Endress+Hauser WirelessHART Adapter SWA70 Specifications

Page 1
TI00026S/04/EN/22.17 71396550
Products Solutions Services
Technical Information
WirelessHART Adapter SWA70
Smart WirelessHART interface module with power supply for field devices
Application
• Process optimization: By connecting the WirelessHART Adapter, it is possible to monitor and optimize plant sections with less cost and effort.
• Level monitoring in tanks and silos: Measured values together with the device and battery status are transmitted at regular intervals to a higher-level system.
• Plant condition monitoring: Wireless devices are mounted at critical points in the plant which are not normally connected to the control room due to their limited accessibility or wiring costs. Improved data flow and diagnostics increase plant reliability and safety.
Your benefits
The flexible adapter concept offers the following advantages:
• HART devices are quickly upgraded to WirelessHART technology
• Fast integration of 4 to 20 mA field devices into a WirelessHART network
• One 4 to 20 mA field device and up to four HART field devices in multidrop mode can be connected to a WirelessHART Adapter
• Burst mode and event notification supported
• Remote and difficult-to-access HART devices are connected to the control room without expensive cabling
• Easy planning, quick installation and integration
Page 2

WirelessHART Adapter SWA70

Function and system design

WirelessHART WirelessHART adds wireless capabilities to the HART protocol, while ensuring compatibility with

existing HART devices, commands and tools. A WirelessHART network comprises:
• Wireless field devices
• Wired field devices with a connected WirelessHART Adapter
• Gateways responsible for communication between devices and host applications
• Network and Safety Manager responsible for configuring, managing and monitoring the network
The WirelessHART protocol may not be used to replace the wiring in the case of safety applications with a control function.
WirelessHART Adapter SWA70

System design The WirelessHART Adapter SWA70 transmits information to a host application via a WirelessHART

The WirelessHART Adapter SWA70 acts as an add-on interface for wireless communication with HART field devices or 4 to 20 mA field devices. It is powered by either a battery pack, a wide range power unit or a DC power unit. The DC power unit can use solar power, for example. A special long-life, high-power battery is used as the battery.
The WirelessHART Adapter SWA70 supports the following functions:
• Power supply for a HART field device or a 4 to 20 mA field device
• Power supply of up to four HART devices in the multidrop mode with a wide range power unit
• Connection of up to four externally powered HART field devices in the multidrop mode
• Scaling of the current signal from a connected 4 to 20 mA field device
• Burst mode and event notification for the WirelessHART Adapter and the connected field devices
Fieldgate. The figure below shows a typical WirelessHART network architecture.
Ethernet
2
Page 3
WirelessHART Adapter SWA70

Inputs (wired interface)

Inputs

One input channel for: • One point-to-point connection with a HART field device or
• One point-to-point connection with a 4-20 mA field device or
• Up to four HART field devices connected in multidrop mode if a wide range power unit is used. The wide range power unit provides 24 V to power the field devices.

Communication interface • HART interface to configure the WirelessHART Adapter with a HART modem

• LPI interface (internal interface for the manufacturing and diagnosis)

Protocol version HART Version 7.3 (backwards compatible with earlier HART versions)

Transmission rate 1200 bits/s

Field device power supply

Current: 4 to 20 mA (according to NAMUR recommendation NE 43) or 4 mA if
only one field device is connected in multidrop mode
3.6 mA or I 21 mA
Error current:
I Protection: Short-circuit protection, triggered if currents > 25 mA Terminal voltage: 8 to 23 V DC, configurable
Connection of externally powered devices on
max. permissible input current terminals 2...6: 100 mA max. permissible input voltage terminals 2...6: 30 V DC
terminals 2...6
Only the connection of power supply units of the protection class II is permissible.

Terminals The WirelessHART Adapter has a terminal block with screw terminals 1-6 and 2 eyelets 7 and 8 for

connection purposes.
Schleifenstrom-
Application Terminal
assignment
Power supply to a loop­powered field device
Integration of the WirelessHART Adapter into a current loop
Integration of the WirelessHART Adapter into a current loop
1 (+) and 2 (–) • Current measurement
2 (+) and 3 (–) • Current measurement
5 and 6 • Integration into HART
messung und HART­Kommunikation
123 4
Remarks Connection values
• Loop current flows
• Loop current flows
• Loop current does not
HART­Kommunikation
7
8
5
6
and HART communica­tion where applicable
through the adapter
and HART communica­tion where applicable
through the adapter
communication
flow through the adapter
Schleifen­strommessung 1 – 2
Schleifen­strommessung 2 – 3
• 4 to 20 mA (according to NAMUR NE43)
• 8-23 V power supply for field device, configurable, see the following diagram
•Integrated load: 250Ohm
• 4 to 20 mA (according to NAMUR NE43)
•Integrated load: 250Ohm
• Input impedance for HART communication: > 10 kOhm at 1700 Hz
• DC input impedance: 1 MOhm
3
Page 4
WirelessHART Adapter SWA70
12
14
16
18
20
22
24
Field device power supply [V]
Loop current [mA]
04812
16
20
1
2
3

