Measuring principleFollowing Faraday's law of magnetic induction, a voltage is induced in a conductor moving through a
magnetic field.
In the electromagnetic measuring principle, the flowing medium is the moving conductor.
The voltage induced is proportional to the flow velocity and is supplied to the amplifier by means of
two measuring electrodes. The flow volume is calculated by means of the pipe cross-sectional area.
The DC magnetic field is created through a switched direct current of alternating polarity.
Ue = B · L · v
Q = A · v
UeInduced voltage
B Magnetic induction (magnetic field)
LElectrode spacing
vFlow velocity
QVolume flow
APipe cross-section
ICurrent strength
Measuring systemThe measuring system consists of a transmitter and a sensor.
Two versions are available:
• Compact version: Transmitter and sensor form a mechanical unit.
• Remote version: Sensor is mounted separate from the transmitter.
Power supply failureLasting min. ½ cycle frequency: EEPROM saves measuring system data
Electrical connection
Connecting the transmitter (aluminum field housing), cable cross-section max. 2.5 mm2 (14 AWG)
aElectronics compartment cover
bPower supply cable
cGround terminal for power supply cable
dTerminal connector for power supply cable
eElectrode cable
fGround terminal for electrode cable
gTerminal connector for electrode cable
hService connector for connecting service interface FXA 193 (Fieldcheck, FieldCare)
iGround terminal for potential equalization
Note!
The measuring system must be included in the potential equalization.
Perfect measurement is only ensured when the fluid and the sensor have the same electrical potential.
This is ensured by the reference electrode integrated in the sensor as standard.
The following should also be taken into consideration for potential equalization:
• Internal grounding concepts in the company
• Operating conditions, such as the material/grounding of the pipes (see table)
Standard situation
Operating conditionsPotential equalization
When using the measuring device in a:
• Metal, grounded pipe
Potential equalization takes place via the ground terminal
of the transmitter.
Note!
!
When installing in metal pipes, we recommend you connect
the ground terminal of the transmitter housing with the
piping.
Via the ground terminal of the transmitter
A0010831
Endress+Hauser9
Page 10
Special situations
DN 300£
DN 350
³
1
22
Operating conditionsPotential equalization
When using the measuring device in a:
• Metal pipe that is not grounded
This connection method also applies in situations where:
• Customary potential equalization cannot be ensured.
• Excessively high equalizing currents can be expected.
Both sensor flanges are connected to the pipe flange by
means of a ground cable (copper wire, at least 6 mm² /
0.0093 in²) and grounded. Connect the transmitter or
sensor connection housing, as applicable, to ground
potential by means of the ground terminal provided for the
purpose.
Ground cable installation depends on the nominal
diameter:
•DN 300 (12"): The ground cable is mounted directly on
the conductive flange coating with the flange screws.
•DN 350 (14"): The ground cable is mounted directly on
the metal transport bracket.
Note!
!
The ground cable for flange-to-flange connections can be
ordered separately as an accessory from Endress+Hauser.
Via the ground terminal of the transmitter and the
flanges of the pipe
Proline Promag 10W
A0010832
When using the measuring device in a:
• Plastic pipe
• Pipe with insulating lining
This connection method also applies in situations where:
• Customary potential equalization cannot be ensured.
• Excessively high equalizing currents can be expected.
Potential equalization takes place using additional ground
disks, which are connected to the ground terminal via a
ground cable (copper wire, at least 6 mm² / 0.0093 in²).
When installing the ground disks, please comply with the
enclosed Installation Instructions.
When using the measuring device in a:
• Pipe with a cathodic protection unit
The device is installed potential-free in the pipe.
Only the two flanges of the pipe are connected with a
ground cable (copper wire, at least 6 mm² / 0.0093 in²).
Here, the ground cable is mounted directly on the
conductive flange coating with flange screws.
Note the following when installing:
• The applicable regulations regarding potential-free
installation must be observed.
•There should be no electrically conductive connection
between the pipe and the device.
• The mounting material must withstand the applicable
torques.
A0010833
Via the ground terminal of the transmitter and the
optionally available ground disks
Operation in zones of severe electrical interference
The measuring device complies with the general safety requirements in accordance with EN 61010-1,
the EMC requirements of IEC/EN 61326 and NAMUR Recommendation NE 21.
Note!
Grounding is by means of the ground terminals provided for the purpose inside the connection
housing.
Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as short as
possible.
