Endress+Hauser Proline Promag 50 Operating Instructions Manual

Page 1

Operating Instructions

Proline Promag 50 HART
Electromagnetic flow measuring system
BA00046D/06/EN/14.11 71136623
Valid as of version V 2.03.XX (device software)
Page 2
Page 3
Promag 50 Table of contents

Table of contents

1 Safety instructions . . . . . . . . . . . . . . . . 5
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Installation, commissioning and operation . . . . . . . . 5
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Notes on safety conventions and icons . . . . . . . . . . . 6
2 Identification . . . . . . . . . . . . . . . . . . . . 7
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.1 Nameplate of the transmitter . . . . . . . . . . . . 7
2.1.2 Nameplate of the sensor . . . . . . . . . . . . . . . 8
2.1.3 Nameplate, connections . . . . . . . . . . . . . . . 9
2.2 Certificates and approvals . . . . . . . . . . . . . . . . . . . . 9
2.3 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 10
3 Installation . . . . . . . . . . . . . . . . . . . . . 11
3.1 Incoming acceptance, transport and storage . . . . . . 11
3.1.1 Incoming acceptance . . . . . . . . . . . . . . . . . 11
3.1.2 Transport . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 13
3.2.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.2 Mounting location . . . . . . . . . . . . . . . . . . . 13
3.2.3 Orientation . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.4 Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.5 Foundations, supports . . . . . . . . . . . . . . . . 17
3.2.6 Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.7 Nominal diameter and flow rate . . . . . . . . 18
3.2.8 Length of connecting cable . . . . . . . . . . . . 20
3.3 Installation instructions . . . . . . . . . . . . . . . . . . . . . 21
3.3.1 Installing the Promag D sensor . . . . . . . . . . 21
3.3.2 Installing the Promag L sensor . . . . . . . . . . 24
3.3.3 Installing the Promag W sensor . . . . . . . . . 27
3.3.4 Installing the Promag P sensor . . . . . . . . . . 32
3.3.5 Installing the Promag H sensor . . . . . . . . . . 36
3.3.6 Turning the transmitter housing . . . . . . . . 39
3.3.7 Turning the onsite display . . . . . . . . . . . . . 40
3.3.8 Installing the wall-mount housing . . . . . . . 41
3.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 43
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 44
4.1 Connecting the remote version . . . . . . . . . . . . . . . 44
4.1.1 Connecting Promag D, L, W, P, H . . . . . . 44
4.1.2 Cable specifications . . . . . . . . . . . . . . . . . . 49
4.2 Connecting the measuring unit . . . . . . . . . . . . . . . 50
4.2.1 Connecting the transmitter . . . . . . . . . . . . 50
4.2.2 Terminal assignment . . . . . . . . . . . . . . . . . 52
4.2.3 HART connection . . . . . . . . . . . . . . . . . . . 52
4.3 Potential equalization . . . . . . . . . . . . . . . . . . . . . . 53
4.3.1 Potential equalization for Promag D . . . . . . 53
4.3.2 Potential equalization for Promag W, P, L . 53
4.3.3 Potential equalization for Promag H . . . . . . 53
4.3.4 Exampels for potential equalization connections
for Promag D . . . . . . . . . . . . . . . . . . . . . . . 54
4.3.5 Exampels for potential equalization connections
for Promag L, W, P . . . . . . . . . . . . . . . . . . 55
4.4 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . 56
4.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 57
5 Operation . . . . . . . . . . . . . . . . . . . . . . 58
5.1 Display and operating elements . . . . . . . . . . . . . . . 58
5.2 Brief operating instructions on the function matrix . 59
5.2.1 General notes . . . . . . . . . . . . . . . . . . . . . . 60
5.2.2 Enabling the programming mode . . . . . . . . 60
5.2.3 Disabling the programming mode . . . . . . . . 60
5.3 Displaying error messages . . . . . . . . . . . . . . . . . . . 61
5.3.1 Type of error . . . . . . . . . . . . . . . . . . . . . . . 61
5.3.2 Error message types . . . . . . . . . . . . . . . . . . 61
5.4 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
5.4.1 Operating options . . . . . . . . . . . . . . . . . . . 62
5.4.2 Current device description files . . . . . . . . . 63
5.4.3 Device variables . . . . . . . . . . . . . . . . . . . . . 63
5.4.4 Switching HART write protection on/off . . 63
5.4.5 Universal and common practice HART
commands . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.4.6 Device status and error messages . . . . . . . . 68
6 Commissioning . . . . . . . . . . . . . . . . . . 70
6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
6.2 Switching on the measuring device . . . . . . . . . . . . 70
6.3 Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
6.3.1 "Commissioning" Quick Setup menu . . . . . 71
6.4 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6.4.1 Current output: active/passive . . . . . . . . . . 72
6.5 Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.5.1 Empty-pipe/full-pipe adjustment . . . . . . . . 73
6.6 Data storage device (HistoROM) . . . . . . . . . . . . . . 74
6.6.1 HistoROM/S-DAT (sensor-DAT) . . . . . . . . 74
7 Maintenance . . . . . . . . . . . . . . . . . . . . 75
7.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 75
7.2 Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
8 Accessories . . . . . . . . . . . . . . . . . . . . . 76
8.1 Device-specific accessories . . . . . . . . . . . . . . . . . . . 76
8.2 Measuring principle-specific accessories . . . . . . . . . 76
8.3 Communication-specific accessories . . . . . . . . . . . . 77
8.4 Service-specific accessories . . . . . . . . . . . . . . . . . . . 78
9 Troubleshooting . . . . . . . . . . . . . . . . . 79
9.1 Troubleshooting instructions . . . . . . . . . . . . . . . . . 79
9.2 System error messages . . . . . . . . . . . . . . . . . . . . . . 80
9.3 Process error messages . . . . . . . . . . . . . . . . . . . . . . 82
9.4 Process errors without messages . . . . . . . . . . . . . . 83
9.5 Response of outputs to errors . . . . . . . . . . . . . . . . . 84
9.6 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.6.1 Removing and installing printed circuit boards 87
Endress+Hauser 3
Page 4
Promag 50 Table of contents
9.6.2 Replacing the device fuse . . . . . . . . . . . . . . 91
9.6.3 Replacing the exchangeable electrode . . . . 92
9.7 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.8 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.9 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . 94
10 Technical data . . . . . . . . . . . . . . . . . . . 96
10.1 Technical data at a glance . . . . . . . . . . . . . . . . . . . 96
10.1.1 Application . . . . . . . . . . . . . . . . . . . . . . . . 96
10.1.2 Function and system design . . . . . . . . . . . . 96
10.1.3 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
10.1.4 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
10.1.5 Power supply . . . . . . . . . . . . . . . . . . . . . . . 97
10.1.6 Performance characteristics . . . . . . . . . . . . 98
10.1.7 Operating conditions: Installation . . . . . . . . 98
10.1.8 Operating conditions: Environment . . . . . . 99
10.1.9 Operating conditions: Process . . . . . . . . . 100
10.1.10 Mechanical construction . . . . . . . . . . . . . 105
10.1.11 Human interface . . . . . . . . . . . . . . . . . . . 114
10.1.12 Certificates and approvals . . . . . . . . . . . . 115
10.1.13 Ordering information . . . . . . . . . . . . . . . 116
10.1.14 Accessories . . . . . . . . . . . . . . . . . . . . . . . 116
10.1.15 Documentation . . . . . . . . . . . . . . . . . . . 116
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
4 Endress+Hauser
Page 5
Promag 50 Safety instructions

1 Safety instructions

1.1 Designated use

The measuring device described in this Operating Manual is to be used only for measuring the flow rate of conductive fluids in closed pipes.
A minimum conductivity of 20 μS/cm is required for measuring demineralized water. Most liquids can be measured as of a minimum conductivity of 5 μS/cm.
Examples:
• Acids, alkalis,
• Drinking water, wastewater, sewage sludge,
• Milk, beer, wine, mineral water, etc. Resulting from incorrect use or from use other than that designated the operational safety of the
measuring devices can be suspended. The manufacturer accepts no liability for damages being produced from this.

1.2 Installation, commissioning and operation

Please note the following:
• Installation, connection to the electricity supply, commissioning and maintenance of the device must be carried out by trained, qualified specialists authorized to perform such work by the facility's owner-operator. The specialist must have read and understood this Operating Manual and must follow the instructions it contains.
• The device must be operated by persons authorized and trained by the facility's owner-operator. Strict compliance with the instructions in the Operating Manual is mandatory.
• With regard to special fluids, including fluids used for cleaning, Endress+Hauser will be happy to assist in clarifying the corrosion-resistant properties of wetted materials. However, minor changes in temperature, concentration or in the degree of contamination in the process may result in variations in corrosion resistance. For this reason, Endress+Hauser does not accept any responsibility with regard to the corrosion resistance of wetted materials in a specific application. The user is responsible for the choice of suitable wetted materials in the process.
• If welding work is performed on the piping system, do not ground the welding appliance through the Promag flowmeter.
• The installer must ensure that the measuring system is correctly wired in accordance with the wiring diagrams. The transmitter must be grounded apart from when special protective measures are taken (e.g. galvanically isolated SELV or PELV power supply)
• Invariably, local regulations governing the opening and repair of electrical devices apply.

1.3 Operational safety

Please note the following:
• Measuring systems for use in hazardous environments are accompanied by separate Ex documentation, which is an integral part of this Operating Manual. Strict compliance with the installation instructions and ratings as stated in this supplementary documentation is mandatory. The symbol on the front of this Ex documentation indicates the approval and the certification body (e.g.
• The measuring device complies with the general safety requirements in accordance with EN 61010-1, the EMC requirements of IEC/EN 61326 and NAMUR Recommendations NE 21 and NE 43.
• Depending on the application, the seals of the process connections of the Promag H sensor require periodic replacement.
0 Europe, 2 USA, 1 Canada).
Endress+Hauser 5
Page 6
Safety instructions Promag 50
• When hot fluid passes through the measuring tube, the surface temperature of the housing increases. In the case of the sensor, in particular, users should expect temperatures that can be close to the fluid temperature. If the temperature of the fluid is high, implement sufficient measures to prevent burning or scalding.
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to these Operating Instructions.

1.4 Return

• Do not return a measuring device if you are not absolutely certain that all traces of hazardous substances have been removed, e.g. substances which have penetrated crevices or diffused through plastic.
• Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be charged to the owner-operator.

1.5 Notes on safety conventions and icons

The devices are designed to meet state-of-the-art safety requirements, have been tested, and left the factory in a condition in which they are safe to operate. The devices comply with the applicable standards and regulations in accordance with EN 61010-1 "Safety requirements for electrical equipment for measurement, control and laboratory use". The devices can, however, be a source of danger if used incorrectly or for anything other than the designated use. Consequently, always pay particular attention to the safety instructions indicated in this Operating Manual by the following icons:
#
Warning! "Warning" indicates an action or procedure which, if not performed correctly, can result in injury or a safety hazard. Comply strictly with the instructions and proceed with care.
Caution!
"
"Caution" indicates an action or procedure which, if not performed correctly, can result in incorrect operation or destruction of the device. Comply strictly with the instructions.
!
Note! "Note" indicates an action or procedure which, if not performed correctly, can have an indirect effect on operation or trigger an unexpected response on the part of the device.
6 Endress+Hauser
Page 7
Promag 50 Identification
Promag 50
-20°C (-4°F) <Tamb<+60°C (+140°F)
IP67 / NEMA/Type 4XOrder Code:
Ser.No.:
TAG No.:
50PXX-XXXXXXXXXXXX 12345678901 ABCDEFGHJKLMNPQRST
20-55VAC/16-62VDC
50-60Hz
I-OUT (HART), f-OUT
15VA/W
i
EPD / MSÜ
STATUS-IN
2 3
4 5
9
8
1
N12895
ECC
6
7

2 Identification

2.1 Device designation

The flow measuring system consists of the following components:
• Promag 50 transmitter
• Promag D, Promag L, Promag W, Promag P or Promag H sensor In the compact version, the transmitter and sensor form a single mechanical unit; in the remote
version they are installed separately.

2.1.1 Nameplate of the transmitter

A0005412
Fig. 1: Nameplate specifications for the "Promag 50" transmitter (example)
1 Ordering code/serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits. 2 Power supply, frequency, power consumption 3 Additional information:
EPD/MSÜ: with Empty Pipe Detection
ECC: with electrode cleaning 4 Outputs available:
I-OUT (HART): with current output (HART)
f-OUT (HART): with frequency output
STATUS-IN: with status input (power supply) 5Reserved for information on special products 6 Observe device documentation 7 Reserved for additional information on device version (approvals, certificates) 8 Permitted ambient temperature range 9 Degree of protection
Endress+Hauser 7
Page 8
Identification Promag 50
-20°C (-4°F)<Tamb<+60°C (+140°F) NEMA/Type4X
50PXX-XXXXXXXXXXXX
1.0000/0000
–10 ...150°C/+14 ...300°F°C °F PFA
12345678901 RY ABCDEFGHJKLMNPQRST
DN100 DIN EN PN40/ pnom =PS= 40bar
EPD/MSÜ, R/B
TM:
Order Code:
Materials:
K-factor:
Ser.No.: TAG No.:
PROMAG P
1 2 3
7
13
12
1.4435/316L
Electrodes:
0.2% CAL
4 5
6
10
11
i
9
8
IP67
2007
N12895

2.1.2 Nameplate of the sensor

A0004374
Fig. 2: Nameplate specifications for the "Promag" sensor (example)
1 Ordering code/serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits. 2 Calibration factor with zero point 3 Nominal diameter / Pressure rating 4 Fluid temperature range 5 Materials: lining/measuring electrodes 6Reserved for information on special products 7 Permitted ambient temperature range 8 Observe device documentation 9 Reserved for additional information on device version (approvals, certificates) 10 Calibration tolerance 11 Additional information (examples):
– EPD/MSÜ: with Empty Pipe Detection electrode
– R/B: with reference electrode 12 Degree of protection 13 Flow direction
8 Endress+Hauser
Page 9
Promag 50 Identification
Communication:
Drivers:
Device SW:
ID xxxx (HEX)
XX.XX.XX (WEA) XXXXXXXXXX
Date: DD.MMM.YYYY
Ex-works / ab-Werk/réglages usine
26(+) / 27(-)
NC:
Versorgung / Tension d'alimentation
Observer manuel d'instruction
See operating manual Betriebsanleitung beachten
Active: 0/4...20mA, RL max. = 700 Ohm Passive: 4...20mA, max. 30VDC
Passive: 30VDC, 250mA
Active: 24VDC/25mA (max. 250mA/20ms) Passive: 30VDC, 250mA
(HART:RL.min.=250 OHM)
fmax=1kHz
3...30VDC, Ri = 5kOhm
f-OUT
I-
OUT (HART)
12345678912Ser.No.:
Supply /
24(+) / 25(-)
22(+) / 23(-)
20(+) / 21(-)
N/L­PE
A: NO:
P:
L1/L+
12
319475-00XX
A
P
active passive normally open contact
normallyclosed contact
X
STATUS-OUT
STATUS-IN
X
Update 1 Update 2
2 3
1
4
5
6 7 8 9
10

2.1.3 Nameplate, connections

A0000963
Fig. 3: Nameplate specifications for transmitter (example)
1 Serial number 2 Possible configuration of current output 3 Possible configuration of relay contacts 4 Terminal assignment, cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC Terminal No. 2: N for AC, L– for DC
5 Signals present at inputs and outputs, possible configuration and terminal assignment (20 to 27),
see also "Electrical values of inputs/outputs" 6 Version of device software currently installed 7 Installed communication type, e.g.: HART, PROFIBUS PA, etc. 8 Information on current communication software (Device Revision and Device Description), e.g.:
Dev. 01 / DD 01 for HART 9 Date of installation
Endress+Hauser 9
10 Current updates to data specified in points 6 to 9

2.2 Certificates and approvals

The devices are designed to meet state-of-the-art safety requirements in accordance with sound engineering practice. They have been tested and left the factory in a condition in which they are safe to operate.
The devices comply with the applicable standards and regulations in accordance with EN 61010-1 "Safety requirements for electrical equipment for measurement, control and laboratory use" and with the EMC requirements of IEC/EN 61326/A1.
The measuring system described in this Operating Manual is therefore in conformity with the statutory requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
The measuring system meets the EMC requirements of the Australian Communications and Media Authority (ACMA)
Page 10
Identification Promag 50

2.3 Registered trademarks

KALREZ® and VITON Registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA
TRI-CLAMP
®
Registered trademark of Ladish & Co., Inc., Kenosha, USA
®
HART Registered trademark of the HART Communication Foundation, Austin, USA
HistoROM™, S-DAT®, Field Xpert™, FieldCare Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH
®
®
, Fieldcheck®, Applicator
®
10 Endress+Hauser
Page 11
Promag 50 Installation

3 Installation

3.1 Incoming acceptance, transport and storage

3.1.1 Incoming acceptance

On receipt of the goods, check the following:
• Check the packaging and the contents for damage.
• Check the shipment, make sure nothing is missing and that the scope of supply matches your
order.

3.1.2 Transport

The following instructions apply to unpacking and to transporting the device to its final location:
• Transport the devices in the containers in which they are delivered.
• Do not remove the protective plates or caps on the process connections until you are ready to
install the device. This is particularly important in the case of sensors with PTFE linings.
Special notes on flanged devices
Caution!
"
• The wooden covers mounted on the flanges from the factory protect the linings on the flanges
during storage and transportation. In case of Promag L they are additionally used to hold the lap joint flanges in place. Do not remove these covers until immediately before the device in the pipe.
• Do not lift flanged devices by the transmitter housing, or the connection housing in the case of
the remote version.
#
Transporting flanged devices DN 300 (12")
Use webbing slings slung round the two process connections. Do not use chains, as they could damage the housing.
Warning! Risk of injury if the measuring device slips. The center of gravity of the assembled measuring device might be higher than the points around which the slings are slung. At all times, therefore, make sure that the device does not unexpectedly turn around its axis or slip.
a0004294
Fig. 4: Transporting sensors with DN 300 ( 12")
Endress+Hauser 11
Page 12
Installation Promag 50
Transporting flangeddevices DN > 300 (> 12")
Use only the metal eyes on the flanges for transporting the device, lifting it and positioning the sensor in the piping.
Caution!
"
Do not attempt to lift the sensor with the tines of a fork-lift truck beneath the metal casing. This would buckle the casing and damage the internal magnetic coils.
a0004295
Fig. 5: Transporting sensors with DN > 300 (> 12")

3.1.3 Storage

Please note the following:
• Pack the measuring device in such a way as to protect it reliably against impact for storage (and transportation). The original packaging provides optimum protection.
• The storage temperature corresponds to the operating temperature range of the measuring transmitter and the appropriate measuring sensors ä 99.
• Do not remove the protective plates or caps on the process connections until you are ready to install the device. This is particularly important in the case of sensors with PTFE linings.
• The measuring device must be protected against direct sunlight during storage in order to avoid unacceptably high surface temperatures.
• Choose a storage location where moisture does not collect in the measuring device. This will help prevent fungus and bacteria infestation which can damage the liner.
12 Endress+Hauser
Page 13
Promag 50 Installation
h 2 x DN³

3.2 Installation conditions

3.2.1 Dimensions
The dimensions and installation lengths of the sensor and transmitter can be found in the "Technical Information" for the device in question. This document can be downloaded as a PDF file from www.endress.com. A list of the "Technical Information" documents available is provided in the "Documentation" section on ä 116.

