• Make sure the document is stored in a safe place such that it is always available when
working on or with the device.
• To avoid danger to individuals or the facility, read the "Basic safety instructions" section
carefully, as well as all other safety instructions in the document that are specific to
working procedures.
• The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser distributor will supply you with current information and updates to
these Instructions.
A0023555
2Endress+Hauser
Page 3
Waterpilot FMX21Table of contents
Table of contents
1Document information .............. 5
1.1Document function ..................... 5
1.2Symbols used .......................... 5
1.3Documentation ........................ 6
1.4Terms and abbreviations ................. 7
2Basic safety instructions ............ 8
2.1Requirements concerning the staff .......... 8
2.2Designated use ........................ 8
2.3Workplace safety ....................... 8
2.4Operational safety ...................... 8
2.5Product safety ......................... 9
3Product description ................ 10
3.1Function ............................ 10
4Incoming acceptance and product
identification ..................... 11
4.1Incoming acceptance ................... 11
4.2Product identification ................... 12
4.3Nameplates .......................... 13
4.4Identification of sensor type .............. 14
4.5Storage and transport .................. 14
4.6Scope of delivery ...................... 14
5Installation ....................... 16
5.1Installation conditions .................. 16
5.2Additional mounting instructions .......... 17
5.3Dimensions .......................... 17
5.4Mounting the Waterpilot with a mounting
clamp .............................. 18
5.5Mounting the Waterpilot with a cable
mounting screw ....................... 19
5.6Mounting the terminal box .............. 20
5.7Mounting the TMT182 temperature head
transmitter with terminal box ............ 20
5.8Mounting the terminal strip for the Pt100
passive (without TMT182) ............... 21
5.9Post-installation check .................. 21
7Operation options ................. 32
7.1Overview of operating options ............ 32
7.2Operating concept ..................... 33
7.3Structure of the operating menu ........... 33
7.4Locking/unlocking operation ............. 34
7.5Resetting to factory settings (reset) ........ 35
8
Integrating device via HART
®
protocol .......................... 36
8.1HART process variables and measured
values .............................. 36
8.2Device variables and measured values ....... 37
9Commissioning .................... 38
9.1Post-installation check and function check ... 38
9.2Unlocking/locking configuration .......... 38
9.3Commissioning ....................... 38
9.4Selecting the language .................. 39
9.5Measuring mode selection ............... 39
9.6For selecting the pressure engineering unit ... 40
9.7Position adjustment .................... 40
9.8Configuring the damping ................ 41
9.9Configuring pressure measurement ........ 41
9.10Configuring level measurement ........... 43
9.11Automatic density compensation .......... 56
9.12Linearization ......................... 59
9.13Manual entry of a linearization table via
operating tool ........................ 62
9.14Backing up or duplicating the device data .... 63
10Diagnostics and troubleshooting ... 64
10.1Troubleshooting ...................... 64
10.2Diagnostic events ...................... 64
10.3Troubleshooting specific to Waterpilot
FMX21 with optional Pt100 .............. 67
10.4Troubleshooting specific to TMT182
temperature head transmitter ............ 68
10.5Response of output to errors .............. 68
10.6Firmware history ...................... 69
6Electrical connection .............. 23
6.1Connecting the device .................. 23
6.2Supply voltage ........................ 25
6.3Cable specifications .................... 25
6.4Power consumption .................... 25
6.5Current consumption ................... 26
6.6Maximum load ....................... 26
6.7Connecting the measuring unit ........... 27
6.8Post-connection check .................. 31
Endress+Hauser3
11Maintenance ...................... 70
11.1Exterior cleaning ...................... 70
12Repairs ........................... 71
12.1General notes ........................ 71
12.2Spare parts .......................... 71
12.3Return .............................. 71
12.4Disposal ............................ 71
Page 4
Table of contentsWaterpilot FMX21
13Overview of the operating menu .... 72
13.1Overview of parameters in the "Expert"
menu .............................. 75
14Description of device parameters ... 80
14.1Expert → System ...................... 80
14.2Expert → System → Instrument info ........ 81
14.3Expert → System → Management .......... 83
14.4Expert → Measurement → Measuring mode .. 83
14.5Expert → Measurement → Basic setup ....... 84
14.6Expert → Measurement → Pressure ........ 86
14.7Expert → Measurement → Level ........... 88
14.8Expert → Measurement → Linearization ..... 93
14.9Expert → Measurement → Sensor limits ..... 96
14.10 Expert → Measurement → Sensor trim ...... 97
14.11 Expert → Output → Current output ......... 98
14.12 Expert→ Communication → HART config. ... 102
14.13 Expert→ Communication → HART info ..... 104
14.14 Expert→ Communication → HART output ... 106
14.15 Expert→ Communication → HART input .... 109
14.16 Expert → Application .................. 111
14.17 Expert → Diagnosis ................... 112
14.18 Expert → Diagnosis → Diagnostic list ....... 114
These Operating Instructions contain all the information that is required in various phases
of the life cycle of the device: from product identification, incoming acceptance and
storage, to mounting, connection, operation and commissioning through to
troubleshooting, maintenance and disposal.
1.2 Symbols used
1.2.1 Safety symbols
SymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.2.2 Electrical symbols
SymbolMeaningSymbolMeaning
Direct currentAlternating current
Direct current and alternating currentGround connection
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
1.2.3 Tool symbols
SymbolMeaning
Flat blade screwdriver
A0011220
Philips screwdriver
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Equipotential connection
A connection that has to be connected
to the plant grounding system: This
may be a potential equalization line
or a star grounding system depending
on national or company codes of
practice.
A0011219
Endress+Hauser5
Page 6
Document informationWaterpilot FMX21
,…,
,…,
SymbolMeaning
Allen key
A0011221
Open-ended wrench
A0011222
1.2.4 Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Series of steps
Result of a step
Help in the event of a problem
Visual inspection
1.2.5 Symbols in graphics
SymbolMeaning
1, 2, 3 ...Item numbers
Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ... Sections
1.3 Documentation
The document types listed are available:
In the Downloads area of the Endress+Hauser website: www.endress.com →
Downloads
1.3.1 Technical Information (TI): planning aid for your device
TI00431P:
The document contains all the technical data on the device and provides an overview of
the accessories and other products that can be ordered for the device.
6Endress+Hauser
Page 7
Waterpilot FMX21Document information
1.3.2 Brief Operating Instructions (KA): getting the 1st measured
value quickly
KA01189P:
The Brief Operating Instructions contain all the essential information from incoming
acceptance to initial commissioning.
1.3.3 Safety Instructions (XA)
Depending on the approval, the following Safety Instructions (XA) are supplied with the
device. They are an integral part of the Operating Instructions.
DirectiveType of protectionCategoryDocumentation Option
ATEXEx ia IICII 2 GXA00454PBD
ATEXEx nA IICII 3 GXA00485PBE
IECExEx ia IICn/aXA00455PIC
CSA C/USEx ia IICn/aZD00232P
(960008976)
FMAEx ia IICn/aZD00231P
(960008975)
NEPSIEx ia IICn/aXA00456PNA
INMETROEx ia IICn/aXA01066PMA
1)Product Configurator order code for "Approval"
CE
FE
The nameplate indicates the Safety Instructions (XA) that are relevant to the device.
1.4 Terms and abbreviations
Term/abbreviationExplanation
XADocument type "Safety Instructions"
KADocument type "Brief Operating Instructions"
BADocument type "Operating Instructions"
SDDocument type "Special Documentation"
1)
TDTurn down
Set span and zero-based span.
Endress+Hauser7
Page 8
Basic safety instructionsWaterpilot FMX21
2 Basic safety instructions
2.1 Requirements concerning the staff
The personnel for installation, commissioning, diagnostics and maintenance must fulfill
the following requirements:
Trained, qualified specialists: must have a relevant qualification for this specific
‣
function and task
Are authorized by the plant owner/operator
‣
Are familiar with federal/national regulations
‣
Before beginning work, the specialist staff must have read and understood the
‣
instructions in the Operating Instructions and supplementary documentation as well as
in the certificates (depending on the application)
Following instructions and basic conditions
‣
The operating personnel must fulfill the following requirements:
Being instructed and authorized according to the requirements of the task by the
‣
facility's owner-operator
Following the instructions in these Operating Instructions
‣
2.2 Designated use
2.2.1 Application and media
The Waterpilot FMX21 is a hydrostatic pressure sensor for measuring the level of fresh
water, wastewater and salt water. The temperature is measured simultaneously in the case
of sensor versions with a Pt100 resistance thermometer. An optional temperature head
transmitter converts the Pt100 signal to a 4 to 20 mA signal with superimposed digital
communication protocol HART 6.0.
2.2.2 Incorrect use
The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance
‣
in verifying the corrosion resistance of fluid-wetted materials, but does not accept any
warranty or liability.
2.3 Workplace safety
For work on and with the device:
Wear the required personal protective equipment according to federal/national
‣
regulations.
Switch off the supply voltage before connecting the device.
‣
2.4 Operational safety
Risk of injury!
Operate the device in proper technical condition and fail-safe condition only.
‣
The operator is responsible for interference-free operation of the device.
‣
8Endress+Hauser
Page 9
Waterpilot FMX21Basic safety instructions
Modifications to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
If, despite this, modifications are required, consult with Endress+Hauser.
‣
Repairs
To ensure continued operational safety and reliability,
Carry out repairs on the device only if they are expressly permitted.
‣
Observe federal/national regulations pertaining to repair of an electrical device.
‣
Use original spare parts and accessories from Endress+Hauser only.
‣
Hazardous area
To eliminate danger to persons or the facility when the device is used in the approvalrelated area (e.g. explosion protection, pressure vessel safety):
Check the nameplate to verify if the device ordered can be put to its intended use in the
‣
approval-related area.
Observe the specifications in the separate supplementary documentation that is an
‣
integral part of these Instructions.
2.5 Product safety
This measuring device is designed in accordance with good engineering practice to meet
state-of-the-art safety requirements, has been tested, and left the factory in a condition in
which it is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EC
directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser
confirms this by affixing the CE mark to the device.
Endress+Hauser9
Page 10
Product descriptionWaterpilot FMX21
h
2
1
p
atm
p
hydr.
p = p + p
atmhydr.
p
atm
p
atm
h ~ p
r • g
h =
p
Rel.: p=
sens
(p + p ) - p
atmhydr.atm
p = p + p
atmhydr.
Abs.: p=
sens
(p + p )
atmhydr.
3 Product description
3.1 Function
The ceramic measuring cell is a dry measuring cell i.e. the pressure acts directly on the
robust, ceramic process isolating diaphragm of the Waterpilot FMX21. Potential changes
in air pressure are guided via a pressure compensation tube through the extension cable to
the rear of the ceramic process isolating diaphragm and are compensated for. A pressuredependent change in capacitance, caused by the movement of the process isolating
diaphragm, is measured at the electrodes of the ceramic carrier. The electronics unit then
converts this to a signal that is proportional to the pressure and linear to the level.
1Ceramic measuring cell
2Pressure compensation tube
hHeight level
pTotal pressure = atmospheric pressure + hydrostatic pressure
ρDensity of the medium
gAcceleration due to gravity
P
Hydrostatic pressure
hydr.
P
Atmospheric pressure
atm
P
Pressure displayed on the sensor
sens
A0019140
10Endress+Hauser
Page 11
Waterpilot FMX21Incoming acceptance and product identification
DELIVERY NOTE
1 = 2
Dat./Insp.:
FW.Ver.:
Dev.Rev.:
Cal./Adj.
Mat:
L=
Ser. no.:
Order code:
Ext.order code:
TAG:
Waterpilot FMX21
Made in Germany,D-79689 Maulburg
p
DELIVERYNOTE
Dat./Insp.:
FW.Ver.:
Dev.Rev.:
Cal./Adj.
Mat:
L=
Ser. no.:
Order code:
Ext. order code:
TAG:
Waterpilot FMX21
Made in Germany,D-79689 Maulburg
p
4 Incoming acceptance and product
identification
4.1 Incoming acceptance
A0015502
A0016870
Is the order code on the delivery note (1) identical to the order code on
the product sticker (2)?
A0015502
A0015502
A0026535
A0026536
Are the goods undamaged?
A0026537
Do the data on the nameplate correspond to the order specifications and
the delivery note?
Endress+Hauser11
Page 12
Incoming acceptance and product identificationWaterpilot FMX21
A0015502
A0022106
Is the documentation available?
