units
DN
[mm]
300557
350581
400605
Weight [kg]
Weight in US units
DN
[in]
121227
141280
161333
Weight [lbs]
MaterialsTransmitter housing
Housing of Proline 500 – digital transmitter
Order code for "Transmitter housing":
• Option A "Aluminum coated": aluminum, AlSi10Mg, coated
• Option D "Polycarbonate": polycarbonate
Housing of Proline 500 transmitter
Order code for "Transmitter housing":
Option L "Cast, stainless": cast, stainless steel, 1.4409 (CF3M) similar to 316L
Window material
Order code for "Transmitter housing":
• Option A "Aluminum, coated": glass
• Option D "Polycarbonate": plastic
• Option L "Cast, stainless": glass
Sensor connection housing
Order code for "Sensor connection housing":
Option L "Cast, stainless": 1.4409 (CF3M) similar to 316L
Endress+Hauser81
Page 82
Cable entries/cable glands
1
2
3
4
49Possible cable entries/cable glands
1Female thread M20 × 1.5
2Cable gland M20 × 1.5
3Adapter for cable entry with internal thread G ½" or NPT ½"
4Device plugs
Proline Promass X 500
A0028352
Cable entries and adaptersMaterial
Cable gland M20 × 1.5Plastic
• Adapter for cable entry with internal thread G ½"
• Adapter for cable entry with internal thread NPT ½"
Only available for certain device versions:
• Order code for "Transmitter housing":
• Option A "Aluminum, coated"
• Option D "Polycarbonate"
• Order code for "Sensor connection housing":
• Proline 500 – digital:
Option L "Cast, stainless"
• Proline 500:
Option L "Cast, stainless"
• Adapter for cable entry with internal thread G ½"
• Adapter for cable entry with internal thread NPT ½"
Only available for certain device versions:
• Order code for "Transmitter housing":
Option L "Cast, stainless"
• Order code for "Sensor connection housing":
Option L "Cast, stainless"
Adapter for device plug
Device plug for digital communication:
Only available for certain device versions → 32.
Flanges in accordance with EN 1092-1 (DIN2501) / ASME B 16.5:
Stainless steel, 1.4404 (F316/F316L)
Available process connections→ 83
Process connections
Surface roughness
Seals
Welded process connections without internal seals
Accessories
Protective cover
Stainless steel, 1.4404 (316L)
External WLAN antenna
• Antenna: ASA plastic (acrylic ester-styrene-acrylonitrile) and nickel-plated brass
• Adapter: Stainless steel and nickel-plated brass
• Cable: Polyethylene
• Plug: Nickel-plated brass
• Angle bracket: Stainless steel
Fixed flange connections:
• EN 1092-1 (DIN 2501) flange
• EN 1092-1 (DIN 2512N) flange
• ASME B16.5 flange
Process connection materials → 83
All data relate to parts in contact with fluid. The following surface roughness quality can be ordered.
Not polished
Human interface
Operating concept
Endress+Hauser83
Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Page 84
Proline Promass X 500
12
Fast and safe commissioning
• Guided menus ("Make-it-run" wizards) for applications
• Menu guidance with brief descriptions of the individual parameter functions
• Access to the device via Web server → 104
• WLAN access to the device via mobile handheld terminal, tablet or smart phone
Reliable operation
• Operation in local language → 84
• Uniform operating philosophy applied to device and operating tools
• If replacing electronic modules, transfer the device configuration via the integrated memory
(HistoROM backup) which contains the process and measuring device data and the event logbook.
No need to reconfigure.
• Troubleshooting measures can be called up via the device and in the operating tools
• Diverse simulation options, logbook for events that occur and optional line recorder functions
Languages
Can be operated in the following languages:
• Via local operation
English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese,
Japanese, Korean, Bahasa (Indonesian), Vietnamese, Czech, Swedish
• Via Web browser
English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese,
Japanese, Korean, Bahasa (Indonesian), Vietnamese, Czech, Swedish
• Via "FieldCare", "DeviceCare" operating tool: English, German, French, Spanish, Italian, Chinese,
Japanese
Local operationVia display module
Equipment:
• Order code for "Display; operation", option F "4-line, illuminated, graphic display; touch control"
• Order code for "Display; operation", option G "4-line, illuminated, graphic display; touch control +
WLAN"
Information about WLAN interface → 90
A0028232
50Operation with touch control
1Proline 500 – digital
2Proline 500
Display elements
• 4-line, illuminated, graphic display
• White background lighting; switches to red in event of device errors
• Format for displaying measured variables and status variables can be individually configured
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
84Endress+Hauser
Page 85
Proline Promass X 500
1235
8
47
6
1
10
2
3
457
69
8
Operating elements
• External operation via touch control (3 optical keys) without opening the housing: , ,
• Operating elements also accessible in the various zones of the hazardous area
Remote operationVia HART protocol
This communication interface is available in device versions with a HART output.