3.2.2 Mounting location

Entrained air or gas bubble formation in the measuring tube can result in an increase in measuring errors. Avoid the following locations:
• Highest point of a pipeline. Risk of air accumulating!
• Directly upstream from a free pipe outlet in a vertical pipeline.
A0008154
Fig. 6: Mounting location
Installation of pumps
Do not install the sensor on the intake side of a pump. This precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. Information on the lining's resistance to partial vacuum can be found on ä 103.
It might be necessary to install pulse dampers in systems incorporating reciprocating, diaphragm or peristaltic pumps. Information on the measuring system's resistance to vibration and shock can be found on ä 99.
A0003203
Fig. 7: Installation of pumps
Endress+Hauser 13
Page 14
Installation Promag 50
5 x DN
2 x DN
³
³
h
2
1
Partially filled pipes
Partially filled pipes with gradients necessitate a drain-type configuration. The Empty Pipe Detection function (EPD ä 73) offers additional protection by detecting empty or partially filled pipes.
Caution!
"
Risk of solids accumulating. Do not install the sensor at the lowest point in the drain. It is advisable to install a cleaning valve.
A0008155
Fig. 8: Installation in a partially filled pipe
Down pipes
Install a siphon or a vent valve downstream of the sensor in down pipes whose length h 5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. This measure also prevents the system losing prime, which could cause air pockets. Information on the lining's resistance to partial vacuum can be found on ä 103.
A0008157
Fig. 9: Measures for installation in a down pipe
1 Vent valve 2Pipe siphon h Length of down pipe
14 Endress+Hauser
Page 15
Promag 50 Installation
A
1
22
A
3

3.2.3 Orientation

An optimum orientation position helps avoid gas and air accumulations and deposits in the measuring tube. However, Promag offers the additional Empty Pipe Detection (EPD) function to ensure the detection of partially filled measuring tubes, e.g. in the case of degassing fluids or varying process pressure:
• Electrode Cleaning Circuit (ECC) for applications with accretive fluids, e.g. electrically conductive deposits ("Description of Device Functions" manual).
• Empty Pipe Detection (EPD) ensures the detection of partially filled measuring tubes, e.g. in the case of degassing fluids (ä 73)
• Exchangeable Measuring Electrodes for abrasive fluids (ä 92)
Vertical orientation
This is the ideal orientation for self-emptying piping systems and for use in conjunction with Empty Pipe Detection.
Fig. 10: Vertical orientation
Horizontal orientation
The measuring electrode plane should be horizontal. This prevents brief insulation of the two measuring electrodes by entrained air bubbles.
Caution!
"
Empty Pipe Detection functions correctly only when the measuring device is installed horizontally and the transmitter housing is facing upward (å 10). Otherwise there is no guarantee that Empty Pipe Detection will respond if the measuring tube is only partially filled or empty.
A0008158
Fig. 11: Horizontal orientation
1 EPD electrode for the detection of empty pipes (not with Promag D and Promag H (DN 2 to 15; 1/12" to ½")) 2 Measuring electrodes for signal detection 3 Reference electrode for the potential equalization (not with Promag D and H)
Endress+Hauser 15
A0003207
Page 16
Installation Promag 50
5 x DN³
³ 2 x DN
L
Inlet and outlet run
If possible, install the sensor upstream from fittings such as valves, T-pieces, elbows, etc. The following inlet and outlet runs must be observed in order to meet accuracy specifications:
• Inlet run: 5 × DN
•Outlet run: 2 × DN
A0003210
Fig. 12: Inlet and outlet runs

3.2.4 Vibrations

Secure the piping and the sensor if vibration is severe. Caution!
"
If vibrations are too severe, we recommend the sensor and transmitter be mounted separately. Information on resistance to vibration and shock can be found on ä 99.
A0003208
Fig. 13: Measures to prevent vibration of the device (L > 10 m (32.8 ft))
16 Endress+Hauser
Page 17
Promag 50 Installation
100
10
0.5
d / D
[mbar]
0.60.70.80.9
1m/s
2m/s
3m/s
4 m/s
5m/s
6m/s
7m/s
8m/s
1
D
d
max. 8°

3.2.5 Foundations, supports

If the nominal diameter is DN 350, mount the sensor on a foundation of adequate load-bearing strength.
Caution!
"
Risk of damage. Do not support the weight of the sensor on the metal casing: the casing would buckle and damage the internal magnetic coils.
A0003209
Fig. 14: Correct support for large nominal diameters (DN 350)
!

3.2.6 Adapters

Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger­diameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very slow-moving fluids. The nomogram shown here can be used to calculate the pressure loss caused by reducers and expanders.
Note! The nomogram only applies to liquids of viscosity similar to water.
1. Calculate the ratio of the diameters d/D.
2. From the nomogram read off the pressure loss as a function of flow velocity (downstream from
the reduction) and the d/D ratio.
Fig. 15: Pressure loss due to adapters
A0011907
Endress+Hauser 17
Page 18
Installation Promag 50

3.2.7 Nominal diameter and flow rate

The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The optimum velocity of flow is between 2 and 3 m/s (6.5 to 9.8 ft/s)
The velocity of flow (v), moreover, has to be matched to the physical properties of the fluid:
• v < 2 m/s (v < 6.5 ft/s): for abrasive fluids
• v > 2 m/s (v > 6.5 ft/s): for fluids producing buildup
!
Note! Flow velocity can be increased, if necessary, by reducing the nominal diameter of the sensor (ä 17).
Recommended flow (SI units)
Nominal
diameter
[mm] Min./max. full scale value (v 0.3 or 10 m/s) in [dm³/min]
2 – – – – 0.06 to 1.8 4 – – – – 0.25 to 7
8 – – – – 1 to 30 15 – – – 4 to 100 4 to 100 25 9 to 300 – 9 to 300 9 to 300 9 to 300 32 – – 15 to 500 15 to 500 – 40 25 to 700 – 25 to 700 25 to 700 25 to 700 50 35 to 1100 35 to 1100 35 to 1100 35 to 1100 35 to 1100 65 60 to 2000 60 to 2000 60 to 2000 60 to 2000 60 to 2000 80 90 to 3000 90 to 3000 90 to 3000 90 to 3000 90 to 3000
100 145 to 4700 145 to 4700 145 to 4700 145 to 4700 145 to 4700 125 – 220 to 7500 220 to 7500 220 to 7500 –
[mm] Min./max. full scale value (v 0.3 or 10 m/s) in [m³/h]
150 – 20 to 600 20 to 600 20 to 600 – 200 – 35 to 1100 35 to 1100 35 to 1100 – 250 – 55 to 1700 55 to 1700 55 to 1700 – 300 – 80 to 2400 80 to 2400 80 to 2400 – 350 – 110 to 3300 110 to 3300 110 to 3300 – 375 – 140 to 4200 140 to 4200 – – 400 – 140 to 4200 140 to 4200 140 to 4200 – 450 – 180 to 5400 180 to 5400 180 to 5400 – 500 – 220 to 6600 220 to 6600 220 to 6600 – 600 – 310 to 9600 310 to 9600 310 to 9600 – 700 – 420 to 13500 420 to 13500 – – 750 – 480 to 15200 480 to 15200 – – 800 – 550 to 18000 550 to 18000 – –
900 – 690 to 22500 690 to 22500 – – 1000 – 850 to 28000 850 to 28000 – – 1050 – 950 to 40000 950 to 40000 – – 1200 – 1250 to 40000 1250 to 40000 – – 1400 – – 1700 to 55000 – – 1600 – – 2200 to 70000 – – 1800 – – 2800 to 90000 – – 2000 – – 3400 to 110000 – –
Promag D Promag L Promag W Promag P Promag H
18 Endress+Hauser
Page 19
Promag 50 Installation
Recommended flow (US units)
Nominal diameter Promag D Promag L Promag W Promag P Promag H
[inch] Min./max. full scale value (v 0.3 or 10 m/s) in [gal/min]
/" – – – – 0.015 to 0.5
1
/"–– – –0.07 to 2
/"–– – –0.25 to 8
/" – – – 1.0 to 27 1.0 to 27 1" 2.5 to 80 – 2.5 to 80 2.5 to 80 2.5 to 80
1
/" – – 4 to 130 4 to 130 –
/" 7 to 190 7 to 190 7 to 190 7 to 190 7 to 190
1
2" 10 to 300 10 to 300 10 to 300 10 to 300 10 to 300
2
/" 16 to 500 16 to 500 16 to 500 16 to 500 16 to 500 3" 24 to 800 24 to 800 24 to 800 24 to 800 24 to 800 4" 40 to 1250 40 to 1250 40 to 1250 40 to 1250 40 to 1250 5" – 60 to 1950 60 to 1950 60 to 1950 – 6" – 90 to 2650 90 to 2650 90 to 2650 – 8" – 155 to 4850 155 to 4850 155 to 4850 –
10" – 250 to 7500 250 to 7500 250 to 7500 – 12" – 350 to 10600 350 to 10600 350 to 10600 – 14" – 500 to 15000 500 to 15000 500 to 15000 – 15" – 600 to 19000 600 to 19000 – – 16" – 600 to 19000 600 to 19000 600 to 19000 – 18" – 800 to 24000 800 to 24000 800 to 24000 – 20" – 1000 to 30000 1000 to 30000 1000 to 30000 – 24" – 1400 to 44000 1400 to 44000 1400 to 44000 – 28" – 1900 to 60000 1900 to 60000 – – 30" – 2150 to 67000 2150 to 67000 – – 32" – 2450 to 80000 2450 to 80000 – – 36" – 3100 to 100000 3100 to 100000 – – 40" – 3800 to 125000 3800 to 125000 – – 42" – 4200 to 135000 4200 to 135000 – – 48" – 5500 to 175000 5500 to 175000 – –
[inch] Min./max. full scale value (v 0.3 or 10 m/s) in [Mgal/d]
54" – – 9 to 300 – – 60" – – 12 to 380 – – 66" – – 14 to 500 – – 72" – – 16 to 570 – – 78" – – 18 to 650 – –
Endress+Hauser 19
Page 20
Installation Promag 50
200
100
5
10 100 200
L
max
[m][m]
[µS/cm]
L
max
[ft]
200 6000
400

3.2.8 Length of connecting cable

In order to ensure measuring accuracy, comply with the following instructions when installing the remote version:
• Fix cable run or lay in armored conduit. Cable movements can falsify the measuring signal especially in the case of low fluid conductivities.
• Route the cable well clear of electrical machines and switching elements.
• Ensure potential equalization between sensor and transmitter, if necessary.
• The permitted connecting cable length L
is determined by the fluid conductivity (å 16).
max
A minimum conductivity of 20 μS/cm is required for measuring demineralized water. Most liquids can be measured as of a minimum conductivity of 5 μS/cm.
• The maximum connecting cable length is 10 m (32.8 ft) when empty pipe detection (EPD ä 73) is switched on.
Fig. 16: Permissible cable length for the remote version
Area shaded gray = permitted range Lmax = connecting cable length in [m] Fluid conductivity in [μS/cm]
A0010734
20 Endress+Hauser
Page 21
Promag 50 Installation
5
1
2
3
4

3.3 Installation instructions

3.3.1 Installing the Promag D sensor

The sensor is installed between the pipe flanges with a mounting kit. The device is centered using recesses on the sensor (ä 22).
!
"
Note! A mounting kit consisting of mounting bolts, seals, nuts and washers can be ordered separately (ä 76). Centering sleeves are provided with the device if they are required for the installation.
Caution! When installing the transmitter in the pipe, observe the necessary torques (ä 23).
a0010776
Fig. 17: Mounting the sensor
1Nut 2Washer 3 Mounting bolt 4 Centering sleeve 5Seal
Seals
When installing the sensor, make sure that the seals used do not project into the pipe cross-section. Caution!
"
Risk of short circuit! Do not use electrically conductive sealing compounds such as graphite! An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal.
!
Endress+Hauser 21
Note! Use seals with a hardness rating of 70° Shore.
Page 22
Installation Promag 50
1
1
1
1
1
1
1
1
1
1
1
1
2
2
22
3
3
3
3
3
3
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Arrangement of the mounting bolts and centering sleeves
The device is centered using recesses on the sensor. The arrangement of the mounting bolts and the use of the centering sleeves supplied depend on the nominal diameter, the flange standard und the pitch circle diameter.
Process connection
EN (DIN) ANSI JIS
DN 25 to 40 (DN 1" to 1 ½")
A0010896 A0010824 A0010896
DN 50 (DN 2")
DN 65
DN 80 (DN 3")
DN 100 (DN 4")
A0010897 A0010825 A0010825
–––––––––––––––––
A0012170
A0010898 A0010827 A0010826
A0012171
A0012168 A0012168 A0012169
1 = Mounting bolts with centering sleeves 2 = EN (DIN) flanges: 4-hole with centering sleeves 3 = EN (DIN) flanges: 8-hole without centering sleeves
22 Endress+Hauser
Page 23
Promag 50 Installation
Screw tightening torques (Promag D)
Please note the following:
• The tightening torques listed below are for lubricated threads only.
• Always tighten the screws uniformly and in diagonally opposite sequence.
• Overtightening the screws will deform the sealing faces or damage the seals.
• The tightening torques listed below apply only to pipes not subjected to tensile stress. The tightening torques apply to situations where an EPDM soft material flat seal (e.g. 70 Shore) is
used.
Tightening torques, mounting bolts and centering sleeves for EN (DIN) PN 16
Nominal diameter
[mm] [mm] [mm] smooth seal face raised face
25 4 × M12 × 145 54 19 19 40 4 × M16 × 170 68 33 33 50 4 × M16 × 185 82 41 41

65

65
80 8 × M16 × 225 116 36 36
100 8 × M16 × 260 147 40 40

EN (DIN) flanges: 4-hole with centering sleeves

EN (DIN) flanges: 8-hole without centering sleeves

A centering sleeve is not required. The device is centered directly via the sensor housing.
Mounting bolts
4 × M16 × 200 92 44 44 8 × M16 × 200 –
Centering sleeve
length

Tightening torque [Nm]
with a process flange with a
29 29
Tightening torques, mounting bolts and centering sleeves for JIS 10 K
Nominal diameter
[mm] [mm] [mm] smooth seal face raised face
25 4 × M16 × 170 54 24 24 40 4 × M16 × 170 68 32 25 50 4 × M16 × 185 – * 38 30 65 4 × M16 × 200 – * 42 42 80 8 × M16 × 225 – * 36 28
100 8 × M16 × 260 – * 39 37
* A centering sleeve is not required. The device is centered directly via the sensor housing.
Mounting bolts
Centering sleeve
length
Tightening torque [Nm]
with a process flange with a
Tightening torques, mounting bolts and centering sleeves for ANSI Class 150
Nominal diameter
[inch] [inch] [inch] smooth seal face raised face
1" 4 × UNC 1/2" × 5.70" – * 14 7
1 ½" 4 × UNC 1/2" × 6.50" – * 21 14
2" 4 × UNC 5/8" × 7.50" – * 30 27 3" 4 × UNC 5/8" × 9.25" – * 31 31 4" 8 × UNC 5/8" × 10,4" 5,79 28 28
* A centering sleeve is not required. The device is centered directly via the sensor housing.
Mounting bolts
Centering sleeve
length
Tightening torque [lbf · ft]
with a process flange with a
Endress+Hauser 23
Page 24
Installation Promag 50

3.3.2 Installing the Promag L sensor

Caution!
"
• The protective covers mounted on the two sensor flanges (DN 50…300) are used to hold the lap joint flanges in place and to protect the PTFE liner during transportation. Consequently, do not remove these covers until immediately before the sensor is installed in the pipe.
• The covers must remain in place while the device is in storage.
• Make sure that the lining is not damaged or removed from the flanges.
!
Note! Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer.
The sensor is designed for installation between the two piping flanges.
• Observe in any case the necessary screw tightening torques on ä 25
• If grounding disks are used, follow the mounting instructions which will be enclosed with the shipment
• To comply with the device specification, a concentrical installation in the measuring section is required
Fig. 18: Installing the Promag L sensor
Seals
Comply with the following instructions when installing seals:
• Hard rubber lining additional seals are always necessary.
• Polyurethane lining no seals are required.
• PTFE lining no seals are required.
• For DIN flanges, use only seals according to EN 1514-1.
• Make sure that the seals do not protrude into the piping cross-section.
Caution!
"
Risk of short circuit! Do not use electrically conductive sealing compounds such as graphite! An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal.
Ground cable
• If necessary, special ground cables for potential equalization can be ordered as an accessory (ä 76).
• Information on potential equalization and detailed mounting instructions for the use of ground cables can be found on ä 55.
a0004296
24 Endress+Hauser
Page 25
Promag 50 Installation
Screw tightening torques (Promag L)
Please note the following:
• The tightening torques listed below are for lubricated threads only.
• Always tighten the screws uniformly and in diagonally opposite sequence.
• Overtightening the screws will deform the sealing faces or damage the seals.
• The tightening torques listed below apply only to pipes not subjected to tensile stress.
Promag L tightening torques for EN (DIN)
Nominal diameter EN (DIN) Max. tightening torque
Hard rubber Polyurethane PTFE
[mm] Pressure rating
[bar]
50 PN 10/16 4 × M 16 - 15 40
65* PN 10/16 8 × M 16 - 10 22
80 PN 10/16 8 × M 16 - 15 30 100 PN 10/16 8 × M 16 - 20 42 125 PN 10/16 8 × M 16 - 30 55 150 PN 10/16 8 × M 20 - 50 90 200 PN 10 8 × M 20 - 65 130 250 PN 10 12 × M 20 - 50 90 300 PN 10 12 × M 20 - 55 100 350 PN 6 12 × M 20 111 120 ­350 PN 10 16 × M 20 112 118 ­400 PN 6 16 × M 20 90 98 ­400 PN 10 16 × M 24 151 167 ­450 PN 6 16 × M 20 112 126 ­450 PN 10 20 × M 24 153 133 ­500 PN 6 20 × M 20 119 123 ­500 PN 10 20 × M 24 155 171 ­600 PN 6 20 × M 24 139 147 ­600 PN 10 20 × M 27 206 219 ­700 PN 6 24 × M 24 148 139 ­700 PN 10 24 × M 27 246 246 ­800 PN 6 24 × M 27 206 182 ­800 PN 10 24 × M 30 331 316 ­900 PN 6 24 × M 27 230 637 ­900 PN 10 28 × M 30 316 307 -
1000 PN 6 28 × M 27 218 208 ­1000 PN 10 28 × M 33 402 405 ­1200 PN 6 32 × M 30 319 299 ­1200 PN 10 32 × M 36 564 568 -
* Designed acc. to EN 1092-1 (not to DIN 2501)
Threaded
fasteners
[Nm] [Nm] [Nm]
Promag L tightening torques for ANSI
Nominal diam-
eter
[mm] [inch] [lbs] [Nm] [lbf · ft] [Nm] [lbf · ft] [Nm] [lbf · ft]
50 2" Class 150 4 × 5/8" - - 15 11 40 29
80 3" Class 150 4 × 5/8" - - 25 18 65 48 100 4" Class 150 8 × 5/8" - - 20 15 44 32 150 6" Class 150 8 × ¾" - - 45 33 90 66 200 8" Class 150 8 × ¾" - - 65 48 125 92 250 10" Class 150 12 × 7/8" - - 55 41 100 74 300 12" Class 150 12 × 7/8" - - 68 56 115 85 350 14" Class 150 12 × 1" 135 100 158 117 - -
ANSI Threaded
fasteners
Pressure rating Hard rubber Polyurethane PTFE
Max. tightening torque
Endress+Hauser 25
Page 26
Installation Promag 50
Nominal diam-
eter
[mm] [inch] [lbs] [Nm] [lbf · ft] [Nm] [lbf · ft] [Nm] [lbf · ft]
400 16" Class 150 16 × 1" 128 94 150 111 - ­450 18" Class 150 16 × 1 1/8" 204 150 234 173 - ­500 20" Class 150 20 × 1 1/8" 183 135 217 160 - ­600 24" Class 150 20 × 1 ¼" 268 198 307 226 - -
ANSI Threaded
fasteners
Pressure rating Hard rubber Polyurethane PTFE
Max. tightening torque
Promag L tightening torques for AWWA
Nominal diam-
eter
[mm] [inch] [Nm] [lbf · ft] [Nm] [lbf · ft] [Nm] [lbf · ft]
700 28" Class D 28 × 1 ¼" 247 182 292 215 - ­750 30" Class D 28 × 1 ¼" 287 212 302 223 - ­800 32" Class D 28 × 1 ½" 394 291 422 311 - -
900 36" Class D 32 × 1 ½" 419 309 430 317 - ­1000 40" Class D 36 × 1 ½" 420 310 477 352 - ­1050 42" Class D 36 × 1 ½" 528 389 518 382 - ­1200 48" Class D 44 × 1 ½" 552 407 531 392 - -
AWWA Threaded
fasteners
Pressure rating Hartgummi Polyurethane PTFE
Max. tightening torque
Promag L tightening torques for AS 2129
Nominal
diameter
[mm] [Nm] [Nm] [Nm]
350 Table E 12 × M 24 203 - ­400 Table E 12 × M 24 226 - ­450 Table E 16 × M 24 226 - ­500 Table E 16 × M 24 271 - ­600 Table E 16 × M 30 439 - ­700 Table E 20 × M 30 355 - ­750 Table E 20 × M 30 559 - ­800 Table E 20 × M 30 631 - -
900 Table E 24 × M 30 627 - ­1000 Table E 24 × M 30 634 - ­1200 Table E 32 × M 30 727 - -
AS 2129 Threaded
fasteners
Pressure rating Hard rubber Polyurethane PTFE
Max. tightening torque
Promag L tightening torques for AS 4087
Nominal dia-
meter
[mm] [Nm] [Nm] [Nm]
350 PN 16 12 × M 24 203 - -
375 PN 16 12 × M 24 137 - -
400 PN 16 12 × M 24 226 - -
450 PN 16 12 × M 24 301 - -
500 PN 16 16 × M 24 271 - -
600 PN 16 16 × M 27 393 - -
700 PN 16 20 × M 27 330 - -
750 PN 16 20 × M 30 529 - -
800 PN 16 20 × M 33 631 - -
900 PN 16 24 × M 33 627 - -
1000 PN 16 24 × M 33 595 - ­1200 PN 16 32 × M 33 703 - -
AS 4087 Threaded
fasteners
Pressure rating Hard rubber Polyurethane PTFE
Max. tightening torque
26 Endress+Hauser
Page 27
Promag 50 Installation