If required (see nameplate): Are the safety instructions (XA) present?
If one of these conditions does not apply, please contact your
Endress+Hauser sales office.
4.2 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is
displayed.
For an overview of the technical documentation provided, enter the serial number from
the nameplates in the W@M Device Viewer (www.endress.com/deviceviewer)
12Endress+Hauser
Page 13
Waterpilot FMX21Incoming acceptance and product identification
Dat./Insp.:
FW.Ver.:
Dev.Rev.:
Cal./Adj.
Mat:
L=
Ser. no.:
Order code:
Ext. order code:
TAG:
Waterpilot FMX21
Made in Germany, D-79689 Maulburg
p
1
2
17
16
15
14
3 4
5
6/7
89
101112
13
Mat.: 316L/1.4435/1.4404, Al O , PE, EPDM, PPO
2 3
For use in drinking water according to:
Made in Germany, D-79689 Maulburg
Waterpilot FMX21
250002737-B
1
23
4.3 Nameplates
4.3.1 Nameplates on extension cable
A0018802
1Order code (shortened for reordering); The meaning of the individual letters and digits is explained in the
order confirmation details.
2Extended order number (complete)
3Serial number (for clear identification)
4TAG (device tag)
5FMX21 connection diagram
6Pt100 connection diagram (optional)
7Warning (hazardous area), (optional)
8Length of extension cable
9Approval symbol, e.g. CSA, FM, ATEX (optional)
10 Text for approval (optional)
11 Materials in contact with process
12 Test date (optional)
13 Software version/device version
14 Supply voltage
15 Output signal
16 Set measuring range
17 Nominal measuring range
Additional nameplate for devices with approvals
1Approval symbol (drinking water approval)
2Reference to associated documentation
3Approval number (marine approval)
Endress+Hauser13
A0018805
Page 14
Incoming acceptance and product identificationWaterpilot FMX21
x
Install per dwg. 96000xxxx-
Ser.-No.:
p
Waterpilot FMX21
Cal./Adj.
1 2 3 4567
4.3.2 Additional nameplate for devices with external diameter
22 mm (0.87 in) and 42 mm (1.65 in)
A0018804
1Serial number
2Nominal measuring range
3Set measuring range
4CE mark or approval symbol
5Certificate number (optional)
6Text for approval (optional)
7Reference to documentation
4.4 Identification of sensor type
With relative pressure or absolute pressure sensors, the "Pos.zero adjust" parameter is
displayed in the operating menu. With absolute pressure sensors, the "Calib. offset"
parameter is displayed in the operating menu.
4.5 Storage and transport
4.5.1 Storage conditions
Use original packaging.
Store the measuring device in clean and dry conditions and protect from damage caused by
shocks (EN 837-2).
Storage temperature range
• FMX21: –40 to +80 °C (–40 to +176 °F)
• TMT182: –40 to +100 °C (–40 to +212 °F)
• Terminal box: –40 to +80 °C (–40 to +176 °F)
4.5.2 Transporting the product to the measuring point
WARNING
L
Incorrect transport!
Device or cable may become damaged, and there is a risk of injury!
Transport measuring device in the original packaging.
‣
Follow the safety instructions and transport conditions for devices weighing more than
‣
18 kg (39.6 lbs).
4.6 Scope of delivery
The scope of delivery comprises:
• Waterpilot FMX21, optionally with integrated Pt100 resistance thermometer
• Optional accessories
14Endress+Hauser
Page 15
Waterpilot FMX21Incoming acceptance and product identification
Documentation supplied:
• The Operating Instructions BA00380P are available on the internet. → see:
www.de.endress.com → Downloads.
• Brief Operating Instructions KA01189P
• Final inspection report
• Drinking water approvals (optional): SD00289P, SD00319P, SD00320P
• Devices that are suitable for use in hazardous areas: Additional documentation e.g.
Safety Instructions (XA, ZD)
Endress+Hauser15
Page 16
InstallationWaterpilot FMX21
1
2
3
4
5
6
7
8
9
Dat./Insp.:
FW.Ver.: xxxx
Dev.Rev.: xxxx
Cal./Adj.
Mat:
L=
Ser. no.:xxxxxxxxxxxxx
Order code: xxxxxxxxxxxxxxxxxxxxxx
Ext. order code:xxxxxxxxxxxxxxxxxxxxxx
TAG:xxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxx
Waterpilot FMX21
Made in Germany,D-79689 Maulburg
p
Ex ia IICT6-T4
£
-10°C Ta 70°C
£
Ta 40°C forT6
£
Ta 70°C forT4
£
Ui 30VDC ; Ii 133mA; Pi 1W
£
£
£
II 2G
Ci= 5nF + 180pF/m ; Li= 1 µH/m
Warning!
Avoid electrostatic
charge
0...400mbar
4... 20 mA
0...600mbar
red
+
black
-
yellow-green
4…20 mA
Sensor
250002736--
10,5... 35VDC
XAxxxxxP-
XX/XXXX
TÜV 01ATEX 1685
PPS/Polyolefin
AL2O3
FEPEPDM
OPEN
CLOSE
90°
90°
Warning:
Avoid electrostatic charge in explosive atmosphere.
See instructions
Terminal Box for FMX21
5 Installation
5.1 Installation conditions
A0018770
1Cable mounting screw (can be ordered as an accessory)
2Terminal box (can be ordered as an accessory)
3Bending radius of extension cable > 120 mm (4.72 in)
4Mounting clamp (can be ordered as an accessory)
5Extension cable
6Guide tube
7Waterpilot FMX21
8Additional weight can be ordered as an accessory for the FMX21 with external diameter of 22 mm (0.87 in)
and 29 mm (1.14 in)
9Protection cap
16Endress+Hauser
Page 17
Waterpilot FMX21Installation
5.2 Additional mounting instructions
• Cable length
– Customer-specific in meters or feet.
– Limited cable length when performing installation with freely suspended device with
cable mounting screw or mounting clamp, as well as for FM/CSA approval: max. m/ft.
300 m (984 ft).
• Sideways movement of the level probe can result in measuring errors. For this reason,
install the probe at a point free from flow and turbulence, or use a guide tube. The
internal diameter of the guide tube should be at least 1 mm (0.04 in) greater than the
external diameter of the selected FMX21.
• To avoid mechanical damage to the measuring cell, the device is equipped with a
protection cap.
• The cable must end in a dry room or a suitable terminal box. The terminal box from
Endress+Hauser provides optimum protection from the effects of humidity and weather
conditions and is suitable for outdoor installation→ 118.
• Cable length tolerance: < 5 m (16 ft): ±17.5 mm (0.69 in); > 5 m (16 ft): ±0.2 %
• If the cable is shortened, the filter at the pressure compensation tube must be
reattached. Endress+Hauser offers a cable shortening kit for this purpose
(documentation SD00552P/00/A6).
• Endress+Hauser recommends using twisted, shielded cable.
• In shipbuilding applications, measures are required to restrict the spread of fire along
cable looms.
• The length of the extension cable depends on the intended level zero point. The height
of the protection cap must be taken into consideration when designing the layout of the
measuring point. The level zero point (E) corresponds to the position of the process
isolating diaphragm. Level zero point = E; tip of probe = L (see the following diagram).
5.3 Dimensions
For dimensions, please refer to the Technical Information TI00431P/00/EN, "Mechanical
construction" section (see also: www.de.endress.com → Downloads → Media Type:
Documentation).
Endress+Hauser17
Page 18
InstallationWaterpilot FMX21
1
2
3
5.4 Mounting the Waterpilot with a mounting clamp
1Extension cable
2Suspension clamp
3Clamping jaws
5.4.1 Mounting the suspension clamp:
1.Installing the mounting clamp (item 2) . When selecting the place to attach the unit,
note the weight of the extension cable (item 1) and of the device.
2.Raise the clamping jaws (item 3). Hold the extension cable in position (item 1)
between the clamping jaws as illustrated in the diagram.
3.Hold the extension cable in position (item 1) and push the clamping jaws (item 3)
back down. Tap the clamping jaws gently from above to fix them in place.
A0018793
18Endress+Hauser
Page 19
Waterpilot FMX21Installation
+40
( +1.57)
1
6
8
7
2
3
4
5
36
41
5.5 Mounting the Waterpilot with a cable mounting
screw
A0018794
1Extension cable
2Cover for cable mounting screw
3Sealing ring
4Clamping sleeves
5Adapter for cable mounting screw
6Top edge of clamping sleeve
7Desired length of extension cable and Waterpilot probe prior to assembly
8After assembly, item 7 is located next to the mounting screw with G 1½" thread: height of sealing surface of
the adapter or NPT 1½" thread height of thread run-out of adapter
Engineering unit mm (in). Illustrated with G 1½" thread
If you want to lower the level probe to a certain depth, position the top edge of the
clamping sleeve 40 mm (4.57 in) higher than the required depth. Then push the
extension cable and the clamping sleeve into the adapter as described in Step 6 in the
following section.
5.5.1 Mount cable mounting screw with G 1½" or NPT 1½" thread:
1.Mark the desired length of extension cable on the extension cable
2.Insert the probe through the measuring aperture and carefully lower on the
extension cable. Fix the extension cable to prevent it from slipping.
3.Push the adapter (item 5) over the extension cable and screw it tightly into the
measuring aperture.
4.Push the sealing ring (item 3) and cover (item 2) onto the cable from above. Press
the sealing ring into the cover.
5.Place clamping sleeves (item 4) around the extension cable (item 1) at the marked
position as illustrated in the diagram.
6.Push the extension cable with the clamping sleeves (item 4) into the adapter (item 5)
7.Slide the cover (item 2) with sealing ring (item 3) onto the adapter (item 5) and
screw tightly to the adapter.
To remove the cable mounting screw, perform this sequence of steps in reverse.
CAUTION
L
Risk of injury!
Use only in unpressurized vessels.
‣
Endress+Hauser19
Page 20
InstallationWaterpilot FMX21
1
3
2
6
5
4
3
CLOSE
90°
OPEN
90°
Warning:
Avoid electrostatic charge in explosive atmosphere.
See instructions
Terminal Box for FMX21
1
2
3
4
5
5.6 Mounting the terminal box
The optional terminal box is mounted using four screws (M4). For the dimensions of the
terminal box, please see the Technical Information TI00431P/00/ EN, "Mechanical
construction" section (see also: www.de.endress.com → Downloads → Media Type:
Documentation).
5.7 Mounting the TMT182 temperature head transmitter
with terminal box
1Mounting screws
2Mounting springs
3TMT182 temperature head transmitter
4Circlips
5Terminal box
Only open the terminal box with a screwdriver.
WARNING
L
Risk of explosion!
The TMT182 is not designed for use in hazardous areas.
‣
5.7.1 Mounting the temperature head transmitter:
1.Guide the mounting screws (item 1) with the mounting springs (item 2) through the
hole in the temperature head transmitter (item 3)
2.Secure the mounting screws with the circlips (item 4). Circlips, mounting screws and
springs are included in the scope of delivery for the temperature head transmitter.
3.Screw the temperature head transmitter into the field housing tightly. (width of
screwdriver blade max. 6 mm (0.24 in))
NOTICE
Avoid damage to the temperature head transmitter.
Do not overtighten the mounting screw too.
‣
A0018813
20Endress+Hauser
Page 21
Waterpilot FMX21Installation
>7 (0.28)
A0018696
Engineering unit mm (in)
NOTICE
Incorrect connection!
A distance of >7 mm (> 0.28) must be maintained between the terminal strip and the
‣
TMT182 temperature head transmitter.
5.8 Mounting the terminal strip for the Pt100 passive
(without TMT182)
If the FMX21 with optional Pt100 is supplied without the optional TMT182 temperature
head transmitter, a terminal strip is provided with the terminal box for the purpose of
wiring the Pt100.
WARNING
L
Risk of explosion!
The Pt100, as well as the terminal strip, are not designed for use in hazardous areas.
‣
A0018815
5.9 Post-installation check
Endress+Hauser21
Is the device undamaged (visual inspection)?
Does the device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature
• Measuring range
Are the measuring point identification and labeling correct (visual inspection)?
Page 22
InstallationWaterpilot FMX21
Is the device adequately protected from precipitation and direct sunlight?
Check that all screws are firmly seated.
