Endress+Hauser PMP75 Specifications

TI00383P/00/EN/33.20 71475824 2020-04-01
Products
Solutions Services
Technical Information
Cerabar S PMC71, PMP71, PMP75
Process pressure measurement
Pressure transmitter with ceramic and metal sensors
Applications
The device is used for the following measuring tasks:
• Absolute pressure and gauge pressure measurement in gases, steams or liquids in all areas of process engineering and process measurement technology
• Level, volume or mass measurements in liquids
• High process temperatures
• up to 400 °C (752 °F)with typical diaphragm seals
• High pressures up to 700 bar (10 500 psi)
• Low-energy version with voltage output (1-5V DC), e.g. for operation on solar­operated control units (Remote Terminal Unit (RTU))
Your benefits
• Very good reproducibility and long-term stability
• High reference accuracy up to ±0.025 %
• Turn down up to 100:1, higher on request
• Used for process pressure monitoring up to SIL 3, certified to IEC 61508 by TÜV SÜD
• High level of safety during operation thanks to function monitoring from the measuring cell to the electronics
• Easy electronics replacement guaranteed with HistoROM®/M-DAT

Table of contents

Cerabar S PMC71, PMP71, PMP75
About this document ........................ 4
Document function ............................ 4
Symbols used ................................ 4
Documentation ............................... 5
Terms and abbreviations ........................ 6
Turn down calculation .......................... 7
Registered trademarks .......................... 7
Function and system design ................... 8
Device features ............................... 8
Measuring principle ........................... 10
Product design .............................. 12
Applications suitable for custody transfer measurement ... 12
Communication protocol ........................ 12
Input .................................... 13
Measured variable ............................ 13
Measuring range ............................. 13
Output .................................. 16
Output signal ............................... 16
Signal range ................................ 16
Signal on alarm .............................. 16
Load ..................................... 17
Damping .................................. 18
Alarm current ............................... 18
Firmware version ............................ 18
Protocol-specific data HART ..................... 18
Wireless HART data ........................... 19
Protocol-specific data PROFIBUS PA ................ 19
Protocol-specific data FOUNDATION Fieldbus .......... 20
Power supply ............................. 23
Terminal assignment .......................... 23
Supply voltage .............................. 24
Current consumption .......................... 25
Electrical connection .......................... 25
Terminals ................................. 25
Cable entries ............................... 25
Device plugs ................................ 25
Cable specification ............................ 27
Start-up current ............................. 27
Residual ripple .............................. 27
Overvoltage protection (optionally for HART, PROFIBUS
PA and FOUNDATION Fieldbus) ................... 28
Influence of power supply ....................... 28
Performance characteristics for measuring devices with ceramic process isolating
diaphragm ............................... 29
Response time .............................. 29
Reference operating conditions ................... 29
Maximum measured error (total performance) ......... 29
Resolution ................................. 31
Total error ................................. 31
Long-term stability ........................... 32
Response time T63 and T90 ..................... 32
Installation factors ............................ 33
Performance characteristics for measuring devices with metal process isolating diaphragm .. 34
Response time .............................. 34
Reference operating conditions ................... 34
Maximum measured error (total performance) ......... 34
Resolution ................................. 37
Total error ................................. 37
Long-term stability ........................... 38
Response time T63 and T90 ..................... 38
Installation factors ............................ 41
Installation ............................... 42
General installation instructions ................... 42
Measuring arrangement for devices without diaphragm
seals – PMC71, PMP71 ........................ 42
Measuring arrangement for devices with diaphragm seals
– PMP75 .................................. 42
Orientation ................................ 42
Wall and pipe mounting, transmitter (optional) ........ 43
Wall and pipe mounting, valve manifold (optional) ...... 43
Heat insulation – PMC71 high-temperature version ..... 43
Mounting of PVDF screw-in fittings ................ 44
"Separate housing" version ....................... 45
Turning the housing .......................... 46
Environment .............................. 47
Ambient temperature range ..................... 47
Storage temperature range ...................... 48
Degree of protection .......................... 48
Climate class ............................... 48
Electromagnetic compatibility .................... 48
Vibration resistance ........................... 48
Oxygen applications ........................... 49
PWIS-free applications ......................... 49
Ultrapure gas applications ....................... 49
Hydrogen applications ......................... 49
Operation in very corrosive environment ............. 49
Process .................................. 50
Process temperature limits ...................... 50
Process temperature limits of capillary armoring: PMP75 .. 51
Pressure specifications ......................... 52
Mechanical construction .................... 53
Device height ............................... 53
T14 housing, optional display on the side ............ 54
T17 housing (hygienic), optional display on the side ..... 55
Process connections for PMC71 with internal process
isolating diaphragm ........................... 56
Process connections for PMC71 with internal process
isolating diaphragm ........................... 58
Process connections for PMC71 with internal process