51Options for remote operation via HART protocol (active)
1Control system (e.g. PLC)
2Field Communicator 475
3Computer with Web browser (e.g. Internet Explorer) for access to the integrated device Web server or
computer with an operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) with COM
DTM "CDI Communication TCP/IP"
4Commubox FXA195 (USB)
5Field Xpert SFX350 or SFX370
6Field Xpert SMT70
7VIATOR Bluetooth modem with connecting cable
8Transmitter
A0028747
Endress+Hauser85
52Options for remote operation via HART protocol (passive)
1Control system (e.g. PLC)
2Transmitter power supply unit, e.g. RN221N (with communication resistor)
3Connection for Commubox FXA195 and Field Communicator 475
4Field Communicator 475
5Computer with Web browser (e.g. Internet Explorer) for access to the integrated device Web server or
computer with an operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) with COM
DTM "CDI Communication TCP/IP"
6Commubox FXA195 (USB)
7Field Xpert SFX350 or SFX370
8Field Xpert SMT70
9VIATOR Bluetooth modem with connecting cable
10 Transmitter
A0028746
Page 86
Proline Promass X 500
12
3
1
9898
4
66
5
12
3
444
Via FOUNDATION Fieldbus network
This communication interface is available in device versions with FOUNDATION Fieldbus.
53Options for remote operation via FOUNDATION Fieldbus network
1Automation system
2Computer with FOUNDATION Fieldbus network card
3Industry network
4High Speed Ethernet FF-HSE network
5Segment coupler FF-HSE/FF-H1
6FOUNDATION Fieldbus FF-H1 network
7Power supply FF-H1 network
8T-box
9Measuring device
Via PROFIBUS DP network
This communication interface is available in device versions with PROFIBUS DP.
A0028837
54Options for remote operation via PROFIBUS DP network
1Automation system
2Computer with PROFIBUS network card
3PROFIBUS DP network
4Measuring device
A0020903
86Endress+Hauser
Page 87
Proline Promass X 500
2
3
1
76
5
4
12
3
Via PROFIBUS PA network
This communication interface is available in device versions with PROFIBUS PA.
A0028838
55Options for remote operation via PROFIBUS PA network
1Automation system
2Computer with PROFIBUS network card
3PROFIBUS DP network
4Segment coupler PROFIBUS DP/PA
5PROFIBUS PA network
6T-box
7Measuring device
Via Modbus RS485 protocol
This communication interface is available in device versions with a Modbus-RS485 output.
A0029437
56Options for remote operation via Modbus-RS485 protocol (active)
1Control system (e.g. PLC)
2Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP" or Modbus DTM
3Transmitter
Via EtherNet/IP network
This communication interface is available in device versions with EtherNet/IP.
Endress+Hauser87
Page 88
Proline Promass X 500
4
213
555
4
213
5
55
Star topology
57Options for remote operation via EtherNet/IP network: star topology
1Automation system, e.g. "RSLogix" (Rockwell Automation)
2Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell
Automation) or with Electronic Data Sheet (EDS)
3Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP"
4Ethernet switch
5Measuring device
A0032078
Ring topology
The device is integrated via the terminal connection for signal transmission (output 1) and the
service interface (CDI-RJ45).
58Options for remote operation via EtherNet/IP network: ring topology
1Automation system, e.g. "RSLogix" (Rockwell Automation)
2Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell
Automation) or with Electronic Data Sheet (EDS)
3Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP"
4Ethernet switch
5Measuring device
A0033725
Via PROFINET network
This communication interface is available in device versions with PROFINET.