22Endress+Hauser
Page 23
Waterpilot FMX21Electrical connection
RD
BK
RD
BK
WH
YEBU
BR
a
AB
e
)
)
)
)
c
c
d
d
b
b
a
FMX21
FMX21
6 Electrical connection
WARNING
L
Electrical safety is compromised by an incorrect connection!
When using the measuring device in a hazardous area, the relevant national standards
‣
and guidelines as well as the Safety Instructions (XAs) or installation or control
drawings (ZDs) must be adhered to. All data relating to explosion protection can be
found in separate documentation which is available on request. This documentation is
supplied with the devices as standard → 7
6.1 Connecting the device
WARNING
L
Electrical safety is compromised by an incorrect connection!
The supply voltage must match the supply voltage specified on the nameplate → 13
‣
Switch off the supply voltage before connecting the device.
‣
The cable must end in a dry room or a suitable terminal box. The IP66/IP67 terminal
‣
box with GORE-TEX® filter from Endress+Hauser → 20 is suitable for outdoor
installation.
Connect the device in accordance with the following diagrams. Reverse polarity
‣
protection is integrated into the Waterpilot FMX21 and the TMT182 temperature head
transmitter. Changing the polarities will not result in the destruction of the devices.
A suitable circuit breaker should be provided for the device in accordance with IEC/EN
‣
61010.
6.1.1 Waterpilot with Pt100
A0019441
AWaterpilot FMX21
BWaterpilot FMX21 with Pt100 (not for use in hazardous areas); option "NB", Product Configurator order code
for "Accessories"
aNot for the FMX21 with external diameter of 29 mm (1.14 in)
b10.5 to 30 V DC (hazardous area), 10.5 to 35 V DC
c4...20 mA
dResistance (RL)
ePt100
Endress+Hauser23
Page 24
Electrical connectionWaterpilot FMX21
)
)
a
b
c
e
f
d
cd
g
RD BKWHYE
BU
BR
6
5
4
3
2
1
FMX21
6.1.2 Waterpilot with Pt100 and TMT182 temperature head
transmitter (4 to 20 mA)
aNot for the FMX21 with external diameter of 29 mm (1.14 in)
b10.5 to 35 V DC
c4...20 mA
dResistance (RL)
eTemperature head transmitter TMT182 (4 to 20 mA) (not for use in hazardous areas)
f11.5 to 35 V DC
gPt100
Ordering information: options "NB" and "PT", Product Configurator order code for
"Accessories mounted" and "Accessories enclosed"
6.1.3 Wire colors
RD = red, BK = black, WH = white, YE = yellow, BU = blue, BR = brown
Connection classification as per IEC 61010-1:
• Overvoltage category 1
• Pollution level 1
6.1.4 Connection data
Connection classification as per IEC 61010-1:
• Overvoltage category 1
• Pollution level 1
A0018780
Connection data in the hazardous area
See relevant XA.
24Endress+Hauser
Page 25
Waterpilot FMX21Electrical connection
6.2 Supply voltage
WARNING
L
Supply voltage might be connected!
Risk of electric shock and/or explosion!
When using the measuring device in hazardous areas, installation must comply with
‣
the corresponding national standards and regulations as well as the Safety Instructions.
All explosion protection data are given in separate documentation which is available
‣
upon request. The Ex documentation is supplied as standard with all devices approved
for use in explosion hazardous areas.
6.2.1 FMX21 + Pt100 (optional)
• 10.5 to 35 V (not hazardous areas)
• 10.5 to 30 V (hazardous areas)
6.2.2 TMT182 temperature head transmitter (optional)
11.5 to 35 V DC
6.3 Cable specifications
In the following cases, Endress+Hauser recommends the use of a shielded cable as the
cable extension:
• For large distances between the end of the extension cable and the display and/or
evaluation unit
• For large distances between the end of the extension cable and the temperature head
transmitter
• When directly connecting the Pt100 signal to a display and/or evaluation unit
The extension cables are shielded for device versions with external diameters of 22
mm (0.87 in) and 42 mm (1.65 in).
6.3.1 FMX21 + Pt100 (optional)
• Commercially available instrument cable
• Terminals, terminal box: 0.08 to 2.5 mm2 (28 to 14 AWG)
6.3.2 TMT182 temperature head transmitter (optional)
• Commercially available instrument cable
• Terminals, terminal box: 0.08 to 2.5 mm2 (28 to 14 AWG)
• Transmitter connection: max. 1.75 mm2 (15 AWG)
6.4 Power consumption
6.4.1 FMX21 + Pt100 (optional)
• ≤ 0.805 W at 35 V DC (non-hazardous area)
• ≤ 0.690 W at 30 V DC (hazardous area)
6.4.2 TMT182 temperature head transmitter (optional)
≤ 0.805 W at 35 V DC
Endress+Hauser25
Page 26
Electrical connectionWaterpilot FMX21
R
Lmax
– 2 0.09•
• L – R
U – 10.5 V
23 mA
W
m
£
413
630
195
1065
35
20
25
10.5
15
847
30
R
[ ]W
U
[ ]
V
– R
U – 11.5 V
0.023 A
£
R
Lmax
370
587
152
1022
35
20
25
11.5
15
804
30
R
[ ]W
U
[ ]
V
AB
addadd
6.5 Current consumption
6.5.1 FMX21 + Pt100 (optional)
• Max. current consumption: ≤ 23 mA
Min. current consumption: ≥ 3.6 mA
• Pt100: ≤ 0.6 mA
6.5.2 TMT182 temperature head transmitter (optional)
• Max. current consumption: ≤ 23 mA
• Min. current consumption: ≥ 3.5 mA
• Pt100 via temperature head transmitter: ≤ 0.6 mA
6.6 Maximum load
The maximum load resistance depends on the supply voltage (U) and must be determined
individually for each current loop, see formula and diagrams for FMX21 and temperature
head transmitter.
The total resistance resulting from the resistances of the connected devices, the
connecting cable and, where applicable, the resistance of the extension cable may not
exceed the load resistance value.
AFMX21 load chart for estimating the load resistance. Additional resistances, such as the resistance of the
extension cable, have to be subtracted from the value calculated as shown in the equation.
BLoad diagram for TMT182 temperature head transmitter for estimating the load resistance. Additional
resistances must be subtracted from the value calculated as shown in the equation
R
Max. load resistance [Ω]
Lmax
R
Additional resistances, such as resistance of the evaluation unit and/or display unit, cable resistance [Ω]
add
USupply voltage [V]
LBasic length of extension cable [m] (cable resistance per wire 0.09 Ω/m)
26Endress+Hauser
• When using the measuring device in a hazardous area, the relevant national
standards and regulations as well as the Safety Instructions or installation or control
drawings (XA) must be adhered to.
• When operating via a handheld terminal or via a PC with an operating program, a
minimum communication resistance of 250 Ω must be taken into account.
A0026500-EN
Page 27
Waterpilot FMX21Electrical connection
1
3
4
3
4
5
5
5
5
5
5
5
6
6
6
2
A
B
B
C
2
6.7 Connecting the measuring unit
6.7.1 Overvoltage protection
To protect the Waterpilot and the TMT182 temperature head transmitter from large
interference voltage peaks, Endress+Hauser recommends installing overvoltage protection
upstream and downstream of the display and/or evaluation unit as shown in the graphic.
APower supply, display and evaluation unit with one input for Pt100
BPower supply, display and evaluation unit with one input for 4 to 20 mA
CPower supply, display and evaluation unit with two inputs for 4 to 20 mA
1Waterpilot FMX21 HART
2Connection for integrated Pt100 in the FMX21
34 to 20 mA HART (temperature)
44 to 20 mA HART (level)
5Overvoltage protection, e.g. HAW from Endress+Hauser (not for use in hazardous areas).
6Power supply
A0018941
Further information on the TMT182 temperature head transmitter for HART
applications from Endress+Hauser can be found in the Technical Information
TI00078R/09/EN.
6.7.2 Connecting the Commubox FXA195
Endress+Hauser27
The Commubox FXA195 connects intrinsically safe transmitters with HART protocol to the
USB interface of a computer. This enables remote operation of the transmitter using the
Endress+Hauser operating program FieldCare. The power is supplied to the Commubox via
Page 28
Electrical connectionWaterpilot FMX21
3
76
4
1
5
2
the USB interface. The Commubox is also suitable for connecting to intrinsically safe
circuits. For further information, see the Technical Information TI00404F/00/EN.
6.7.3 Connecting the Field Xpert SFX
Compact, flexible and robust industrial handheld terminal for remote configuration and for
obtaining measured values via the HART current output (4 to 20 mA). For details, see
Operating Instructions BA00060S/04/EN.
A0018811
1Waterpilot FMX21
2Required communication resistor ≥ 250 Ω
3Computer with operating tool (e.g. FieldCare)
4Commubox FXA195 (USB)
5Transmitter power supply unit, e.g. RN221N (with communication resistor)
6Field Xpert SFX
7VIATOR Bluetooth modem with connecting cable
Only use certified operating devices in hazardous area!
WARNING
L
Risk of explosion!
Do not change the battery of the handheld terminal in the hazardous area.
‣
When using the measuring device in a hazardous area, the relevant national standards
‣
and regulations as well as the Safety Instructions (XAs) or installation or control
drawings (ZDs) must be adhered to.
28Endress+Hauser
Page 29
Waterpilot FMX21Electrical connection
FXN520
1234
6.7.4 Connecting for air pressure compensation with external
measured value
For applications in which condensation may occur, the use of an absolute pressure probe is
recommended. For level measurement using an absolute pressure probe, the measured
value is affected by fluctuations in the ambient air pressure. To correct the resulting
measured error, you can connect an external absolute pressure sensor (e.g. Cerabar) to the
HART signal cable, switch the Waterpilot to burst mode and operate the Cerabar in "Electr.
Delta P" mode.
By switching on the "Electr. Delta P" application, the external absolute pressure sensor
calculates the difference between the two pressure signals and can thus determine the
level precisely. Only one level measured value can be corrected in this way.
If using intrinsically safe devices, the regulations which apply to interconnecting
intrinsically safe circuits as outlined in IEC 60079-14 (proof of intrinsic safety) must
be observed.
6.7.5 Connecting an external temperature sensor/temperature head
transmitter for density compensation
The Waterpilot FMX21 can correct measured errors that result from fluctuations in the
density of the water caused by temperature. Users can choose from the following options:
Use the internally measured sensor temperature of the FMX21
The internally measured sensor temperature is calculated in the Waterpilot FMX21 for
density compensation. The level signal is thus corrected according to the density
characteristic line of the water.
Use the optional internal Pt100 temperature sensor for density compensation in a
suitable HART master (e.g. PLC)
The Waterpilot FMX21 is available with an optional Pt100 temperature sensor. Endress
+Hauser additionally offers the TMT182 temperature head transmitter to convert the
Pt100 signal to a 4 to 20 mA HART signal. The temperature and pressure signal is
requested by a HART master (e.g. PLC), where a corrected level value can be generated
using a stored linearization table or density function (of a chosen medium).
Endress+Hauser29
Page 30
Electrical connectionWaterpilot FMX21
1234
FXN520
FXN520
1234
A0018763
1HART master, e.g. PLC (programmable logic controller)
2Multidrop connector FXN520
3Temperature head transmitter TMT182
4Waterpilot FMX21
Use an external temperature signal which is transmitted to the FMX21 via HART
burst mode
The Waterpilot FMX21 is available with an optional Pt100 temperature sensor. In this
case, the signal of the Pt100 is analyzed using a HART-compliant (min. HART 5.0)
temperature head transmitter that supports burst mode. The temperature signal can thus
be transmitted to the FMX21. The FMX21 uses this signal for density correction of the
level signal.
The TMT182 temperature head transmitter is not suitable for this configuration.
Without additional compensation due to the anomaly of water, errors of up to 4% may
occur at a temperature of +70 °C (+158 °F), for example. With density compensation, this
error can be decreased to 0.5 % in the entire temperature range from
0 to +70 °C (+32 to +158 °F).
For further information on the devices, please refer to the relevant Technical
Information:
• TI00078R: Temperature head transmitter TMT182 (4 to 20 mA HART)
• TI00369F: Fieldgate FXA520
• TI00400F: Multidrop connector FXN520
30Endress+Hauser
A0018764
Page 31
Waterpilot FMX21Electrical connection
6.8 Post-connection check
Is the device or cable undamaged (visual check)?
Do the cables comply with the requirements ?
Do the cables have adequate strain relief?
Are all cable glands installed, securely tightened and leak-tight?