Endress+Hauser11
Page 12
Performance characteristics
2.5
[%]
2.0
1.5
1.0
0.5
0
0.5 %
0
1
246810 [m/s]
v
5101520253032 [ft/s]0
Proline Promag 10W
Reference operating
conditions
As per DIN EN 29104 and VDI/VDE 2641:
• Fluid temperature: +28 °C ± 2 K (+82 °F ± 2 K)
• Ambient temperature: +22 °C ±2 K (+72 °F ± 2 K)
• Warm-up period: 30 minutes
Installation conditions:
• Inlet run > 10 × DN
• Outlet run > 5 × DN
• Sensor and transmitter grounded.
• The sensor is centered in the pipe.
Maximum measured error• Current output: also typically ±5 μA
Mounting locationEntrained air or gas bubble formation in the measuring tube can result in an increase in measuring
errors.
Avoid the following installation locations in the pipe:
• Highest point of a pipeline. Risk of air accumulating!
• Directly upstream from a free pipe outlet in a vertical pipeline.
A0003202
Mounting location
A0033017
Installation of the sensor after a control valve is not recommended
1Control valve
Installation of pumps
Sensors may not be installed on the pump suction side. This precaution is to avoid low pressure and the
consequent risk of damage to the lining of the measuring tube. Information on the pressure tightness
of the measuring tube lining → 21, Section "Pressure tightness".
Pulsation dampers may be needed when using piston pumps, piston diaphragm pumps or hose pumps.
Information on the shock and vibration resistance of the measuring system → 17, Section "Shock and
vibration resistance".
A0003203
Installation of pumps
Endress+Hauser13
Page 14
!
³´5DN
³ 2
´ DN
h
2
1
Proline Promag 10W
Partially filled pipes
Partially filled pipes with gradients necessitate a drain-type configuration.
The empty pipe detection function (EPD) provides additional security in detecting empty or partially
filled pipes.
Note!
Risk of solids accumulating. Do not install the sensor at the lowest point in the drain. It is advisable to
install a cleaning valve.
A0003204
Installation with partially filled pipes
Down pipes
Install a siphon or a vent valve downstream of the sensor in down pipes h 5 m (16.4 ft). This
precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring
tube. This measure also prevents the liquid current stopping in the pipe which could cause air locks.
Information on the pressure tightness of the measuring tube lining → 21, Section "Pressure
tightness".
A0008157
Installation measures for vertical pipes
1Vent valve
2Pipe siphon
hLength of the down pipe
OrientationAn optimum orientation helps avoid gas and air accumulations and deposits in the measuring tube.
However, the measuring device also offers the additional function of empty pipe detection (EPD) for
detecting partially filled measuring tubes or if outgassing fluids or fluctuating operating pressures are
present.
Vertical orientation
This is the ideal orientation for self-emptying piping systems and for use in conjunction with empty
pipe detection.
Vertical orientation
A0008158
14Endress+Hauser
Page 15
Proline Promag 10W
A
1
22
A
3
³ 5DNx
³ 2DNx
≥ 0 × DN
!
Horizontal orientation
The measuring electrode axis should be horizontal. This prevents brief insulation of the two measuring
electrodes by entrained air bubbles.
Note!
Empty pipe detection only works correctly with horizontal orientation if the transmitter housing is
facing upwards. Otherwise there is no guarantee that empty pipe detection will respond if the
measuring tube is only partially filled or empty.
A0003207
Horizontal orientation
1EPD electrode for empty pipe detection
2Measuring electrodes for signal detection
3Reference electrode for potential equalization
Inlet and outlet runIf possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows etc.
Note the following inlet and outlet runs to comply with measuring accuracy specifications:
• Inlet run: 5 × DN
•Outlet run: 2 × DN
Inlet and outlet run standard version
A0003210
Endress+Hauser15
A0032859
Optional version: w/o inlet and outlet run
Page 16
Proline Promag 10W
100
10
0.5
d / D
[mbar]
0.60.70.80.9
1 m/s
2 m/s
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
1
D
d
max. 8°
L
max
[]ft
2006000
400
200
100
50100200
[m]
[ S/cm]μ
L
max
50
AdaptersSuitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-
diameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very slowmoving fluids. The nomogram shown here can be used to calculate the pressure loss caused by reducers
and expanders.
!
Note!
The nomogram only applies to liquids of viscosity similar to water.
1.Calculate the ratio of the diameters d/D.
2.From the nomogram read off the pressure loss as a function of flow velocity (downstream from
the reduction) and the d/D ratio.