88Endress+Hauser
Page 89
Proline Promass X 500
312
444
3
12
444
Star topology
A0026545
59Options for remote operation via PROFINET network: star topology
1Automation system, e.g. Simatic S7 (Siemens)
2Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare, SIMATIC PDM) with COM DTM "CDI Communication
TCP/IP"
3Switch, e.g. Scalance X204 (Siemens)
4Measuring device
Ring topology
The device is integrated via the terminal connection for signal transmission (output 1) and the
service interface (CDI-RJ45).
A0033719
60Options for remote operation via PROFINET network: ring topology
1Automation system, e.g. Simatic S7 (Siemens)
2Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare, SIMATIC PDM) with COM DTM "CDI Communication
TCP/IP"
3Switch, e.g. Scalance X204 (Siemens)
4Measuring device
Endress+Hauser89
Page 90
Service interfaceVia service interface (CDI-RJ45)
open
press
2
3
2
3
A point-to-point connection can be established to configure the device onsite. With the housing
open, the connection is established directly via the service interface (CDI-RJ45) of the device.
An adapter for RJ45 and the M12 connector is optionally available:
Order code for "Accessories", option NB: "Adapter RJ45 M12 (service interface)"
The adapter connects the service interface (CDI-RJ45) to an M12 connector mounted in the
cable entry. Therefore the connection to the service interface can be established via an M12
connector without opening the device.
Proline 500 – digital transmitter
Proline Promass X 500
A0029163
61Connection via service interface (CDI-RJ45)
1Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated
device Web server or with "FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"
or Modbus DTM
2Standard Ethernet connecting cable with RJ45 connector
3Service interface (CDI-RJ45) of the measuring device with access to the integrated Web server
Proline 500 transmitter
A0027563
62Connection via service interface (CDI-RJ45)
1Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated
device Web server or with "FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"
or Modbus DTM
2Standard Ethernet connecting cable with RJ45 connector
3Service interface (CDI-RJ45) of the measuring device with access to the integrated Web server
Via WLAN interface
The optional WLAN interface is available on the following device version:
Order code for "Display; operation", option G "4-line, illuminated; touch control + WLAN"
90Endress+Hauser
Page 91
Proline Promass X 500
1
22
1
3
4
3
4
3
4
3
4
567
A0034569
1Transmitter with integrated WLAN antenna
2Transmitter with external WLAN antenna
3LED lit constantly: WLAN reception is enabled on measuring device
4LED flashing: WLAN connection established between operating unit and measuring device
5Computer with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for
accessing the integrated device Web server or with operating tool (e.g. FieldCare, DeviceCare)
6Mobile handheld terminal with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft
Edge) for accessing the integrated device Web server or operating tool (e.g. FieldCare, DeviceCare)
7Smart phone or tablet (e.g. Field Xpert SMT70)
FunctionWLAN: IEEE 802.11 b/g (2.4 GHz)
• Access point with DHCP server (default setting)
• Network
EncryptionWPA2-PSK AES-128 (in accordance with IEEE 802.11i)
Configurable WLAN channels1 to 11
Degree of protectionIP67
Available antennas• Internal antenna
• External antenna (optional)
In the event of poor transmission/reception conditions at the place of
installation.
Range• Internal antenna: typically 10 m (32 ft)
Materials (external antenna)• Antenna: ASA plastic (acrylic ester-styrene-acrylonitrile) and nickel-
Available as an accessory → 102.
Only one antenna active in each case!
• External antenna: typically 50 m (164 ft)
plated brass
• Adapter: Stainless steel and nickel-plated brass
• Cable: Polyethylene
• Connector: Nickel-plated brass
• Angle bracket: Stainless steel
Endress+Hauser91
Page 92
Proline Promass X 500
213
555
4
6
7
8
Network integration
With the optional "OPC-UA Server" application package, the device can be integrated into an Ethernet
network via the service interface (CDI-RJ45 and WLAN) and communicate with OPC-UA clients. If
the device is used in this way, IT security must be considered.
Transmitters with an Ex de approval may not be connected via the service interface (CDI-RJ45)!
Order code for "Approval transmitter + sensor", options (Ex de):
BA, BB, C1, C2, GA, GB, MA, MB, NA, NB
For permanent access to device data and for device configuration via the Web server, the device is
incorporated directly in a network via the service interface (CDI-RJ45). In this way, the device can be
accessed any time from the control station. The measured values are processed separately via the
inputs and outputs through the automation system.