Does the supply voltage match the specifications on the nameplate?
Is the terminal assignment correct ?
Endress+Hauser31
Page 32
Operation optionsWaterpilot FMX21
7 Operation options
Endress+Hauser offers comprehensive measuring point solutions with display and/or
evaluation units for the Waterpilot FMX21 and TMT182 temperature head transmitter.
Your Endress+Hauser service organization would be glad to be of service if you have
any other questions. Contact addresses can be found on the website at
www.endress.com/worldwide
7.1 Overview of operating options
7.1.1 Operation using Endress+Hauser operating program
The FieldCare operating program is an Endress+Hauser plant asset management tool
based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as
well as devices from other manufacturers that support the FDT standard.
Hardware and software requirements can be found on the Internet:
• Configuration of transmitters in online/offline mode
• Loading and saving device data (upload/download)
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA195 and the USB port of a computer
• HART via FXA520 Fieldgate
• Further information on FieldCare and software download can be found on the
internet (www.de.endress.com ® Downloads ® Text Search: FieldCare).
• Connecting the Commubox FXA195
• As not all internal device dependencies can be mapped in offline operation, the
consistency of the parameters must be checked once again before they are
transmitted to the device.
7.1.2 Operation using Field Xpert SFX
Compact, flexible and robust industrial handheld terminal for remote configuration and for
obtaining measured values via the HART current output or FOUNDATION Fieldbus. For
details, see the Operating Instructions BA00060S/04.
32Endress+Hauser
Page 33
Waterpilot FMX21Operation options
7.2 Operating concept
Operation with an operating menu is based on an operation concept with "user roles" .
User roleMeaning
OperatorOperators are responsible for the devices during normal "operation". This is usually limited to
reading process values either directly at the device or in a control room. If the work with the
devices goes beyond reading, it concerns simple, application-specific functions that are used in
operation. Should an error occur, these users simple forward the information on the errors but
do not intervene themselves.
Maintenance Service engineers usually work with the devices in the phases following device commissioning.
They are primarily involved in maintenance and troubleshooting activities for which simple
settings have to be made at the device. Technicians work with the devices over the entire life
cycle of the product. Thus, commissioning and advanced settings and configurations are some of
the tasks they have to carry out.
ExpertExperts work with the devices over the entire life cycle of the device, but, in part, have high
requirements on the devices. Individual parameters/functions from the overall functionality of
the devices are required for this purpose time and again. In addition to technical, processoriented tasks, experts can also perform administrative tasks (e.g. user administration). "Experts"
can avail of the entire parameter set.
7.3 Structure of the operating menu
User roleSubmenuMeaning/use
OperatorDisplay/
operat.
Maintenance setupContains all the parameters that are needed to commission measuring operations.
Contains parameters that are needed to configure the measured value display
(selecting the values displayed, display format, etc.). With this submenu, users can
change the measured value display without affecting the actual measurement.
This submenu has the following structure:
• Standard setup parameters
A wide range of parameters, which can be used to configure a typical application,
is available at the start. The measuring mode selected determines which
parameters are available. After making settings for all these parameters, the
measuring operation should be completely configured in the majority of cases.
• "Extended setup" submenu
The "Extended setup" submenu contains additional parameters for more in-depth
configuration of the measurement operation, for conversion of the measured
value and for scaling the output signal. This menu is split into additional
submenus depending on the measuring mode selected.
Endress+Hauser33
Page 34
Operation optionsWaterpilot FMX21
User roleSubmenuMeaning/use
Maintenance DiagnosisContains all the parameters that are needed to detect and analyze operating errors.
This submenu has the following structure:
• Diagnostic list
contains up to 10 currently pending error messages.
• Event logbook
contains the last 10 error messages (no longer pending).
• Instrument info
contains information for identifying the device.
• Measured values
contains all current measured values.
• Simulation
Is used to simulate pressure, level, current and alarm/warning.
• Enter reset code
ExpertExpertContains all the parameters of the device (including those already in one of the
submenus). The "Expert" submenu is structured by the function blocks of the device.
It thus contains the following submenus:
• System
contains all device parameters that do not affect either measurement or
integration into a distributed control system.
• Measurement
contains all parameters for configuring the measurement.
• Output
contains all parameters for configuring the current output.
• Communication
contains all parameters for configuring the HART interface.
• Diagnosis
contains all parameters required to detect and analyze operating errors.
7.4 Locking/unlocking operation
Once you have entered all the parameters, you can lock your entries against unauthorized
and undesired access.
The "Operator code" parameter is used to lock/unlock the device.
There are various reset codes for the device. The following table illustrates which
parameters are reset by the particular reset codes. To perform a reset, operation must
be unlocked (see "Locking/unlocking operation" section → 34).
Any customer-specific configuration carried out at the factory is not affected by a
reset (customer-specific configuration remains). If you want to change the customerspecific configuration carried out at the factory, please contact Endress+Hauser
Service. As there is no separate service level, the order code and serial number can be
changed without a specific release code.
Reset code
62PowerUp reset (warm start)
333User reset
7864Total reset
1)
Description and effect
• The device is restarted.
• Data is read back anew from the EEPROM (process is reinitialized).
• Any simulation which may be running is ended.
• This code resets all the parameters apart from:
- Device tag
- Linearization table
- Operating hours
- Event logbook
- Curr. trim 4 mA
- Curr. trim 20 mA
• Any simulation which may be running is ended.
• The device is restarted.
• This code resets all the parameters apart from:
- Operating hours
- Event logbook
• Any simulation which may be running is ended.
• The device is restarted.
1)To be entered in "System" → "Management" → "Enter reset code"
After a "Total reset" in FieldCare you have to press the "refresh" button in order to
ensure that the measuring units are also reset.
1). The factory setting for the individual parameters is specified in the parameter description
Endress+Hauser35
Page 36
Integrating device via HART® protocol
Waterpilot FMX21
8
Integrating device via HART® protocol
Version data for the device
Firmware version01.00.zz• On the title page of the Operating instructions
• On nameplate
• Firmware Version parameter
Diagnosis→ Instrument info → Firmware version
• Device revision parameter
Diagnosis→ Instrument info → Device revision
The suitable device description file (DD) for the individual operating tools is listed in the
table below, along with information on where the file can be acquired.
Operating tools
Operating toolReference sources for device descriptions (DD and DTM)
FieldCare• www.endress.com → Downloads area
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
AMS Device Manager
(Emerson Process Management)
SIMATIC PDM
(Siemens)
Field Communicator 375, 475
(Emerson Process Management)
www.endress.com → Downloads area
www.endress.com → Downloads area
Use update function of handheld terminal
8.1 HART process variables and measured values
The following numbers are assigned to the process variables in the factory:
Process variableMeas.Level
LinearTable active
First process variable
(Primary variable)
Second process variable
(Secondary variable)
(Pressure measured)
0
2
(Corrected press.)
8
(Level before
linearization)
0
(Pressure measured)
(Tank content)
(Level before
linearization)
9
8
36Endress+Hauser
Page 37
Waterpilot FMX21
Process variableMeas.Level
Third process variable
(Tertiary variable)
Fourth process variable
(Quaternary variable)
3
(Sensor pressure)
The assignment of the device variables to the process variable is displayed in the
Expert → Communication → HART output menu.
The assignment of the device variables to the process variable can be changed using
HART command 51.
An overview of the possible device variables can be found in the following section.
8.2 Device variables and measured values
The following measured values are assigned to the individual device variables:
Device variable codeDevice variableMeasured value
0PRESSURE_1_FINAL_VALUEPressure measuredAll
1PRESSURE_1_AFTER_DAMPINGPress after dampingAll
2PRESSURE_1_AFTER_CALIBRATIONCorrected press.All
3PRESSURE_1_AFTER_SENSORCorrected press.All
4MEASURED_TEMPERATURE_1Sensor temp.All
8MEASURED_LEVEL_AFTER_ SIMULATIONLevel before lin.Only level
12HART_INPUT_VALUEHART input val.Cannot be selected as output
251None (no device variable is mapped)-All (but only for quaternary variable)
Integrating device via HART® protocol
LinearTable active
2
(Corrected press.)
4
(Sensor temp.)
(Pressure measured)
0
The device variables can be queried from a HART® master using HART® command 9 or
33.
Endress+Hauser37
Page 38
CommissioningWaterpilot FMX21
9 Commissioning
NOTICE
If a pressure smaller than the minimum permitted pressure or greater than the
maximum permitted pressure is present at the device, the following messages are
output in succession:
"S140 Working range P" or "F140 Working range P" (depending on the setting in the
‣
"Alarm behav. P" parameter)
"S841 Sensor range" or "F841 Sensor range" (depending on the setting in the "Alarm
‣
behav. P" parameter)
"S971 Adjustment" (depending on setting in "Alarm behav. P" parameter
‣
9.1 Post-installation check and function check
Before commissioning your measuring point, ensure that the post-installation and postconnection check have been performed.
• "Post-installation check" checklist → 21
• "Post-connection check" checklist → 31
9.2 Unlocking/locking configuration
If the device is locked to prevent configuration, it must first be unlocked.
9.2.1 Locking/unlocking software
If the device is locked via the software (device access code), the key symbol appears in the
measured value display. If an attempt is made to write to a parameter, a prompt for the
device access code appears. To unlock, enter the user-defined device access code.
9.3 Commissioning
Commissioning comprises the following steps:
• Function check → 38
• Selecting the language, measuring mode and pressure unit → 39
The device is configured for the "Pressure" measuring mode as standard. The
measuring range and the unit in which the measured value is transmitted correspond
to the data on the nameplate.
WARNING
L
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in
‣
the "Setup" operating menu and readjusted if necessary.
DescriptionPosition adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known.
Options• Confirm
• Cancel
Example• Measured value = 2.2 mbar (0.033 psi)
• You correct the measured value via the "Pos. zero adjust" parameter with the "Confirm"
option. i.e. This means that you are assigning the value 0.0 to the pressure present.
• Measured value (after pos. zero adjust) = 0.0 mbar
DescriptionPosition adjustment – the pressure difference between zero (set point) and the measured
pressure must be known.
Options• Confirm
• Cancel
Example• Measured value = 982.2 mbar (15 psi)
• You correct the measured value via the "Calib. offset" parameter with the "Confirm"
option. i.e. This means that you are assigning the value 980.0 to the pressure present.
• Measured value (after position adjustment) = 980 mbar (15 psi)
• The current value is also corrected.
Factory settingCancel
9.8 Configuring the damping
The pressure resulting from the orientation of the device can be corrected here.
Factory setting2.0 sec. or according to order specifications
Enter damping time (time constant t) ("Damping" DIP switch set to "on")
Display damping time (time constant t) ("Damping" DIP switch set to "off").
The damping affects the speed at which the measured value reacts to changes in pressure.
9.9 Configuring pressure measurement
9.9.1 Calibration with reference pressure (wet calibration)
Example:
In this example, a device with a 400 mbar (6 psi) sensor module is configured for the
0 to +300 mbar (0 to 4.5 psi) measuring range i.e. 0 mbar is assigned to the 4 mA value
and 300 mbar (4.5 psi) is assigned to the 20 mA value.
Endress+Hauser41
Page 42
CommissioningWaterpilot FMX21
i
p
A
B
Prerequisite:
The pressure values 0 mbar and 300 mbar (4.5 psi) can be specified. For example, the
device is already installed.
Due to the orientation of the device, there may be pressure shifts in the measured
value, i.e. the measured value is not zero in a pressureless condition. For information
on how to perform a position adjustment, see → 40.
Description
1Select the "Pressure" measuring mode via the
"Measuring Mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the
span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the
‣
setting for the span (URV) must be
checked in the "Setup" operating menu and
readjusted if necessary.
2Select a pressure unit via the "Press. eng. unit"
parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3The pressure for the LRV (4 mA value) is
present at the device, 0 mbar for example.
Select the "Get LRV" parameter.
Menu path: Setup → Extended setup → Current
output → Get LRV
Confirm the present value by selecting "Apply".
The present pressure value is assigned to the
lower current value (4 mA).
4The pressure for the URV (20 mA value) is
present at the device, 300 mbar (4.5 psi).
Select the "Get URV" parameter.
Menu path: Setup → Extended setup → Current
output → Get URV
Confirm the present value by selecting "Apply".
The present pressure value is assigned to the
upper current value (20 mA).
5Result:
The measuring range is configured for
0 to +300 mbar (0 to 4.5 psi).
