WirelessHART Fieldgate SWG70
Intelligent WirelessHART gateway with Ethernet and RS-485 interface
Application
WirelessHART
field devices to communi-
Your benefits
• Easy commissioning and diagnosis of a self-organized WirelessHART network
• Seamless integration of field device information into higher­order system applications using standardized protocols such as MODBUS, EtherNet/IP, HART-IP or OPC
• Wireless configuration and management of smart field devices in a facility using FieldCare
• Flexible use of Fieldgate in hazardous areas of a facility

WirelessHART Fieldgate SWG70

Ethernet
1
2
3
4
4
4
4
4
4

Function and system design

WirelessHART WirelessHART adds wireless capabilities to the HART protocol, while guaranteeing compatibility with

existing HART devices, commands and tools.
A WirelessHART network comprises:
• WirelessHART field devices
• Wired field devices with a connected WirelessHART Adapter
• Fieldgate
The WirelessHART protocol may not be used to replace the wiring in the case of safety applications with a control function.
WirelessHART Fieldgate SWG70

System design The WirelessHART Fieldgate stores information received from the WirelessHART Adapter SWA70

The WirelessHART Fieldgate SWG70 acts as an interface between the WirelessHART network and a system that has an Ethernet or RS-485 connection.
The WirelessHART Fieldgate SWG70 supports the following functions:
• Wireless network configuration and management
• Acquisition of data from the field devices and presentation to connected systems
• MODBUS, HART, HART-IP, OPC and EtherNet/IP support for system integration
• Configuration of network, Fieldgate and field devices via Web interface or FDT/DTM.
Fieldgate is designed for installation in hazardous areas Zone 2. You can mount the antenna directly on the Fieldgate or remotely depending on the requirements of the application.
or other WirelessHART field devices in a buffer which can be accessed by a host application via an Ethernet or RS-485 connection. The figure shows a Fieldgate operating in a typical meshed Wire­lessHART network architecture.
2
1Host application 2Ethernet
3 WirelessHART Fieldgate 4 Field devices with WirelessHART
WirelessHART Fieldgate SWG70

Input

Communication interface WirelessHART communication interface (IEC 62591)

Transmission rate Nominal 250 kbits/s

Transmission range 2.4 GHz (ISM band)

Range Up to 250 m outdoors, up to 50 m indoors

Transmission power Configurable to 0 dBm or 10 dBm, for adapting to national regulations

Input variables • Process variables according to HART standard are sent to the network by the field devices in the

burst mode.
• Up to 250 WirelessHART-based devices can be connected.

Output

Overview of versions and protocols

All Fieldgate SWG70 versions feature an Ethernet interface and a serial interface. Depending on the device version, this interface can support different protocols.
Fieldgate SWG70 version
SWG70-xx-1 Modbus
SWG70-xx-2 MODBUS + OPC
SWG70-xx-3 EtherNet/IP
1) For OPC, there is an OPC DA server. The software is included in the scope of delivery and must be installed on a Windows PC.
Interface Protocol
MODBUS EtherNet/IP HART-IP AMS
Ethernet X X X Serial (RS-485) X X – Ethernet X X X
1)
Serial (RS-485) X X – Ethernet X X X Serial (RS-485) X

Ethernet (via MODBUS-TCP or OPC)

Communication interfaces Configurable for HART-IP and MODBUS-TCP communication

Protocols HART-IP, MODBUS-TCP and also OPC server

Physical layer Ethernet 10 BASE-T/100 BASE-TX, complete galvanic isolation

Transmission rate 100 Mbit/s (max. cable length 100 m at 25 °C ambient temperature)

Type of protection None

Maximum bus length 100 m (110 yds) depending upon cable

Connection facilities • 7-port terminal block

• Screw terminals: 0.2 mm
2
to 4 mm2 for solid wire and 0.2 mm2 to 2.5 mm2 for stranded wires
3

Ethernet (via EtherNet/IP)

Communication interfaces Configurable for HART-IP and EtherNet/IP communication

Protocols HART-IP and EtherNet/IP

Physical layer Ethernet 10 BASE-T/100 BASE-TX, complete galvanic isolation

Transmission rate 100 Mbit/s (max. cable length 100 m at 25 °C ambient temperature)

Type of protection None

Maximum bus length 100 m (110 yds) depending upon cable

Connection facilities M12 connector

RS-485 serial interface

Communication interfaces Configurable for HART Version 7.0 or MODBUS RTU communication

WirelessHART Fieldgate SWG70

Transmission rate Hardware or software configurable between 1200 Bit/s to 115200 Bit/s

Type of protection None

Galvanic isolation Fully isolated from all other circuits

Maximum bus length 1200 m (1230 yds), depending upon cable and transmission rate

Terminal resistor Integrated, settable by hardware (DIP-switch) or software Connection facilities

• Two 3-port terminal blocks, allowing series connection of several Fieldgates
• Screw terminals: 0.2 mm2 to 4 mm2 for solid wire and 0.2 mm2 to 2.5 mm2 for stranded wires

Power supply

Power supply 20 VDC to 30 VDC SELV / PELV

Power <5 W

Connection facilities • Two 2-port terminal blocks, 2nd port for redundant power supply

• Screw terminals: 0.2 mm
2
to 4 mm2 for solid wire, 0.2 mm2 to 2.5 mm2 for stranded wires
4