Pressure loss due to adapters
Length of connecting cableWhen mounting the remote version, please note the following to achieve correct measuring results:
• Fix cable run or lay in armored conduit. Cable movements can falsify the measuring signal especially
in the case of low fluid conductivities.
• Route the cable well clear of electrical machines and switching elements.
• If necessary, ensure potential equalization between sensor and transmitter.
• The permitted cable length L
is determined by the fluid conductivity. A minimum conductivity of
max
50 μS/cm is needed for all fluids.
• When the empty pipe detection function is switched on (EPD), the maximum connecting cable
length is 10 m (33 ft).
Permitted length of connecting cable for remote version
Area marked in gray = permitted range; L
= length of connecting cable in [m] ([ft]); fluid conductivity in [μS/cm]
max
A0003213
A0003214
16Endress+Hauser
Page 17
Proline Promag 10W
Environment
Ambient temperature rangeTransmitter
• –20 to +60 °C (–4 to +140 °F)
Sensor
• Flange material carbon steel: –10 to +60 °C (+14 to +140 °F)
• Flange material stainless steel: –40 to +60 °C (–40 to +140 °F)
!
Storage temperatureThe storage temperature corresponds to the operating temperature range of the measuring
!
Note!
The permitted temperature range of the measuring tube lining may not be undershot or overshot (→ 18, Section "Medium temperature range").
Please note the following points:
• Install the device in a shady location. Avoid direct sunlight, particularly in warm climatic regions.
• The transmitter must be mounted separate from the sensor if both the ambient and fluid
temperatures are high.
transmitter and the appropriate measuring sensors.
Note!
• The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
• A storage location must be selected where moisture does not collect in the measuring device. This
will help prevent fungus and bacteria infestation which can damage the liner.
Degree of protection• Standard: IP 67 (NEMA 4X) for transmitter and sensor.
• Optional: IP 68 (NEMA 6P) for sensor for remote version.
• For information regarding applications where the device is buried directly in the soil or is installed
in a flooded wastewater basin please contact your local Endress+Hauser Sales Center.
Shock and vibration
resistance
Electromagnetic
compatibility (EMC)
Acceleration up to 2 g following IEC 600 68-2-6
• As per IEC/EN 61326 as well as NAMUR Recommendation NE 21
• Emission: to limit value for industry EN 55011
Endress+Hauser17
Page 18
Process
0
5
10
15
20
25
35
30
40
[bar][psi]
-40
-20
020
40 60 80 100120140160180 [°C]
360 [°F]
0-40100200300
200
100
400
300
500
600
0
PN25
PN16
PN10
PN6
PN40
PN16
PN10
PN40
PN6
0
5
10
15
20
25
35
30
40
[bar][psi]
-60
-40
-20
020
40 60 80 100120140 160180 [°C]
360 [°F]
0-40100200300
200
100
400
300
500
600
0
PN25
Medium temperature rangeThe permitted temperature depends on the measuring tube lining:
• Polyurethane: –20 to +50 °C (-4 to +122 °F) (DN 25 to 1200 / 1 to 48")
• Hard rubber: 0 to +80 °C (+32 to +176 °F) (DN 50 to 2000 / 2 to 78")
ConductivityThe minimum conductivity is: 50 μS/cm
!
Note!
In the remote version, the necessary minimum conductivity also depends on the cable length
(→ 16, Section "Length of connecting cable").
Proline Promag 10W
Pressure-temperature
ratings
Caution!
The following diagrams contain material load diagrams (reference curves) for flange materials with
regard to the medium temperature. However, the maximum medium temperatures permitted always
depend on the lining material of the sensor and/or the sealing material.
