Intelligent WirelessHART gateway
with Ethernet and RS-485 interface
Application
Fieldgate SWG70 is a gateway for
networks. It enables WirelessHART
cate with each other and manages network security and connectivity. Fieldgate converts and saves the wireless field device data
to a format that is compatible with other systems.
It has Ethernet and serial interfaces to connect to host applications such as SCADA tools.
WirelessHART
field devices to communi-
Your benefits
• Easy commissioning and diagnosis of a self-organized
WirelessHART network
• Seamless integration of field device information into higherorder system applications using standardized protocols such
as MODBUS, EtherNet/IP, HART-IP or OPC
• Wireless configuration and management of smart field
devices in a facility using FieldCare
• Flexible use of Fieldgate in hazardous areas of a facility
Page 2
WirelessHART Fieldgate SWG70
Ethernet
1
2
3
4
4
4
4
4
4
Function and system design
WirelessHARTWirelessHART adds wireless capabilities to the HART protocol, while guaranteeing compatibility with
existing HART devices, commands and tools.
A WirelessHART network comprises:
• WirelessHART field devices
• Wired field devices with a connected WirelessHART Adapter
• Fieldgate
The WirelessHART protocol may not be used to replace the wiring in the case of safety applications
with a control function.
WirelessHART Fieldgate
SWG70
System designThe WirelessHART Fieldgate stores information received from the WirelessHART Adapter SWA70
The WirelessHART Fieldgate SWG70 acts as an interface between the WirelessHART network and a
system that has an Ethernet or RS-485 connection.
The WirelessHART Fieldgate SWG70 supports the following functions:
• Wireless network configuration and management
• Acquisition of data from the field devices and presentation to connected systems
• MODBUS, HART, HART-IP, OPC and EtherNet/IP support for system integration
• Configuration of network, Fieldgate and field devices via Web interface or FDT/DTM.
Fieldgate is designed for installation in hazardous areas Zone 2. You can mount the antenna directly
on the Fieldgate or remotely depending on the requirements of the application.
or other WirelessHART field devices in a buffer which can be accessed by a host application via an
Ethernet or RS-485 connection. The figure shows a Fieldgate operating in a typical meshed WirelessHART network architecture.
2
1Host application
2Ethernet
3 WirelessHART Fieldgate
4 Field devices with WirelessHART
Page 3
WirelessHART Fieldgate SWG70
Input
Communication interfaceWirelessHART communication interface (IEC 62591)
Transmission rateNominal 250 kbits/s
Transmission range2.4 GHz (ISM band)
RangeUp to 250 m outdoors, up to 50 m indoors
Transmission powerConfigurable to 0 dBm or 10 dBm, for adapting to national regulations
Input variables• Process variables according to HART standard are sent to the network by the field devices in the
burst mode.
• Up to 250 WirelessHART-based devices can be connected.
Output
Overview of versions and
protocols
All Fieldgate SWG70 versions feature an Ethernet interface and a serial interface. Depending on the
device version, this interface can support different protocols.
Fieldgate
SWG70 version
SWG70-xx-1
Modbus
SWG70-xx-2
MODBUS + OPC
SWG70-xx-3
EtherNet/IP
1) For OPC, there is an OPC DA server. The software is included in the scope of delivery and must be installed on
a Windows PC.
InterfaceProtocol
MODBUSEtherNet/IPHART-IPAMS
EthernetX–XX
Serial (RS-485)X–X–
EthernetX–XX
1)
Serial (RS-485)X–X–
Ethernet–XXX
Serial (RS-485)––X–
Ethernet (via MODBUS-TCP or OPC)
Communication interfacesConfigurable for HART-IP and MODBUS-TCP communication
Transmission rate100 Mbit/s (max. cable length 100 m at 25 °C ambient temperature)
Type of protectionNone
Maximum bus length100 m (110 yds) depending upon cable
Connection facilitiesM12 connector
RS-485 serial interface
Communication interfacesConfigurable for HART Version 7.0 or MODBUS RTU communication
WirelessHART Fieldgate SWG70
Transmission rateHardware or software configurable between 1200 Bit/s to 115200 Bit/s
Type of protectionNone
Galvanic isolationFully isolated from all other circuits
Maximum bus length1200 m (1230 yds), depending upon cable and transmission rate
Terminal resistorIntegrated, settable by hardware (DIP-switch) or software
Connection facilities
• Two 3-port terminal blocks, allowing series connection of several Fieldgates
• Screw terminals: 0.2 mm2 to 4 mm2 for solid wire and 0.2 mm2 to 2.5 mm2 for stranded wires
Power supply
Power supply20 VDC to 30 VDC SELV / PELV
Power<5 W
Connection facilities• Two 2-port terminal blocks, 2nd port for redundant power supply
• Screw terminals: 0.2 mm
2
to 4 mm2 for solid wire, 0.2 mm2 to 2.5 mm2 for stranded wires
4
Page 5
WirelessHART Fieldgate SWG70
Operating conditions
Application rangeThe Fieldgate SWG70 serves as a gateway for WirelessHART networks.