3.3.3 Installing the Promag W sensor

!
"
Note! Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer.
The sensor is designed for installation between the two piping flanges.
• Observe in any case the necessary screw tightening torques on ä 27
• If grounding disks are used, follow the mounting instructions which will be enclosed with the shipment
a0004296
Fig. 19: Installing the Promag W sensor
Seals
Comply with the following instructions when installing seals:
• Hard rubber lining additional seals are always necessary.
• Polyurethane lining no seals are required.
• For DIN flanges, use only seals according to EN 1514-1.
• Make sure that the seals do not protrude into the piping cross-section.
Caution! Risk of short circuit! Do not use electrically conductive sealing compounds such as graphite! An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal.
Ground cable
• If necessary, special ground cables for potential equalization can be ordered as an accessory (ä 76).
• Information on potential equalization and detailed mounting instructions for the use of ground cables can be found on ä 55
Screw tightening torques (Promag W)
Please note the following:
• The tightening torques listed below are for lubricated threads only.
• Always tighten the screws uniformly and in diagonally opposite sequence.
• Overtightening the screws will deform the sealing faces or damage the seals.
• The tightening torques listed below apply only to pipes not subjected to tensile stress.
Endress+Hauser 27
Page 28
Installation Promag 50
Tightening torques for:
•EN (DIN)ä 28
• JISä 30
•ANSIä 29
• AWWA ä 30
• AS 2129 ä 31
• AS 4087 ä 31
Promag W tightening torques for EN (DIN)
Nominal diameter EN (DIN)
[mm] Pressure rating [bar] Hard rubber Polyurethane
25 PN 40 4 × M 12 - 15 32 PN 40 4 × M 16 - 24 40 PN 40 4 × M 16 - 31 50 PN 40 4 × M 16 48 40 65* PN 16 8 × M 16 32 27 65 PN 40 8 × M 16 32 27 80 PN 16 8 × M 16 40 34
80 PN 40 8 × M 16 40 34 100 PN 16 8 × M 16 43 36 100 PN 40 8 × M 20 59 50 125 PN 16 8 × M 16 56 48 125 PN 40 8 × M 24 83 71 150 PN 16 8 × M 20 74 63 150 PN 40 8 × M 24 104 88 200 PN 10 8 × M 20 106 91 200 PN 16 12 × M 20 70 61 200 PN 25 12 × M 24 104 92 250 PN 10 12 × M 20 82 71 250 PN 16 12 × M 24 98 85 250 PN 25 12 × M 27 150 134 300 PN 10 12 × M 20 94 81 300 PN 16 12 × M 24 134 118 300 PN 25 16 × M 27 153 138 350 PN 6 12 × M 20 111 120 350 PN 10 16 × M 20 112 118 350 PN 16 16 × M 24 152 165 350 PN 25 16 × M 30 227 252 400 PN 6 16 × M 20 90 98 400 PN 10 16 × M 24 151 167 400 PN 16 16 × M 27 193 215 400 PN 25 16 × M 33 289 326 450 PN 6 16 × M 20 112 126 450 PN 10 20 × M 24 153 133 450 PN 16 20 × M 27 198 196 450 PN 25 20 × M 33 256 253 500 PN 6 20 × M 20 119 123 500 PN 10 20 × M 24 155 171 500 PN 16 20 × M 30 275 300 500 PN 25 20 × M 33 317 360 600 PN 6 20 × M 24 139 147 600 PN 10 20 × M 27 206 219
600 * PN 16 20 × M 33 415 443
600 PN 25 20 × M 36 431 516 700 PN 6 24 × M 24 148 139 700 PN 10 24 × M 27 246 246 700 PN 16 24 × M 33 278 318
Threaded
fasteners
Max. tightening torque [Nm]
28 Endress+Hauser
Page 29
Promag 50 Installation
Nominal diameter EN (DIN)
[mm] Pressure rating [bar] Hard rubber Polyurethane
700 PN 25 24 × M 39 449 507 800 PN 6 24 × M 27 206 182 800 PN 10 24 × M 30 331 316 800 PN 16 24 × M 36 369 385 800 PN 25 24 × M 45 664 721 900 PN 6 24 × M 27 230 637 900 PN 10 28 × M 30 316 307 900 PN 16 28 × M 36 353 398
900 PN 25 28 × M 45 690 716 1000 PN 6 28 × M 27 218 208 1000 PN 10 28 × M 33 402 405 1000 PN 16 28 × M 39 502 518 1000 PN 25 28 × M 52 970 971 1200 PN 6 32 × M 30 319 299 1200 PN 10 32 × M 36 564 568 1200 PN 16 32 × M 45 701 753 1400 PN 6 36 × M 33 430 398 1400 PN 10 36 × M 39 654 618 1400 PN 16 36 × M 45 729 762 1600 PN 6 40 × M 33 440 417 1600 PN 10 40 × M 45 946 893 1600 PN 16 40 × M 52 1007 1100 1800 PN 6 44 × M 36 547 521 1800 PN 10 44 × M 45 961 895 1800 PN 16 44 × M 52 1108 1003 2000 PN 6 48 × M 39 629 605 2000 PN 10 48 × M 45 1047 1092 2000 PN 16 48 × M 56 1324 1261
* Designed acc. to EN 1092-1 (not to DIN 2501)
Threaded
fasteners
Max. tightening torque [Nm]
Promag W tightening torques for ANSI
Nominal diameter
[mm] [inch] [Nm] [lbf · ft] [Nm] [lbf · ft]
25 1" Class 150 4 × ½" - - 7 5 25 1" Class 300 4 × 5/8" - - 8 6 40 1 ½" Class 150 4 × ½" - - 10 7 40 1 ½" Class 300 4 × ¾" - - 15 11 50 2" Class 150 4 × 5/8" 35 26 22 16 50 2" Class 300 8 × 5/8" 18 13 11 8 80 3" Class 150 4 × 5/8" 60 44 43 32
80 3" Class 300 8 × ¾" 38 28 26 19 100 4" Class 150 8 × 5/8" 42 31 31 23 100 4" Class 300 8 × ¾" 58 43 40 30 150 6" Class 150 8 × ¾" 79 58 59 44 150 6" Class 300 12 × ¾" 70 52 51 38 200 8" Class 150 8 × ¾" 107 79 80 59 250 10" Class 150 12 × 7/8" 101 74 75 55 300 12" Class 150 12 × 7/8" 133 98 103 76 350 14" Class 150 12 × 1" 135 100 158 117 400 16" Class 150 16 × 1" 128 94 150 111 450 18" Class 150 16 × 1 1/8" 204 150 234 173 500 20" Class 150 20 × 1 1/8" 183 135 217 160 600 24" Class 150 20 × 1 ¼" 268 198 307 226
ANSI Max. tightening torque
Pressure rating
[lbs]
Threaded
fasteners
Hard rubber Polyurethane
Endress+Hauser 29
Page 30
Installation Promag 50
Promag W tightening torques for JIS
Nominal diameter JIS Threaded
[mm] Pressure rating Hard rubber Polyurethane
25 10K 4 × M 16 - 19 25 20K 4 × M 16 - 19 32 10K 4 × M 16 - 22 32 20K 4 × M 16 - 22 40 10K 4 × M 16 - 24 40 20K 4 × M 16 - 24 50 10K 4 × M 16 40 33 50 20K 8 × M 16 20 17 65 10K 4 × M 16 55 45 65 20K 8 × M 16 28 23 80 10K 8 × M 16 29 23
80 20K 8 × M 20 42 35 100 10K 8 × M 16 35 29 100 20K 8 × M 20 56 48 125 10K 8 × M 20 60 51 125 20K 8 × M 22 91 79 150 10K 8 × M 20 75 63 150 20K 12 × M 22 81 72 200 10K 12 × M 20 61 52 200 20K 12 × M 22 91 80 250 10K 12 × M 22 100 87 250 20K 12 × M 24 159 144 300 10K 16 × M 22 74 63 300 20K 16 × M 24 138 124
fasteners
Max. tightening torque [Nm]
Promag W tightening torques for AWWA
Nominal diameter AWWA Max. tightening torque
Pressure
[mm] [inch] [Nm] [lbf · ft] [Nm] [lbf · ft]
700 28" Class D 28 × 1 ¼" 247 182 292 215 750 30" Class D 28 × 1 ¼" 287 212 302 223 800 32" Class D 28 × 1 ½" 394 291 422 311
900 36" Class D 32 × 1 ½" 419 309 430 317 1000 40" Class D 36 × 1 ½" 420 310 477 352 1050 42" Class D 36 × 1 ½" 528 389 518 382 1200 48" Class D 44 × 1 ½" 552 407 531 392 1350 54" Class D 44 × 1 ¾" 730 538 633 467 1500 60" Class D 52 × 1 ¾" 758 559 832 614 1650 66" Class D 52 × 1 ¾" 946 698 955 704 1800 72" Class D 60 × 1 ¾" 975 719 1087 802 2000 78" Class D 64 × 2" 853 629 786 580
rating
Threaded
fasteners
Hard rubber Polyurethane
30 Endress+Hauser
Page 31
Promag 50 Installation
Promag W tightening torques for AS 2129
Nominal diameter
[mm]
50 Table E 4 × M 16 32
80 Table E 4 × M 16 49 100 Table E 8 × M 16 38 150 Table E 8 × M 20 64 200 Table E 8 × M 20 96 250 Table E 12 × M 20 98 300 Table E 12 × M 24 123 350 Table E 12 × M 24 203 400 Table E 12 × M 24 226 450 Table E 16 × M 24 226 500 Table E 16 × M 24 271 600 Table E 16 × M 30 439 700 Table E 20 × M 30 355 750 Table E 20 × M 30 559 800 Table E 20 × M 30 631 900 Table E 24 × M 30 627
1000 Table E 24 × M 30 634 1200 Table E 32 × M 30 727
AS 2129
Pressure rating
Promag W tightening torques for AS 4087
Nominal diameter
[mm]
50 Table E 4 × M 16 32
80 PN 16 4 × M 16 49 100 PN 16 4 × M 16 76 150 PN 16 8 × M 20 52 200 PN 16 8 × M 20 77 250 PN 16 8 × M 20 147 300 PN 16 12 × M 24 103 350 PN 16 12 × M 24 203 375 PN 16 12 × M 24 137 400 PN 16 12 × M 24 226 450 PN 16 12 × M 24 301 500 PN 16 16 × M 24 271 600 PN 16 16 × M 27 393 700 PN 16 20 × M 27 330 750 PN 16 20 × M 30 529 800 PN 16 20 × M 33 631 900 PN 16 24 × M 33 627
1000 PN 16 24 × M 33 595 1200 PN 16 32 × M 33 703
AS 4087
Pressure rating
Threaded
fasteners
Threaded
fasteners
Max. tightening torque [Nm]
Hard rubber
Max. tightening torque [Nm]
Hard rubber
Endress+Hauser 31
Page 32
Installation Promag 50

3.3.4 Installing the Promag P sensor

Caution!
"
• The protective covers mounted on the two sensor flanges guard the PTFE, which is turned over the flanges. Consequently, do not remove these covers until immediately before the sensor is installed in the pipe.
• The covers must remain in place while the device is in storage.
• Make sure that the lining is not damaged or removed from the flanges.
!
Note! Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer.
The sensor is designed for installation between the two piping flanges.
• Observe in any case the necessary screw tightening torques on ä 33
• If grounding disks are used, follow the mounting instructions which will be enclosed with the shipment
Fig. 20: Installing the Promag P sensor
Seals
Comply with the following instructions when installing seals:
• PFA or PTFE lining No seals are required!
• For DIN flanges, use only seals according to EN 1514-1.
• Make sure that the seals do not protrude into the piping cross-section.
Caution!
"
Risk of short circuit! Do not use electrically conductive sealing compounds such as graphite! An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal.
Ground cable
• If necessary, special ground cables for potential equalization can be ordered as an accessory (ä 76).
• Information on potential equalization and detailed mounting instructions for the use of ground cables can be found on ä 53
a0004296
32 Endress+Hauser
Page 33
Promag 50 Installation
Esc
E
-
+
max.
Installing the high-temperature version (with PFA lining)
The high-temperature version has a housing support for the thermal separation of sensor and transmitter. The high-temperature version is always used for applications in which high ambient temperatures are encountered in conjunction with high fluid temperatures. The high-temperature version is obligatory if the fluid temperature exceeds +150 °C.
!
Note! You will find information on permissible temperature ranges on ä 100
Insulation
Pipes generally have to be insulated if they carry very hot fluids, in order to avoid energy losses and to prevent accidental contact with pipes at temperatures that could cause injury. Guidelines regulating the insulation of pipes have to be taken into account.
Caution!
"
Risk of measuring electronics overheating. The housing support dissipates heat and its entire surface area must remain uncovered. Make sure that the sensor insulation does not extend past the top of the two sensor shells.
A0004300
Fig. 21: Promag P (high-temperature version): Insulating the pipe
Tightening torques for threaded fasteners (Promag P)
Please note the following:
• The tightening torques listed below are for lubricated threads only.
• Always tighten the screws uniformly and in diagonally opposite sequence.
• Overtightening the screws will deform the sealing faces or damage the seals.
• The tightening torques listed below apply only to pipes not subjected to tensile stress. Tightening torques for:
• EN (DIN) ä 34
•ANSI ä 35
• JIS ä 35
• AS 2129 ä 36
• AS 4087 ä 36
Endress+Hauser 33
Page 34
Installation Promag 50
Promag P tightening torques for EN (DIN)
Nominal diameter EN (DIN) Threaded
[mm] Pressure rating [bar] PTFE PFA
15 PN 40 4 × M 12 11 – 25 PN 40 4 × M 12 26 20 32 PN 40 4 × M 16 41 35 40 PN 40 4 × M 16 52 47 50 PN 40 4 × M 16 65 59 65 * PN 16 8 × M 16 43 40 65 PN 40 8 × M 16 43 40 80 PN 16 8 × M 16 53 48
80 PN 40 8 × M 16 53 48 100 PN 16 8 × M 16 57 51 100 PN 40 8 × M 20 78 70 125 PN 16 8 × M 16 75 67 125 PN 40 8 × M 24 111 99 150 PN 16 8 × M 20 99 85 150 PN 40 8 × M 24 136 120 200 PN 10 8 × M 20 141 101 200 PN 16 12 × M 20 94 67 200 PN 25 12 × M 24 138 105 250 PN 10 12 × M 20 110 – 250 PN 16 12 × M 24 131 – 250 PN 25 12 × M 27 200 – 300 PN 10 12 × M 20 125 – 300 PN 16 12 × M 24 179 – 300 PN 25 16 × M 27 204 – 350 PN 10 16 × M 20 188 – 350 PN 16 16 × M 24 254 – 350 PN 25 16 × M 30 380 – 400 PN 10 16 × M 24 260 – 400 PN 16 16 × M 27 330 – 400 PN 25 16 × M 33 488 – 450 PN 10 20 × M 24 235 – 450 PN 16 20 × M 27 300 – 450 PN 25 20 × M 33 385 – 500 PN 10 20 × M 24 265 – 500 PN 16 20 × M 30 448 – 500 PN 25 20 × M 33 533 – 600 PN 10 20 × M 27 345 –
600 * PN 16 20 × M 33 658 –
600 PN 25 20 × M 36 731 –
* Designed acc. to EN 1092-1 (not to DIN 2501)
fasteners
Max. tightening torque [Nm]
34 Endress+Hauser
Page 35
Promag 50 Installation
Promag P tightening torques for ANSI
Nominal diameter ANSI Max. tightening torque
Pressure rating
[mm] [inch] [Nm] [lbf · ft] [Nm] [lbf · ft]
15 ½" Class 150 4 × ½" 6 4 – – 15 ½" Class 300 4 × ½" 6 4 – – 25 1" Class 150 4 × ½" 11 8 10 7 25 1" Class 300 4 × 5/8" 14 10 12 9 40 1 ½" Class 150 4 × ½" 24 18 21 15 40 1 ½" Class 300 4 × ¾" 34 25 31 23 50 2" Class 150 4 × 5/8" 47 35 44 32 50 2" Class 300 8 × 5/8" 23 17 22 16 80 3" Class 150 4 × 5/8" 79 58 67 49
80 3" Class 300 8 × ¾" 47 35 42 31 100 4" Class 150 8 × 5/8" 56 41 50 37 100 4" Class 300 8 × ¾" 67 49 59 44 150 6" Class 150 8 × ¾" 106 78 86 63 150 6" Class 300 12 × ¾" 73 54 67 49 200 8" Class 150 8 × ¾" 143 105 109 80 250 10" Class 150 12 × 7/8" 135 100 – – 300 12" Class 150 12 × 7/8" 178 131 – – 350 14" Class 150 12 × 1" 260 192 – – 400 16" Class 150 16 × 1" 246 181 – – 450 18" Class 150 16 × 1 1/8" 371 274 – – 500 20" Class 150 20 × 1 1/8" 341 252 – – 600 24" Class 150 20 × 1 ¼" 477 352 – –
[lbs]
Threaded
fasteners
PTFE PFA
Promag P tightening torques for JIS
Nominal diameter JIS Max. tightening torque [Nm]
[mm] Pressure rating Threaded fasteners PTFE PFA
25 10K 4 × M 16 32 27 25 20K 4 × M 16 32 27 32 10K 4 × M 16 38 – 32 20K 4 × M 16 38 – 40 10K 4 × M 16 41 37 40 20K 4 × M 16 41 37 50 10K 4 × M 16 54 46 50 20K 8 × M 16 27 23 65 10K 4 × M 16 74 63 65 20K 8 × M 16 37 31 80 10K 8 × M 16 38 32
80 20K 8 × M 20 57 46 100 10K 8 × M 16 47 38 100 20K 8 × M 20 75 58 125 10K 8 × M 20 80 66 125 20K 8 × M 22 121 103 150 10K 8 × M 20 99 81 150 20K 12 × M 22 108 72 200 10K 12 × M 20 82 54 200 20K 12 × M 22 121 88 250 10K 12 × M 22 133 – 250 20K 12 × M 24 212 – 300 10K 16 × M 22 99 – 300 20K 16 × M 24 183 –
Endress+Hauser 35
Page 36
Installation Promag 50
A
B
C
Promag P tightening torques for AS 2129
Nominal diameter
[mm]
25 Table E 4 × M 12 21 50 Table E 4 × M 16 42
AS 2129
Pressure rating
Threaded
fasteners
Max. tightening torque [Nm]
PTFE
Promag P tightening torques for AS 4087
Nominal diameter
[mm]
50 PN 16 4 × M 16 42
AS 4087
Pressure rating
Threaded
fasteners
Max. tightening torque [Nm]
PTFE