isolating diaphragm - height H ................... 58
Process connections for PMC71 with flush-mounted
process isolating diaphragm ..................... 59
2 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
Process connections for PMC71 with flush-mounted
process isolating diaphragm ..................... 60
Process connections for PMC71 with flush-mounted
process isolating diaphragm - height H .............. 60
Process connections for PMC71 with flush-mounted
process isolating diaphragm ..................... 61
Process connections for PMC71 with flush-mounted
process isolating diaphragm ..................... 64
Hygienic process connections for PMC71 with flush mount
process isolating diaphragm ..................... 65
Process connections for PMP71 with internal process
isolating diaphragm ........................... 67
Process connections for PMP71 with internal process
isolating diaphragm ........................... 68
Process connections for PMP71 with internal process
isolating diaphragm ........................... 69
Process connections for PMP71 with flush mount process
isolating diaphragm ........................... 70
Process connections for PMP71 with flush-mounted
process isolating diaphragm ..................... 72
Process connections for PMP71 with flush-mounted
process isolating diaphragm ..................... 73
Process connections for PMP71 with flush-mounted
process isolating diaphragm ..................... 74
Process connections for PMP71 with flush-mounted
process isolating diaphragm ..................... 75
PMP71: process connections with flush-mounted process
isolating diaphragm ........................... 76
Process connections for PMP71 ................... 77
Process connections for PMP71 ................... 77
Valve manifold DA63M- (optional) ................. 78
PMP75 basic device ........................... 79
Process connections for PMP75 with flush-mounted
process isolating diaphragm ..................... 80
Process connections for PMP75 with flush-mounted
process isolating diaphragm ..................... 81
Process connections for PMP75 with flush-mounted
process isolating diaphragm ..................... 82
Process connections for PMP75 with flush-mounted
process isolating diaphragm ..................... 83
Hygienic process connections for PMP75 with flush mount
process isolating diaphragm ..................... 84
Hygienic process connections for PMP75 with flush-
mounted process isolating diaphragm ............... 85
Hygienic process connections for PMP75 with flush-
mounted process isolating diaphragm ............... 87
Process connections for PMP75 with flush mount process
isolating diaphragm ........................... 90
Process connections for PMP75 with flush mount process
isolating diaphragm ........................... 92
Process connections for PMP75 ................... 95
Separate housing: Wall and pipe mounting with mounting
bracket ................................... 98
Flushing rings ............................... 99
Weight ................................... 99
Materials not in contact with process .............. 100
Materials in contact with process ................. 103
Fill fluid .................................. 105
Operability .............................. 106
Operating concept ........................... 106
Local operation ............................. 106
Remote operation ........................... 109
HistoROM®/M-DAT (optional) .................. 111
System integration ........................... 111
Planning instructions for diaphragm seal
systems ................................. 112
Applications ............................... 112
Function and design .......................... 113
Diaphragm seal filling oils ...................... 115
Cleaning instructions ......................... 115
Installation instructions ....................... 115
Vacuum applications ......................... 119
Certificates and approvals .................. 120
CE mark .................................. 120
RoHS .................................... 120
RCM-Tick marking ........................... 120
Ex approvals ............................... 120
EAC conformity ............................. 120
Suitable for hygiene applications ................. 120
Certificate of current Good Manufacturing Practices
(cGMP) .................................. 120
Functional safety SIL/ IEC 61508 Declaration of
Conformity (optional) ......................... 120
Overfill prevention ........................... 120
CRN approval .............................. 121
Other standards and guidelines .................. 121
Pressure Equipment Directive 2014/68/EU (PED) ...... 121
Manufacturer declarations ..................... 122
Marine approval ............................ 122
Drinking water approval ....................... 122
Approvals for custody transfer ................... 122
MID Parts Certificate ......................... 122
Classification of process sealing between electrical systems and (flammable or combustible) process fluids in
accordance with ANSI/ISA 12.27.01 ............... 123
Inspection certificate ......................... 123
Calibration ................................ 124
Service .................................. 124
Ordering information ...................... 125
Special device versions ........................ 125
Scope of delivery ............................ 125
Measuring point (TAG) ........................ 125
Configuration data sheet ....................... 126
Accessories .............................. 128
HistoROM®/M-DAT .......................... 128
Welding flanges and weld-in adapters .............. 128
Manifolds ................................ 128
Additional mechanical accessories ................ 128
Service-specific accessories ..................... 128
Supplementary documentation .............. 129
Field of Activities ............................ 129
Technical Information ........................ 129
Special Documentation ........................ 129
Operating Instructions ........................ 129
Brief Operating Instructions ..................... 129
Functional safety manual (SIL) ................... 129
Overfill prevention ........................... 129
Safety Instructions (XA) ....................... 129
Installation/Control Drawings ................... 131
Endress+Hauser 3