• EN 1092-1 (DIN 2501)
– PN 6 (DN 350 to 2000 / 14 to 78")
– PN 10 (DN 200 to 2000 / 8 to 78")
– PN 16 (DN 65 to 2000 / 3 to 78")
– PN 25 (DN 200 to 1000 / 8 to 40")
– PN 40 (DN 25 to 150 / 1 to 6")
•ASME B 16.5
– Class 150 (DN 25 to 600 / 1 to 24")
– Class 300 (DN 25 to 150 / 1 to 6")
• AWWA C2072
– Class D (DN 700 to 2000 / 28 to 78")
• JIS B2220
– 10 K (DN 50 to 750 / 2 to 30")
– 20 K (DN 25 to 600 / 1 to 24")
• AS 2129
– Table E (DN 80, 100, 150 to 1200 / 3", 4", 6 to 48")
• AS 4087
– PN 16 (DN 80, 100, 150 to 1200 / 3", 4", 6 to 48")
Nominal diameterLimit values for abs. pressure [mbar] ([psi]) at fluid temperatures:
25 °C (77 °F)50 °C (122 °F)
[mm][inch][mbar][psi][mbar][psi]
25 to 12001 to 48"0000
Measuring tube lining: Hard rubber
Nominal diameterLimit values for abs. pressure [mbar] ([psi]) at fluid temperatures:
25 °C (77 °F)70 °C (158 °F)80 °C (176 °F)
[mm][inch][mbar][psi][mbar][psi][mbar][psi]
50 to 20002 to 78"000000
Limiting flowThe diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The
optimum flow velocity is between 2 to 3 m/s (6.5 to 9.8 ft/s).
The velocity of flow (v), moreover, has to be matched to the physical properties of the fluid:
• v < 2 m/s (6.5 ft/s): for abrasive fluids such as potter's clay, lime milk, ore slurry etc.
• v > 2 m/s (6.5 ft/s): for fluids causing build-up such as wastewater sludges etc.
!
Pressure loss• No pressure loss if the sensor is installed in a pipe with the same nominal diameter.
Note!
• A necessary increase in the flow velocity can be achieved by reducing the sensor nominal diameter
(→ 16, Section "Adapters").
•For fluids with high levels of solids, the selection of a pipe with nominal diameter > DN 8 (³⁄₈") may
be considered, to improve the stability of the signal and cleanability due to larger electrodes.
• Pressure losses for configurations incorporating adapters according to DIN EN 545
(→ 16, Section "Adapters").
Endress+Hauser21
Page 22
Pressure loss DN 50 to 80 (2 to 3") for optional version w/o inlet and outlet runs
DN80
(3")
DN65
(2½")
DN50
(2")
500
450
400
350
300
250
200
150
100
50
0
010 20 30 40 50 60 70 80 90 100 110 120
[mbar]
[m /h]³
010020030040050050150250350450
[gal/min]
7
[psi]
0
1
2
3
4
5
6
DN300
(12")
DN100
(4")
DN250
(10")
DN200
(8")
DN150
(6")
DN125
(5")
[mbar]
900
800
700
600
500
400
300
200
100
0
0200 400 600800 1000 1200 1400 1600 1800
[m /h]³
0
13
12
11
10
9
8
7
6
5
4
3
2
1
01000 2000 3000 4000 5000 6000 7000 8000
[gal/min]
L
Proline Promag 10W
A0032667-DE
Pressure loss DN 100 to 300 (4 to 12") for optional version w/o inlet and outlet runs
VibrationsSecure the piping and the sensor if vibration is severe.
!
Note!
If vibrations are too severe, we recommend the sensor and transmitter be mounted separately.
Information on the permitted shock and vibration resistance → 17, Section "Shock and vibration
22Endress+Hauser
resistance".
Measures to prevent vibration of the measuring device
L > 10 m (33 ft)
A0032668-DE
A0003208
Page 23
Proline Promag 10W
K
F
E
D
A
H
L
N
O
P
J
G
B
C
M
248 ±2
(9.76 ±0.08)
238 (9.37)
AB
ANSCHLUSSKLEMMEN - FIELD TERMINALS
Mechanical construction
Design, dimensionsTransmitter, remote version
Transmitter dimensions, remote version
Dimensions in SI units
ABCDEFGØ H
17811313520 to 27.5153 to 1681131008.6 (M8)
JKLMNOP
12315010025133177.5327.5
All dimensions in [mm]
Dimensions in US units
ABCDEFGØ H
7.004.455.310.79 to 1.08 6.02 to 6.614.453.940.34 (M8)
JKLMNOP
4.845.903.940.985.246.9912.89
All dimensions in [inch]
A0010718
Transmitter mounting, remote version. Engineering unit mm (in)
(DN ≤ 300 (12") with Al/Zn protective coating; DN ≥ 350 (14") with protective lacquering)
– AS 2129: Carbon steel, A105, P235GH, P265GH, S235JRG2
– AS 4087: Carbon steel, A105, P265GH, S275JR
• Seals: to DIN EN 1514-1 IBC form
• Ground disks: 1.4435 (316L) or Alloy C22
1Order code "Design", option A "insertion length short""
Proline Promag 10W
Fitted electrodesMeasuring electrodes, reference electrodes and empty pipe detection electrodes available as standard
with:
• 1.4435 (316L)
• Alloy C22
Process connectionsFlange connection:
• EN 1092-1 (DIN 2501), DN 300 (12") form A, DN 350 (14") form B
(Dimensions to DIN 2501, DN 65 PN 16 and DN 600 (24") PN 16 exclusively to EN 10921)
•ASME B16.5
• AWWA C 207, Class D
• JIS B2220
• AS 2129 Table E
• AS 4087 PN 16
Surface roughnessElectrodes with 1.4435 (316L), Alloy C22: 0.3 to 0.5 μm (12 to 20 μin)