Supported operating tools
A0033618
1Automation system, e.g. Simatic S7 (Siemens)
2Ethernet switch
3Edge Gateway
4Cloud
5Measuring device
6Ethernet network
7Measured values via inputs and outputs
8Optional WLAN interface
The optional WLAN interface is available on the following device version:
Order code for "Display; operation", option G "4-line, illuminated, graphic display; touch control +
WLAN"
Special Documentation for the OPC-UA Server application package → 106.
Different operating tools can be used for local or remote access to the measuring device. Depending
on the operating tool used, access is possible with different operating units and via a variety of
interfaces.
Supported operating
tools
Web browserNotebook, PC or tablet
DeviceCare SFE100Notebook, PC or tablet
Operating unitInterfaceAdditional information
with Web browser
with Microsoft Windows
system
• CDI-RJ45 service
interface
• WLAN interface
• Ethernet-based
fieldbus (EtherNet/IP,
PROFINET)
• CDI-RJ45 service
interface
• WLAN interface
• Fieldbus protocol
Special Documentation for
device → 106
→ 104
92Endress+Hauser
Page 93
Proline Promass X 500
Supported operating
tools
FieldCare SFE500Notebook, PC or tablet
Device XpertField Xpert SFX
Operating unitInterfaceAdditional information
with Microsoft Windows
system
100/350/370
• CDI-RJ45 service
interface
• WLAN interface
• Fieldbus protocol
HART and
FOUNDATION Fieldbus
fieldbus protocol
→ 104
Operating Instructions
BA01202S
Device description files:
Use update function of
handheld terminal
Other operating tools based on FDT technology with a device driver such as DTM/iDTM or
DD/EDD can be used for device operation. These operating tools are available from the
individual manufacturers. Integration into the following operating tools, among others, is
supported:
• FactoryTalk AssetCentre (FTAC) by Rockwell Automation → www.rockwellautomation.com
• Process Device Manager (PDM) by Siemens → www.siemens.com
• Asset Management Solutions (AMS) by Emerson → www.emersonprocess.com
• FieldCommunicator 375/475 by Emerson → www.emersonprocess.com
• Field Device Manager (FDM) by Honeywell → www.honeywellprocess.com
• FieldMate by Yokogawa → www.yokogawa.com
• PACTWare → www.pactware.com
The associated device description files are available at: www.endress.com → Downloads
Web server
Thanks to the integrated Web server, the device can be operated and configured via a Web browser
and via a service interface (CDI-RJ45) or via a WLAN interface. The structure of the operating menu
is the same as for the local display. In addition to the measured values, status information on the
device is also displayed and allows the user to monitor the status of the device. Furthermore the
device data can be managed and the network parameters can be configured.
A device that has a WLAN interface (can be ordered as an option) is required for the WLAN
connection: order code for "Display; operation", option G "4-line, illuminated; touch control + WLAN".
The device acts as an Access Point and enables communication by computer or a mobile handheld
terminal.
Supported functions
Data exchange between the operating unit (such as a notebook for example) and the measuring
device:
• Upload the configuration from the measuring device (XML format, configuration backup)
• Save the configuration to the measuring device (XML format, restore configuration)
• Export event list (.csv file)
• Export parameter settings (.csv file or PDF file, document the measuring point configuration)
• Export the Heartbeat verification log (PDF file, only available with the "Heartbeat Verification"
application package)
• Flash firmware version for device firmware upgrade, for instance
• Download driver for system integration
• Visualize up to 1000 saved measured values (only available with the Extended HistoROM
application package → 101)
Web server special documentation → 106
HistoROM data management
The measuring device features HistoROM data management. HistoROM data management
comprises both the storage and import/export of key device and process data, making operation and
servicing far more reliable, secure and efficient.
When the device is delivered, the factory settings of the configuration data are stored as a
backup in the device memory. This memory can be overwritten with an updated data record, for
example after commissioning.