9.9.2 Calibration without reference pressure (dry calibration)
Example:
In this example, a device with a 400 mbar (6 psi) sensor module is configured for the
0 to +300 mbar (0 to 4.5 psi) measuring range, i.e. 0 mbar is assigned to the 4 mA value
and 300 mbar (4.5 psi) is assigned to the 20 mA value.
Prerequisite:
42Endress+Hauser
This is a theoretical calibration, i.e. the pressure values for the lower and upper range are
known.
Due to the orientation of the device, there may be pressure shifts in the measured
value, i.e. the measured value is not zero in a pressureless condition. For information
on how to perform a position adjustment, see → 40.
Page 43
Waterpilot FMX21Commissioning
i
p
A
B
Description
1Select the "Pressure" measuring mode via the
"Measuring Mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the
span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the
‣
setting for the span (URV) must be
checked in the "Setup" operating menu and
readjusted if necessary.
2Select a pressure unit via the "Press. eng. unit"
parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3Select the "Set LRV" parameter.
Menu path: Setup → Extended setup → Current
output → Set LRV
Enter the value for the "Set LRV" parameter
(here 0 mbar) and confirm. This pressure value
is assigned to the lower current value (4 mA).
4Select the "Set URV" parameter.
Menu path: Setup → Extended setup → Current
output → Set URV
Enter the value for the "Set URV" parameter,
here 300 mbar (4.5 psi), and confirm. This
pressure value is assigned to the upper current
value (20 mA).
5Result:
The measuring range is configured for
0 to +300 mbar (0 to 4.5 psi).
You have a choice of two methods for calculating the level: "In pressure" and "In
height". The table in the "Overview of level measurement" section that follows
provides you with an overview of these two measuring tasks.
• The limit values are not checked, i.e. the values entered must be appropriate for the
sensor module and the measuring task for the device to be able to measure
correctly.
• Customer-specific units are not possible.
• The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure",
"Empty height/Full height" and "Set LRV/Set URV" must be at least 1% apart. The
value will be rejected, and a warning message displayed, if the values are too close
together.
Endress+Hauser43
Page 44
CommissioningWaterpilot FMX21
1000 l
0 l
400 mbar
r = 1
g
cm
3
9.10.2 Overview of level measurement
Measuring taskLevel
selection
Calibration is
performed by
entering two
pressure-level value
pairs.
Calibration is
performed by
entering the density
and two height-level
value pairs.
"In
pressure"
"In height"• Calibration with
Measured variable
options
Via the "Output unit"
parameter :
%, level, volume or
mass units
DescriptionMeasured value
display
• Calibration with
reference pressure
(wet calibration)
→ 46
• Calibration without
reference pressure (dry
calibration) → 44
reference pressure
(wet calibration)
→ 51
• Calibration without
reference pressure (dry
calibration) → 48
The measured value
display and the "Level
before lin" parameter
display the measured
value.
9.10.3 "In pressure" level selection Calibration without reference
pressure (dry calibration)
Example:
In this example, the volume in a tank should be measured in liters. The maximum volume
of 1000 l (264 gal) corresponds to a pressure of 400 mbar (6 psi).
The minimum volume of 0 liters corresponds to a pressure of 0 mbar since the process
isolating diaphragm of the probe is at the start of the level measuring range.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration i.e. the pressure and volume values for the lower and
upper calibration point must be known.
• The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure" and
"Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a
warning message displayed, if the values are too close together. Further limit values
are not checked, i.e. the values entered must be appropriate for the sensor module
and the measuring task for the device to be able to measure correctly.
• Due to the orientation of the device, there may be pressure shifts in the measured
value, i.e. when the vessel is empty or partly filled, the measured value is not zero.
For information on how to perform a position adjustment, see → 40.
Description
1Select the "Level" measuring mode via the
"Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the
span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the
‣
setting for the span (URV) must be
checked in the "Setup" operating menu and
2Select a pressure unit via the "Press. eng. unit"
readjusted if necessary.
parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
44Endress+Hauser
A0018818
Page 45
Waterpilot FMX21Commissioning
C
D
E
F
G
H
v
p
i
v
Description
3
Select the "In pressure" level mode via the "Level
selection" parameter.
Menu path: Setup → Extended setup → Level →
Level selection.
4Select a volume unit via the "Unit before lin."
parameter, here "l" (liter) for example.
Menu path: Setup → Extended setup → Level→
Unit before lin.
calibration point via the "Empty calib."
parameter, here 0 liters for example.
Menu path: Setup → Extended setup → Level →
Empty calib.
7Enter the pressure value for the lower
calibration point via the "Empty pressure"
parameter, here "0 mbar" for example.
Menu path: Setup → Extended setup → Level →
Empty pressure
8Enter the volume value for the upper
calibration point via the "Full calib." parameter,
here 1000 l (264 gal).
Menu path: Setup → Extended setup → Level →
Full calib.
9Enter the pressure value for the upper
calibration point via the "Full pressure"
parameter, here 400 mbar (6 psi).
Menu path: Setup → Extended setup → Level →
Full pressure
10"Adjust density" contains the factory setting 1.0
but can be changed if required. The value pairs
subsequently entered must correspond to this
density.
Menu path: Setup → Extended setup → Level →
Adjust density
11Set the volume value for the lower current
value (4 mA) via the "Set LRV" parameter (0 l).
Menu path: Setup → Extended setup → Current
output → Set LRV
12Set the volume value for the upper current
value (20 mA) via the "Set URV" parameter
(1000 l (264 gal)).
Menu path: Setup → Extended setup → Current
output → Set URV
13If the process uses a medium other than that
on which the calibration was based, the new
density must be specified in the "Process
density" parameter.
Menu path: Setup → Extended setup → Current
output → Process density.
1See table, steps 6 and 7.
2See table, steps 8 and 9.
temperature probe in the "Auto dens. corr."
parameter. A density correction is only possible
for water. A temperature-density curve that is
saved in the device is used. For this reason, the
"Adjust density" (step 10) and "Process density"
(step 13) parameters are not used here.
Menu path: Expert → Application → Level →
Auto dens. corr.
15Result:
The measuring range is configured for
0 to 1000 l (0 to 264 gal).
For this level mode, the measured variables %, level, volume and mass are available,
see "Unit before lin." .
9.10.4 "In pressure" level selection Calibration with reference
pressure (wet calibration)
Example:
In this example, the level in a tank should be measured in "m". The maximum level is
3 m (9.8 ft).
The pressure range is derived from the level and the density of the medium. In this
situation, the device sets the pressure range to 0 to +300 mbar (0 to 4.5 psi).
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled and emptied.
The values entered for "Empty calib./Full calib." and" Set LRV/Set URV" and the
pressures present must be at least 1% apart. The value will be rejected, and a warning
message displayed, if the values are too close together. Other limit values are not
checked, i.e. the values entered must be appropriate for the sensor and the measuring
task for the device to be able to measure correctly.
Description
1Perform a "position adjustment" → 40.
2Select the "Level" measuring mode via the
"Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the
span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the
‣
setting for the span (URV) must be
checked in the "Setup" operating menu and
readjusted if necessary.
3Select a pressure unit via the "Press. eng. unit"
parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
4Select the "In pressure" level mode via the "Level
temperature probe in the "Auto dens. corr."
parameter.
Menu path: Expertc → Application → Auto
dens. corr.
A density correction is only possible for water.
A temperature-density curve that is saved in
the device is used. For this reason, the "Adjust
density" (step 8) and "Process density" (step 13)
parameters are not used here.
6Select a level unit via the "Output unit"
parameter, "m" for example.
Menu path: Setup → Extended setup → Level →
Output unit
other than the process medium, enter the
density of the calibration medium in the
"Adjust density" parameter.
Menu path: Setup → Extended setup → Level →
Adjust density
The process density can be changed only
if automatic density correction is
switched off (see step 5).
9The hydrostatic pressure for the lower
calibration point is present at the device, here
"0 mbar" for example.
Select the "Empty calib." parameter.
Menu path: Setup → Extended setup → Level →
Empty calib.
Enter the level value, here 0 m for example.
The pressure value present is assigned to the
lower level value by confirming the value.
10The hydrostatic pressure for the upper
calibration point is present at the device, here
300 mbar (4.35 psi) for example.
Select the "Full calib." parameter.
Menu path: Setup → Extended setup → Level →
Full calib.
Enter the level value, 3 m (9.8 ft). The pressure
value present is assigned to the upper level
value by confirming the value.
11Use the "Set LRV" parameter to set the level
value for the lower current value (4 mA), here
"0 m" for example.
Menu path: Setup → Extended setup → Current
output → Set LRV
12Use the "Set URV" parameter to set the upper
current value (20 mA) (3 m (9.8 ft)).
Menu path: Setup → Extended setup → Current
output → Set URV
on which the calibration was based, the new
density must be specified in the "Process
density" parameter.
Menu path: Setup → Extended setup → Level →
Process density.
The process density can be changed only
if automatic density correction is
switched off (see step 5).
13Result:
The measuring range is configured for
0 to 3 m (0 to 9.8 ft).
For this level mode, the measured variables %, level, volume and mass are available,
see "Unit before lin." .
9.10.5 "In height" level selection Calibration without reference
pressure (dry calibration)
Example:
In this example, the volume in a tank should be measured in liters. The maximum volume
of 1000 l (264 gal) corresponds to a level of 4 m (13 ft). The minimum volume of 0 liter
corresponds to a level of 0 m since the process isolating diaphragm of the probe is at the
start of the level measuring range.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration i.e. the height and volume values for the lower and upper
calibration point must be known.
• The values entered for "Empty calib./Full calib.", "Empty height/Full height" and" Set
LRV/Set URV" must be at least 1% apart. The value will be rejected, and a warning
message displayed, if the values are too close together. Other limit values are not
checked, i.e. the values entered must be appropriate for the sensor and the
measuring task for the device to be able to measure correctly.
• Due to the orientation of the device, there may be pressure shifts in the measured
value, i.e. when the vessel is empty or partly filled, the measured value is not zero.
For information on how to perform a position adjustment, see → 40.
Description
1Select the "Level" measuring mode via the
"Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the
span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the
‣
setting for the span (URV) must be
checked in the "Setup" operating menu and
readjusted if necessary.
2Select a pressure unit via the "Press. eng. unit"
parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
temperature probe in the "Auto dens. corr."
parameter.
Menu path: Setup → Extended setup → Level →
Level selection.
4Select a volume unit via the "Unit before lin."
parameter, here "l" (liter) for example.
Menu path: Setup → Extended setup → Level→
Unit before lin.
A density correction is only possible for water.
A temperature-density curve that is saved in
the device is used. For this reason, the "Adjust
density" (step 12) and "Process density" (step
15) parameters are not used here.
5Select a volume unit via the "Output unit"
parameter, here here "l" (liter) for example.
Menu path: Setup → Extended setup → Level →
Output unit
6Select a level unit via the "Height unit"
parameter, "m" for example.
Menu path: Setup → Extended setup → Level →
Height unit
1See table, steps 10 and 11.
2See table, steps 13 and 14.
3See table, step 12
calibration point via the "Empty calib."
parameter, here 0 liters for example.
Menu path: Setup → Extended setup → Level →
Empty calib.
9Enter the height value for the lower calibration
point via the "Empty height" parameter, here 0
m for example.
Menu path: Setup → Extended setup → Level →
Empty height
10Enter the volume value for the upper
calibration point via the "Full calib." parameter,
here 1000 l (264 gal) for example.
Menu path: Setup → Extended setup → Level →
Full calib.
11Enter the height value for the upper calibration
point via the "Full height" parameter, here
4 m (13 ft) for example.
Menu path: Setup → Extended setup → Level →
Full height
12Enter the density of the medium via the "Adjust
density" parameter, here "1 g/cm3" (1 SGU) for
example.
Menu path: Setup → Extended setup → Level →
Adjust density
13Set the volume value for the lower current
value (4 mA) via the "Set LRV" parameter (0 l).
Menu path: Setup → Extended setup → Current
output → Set LRV
14Set the volume value for the upper current
value (20 mA) via the "Set URV" parameter
(1000 l (264 gal)).
Menu path: Setup → Extended setup → Current
output → Set URV
15If the process uses a medium other than that
on which the calibration was based, the new
density must be specified in the "Process
density" parameter.
Menu path: Setup → Extended setup → Current
output → Process density.
The process density can only be changed
if automatic density correction is
switched off (see Step 4).