(All data refer to parts in contact with medium)
Operability
Local operationDisplay elements
• Liquid crystal display: unilluminated, two-line, 16 characters per line
38Endress+Hauser
Page 39
Proline Promag 10W
• Display (operating mode) preconfigured: volume flow and totalizer status
• 1 totalizer
Operating elements
Local operation via three keys (S, O, F)
Remote operationOperation via HART protocol and FieldCare
Certificates and approvals
CE mark The measuring system is in conformity with the statutory requirements of the EC Directives.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
C-tick mark The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
Ex approvalInformation about currently available Ex versions (FM, CSA etc.) can be supplied by your
Endress+Hauser Sales Center on request. All explosion protection data are given in a separate
documentation which is available upon request.
Other standards and
guidelines
Pressure equipment directiveThe measuring devices can be ordered with or without PED (Pressure Equipment Directive). If a device
• EN 60529
Degrees of protection by housing (IP code).
• EN 61010
Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory
Procedures.
• IEC/EN 61326
"Emission in accordance with requirements for Class A". Electromagnetic compatibility (EMC
requirements).
• ANSI/ISA-S82.01
Safety Standard for Electrical and Electronic Test, Measuring, Controlling and related Equipment General Requirements. Pollution degree 2, Installation Category II.
• CAN/CSA-C22.2 No. 1010.1-92
Safety requirements for Electrical Equipment for Measurement and Control and Laboratory Use.
Pollution degree 2, Installation Category II.
with PED is required, this must ordered explicitly. This is not possible or required for devices with
nominal diameters of DN 25 (1") or smaller.
• With the identification PED/G1/III on the sensor nameplate, Endress+Hauser confirms conformity
with the "Basic safety requirements" of Appendix I of the Pressure Equipment Directive 2014/68/EU.
• Devices with this identification (with PED) are suitable for the following types of fluid:
– Fluids of Group 1 and 2 with a steam pressure of greater than, or smaller and equal to 0.5 bar (7.3
psi)
–Unstable gases
• Devices without this identification (without PED) are designed and manufactured according to good
engineering practice. They correspond to the requirements of Art.4, Section 3 of the Pressure
Equipment Directive 2014/68/EU. Their application is illustrated in Diagrams 6 to 9 in Appendix II
of the Pressure Equipment Directive 2014/68/EU.
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com → Select country →
Instruments → Select device → Product page function: Configure this product
• From your Endress+Hauser Sales Center: www.endress.com/worldwide
Product Configurator - the tool for individual product configuration:
• Up-to-the-minute configuration data
Endress+Hauser39
Page 40
• Depending on the device: Direct input of measuring point-specific information such as measuring
range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the
transmitter and the sensor. Your Endress+Hauser service organization can provide detailed
information on the order codes in question.
Device-specific accessoriesFor the transmitter
AccessoryDescription
Proline Promag 10
transmitter
Mounting set for Promag 10
transmitter
Cable for remote versionCoil and electrode cables, various lengths.
Process display RIA45Multifunctional 1-channel display unit:
Process display RIA251Digital display device for looping into the 4 to 20 mA current loop.
Field display unit RIA16Digital field display device for looping into the 4 to 20 mA current loop.
Application Manager
RMM621
Proline Promag 10W
Transmitter for replacement or storage. Use the order code to define the
following specifications:
• Approvals
• Degree of protection/version
• Cable for remote version
•Cable entry
• Display/power supply/operation
•Software
• Outputs/inputs
Mounting set for aluminum field housing (remote version). Suitable for Pipe
mounting
•Universal input
• Transmitter power supply
• Limit relay
•Analog output
Electronic recording, display, balancing, control, saving and event and alarm
monitoring of analog and digital input signals. Values and conditions
determined are output by means of analog and digital output signals. Remote
transmission of alarms, input values and calculated values using a PSTN or GSM
modem.