Endress+Hauser93
Page 94
Additional information on the data storage concept
There are different types of data storage units in which device data are stored and used by the device:
Device memoryT-DATS-DAT
Available data• Event logbook such as diagnostic events for example
• Parameter data record backup
• Device firmware package
• Driver for system integration for exporting via Web
server, e.g:
• GSD for PROFIBUS DP
• GSD for PROFIBUS PA
• GSDML for PROFINET
• EDS for EtherNet/IP
• DD for FOUNDATION Fieldbus
Storage location Fixed on the user interface board in the connection
compartment
• Measured value logging
("Extended HistoROM" order
option)
• Current parameter data record
(used by firmware at run time)
• Peakhold indicator (min/max
values)
• Totalizer values
Attachable to the user interface
board in the connection
compartment
Data backup
Automatic
• The most important device data (sensor and transmitter) are automatically saved in the DAT
modules
• If the transmitter or measuring device is replaced: once the T-DAT containing the previous device
data has been exchanged, the new measuring device is ready for operation again immediately
without any errors
• If the sensor is replaced: once the sensor has been replaced, new sensor data are transferred from
the S-DAT in the measuring device and the measuring device is ready for operation again
immediately without any errors
• If exchanging the electronics module (e.g. I/O electronics module): Once the electronics module
has been replaced, the software of the module is compared against the current device firmware.
The module software is upgraded or downgraded where necessary. The electronics module is
available for use immediately afterwards and no compatibility problems occur.
Manual
Additional parameter data record (complete parameter settings) in the integrated device memory
HistoROM backup for:
• Data backup function
Backup and subsequent restoration of a device configuration in the device memory HistoROM
backup
• Data comparison function
Comparison of the current device configuration with the device configuration saved in the device
memory HistoROM backup
Proline Promass X 500
• Sensor data: nominal diameter
etc.
• Serial number
• Calibration data
• Device configuration (e.g. SW
options, fixed I/O or multi I/O)
In the sensor plug in the transmitter
neck part
Data transfer
Manual
• Transfer of a device configuration to another device using the export function of the specific
operating tool, e.g. with FieldCare, DeviceCare or Web server: to duplicate the configuration or to
store in an archive (e.g. for backup purposes)
• Transmission of the drivers for system integration via Web server, e.g.:
• GSD for PROFIBUS DP
• GSD for PROFIBUS PA
• GSDML for PROFINET
• EDS for EtherNet/IP
• DD for FOUNDATION Fieldbus
Event list
Automatic
• Chronological display of up to 20 event messages in the events list
• If the Extended HistoROM application package (order option) is enabled: up to 100 event
messages are displayed in the events list along with a time stamp, plain text description and
remedial measures
• The events list can be exported and displayed via a variety of interfaces and operating tools e.g.
DeviceCare, FieldCare or Web server
94Endress+Hauser
Page 95
Proline Promass X 500
Data logging
Manual
If the Extended HistoROM application package (order option) is enabled:
• Record up to 1000 measured values via 1 to 4 channels
• User configurable recording interval
• Record up to 250 measured values via each of the 4 memory channels
• Export the measured value log via a variety of interfaces and operating tools e.g. FieldCare,
DeviceCare or web server
Certificates and approvals
Currently available certificates and approvals can be called up via the product configurator.
CE mark
RCM-tick symbol
Ex approval
The device meets the legal requirements of the applicable EU Directives. These are listed in the
corresponding EU Declaration of Conformity along with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
The measuring device is certified for use in hazardous areas and the relevant safety instructions are
provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on
the nameplate.
The following devices have equipment protection level (EPL) Ga/Gb (Zone 0 in the measuring tube):
• Device versions with the order code for "Integrated ISEM electronics", option A and the order code
for "Approval; transmitter; sensor", option BI, BJ, BM or BN.
• Device versions with the order code for "Integrated ISEM electronics", option B and the order code
for "Approval; transmitter; sensor", option BA, BB, BC or BD.
The separate Ex documentation (XA) containing all the relevant explosion protection data is
available from your Endress+Hauser sales center.