3.3.5 Installing the Promag H sensor

The sensor is supplied to order, with or without pre-installed process connections. Pre-installed process connections are secured to the sensor with 4 or 6 hex-head threaded fasteners.
Caution!
"
The sensor might require support or additional attachments, depending on the application and the length of the piping run. When plastic process connections are used, the sensor must be additionally supported mechanically. A wall-mounting kit can be ordered separately from Endress+Hauser as an accessory (ä 76).
a0004301
Abb. 22: Promag H process connections (DN 2…25 / DN 40…100, 1/12"…1" / DN 1½"…4")
A = DN 2…25, 1/12"…1"/ process connections with O-ring – welding flanges (DIN EN ISO 1127, ODT / SMS), – flange (EN (DIN), ANSI, JIS ), flange PVDF (EN (DIN), ANSI, JIS ) – external and internal thread, hose connection, PVC adhesive fitting
B = DN 2…25, 1/12"…1"/ process connections with aseptic gasket vseal – weld nipples (DIN 11850, ODT/SMS) – Clamp (ISO 2852, DIN 32676, L14 AM7) – coupling (DIN 11851, DIN 11864-1, SMS 1145) – flange DIN 11864-2
C = DN 40…100, 1½…4"/ process connections with aseptic gasket seal – weld nipples (DIN 11850, ODT/SMS) – Clamp (ISO 2852, DIN 32676, L14 AM7) – coupling (DIN 11851, DIN 11864-1, ISO 2853, SMS 1145) – flange DIN 11864-2
Seals
When installing the process connections, make sure that the seals are clean and correctly centered.
36 Endress+Hauser
Page 37
Promag 50 Installation
Caution!
"
• With metal process connections, you must fully tighten the screws. The process connection forms a metallic connection with the sensor, which ensures a defined compression of the seal.
• With plastic process connections, note the max. torques for lubricated threads (7 Nm / 5.2 lbf ft). With plastic flanges, always use seals between connection and counter flange.
• The seals must be replaced periodically, depending on the application, particularly in the case of gasket seals (aseptic version)! The period between changes depends on the frequency of cleaning cycles, the cleaning temperature and the fluid temperature. Replacement seals can be ordered as accessories ä 76.
Usage and assembly of ground rings (DN 2 to 25, 1/12" to 1")
In case the process connections are made of plastic (e.g. flanges or adhesive fittings), the potential between the sensor and the fluid must be equalized using additional ground rings. If the ground rings are not installed this can affect the accuracy of the measurements or cause the destruction of the sensor through the electrochemical erosion of the electrodes.
Caution!
"
• Depending on the option ordered, plastic disks may be installed at the process connections instead of ground rings. These plastic disks serve only as spacers and have no potential equalization function. In addition, they provide a sealing function at the interface between the sensor and process connection. For this reason, with process connections without ground rings, these plastic disks/seals must not be removed, or must always be installed.
• Ground rings can be ordered separately from Endress+Hauser as accessories (ä 76). When placing the order, make certain that the ground ring is compatible with the material used for the electrodes. Otherwise, there is a risk that the electrodes may be destroyed by electrochemical corrosion! Information about the materials can be found on ä 111.
• Ground rings, including the seals, are mounted within the process connections. Therefore, the fitting length is not affected.
1. Loosen the four or six hexagonal headed bolts (1) and remove the process connection from the
sensor (4).
2. Remove the plastic disk (3), including the two O-ring seals (2).
3. Place one seal (2) in the groove of the process connection.
4. Place the metal ground ring (3) on the process connection.
5. Now place the second seal (2) in the groove of the ground ring.
6. Finally, mount the process connection on the sensor again.
With plastic process connections, note the max. torques for lubricated threads (7 Nm / 5.2 lbf ft).
Endress+Hauser 37
Page 38
Installation Promag 50
1
3
2
4
2
a0002651
Fig. 23: Installing ground rings with Promag H (DN 2 to 25, 1/12" to 1")
1 = Hexagonal-headed bolt (process connection) 2 = O-ring seals 3 = Ground ring or plastic disk (spacer) 4 = Sensor
"
!
Welding the transmitter into the piping (weld nipples)
Caution! Risk of destroying the measuring electronics. Make sure that the welding machine is not grounded via the sensor or the transmitter.
1. Tack-weld the sensor into the pipe. A suitable welding jig can be ordered separately as an accessory (ä 76).
2. Loosen the screws on the process connection flange and remove the sensor, complete with the seal, from the pipe.
3. Weld the process connection to the pipe.
4. Reinstall the sensor in the pipe. Make sure that everything is clean and that the seal is correctly seated.
Note!
• If thin-walled foodstuffs pipes are not welded correctly, the heat could damage the installed seal.
It is therefore advisable to remove the sensor and the seal prior to welding.
• The pipe has to be spread approximately 8 mm to permit disassembly.
Cleaning with pigs
If pigs are used for cleaning, it is essential to take the inside diameters of the measuring tube and process connection into account. All the dimensions and lengths of the sensor and transmitter are provided in the separate documentation "Technical Documentation" ä 116.
38 Endress+Hauser
Page 39
Promag 50 Installation
3
5
6
1
2
4
1
2
3
4
5

3.3.6 Turning the transmitter housing

Turning the aluminum field housing
#
Warning! The turning mechanism in devices with Ex d/de or FM/CSA Cl. I Div. 1 classification is not the same as that described here. The procedure for turning these housings is described in the Ex-specific documentation.
1. Loosen the two securing screws.
2. Turn the bayonet catch as far as it will go.
3. Carefully lift the transmitter housing: – Promag D: approx. 10 mm (0.39 inch) above the securing screws – Promag L, W, P, H: to the stop
4. Turn the transmitter housing to the desired position: – Promag D: max. 180° clockwise or max. 180° counterclockwise – Promag L, W, P, H: max. 280° clockwise or max. 20° counterclockwise
5. Lower the housing into position and re-engage the bayonet catch.
6. Retighten the two securing screws.
a0004302
Fig. 24: Turning the transmitter housing (aluminum field housing)
Turning the stainless-steel field housing
1. Loosen the two securing screws.
2. Carefully lift the transmitter housing as far as it will go.
3. Turn the transmitter housing to the desired position (max. 2 × 90° in either direction).
4. Lower the housing into position.
5. Retighten the two securing screws.
Fig. 25: Turning the transmitter housing (stainless-steel field housing)
a0004303
Endress+Hauser 39
Page 40
Installation Promag 50
4 x 45°

3.3.7 Turning the onsite display

1. Unscrew the cover of the electronics compartment from the transmitter housing.
2. Press the side latches on the display module and remove it from the electronics compartment cover plate.
3. Turn the display to the desired position (max. 4 × 45° in both directions) and reset it onto the cover plate of the electronics compartment.
4. Screw the cover of the electronics compartment firmly back onto the transmitter housing.
Fig. 26: Turning the local display (field housing)
a0003236
40 Endress+Hauser
Page 41
Promag 50 Installation
a
b
c
c
90 (3.54)
35 (1.38)
192 (7.56)
81.5(3.2)
mm (inch)

3.3.8 Installing the wall-mount housing

There are various ways of installing the wall-mount transmitter housing:
• Direct wall mounting
• Installation in control panel (with separate mounting kit, accessories) ä 42
• Pipe mounting (with separate mounting kit, accessories) ä 42 Caution!
"
• Make sure that the ambient temperature does not exceed the permissible range at the mounting location, –20 to +60 °C (–4 to + °140 F), optional –40 to +60 °C (–40 to +140 °F). Install the device at a shady location. Avoid direct sunlight.
• Always install the wall-mount housing in such a way that the cable entries are pointing down.
Direct wall mounting
1. Drill the holes as illustrated in the graphic.
2. Remove the cover of the connection compartment (a).
3. Push the two securing screws (b) through the appropriate bores (c) in the housing.
– Securing screws (M6): max. Ø 6.5 mm (0.26") – Screw head: max. Ø 10.5 mm (0.41")
4. Secure the transmitter housing to the wall as indicated.
5. Screw the cover of the connection compartment (a) firmly onto the housing.
Fig. 27: Mounted directly on the wall
Endress+Hauser 41
a0001130
Page 42
Installation Promag 50
245(9.65)
~110 (~4.33)
210 (8.27)
+0.5 (+0.019) –0.5(–0.019)
+0.5 (+0.019) –0.5(–0.019)
mm (inch)
Ø 20…70
(Ø 0.79…2.75)
~~6.1)155 (
mm (inch)
Panel-mounted installation
1. Prepare the opening in the panel as illustrated in the graphic.
2. Slide the housing into the opening in the panel from the front.
3. Screw the fasteners onto the wall-mount housing.
4. Place the threaded rods in the fasteners and screw them down until the housing is seated tightly against the panel. Afterwards, tighten the locking nuts. Additional support is not necessary.
Fig. 28: Panel installation (wall-mount housing)
Pipe mounting
The assembly should be performed by following the instructions in the graphic. Caution!
"
If the device is mounted to a warm pipe, make certain that the housing temperature does not exceed +60 °C (+140 °F), which is the maximum permissible temperature.
a0001131
Fig. 29: Pipe mounting (wall-mount housing)
42 Endress+Hauser
a0001132
Page 43
Promag 50 Installation

3.4 Post-installation check

Perform the following checks after installing the measuring device in the pipe:
Device condition and specifications Notes
Is the device damaged (visual inspection)? -
Does the device correspond to specifications at the measuring point, including process temperature and pressure, ambient temperature, minimum fluid conductivity, measuring range, etc.?
Installation Notes
Does the arrow on the sensor nameplate match the actual direction of flow through the pipe?
Is the position of the measuring electrode plane correct? ä 15
Is the position of the empty pipe detection electrode correct? ä 15
Were all screws tightened to the specified torques when the sensor was installed? Promag D ä 23
Were the correct seals used (type, material, installation)? Promag D ä 21
Are the measuring point number and labeling correct (visual inspection)? -
Process environment / process conditions Notes
ä 100
-
Promag L ä 25 Promag W ä 27 Promag P ä 33
Promag Lä 24 Promag W ä 27 Promag P ä 32 Promag H ä 36
Were the inlet and outlet runs respected? Inlet run 5 × DN
Outlet run 2 × DN
Is the measuring device protected against moisture and direct sunlight? -
Is the sensor adequately protected against vibration (attachment, support)? Acceleration up to 2 g by
analogy with IEC 600 68-2-8
Endress+Hauser 43
Page 44
Wiring Promag 50

4 Wiring

#
!
#
"
Warning! When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to these Operating Instructions. Please do not hesitate to contact your Endress+Hauser representative if you have any questions.
Note! The device does not have an internal circuit breaker. For this reason, assign the device a switch or power-breaker switch capable of disconnecting the power supply line from the mains.

4.1 Connecting the remote version

4.1.1 Connecting Promag D, L, W, P, H

Warning!
• Risk of electric shock! Switch off the power supply before opening the device. Do not install or
wire the device while it is connected to the power supply. Failure to comply with this precaution can result in irreparable damage to the electronics.
• Risk of electric shock! Connect the protective conductor to the ground terminal on the housing
before the power supply is applied.
Caution!
• Only sensors and transmitters with the same serial number can be connected to one another.
Communication problems can occur if the devices are not connected in this way.
• Risk of damaging the coil driver. Always switch off the power supply before connecting or
disconnecting the coil cable.
Procedure
1. Transmitter: Remove the cover from the connection compartment (a).
2. Sensor: Remove the cover from the connection housing (b).
3. Feed the signal cable (c) and the coil cable (d) through the appropriate cable entries.
Caution!
"
Route the connecting cables securely (see "Connecting cable length" ä 20).
4. Terminate the signal and coil current cable as indicated in the table: Promag D, L, W, P Refer to the table ä 47 Promag H Refer to the "Cable termination" table ä 48
5. Establish the wiring between the sensor and the transmitter. The electrical wiring diagram that applies to your device can be found:
• In the corresponding graphic:
å 30 (Promag D) å 31 (Promag L, W, P); å 32 (Promag H)
• In the cover of the sensor and transmitter
Note!
!
The cable shields of the Promag H sensor are grounded by means of the strain relief terminals (see also the "Cable termination" table ä 48)
Caution!
"
Insulate the shields of cables that are not connected to eliminate the risk of short-circuits with neighboring cable shields inside the connection housing.
6. Transmitter: Screw the cover on the connection compartment (a).
7. Sensor: Secure the cover on the connection housing (b).
44 Endress+Hauser
Page 45
Promag 50 Wiring
E1
E2
GND
E
S1
E1
E2
S2
GND
E
S
5
7
4
37
42 41
42 41
6
5
7
8437 36
n.c. n.c.
dc
c
d
a
b
E1
E2
GND
E
S1
E1
E2
S2
GND
E
S
5
7
4
37
42 41
42 41
6
5
7
8437 36
n.c. n.c.
dc
c
d
a
b
n.c.
Promag D
A0010882
Fig. 30: Connecting the remote version of Promag D
a Wall-mount housing connection compartment b Cover of the sensor connection housing c Signal cable d Coil current cable n.c. Not connected, insulated cable shields
Wire colors/Terminal No.: 5/6 = braun, 7/8 = white, 4 = green, 37/36 = yellow
Promag L, W, P
A0011722
Fig. 31: Connecting the remote version of Promag L, W, P
a Wall-mount housing connection compartment b Cover of the sensor connection housing c Signal cable d Coil current cable n.c. Not connected, insulated cable shields
Wire colors/Terminal No.: 5/6 = braun, 7/8 = white, 4 = green, 37/36 = yellow
Endress+Hauser 45
Page 46
Wiring Promag 50
E1
E2
GND
E
S1
E1
E2
S2
GND
E
S
5
7
4
37
42 41
42 41
6
5
7
8437 36
n.c. n.c.
dc
c
d
a
b
n.c.
Promag H
Fig. 32: Connecting the remote version of Promag H
a Wall-mount housing connection compartment b Cover of the sensor connection housing c Signal cable d Coil current cable n.c. Not connected, insulated cable shields
Wire colors/Terminal No.: 5/6 = braun, 7/8 = white, 4 = green, 37/36 = yellow
A0011747
46 Endress+Hauser
Page 47
Promag 50 Wiring
A
B
GND
m
m
m
m
n
n
n
n
80 (3.15)
50 (1.97)
17 (0.67)
8 (0.31)
100 (3.94)*mm (inch)
A
B
m
m
m
90 (3.54)*
70 (2.76)
50 (1.97)
10 (0.39)
8 (0.31)
mm (inch)
A
B
m
n
m
n
n
GND
mm (inch)
80 (3.15)
50 (1.97)
8 (0.31)
³1 (0.04)
170 (6.69)*
20 (0.79)*
17 (0.67)
B
A
m
m
m
mm (inch)
70 (2.76) 50 (1.97) 10 (0.39)
8 (0.31)
160 (6.30)*20 (0.79)*
Cable termination for the remote version Promag D / Promag L / Promag W / Promag P
Terminate the signal and coil current cables as shown in the figure below (Detail A). Ferrules must be provided on the fine-wire cores (Detail B: m = red ferrules, 1.0 mm; n = white ferrules, 0.5 mm). * Stripping only for reinforced cables
Caution!
"
When fitting the connectors, pay attention to the following points:
• Signal cable Make sure that the ferrules do not touch the wire shield on the sensor side. Minimum distance = 1 mm (exception "GND" = green cable)
• Coil current cable Insulate one core of the three-core wire at the level of the core reinforcement; you only require two cores for the connection.
TRANSMITTER
Signal cable Coil current cable
A0002687 A0002688
SENSOR
Signal cable Coil current cable
A0002646
Endress+Hauser 47
A0002650
Page 48
Wiring Promag 50
A
B
GND
m
m
m
m
n
n
n
n
80 (3.15)
50 (1.97)
17 (0.67) 8 (0.31)
mm (inch)
A
B
m
m
m
70 (2.76)
50 (1.97)
8 (0.31)
mm (inch)
10 (0.39)
A
B
GND
m
n
n
n
mm (inch)
80 (3.15)
15 (0.59)
8 (0.31)
17 (0.67)
³
1 (0.04)³
A
B
m
m
70 (2.76)
15 ( )0.59
8 (0.31)
40 (1.57)
mm (inch)
Cable termination for the remote version Promag H
Terminate the signal and coil current cables as shown in the figure below (Detail A). Ferrules must be provided on the fine-wire cores (Detail B: m = red ferrules, 1.0 mm; n = white ferrules, 0.5 mm).
Caution!
"
When fitting the connectors, pay attention to the following points:
• Signal cable Make sure that the ferrules do not touch the wire shield on the sensor side. Minimum distance = 1 mm (exception "GND" = green cable).
• Coil current cable Insulate one core of the three-core wire at the level of the core reinforcement; you only require two cores for the connection.
• On the sensor side, reverse both cable shields approx. 15 mm over the outer jacket. The strain relief ensures an electrical connection with the connection housing.
TRANSMITTER
Signal cable Coil current cable
A0002686 A0002684
SENSOR
Signal cable Coil current cable
48 Endress+Hauser
A0002647
A0002648
Page 49
Promag 50 Wiring
1 2 3 4 5 6 7
ab

4.1.2 Cable specifications

Signal cable
• 3 × 0.38 mm² PVC cable with common, braided copper shield ( 7 mm) and individually shielded cores
• With Empty Pipe Detection (EPD): 4 × 0.38 mm² PVC cable with common, braided copper shield ( 7 mm) and individually shielded cores
• Conductor resistance: 50 km
• Capacitance: core/shield: 420 pF/m
• Permanent operating temperature: –20 to +80 °C
• Cable cross-section: max. 2.5 mm²
Coil cable
• 2 × 0.75 mm² PVC cable with common, braided copper shield ( 7 mm)
• Conductor resistance: 37 km
• Capacitance: core/core, shield grounded: 120 pF/m
• Operating temperature: –20 to +80 °C
• Cable cross-section: max. 2.5 mm²
• Test voltage for cable insulation: 1433 V AC r.m.s. 50/60 Hz or 2026 V DC
Fig. 33: Cable cross-section
a Signal cable b Coil current cable
1Core 2 Core insulation 3Core shield 4 Core jacket 5 Core reinforcement 6 Cable shield 7 Outer jacket
Reinforced connecting cables
As an option, Endress+Hauser can also deliver reinforced connecting cables with an additional, reinforcing metal braid. Reinforced connecting cables should be used when laying the cable directly in the ground, if there is a risk of damage from rodents or if using the measuring device below IP 68 degree of protection.
Operation in zones of severe electrical interference:
The measuring device complies with the general safety requirements in accordance with EN 61010 and the EMC requirements of IEC/EN 61326.
Caution!
"
Grounding is by means of the ground terminals provided for the purpose inside the connection housing. Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as
Endress+Hauser 49
short as possible.
A0003194
Page 50
Wiring Promag 50
b
b
c
d
a
a
2 1
–27 –25 –23 –21
+26
+24 +22 +20
L1 (L+)
N(L-)
g
f
e

4.2 Connecting the measuring unit

4.2.1 Connecting the transmitter

#
Warning!
• Risk of electric shock! Switch off the power supply before opening the device. Do not install or wire the device while it is energized. Failure to comply with this precaution can result in irreparable damage to the electronics.
• Risk of electric shock! Connect the protective conductor to the ground terminal on the housing before the power supply is applied (not necessary if the power supply is galvanically isolated).
• Compare the specifications on the nameplate with the local voltage supply and frequency. Also comply with national regulations governing the installation of electrical equipment.
1. Remove the cover of the connection compartment (f) from the transmitter housing.
2. Feed the power supply cable (a) and the signal cable (b) through the appropriate cable entries.
3. Perform the wiring:
– Wiring diagram (aluminum housing) å 34 – Wiring diagram (stainless steel housing) å 35 – Wiring diagram (wall-mount housing) å 36 – Terminal assignment ä 52
4. Screw the cover of the connection compartment (f) firmly onto the transmitter housing.
Fig. 34: Connecting the transmitter (aluminum field housing). Cable cross-section: max. 2.5 mm
a Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC b Signal cable: Terminals Nos. 20–27 ä 52 c Ground terminal for protective ground d Ground terminal for signal cable shield e Service connector for connecting service interface FXA193 (Fieldcheck, FieldCare) f Cover of the connection compartment g Securing clamp
50 Endress+Hauser
a0004582
Page 51
Promag 50 Wiring
b
c
d
a
2 1
L1 (L+)
N (L-)
f
b
a
e
–27 –25 –23 –21
+26 +24 +22 +20
1
2
cd
e
a
abb
f
+
22
–
23
+
20
–
21
+
24
–
25
+
26
–
27
L1 (L+)
N(L-)
a0004584
Fig. 35: Connecting the transmitter (stainless steel field housing); cable cross-section: max. 2.5 mm
a Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC b Signal cable: Terminals Nos. 20–27 ä 52 c Ground terminal for protective ground d Ground terminal for signal cable shield e Service connector for connecting service interface FXA193 (Fieldcheck, FieldCare) f Cover of the connection compartment
a0001135
Fig. 36: Connecting the transmitter (wall-mount housing); cable cross-section: max. 2.5 mm
a Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC b Signal cable: Terminals Nos. 20–27 ä 52 c Ground terminal for protective ground d Ground terminal for signal cable shield e Service connector for connecting service interface FXA193 (Fieldcheck, FieldCare) f Cover of the connection compartment
Endress+Hauser 51
Page 52
Wiring Promag 50
+26
-27
4
2
³W250
1
3