Field device power supply through SWA70

Application Terminal
assignment
Configuration of the WirelessHART Adapter with a HART modem
7 and 8 Temporary connection of
Remarks Connection values
• Input impedance for
the modem via eyelets
HART communication: > 10 kOhm at 1700 Hz
• DC input impedance: > 1 MOhm
1 SWA70 non-Ex versions with 4 to 20 mA field device 2 SWA70 non-Ex versions with HART field device 3 SWA70 Ex versions with HART field device or 4 to 20 mA field device

Output (wireless interface)

Communication interface WirelessHART communication interface (IEC 62591),

HART version 7.3 (backwards compatible with earlier HART versions)

Transmission rate Nominal 250 kBits/s

Operating frequency 2.4 GHz (ISM band)

Range Up to 250 m outdoors, up to 50 m indoors

Transmission power Can be configured for 0 dBm or 10 dBm to adapt to national regulations

Device variables Up to 10 bursts can be configured in accordance with the HART specification. Up to eight device

variables per burst can be configured depending on user transmission requirements.

Additional functions • Event notification, configurable for up to eight variables from the WirelessHART adapter and/or

Example:
• HART field device: device variables
• 4 to 20 mA field device: scaled or linearized process values
• WirelessHART Adapter: scaled loop current and other variables, choose from: estimated battery life, battery voltage, energy used, adapter temperature
connected field devices
• Error notification and scaling or linearization of the 4 to 20 mA signal of the connected analog field
device
• Monitoring of energy consumption
• Locking of device parameterization
4
Page 5
WirelessHART Adapter SWA70

Diagnostics Diagnostics function in accordance with NAMUR NE 107, ASM and HART recommendations

Power supply

Versions • Battery unit BU 191: special long-life high-power lithium-thionyl chloride battery unit

• Wide range power unit
• DC power unit, e.g. solar-powered

Power supply • Wide range power unit: 24 V to 230 V AC/DC ± 10 %, 50/60 Hz

•DC power unit: 8 to 50VDC In the event of an external power supply failure, wireless communication is maintained for at least one hour thanks to an internal power supply system.

Current consumption • Wide range power unit: <350 mA, 1 A slow-blow back-up fuse must be installed by the customer

onsite
• DC power unit: < 250 mA, 1 A slow-blow back-up fuse must be installed by the customer onsite

Power consumption • Wide range power unit: max. active power 7 W / max. reactive power 12 VA with alternating voltage

• DC power unit: < 2.2 W

Battery capacity • 19 Ah nominal capacity at 20 °C

•7.2 V DC
• Lithium metal content: 10 g

Battery life Up to 10 years, depending on update rate of process variables, field device type and environmental

conditions

Cable Field device connection

• Mounted directly on field devices: cable supplied (0.25 mm
• Remote mounting: standard installation cable (0.25 mm2)
Wide range power unit or DC power unit (M12 socket): 0.75 mm
2
)
2

Performance characteristics

Reference operating conditions

Maximum measured error 4 to 20 mA circuit: 0.125 % of measuring range

Influence of ambient temperature

According to IEC 61298 Part 2
4 to 20 mA circuit: 5 μA/10 K
5
Page 6
WirelessHART Adapter SWA70

Operating conditions

Application range The WirelessHART adapter SWA70 is a smart wireless module designed for the wireless transmission

of 4 to 20 mA HART signals from connected field devices to a WirelessHART Fieldgate SWG70.
The WirelessHART protocol may not be used to replace the wiring in the case of safety applications with a control function.

Installation conditions

Installation • Directly on field device

• Remotely on a wall or pipe using optional mounting bracket

Installation instructions (recommendations)

Protection against lightning • Do not mount the WirelessHART Adapter at the highest point in the plant.

• Consider the range. See Seite 4, Range.
• Avoid mounting too near walls, pipes and heavy-duty electrical equipment.
• Mount in line of sight with a neighboring adapter and Fieldgate.
• Consider the development of the Fresnel zone.
• Align antenna so that it is completely vertical.
• WirelessHART Adapter with metal housing: connect protective ground to protective ground
connection of the housing. Protective ground in 2.5 mm
2
.