16Result:
The measuring range is configured for
0 to 1000 l (0 to 264 gal).
For this level mode, the measured variables %, level, volume and mass are available,
see "Unit before lin." .
50Endress+Hauser
Page 51
Waterpilot FMX21Commissioning
1000 l
0 l
4 m
r = 1
g
cm
3
9.10.6 "In height" level selection Calibration with reference pressure
(wet calibration)
Example:
In this example, the volume in a tank should be measured in liters. The maximum volume
of 1000 l (264 gal) corresponds to a level of 4 m (13 ft).
The minimum volume of 0 liter corresponds to a level of 0 m since the process isolating
diaphragm of the probe is at the start of the level measuring range. The density of the
fluid is 1 g/cm3 (1 SGU).
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled and emptied.
The values entered for "Empty calib./Full calib." and" Set LRV/Set URV" and the
pressures present must be at least 1% apart. The value will be rejected, and a warning
message displayed, if the values are too close together. Other limit values are not
checked, i.e. the values entered must be appropriate for the sensor and the measuring
task for the device to be able to measure correctly.
Description
1Perform a "position adjustment" → 40.
2Select the "Level" measuring mode via the
"Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the
span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the
‣
setting for the span (URV) must be
checked in the "Setup" operating menu and
readjusted if necessary.
temperature probe in the "Auto dens. corr."
parameter.
Menu path: Expertc → Application → Auto
dens. corr.
A density correction is only possible for water.
A temperature-density curve that is saved in
the device is used. For this reason, the "Adjust
density" (step 11) and "Process density" (step
14) parameters are not used here.
5Select a pressure unit via the "Press. eng. unit"
parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
calibration point is present at the device, here
"0 mbar" for example.
Enter the volume value for the lower
calibration point via the "Empty calib."
parameter, here "0 liter" for example.
Menu path: Setup → Extended setup → Level →
Empty calib.
10The hydrostatic pressure for the upper
calibration point is present at the device, here
"400 mbar (6 psi)" for example.
Enter the volume value for the upper
calibration point via the "Full calib." parameter,
here 1000 l (264 gal) for example.
Menu path: Setup → Extended setup → Level →
Full calib.
11If the calibration is performed with a medium
other than the process medium, enter the
density of the calibration medium in the
"Adjust density" parameter, here 1 g/cm3 (1
SGU) for example.
Menu path: Setup → Extended setup → Level →
Adjust density
The process density can only be changed
if automatic density correction is
switched off (see Step 4).
12Set the volume value for the lower current
value (4 mA) via the "Set LRV" parameter (0 l).
Menu path: Setup → Extended setup → Current
output → Set LRV
13Set the volume value for the upper current
value (20 mA) via the "Set URV"
parameter(1000 l (264 gal)).
Menu path: Setup → Extended setup → Current
output → Set URV
14If the process uses a medium other than that
on which the calibration was based, the new
density must be specified in the "Process
density" parameter.
Menu path: Setup → Extended setup → Level →
Process density.
The process density can only be changed
if automatic density correction is
switched off (see Step 4).
15Result:
The measuring range is configured for
0 to 1000 l (0 to 264 gal).
The measured variables %, level, volume and mass are available for this level mode,
see "Output unit".
9.10.7 Calibration with partially filled vessel (wet calibration)
Example:
This example explains a wet calibration for cases in which it is not possible to empty the
vessel and then fill it to 100%.
During this wet calibration, a level of 20% is used as the calibration point for "Empty" and a
level of "25%" is used as the calibration point for "Full".
The calibration is then extended to 0% to 100% and lower range-value (LRV)/upper
range-value (URV) are adapted accordingly.
Prerequisite:
• The default value in level mode for the calibration mode is "Wet".
• This value can be adjusted: Menu path: Setup → Extended setup → Level → Calibration
mode
Description
1Select the "Level" measuring mode via the
"Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the
span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the
‣
setting for the span (URV) must be
checked in the "Setup" operating menu and
readjusted if necessary.
2Set the value for "Empty calib." with the acting
pressure for the level, e.g. 20 %
Menu path: Setup → Extended setup → Level →
Empty calib.
A0018841
1See table, step 2
2See table, step 3
Endress+Hauser53
Page 54
CommissioningWaterpilot FMX21
Description
3Set the value for "Full calib." with the acting
pressure for the level, e.g. 25 %.
Menu path: Setup → Extended setup → Level →
Full calib.
4The values for the pressure when the vessel is
full or empty are measured automatically
during adjustment. The transmitter
automatically sets the pressure values that are
most suitable for "Empty calib." and "Full calib."
as the minimum and maximum pressure which
generates the output current. For this reason,
the correct upper-range value (URV) and the
correct lower-range value (LRV) must be set.
If the process uses a medium other than that on which the calibration was based,
the new density must be specified in the "Process density" parameter. In this
case, you have to enter the various densities via the following menu path:
• Setup → Extended setup → Level → Adjust density (034) e.g. 1.0 kg/l for water)
• Setup → Extended setup → Level → Process density (035) e.g. 0.8 kg/l for oil)
9.10.8 Level measurement with absolute pressure probe and external
pressure signal (electrical differential pressure)
Example:
In this example, a Waterpilot FMX21 and a Cerabar M device (each with an absolute
pressure measuring cell) are connected via the common communication bus. The level can
thus be measured in a deep well, with simultaneous compensation for the effect of
atmospheric pressure.
54Endress+Hauser
Page 55
Waterpilot FMX21Commissioning
FXN520
OPEN
CLOSE
90°
90°
Warning:
Avoid electrostatic charge in explosive atmosphere.
See instructions
Terminal Box for FMX21
12
4
3
5
1Fieldgate FXA520
2Multidrop connector FXN520
3Terminal box (can be ordered as an accessory)
4Cerabar M absolute pressure (atmospheric pressure)
5Waterpilot absolute pressure (level)
Adjustment of the level sensor (Waterpilot)
1Select the "Level" measuring mode via the "Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in the "Setup"
‣
operating menu and readjusted if necessary.
2Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3The sensor is unpressurized, perform a position adjustment → 40
4Switch on burst mode via the "Burst mode" parameter.
Menu path: Expert → Communication → HART config
5Set the output current to "Fixed" 4.0 mA via the "Current Mode" parameter.
Menu path: Expert → Communication → HART config
6Configure an address ≠0 using the "Bus address" parameter, e.g. bus address = 1.
(HART 5.0 master: Range 0 to 15, where address = 0 calls up the "Signaling" setting; HART 6.0 master:
Range 0 to 63)
Menu path: Expert → Communication → HART config
A0018821
Endress+Hauser55
Page 56
CommissioningWaterpilot FMX21
Adjustment of the level sensor (Waterpilot)
1Select the "Level" measuring mode via the "Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in the "Setup"
‣
operating menu and readjusted if necessary.
2Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3The sensor is unpressurized, perform a position adjustment → 40
4Set the output current to "Fixed" 4.0 mA via the "Current Mode" parameter.
Menu path: Expert → Communication → HART config
5Configure an address ≠0 using the "Bus address" parameter, e.g. bus address = 2.
(HART 5.0 master: Range 0 to 15, where address = 0 calls up the "Signaling" setting; HART 6.0 master:
Range 0 to 63)
Menu path: Expert → Communication → HART config
6Activate the reading of a value sent externally in burst mode via the "Electr. delta P" parameter.
Menu path: Expert → Application
7Perform level adjustment (wet or dry)
8Result: The measured value output by the atmospheric pressure sensor equals the level in the deep well
(differential signal) and can be read out by means of a HART request for the address of the atmospheric
pressure sensor.
• It is not permissible to reverse the assignment of the measuring points to the direction of
communication.
• The measured value of the transmitting device (via burst) must always be greater than
the measured value of the receiving device (via "Electr. Delta P" mode).
• Adjustments that result in an offset of the pressure values (e.g. position adjustment,
trim) must always be performed in accordance with the individual sensor and its
orientation and independently of the "Electr. Delta P" application.
• Other settings result in non-permitted use of the "Electr. Delta P" mode and can lead to
incorrect measured values.
9.11 Automatic density compensation
9.11.1 Automatic density compensation with the internally measured
sensor temperature
Example:
In this example, a Waterpilot FMX21 is used for level measurement in water. The change
in the water density caused by changing temperatures is automatically factored into the
level signal by activating the automatic density compensation.
56Endress+Hauser
Page 57
Waterpilot FMX21Commissioning
1
2
A0018822
1HART master, e.g. PLC (programmable logic controller)
2Waterpilot FMX21
Adjustment of the Waterpilot for level measurement
1Select the "Level" measuring mode via the "Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in the "Setup"
‣
operating menu and readjusted if necessary.
2Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3The sensor is unpressurized, perform a position adjustment → 40
4Set the "Auto dens. corr." parameter to Sensor temperature.
Menu path: Expert → Application
5Perform level adjustment (wet or dry)
6Result: The measured value output by the Waterpilot corresponds to the level in the deep well corrected
by means of the density characteristic line of the water.
9.11.2 Automatic density compensation using an integrated Pt100
for calculation in a suitable HART master (e.g. PLC)
Example:
In this example, the FMX21 with an integrated Pt100 is connected via the common
communication bus to any temperature head transmitter with HART communication (e.g.
TMT182). The temperature and pressure signal are transmitted to the HART master (e.g.
PLC), where a corrected level value can be generated using a stored linearization table or
density function (of a chosen medium). A pressure signal and a temperature signal can
thus be generated with a chosen density function to compensate for a level.
Adjustment of the Waterpilot for level measurement
1Select the "Level" measuring mode via the "Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in the "Setup"
‣
operating menu and readjusted if necessary.
2Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3The sensor is unpressurized, perform a position adjustment → 40
4Set the output current to "Fixed" 4.0 mA via the "Current Mode" parameter.
Menu path: Expert → Communication → HART config
5Perform level adjustment (wet or dry)
6Configure an address ≠0 using the "Bus address" parameter, e.g. bus address = 1.
(HART 5.0 master: Range 0 to 15, where address = 0 calls up the "Signaling" setting; HART 6.0 master:
Range 0 to 63)
Menu path: Expert → Communication → HART config
The output current of the temperature head transmitter used must also be set to "Fixed" and have a
HART address other than zero (e.g. address = 2).
7Result: By calculating the pressure signal and temperature signal in a suitable HART master (e.g. PLC), a
corrected level value can be determined for a chosen medium using a suitable density function.
9.11.3 Automatic density compensation using an external
temperature signal for calculation in the FMX21
Example:
In this example, the FMX21 with an integrated Pt100 is connected to a HART-compliant
temperature head transmitter via the common communication bus. In this case, the signal
of the Pt100 is analyzed using a HART-compliant (min. HART 5.0) temperature head
transmitter that supports burst mode. The change in the water density caused by changing
temperatures is automatically factored into the level signal by activating the automatic
density compensation.
Configuring the HART-compliant temperature head transmitter (min. HART 5.0) with burst
function
The output current of the temperature head transmitter used should be set to "Fixed" and must have a
HART address other than zero (e.g. address = 1). The burst function must then be switched on with HART
command 1. This step should be performed before the procedure described below in order to avoid a
HART input error of the FMX21 being output during commissioning.
1Select the "Level" measuring mode via the "Measuring mode" parameter.
Menu path: Setup → Measuring mode
WARNING
L
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in the "Setup"
‣
operating menu and readjusted if necessary.
2Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3The sensor is unpressurized, perform a position adjustment → 40
4Set the "Auto dens. corr." parameter to "External value".
Menu path: Expert → Application
5Perform level adjustment (wet or dry)
Result: The measured value output by the Waterpilot equals the level in the deep well corrected by means
of the density characteristic line of the water.
The TMT182 temperature head transmitter is not suitable for this configuration.
9.12 Linearization
9.12.1 Semi-automatic entry of a linearization table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m3.
Endress+Hauser59
Page 60
CommissioningWaterpilot FMX21
3.5
0
3.0
V
[m]
3
h
[m]
0
v
h
i
v
Prerequisite:
• The tank can be filled or emptied. The linearization characteristic must rise or fall
continuously.
• The "Level" measuring mode has been selected.
• A level calibration has been performed.
• For a description of the parameters mentioned, see the "Description of device
parameters" section .
WARNING
L
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in
‣
the "Setup" operating menu and readjusted if necessary.
Menu path: Setup → Extended setup →
Linearization → Unit after lin.
3Fill the tank to the height of the 1st point.
