Measuring principleFollowing Faraday's law of magnetic induction, a voltage is induced in a conductor moving through a
magnetic field.
A0017035
UeInduced voltage
B Magnetic induction (magnetic field)
LElectrode spacing
ICurrent
vFlow velocity
In the electromagnetic measuring principle, the flowing medium is the moving conductor.
The voltage induced (U
) is proportional to the flow velocity (v) and is supplied to the amplifier by
e
means of two measuring electrodes. The flow volume (Q) is calculated via the pipe cross-section (A).
The DC magnetic field is created through a switched direct current of alternating polarity.
Formulae for calculation:
• Induced voltage Ue = B · L · v
• Volume flow Q = A · v
Measuring systemThe measuring system consists of a transmitter and a sensor.
Two versions are available:
• Compact version: Transmitter and sensor form a mechanical unit.
• Remote version: Sensor is mounted separate from the transmitter.
Terminal numbers and cable colors:
5/6=brown, 7/8=white, 4=green, 37/36=yellow
Note!
The measuring system must be included in the potential equalization.
Perfect measurement is only ensured when the fluid and the sensor have the same electrical potential.
This is ensured by the reference electrode integrated in the sensor as standard.
Endress+Hauser7
Page 8
The following should also be taken into consideration for potential equalization:
• Internal grounding concepts in the company
• Operating conditions, such as the material/ grounding of the pipes (see table)
Standard situation
Operating conditionsPotential equalization
When using the measuring device in a:
• Metal, grounded pipe
Potential equalization takes place via the ground terminal
of the transmitter.
Note!
!
When installing in metal pipes, we recommend you connect
the ground terminal of the transmitter housing with the
piping.
Via the ground terminal of the transmitter
Special situations
Operating conditionsPotential equalization
Proline Promag 10L
A0010831
When using the measuring device in a:
• Metal pipe that is not grounded
This connection method also applies in situations where:
• Customary potential equalization cannot be ensured.
• Excessively high equalizing currents can be expected.
Both sensor flanges are connected to the pipe flange by
means of a ground cable (copper wire, at least 6 mm² /
0.0093 in²) and grounded. Connect the transmitter or
sensor connection housing, as applicable, to ground
potential by means of the ground terminal provided for the
purpose.
The ground cable is mounted directly on the conductive
flange coating with the flange screws.
Note!
!
The ground cable for flange-to-flange connections can be
ordered separately as an accessory from Endress+Hauser.
When using the measuring device in a:
• Plastic pipe
• Pipe with insulating lining
This connection method also applies in situations where:
• Customary potential equalization cannot be ensured.
• Excessively high equalizing currents can be expected.
Potential equalization takes place using additional ground
disks, which are connected to the ground terminal via a
ground cable (copper wire, at least 6 mm² / 0.0093 in²).
When installing the ground disks, please comply with the
enclosed Installation Instructions.
A0011567
Via the ground terminal of the transmitter and the
flanges of the pipe
A0010833
Via the ground terminal of the transmitter and the
optionally available ground disks
8Endress+Hauser
Page 9
Proline Promag 10L
1
22
1
2
3
4
5
6
7
a
b
Operating conditionsPotential equalization
When using the measuring device in a:
• Pipe with a cathodic protection unit
The device is installed potential-free in the pipe.
Only the two flanges of the pipe are connected with a
ground cable (copper wire, at least 6 mm² / 0.0093 in²).
Here, the ground cable is mounted directly on the
conductive flange coating with flange screws.
Note the following when installing:
• The applicable regulations regarding potential-free
installation must be observed.
•There should be no electrically conductive connection
between the pipe and the device.
• The mounting material must withstand the applicable
torques.
Cable entryPower supply and electrode cables (inputs/ outputs):
• Cable entry M20 × 1.5 (8 to 12 mm / 0.31 to 0.47")
• Thread for cable entries, ½" NPT, G ½"
Connecting cable for remote version:
• Cable entry M20 × 1.5 (8 to 12 mm / 0.31 to 0.47")
Operation in zones of severe electrical interference
The measuring device complies with the general safety requirements in accordance with EN 61010
and the EMC requirements of IEC/EN 61326.
Note!
Grounding is by means of the ground terminals provided for the purpose inside the connection
housing. Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as
short as possible.