Environment

Climate class EN 60721-3-4: 4K4H, suitable for stationary use at unprotected outdoor locations

Ambient temperature range • –40 to +80 °C (–40 to +176 °F)

• Ex versions –40 to +60 °C (–40 to +146 °F) for temperature class T3
• Ex versions –40 to+50 °C (–40 to+122 °F) for temperature class T4
• The battery pack capacity decreases significantly at temperatures below –30 °C (–22 °F).

Storage temperature • WirelessHART Adapter without battery unit: –40 to +85 °C (–40 to +185 °F)

• WirelessHART Adapter with disconnected battery unit: –40 to +25 °C (–40 to +77 °F)
• Battery unit BU 191: –40 to +25 °C (–40 to +77 °F)

Vibration resistance EN 60068-2-64: 20 Hz f 2000 Hz: 0.01 g²/Hz

Shock resistance EN 60068-2-27: 15 g, 11 ms

Electromagnetic compatibility

All modules are suitable for industrial use and meet the requirements of EU Directive 2014/30/EU "Electromagnetic compatibility":
• Emission:
• With wide range power unit: EN 61326-1: 2013, Class A
• With DC power unit or battery unit: EN 61326-1: 2013, Class B
• Interference immunity:
• EN 61326-1: 2013 Tab. 2 (industry)
• Namur recommendation EMC (NE21)
6
Page 7
WirelessHART Adapter SWA70

Temperature restrictions

The temperature restrictions listed are based on the assumption that more than 30% battery capacity is remaining.

Ex version, 4 to 20 mA supply mode

Ex version with fixed current of 4 mA (multidrop mode)

The application range is limited in the event of high measuring currents close to 22 mA.
Current strength in mA
422 8 –40°C –30°C 10 –40°C –30°C 12 –40°C –30°C 14 –40°C –25°C 16 –40°C –25°C 18 –40°C 20 –40°C 22 –40°C
Terminal voltage of
field device in V
Start-up current in mA See Operating Instructions, "Field device power supply" section.
4 6 8 10121416182022 8 –40°C –40°C –40°C –40°C –40°C –40°C –40°C –35°C –25°C –15°C 10 –40°C –40°C –40°C –40°C –40°C –40°C –40°C –30°C –15°C –10°C 12 –40°C –40°C –40°C –40°C –40°C –40°C –35°C –20°C 14 –40°C –40°C –40°C –40°C –40°C –35°C –25°C –10°C 16 –40°C –40°C –40°C –40°C –40°C –25°C 18 –40°C –40°C –40°C –30°C –5°C 20 –40°C –35°C 22
Terminal voltage of
field device in V

Non-Ex version, 4 to 20 mA supply mode

The application range is limited in the event of high measuring currents close to 22 mA.
Current strength in mA
422 8 –40°C –30°C 10 –40°C –30°C 12 –40°C –30°C 14 –40°C –25°C 16 –40°C –25°C 18 –40°C 20 –40°C 22 –40°C
Terminal voltage of
field device in V
7
Page 8
Non-Ex version with fixed
189.9
26.1
92
111.5
Dimensions in mm
25.4 mm = 1 inch
32.1
24.9
184.4
139.7
21.9
92.8
89.5
Cable entry for
direct installation,
internal thread
M20x1.5
Cable entry for
remote installation,
internal thread M20x1.5
current of 4 mA (multidrop mode)

Design/dimensions

Start-up current in mA See Operating Instructions, "Field device power supply" section.
4 6 8 10121416182022 8 –40°C –40°C –40°C –40°C –40°C –40°C –40°C –40°C –40°C –40°C 10 –40°C –40°C –40°C –40°C –40°C –40°C –40°C –40°C –40°C –35°C 12 –40°C –40°C –40°C –40°C –40°C –40°C –40°C –40°C –40°C –35°C 14 –40°C –40°C –40°C –40°C –40°C –40°C –40°C –35°C –35°C –35°C 16 –40°C –40°C –40°C –40°C –40°C –40°C –40°C –35°C –20°C 18 –40°C –40°C –40°C –40°C –40°C –40°C –40°C –35°C 20 –40°C –40°C –40°C –40°C –40°C –35°C 22 –40°C –40°C –40°C
Terminal voltage of
field device in V

Mechanical construction

WirelessHART Adapter SWA70

Weight • Polyester housing with power supply unit: 0.785 kg

• Aluminum housing with power supply unit: 0.9 kg
• AISI 316L housing with power supply unit: 1.9 kg