For the sensor
AccessoryDescription
Wall-mounting kit for
Promag H
Mounting kit for Promag D
as wafer version
Set of seals for Promag D as
wafer version
Mounting kit for Promag H• 2 process connections
Set of seals for Promag HFor regular replacement of the seals of the Promag H sensor.
Welding jig for Promag HWeld nipple as process connection:
Wall-mounting kit for the Promag H sensor.
•Mounting bolts
• Nuts incl. washers
• Flange seals
• Centering sleeves (if required for the flange)
Set of seals consisting of two flange seals.
• Threaded fasteners
•Seals
welding jig for installation in pipe.
40Endress+Hauser
Page 41
Proline Promag 10W
AccessoryDescription
Adapter connection for
Promag A/H
Ground cable for
Promag E/L/P/W
Ground disk for
Promag E/L/P/W
Adapter connections for installing a Promag H instead of a Promag 30/33A or
Promag 30/33H DN 25.
Ground cable for potential equalization.
Ground disk for potential equalization.
Communication-specific
accessories
AccessoryDescription
HART Communicator Field
Xpert SFX 100
Fieldgate FXA320Gateway for remote interrogation of HART sensors and actuators via Web
Fieldgate FXA520Gateway for remote interrogation of HART sensors and actuators via Web
FXA195The Commubox FXA195 connects intrinsically safe Smart transmitters with
Handheld terminal for remote configuration and for obtaining measured values
via the HART current output (4 to 20 mA).
Contact your Endress+Hauser representative for more information.
browser:
• 2-channel analog input (4 to 20 mA)
• 4 binary inputs with event counter function and frequency measurement
• Communication via modem, Ethernet or GSM
• Visualization via Internet/Intranet in Web browser and/or WAP cellular
phone
• Limit value monitoring with alarm by e-mail or SMS
• Synchronized time stamping of all measured values.
browser:
• Web server for remote monitoring of up to 30 measuring points
• Intrinsically safe version [EEx ia]IIC for applications in hazardous areas
• Communication via modem, Ethernet or GSM
• Visualization via Internet/Intranet in Web browser and/or WAP cellular
phone
• Limit value monitoring with alarm by e-mail or SMS
• Synchronized time stamping of all measured values
• Remote diagnosis and remote configuration of connected HART devices
HART protocol to the USB port of a personal computer. This makes the remote
operation of the transmitters possible with the aid of configuration programs
(e.g. FieldCare).
Power is supplied to the Commubox by means of the USB port
Service-specific accessories
AccessoryDescription
ApplicatorSoftware for selecting and planning flowmeters. The Applicator software can be
downloaded from the Internet or ordered on CD-ROM for installation on a local
PC.
Contact your Endress+Hauser representative for more information.
FieldcheckTester/simulator for testing flowmeters in the field. When used in conjunction
with the "FieldCare" software package, test results can be imported into a
database, printed out and used for official certification.
Contact your Endress+Hauser representative for more information.
FieldCareFieldCare is Endress+Hauser's FDT-based asset management tool. It can configure
all intelligent field units in your system and helps you manage them. By using
status information, it is also a simple but effective way of checking their status
and condition.
Endress+Hauser41
Page 42
Proline Promag 10W
AccessoryDescription
Memograph M graphic
display recorder
FXA193Service interface from the device to the PC for operation via FieldCare.
The Memograph M graphic display recorder provides information on all the
relevant process variables. Measured values are recorded correctly, limit values
are monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on a DSD card or USB stick.
Memograph M boasts a modular design, intuitive operation and a comprehensive
security concept. The ReadWin
and is used for configuring, visualizing and archiving the data captured.
The mathematics channels which are optionally available enable continuous
monitoring of specific power consumption, boiler efficiency and other parameters
which are important for efficient energy management.
®
2000 PC software is part of the standard package
Documentation
• System Information Promag 10 (SI042D/06)
• Operating Instructions Promag 10 (BA00082D/06)
Registered trademarks
KALREZ® and VITON
Registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA
TRI-CLAMP
®
Registered trademark of Ladish & Co., Inc., Kenosha, USA
HART®
Registered trademark of the HART Communication Foundation, Austin, USA
FieldCare®, Fieldcheck®, Field Xpert™, Applicator
Registered or registration-pending trademarks of the Endress+Hauser Group
®
®
42Endress+Hauser
Page 43
Proline Promag 10W
Endress+Hauser43
Page 44
www.addresses.endress.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.