Performance characteristics
Reference operating
conditions
Maximum measured error• Current output: also typically ± 5 μA
• Error limits following DIN EN 29104, future ISO 20456
• Water, typically +15 to +45°C (+59 to +113 °F); 0.5 to 7 bar (73 to 101 psi)
• Specification as per calibration protocol
• Data on the measured error based on accredited calibration rigs traced back to ISO 17025
Mounting locationEntrained air or gas bubble formation in the measuring tube can result in an increase in measuring
errors.
Avoid the following installation locations in the pipe:
• Highest point of a pipeline. Risk of air accumulating!
• Directly upstream from a free pipe outlet in a vertical pipeline.
!
A0003202
Mounting location
Installation of pumps
Sensors may not be installed on the pump suction side. This precaution is to avoid low pressure and the
consequent risk of damage to the lining of the measuring tube. Information on the pressure tightness
of the measuring tube lining → 17, Section "Pressure tightness".
Pulsation dampers may be needed when using piston pumps, piston diaphragm pumps or hose pumps.
Information on the shock and vibration resistance of the measuring system → 16, Section "Shock and
vibration resistance".
A0003203
Installation of pumps
Partially filled pipes
Partially filled pipes with gradients necessitate a drain-type configuration.
The empty pipe detection function (EPD) provides additional security in detecting empty or partially
filled pipes.
Note!
Risk of solids accumulating. Do not install the sensor at the lowest point in the drain. It is advisable to
install a cleaning valve.
Endress+Hauser11
Page 12
Proline Promag 10L
³´5DN
³ 2
´ DN
h
2
1
A0003204
Installation with partially filled pipes
Down pipes
Install a siphon or a vent valve downstream of the sensor in down pipes h ≥ 5 m (16.4 ft). This
precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring
tube. This measure also prevents the liquid current stopping in the pipe which could cause air locks.
Information on the pressure tightness of the measuring tube lining → 17, Section "Pressure
tightness".
A0008157
Installation measures for vertical pipes
1Vent valve
2Pipe siphon
hLength of the down pipe
OrientationAn optimum orientation helps avoid gas and air accumulations and deposits in the measuring tube.
However, the measuring device also offers the additional function of empty pipe detection (EPD) for
detecting partially filled measuring tubes or if outgassing fluids or fluctuating operating pressures are
present.
Vertical orientation
This is the ideal orientation for self-emptying piping systems and for use in conjunction with empty
pipe detection.
A0008158
Vertical orientation
12Endress+Hauser
Page 13
Proline Promag 10L
A
1
22
A
3
³ 5DNx
³ 2DNx
!
Horizontal orientation
The measuring electrode axis should be horizontal. This prevents brief insulation of the two measuring
electrodes by entrained air bubbles.
Note!
Empty pipe detection only works correctly with horizontal orientation if the transmitter housing is
facing upwards. Otherwise there is no guarantee that empty pipe detection will respond if the
measuring tube is only partially filled or empty.
A0003207
Horizontal orientation
1EPD electrode for empty pipe detection
2Measuring electrodes for signal detection
3Reference electrode for potential equalization
Inlet and outlet runIf possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows etc.
Note the following inlet and outlet runs to comply with measuring accuracy specifications:
• Inlet run: ≥ 5 × DN
•Outlet run: ≥ 2 × DN
Inlet and outlet run
A0003210
Endress+Hauser13
Page 14
Proline Promag 10L
100
10
0.5
d / D
[mbar]
0.60.7 0.80.9
1 m/s
2 m/s
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
1
D
d
max. 8°
AdaptersSuitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-
diameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very slowmoving fluids. The nomogram shown here can be used to calculate the pressure loss caused by reducers
and expanders.
!
Note!
The nomogram only applies to liquids of viscosity similar to water.
1.Calculate the ratio of the diameters d/D.
2.From the nomogram read off the pressure loss as a function of flow velocity (downstream from
the reduction) and the d/D ratio.
A0003213
Pressure loss due to adapters
14Endress+Hauser
Page 15
Proline Promag 10L
L
max
[]ft
2006000
400
200
100
50100200
[m]
[ S/cm]μ
L
max
50
≤≤3 ( 10)
Length of connecting cableWhen mounting the remote version, please note the following to achieve correct measuring results:
• Fix cable run or lay in armored conduit. Cable movements can falsify the measuring signal especially
in the case of low fluid conductivities.