Proline 500 – digital
ATEX/IECEx
Currently, the following versions for use in hazardous areas are available:
Ex ia
TransmitterSensor
CategoryType of protectionCategoryType of protection
CategoryType of protectionCategoryType of protection
II(1)D[Ex ia] IIICII2DEx ia tb IIIC T** °C Db
Endress+Hauser95
Page 96
Proline Promass X 500
Non-Ex / Ex ec
TransmitterSensor
CategoryType of protectionCategoryType of protection
Non - ExNon-ExII3GEx ec IIC T5…T1 Gc
II3GEx ec IIC T5…T4 GcII3GEx ec IIC T5…T1 Gc
CSA
C
US
Currently, the following versions for use in hazardous areas are available:
IS (Ex nA, Ex i)
TransmitterSensor
Class I Division 2 Groups A - DClass I, II, III Division 1 Groups A-G
Class I Division 2 Groups A - DClass I, II, III Division 1 Groups C-G
NI (Ex nA)
TransmitterSensor
Class I Division 2 Groups A - D
Ex nA / Ex i
TransmitterSensor
Class I, Zone 2 AEx/ Ex nA [ia Ga] IIC T5…T4 GbClass I, Zone 1 AEx/ Ex ia IIC T6…T1 Ga/Gb
Class I, Zone 1 AEx/ Ex ia IIB T6…T1 Ga/Gb
Class I, Zone 2 AEx/ Ex nA [ia Ga] IIC T5…T4 GbClass I, Zone 1 AEx/ Ex ia IIC T6…T1 Gb
Class I, Zone 1 AEx/ Ex ia IIB T6…T1 Gb
Ex nA
TransmitterSensor
Class I, Zone 2 AEx/ Ex nA IIC T5...T4 GcClass I, Zone 2 AEx/ Ex nA IIC T5...T1 Gc
Ex tb
TransmitterSensor
[AEx / Ex ia ] IIICZone 21 AEx/ Ex ia tb IIIC T** °C Db
Proline 500
ATEX/IECEx
Currently, the following versions for use in hazardous areas are available:
Ex db eb
TransmitterSensor
CategoryType of protectionCategoryType of protection
II2GEx db eb ia IIC T6…T4 GbII1/2GEx ia IIC T6…T1 Ga/Gb
II2GEx db eb ia IIB T6…T4 GbII1/2GEx ia IIB T6…T1 Ga/Gb
II2GEx db eb ia IIC T6…T4 GbII2GEx ia IIC T6…T1 Gb
II2GEx db eb ia IIB T6…T4 GbII2GEx ia IIB T6…T1 Gb
96Endress+Hauser
Page 97
Proline Promass X 500
Ex db
TransmitterSensor
CategoryType of protectionCategoryType of protection
II2GEx db ia IIC T6…T4 GbII1/2GEx ia IIC T6…T1 Ga/Gb
II2GEx db ia IIB T6…T4 GbII1/2GEx ia IIB T6…T1 Ga/Gb
II2GEx db ia IIC T6…T4 GbII2GEx ia IIC T6…T1 Gb
II2GEx db ia IIB T6…T4 GbII2GEx ia IIB T6…T1 Gb
Ex tb
CategoryType of protection
TransmitterSensor
II2DEx tb IIIC T85°C DbEx ia tb IIIC T** °C Db
Ex ec
CategoryType of protection
TransmitterSensor
II3GEx ec IIC T5…T4 GcEx ec IIC T5…T1 Gc
CSA
C
US
Currently, the following versions for use in hazardous areas are available:
IS (Ex i) and XP (Ex d)
TransmitterSensor
Class I, III, III Division 1 Groups A-G
Class I, III, III Division 1 Groups C-G
NI (Ex nA)
TransmitterSensor
Class I Division 2 Groups ABCD
Ex de
TransmitterSensor
Class I, Zone 1 AEx/ Ex de ia IIC T6…T4 GbClass I, Zone 1 AEx/ Ex ia IIC T6…T1 Ga/Gb
Class I, Zone 1 AEx/ Ex de ia IIB T6…T4 GbClass I, Zone 1 AEx/ Ex ia IIB T6…T1 Ga/Gb
Class I, Zone 1 AEx/ Ex de ia IIC T6…T4 GbClass I, Zone 1 AEx/ Ex ia IIC T6…T1 Gb
Class I, Zone 1 AEx/ Ex de ia IIB T6…T4 GbClass I, Zone 1 AEx/ Ex ia IIB T6…T1 Gb
Ex d
TransmitterSensor
Class I, Zone 1 AEx/ Ex d ia IIC T6…T4 GbClass I, Zone 1 AEx/ Ex ia IIC T6…T1 Ga/Gb
Class I, Zone 1 AEx/ Ex d ia IIB T6…T4 GbClass I, Zone 1 AEx/ Ex ia IIB T6…T1 Ga/Gb
Class I, Zone 1 AEx/ Ex d ia IIC T6…T4 GbClass I, Zone 1 AEx/ Ex ia IIC T6…T1 Gb
Class I, Zone 1 AEx/ Ex d ia IIB T6…T4 GbClass I, Zone 1 AEx/ Ex ia IIB T6…T1 Gb
Endress+Hauser97
Page 98
Proline Promass X 500
Ex nA
TransmitterSensor
Class I, Zone 2 AEx/ Ex nA IIC T5...T4 GcClass I, Zone 2 AEx/ Ex nA IIC T5...T1 Gc
Ex tb
TransmitterSensor
Zone 21 AEx/ Ex tb IIIC T85°C DbZone 21 AEx/ Ex ia tb IIIC T** °C Db
Pharmaceutical compatibility
• FDA
• USP Class VI
• TSE/BSE Certificate of Suitability
Functional safety
The measuring device can be used for flow monitoring systems (min., max., range) up to SIL 2
(single-channel architecture; order code for "Additional approval", option LA) and SIL 3
(multichannel architecture with homogeneous redundancy) and is independently evaluated and
certified by the TÜV in accordance with IEC 61508.