4.2.2 Terminal assignment

Terminal No. (inputs / outputs)
Order version 20 (+) / 21 (–) 22 (+) / 23 (–) 24 (+) / 25 (–) 26 (+) / 27 (–)
50***-***********W - - -
50***-***********A - - Frequency output
50***-***********D
50***-***********S - -
50***-***********T - -
Status input Status output Frequency output
Frequency output
Ex i
Frequency output
Ex i
Current output
HART
Current output
HART
Current output
HART
Current output, Ex i,
active, HART
Current output, Ex i,
passive, HART
!
!
Note! Functional values of the inputs and outputs ä 96

4.2.3 HART connection

Users have the following connection options at their disposal:
• Direct connection to transmitter by means of terminals 26(+) and 27 ()
• Connection by means of the 4 to 20 mA circuit. Note!
• The measuring loop's minimum load must be at least 250 .
• After commissioning, make the following settings: – CURRENT SPAN function "4–20 mA HART"
– Switch HART write protection on or off ä 63
Connection of the HART handheld communicator
See also the documentation issued by the HART Communication Foundation, and in particular HCF LIT 20: "HART, a technical summary".
a0004586
Fig. 37: Electrical connection of HART handheld Field Xpert SFX100
1 HART handheld Field Xpert SFX100 2 Auxiliary energy 3 Shielding 4 Other devices or PLC with passive input
52 Endress+Hauser
Page 53
Promag 50 Wiring
+26
³W250
–27
1
2
3
5
4
Connection of a PC with an operating software
In order to connect a PC with operating software (e.g. "FieldCare"), a HART modem (e.g. "Commubox FXA195") is needed.
a0004592
Fig. 38: Electrical connection of a PC with operating software
1 PC with operating software 2 Auxiliary energy 3 Shielding 4 Other devices or PLC with passive input 5 HART modem, e.g. Commubox FXA195

4.3 Potential equalization

#
Warning! The measuring system must be included in the potential equalization.
Perfect measurement is only ensured when the fluid and the sensor have the same electrical potential. This is ensured by the reference electrode integrated in the sensor as standard.
The following should also be taken into consideration for potential equalization:
• Internal grounding concepts in the company
• Operating conditions, such as the material/grounding of the pipes (see Table)

4.3.1 Potential equalization for Promag D

• No reference electrode is integrated! For the two ground disks of the sensor an electrical connection to the fluid is always ensured.
• Exampels for connections ä 54

4.3.2 Potential equalization for Promag W, P, L

• Reference electrode integrated in the sensor as standard
• Exampels for connections ä 55

4.3.3 Potential equalization for Promag H

No reference electrode is integrated! For the metal process connections of the sensor an electrical connection to the fluid is always ensured.
Caution!
"
If using process connections made of a synthetic material, ground rings have to be used to ensure that potential is equalized (ä 37). The necessary ground rings can be ordered separately from Endress+Hauser as accessories (ä 76).
Endress+Hauser 53
Page 54
Wiring Promag 50
2
2
1

4.3.4 Exampels for potential equalization connections for Promag D

Standard case
Operating conditions Potential equalization
When using the measuring device in a:
• Metal, grounded pipe
• Plastic pipe
• Pipe with insulating lining Potential equalization takes place via the ground terminal of the
transmitter (standard situation).
Note!
!
When installing in metal pipes, we recommend you connect the ground terminal of the transmitter housing with the piping.
Fig. 39: Via the ground terminal of the
transmitter
Special cases
a00012172
Operating conditions Potential equalization
When using the measuring device in a:
• Metal pipe that is not grounded This connection method also applies in situations where:
• Customary potential equalization cannot be ensured
• Excessively high equalizing currents can be expected Potential equalization takes place via the ground terminal of the
transmitter and the two pipe flanges. Here, the ground cable (copper wire, 6 mm² (0.0093 in mounted directly on the conductive flange coating with flange screws.
When using the measuring device in a:
• Pipe with a cathodic protection unit The device is installed potential-free in the pipe.
Only the two flanges of the pipe are connected with a ground cable (copper wire, 6 mm² (0.0093 in is mounted directly on the conductive flange coating with flange screws.
Note the following when installing:
• The applicable regulations regarding potential-free installation must be observed.
•There should be no electrically conductive connection between the pipe and the device.
• The mounting material must withstand the applicable torques.
)). Here, the ground cable
)) is
Fig. 40: Via the ground terminal of the
transmitter and the flanges of the pipe .
Fig. 41: Potential equalization and cathodic
protection
1 Power supply isolation transformer 2 Electrically isolated
a00012173
a00012174
54 Endress+Hauser
Page 55
Promag 50 Wiring
DN 300£ DN 350³
4.3.5 Exampels for potential equalization connections for PromagL,W,P
Standard case
Operating conditions Potential equalization
When using the measuring device in a:
• Metal, grounded pipe Potential equalization takes place via the ground terminal of the
transmitter (standard situation).
Note!
!
When installing in metal pipes, we recommend you connect the ground terminal of the transmitter housing with the piping.
A0011892
Fig. 42: Via the ground terminal of the
transmitter
Special cases
Operating conditions Potential equalization
When using the measuring device in a:
• Metal pipe that is not grounded This connection method also applies in situations where:
• Customary potential equalization cannot be ensured
• Excessively high equalizing currents can be expected Both sensor flanges are connected to the pipe flange by means of
a ground cable (copper wire, 6 mm² (0.0093 in Connect the transmitter or sensor connection housing, as applicable, to ground potential by means of the ground terminal provided for the purpose.
Ground cable installation depends on the nominal diameter:
•DN  300: The ground cable is mounted directly on the conductive flange coating with the flange screws.
•DN  350: The ground cable is mounted directly on the metal transport bracket.
Note!
!
The ground cable for flange-to-flange connections can be ordered separately as an accessory from Endress+Hauser.
When using the measuring device in a:
• Plastic pipe
• Pipe with insulating lining
This connection method also applies in situations where:
• Customary potential equalization cannot be ensured
• Excessively high equalizing currents can be expected
Potential equalization takes place using additional ground disks, which are connected to the ground terminal via a ground cable (copper wire, min. 6 mm² (0.0093 in ground disks, please comply with the enclosed Installation Instructions.
)) and grounded.
)). When installing the
Fig. 43: Via the ground terminal of the
transmitter and the flanges of the pipe
Fig. 44: Via the ground terminal of the
transmitter
A0011893
A0011895
Endress+Hauser 55
Page 56
Wiring Promag 50
1
2
2
ab
Operating conditions Potential equalization
When using the measuring device in a:
• Pipe with a cathodic protection unit The device is installed potential-free in the pipe.
Only the two flanges of the pipe are connected with a ground cable (copper wire, 6 mm² (0.0093 in is mounted directly on the conductive flange coating with flange screws.
Note the following when installing:
• The applicable regulations regarding potential-free installation must be observed.
•There should be no electrically conductive connection between the pipe and the device.
• The mounting material must withstand the applicable torques.
)). Here, the ground cable
A0011896
Fig. 45: Potential equalization and cathodic
protection
1 Power supply isolation transformer 2 Electrically isolated

4.4 Degree of protection

The devices meet all the requirements of IP 67 degree of protection. Compliance with the following points is mandatory following installation in the field or servicing in
order to ensure that IP 67 protection is maintained:
• The housing seals must be clean and undamaged when inserted into their grooves. The seals must be dried, cleaned or replaced if necessary.
• All threaded fasteners and screw covers must be firmly tightened.
• The cables used for connection must be of the specified outside diameter ä 49.
• Firmly tighten the cable entries.
• The cables must loop down before they enter the cable entries ("water trap"). This arrangement prevents moisture penetrating the entry. Always install the measuring device in such a way that the cable entries do not point up.
• Remove all unused cable entries and insert plugs instead.
• Do not remove the grommet from the cable entry.
Fig. 46: Installation instructions, cable entries
Caution!
"
Do not loosen the threaded fasteners of the sensor housing, as otherwise the degree of protection guaranteed by Endress+Hauser no longer applies.
!
Note! The Promag L, Promag W and Promag P sensors can be supplied with IP 68 rating (permanent immersion in water to a depth of 3 meters (10 ft)). In this case the transmitter must be installed remote from the sensor. The Promag L sensors with IP 68 rating are only available with stainless steel flanges.
56 Endress+Hauser
a0001914
Page 57
Promag 50 Wiring

4.5 Post-connection check

Perform the following checks after completing electrical installation of the measuring device:
Device condition and specifications Notes
Are cables or the device damaged (visual inspection)? -
Electrical connection Notes
Does the supply voltage match the specifications on the nameplate? • 85 to 250 V AC (50 to 60 Hz)
Do the cables used comply with the necessary specifications? ä 49
Do the cables have adequate strain relief? -
Is the cable type route completely isolated? Without loops and crossovers?
Are the power-supply and signal cables correctly connected? See the wiring diagram inside the
Only remote version: Is the flow sensor connected to the matching transmitter electronics?
Only remote version: Is the connecting cable between sensor and transmitter connected correctly?
Are all screw terminals firmly tightened? -
Have the measures for grounding/potential equalization been correctly implemented?
Are all cable entries installed, firmly tightened and correctly sealed? Cables looped as "water traps"?
• 20 to 28 V AC (50 to 60 Hz) 11 to 40 V DC
-
cover of the terminal compartment
Check serial number on nameplates of sensor and connected transmitter.
ä 44
ä 53
ä 56
Are all housing covers installed and firmly tightened? -
Endress+Hauser 57
Page 58
Operation Promag 50
Esc
E
+
-
1
32
+48.25 xx/yy
+3702.6 x

5Operation

5.1 Display and operating elements

The local display enables you to read all important parameters directly at the measuring point and configure the device. The display area consists of two lines; this is where measured values are displayed, and/or status variables (direction of flow, partially filled pipe, bar graph, etc.). You can change the assignment of display lines to variables at will in order to customize the display to suit your needs and preferences ( "Description of Device Functions" manual).
A0001141
Fig. 47: Display and operating elements
1 Liquid crystal display
The two-line liquid-crystal display shows measured values, dialog texts, error messages and information messages. The display as it appears when normal measuring is in progress is known as the HOME position (operating mode). – Upper display line: Shows primary measured values, e.g. volume flow in [ml/min] or in [%]. – Lower display line: Shows supplementary measured variables and status variables, e.g. totalizer reading in [m3],
bar graph, measuring point designation
2 Plus/minus keys
– Enter numerical values, select parameters – Select different function groups within the function matrix
Press the +/- keys simultaneously to trigger the following functions: – Exit the function matrix step by step HOME position – Press and hold down +/- keys for longer than 3 seconds Return directly to HOME position – Cancel data entry
3 Enter key
–HOME positionEntry into the function matrix – Save the numerical values you input or settings you change
58 Endress+Hauser
Page 59
Promag 50 Operation
>3s
-
+
E
Esc
E
E
E
E
E E E E E
–
+
+
Esc
–
+
Esc
–
+
Esc
–
E
m
n
o
p

5.2 Brief operating instructions on the function matrix

!
Note!
• See the general notes on ä 60.
• Detailed description of all the functions "Description of Device Functions" manual The function matrix comprises two levels, namely the function groups and the functions of the
function groups. The groups are the highest-level grouping of the control options for the device. A number of functions is assigned to each group. You select a group in order to access the individual functions for operating and configuring the device.
1. HOME position F Enter the function matrix
2. Select a function group (e.g. OPERATION)
3. Select a function (e.g. LANGUAGE) Change parameter/enter numerical values:
P select or enter enable code, parameters, numerical values F save your entries
4. Exit the function matrix: – Press and hold down Esc key (X) for longer than 3 seconds HOME position – Repeatedly press Esc key (X) return step by step to HOME position
A0001142
Fig. 48: Selecting functions and configuring parameters (function matrix)
Endress+Hauser 59
Page 60
Operation Promag 50

5.2.1 General notes

The Quick Setup menu (ä 70) is adequate for commissioning in most instances. Complex measuring operations on the other hand necessitate additional functions that you can configure as necessary and customize to suit your process parameters. The function matrix, therefore, comprises a multiplicity of additional functions which, for the sake of clarity, are arranged in a number of function groups.
Comply with the following instructions when configuring functions:
• You select functions as described on ä 59.
• You can switch off certain functions (OFF). If you do so, related functions in other function groups will no longer be displayed.
• Certain functions prompt you to confirm your data entries. Press P to select "SURE [ YES ]" and press F again to confirm. This saves your setting or starts a function, as applicable.
• Return to the HOME position is automatic if no key is pressed for 5 minutes.
!
"
"
Note!
• The transmitter continues to measure while data entry is in progress, i.e. the current measured values are output via the signal outputs in the normal way.
• If the power supply fails, all preset and configured values remain safely stored in the EEPROM.
Caution! All functions are described in detail, including the function matrix itself, in the "Description of Device Functions" manual, which is a separate part of these Operating Instructions.

5.2.2 Enabling the programming mode

The function matrix can be disabled. Disabling the function matrix rules out the possibility of inadvertent changes to device functions, numerical values or factory settings. A numerical code (factory setting = 50) has to be entered before settings can be changed. If you use a code number of your choice, you exclude the possibility of unauthorized persons accessing data ( see the "Description of Device Functions" manual).
Comply with the following instructions when entering codes:
• If programming is disabled and the P operating elements are pressed in any function, a prompt for the code automatically appears on the display.
• If "0" is specified as the customer's code, programming is always enabled.
• The Endress+Hauser service organization can be of assistance if you mislay your personal code.
Caution! Changing certain parameters such as all sensor characteristics, for example, influences numerous functions of the entire measuring system, particularly measuring accuracy. There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the Endress+Hauser service organization. Please contact Endress+Hauser if you have any questions.

5.2.3 Disabling the programming mode

Programming is disabled if you do not press the operating elements within 60 seconds following automatic return to the HOME position. You can also disable programming in the "ACCESS CODE" function by entering any number (other than the customer's code).
60 Endress+Hauser
Page 61
Promag 50 Operation
1
2453
XXXXXXXXXX #000 00:00:05
P

5.3 Displaying error messages

5.3.1 Type of error

Errors which occur during commissioning or measuring operation are displayed immediately. If two or more system or process errors occur, the error with the highest priority is the one shown on the display.
The measuring system distinguishes between two types of error:
• System errors ä 80: This group comprises all device errors, e.g. communication errors, hardware faults, etc.
• Process errors ä 82: This group comprises all application errors, e.g. empty pipe, etc.
A0000991
Fig. 49: Error messages on the display (example)
1 Error type:
– P = process error – S = system error
2 Error message type:
– $ = fault message
– ! = notice message 3 Error designation: e.g. EMPTY PIPE = measuring tube is only partly filled or completely empty 4 Error number: e.g. #401 5 Duration of most recent error occurrence (in hours, minutes and seconds)

5.3.2 Error message types

Users have the option of weighting certain errors differently, in other words having them classed as "Fault messages" or "Notice messages". You can define messages in this way with the aid of the function matrix ("Description of Device Functions" manual). Serious system errors, e.g. module defects, are always identified and classed as "fault messages" by the measuring device.
Notice message (!)
• Displayed as Exclamation mark (!), error type (S: system error, P: process error)
• The error in question has no effect on the outputs of the measuring device.
Fault message ($)
• Displayed as Lightning flash ( $), error type (S: system error, P: process error).
• The error in question has a direct effect on the outputs.
The response of the individual outputs (failsafe mode) can be defined in the function matrix using the "FAILSAFE MODE" function ( "Description of Device Functions" manual).
!
Note! For security reasons, error messages should be output via the status output.
Endress+Hauser 61
Page 62
Operation Promag 50

5.4 Communication

In addition to local operation, the measuring device can be configured and measured values can be obtained by means of the HART protocol. Digital communication takes place using the 4–20 mA current output HART ä 52.
The HART protocol allows the transfer of measuring and device data between the HART master and the field devices for configuration and diagnostics purposes. The HART master, e.g. a handheld terminal or PC-based operating programs (such as FieldCare), require device description (DD) files which are used to access all the information in a HART device. Information is exclusively transferred using so-called "commands". There are three different command classes:
• Universal commands: All HART device support and use universal commands. The following functionalities are linked to them: – Identify HART devices – Reading digital measured values (volume flow, totalizer, etc.)
• Common practice commands: Common practice commands offer functions which are supported and can be executed by most but not all field devices.
• Device-specific commands: These commands allow access to device-specific functions which are not HART standard. Such commands access individual field device information, amongst other things, such as empty/full pipe calibration values, low flow cutoff settings, etc.
!
Note! The device has access to all three command classes. A list of all the "Universal commands" and "Common practice commands" is provided on ä 64.

5.4.1 Operating options

For the complete operation of the measuring device, including device-specific commands, there are DD files available to the user to provide the following operating aids and programs:
Field Xpert HART Communicator
Selecting device functions with a HART Communicator is a process involving a number of menu levels and a special HART function matrix. The HART manual in the carrying case of the HART Communicator contains more detailed information on the device.
Operating program "FieldCare"
FieldCare is Endress+Hauser’s FDT-based plant Asset Management Tool and allows the configuration and diagnosis of intelligent field devices. By using status information, you also have a simple but effective tool for monitoring devices. The Proline flow measuring devices are accessed via a service interface or via the service interface FXA193.
Operating program "SIMATIC PDM" (Siemens)
SIMATIC PDM is a standardized, manufacturer-independent tool for the operation, configuration, maintenance and diagnosis of intelligent field devices.
Operating program "AMS" (Emerson Process Management)
AMS (Asset Management Solutions): program for operating and configuring devices.
62 Endress+Hauser
Page 63
Promag 50 Operation

5.4.2 Current device description files

The following table illustrates the suitable device description file for the operating tool in question and then indicates where these can be obtained.
HART protocol:
Valid for device software: 2.03.XX Function DEVICE SOFTWARE
Device data HART
Manufacturer ID: Device ID:
HART version data: Device Revision 6/ DD Revision 1
Software release: 07.2009
Operating program: Sources for obtaining device descriptions:
Handheld Field Xpert SFX100 Use update function of handheld terminal
FieldCare / DTM • www.endress.com Download
AMS www.endress.com Download
SIMATIC PDM www.endress.com Download
(ENDRESS+HAUSER)
11
hex
41
hex
• CD-ROM (Endress+Hauser order number 56004088)
• DVD (Endress+Hauser order number 70100690)
Function MANUFACTURER ID Function DEVICE ID
!
!
Tester/simulator: Sources for obtaining device descriptions:
Fieldcheck Update by means of FieldCare with the flow device FXA193/291 DTM in the
Fieldflash module
Note! The "Fieldcheck" tester/simulator is used for testing flowmeters in the field. When used in conjunction with the "FieldCare" software package, test results can be imported into a database, printed out and used for official certification. Contact your Endress+Hauser representative for more information.

5.4.3 Device variables

The following device variables are available using the HART protocol:
Code (decimal) Device variable
0 OFF (not assigned)
1 Volume flow
250 Totalizer 1
251 Totalizer 2
At the factory, the process variables are assigned to the following device variables:
• Primary process variable (PV) Volume flow
• Second process variable (SV) Totalizer 1
• Third process variable (TV) not assigned
• Fourth process variable (FV) not assigned Note!
You can set or change the assignment of device variables to process variables using Command 51.