A0018843
hHeight
vVolume
4Enter the number of the point in the table
using the "Line-numb" parameter e.g. 1.
Menu path: Setup → Extended setup →
Linearization → Line numb
The current level is displayed via the "X-value"
parameter.
Menu path: Setup → Extended setup →
Linearization → X-val
Enter the associated volume value via the "Yval" parameter, here 0 m3 for example, and
confirm value.
Menu path: Setup → Extended setup →
Linearization → Y-val
5To enter another point in the table, continue
filling the tank and select the "Next point"
option via the "Edit table" parameter. Enter the
next point as explained in Step 4.
Menu path: Setup → Extended setup →
Linearization → Edit table
A0017670
60Endress+Hauser
Page 61
Waterpilot FMX21Commissioning
3.5
0
3.0
V
[m]
3
h
[m]
0
Description
6Once all the points have been entered in the
table, select the "Activate table" option via the
"Lin. mode" parameter.
Menu path: Setup → Extended setup →
Linearization → Lin. mode
7Result:
Result: The measured value after linearization
is displayed.
hHeight
iCurrent value
vVolume
• Error message F510 "Linearization" and alarm current as long as the table is being
entered and until the table is activated.
• The lower-range value (= 4mA) is defined by the smallest point in the table.
The upper-range value (= 20mA) is defined by the largest point in the table.
• Using the parameters "Set LRV" and "Set URV", you can change the allocation of the
volume/mass values to the current values.
9.12.2 Manual entry of a linearization table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m3.
Prerequisite:
• This is a theoretical calibration, i.e. the points for the linearization table are known.
• The "Level" measuring mode has been selected.
• A level calibration has been performed.
• The linearization characteristic must rise or fall continuously.
• For a description of the parameters mentioned, see the "Description of device
parameters" section .
WARNING
L
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in
‣
the "Setup" operating menu and readjusted if necessary.
Menu path: Setup → Extended setup →
Linearization → Unit after lin.
A0018843
hHeight
vVolume
Endress+Hauser61
Page 62
CommissioningWaterpilot FMX21
v
h
i
v
Description
3Enter the number of the point in the table
using the "Line-numb" parameter e.g. 1.
Menu path: Setup → Extended setup →
Linearization → Line numb
The level is entered via the "X-val" parameter,
here 0 m for example. Confirm your entry.
Menu path: Setup → Extended setup →
Linearization → X-val
Enter the associated volume value via the "Yval" parameter, here 0 m3 for example, and
confirm value.
Menu path: Setup → Extended setup →
Linearization → Y-val
4To enter another point in the table, select the
"Next point" option via the "Edit table"
parameter. Enter the next point as explained in
Step 3.
Menu path: Setup → Extended setup →
Linearization → Edit table
5Once all the points have been entered in the
table, select the "Activate table" option via the
"Lin. mode" parameter.
Menu path: Setup → Extended setup →
Linearization → Lin. mode
6Result:
Result: The measured value after linearization
is displayed.
hHeight
iCurrent value
vVolume
A0017670
• Error message F510 "Linearization" and alarm current as long as the table is being
entered and until the table is activated.
• Error message F511/F512 "Linearization" and alarm current as long as the
linearization table consists of fewer than 2 points.
• The lower-range value (= 4mA) is defined by the smallest point in the table.
The upper-range value (= 20mA) is defined by the largest point in the table.
• Using the parameters "Set LRV" and "Set URV", you can change the allocation of the
volume/mass values to the current values.
9.13 Manual entry of a linearization table via operating
tool
The following options are available to you with an operating tool that is based on FDT
technology (e.g. FieldCare), you can enter linearization using a module specially designed
for this purpose. This provides you with an overview of the selected linearization, even
during entry. In addition, it is possible to configure different tank shapes in FieldCare
("Device operation" → "Device functions" → "Additional functions" → "Linearization table"
menu).
The linearization table may also be entered manually point by point in the operating
tool menu (see section).
62Endress+Hauser
Page 63
Waterpilot FMX21Commissioning
9.14 Backing up or duplicating the device data
The following options are available to you with an operating tool that is based on FDT
technology (e.g. FieldCare):
• Storage/recovery of configuration data.
• Duplication of device parameters.
• Transfer of all relevant parameters when replacing electronic inserts.
Use the following parameter for this:
Download select. (visible only in FieldCare)
NavigationExpert → System → Management → Download select.
DescriptionSelection of data packages for up/download function in Fieldcare and PDM.
PrerequisiteDIP switch set to "SW" and "Damping" set to "on". If you download using the factory setting
"Configuration copy", all parameters required for a measurement will be downloaded. The
functionality of the "Electronics replace" setting is reserved for Endress+Hauser Service and
can be accessed only if the correct device access code is entered.
Options• Configuration copy: This option overwrites general configuration parameters with the
exception of the serial number, order number, calibration, pos. zero adjust, application
and day information.
• Device replacement: This option overwrites general configuration parameters with the
exception of the serial number, order number, calibration and position adjustment.
• Electronics replace: This option overwrites general configuration parameters.
Factory settingConfiguration copy
Endress+Hauser63
Page 64
Diagnostics and troubleshootingWaterpilot FMX21
10 Diagnostics and troubleshooting
10.1 Troubleshooting
General errors
ErrorPossible causeSolution
Device is not responding.Supply voltage does not match the
specification on the nameplate.
Supply voltage has incorrect polarity.Reverse polarity of supply voltage.
Connecting cables are not in contact
with the terminals.
Output current < 3.6 mASignal line is not wired correctly.
Electronics unit is defective.
Device measures incorrectly.Configuration errorCheck and correct parameter
HART communication is not
working.
Communication resistor missing or
incorrectly installed.
Commubox is not properly connected.Connect Commubox correctly .
Commubox is not set to "HART".Set Commubox selector switch to
Apply correct voltage.
Check the connection of the cables
and correct if necessary.
Check wiring.
configuration (see below).
Install the communication resistor
(250 Ω) correctly.
"HART".
10.2 Diagnostic events
10.2.1 Diagnostic message
Faults detected by the self-monitoring system of the measuring device are displayed as a
diagnostic message in alternation with the measured value display.
Status signals
The table → 65 lists the messages that may occur. The ALARM STATUS parameter
shows the message with the highest priority. The device has four different status
information codes according to NE107:
"Failure"
A device error has occurred. The measured value is no longer valid.
A0013956
"Maintenance required"
Maintenance is required. The measured value remains valid.
A0013957
"Function check"
The device is in service mode (e.g. during a simulation).
A0013959
"Out of specification"
The device is being operated:
• Outside its technical specifications (e.g. during warm-up or cleaning).
A0013958
• Outside the parameter configuration undertaken by the user (e.g. level outside of configured span)
Diagnostic event and event text
The fault can be identified by means of the diagnostic event.
64Endress+Hauser
Page 65
Waterpilot FMX21Diagnostics and troubleshooting
The event text helps you by providing information on the fault.
Diagnostic event
Status signalEvent numberEvent text
↓↓↓
Example
A0013958
841Sensor range
3-digit number
If two or more diagnostic events are pending simultaneously, only the diagnostic message
with the highest priority is shown.
Other diagnostic messages that are pending can be viewed in the Diagnostic list
submenu .
Past diagnostic messages that are no longer pending are shown in the Event logbook
submenu .
10.2.2 List of diagnostic events
General messages
Diagnostic eventReasonCorrective measure
CodeDescription
0No error--
"F" messages
Diagnostic eventReasonCorrective measure
CodeDescription
F002 Sensor unknownSensor does not suit the device (electronic sensor
nameplate).
F062 Sensor conn.• Faulty sensor.
• Electromagnetic effects are greater than
specifications in the technical data. This message
appears for a short time only.
F081 Initialization• Faulty sensor.
• Electromagnetic effects are greater than
specifications in the technical data. This message
appears for a short time only.
F083 Memory content• Faulty sensor.
• Electromagnetic effects outside the permitted
range. This message appears for a short time only.
F140 Working range P • Overpressure and low pressure present.
• Electromagnetic effects outside the permitted
range.
• Faulty sensor.
F261 Electronic module • Main electronics defective.
• Fault in the main electronics.
F282 Memory• Fault in the main electronics.
• Main electronics defective.
Contact Endress+Hauser
Service
• Check the sensor module
cable
• Contact Endress+Hauser
Service
• Check sensor cable
• Contact Endress+Hauser
Service
• Restart the device
• Contact Endress+Hauser
Service
• Check the process pressure
• Check sensor range
Restart the device
Restart the device
Endress+Hauser65
Page 66
Diagnostics and troubleshootingWaterpilot FMX21
Diagnostic eventReasonCorrective measure
CodeDescription
F283 Memory content• Main electronics defective.
• Electromagnetic effects are greater than
specifications in the technical data.
• The supply voltage is disconnected when writing.
• An error occurred when writing.
F411 Up-/download• File is defective.
• During the download, the data are not correctly
transmitted to the processor, e.g. because of open
cable connections, spikes (ripple) on the supply
voltage or electromagnetic effects.
F510 LinearizationThe linearization table is being edited.• Conclude entries
F511 LinearizationThe linearization table consists of less than 2 points.• Table too small
F512 LinearizationThe linearization table is not monotonic increasing or
decreasing.
F841 Sensor range• Overpressure or low pressure present.
• Faulty sensor.
F882 Input signalExternal measured value is not received or displays a
failure status.
Perform a reset
• Repeat download
• Use other file
• Perform a reset
• Select "linear"
• Correct table
• Activate table
• Table not monotonic
• Correct table
• Activate table
• Check the pressure value
• Contact Endress+Hauser
Service
• Check the bus
• Check source device
• Check the setting
"M" messages
Diagnostic eventReasonCorrective measure
CodeDescription
M002 Sens. unknown Sensor does not suit the device (electronic sensor
nameplate). Device continues measuring.
M283 Memory
content
M431 AdjustmentThe calibration carried out would result in values that
M434 Scaling• Values for calibration (e.g. lower-range value and
M438 Data set• The supply voltage is disconnected when writing.
M882 Input signalExternal measured value displays a warning status.• Check the bus
• Cause as indicated for F283.
• Correct measurement can continue as long as you
do not need the peakhold indicator function.
exceed or fall below the nominal range of the sensor.
upper-range value) are too close together.
• Lower-range value and/or upper-range value exceed
or fall below the range limits of the sensor.
• The sensor was replaced and the customer-specific
configuration does not suit the sensor module.
• Unsuitable download carried out.
• An error occurred when writing.
Contact Endress+Hauser
Service
Perform a reset
• Check the measuring
range
• Check position
adjustment
• Check the setting
• Check the measuring
range
• Check the setting
• Contact Endress+Hauser
Service
• Check the setting
• Restart the device
• Check the source device
• Check the setting
66Endress+Hauser
Page 67
Waterpilot FMX21Diagnostics and troubleshooting
"C" messages
Diagnostic eventReasonCorrective measure
CodeDescription
C412 Backup in prog. Downloading.Wait for download to
complete.
C482 Simul. outputSimulation of the current output is switched on, i.e. the
device is not measuring at present.
C484 Error simul.Simulation of an error status is switched on, i.e. the
device is not measuring at present.
C485 Measure simul.Simulation is switched on, i.e. the device is not
measuring at present.
C824 Process pressure • Overpressure or low pressure present.
• Electromagnetic effects outside the permitted range.
This message appears for a short time only.
End the simulation
End the simulation
End the simulation
• Check the pressure
value
• Restart the device
• Perform a reset
"S" messages
Diagnostic eventReasonCorrective measure
CodeDescription
S110 Operational
range T
S140 Working range P
LP/HP
S822 Process temp.
LP/HP
S841 Sensor range• Overpressure or low pressure present.
S971 Adjustment• The current is outside the permitted range from 3.8
• High temperature or low temperature present.
• Electromagnetic effects outside the permitted range.
• Faulty sensor.
• Overpressure or low pressure present.
• Electromagnetic effects outside the permitted range.
• Faulty sensor.
• The temperature measured in the sensor is higher
than the upper nominal temperature of the sensor.
• The temperature measured in the sensor is lower
than the lower nominal temperature of the sensor.
• Faulty sensor.
to 20.5 mA.
• The present pressure value is outside the configured
measuring range (but within the sensor module
range, if applicable).
• The calibration carried out would result in values
that exceed or fall below the nominal range of the
sensor.