The following types of monitoring in safety equipment are possible:
• Mass flow
• Volume flow
• Density
Functional Safety Manual with information on the SIL device → 106
HART certificationHART interface
The measuring device is certified and registered by the FieldComm Group. The measuring system
meets all the requirements of the following specifications:
• Certified according to HART 7
• The device can also be operated with certified devices of other manufacturers (interoperability)
FOUNDATION Fieldbus
certification
FOUNDATION Fieldbus interface
The measuring device is certified and registered by the FieldComm Group. The measuring system
meets all the requirements of the following specifications:
• Certified in accordance with FOUNDATION Fieldbus H1
• Interoperability Test Kit (ITK), revision version 6.2.0 (certificate available on request)
• Physical Layer Conformance Test
• The device can also be operated with certified devices of other manufacturers (interoperability)
Certification PROFIBUSPROFIBUS interface
The measuring device is certified and registered by the PNO (PROFIBUS User Organization
Organization). The measuring system meets all the requirements of the following specifications:
• Certified in accordance with PROFIBUS PA Profile 3.02
• The device can also be operated with certified devices of other manufacturers (interoperability)
EtherNet/IP certification
The measuring device is certified and registered by the ODVA (Open Device Vendor Association).
The measuring system meets all the requirements of the following specifications:
• Certified in accordance with the ODVA Conformance Test
• EtherNet/IP Performance Test
• EtherNet/IP PlugFest compliance
• The device can also be operated with certified devices of other manufacturers (interoperability)
98Endress+Hauser
Page 99
Proline Promass X 500
Certification PROFINETPROFINET interface
The measuring device is certified and registered by the PNO (PROFIBUS User Organization). The
measuring system meets all the requirements of the following specifications:
• Certified according to:
• Test specification for PROFINET devices
• PROFINET Security Level 2 – Netload Class
• The device can also be operated with certified devices of other manufacturers (interoperability)
• The device supports PROFINET S2 system redundancy.
Pressure Equipment
Directive
The devices can be ordered with or without a PED approval. If a device with a PED approval is
required, this must be explicitly stated in the order.
• With the identification PED/G1/x (x = category) on the sensor nameplate, Endress+Hauser
confirms conformity with the "Essential Safety Requirements" specified in Appendix I of the
Pressure Equipment Directive 2014/68/EU.
• Devices bearing this marking (PED) are suitable for the following types of medium:
• Media in Group 1 and 2 with a vapor pressure greater than, or smaller and equal
to0.5 bar (7.3 psi)
• Unstable gases
• Devices not bearing this marking (PED) are designed and manufactured according to good
engineering practice. They meet the requirements of Article 4 paragraph 3 of the Pressure
Equipment Directive 2014/68/EU. The range of application is indicated in tables 6 to 9 in Annex II
of the Pressure Equipment Directive 2014/68/EU.
Radio approval
The measuring device has radio approval.
For detailed information regarding radio approval, see Special Documentation → 106
Measuring instrument
approval
The measuring device is (optionally) approved as a gas meter (MI‐002) or component in measuring
systems (MI-005) in service subject to legal metrological control in accordance with the European
Measuring Instruments Directive 2004/22/EC (MID).
The measuring device is qualified to OIML R117 or OIML R137 OIML R117 and has an OIML
Certificate of Conformity (optional).
Additional certificationCRN approval
Some device versions have CRN approval. A CRN-approved process connection with a CSA approval
must be ordered for a CRN-approved device.
Tests and certificates
• EN10204-3.1 material certificate, parts and sensor housing in contact with medium