The WirelessHART protocol may not be used to replace the wiring in the case of safety applications
with a control function.
Installation conditions
Installation instructions
Location:Avoid mounting the WirelessHART Fieldgate near a pipe or high-voltage equipment
wherever possible.
Where possible, the WirelessHART Fieldgate should be in radio contact with at least
20 % of all wireless field devices
Under typical conditions, the maximum spacing is 250 m outdoors and 50 m indoors.
Installation:A remote antenna can be mounted outside a cabinet.
Orientation:With vertical antenna.
Protection
against
lightning:
Hazardous
area:
If there is a risk of lightning, install suitable antenna accessories. See “Accessories” on
page 7.
Connect the protective ground to the protective ground connection of the Fieldgate
housing. The minimum cross-section of the protective ground is 2.5 mm
Fieldgates with the appropriate certification (see ordering information) can be
mounted in Zone 2.
The housing cover can be removed in Zone 2 to view the LEDs. It is not permitted to
operate any switches in an explosive atmosphere.
Environment
Ambient temperature range–20 °C to +60 °C (–4 °F to 140 °F)
Storage temperature–40 °C to +85 °C (–40 °F to +185 °F)
Relative humidity5% to 95%, non-condensing
or adapters.
2
.
Vibration resistanceEN 60068-2-6: 10 Hz ≤ f ≤ 150 Hz/1g
Shock resistanceEN 60068-2-27: 15 g, 11 ms
Electromagnetic
compatibility
The WirelessHART Fieldgate meets EU Directive 2004/108/EC "Electromagnetic compatibility"
• EN 61326:
– Interference immunity: EN 61326-1, 2006, Industry
– Interference emission: EN 61326-1, 2006, Class A
5
Page 6
Overall dimensions
228 (8.98)
257 (10.12)
57 (2.24)
From center
to center
240 - 250
(9.45 - 9.84)
115 (4.53)
20 (0.79)
150 (5.91)
52 (2.05)
85 (3.35)
10 (0.39)
52 (2.05)
85 (3.35)
228 (8.98)
257 (10.12)
mm (inch)
150 (5.91)
115 (4.53)
20 (0.79)
WirelessHART Fieldgate SWG70
Mechanical Construction
WeightApprox. 1.6 kg
Housing• Material: Painted aluminum
• Color: Light gray, RAL 7035
Degree of protectionIP 66 / IP 67
Antenna• Omnidirectional dipole antenna
• Remote antennas: See “Accessories” on page 7.
Operation
Configuration• Web browser via Ethernet
• FieldCare via Ethernet (HART IP CommDTM) or RS-485 (serial CommDTM)
Operating elements• 2x Pushbuttons within housing for selecting operating mode during local configuration
• 5x LEDs within housing for indicating current operating mode during local configuration
• 1x 8-position DIP switch for HART device address (1 to 4),
IP address• Configurable via Web browser or DTM, default 192.168.1.1
Configurable functions• Wireless network
baudrate of RS485 interface (5 to 6), terminating resistor (7) and security mode (8)
hardware settings can be overwritten by software settings.
• The EtherNet/IP version of Fieldgate uses DHCP to assign the IP address
• HART, MODBUS and Ethernet communication interfaces
6
Page 7
WirelessHART Fieldgate SWG70
Gain (< max. gain)
Antenna gain - losses of cables and surge arrester
1
5
3
2
3
4
Diagnosis• Display of wireless field device list with process values of selected field device
• Display of wireless field device list with burst message identification of selected field device
• Network monitoring of wireless communication events
• Diagnostic function
Accessories
Antenna accessoriesNote the following when selecting accessories for the antenna:
• The Ex approval for Fieldgate SWG70 is only valid for the 2 dBi antenna supplied.
• The antenna must comply with the rules for the usage of 2.4 GHz equipment that apply in the
country of installation. In case of doubt, please contact a regional expert for radio approvals.
• The gain is calculated from the difference in the antenna gain and the losses of the individual
components such as the cables and surge arrester. The gain may not exceed the 2 dBi limit.
• The WirelessHART range of the Fieldgate SWG70 depends on the coaxial cable used (attenuation)
between the Fieldgate and the antenna.