5.4.4 Switching HART write protection on/off

The HART write protection can be switched on and off using the HART WRITE PROTECT device function ("Description of Device Functions" manual).
Endress+Hauser 63
Page 64
Operation Promag 50

5.4.5 Universal and common practice HART commands

The following table contains all the universal commands supported by the device.
Command No. HART command / Access type
Universal commands
0 Read unique device identifier
Access type = read
1 Read primary process variable
Access type = read
2 Read the primary process variable
as current in mA and percentage of the set measuring range Access type = read
3 Read the primary process variable
as current in mA and four dynamic process variables Access type = read
Command data (numeric data in decimal form)
none Device identification delivers information on the device and
none – Byte 0: HART unit code of the primary process variable
none – Bytes 0-3: actual current of the primary process variable in
none 24 bytes are sent as a response:
Response data (numeric data in decimal form)
the manufacturer. It cannot be changed. The response consists of a 12 byte device ID:
– Byte 0: fixed value 254 – Byte 1: Manufacturer ID, 17 = E+H – Byte 2: Device type ID, 65 = Promag 50 – Byte 3: Number of preambles – Byte 4: Universal commands rev. no. – Byte 5: Device-specific commands rev. no. – Byte 6: Software revision – Byte 7: Hardware revision – Byte 8: Additional device information – Bytes 9-11: Device identification
– Bytes 1-4: Primary process variable Factory setting:
Primary process variable = Volume flow
Note!
!
• Manufacturer-specific units are represented using the HART unit code "240".
• You can change the assignment of device variables to process variables using Command 51.
mA
– Bytes 4-7: % value of the set measuring range Factory setting:
Primary process variable = Volume flow
Note!
!
You can change the assignment of device variables to process variables using Command 51.
– Bytes 0-3: primary process variable current in mA – Byte 4: HART unit code of the primary process variable – Bytes 5-8: Primary process variable – Byte 9: HART unit code of the second process variable – Bytes 10-13: Second process variable – Byte 14: HART unit code of the third process variable – Bytes 15-18: Third process variable – Byte 19: HART unit code of the fourth process variable – Bytes 20-23: Fourth process variable
Factory setting:
• Primary process variable = Volume flow
• Second process variable = Totalizer 1
• Third process variable = OFF (not assigned)
• Fourth process variable = OFF (not assigned)
Note!
!
• Manufacturer-specific units are represented using the HART unit code "240".
• You can change the assignment of device variables to process variables using Command 51.
64 Endress+Hauser
Page 65
Promag 50 Operation
Command No. HART command / Access type
6 Set HART shortform address
Access type = write
11 Read unique device identification
using the TAG (measuring point designation) Access type = read
12 Read user message
Access type = read
13 Read TAG, descriptor and date
Access type = read
14 Read sensor information on
primary process variable
15 Read output information of
primary process variable Access type = read
Command data (numeric data in decimal form)
Byte 0: desired address (0 to 15) Factory setting: 0
Note!
!
With an address >0 (multidrop mode), the current output of the primary process variable is set to 4 mA.
Bytes 0-5: TAG Device identification delivers information on the device and
none Bytes 0-24: User message
none – Bytes 0-5: TAG
none – Bytes 0-2: Sensor serial number
none – Byte 0: Alarm selection ID
Response data (numeric data in decimal form)
Byte 0: active address
the manufacturer. It cannot be changed. The response consists of a 12 byte device ID if the given TAG
agrees with the one saved in the device: – Byte 0: fixed value 254 – Byte 1: Manufacturer ID, 17 = E+H – Byte 2: Device type ID, 65 = Promag 50 – Byte 3: Number of preambles – Byte 4: Universal commands rev. no. – Byte 5: Device-specific commands rev. no. – Byte 6: Software revision – Byte 7: Hardware revision – Byte 8: Additional device information – Bytes 9-11: Device identification
Note!
!
You can write the user message using Command 17.
– Bytes 6-17: descriptor – Bytes 18-20: Date
Note!
!
You can write the TAG, descriptor and date using Command 18.
– Byte 3: HART unit code of sensor limits and measuring
range of the primary process variable – Bytes 4-7: Upper sensor limit – Bytes 8-11: Lower sensor limit – Bytes 12-15: Minimum span
Note!
!
• The data relate to the primary process variable
(= volume flow).
• Manufacturer-specific units are represented using the
HART unit code "240".
– Byte 1: Transfer function ID – Byte 2: HART unit code for the set measuring range of the
primary process variable – Bytes 3-6: upper range, value for 20 mA – Bytes 7-10: lower range, value for 4 mA – Bytes 11-14: Damping constant in [s] – Byte 15: Write protection ID – Byte 16: OEM dealer ID, 17 = E+H
Factory setting: Primary process variable = Volume flow
Note!
!
• Manufacturer-specific units are represented using the
HART unit code "240".
• You can change the assignment of device variables to
process variables using Command 51.
Endress+Hauser 65
Page 66
Operation Promag 50
Command No. HART command / Access type
16 Read the device production
number Access type = read
17 Write user message
Access = write
18 Write TAG, descriptor and date
Access = write
19 Write the device production
number Access = write
The following table contains all the common practice commands supported by the device.
Command No. HART command / Access type
Common practice commands
34 Write damping value for primary
process variable Access = write
35 Write measuring range of primary
process variable Access = write
38 Device status reset (configuration
changed) Access = write
40 Simulate input current of primary
process variable Access = write
42 Perform master reset
Access = write
Command data (numeric data in decimal form)
none Bytes 0-2: Production number
You can save any 32-character long text in the device under this parameter: Bytes 0-23: Desired user message
With this parameter, you can store an 8 character TAG, a 16 character descriptor and a date: –Bytes 0-5: TAG – Bytes 6-17: descriptor – Bytes 18-20: Date
Bytes 0-2: Production number Bytes 0-2: Production number
Command data (numeric data in decimal form)
Bytes 0-3: Damping value of the primary process variable "volume flow" in seconds
Factory setting:
Primary process variable = Current output damping
Write the desired measuring range: – Byte 0: HART unit code of the primary process
variable – Bytes 1-4: upper range, value for 20 mA – Bytes 5-8: lower range, value for 4 mA
Factory setting:
Primary process variable = Volume flow
Note!
!
• The start of the measuring range (4 mA) must
correspond to the zero flow.
• If the HART unit code is not the correct one for the
process variable, the device will continue with the
last valid unit.
none none
Simulation of the desired output current of the primary process variable. An entry value of 0 exits the simulation mode: Bytes 0-3: Output current in mA
Factory setting:
Primary process variable = Volume flow
Note!
!
You can set the assignment of device variables to process variables using Command 51.
none none
Response data (numeric data in decimal form)
Displays the current user message in the device: Bytes 0-23: Current user message in the device
Displays the current information in the device: – Bytes 0-5: TAG – Bytes 6-17: descriptor – Bytes 18-20: Date
Response data (numeric data in decimal form)
Displays the current damping value in the device: Bytes 0-3: Damping value in seconds
The currently set measuring range is displayed as a response: – Byte 0: HART unit code for the set measuring range of the
primary process variable – Bytes 1-4: upper range, value for 20 mA – Bytes 5-8: lower range, value for 4 mA
Note!
!
• Manufacturer-specific units are represented using the
HART unit code "240".
• You can change the assignment of device variables to
process variables using Command 51.
Note!
!
It is also possible to execute this HART command when write protection is activated (= ON)!
The momentary output current of the primary process variable is displayed as a response: Bytes 0-3: Output current in mA
66 Endress+Hauser
Page 67
Promag 50 Operation
Command No. HART command / Access type
44 Write unit of primary process
variable Access = write
48 Read additional device status
Access = read
50 Read assignment of the device
variables to the four process variables Access = read
51 Write assignment of the device
variables to the four process variables Access = write
53 Write device variable unit
Access = write
59 Write number of preambles in
response message Access = write
Command data (numeric data in decimal form)
Set unit of primary process variable. Only units which are suitable for the process variable are transferred to the device: Byte 0: HART unit code
Factory setting:
Primary process variable = Volume flow
Note!
!
• If the written HART unit code is not the correct one for the process variable, the device will continue with the last valid unit.
• If you change the unit of the primary process variable, this has a direct impact on the system units.
none The device status is displayed in extended form as the
none Display of the current variable assignment of the process
Setting of the device variables to the four process variables: – Byte 0: Device variable code to the primary process
variable
– Byte 1: Device variable code to the second process
variable
– Byte 2: Device variable code to the third process
variable
– Byte 3: Device variable code to the fourth process
variable
Factory setting:
• Primary process variable: Volume flow
• Second process variable: Totalizer 1
• Third process variable: OFF (not assigned)
• Fourth process variable: OFF (not assigned)
This command sets the unit of the given device variables. Only those units which suit the device variable are transferred: – Byte 0: Device variable code – Byte 1: HART unit code
Code of the supported device variables: See information ä 63
Note!
!
• If the written unit is not the correct one for the device variable, the device will continue with the last valid unit.
• If you change the unit of the device variable, this has a direct impact on the system units.
This parameter sets the number of preambles which are inserted in the response messages: Byte 0: Number of preambles (4 to 20)
Response data (numeric data in decimal form)
The current unit code of the primary process variable is displayed as a response: Byte 0: HART unit code
Note!
!
Manufacturer-specific units are represented using the HART unit code "240".
response: Coding: see table ä 68
variables: – Byte 0: Device variable code to the primary process
variable – Byte 1: Device variable code to the second process variable – Byte 2: Device variable code to the third process variable – Byte 3: Device variable code to the fourth process variable
Factory setting:
• Primary process variable: Code 1 for volume flow
• Second process variable: Code 250 for totalizer
• Third process variable: Code 0 for OFF (not assigned)
• Fourth process variable: Code 0 for OFF (not assigned)
The variable assignment of the process variables is displayed as a response: – Byte 0: Device variable code to the primary process
variable – Byte 1: Device variable code to the second process variable – Byte 2: Device variable code to the third process variable – Byte 3: Device variable code to the fourth process variable
The current unit of the device variables is displayed in the device as a response: – Byte 0: Device variable code – Byte 1: HART unit code
Note!
!
Manufacturer-specific units are represented using the HART unit code "240".
The current number of preambles is displayed in the response telegram: Byte 0: Number of preambles
Endress+Hauser 67
Page 68
Operation Promag 50

5.4.6 Device status and error messages

You can read the extended device status, in this case, current error messages, via Command "48". The command delivers information which is partly coded in bits (see table below).
!
Note!
• You can find a detailed explanation of the device status and error messages and their elimination on ä 68
• Bits and bytes not listed are not assigned.
Byte Bit Error No. Short error description
0 001 Serious device error
0
1 011 Measuring amplifier has faulty EEPROM
2 012 Error when accessing data of the measuring amplifier EEPROM
1 031 S-DAT: defective or missing
1
2 032 S-DAT: Error accessing saved values
5 051 I/O and the amplifier are not compatible.
3 111 Totalizer checksum error
3
4 121 I/O board and amplifier not compatible.
3 251 Internal communication fault on the amplifier board.
4
4 261 No data reception between amplifier and I/O board
0 321 Coil current of the sensor is outside the tolerance.
5
7 339 Flow buffer:
0340
1341
2342
3 343 Frequency buffer:
6
4344
5345
6346
7 347 Pulse buffer:
0348
1349
2350
3351Current output:
7
4352
The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds.
The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds.
The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds.
Flow is out of range.
5353
6354
7 355 Frequency output:
0356
8
1357
2358
Flow is out of range.
68 Endress+Hauser
Page 69
Promag 50 Operation
Byte Bit Error No. Short error description
3 359 Pulse output:
4360
8
5361
6362
10 7 401 Measuring tube partially filled or empty
Flow is out of range.
2461
11
4463
12
13 0 502 Upload/download of device files. Currently no other commands are possible.
14
15
1 474 Maximum flow value entered is overshot
7 501 Amplifier software version is loaded. Currently no other commands are possible.
3 601 Positive zero return active
7 611 Simulation current output active
0612
1613
2614
3 621 Simulation frequency output active
4622
5623
6624
7 631 Simulation pulse output active
EPD calibration not possible because the fluid's conductivity is either too low or too high.
The EPD calibration values for empty pipe and full pipe are identical, and therefore incorrect.
0632
1633
2634
16
17 7 671 Simulation of the status input active
18
3 641 Simulation status output active
4642
5643
6644
0672
1673
2674
3 691 Simulation of response to error (outputs) active
4 692 Simulation of volume flow active
Endress+Hauser 69
Page 70
Commissioning Promag 50

6 Commissioning

6.1 Function check

Make sure that all final checks have been completed before you start up your measuring point:
• Checklist for "Post-installation check" ä 43
• Checklist for "Post-connection check" ä 57

6.2 Switching on the measuring device

Once the connection checks have been successfully completed, it is time to switch on the power supply. The device is now operational. The measuring device performs a number of post switch-on self-tests. As this procedure progresses the following sequence of messages appears on the local display:
!
PROMAG 50 STARTUP. . .
Æ
DEVICE SOFTWARE V XX.XX.XX
Æ
SYSTEM OK OPERATION
Æ
Normal measuring mode commences as soon as start-up completes. Various measured-value and/or status variables (HOME position) appear on the display.
Note! If start-up fails, an error message indicating the cause is displayed.
Start-up message
Current software version
Beginning of normal measuring mode
70 Endress+Hauser
Page 71
Promag 50 Commissioning
+
+
+
E
E
Esc
E
+
-
XXX.XXX.XX
HOME-POSITION
QS
Commission
Language
Defaults
Quick Setup
Unit
Volume flow
Measuring
Mode
Frequency Pulse
Current Output Freq.-/ Pulse Output
Quit
Assign
Current
Assign
Frequency
Assign
Pulse
Current
Span
Value
20 mA
Time
Constant
Time
Constant
Failsafe
Mode
Failsafe
Mode
Failsafe
Mode
Operation
Mode
End Value
Freq. Value
f max
Pulse Value
Pulse
Width
Output
Signal
Output
Signal
Automatic parameterization
of the display
Quit Quick Setup

6.3 Quick Setup

In the case of measuring devices without a local display, the individual parameters and functions must be configured via the operating program, e.g. FieldCare. If the measuring device is equipped with a local display, all the important device parameters for standard operation, as well as additional functions, can be configured quickly and easily by means of the following Quick Setup menu.

6.3.1 "Commissioning" Quick Setup menu

This Quick Setup menu guides you systematically through the setup procedure for all the major device functions that have to be configured for standard measuring operation.
Fig. 50: "QUICK SETUP COMMISSIONING" menu for the rapid configuration of important device functions
A0005413-EN
Endress+Hauser 71
Page 72
Commissioning Promag 50
1
2

6.4 Configuration

6.4.1 Current output: active/passive

The current output is configured as "active" or "passive" by means of various jumpers on the I/O board.
#
Warning! Risk of electric shock! Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment.
1. Switch off power supply.
2. Remove the I/O board ä 87
3. Position the jumper å 51
Caution!
"
Risk of destroying the measuring device. Set the jumpers exactly as shown in the graphic. Pay strict attention to the position of the jumpers as indicated in the graphic.
4. Installation of the I/O board is the reverse of the removal procedure.
A0001044
Fig. 51: Configuring current outputs using jumpers (I/O board)
1 Active current output (factory setting) 2 Passive current output
72 Endress+Hauser
Page 73
Promag 50 Commissioning

6.5 Adjustment

6.5.1 Empty-pipe/full-pipe adjustment

Flow cannot be measured correctly unless the measuring tube is completely full. This status can be permanently monitored using the Empty Pipe Detection:
• EPD = Empty Pipe Detection (with the help of an EPD electrode)
• OED = Open Electrode Detection (Empty Pipe Detection with the help of the measuring electrodes, if the sensor is not equipped with an EPD electrode or the orientation is not suitable for using EPD).
Caution!
"
Detailed information on the empty-pipe/full-pipe adjustment procedure can be found in the "Description of Device Functions" manual:
• EPD/OED ADJUSTMENT (carrying out the adjustment).
• EPD (switching on and off EPD/OED).
• EPD RESPONSE TIME (input of the response time for EPD/OED).
!
Note!
• The EPD function is not available unless the sensor is fitted with an EPD electrode.
• The devices are already calibrated at the factory with water (approx. 500 μS/cm). If the fluid conductivity differs from this reference, empty-pipe/full-pipe adjustment has to be performed again on site.
• The default setting for EPD when the devices are delivered is OFF; the function has to be activated if required.
• The EPD process error can be output by means of the configurable relay output.
Performing empty-pipe and full-pipe adjustment (EPD)
1. Select the appropriate function in the function matrix:
HOME FR PROCESS PARAMETER FR EPD ADJUSTMENT
2. Empty the piping:
– The wall of the measuring tube should still be wet with fluid during EPD empty pipe
adjustment
– The wall of the measuring tube/the measuring electrodes should no longer be wet with
fluid during OED empty pipe adjustment
3. Start empty-pipe adjustment: Select "EMPTY PIPE ADJUST" or "OED EMPTY ADJUST" and
F to confirm.
press
4. After empty-pipe adjustment, fill the piping with fluid.
5. Start full-pipe adjustment: Select "FULL PIPE ADJUST" or "OED FULL ADJUST" and press F
to confirm.
6. Having completed the adjustment, select the setting "OFF" and exit the function by pressing F.
7. Switch on empty pipe detection in the EPD function:
– EPD empty pipe adjustment: Select ON STANDARD or ON SPECIAL and press F to confirm – OED empty pipe adjustment: Select OED and confirm with F.
Caution!
"
The adjustment coefficients must be valid before you can activate the EPD function. If adjustment is incorrect the following messages might appear on the display: – FULL = EMPTY
The adjustment values for empty pipe and full pipe are identical. In cases of this nature you must repeat empty-pipe or full-pipe adjustment!
– ADJUSTMENT NOT OK
Adjustment is not possible because the fluid’s conductivity is out of range.
Endress+Hauser 73
Page 74
Commissioning Promag 50

6.6 Data storage device (HistoROM)

At Endress+Hauser, the term HistoROM refers to various types of data storage modules on which process and measuring device data are stored. It is possible to plug these modules into other devices to copy device configurations from one device to another, for example.

6.6.1 HistoROM/S-DAT (sensor-DAT)

The S-DAT is an exchangeable data storage device in which all sensor relevant parameters are stored, i.e., diameter, serial number, calibration factor, zero point.
74 Endress+Hauser
Page 75
Promag 50 Maintenance

7 Maintenance

No special maintenance work is required.

7.1 Exterior cleaning

When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the surface of the housing and the seals.

7.2 Seals

The seals of the Promag H sensor must be replaced periodically, particularly in the case of gasket seals (aseptic version). The period between changes depends on the frequency of cleaning cycles, the cleaning temperature and the fluid temperature.
Replacement seals (accessories) ä 76.
Endress+Hauser 75
Page 76
Accessories Promag 50

8Accessories

Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter and the sensor. Your Endress+Hauser service organization can provide detailed information on the specific order codes on request.