• Route the cable well clear of electrical machines and switching elements.
• If necessary, ensure potential equalization between sensor and transmitter.
• The permitted cable length L
is determined by the fluid conductivity.
max
A minimum conductivity of 50 μS/cm is needed for all fluids.
• When the empty pipe detection function is switched on (EPD), the maximum connecting cable
length is 10 m (33 ft).
Special mounting
instructions
Permitted length of connecting cable for remote version
Area marked in gray = permitted range; L
= length of connecting cable in [m] ([ft]); fluid conductivity in [μS/cm]
max
Temporary use in water
A remote version in IP67, type 6 is optionally available for temporary use in water up to 168 hours at
≤ 3 m (10 ft) or, in exceptional cases, for use up to 48 hours at ≤ 10 m (30 ft).
Compared to the degree of protection of standard version IP67, type 4X enclosure, the version IP67,
type 6 enclosure was designed to withstand short-term or temporary submergence (e.g. flooding).
Engineering unit m (ft)
A0003214
A0017296
Endress+Hauser15
Page 16
Proline Promag 10L
Environment
Ambient temperature rangeTransmitter
• –20 to +60 °C (–4 to +140 °F)
Sensor
• Flange material carbon steel: –10 to +60 °C (14 to +140 °F)
• Flange material stainless steel (DN ≤ 300/12"): –40 to +60 °C (–40 to +140 °F)
!
Storage temperatureThe storage temperature corresponds to the operating temperature range of the measuring
!
Note!
The permitted temperature range of the measuring tube lining may not be undershot or overshot
(→ 17, Section "Medium temperature range").
Please note the following points:
• Install the device in a shady location. Avoid direct sunlight, particularly in warm climatic regions.
• The transmitter must be mounted separate from the sensor if both the ambient and fluid
temperatures are high.
transmitter and the appropriate measuring sensors.
Note!
• The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
• A storage location must be selected where moisture does not collect in the measuring device. This
will help prevent fungus and bacteria infestation which can damage the liner.
Degree of protectionTransmitter
• As standard: IP67, type 4X enclosure
• When housing is open: IP20; type 1 enclosure
Sensor
• As standard: IP67, type 4X enclosure
• Optionally available for remote version:
– IP67, Type 6P enclosure. Suitable for temporary use in water up to 168 hours at ≤ 3 m (10 ft) or
up to 48 hours at ≤ 10 m (30 ft).
– IP68, Type 6P enclosure (for DN ≤ 300 (12") only possible in conjunction with stainless steel
flanges)
Not suitable for use in corrosive atmospheres/liquids or in buried applications if special
precautions are not taken.
Shock and vibration
resistance
Electromagnetic
compatibility (EMC)
Acceleration up to 2 g following IEC 600 68-2-6
• As per IEC/EN 61326 as well as NAMUR Recommendation NE 21
• Emission: to limit value for industry EN 55011
16Endress+Hauser
Page 17
Proline Promag 10L
0
5
10
15
20
[bar][psi]
-60
-40
-20
020
40 60 80 100120140
[°C]
[°F]
0-40100200300
200
100
300
0
Lapjoint PN16/Class150
Lapjoint flange, stampedplate PN10
Lapjoint PN10
0
5
10
15
20
[bar][psi]
-60
-40
-20
020
40 60 80 100120140
[°C]
[°F]
0-40100200300
200
100
300
0
PN16
PN10
PN6
Process
Medium temperature range• 0 to +80 °C (+32 to +176 °F) for hard rubber (DN 350 to 2400 / 14 to 90")
• –20 to +50 °C (–4 to +122 °F) for polyurethane (DN 25 to 1200 / 1 to 48")
• –20 to +90 °C (–4 to +194 °F) for PTFE (DN 25 to 300 / 1 to 12")
ConductivityThe minimum conductivity is: ≥ 50 μS/cm
!
Pressure-temperature
ratings
!
Note!
In the remote version, the necessary minimum conductivity also depends on the cable length (→ 15,
Section "Length of connecting cable").
Note!
• The following diagrams contain allowable operating pressures as a function of the medium
temperature. However, the maximum medium temperatures permitted always depend on the lining
material of the sensor and/or the sealing material (→ 17).