About this document

DANGER
WARNING
CAUTION
NOTICE
A
Cerabar S PMC71, PMP71, PMP75

Document function

The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.

Symbols used Safety symbols

Symbol Meaning
Electrical symbols
Symbol Meaning Symbol Meaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury.
NOTICE!
This symbol contains information on procedures and other facts which do not result in personal injury.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Symbols for certain types of information
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
4 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
,…,
1.
2.
3.
Symbols in graphics
A-A, B-B, C-C, ... Sections
Symbol Meaning
1, 2, 3 ... Item numbers
Series of steps
A, B, C, ... Views

Documentation

See the "Supplementary documentation" section →  129
The document types listed are available: In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download
Safety Instructions (XA)
See the "Safety instructions" section →  129
Endress+Hauser 5

Terms and abbreviations

URL OPLMWP
LRL
0
p
LRV
URV
1
2
3
4
Cerabar S PMC71, PMP71, PMP75
A0029505
Item Term/abbreviation Explanation
1 OPL The OPL (over pressure limit = sensor overload limit) for the measuring device depends on the lowest-rated element,
with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes see the "Pressure specifications" section →  52. The OPL may only be applied for a limited period of time.
2 MWP The MWP (maximum working pressure) for the sensors depends on the lowest-rated element, with regard to
pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes see the "Pressure specifications" section →  52. The MWP may be applied at the device for an unlimited period. The MWP can also be found on the nameplate.
3 Maximum sensor
measuring range
4 Calibrated/adjusted
span
p - Pressure
- LRL Lower range limit
- URL Upper range limit
- LRV Lower range value
- URV Upper range value
- TD (Turn down) Turn down
Span between LRL and URL This sensor measuring range is equivalent to the maximum calibratable/adjustable span.
Span between LRV and URV Factory setting: 0 to URL Other calibrated spans can be ordered as customized spans.
Example - see the following section.
6 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
LRV
URLURV
LRL
1 = 2
3

Turn down calculation

1 Calibrated/adjusted span 2 Zero point-based span 3 URL sensor
Example
• Sensor:10 bar (150 psi)
• Upper range value (URL) = 10 bar (150 psi)
Turn down (TD):
A0029545
• Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)
• Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
TD =
TD =
In this example, the TD is 2:1. This span is based on the zero point.