8.1 Device-specific accessories

Accessory Description Order code
Proline Promag 50 transmitter
Transmitter for replacement or storage. Use the order code to define the following specifications:
• Approvals
• Degree of protection/version
• Cable for remote version
•Cable entry
• Display/power supply/operation
•Software
• Outputs/inputs
50XXX – XXXXX******

8.2 Measuring principle-specific accessories

Accessory Description Order code
Mounting set for Promag 50 transmitter
Wall-mounting kit for Promag H
Cable for remote version Coil and signal cables, various lengths. DK5CA – **
Mounting kit for Promag D, wafer version
Set of seals for Promag D Set of seals consisting of two flange seals. DK5DD – ***
Mounting kit for Promag H
Set of seals for Promag H For regular replacement of the seals of the Promag H sensor. DK5HS – ***
Welding jig for Promag H
Adapter connection for Promag A, H
Ground rings for Promag H
Ground cable for Promag L, W, P
Ground disk for Promag L, W, P
Mounting set for the transmitter (remote version). Suitable for:
• Wall mounting
• Pipe mounting
• Panel-mounted installation Mounting set for aluminum field housing. Suitable for:
• Pipe mounting
Wall-mounting kit for the Promag H sensor. DK5HM – **
Mounting kit consisting of:
• Mounting bolts
• Nuts incl. washers
•Flange seals
• Centering sleeves (if required for the flange)
Mounting kit consisting of:
• 2 process connections
• Threaded fasteners
•Seals
Weld nipple as process connection: welding jig for installation in pipe.
Adapter connections for installing a Promag 10 H instead of a Promag 30/33 A or Promag 30/33 H DN 25.
Ground rings for potential equalization. DK5HR – ***
Ground cable for potential equalization. DK5GC – ***
Ground disk for potential equalization. DK5GD – * * ***
DK5WM – *
DKD** – **
DKH** – ****
DK5HW – ***
DK5HA – *****
76 Endress+Hauser
Page 77
Promag 50 Accessories
Accessory Description Order code
Process display RIA45
Process display RIA251
Field display unit RIA16
Application Manager RMM621
Multifunctional 1-channel display unit:
•Universal input
• Transmitter power supply
• Limit relay
• Analog output
Digital display device for looping into the 4 to 20 mA current loop. RIA251 – **
Digital field display device for looping into the 4 to 20 mA current loop.
Electronic recording, display, balancing, control, saving and event and alarm monitoring of analog and digital input signals. Values and conditions determined are output by means of analog and digital output signals. Remote transmission of alarms, input values and calculated values using a PSTN or GSM modem.
RIA45 – ******
RIA16 – ***
RMM621 – **********

8.3 Communication-specific accessories

Accessory Description Order code
HART Communicator Field Xpert SFX 100
Fieldgate FXA320 Gateway for remote interrogation of HART sensors and actuators
Fieldgate FXA520 Gateway for remote interrogation of HART sensors and actuators
FXA195 The Commubox FXA195 connects intrinsically safe Smart
Handheld terminal for remote configuration and for obtaining measured values via the HART current output (4 to 20 mA) and FOUNDATION Fieldbus. Contact your Endress+Hauser representative for more information.
via Web browser:
• 2-channel analog input (4 to 20 mA)
• 4 binary inputs with event counter function and frequency measurement
• Communication via modem, Ethernet or GSM
• Visualization via Internet/Intranet in Web browser and/or WAP cellular phone
• Limit value monitoring with alarm by e-mail or SMS
• Synchronized time stamping of all measured values.
via Web browser:
• Web server for remote monitoring of up to 30 measuring points
• Intrinsically safe version [EEx ia]IIC for applications in hazardous areas
• Communication via modem, Ethernet or GSM
• Visualization via Internet/Intranet in Web browser and/or WAP cellular phone
• Limit value monitoring with alarm by e-mail or SMS
• Synchronized time stamping of all measured values
• Remote diagnosis and remote configuration of connected HART devices
transmitters with HART protocol to the USB port of a personal computer. This makes the remote operation of the transmitters possible with the aid of configuration programs (e.g. FieldCare). Power is supplied to the Commubox by means of the USB port
SFX100 – *******
FXA320 – *****
FXA520 – ****
FXA195 – *
Endress+Hauser 77
Page 78
Accessories Promag 50

8.4 Service-specific accessories

Accessory Description Order code
Applicator Software for selecting and planning flowmeters. The Applicator
software can be downloaded from the Internet or ordered on CD-ROM for installation on a local PC. Contact your Endress+Hauser representative for more information.
Fieldcheck Tester/simulator for testing flowmeters in the field. When used in
FieldCare FieldCare is Endress+Hauser's FDT-based asset management tool.
Memograph M graphic display recorder
FXA193 Service interface from the device to the PC for operation via
conjunction with the "FieldCare" software package, test results can be imported into a database, printed out and used for official certification. Contact your Endress+Hauser representative for more information.
It can configure all intelligent field units in your system and helps you manage them. By using status information, it is also a simple but effective way of checking their status and condition.
The Memograph M graphic display recorder provides information on all the relevant process variables. Measured values are recorded correctly, limit values are monitored and measuring points analyzed. The data are stored in the 256 MB internal memory and also on a DSD card or USB stick. Memograph M boasts a modular design, intuitive operation and a comprehensive security concept. The ReadWin software is part of the standard package and is used for configuring, visualizing and archiving the data captured. The mathematics channels which are optionally available enable continuous monitoring of specific power consumption, boiler efficiency and other parameters which are important for efficient energy management.
FieldCare.
®
2000 PC
DXA80 – *
50098801
See the product page on the Endress+Hauser Web site: www.endress.com
RSG40 – ************
FXA193 – *
78 Endress+Hauser
Page 79
Promag 50 Troubleshooting

9 Troubleshooting

9.1 Troubleshooting instructions

Always start troubleshooting with the checklist below if faults occur after start-up or during operation. The routine takes you directly to the cause of the problem and the appropriate remedial measures.
Check the display
No display visible and no output signals present.
No display visible, but output signals are present.
Display texts are in a foreign language.
Measured value indicated, but no signal at the current or pulse output.
Error messages on display
Errors which occur during commissioning or measuring operation are displayed immediately. Error messages consist of a variety of icons: the meanings of these icons are as follows (example):
–Error type: S = system error, P = process error – Error message type: $ = fault message, ! = notice message – EMPTY PIPE = Type of error, e.g. measuring tube is only partly filled or completely empty – 03:00:05 = duration of error occurrence (in hours, minutes and seconds) – #401 = error number
Caution!
"
• See the information on ä 61!
• The measuring system interprets simulations and positive zero return as system errors, but displays them as notice message only.
1. Check the supply voltage terminals 1, 2
2. Check the power line fuse ä 91 85 to 260 V AC: 0.8 A slow-blow / 250 V 20 to 55 V AC / 16 to 62 V DC: 2 A slow-blow / 250 V
3. Measuring electronics defective order spare parts ä 86
1. Check whether the ribbon-cable connector of the display module is correctly plugged into the amplifier board ä 87
2. Display module defective order spare parts ä 86
3. Measuring electronics defective order spare parts ä 86
Switch off power supply. Press and hold down both the OS buttons and switch on the measuring device. The display text will appear in English (default) and is displayed at maximum contrast.
Electronics board defective order spare parts ä 86
Error number: No. 001 – 399 No. 501 – 699
Error number: No. 401 - 499
Other error (without error message)
Some other error has occurred.
System error (device error) has occurred ä 80
Process error (application error) has occurred ä 82
Diagnosis and rectification ä 83
Endress+Hauser 79
Page 80
Troubleshooting Promag 50

9.2 System error messages

Serious system errors are always recognized by the device as "Fault message", and are shown as a lightning flash ( $) on the display. Fault messages immediately affect the outputs.
Caution!
"
In the event of a serious fault, a flowmeter might have to be returned to the manufacturer for repair. The necessary procedures on ä 6 must be carried out before you return a flowmeter to Endress+Hauser. Always enclose a duly completed "Declaration of Contamination" form. You will find a master copy of this form at the back of this manual.
!
No. Error message / Type Cause Remedy (spare part  ä 86)
S = System error $ = Fault message (with an effect on the outputs) ! = Notice message (without an effect on the outputs)
No. # 0xx Hardware error
001 S: CRITICAL FAILURE
$: # 001
011 S: AMP HW EEPROM
$: # 011
012 S: AMP SW EEPROM
$: # 012
031 S: SENSOR HW DAT
$: # 031
032 S: SENSOR SW DAT
$: # 032
No. # 1xx Software error
101 S: GAIN ERROR AMP
$: # 101
Note! Also observe the information on ä 61.
Serious device error Replace the amplifier board.
Amplifier: Defective EEPROM
Amplifier: Error accessing EEPROM data
1. S-DAT is not plugged into the amplifier board correctly (or is missing).
2. S-DAT is defective.
Gain deviation compared to reference gain > 25%. Replace the amplifier board.
Replace the amplifier board.
The EEPROM data blocks in which an error has occurred are displayed in the TROUBLESHOOTING function. Press Enter to acknowledge the errors in question; default values are automatically inserted instead of the errored parameter values.
Note!
!
The measuring device has to be restarted if an error has occurred in a totalizer block (see error No. 111 / CHECKSUM TOTAL).
1. Check whether the S-DAT is correctly plugged into the amplifier board.
2. Replace the S-DAT if it is defective.
Check that the new replacement DAT is compatible with the measuring electronics. Check the:
- Spare part set number
- Hardware revision code
3. Replace measuring electronics boards if necessary.
4. Plug the S-DAT into the amplifier board.
111 S: CHECKSUM TOTAL
$: # 111
121 S: A / C COMPATIB.
!: # 121
Totalizer checksum error. 1. Restart the measuring device.
2. Replace the amplifier board if necessary.
Due to different software versions, I/O board and amplifier board are only partially compatible (possibly restricted functionality).
Note!
!
– This message is only listed in the error history. – Nothing is shown on the display.
Module with lower software version has either to be updated by FieldCare with the required software version or the module has to be replaced.
80 Endress+Hauser
Page 81
Promag 50 Troubleshooting
1
2.10 Hz
=
50 ms
No. Error message / Type Cause Remedy (spare part ä 86)
No. # 2xx Error in DAT / no communication
251 S: COMMUNICATION I/O
$: # 251
261 S: COMMUNICATION I/O
$: # 261
No. # 3xx System limits exceeded
321 S: TOL. COIL CURR.
$: # 321
339
S: STACK CUR OUT n
to
!: # 339 to 342
342
343
S: STACK FREQ. OUT n
to
!: # 343 to 346
346
347
S: STACK PULSE OUT n
to
!: # 343 to 346
350
351
S: CURRENT RANGE n
to
!: # 351 to 354
354
355
S: FREQ. RANGE n
to
!: # 355 to 358
358
359
S: PULSE RANGE
to
!: # 359 to 362
362
Internal communication fault on the amplifier board. Replace the amplifier board.
No data reception between amplifier and I/O board or faulty internal data transfer.
Sensor: Coil current is out of tolerance.
The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds.
The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds.
Current output: flow is out of range.
Frequency output: flow is out of range.
Pulse output: the pulse output frequency is out of range.
Check the BUS contacts.
Warning!
#
Switch off power supply before manipulating the coil current cable, coil current cable connector or measuring electronics boards!
Remote version:
1. Check wiring of terminals 41/42 ä 44
2. Check coil current cable connector. Compact and remote version:
Replace measuring electronics boards if necessary
1. Change the upper or lower limit setting, as applicable.
2. Increase or reduce flow, as applicable. Recommendations in the event of fault category = FAULT
MESSAGE ($)
• Configure the fault response of the output to "ACTUAL VALUE" so that the temporary buffer can be cleared.
• Clear the temporary buffer by the measures described under Item 1.
1. Increase the setting for pulse weighting
2. Increase the max. pulse frequency if the totalizer can handle
a higher number of pulses.
3. Increase or reduce flow, as applicable.
Recommendations in the event of fault category = FAULT MESSAGE ($)
• Configure the fault response of the output to "ACTUAL VALUE" so that the temporary buffer can be cleared.
• Clear the temporary buffer by the measures described under Item 1.
1. Change the upper or lower limit setting, as applicable.
2. Increase or reduce flow, as applicable.
1. Change the upper or lower limit setting, as applicable.
2. Increase or reduce flow, as applicable.
1. Increase the setting for pulse weighting
2. When selecting the pulse width, choose a value that can still
be processed by a connected counter (e.g. mechanical counter, PLC etc.).
Determine the pulse width:
– Variant 1: Enter the minimum duration that a pulse must
be present at the connected counter to ensure its registration.
– Variant 2: Enter the maximum (pulse) frequency as the
half "reciprocal value" that a pulse must be present at the
connected counter to ensure its registration. Example: The maximum input frequency of the connected counter is 10 Hz. The pulse width to be entered is:
3. Reduce flow.
Endress+Hauser 81
a0004437
Page 82
Troubleshooting Promag 50
No. Error message / Type Cause Remedy (spare part ä 86)
No. # 5xx Application error
501 S: SW.-UPDATE ACT.
!: # 501
502 S: UP-/DOWNLOAD ACT
!: # 502
No. # 6xx Simulation mode active
601 S: POS. ZERO-RETURN
!: # 601
611
S: SIM. CURR. OUT. n
to
!: # 611 to 614
614
621
S: SIM. FREQ. OUT. n
to
!: # 621 to 624
624
631
S: SIM. PULSE n
to
!: # 631 to 634
634
641
S: SIM. STAT. OUT n
to
!: # 641 to 644
644
671
S: SIM. STATUS IN n
to
!: # 671 to 674
674
691 S: SIM. FAILSAFE
!: # 691
692 S: SIM. MEASURAND
!: # 692
698 S: DEV. TEST ACT.
!: # 698
New amplifier or communication (I/O module) software version is loaded. Currently no other functions are possible.
Uploading or downloading the device data via operating program. Currently no other functions are possible.
Positive zero return active
Caution!
"
This message has the highest display priority!
Simulation current output active
Simulation frequency output active Switch off simulation
Simulation pulse output active Switch off simulation
Simulation status output active Switch off simulation
Simulation status input active Switch off simulation
Simulation of response to error (outputs) active Switch off simulation
Simulation of a measured variable active (e.g. mass flow).
The measuring device is being checked on site via the test and simulation device.
Wait until the procedure is finished. The device will restart automatically.
Wait until the procedure is finished.
Switch off positive zero return
Switch off simulation
–

9.3 Process error messages

!
No. Error message / Type Cause Remedy (spare part  ä 86)
P = Process error $ = Fault message (with an effect on the outputs) ! = Notice message (without an effect on the outputs)
401 EMPTY PIPE
$: # 401
461 ADJ. NOT OK
!: # 461
463 FULL = EMPTY
$: # 463
82 Endress+Hauser
Note! Also observe the information on ä 61.
Measuring tube partially filled or empty 1. Check the process conditions of the plant
2. Fill the measuring tube
EPD calibration not possible because the fluid's conductivity is either too low or too high.
The EPD calibration values for empty pipe and full pipe are identical, therefore incorrect.
The EPD function cannot be used with fluids of this nature.
Repeat calibration, making sure procedure is correct ä 73.
Page 83
Promag 50 Troubleshooting

9.4 Process errors without messages

Symptoms Rectification
Remark: You may have to change or correct certain settings in functions in the function matrix in order to rectify the fault.
Flow values are negative, even though the fluid is flowing forwards through the pipe.
Measured-value reading fluctuates even though flow is steady.
Measured-value reading shown on display, even though the fluid is at a standstill and the measuring tube is full.
Measured-value reading on display, even though measuring tube is empty.
The current output signal is always 4 mA, irrespective of the flow signal at any given time.
The fault cannot be rectified or some other fault not described above has arisen.
In these instances, please contact your Endress+Hauser service organization.
1. Remote version: – Switch off the power supply and check the wiring ä 44 – If necessary, reverse the connections at terminals 41 and 42
2. Change the setting in the "INSTALLATION DIRECTION SENSOR" function accordingly
1. Check grounding and potential equalization ä 53
2. Check the fluid for presence of gas bubbles.
3. In the "SYSTEM DAMPING" function increase the value
1. Check grounding and potential equalization ä 53
2. Check the fluid for presence of gas bubbles.
3. Activate the "LOW FLOW CUTOFF" function, i.e. enter or increase the value for the switching point.
1. Perform empty-pipe/full-pipe adjustment and then switch on Empty Pipe detection ä 73
2. Remote version: Check the terminals of the EPD cable ä 44
3. Fill the measuring tube.
1. Select the "BUS ADDRESS" function and change the setting to "0".
2. Value for creepage too high. Reduce the value in the "LOW FLOW CUTOFF" function.
The following options are available for tackling problems of this nature:
Request the services of an Endress+Hauser service technician
If you contact our service organization to have a service technician sent out, please be ready to quote the following information: – Brief description of the fault – Nameplate specifications (ä 7): order code, serial number
Returning devices to Endress+Hauser
The necessary procedures (ä 6) must be carried out before you return a flowmeter requiring repair or calibration to Endress+Hauser. Always enclose a duly completed "Declaration of Conformity" form with the flowmeter. You will find a master copy of this form at the back of this manual.
Replace transmitter electronics
Components in the measuring electronics defective order spare parts ä 86
Endress+Hauser 83
Page 84
Troubleshooting Promag 50

9.5 Response of outputs to errors

!
Note! The failsafe mode of totalizers, current, pulse and frequency outputs can be customized by means of various functions in the function matrix. You will find detailed information on these procedures in the "Description of Device Functions" manual.
You can use positive zero return to set the signals of the current, pulse and status outputs to their fallback value, for example when measuring has to be interrupted while a pipe is being cleaned. This function takes priority over all other device functions: simulations, for example, are suppressed.
Failsafe mode of outputs and totalizers
Process/system error is current Positive zero return is activated
Caution!
"
System or process errors defined as "Notice messages" have no effect whatsoever on the inputs and outputs. See the information on ä 64
Current output MINIMUM VALUE
0–20 mA 0 mA 4–20 mA 2 mA 4–20 mA HART 2 mA 4–20 mA NAMUR 3.5 mA 4–20 mA HART NAMUR 3.5 mA 4–20 mA US 3.75 mA 4–20 mA HART US 3,75 mA 0–20 mA (25 mA) 0 mA 4–20 mA (25 mA) 2 mA 4–20 mA (25 mA) HART 2 mA
MAXIMUM VALUE 0–20 mA 22 mA 4–20 mA 22 mA 4–20 mA HART 22 mA 4–20 mA NAMUR 22.6 mA 4–20 mA HART NAMUR 22.6 mA 4–20 mA US 22.6 mA 4–20 mA HART US 22.6 mA 0–20 mA (25 mA) 25 mA 4–20 mA (25 mA) 25 mA 4–20 mA (25 mA) HART 25 mA
HOLD VALUE Last valid value (preceding occurrence of the fault) is output.
ACTUAL VALUE Measured value display on the basis of the current flow measurement. The fault is ignored.
Pulse output MIN/MAX VALUE FALLBACK VALUE
Signal output no pulses
HOLD VALUE Last valid value (preceding occurrence of the fault) is output.
ACTUAL VALUE Fault is ignored, i.e. normal measured-value output on the basis of ongoing flow measurement.
Output signal corresponds to "zero flow"
Output signal corresponds to "zero flow"
84 Endress+Hauser
Page 85
Promag 50 Troubleshooting
Failsafe mode of outputs and totalizers
Process/system error is current Positive zero return is activated
Frequency output
Totalizer STOP
Status output In the event of a fault or power supply failure:
FALLBACK VALUE
Signal output 0 Hz
FAILSAFE LEVEL
Output of the frequency specified in the FALÌLSAFE VALUE function.
HOLD VALUE
Measured value display on the basis of the last saved value preceding occurrence of the fault.
ACTUAL VALUE
Measured value display on the basis of the current flow measurement. The fault is ignored.
The totalizers are paused until the error is rectified.
ACTUAL VALUE
The fault is ignored. The totalizer continues to count in accordance with the current flow value.
HOLD VALUE
The totalizer continues to count the flow in accordance with the last valid flow value (before the error occurred).
Status output non-conductive
Output signal corresponds to "zero flow"
Totalizer stops
No effect on status output
Endress+Hauser 85
Page 86
Troubleshooting Promag 50
1
2
4
5
3

9.6 Spare parts

Detailed troubleshooting instructions are provided in the previous sections ä 79 The measuring device, moreover, provides additional support in the form of continuous self­diagnosis and error messages. Fault rectification can entail replacing defective components with tested spare parts. The illustration below shows the available scope of spare parts.
!
Note! You can order spare parts directly from your Endress+Hauser service organization by providing the serial number printed on the transmitter's nameplate ä 7
Spare parts are shipped as sets comprising the following parts:
• Spare part
• Additional parts, small items (threaded fasteners, etc.)
• Mounting instructions
• Packaging
Fig. 52: Spare parts for Promag 50 transmitter (field and wall-mounted housings)
1 Power unit board (85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC) 2 Amplifier board 3 I/O board (COM module) 4 HistoROM / S-DAT (sensor data memory) 5 Display module
A0009764
86 Endress+Hauser
Page 87
Promag 50 Troubleshooting