• Permitted test pressure = 1.5 × nominal pressure
Process connection: lap joint flange/lap joint flange, stamped plate according to EN 1092-1
(DIN 2501) and ASME B16.5; DN 25 to 300 (1 to 12")
A0021399-EN
Process connection material: stainless steel (min. -40 °C (-40 °F)), carbon steel (min. -10 °C (+14 °F))
Process connection: flange according to EN 1092-1 (DIN 2501); DN 350 to 2400 (14 to 90")
A0025178-EN
Process connection material: carbon steel
Endress+Hauser17
Page 18
Proline Promag 10L
0
5
10
15
20
[bar][psi]
-60
-40
-20
020
40 60 80 100120140
[°C]
[°F]
0-40100200300
200
100
300
0
Class150
0
5
10
15
20
[bar][psi]
-60
-40
-20
020
40 60 80 100120140
[°C]
[°F]
0-40100200300
200
100
300
0
TableE
PN16
Process connection: flange according to ASME B16.5; DN 350 to 600 (14 to 24")
Process connection material: A105
Process connection: flange according to AS 2129 and AS 4087; DN 350 to 2400 (14 to 90")
A0025179-EN
Process connection material: carbon steel
Medium pressure range
(nominal pressure)
• EN 1092-1 (DIN 2501)
– PN 6 (DN 350 to 2400 / 14 to 90")
– PN 10 (DN 200 to 2400 / 8 to 90")
– PN 16 (DN 25 to 2000 / 1 to 78")
• EN 1092-1, lap joint flange, stamped plate
– PN 10 (DN 25 to 300 / 1 to 12")
•ASME B16.5
– Class 150 (1 to 24")
• AWWA C207
– Class D (28 to 90")
•AS2129
– Table E (350 to 1200 / 14 to 48")
•AS4087
– PN 16 (350 to 1200 / 14 to 48")
Pressure tightnessMeasuring tube lining: Polyurethane, hard rubber
Promag L
Nominal diameter
[mm][inch]
25 to 12001 to 48" Polyurethane00 –
350 to 2400 14 to 90" Hard rubber000
18Endress+Hauser
Measuring
tube lining
Resistance of measuring tube lining to partial vacuum: Limit values
for abs. pressure [mbar] ([psi]) at various fluid temperatures
25 °C50 °C80° C
77 °F122 °F176° F
A0025180-EN
Page 19
Proline Promag 10L
L
Measuring tube lining: PTFE
Nominal diameterLimit values for abs. pressure [mbar] ([psi]) at fluid temperatures:
25 °C (77 °F)90 °C (194 °F)
[mm][inch][mbar][psi][mbar][psi]
251"0000
32–0000
401 ½"0000
502"0000
65–00400.58
803"00400.58
1004"001351.96
125–1351.962403.48
1506"1351.962403.48
2008"2002.902904.21
25010"3304.794005.80
30012"4005.805007.25
Limiting flowThe diameter of the pipe and the flow rate determine the nominal diameter of the sensor.
The optimum flow velocity is between 2 to 3 m/s (6.5 to 9.8 ft/s). The velocity of flow (v), moreover,
has to be matched to the physical properties of the fluid:
• v < 2 m/s (6.5 ft/s): for abrasive fluids such as potter's clay, lime milk, ore slurry etc.
• v > 2 m/s (6.5 ft/s): for fluids causing build-up such as wastewater sludges etc.
For an overview of the measuring range full scale values, see the "Measuring range" section → 4.
Pressure loss• No pressure loss if the sensor is installed in a pipe with the same nominal diameter.
• Pressure losses for configurations incorporating adapters according to DIN EN 545 (→ 14, Section
"Adapters").
VibrationsSecure the piping and the sensor if vibration is severe.
!
Note!
If vibrations are too severe, we recommend the sensor and transmitter be mounted separately.
Information on the permitted shock and vibration resistance → 16, Section "Shock and vibration
resistance".