Registered trademarks HART®

Registered trademark of the FieldComm Group, Austin, USA
PROFIBUS®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
FOUNDATIONTMFieldbus
Registered trademark of the FieldComm Group, Austin, Texas, USA
URL
|URV - LRV|
10 bar (150 psi)
= 2
|5 bar (75 psi) - 0 bar (0 psi)|
Endress+Hauser 7

Device features

Cerabar S PMC71, PMP71, PMP75

Function and system design

A0020461
PMC71 with capacitive measuring cell and ceramic process isolating diaphragm (Ceraphire®)
A0020463
PMP71 with piezoresistive measuring cell and metallic welded process isolating diaphragm
PMP75 with diaphragm seal
Field of application
• Gauge pressure and absolute pressure
• Level
Process connections
PMC71:
• Thread
• EN flanges DN 25 – DN 80
• ANSI flanges 1" – 4"
• JIS flanges 50 A – 100 A PMP71:
• Thread
• DN 25 – DN 80
• ASME 1 ½" – 4"
• JIS 25 A – 100 A
• Oval flange adapters
• Prepared for diaphragm seal mount PMP75:
Wide range of diaphragm seals
A0020464
Measuring ranges
• PMC71: From –100/0 to 100 mbar (–1.5/0 to 1.5 psi) to –1/0 to 40 bar (–15/0 to 600 psi)
• PMP71: From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 700 bar (–15/0 to 10500 psi)
• PMP75: From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 400 bar (–15/0 to 6000 psi)
8 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
OPL
• PMC71: max. 60 bar (900 psi)
• PMP71: max. 1 050 bar (15 750 psi)
• PMP75: max. 600 bar (9 000 psi)
Process temperature range (temperature at process connection)
• PMC71:–25 to +125 °C (–13 to +257 °F) –20 to +150 °C (–4 to +302 °F) (High-temperature version, see Product Configurator "Additional option 1" or 110 "Additional option 2" section, option "T")
• PMP71:–40 to +125 °C (–40 to +257 °F)
• PMP75: –70 to +400 °C (–94 to +752 °F) (depending on the filling oil)
Ambient temperature range
• Without LCD display: up to –60 to +85 °C (–76 to +185 °F)
• With LCD display: –20 to +70 °C (–4 to +158 °F) (extended temperature application range –60 to +85 °C (–76 to +185 °F) with limitations in optical properties, such as display speed and contrast)
• Separate housing: –20 to +60 °C (–4 to +140 °F)
• PMP75: Diaphragm seal systems depending on the version
Reference accuracy
• PMC71: Up to ±0.05% of the set span PLATINUM version: up to ±0.025 % of the set span
• PMP71: Up to ±0.05% of the set span PLATINUM version: up to ±0.025 % of the set span
• PMP75: Up to ±0.075% of the set span
Supply voltage
Supply voltage non-Ex
• 4 to 20 mA HART: 10.5 to 45 V DC
• 1-5V DC: 9 to 35 V DC
• PROFIBUS PA and FOUNDATION Fieldbus: 9 to 32 V DC
Supply voltage Ex ia
10.5 to 30 V DC
Supply voltage Ex d (1-5V DC) 9 to 35 V DC
Output
• 4 to 20 mA with superimposed HART protocol
• 1-5V DC
• PROFIBUS PA
• FOUNDATION Fieldbus
Options
• Inspection certificate 3.1
• HistoROM®/M-DAT memory chip
• Separate housing
• PMP75: gold-coated process isolating diaphragm
• PMP71, PMP75: gold-rhodium coated process isolating diaphragm
• PMP71, PMP75:NACE-compliant materials
Endress+Hauser 9
Cerabar S PMC71, PMP71, PMP75
1
2
3
4
p
Specialties
• PMC71:
• Metal-free measurement with PVDF connection
• Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops
• PMP71:
• Process connections with minimum oil volume
• Gas-tight, elastomer-free
• PMP75:
• Wide range of diaphragm seals
• For high medium temperatures
• Process connections with minimum oil volume
• Completely welded versions