• Check process
temperature
• Check the temperature
range
• Check the process
pressure
• Check sensor range
• Check temperature
• Check the setting
• Check the pressure value
• Contact Endress+Hauser
Service
• Check the pressure value
• Check the measuring
range
• Check the setting
10.3 Troubleshooting specific to Waterpilot FMX21 with
optional Pt100
Error descriptionReasonCorrective action
No measuring signal4 to 20 mA cable not connected
correctly
No power supplied via the 4 to 20 mA
cable
Supply voltage too low (at least 10.5 V
DC)
Endress+Hauser67
Connect device as per.
Check current loop.
• Check supply voltage.
• Overall resistance greater than
max. load resistance
Page 68
Diagnostics and troubleshootingWaterpilot FMX21
Error descriptionReasonCorrective action
Waterpilot defectiveReplace the Waterpilot.
Temperature measured value
is inaccurate/incorrect (only
for Waterpilot FMX21 with
Pt100)
Pt100 connected in 2-wire circuit, cable
resistance was not compensated for
• Compensate the cable resistance.
• Connect Pt100 as 3-wire or 4-wire
circuit.
10.4 Troubleshooting specific to TMT182 temperature
head transmitter
Error descriptionReasonCorrective action
No measuring signal4 to 20 mA cable not connected
correctly
No power supplied via the 4 to 20 mA
cable
Supply voltage too low (at least 10.5 V
DC)
Error current ≤ 3.6 mA or ≥ 21mAPt100 not connected correctlyConnect device as per.
4 to 20 mA cable not connected
correctly
Pt100 resistance thermometer
defective
Temperature head transmitter
defective
Measured value is inaccurate/
incorrect
Pt100 connected in 2-wire circuit,
cable resistance was not compensated
for
Connect device as per.
Check current loop.
• Check supply voltage.
• Overall resistance greater than
max. load resistance
Connect device as per.
Replace the Waterpilot.
Replace the temperature head
transmitter.
• Compensate the cable
resistance.
• Connect Pt100 as 3-wire or 4wire circuit.
10.5 Response of output to errors
The behavior of the current output in case of fault is defined by the following
parameters:
• "Alarm behav. P (050)"
• "Output fail mode (190)"
• "High alarm curr. (052)"
68Endress+Hauser
Page 69
Waterpilot FMX21Diagnostics and troubleshooting
10.6 Firmware history
DateFirmware versionModificationsDocumentation
05.200901.00.zzOriginal firmware.
Compatible with:
• FieldCare from version 2.02.00
• Field Communicator DXR375 with Device Rev.: 1, DD Rev.: 1
BA00380P/00/EN/08.09
Endress+Hauser69
Page 70
MaintenanceWaterpilot FMX21
11 Maintenance
No special maintenance work is required.
Terminal box: Keep the pressure compensation tube and GORE-TEX® filter free from
contamination.
11.1 Exterior cleaning
Please note the following points when cleaning the device:
• The cleaning agents used should not corrode the surface and the seals.
• Mechanical damage to the process isolating diaphragm, e.g. due to sharp objects, must
be avoided.
• Only clean the terminal box with water or with a cloth dampened with very diluted
ethanol.
70Endress+Hauser
Page 71
Waterpilot FMX21Repairs
12 Repairs
12.1 General notes
12.1.1 Repair concept
Repairs are not possible.
12.1.2 Replacing a device
Once a complete device has been replaced, the parameters can be transferred back into the
device using FieldCare:
Prerequisite: The configuration of the old device was saved previously to the computer
using FieldCare.
You can continue to measure without performing a new calibration.
12.2 Spare parts
• Some replaceable measuring device components are identified by means of a spare part
nameplate. This contains information about the spare part.
• All the spare parts for the measuring device along with the order code are listed In the
W@M Device Viewer (www.endress.com/deviceviewer) and can be ordered. If available,
users can also download the associated Installation Instructions.
Measuring device serial number:
• Located on the device and spare part nameplate.
• Can be read out via the "Serial number" parameter in the "Instrument info" submenu.
12.3 Return
The measuring device must be returned in the event of a factory calibration, or if the
wrong device has been ordered or delivered.
As an ISO-certified company and due to legal requirements,
Endress+Hauser is required to follow certain procedures when handling returned products
that have been in contact with a medium. To ensure swift, safe and professional device
returns, please read the return procedures and conditions on the Endress+Hauser website
at www.services.endress.com/return-material
Select country.
‣
The web site of the responsible sales office opens with all of the relevant
information relating to returns.
1.If the desired country is not listed:
Click on the "Choose your location" link.
An overview of Endress+Hauser sales offices and representatives opens.
2.Contact your Endress+Hauser sales office or representative.
12.4 Disposal
When disposing, separate and recycle the device components based on the materials.
Endress+Hauser71
Page 72
Overview of the operating menuWaterpilot FMX21
13 Overview of the operating menu
Depending on the parameter configuration, not all submenus and parameters are
available. Information on this can be found in the parameter description under
"Prerequisite".
Full calib. ("Level" measuring mode and "Calibration mode" = wet")→ 90
Set LRV ("Pressure" measuring mode)→ 86
Set URV ("Pressure" measuring mode)→ 86
Damping→ 84
Level before Lin ("Level" measuring mode)→ 92
Press after damping→ 87
Setup →Extended setupDescription
Code definition→ 80
Device tag→ 81
Operator code→ 80
Setup →Extended setup →Level
("Level" measuring mode)
Level selection→ 88
Output unit→ 88
Height unit→ 88
Calibration mode→ 89
Empty calib.→ 89
Empty pressure→ 89
Empty height→ 90
Full calib.→ 90
Full pressure→ 90
Full height→ 91
Adjust density→ 91
Process density→ 92
Level before lin→ 92
Description
Setup →Extended setup →LinearizationDescription
Lin. mode→ 93
Unit after lin.→ 93
Line-numb:→ 93
72Endress+Hauser
Page 73
Waterpilot FMX21Overview of the operating menu
Setup →Extended setup →LinearizationDescription
X-val→ 94
Y-val→ 94
Edit table→ 94
Tank description→ 95
Tank content→ 95
Setup →Extended setup →Current outputDescription
Alarm behav. P→ 98
Output fail mode→ 98
Max. alarm curr.→ 98
Set min. current→ 99
Output current→ 98
Get LRV (only "Pressure")→ 99
Set LRV→ 99
Get URV (only "Pressure")→ 99
Set URV→ 100
DiagnosisDescription
Diagnostic code→ 112
Last diag. code→ 112
Min. meas. press.→ 112
Max. meas. press.→ 112
Diagnosis →Diagnostics ListDescription
Diagnostic 1→ 114
Diagnostic 2→ 114
Diagnostic 3→ 114
Diagnostics 4→ 114
Diagnostics 5→ 114
Diagnostics 6→ 114
Diagnostics 7→ 114
Diagnostics 8→ 114
Diagnostics 9→ 114
Diagnostics 10→ 114
Diagnosis →Event logbookDescription
Last diag. 1→ 115
Last diag. 2→ 115
Last diag. 3→ 115
Last diag. 4→ 115
Last diag. 5→ 115
Last diag. 6→ 115
Endress+Hauser73
Page 74
Overview of the operating menuWaterpilot FMX21
Diagnosis →Event logbookDescription
Last diag. 7→ 115
Last diag. 8→ 115
Last diag. 9→ 115
Last diag. 10→ 115
Diagnosis →Instrument InfoDescription
Firmware Version→ 81
Serial number→ 81
Ext. order code→ 81
Order Identifier→ 82
Cust. tag number→ 81
Device tag→ 81
ENP version→ 82
Config. counter→ 113
LRL sensor→ 96
URL sensor→ 96
Manufacturer ID→ 104
Device type→ 104
Device revision→ 104
Diagnosis →Measured valuesDescription
Level before lin→ 92
Tank content→ 95
Pressure measured→ 86
Sensor pressure→ 86
Corrected press.→ 87
Press after damping→ 87
Sensor temp.→ 85
Diagnosis →SimulationDescription
Simulation mode→ 116
Sim. pressure→ 116
Sim. level→ 116
Sim. tank cont.→ 117
Sim. current→ 117
Sim. alarm/warning→ 117
Diagnosis →Enter reset codeDescription
Enter reset code→ 83
74Endress+Hauser
Page 75
Waterpilot FMX21Overview of the operating menu
13.1 Overview of parameters in the "Expert" menu
The following table lists all of the parameters that can be included in the "Expert"
menu. The page reference indicates where a description of the parameter can be
found in the manual.
Depending on the device version and the parameter configuration, not all submenus
and parameters are available in every device. Information on this can be found in the
parameter description under "Prerequisite".
DescriptionPosition adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known.
Example• Measured value = 2.2 mbar (0.033 psi)
• You correct the measured value via the "Pos. zero adjust" parameter with the "Confirm"
option. i.e. This means that you are assigning the value 0.0 to the pressure present.
• Measured value (after position adjustment) = 0.0 mbar
• The current value is also corrected.
Options• Confirm
• Cancel
Factory settingCancel
Calib. offset
Write permissionService engineers/Expert
DescriptionPosition adjustment – the pressure difference between the set point and the measured
pressure must be known.
Example• Measured value = 982.2 mbar (14.73 psi)
• You use the "Calib. offset" parameter to correct the measured value with the value
entered, e.g. 2.2 mbar (0.033 psi). i.e. This means that you are assigning the value
980.0 (14.7 psi) to the pressure present.
• Measured value (after pos. zero adjust) = 980.0 mbar (14.7 psi)
DescriptionSelect the method for calculating the level
Options• In pressure
If this option is selected, specify two pressure/level value pairs. The level value is
displayed directly in the unit that you select via the "Output unit" parameter.
• In height
If this option is selected, specify two height/level value pairs. From the measured
pressure, the device first calculates the height using the density. Along with the two
value pairs specified, this information is then used to calculate the level in the "Output
unit" selected.
Factory settingIn pressure
Output unit
DescriptionSelect the unit for the measured value display for the level before linearization.
NoteThe selected unit is used only to describe the measured value i.e. when a new output unit
Wet calibration takes place by filling and emptying the vessel. In the case of two
different levels, the level, volume, mass or percentage value entered is assigned to the
pressure measured at this point in time ("Empty calib." and "Full calib." parameters).
• Dry
Dry calibration is a theoretical calibration. For this calibration, you specify two pressurelevel value pairs or height-level value pairs via the following parameters: "Empty calib.",
"Empty pressure", "Empty height", "Full calib.", "Full pressure", "Full height".
DescriptionEnter the output value for the lower calibration point (vessel is empty). The unit defined in
"Output unit" must be used here.
Note• For wet calibration, the level (e.g. empty or partially filled vessel) must actually be
present. The associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel empty) does not have to be available. For
the "In pressure" level selection, the associated pressure must be entered in the "Empty
pressure" parameter. The associated height must be entered in the "Empty height"
parameter for the "In height" level selection.
DescriptionEnter the output value for the upper calibration point (vessel full). The unit defined in
"Output unit" must be used here.
Note• For wet calibration, the level (e.g. empty or partially filled vessel) must actually be
present. The associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel full) does not have to be available. For the
"In pressure" level selection, the associated pressure must be entered in the "Full pressure"
parameter. The associated height has to be entered in the "Full height" parameter for the
"In height" level selection.
DescriptionEnter a new density value for density correction. The calibration was carried out with the
medium water, for example. Now the vessel is to be used for another medium with
another density. The calibration is corrected appropriately by entering the new density
value in the "Process Density" parameter.
Input: Auto dens. corr. = Off
Display: Auto dens. corr. ≠ Off
NoteIf, after completing a wet calibration, you change to dry calibration using the "Calibration
mode" parameter, the density for the "Adjust density" and "Process density" parameters
must be entered correctly before changing the calibration mode.
Factory setting1.0
Level before lin.
Write permissionNo write permissions. Parameter is read only.
DescriptionDisplays the level value prior to linearization.
The level is output without being converted beforehand. "Level before lin" is output.
• Erase table
The existing linearization table is deleted.
• Manual entry (sets the table to edit mode, an alarm is output):
The value pairs of the table (X-value and Y-value) are entered manually.
• Semi-automatic entry (sets the table to edit mode, an alarm is output):
The vessel is emptied or filled in stages in this entry mode. The device automatically
records the level value (X-value). The associated volume, mass or % value is entered
manually (Y-value).
• Activate table
The table entered is activated and checked with this option. The device shows the level
after linearization.