A0003208
Measures to prevent vibration of the measuring device
L > 10 m (33 ft)
Endress+Hauser19
Page 20
Mechanical construction
K
F
E
D
A
H
L
N
O
P
J
G
B
C
M
248 ±2
(9.76 ±0.08)
238 (9.37)
AB
ANSCHLUSSKLEMMEN - FIELD TERMINALS
Design, dimensionsTransmitter, remote version
Proline Promag 10L
Transmitter dimensions, remote version
Dimensions in SI units
ABCDEFGØ H
17811313520 to 30161 to 1811131008.6 (M8)
JKLMNOP
12315010025133177.5327.5
All dimensions in [mm]
Dimensions in US units
ABCDEFGØ H
7.004.455.310.79 to 1.81 6.34 to 7.134.443.940.34 (M8)
JKLMNOP
4.845.903.940.985.246.9912.89
All dimensions in [inch]
A0010718
Transmitter mounting, remote version. Engineering unit mm (in)
ADirect wall mounting
BPipe mounting
20Endress+Hauser
A0010719
Page 21
Proline Promag 10L
J
L
E
G
F
H
B
C
A
D
Sensor, remote version, DN 25 to 300 (1 to 12")
A0012462
Dimensions in SI units
DNL
25200
322002862028412094
402002862028412094
502002862028412094
6520033622710918094
8020033622710918094
10025033622710918094
125250417267150260140
150300417267150260140
200350472292180324156
250450522317205400156
300500572342230460166
1)
The length (L) is regardless of the pressure rating selected. Fitting length to DVGW.
All dimensions in [mm]
1)
ABCDEFGHJ
129163143102
2862028412094
Dimensions in US units
DNL
1"7.87
1 ½"7.8711.37.953.324.723.70
2"7.8711.37.953.324.723.70
3"7.8713.28.944.307.103.70
4"9.8413.28.944.307.103.70
6"11.816.410.55.9110.25.51
8"13.818.611.57.1012.86.14
10"17.720.612.58.0815.86.14
12"19.722.513.59.0618.16.54
1)
The length (L) is regardless of the pressure rating selected. Fitting length to DVGW
All dimensions in [inch]
1)
ABCDEFGHJ
11.37.953.324.723.70
5.086.425.634.02
Endress+Hauser21
Page 22
Sensor, remote version, DN 350 to 2400 (14 to 90")
L
G
E
F
H
A
B
C
Proline Promag 10L
A0014987
Dimensions in SI units
DNLABCFG
350550
375600379290
400600379290
450600407290
500600432290
600600473290
700700538424
750750575454
800800594500
900900644580
10001000694664
12001200808832
140014009201008
1600160010201147
1800180011281379
2000200012391569
2200220013391711
2400240014441859
All dimensions in [mm]
129163102
353290
22Endress+Hauser
Page 23
Proline Promag 10L
DNE with pressure ratingH with pressure rating
PN 6PN 10PN 16ASME
AWWA
350598605613620615490505520533525
375––––654––––550
400649661667677669540565580597580
450704714727724727595615640635640
500754767790781784645670715699705
600850863893879885755780840813825
70096898510031001993860895910927910
750–––10671073–––984995
800108211021107112411249751015102510601060
9001182120212071228123210751115112511681175
10001282130913221339132211751230125512891255
12001511153615511564155314051455125515111490
1400173517581763––163016751685––
1600193519781986––183019151930––
18002150218521932226–2045211521302197–
20002371240124112420–2265232523452362–
220025762614–––24752550–––
240027862824–––26852760–––
All dimensions in [mm]
ASPN 6PN 10PN 16ASME
AWWA
AS
Endress+Hauser23
Page 24
Proline Promag 10L
Dimensions in US units
DNLABCFG
14"21.7
15"23.614.911.4
16"23.614.911.4
18"23.616.011.4
20"23.617.011.4
24"23.618.611.4
28"27.621.216.7
30"29.522.617.9
32"31.523.419.7
36"35.425.422.8
40"39.427.326.2
42"41.328.729.9
48"47.231.832.8
54"53.236.239.7
60"59.140.245.2
66"65.042.250.6
72"70.944.454.3
78"78.748.861.8
84"84.752.767.4
90"90.656.873.2
All dimensions in [inch]
5.086.424.02
13.911.4
DNE with pressure ratingH with pressure rating
PN 6PN 10PN 16ASME
AWWA
14"23.523.824.124.424.219.319.920.521.020.7
15"––––25.7––––21.7
16"25.626.026.326.726.321.322.222.823.522.8
18"27.728.128.628.528.623.424.225.225.025.2
20"29.730.231.130.730.925.426.428.127.527.8