9.6.1 Removing and installing printed circuit boards

Field housing: removing and installing printed circuit boards å 53
#
"
Warning!
• Risk of electric shock! Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment.
• Risk of damaging electronic components (ESD protection). Static electricity can damage electronic components or impair their operability. Use a workplace with a grounded working surface purpose-built for electrostatically sensitive devices!
• If you cannot guarantee that the dielectric strength of the device is maintained in the following steps, then an appropriate inspection must be carried out in accordance with the manufacturer’s specifications.
• When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to these Operating Instructions.
Caution! Use only original Endress+Hauser parts.
1. Switch off power supply.
2. Unscrew cover of the electronics compartment from the transmitter housing.
3. Remove the local display (1) as follows:
– Press in the latches (1.1) at the side and remove the display module. – Disconnect the ribbon cable (1.2) of the display module from the amplifier board.
4. Remove the screws and remove the cover (2) from the electronics compartment.
5. Remove the boards (4, 6): Insert a suitable tool into the hole (3) provided for the purpose and
pull the board clear of its holder.
6. Remove amplifier board (5):
– Disconnect the plug of the electrode signal cable (5.1) including S-DAT (5.3) from the board. – Loosen the plug locking of the coil current cable (5.2) and gently disconnect the plug from
the board, i.e. without moving it to and fro.
– Insert a thin pin into the hole (3) provided for the purpose and pull the board clear of its
holder.
7. Installation is the reverse of the removal procedure.
Endress+Hauser 87
Page 88
Troubleshooting Promag 50
4
5
6
3
2
1
1.2
5.1
5.3
5.2
1.1
3
3
A0002657
Fig. 53: Field housing: removing and installing printed circuit boards
1 Local display
1.1 Latch
1.2 Ribbon cable (display module) 2 Screws of electronics compartment cover 3 Aperture for installing/removing boards 4 Power supply board 5 Amplifier board
5.1 Electrode signal cable (sensor)
5.2 Coil current cable (sensor)
5.3 Histo-ROM / S-DAT (sensor data memory) 6I/O board
88 Endress+Hauser
Page 89
Promag 50 Troubleshooting
Wall-mount housing: removing and installing printed circuit boards  å 54
#
"
Warning!
• Risk of electric shock! Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment.
• Risk of damaging electronic components (ESD protection). Static electricity can damage electronic components or impair their operability. Use a workplace with a grounded working surface purpose-built for electrostatically sensitive devices!
• If you cannot guarantee that the dielectric strength of the device is maintained in the following steps, then an appropriate inspection must be carried out in accordance with the manufacturer’s specifications.
• When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to these Operating Instructions.
Caution! Use only original Endress+Hauser parts.
1. Switch off power supply.
2. Remove the screws and open the hinged cover (1) of the housing. Remove screws of the
electronics module (2).
3. Then push up electronics module and pull it as far as possible out of the wall-mounted housing.
4. Disconnect the following cable plugs from amplifier board (7):
– Electrode signal cable plug (7.1) including S-DAT (7.3). – Plug of coil current cable (7.2). To do so, loosen the plug locking of the coil current cable
and gently disconnect the plug from the board, i.e. without moving it to and fro.
– Ribbon cable plug (3) of the display module.
5. Remove the screws and remove the cover (4) from the electronics compartment.
6. Remove the boards (6, 7, 8): Insert a suitable tool into the hole (5) provided for the purpose
and pull the board clear of its holder.
7. Installation is the reverse of the removal procedure.
Endress+Hauser 89
Page 90
Troubleshooting Promag 50
6
7
8
5
5
3
4
7.1
7.3
7.2
1
2
3
5
Fig. 54: Wall-mount housing: removing and installing printed circuit boards
1 Housing cover 2 Electronics module 3 Ribbon cable (display module) 4 Cover of electronics compartment (3 screws) 5 Aperture for installing/removing boards 6 Power supply board 7 Amplifier board
7.1 Electrode signal cable (sensor)
7.2 Coil current cable (sensor)
7.3 Histo-ROM / S-DAT (sensor data memory) 8I/O board
A0005409
90 Endress+Hauser
Page 91
Promag 50 Troubleshooting
1
2

9.6.2 Replacing the device fuse

#
"
Warning! Risk of electric shock! Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment.
The main fuse is on the power supply board (å 55). The procedure for replacing the fuse is as follows:
1. Switch off power supply.
2. Remove the power supply board: field housing ä 87, wall-mount housing ä 89
3. Remove cap (1) and replace the device fuse (2).
Use only fuses of the following type: – Power supply 20 to 55 V AC / 16 to 62 V DC 2.0 A slow-blow / 250 V;
5.2 × 20 mm – Power supply 85 to 260 V AC 0.8 A slow-blow / 250 V; 5.2 × 20 mm – Ex-rated devices see the Ex documentation.
4. Installation is the reverse of the removal procedure. Caution!
Use only original Endress+Hauser parts.
Fig. 55: Replacing the device fuse on the power supply board
1 Protective cap 2 Device fuse
Endress+Hauser 91
a0001148
Page 92
Troubleshooting Promag 50
A
3
2
1
4
8
7
11
1
6
10
9
5
B

9.6.3 Replacing the exchangeable electrode

The Promag W sensor (DN 350 to 2000; 14" to 78") is available with exchangeable measuring electrodes as an option. This design permits the measuring electrodes to be replaced or cleaned under process conditions.
Fig. 56: Apparatus for replacing exchangeable measuring electrodes
View A = DN 1200 to 2000 (48" to 78")
View B = DN 350 to 1050 (14" to 42")
1Allen screw 2Handle 3 Electrode cable 4 Knurled nut (locknut) 5 Measuring electrode 6 Stop cock (ball valve) 7 Retaining cylinder 8 Locking pin (for handle) 9 Ball-valve housing 10 Seal (retaining cylinder) 11 Coil spring
a0004447
92 Endress+Hauser
Page 93
Promag 50 Troubleshooting
Removing the electrode Installing the electrode
1 Loosen Allen screw (1) and remove the cover. 1 Insert new electrode (5) into retaining cylinder (7)
2 Remove electrode cable (3) secured to handle (2). 2 Mount handle (2) on the electrode and insert
3 Loosen knurled nut (4) by hand.
This knurled nut acts as a locknut.
4 Remove electrode (5) by turning handle (2). The
electrode can now be pulled out of retaining cylinder (7) as far as a defined stop.
Warning!
#
Risk of injury. Under process conditions (pressure in the piping system) the electrode can recoil suddenly against its stop. Apply counter-pressure while releasing the electrode.
5 Close stop cock (6) after pulling out the electrode as
far as it will go.
Warning!
#
Do not subsequently open the stop cock, in order to prevent fluid escaping.
from below. Make sure that the seals at the tip of the electrode are clean.
locking pin (8) to secure it in position.
Caution!
"
Make sure that coil spring (11) is inserted. This is essential to ensure correct electrical contact and correct measuring signals.
3 Pull the electrode back until the tip of the electrode
no longer protrudes from retaining cylinder (7).
4 Screw the retaining cylinder (7) onto ball-valve
housing (9) and tighten it by hand. Seal (10) on the cylinder must be correctly seated and clean.
Note!
!
Make sure that the rubber hoses on retaining cylinder (7) and stop cock (6) are of the same color (red or blue).
5 Open stop cock (6) and turn handle (2) to screw the
electrode all the way into the retaining cylinder.
6 Remove the electrode complete with retaining
cylinder (7).
7 Remove handle (2) from electrode (5) by pressing
out locking pin (8). Take care not to lose coil spring (11).
8 Remove the old electrode and insert the new
electrode. Replacement electrodes can be ordered separately from Endress+Hauser.
6 Screw knurled nut (4) onto the retaining cylinder.
This firmly locates the electrode in position.
7 Use the Allen screw to secure electrode cable (3) to
handle (2).
Caution!
"
Make sure that the machine screw securing the electrode cable is firmly tightened. This is essential to ensure correct electrical contact and correct measuring signals.
8 Reinstall the cover and tighten Allen screw (a).
Endress+Hauser 93
Page 94
Troubleshooting Promag 50

9.7 Return

Caution!
"
Do not return a measuring device if you are not absolutely certain that all traces of hazardous substances have been removed, e.g. substances which have penetrated crevices or diffused through plastic. Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be charged to the owner-operator.
The following steps must be taken before returning a flow measuring device to Endress+Hauser, e.g. for repair or calibration:
• Always enclose a duly completed "Declaration of contamination" form. Only then can Endress+Hauser transport, examine and repair a returned device.
• Enclose special handling instructions if necessary, for example a safety data sheet as per EC REACH Regulation No. 1907/2006.
• Remove all residues. Pay special attention to the grooves for seals and crevices which could contain residues. This is particularly important if the substance is hazardous to health, e.g. flammable, toxic, caustic, carcinogenic, etc.
!
Note! You will find a preprinted "Declaration of contamination" form at the back of these Operating Instructions.

9.8 Disposal

Observe the regulations applicable in your country!

9.9 Software history

Date Software version Changes to software Operating
Instructions
11.2009 Amplifier:
V 2.03.XX
06.2009 Amplifier:
V 2.02.XX
03.2009 Amplifier:
V 2.02.XX
11.2004 Amplifier:
1.06.01 Communication module:
1.04.00
Introduction of Calf history 71106181 / 12.09
71105332 / 11.09
Introduction of Promag L 71095684 / 06.09
Introduction of Promag D Introduction of new nominal diameter
Software update relevant only for production 50097089 / 10.03
71088677 / 03.09
10.2003 Amplifier:
1.06.00 Communication module:
1.03.00
Software expansion:
• Language groups
• Flow direction pulse output selectable New functionalities:
• Second Totalizer
• Adjustable backlight (display)
• Operation hours counter
• Simulation function for pulse output
• Counter for access code
• Reset function (fault history)
• Up-/download with FieldTool
50097089 / 10.03
94 Endress+Hauser
Page 95
Promag 50 Troubleshooting
Date Software version Changes to software Operating
Instructions
08.2003 Communication module:
1.02.01
08.2002 Amplifier:
1.04.00
03.2002 Amplifier:
1.03.00
06.2001 Amplifier:
1.02.00 Communication module:
1.02.00
Software expansion:
• New / revised functionalities New functionalities:
• Current span NAMUR NE 43
• Failsafe mode function
• Troubleshooting function
• System and process error messages
• Response of status output
Software expansion:
• New / revised functionalities New functionalities:
• Current span NAMUR NE 43
•EPD (new mode)
• Failsafe mode function
• Acknowledge fault function
• Troubleshooting function
• System and process error messages
• Response of status output
Software expansion:
• Suitability for custody transfer measurement Promag 50/51
Software expansion:
• New functionalities:
New functionalities:
• General device functions
• "OED" software function
• "Pulse width" software function
50097089 / 08.03
50097089 / 08.02
none
50097089 / 06.01
!
09.2000 Amplifier:
1.01.01 Communication module:
1.01.00
08.2000 Amplifier:
1.01.00
04.2000 Amplifier:
1.00.00 Communication module:
1.00.00
Software expansion:
• Functional adaptations
Software expansion:
• Functional adaptations
Original software
Compatible with:
• FieldTool
• Commuwin II (version 2.05.03 and higher)
• HART Communicator DXR 275 (from OS 4.6) with Rev. 1, DD1
none
none
50097089 / 04.00
Note! Uploads or downloads between the individual software versions are only possible with a special service software.
Endress+Hauser 95
Page 96
Technical data Promag 50

10 Technical data

10.1 Technical data at a glance

10.1.1 Application

ä 5

10.1.2 Function and system design

Measuring principle Electromagnetic flow measurement on the basis of Faraday’s Law.
Measuring system ä 7

10.1.3 Input

Measured variable Flow velocity (proportional to induced voltage)
Measuring range Typically v = 0.01 to 10 m/s (0.033 to 33 ft/s) with the specified accuracy
Operable flow range Over 1000 : 1
Input signal Status input (auxiliary input)
• Galvanically isolated
• U = 3 to 30 V DC
•Ri = 5 k
• Can be configured for: totalizer reset, positive zero return, error message reset.

10.1.4 Output

Output signal Current output
• Galvanically isolated
• Active/passive can be selected: – Active: 0/4 to 20 mA, R – Passive: 4 to 20 mA, supply voltage V
• Time constant can be selected (0.01 to 100s)
• Full scale value adjustable
• Temperature coefficient: typ. 0.005% o.f.s./°C, resolution: 0.5 μA
o.f.s. = of full scale value
< 700 (HART: RL 250 )
L
18 to 30 V DC, Ri 150 )
S
Pulse/frequency output
• Galvanically isolated
• Passive: 30 V DC / 250 mA
• Open collector
• Can be configured as: –Pulse output
Pulse value and pulse polarity can be selected, max. pulse width adjustable (0.5 to 2000 ms)
– Frequency output
Full scale frequency 2 to 1000 Hz (f
96 Endress+Hauser
= 1.25 Hz), on/off ratio 1:1, pulse width max. 10 s
max
Page 97
Promag 50 Technical data
Signal on alarm Current output
Failsafe mode can be selected (e.g. in accordance with NAMUR Recommendation NE 43)
Pulse/frequency output
Failsafe mode can be selected
Status output
"Not conductive" in the event of fault or power supply failure
Load See "Output signal"
Switching output Status output
• Galvanically isolated
• Max. 30 V DC/250 mA
• Open collector
• Can be configured for: error messages, empty pipe detection (EPD), flow direction, limit values
Low flow cut off Low flow cut off, switch-on point can be selected as required
Galvanic isolation All circuits for inputs, outputs, and power supply are galvanically isolated from each other.

10.1.5 Power supply

Electrical connections ä 44
Supply voltage (power supply)
Cable entry Power supply and signal cables (inputs/outputs):
• 85 to 260 V AC, 45 to 65 Hz
• 20 to 55 V AC, 45 to 65 Hz
• 16 to 62 V DC
• Cable entry M20 × 1.5 (8 to 12 mm/0.31 to 0.47 inch)
• Sensor cable entry for armored cables M20 × 1.5 (9.5 to 16 mm / 0.37 to 0.63 inch)
• Threads for cable entries ½" NPT, G ½"
Connecting cable for remote version:
• Cable entry M20 × 1.5 (8 to 12 mm/0.31 to 0.47 inch)
• Sensor cable entry for armored cables M20 × 1.5 (9.5 to 16 mm / 0.37 to 0.63 inch)
• Threads for cable entries ½" NPT, G ½"
Cable specifications ä 49
Power consumption Power consumption
• AC: <15 VA (incl. sensor)
• DC: <15 W (incl. sensor)
Switch-on current
• max. 3 A (<5 ms) for 24 V DC
• max. 8.5 A (<5 ms) for 260 V AC
Endress+Hauser 97
Page 98
Technical data Promag 50
2.5
[%]
2.0
1.5
1.0
0.5 0
0.2%
0.5%
0
1
2 4 6810[m/s]
v
5101520253032[ft]0
Power supply failure • Lasting min. 1 cycle frequency:
• EEPROM saves measuring system data
• S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal diameter, serial number, calibration factor, zero point etc.)
Potential equalization ä 53

10.1.6 Performance characteristics

Reference operating conditions
To DIN EN 29104 and VDI/VDE 2641:
• Fluid temperature: +28 °C ± 2 K
• Ambient temperature: +22 °C ± 2 K
• Warm-up period: 30 minutes
Installation:
• Inlet run >10 × DN
• Outlet run > 5 × DN
• Sensor and transmitter grounded.
• The sensor is centered in the pipe.
Maximum measured error • Current output: plus typically ± 5 μA
• Pulse output: ± 0.5% o.r. ± 1 mm/s Option: ± 0.2% o.r. ± 2 mm/s (o.r. = of reading)
Fluctuations in the supply voltage do not have any effect within the specified range.
Fig. 57: Max. measured error in % of reading
Repeatability Max. ± 0.1% o.r. ± 0.5 mm/s (o.r. = of reading)

10.1.7 Operating conditions: Installation

Installation instructions Any orientation (vertical, horizontal), restrictions and installation instructions ä 13
Inlet and outlet run If possible, install the sensor upstream from fittings such as valves, T-pieces, elbows, etc. The
98 Endress+Hauser
following inlet and outlet runs must be observed in order to meet accuracy specifications (ä 16, å 12):
• Inlet run: 5 × DN
•Outlet run: 2 × DN
A0005531
Page 99
Promag 50 Technical data
Adapters ä 17
Length of connecting cable ä 20

10.1.8 Operating conditions: Environment

Ambient temperature range • Transmitter:
– Standard: –20 to +60 °C (–4 to +140 °F) – Optional: –40 to +60 °C (–40 to +140 °F)
Note!
!
At ambient temperatures below –20 (–4 °F) the readability of the display may be impaired.
• Sensor (the ambient temperatur range is dependent on the sensor type): – Flange material carbon steel: –10 to +60 °C (+14 to +140 °F) – Flange material stainless steel: –40 to +60 °C (–40 to +140 °F)
Caution!
"
• The permitted temperature range of the measuring tube lining may not be undershot or overshot ("Operating conditions: Process" "Medium temperature range").
• Install the device in a shady location. Avoid direct sunlight, particularly in warm climatic regions.
• The transmitter must be mounted separate from the sensor if both the ambient and fluid temperatures are high.
Storage temperature The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors. Caution!
"
• The measuring device must be protected against direct sunlight during storage in order to avoid unacceptably high surface temperatures.
• A storage location must be selected where moisture does not collect in the measuring device. This will help prevent fungus and bacteria infestation which can damage the liner.
Degree of protection • Standard: IP 67 (NEMA 4X) for transmitter and sensor
• Optional: IP 68 (NEMA 6P) for remote version of Promag L, W and P sensor. Promag L only with stainless steel flanges.
Shock and vibration resistance Acceleration up to 2 g following IEC 60068-2-6
(high-temperature version: no data available)
CIP cleaning
Caution!
"
The maximum fluid temperature permitted for the device may not be exceeded.
CIP cleaning is possible:
Promag P, Promag H
CIP cleaning is not possible:
Promag D, Promag L, Promag W
SIP cleaning
Caution!
"
The maximum fluid temperature permitted for the device may not be exceeded.
SIP cleaning is possible:
Promag H
SIP cleaning is not possible:
Promag D, Promag L, Promag W, Promag P
Endress+Hauser 99
Page 100
Technical data Promag 50
PTFE
HT
m
PFA
n
0
0
0
0
-20-40
-40
20
20
40
100
60
140
[°F] [°C]
T
A
406080
T
F
100
100
120 140 160
200 300
180 [°C]
360 [°F]
-20
-40
-40
Electromagnetic compatibility (EMC)
• As per IEC/EN 61326 and NAMUR Recommendation NE 21
• Emission: to limit value for industry EN 55011

10.1.9 Operating conditions: Process

Medium temperature range The permissible temperature depends on the lining of the measuring tube
Promag D
0 to +60 °C (+32 to +140 °F) for polyamide
Promag L
• 0 to +80 °C (+32 to +176 °F) for hard rubber (DN 350 to 1200)
• –20 to +50 °C (–4 to +122 °F) for polyurethane (DN 50 to 1200)
• –20 to +90 °C (–4 to +194 °F) for PTFE (DN 50 to 300)
Promag W
• 0 to +80 °C (+32 to +176 °F) for hard rubber (DN 50 to 2000)
• –20 to +50 °C (–4 to +122 °F) for polyurethane (DN 25 to 1200)
Promag P
Standard
• –40 to +130 °C (–40 to +266 °F) for PTFE (DN 15 to 600 / 1/2" to 24"), Restrictions see the following diagrams
• –20 to +130 °C (–4 to +266 °F) for PFA/HE (DN 25 to 200 / 1" to 8"), Restrictions see the following diagrams
• –20 to +150 °C (–4 to +302 °F) for PFA (DN 25 to 200 / 1" to 8"), Restrictions see the following diagrams
Optional High-temperature version (HT): –20 to +180 °C (–4 to +356 °F) for PFA (DN 25 to 200 / 1" to 8")
100 Endress+Hauser
Abb. 58: Compact version Promag P (with PFA- or PTFE-lining)
= ambient temperature; TF = fluid temperature; HT = high-temperature version with insulation
T
A
m = light gray area temperature range from –10 to –40 °C (–14 to –40 °F) is valid for stainless steel version only n = diagonal hatched area foam lining (HE) and degree of protection IP 68 = fluid temperature
max. 130°C / 266 °F
A0002660
Loading...