Fig. 1: Calculating the maximum gain of a remote antenna
Kit incl. coaxial adapter
71131509Coaxial cable 2.5 m3–0.5 dB
71131508Coaxial cable 5 m3–1.1 dB
71131507Coaxial cable 10 m3–2.1 dB
71131506Coaxial cable 15 m3–3.2 dB
71131505Surge arrester (protection against lightning) 4–0.2 dB
4 Surge arrester,
5 Fieldgate SWG70
1 and 28.5 dBi–
1 and 26.0 dBi–
1 and 26.0 dBi–
λ/4, without mechanical fixing
(Gain)
Loss
(attenuation)
7
Page 8
WirelessHART Fieldgate SWG70
Ordering information
Product structureDetailed information about the product structure is available:
• On the Endress+Hauser website: www.endress.com/SWG70
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Accessories• Remote antennas and antenna accessories: See “Accessories” on page 7.
• Additional accessories on request
Documentation
WirelessHART Fieldgate
SWG70
WirelessHART Fieldgate SWG70
Operating Instructions BA00064S/04/en
WirelessHART Fieldgate SWG70
Safety Instructions ATEX /IECEx
Wireless Adapter and Fieldgate
Competence Brochure CP00013S/04/en
WirelessHART Adapter SWA70
Operating Instructions BA00061S/04/en
XA00001S/04/a3
WirelessHART-Fieldgate SWG70
Control Drawing
XA01565S/04/en
Certificates and Approvals
CE MarkThe WirelessHART Fieldgate SWG70 meets the legal requirements of the relevant EU directives.
Endress+Hauser confirms successful testing of the WirelessHART Fieldgate SWG70 by affixing to it
the CE mark.
Hazardous area approvalsSee the "Documentation" section.
IT security
Ethernet interfaceThe Fieldgate SWG70 is equipped with security mechanisms to protect it against any inadvertent
changes to the device settings. Additional IT security measures in line with operators' security standards and designed to provide additional protection for the device and device data transfer must be
implemented by the operators themselves.
If network firewalls are used, the following TCP/IP ports must be specifically open:
PortServiceUseAccess to
67/UDP,
68/UDP
53/UDP,
53/TCP
443/TCPServerHTTPS over SSL: Web server –
502/TCPServerSystem integration via MODBUS/
5094/TCP
5094/UDP
33333ServerAMS system integration Fieldgate and WirelessHART devices
44818/TCP,
2222/UDP
ClientIP address assignment via DHCPFieldgate IP address (write)
ClientDNS: name resolution
Fieldgate (read and write),
Fieldgate configuration
TCP
ServerOperation via DTM and OPC server
system integration via HART-IP
ServerSystem integration via EtherNet/IP Fieldgate and WirelessHART devices
• Japan: Ministry of internal affairs and communication
• Mexico: COFETEL RCEPNSW12-0651
• Other national certificates are available on request.
Additional national guidelines to be observed:
CountryGuideline
BulgariaGeneral authorization required for outdoor use and public service
ItalyIf used outside of own premises, general authorization is required.
NorwayMay be restricted in the geographical area within a 20 km radius from the center
RomaniaUse on a secondary basis. Individual license required
LatviaThe outdoor usage of the 2.4 GHz band requires an authorization from the
of Ny-Alesund.
Electronic Communications Office.
EuropeThis device complies with the requirements of the EC Radio Equipment Directive 2014/53/EU.
• ETSI EN 300 328: V1.8.1:2012
USA and CanadaThis device complies with part 15 of the FCC Rules.
This device complies with CFR 47, Part 15 of the FCC Rules. The operation of this device is subject to
the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
“Este produto está homologado pela ANATEL, de acordo com os procedimentos regulamentados pela
Resolução 242/2000, e atende aos requisitos técnicos aplicados.”
Para maiores informações, consulte o site da ANATEL www.anatel.gov.br
WirelessHART Fieldgate SWG70
ChineseThis device has been granted a type approval by the SRRC (State Radio Regulatory Commission of P. R.
China): CMIIT ID 2011DJ5309
JapaneseThis device has been granted a designation number by the Japanese Ministry of Internal Affairs and
Communications according to the Ordinance concerning Technical Regulations Conformity Certification etc. of Specified Radio Equipment ( )
• Article 2 clause 1 item 19
• Approval n°: 202WW09117712
This device should not be modified (otherwise the granted designation number will be invalid).
MexicoCOFETEL Approval No.: RCPENSW12-0651
La operación de este equipo está sujeta a las siguientes dos condiciones:
(1) es posible que este equipo o dispositivo no cause interferencia perjudicial y (2) este equipo o dispositivo debe aceptar cualquier interferencia, incluyendo la que pueda causar su operación no deseada.
10
Page 11
WirelessHART Fieldgate SWG70
11
Page 12
WirelessHART Fieldgate SWG70
www.addresses.endress.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.