24"33.534.035.234.634.829.730.733.132.032.5
28"38.139.039.539.639.333.935.235.836.535.8
30"–––42.242.4–––38.739.2
32"42.643.643.644.444.438.440.040.441.741.7
36"46.547.547.548.548.742.343.944.346.046.3
40"50.551.752.052.952.246.348.448.250.749.4
42"–––55.4––––53.0–
48"59.560.661.161.861.355.357.349.459.558.7
54"––69.469.4–––66.366.3–
60"––78.276.7–––76.073.0–
66"–––82.2––––80.0–
72"84.786.086.387.66–80.583.383.986.5–
78"93.494.594.995.3–89.291.592.393.0–
84"–––102.6––––99.8–
90"–––110.1––––106.5–
All dimensions in [inch]
ASPN 6PN 10PN 16ASME
AWWA
AS
24Endress+Hauser
Page 25
Proline Promag 10L
K
J
L
F
H
G
Esc
E
-
+
E
A
D
B
C
Compact version, DN 25 to 300 (1 to 12")
A0012464
Dimensions in SI units
DNL
25200
322003412578494120
402003412578494120
502003412578494120
6520039128210994180
8020039128210994180
10025039128210994180
125250472322150140260
150300472322150140260
200350527347180156324
250450577372205156400
300500627397230166460
1)
The length (L) is regardless of the pressure rating selected. Fitting length to DVGW.
All dimensions in [mm]
1)
ABCDEFGHJK
3412578494120
17820 to 30 153 to 168121150
Dimensions in US units
DNL
1"7.87 7.010.79 to 1.81 6.02 to 6.61 4.765.9113.410.13.323.704.72
1½"7.8713.410.13.323.704.72
2"7.8713.410.13.323.704.72
–7.8715.411.14.303.707.10
3"7.8715.411.14.303.707.10
4"9.8415.411.14.303.707.10
–9.8418.612.75.915.5110.2
6"11.818.612.75.915.5110.2
8"13.820.813.77.106.1412.8
10"17.722.714.78.086.1415.8
12"19.724.715.69.066.5418.1
1)
The length (L) is regardless of the pressure rating selected. Fitting length to DVGW.
Fitted electrodesMeasuring electrodes, reference electrodes and empty pipe detection electrodes available as standard
with:
• 1.4435 (316L)
• Alloy C22, 2.4602 (UNS N06022)
Process connections• EN 1092-1 (DIN 2501)
(Dimensions to DIN 2501, DN 65 PN 16 exclusively to EN 1092-1)
–DN ≤ 300: lap joint flange (PN 10/16), lap joint flange, stamped plate (PN 10) = form A
–DN ≥ 350: fixed flange (PN 6/10)= flat race
For information on the materials of the process connections → 37 Material
Surface roughnessElectrodes with 1.4435 (316L), Alloy C22, 2.4602 (UNS N06022): ≤ 0.3 to 0.5 μm (11.8 to 19.7 μin)
(all data refer to parts in contact with medium)
Endress+Hauser37
Page 38
Proline Promag 10L
Operability
Local operationDisplay elements
• Liquid crystal display: unilluminated, two lines with 16 characters per line
• Display (operating mode) preconfigured: volume flow and totalizer status
•1 totalizers
Operating elements
• Onsite operation via three keys (, , )
Remote operationOperation via HART protocol and FieldCare
Certificates and approvals
CE markThe measuring system is in conformity with the statutory requirements of the EC Directives.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
C-tick markThe measuring system meets the EMC requirements of the "Australian Communication and Media
Authority (ACMA)".
Drinking water approval• WRAS BS 6920
•ACS
•NSF 61
•KTW/W270
Other standards and
guidelines
• EN 60529
Degrees of protection by housing (IP code).
• EN 61010
Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory
Procedures.
• IEC/EN 61326
"Emission in accordance with requirements for Class A".
Electromagnetic compatibility (EMC requirements).
• ANSI/ISA-S82.01
Safety Standard for Electrical and Electronic Test, Measuring, Controlling and related
Equipment - General Requirements. Pollution degree 2, Installation Category II.
• CAN/CSA-C22.2 No. 1010.1-92
Safety requirements for Electrical Equipment for Measurement and Control and Laboratory Use.
Pollution degree 2, Installation Category II
38Endress+Hauser
Page 39
Proline Promag 10L
!