Materials • Housing: polyester or aluminum or AISI 316L, see ordering information

• Color of polyester and aluminum: light-gray, RAL 7035 with blue logo

Degree of protection • Polyester housing F32: IP65/IP66; NEMA Type 4

Connection adapters M20x1.5 to M20x1.5; M20x1.5 to G 1/2; M20x1.5 to NPT 1/2; M20x1.5 to NPT 3/4

Antenna Omnidirectional dipole antenna

8
• Aluminum housing F33: IP67, NEMA Type 4X
• AISI 316L housing F39: IP66/IP67, NEMA Type 4X
See ordering information
Page 9

WirelessHART Adapter SWA70

Operation

Configuration • Local configuration with FieldCare or DeviceCare via modem and DTM for SWA70

• Local operation with FieldXpert also in the hazardous area
• Remote configuration with FieldCare via WirelessHART Fieldgate SWG70 and DTM for SWA70 and SWG70
• Remote configuration with a software and a gateway based on the device description (DTM or DD)

Display and operating elements

Device address Can be configured between 0 to 63 via DD or DTM, default address 15

Display and operating elements in WirelessHART Adapter:
• Push buttons for selecting various functions
• LEDs for indicating communication status, battery status, voltage level and error messages

Ordering information

Product structure Detailed information about the product structure is available:

• In the Product Configurator on the Endress+Hauser website: www.endress.com Enter "SWA70" as the search string click the "WirelessHART Adapter SWA70" link In the window on the right under "Device support", click the link "Configure your selected product"
• From your Endress+Hauser Sales Center: www.addresses.endress.com

Documentation

WirelessHART Adapter SWA70
WirelessHART Adapter SWA70
Operating Instructions BA00061S
WirelessHART Adapter SWA70
Safety Instructions ATEX, IECEx XA01366F
WirelessHART Adapter SWA70
Safety Instructions CSA XA00538F
WirelessHART solutions
for real-world applications Competence brochure CP00013S
WirelessHART Fieldgate SWG70
Operating Instructions BA00064S
WirelessHART-Adapter SWA70
Safety Instructions EAC Ex XA01505F-A

Certificates and approvals

CE mark The WirelessHART Adapter SWA70 meets the legal requirements of the relevant EU Directives.

Endress+Hauser confirms successful testing of the WirelessHART Adapter SWA70 by affixing to it the CE mark.

Ex approval See "Documentation" section.

9
Page 10
WirelessHART Adapter SWA70
R
/6)

Radio approvals

Europe This device meets the requirements of the RED "Radio Equipment Directive" 2014/53/EU.

USA and Canada FCC ID: 2AIKP-SWA70A

IC: 21533-SWA70A
This device has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the device is operated in a commercial environment. This device generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this device in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Changes or modifications made to this device not expressly approved by Endress+Hauser may void the FCC authorization to operate this device. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.
This device complies with Part 15 of the FCC Rules and with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:
• this device may not cause harmful interference, and
• this device must accept any interference received, including interference that may cause undesired operation.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes:
• l'appareil ne doit pas produire de brouillage, et
• l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

Brazil “Este equipamento opera em caráter secundário, isto é, não tem direito a proteção contra interferência

prejudicial, mesmo de estações do mesmo tipo, e não pode causar interferência a sistemas operando em caráter primário”. Para maiores informações, consulte o site da ANATEL www.anatel.gov.br
Modello SWA70

Japan This device is granted pursuant to the Japanese Radio Law ( 電波法 )

This device should not be modified (otherwise the granted designation number will become invalid)

Mexico La operación de este equipo está sujeta a las siguientes dos condiciones:

(1) es posible que este equipo o dispositivo no cause interferencia perjudicial y (2) este equipo o dispositivo debe aceptar cualquier interferencia, incluyendo la que pueda causar su operación no deseada.
IFETEL: RCPENSW17-0342 NOM: 1702CE03608 (wide range power supply)
10
Page 11
WirelessHART Adapter SWA70

Other approvals Other national approvals are available on request

Country Approval/Guideline
Bulgaria General authorization required for the use outdoors and in public. Italy General authorization necessary for the use outside of private terrain. Norway The operation can be restricted within a radius of 20 km from the center
of Ny-Alesund. Romania In case of operation as secondary device; a special license is required. Latvia The outdoor use of the transmission frequency band of 2,4 GHz requires
a national approval.
11
Page 12
WirelessHART Adapter SWA70
www.addresses.endress.com
Loading...