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com → Select country →
Instruments → Select device → Product page function: Configure this product
• From your Endress+Hauser Sales Center: www.endress.com/worldwide
Note!
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as measuring
range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the
transmitter and the sensor. Your Endress+Hauser service organization can provide detailed
information on the order codes in question.
Device-specific accessoriesFor the transmitter
AccessoryDescription
Promag 10 transmitterTransmitter for replacement or for stock. Use the order code to define the following
Mounting setMounting set for the aluminum field housing (remote version). Suitable for pipe
Cable for remote version Coil current and electrode cables, various lengths.
For the sensor
AccessoryDescription
Ground cableGround cable for potential equalization.
Ground diskGround disk for potential equalization.
specifications:
•Approvals
• Degree of protection / version
• Cable type for the remote version
•Cable entries
• Display / power supply / operation
•Software
• Outputs / inputs
mounting.
Endress+Hauser39
Page 40
Proline Promag 10L
Communication-specific
accessories
Service-specific accessories
AccessoryDescription
HART handheld
terminal Field Xpert SFX
100
Fieldgate FXA320Gateway for remote interrogation of HART sensors and actuators via web browser:
Fieldgate FXA520Gateway for remote interrogation of HART sensors and actuators via web browser:
FXA195The Commubox FXA195 connects intrinsically safe smart transmitters using the
AccessoryDescription
ApplicatorSoftware for selecting and configuring flowmeters.
FieldcheckTester/simulator for testing flowmeters in the field.
FieldCareFieldCare is Endress+Hauser’s FDT-based plant asset management tool. It can
FXA193 The FXA193 service interface connects the device to the PC for operation
Memograph M graphic
display recorder
Handheld terminal for remote configuration and for obtaining measured values via
the HART current output (4 to 20 mA).
Contact your Endress+Hauser representative for more information.
• 2-channel analog input (4 to 20 mA)
• 4 binary inputs with event counter function and frequency measurement
• Communication via modem, Ethernet or GSM
• Visualization via Internet/Intranet in the web browser and/or WAP cellular phone
• Limit value monitoring with alarm signaling by e-mail or SMS
• Synchronized time stamping of all measured values.
• Web server for remote monitoring of up to 30 measuring points
• Intrinsically safe version [EEx ia]IIC for applications in hazardous areas
• Communication via modem, Ethernet or GSM
• Visualization via Internet/Intranet in the web browser and/or WAP cellular phone
• Limit value monitoring with alarm signaling by e-mail or SMS
• Synchronized time stamping of all measured values
• Remote diagnostics and remote configuration of connected HART devices
HART protocol to the USB port of a personal computer. This enables remote operation
of the transmitter with operating software (e.g. FieldCare). Power is supplied to the
Commubox via the USB port.
Applicator can be downloaded from the Internet or ordered on CD-ROM for installation
on a local PC.
Contact your Endress+Hauser representative for more information.
When used in conjunction with the "FieldCare" software package, test results can be
imported into a database, printed and used for official certification.
Contact your Endress+Hauser representative for more information.
configure all smart field units in your system and helps you manage them. By using the
status information, it is also a simple but effective way of checking their status and
condition.
via FieldCare.
The Memograph M graphic display recorder provides information on all the relevant
process variables: Measured values are recorded correctly, limit values are monitored
and measuring points analyzed. The data are stored in the 256 MB internal memory
and also on a SD card or USB stick.
The ReadWin
configuring, visualizing and archiving the data captured.
®
2000 PC software is part of the standard package and is used for
Documentation
• Flow measurement (FA00005D/06)
• Operating Instructions Promag 10 (BA00082D/06)
40Endress+Hauser
Page 41
Proline Promag 10L
Registered trademarks
KALREZ® and VITON
Registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA
TRI-CLAMP
®
Registered trademark of Ladish & Co., Inc., Kenosha, USA
®
HART
Registered trademark of the HART Communication Foundation, Austin, USA
FieldCare®, Fieldcheck
Registered or registration-pending trademarks of the Endress+Hauser Group
®
®
, Field Xpert™, Applicator
®
Endress+Hauser41
Page 42
Proline Promag 10L
42Endress+Hauser
Page 43
Proline Promag 10L
Endress+Hauser43
Page 44
www.addresses.endress.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.