Measuring principle

Devices with ceramic process isolating diaphragm (Ceraphire®)
A0020465
1 Air pressure (gauge pressure sensors) 2 Ceramic substrate 3 Electrodes 4 Ceramic process isolating diaphragm
The ceramic sensor is an oil-free sensor, i.e. the process pressure acts directly on the robust ceramic process isolating diaphragm and causes it to deflect. A pressure-dependent change in capacitance is measured at the electrodes of the ceramic substrate and the process isolating diaphragm. The measuring range is determined by the thickness of the ceramic process isolating diaphragm.
Advantages:
• Guaranteed overload resistance up to 40 times the nominal pressure (see "OPL" column in table) →  13)
• The ultrapure 99.9% ceramic (Ceraphire®, see also "www.endress.com/ceraphire") ensures:
• Extremely high chemical durability
• High mechanical durability
• Suitable for vacuums
• Secondary containment for enhanced integrity
• Process temperatures up to 150 °C (302 °F)
10 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
p
1
3
4
2
Devices with metallic process isolating diaphragm
1 Silicon measuring element, substrate 2 Wheatstone bridge 3 Channel with fill fluid 4 Metal process isolating diaphragm
PMP71
The process pressure deflects the metal process isolating diaphragm of the sensor and a fill fluid transfers the pressure to a Wheatstone bridge (semiconductor technology). The pressure-dependent change in the bridge output voltage is measured and evaluated.
Advantages:
• Can be used for process pressures up to 700 bar (10 500 psi)
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
• Secondary containment for enhanced integrity
• Significantly reduced thermal effect e.g. compared to diaphragm seal systems with capillaries
A0016448
PMP75
The operating pressure acts on the process isolating diaphragm of the diaphragm seal and is transferred to the process isolating diaphragm of the sensor by a diaphragm seal fill fluid. The process isolating diaphragm is deflected and a fill fluid transfers the pressure to a resistance measuring bridge. The pressure-dependent change in the bridge output voltage is measured and evaluated.
Advantages:
• Depending on the version, can be used for process pressures up to 400 bar (6 000 psi) and for extreme process temperatures
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
• Secondary containment for enhanced integrity
Endress+Hauser 11

Product design Level measurement (level, volume and mass):

h =
p
ρ g
h
h Height (level) p Pressure ρ Density of the medium g Gravitation constant
Your benefits
• Selection of the level operating mode which is optimum for your application in the device software
• Volume and mass measurements in any vessel shape by means of a freely programmable characteristic curve
• Choice of diverse level units with automatic unit conversion
• A customized unit can be specified.
• Has a wide range of uses, e.g.
• for foam formation
• in vessels with agitators of screen fittings
• for liquid gases
Cerabar S PMC71, PMP71, PMP75
A0020466

Applications suitable for custody transfer measurement

Communication protocol

The Parts Certificate is issued on the basis of the following standards:
• WELMEC guide 8.8 "General and Administrative Aspects of the Voluntary System of Modular Evaluation of Measuring instruments under the MID".
• OIML R117-1 Edition 2007 (E) "Dynamic measuring systems for liquids other than water".
• EN 12405-1/A1 Edition 2006 "Gas meters – Conversion devices – Part 1: Volume conversion".
• 4 to 20 mA with HART communication protocol
• PROFIBUS PA
• Endress+Hauser devices meet the requirements specified by the FISCO model.
• Due to a low current consumption of 13 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO: up to 7 devices for Ex ia, CSA IS and FM IS applications or up to 27 devices for all other applications e.g. in non-hazardous areas, Ex nA etc. Further information on PROFIBUS PA can be found in Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and in the PNO Guideline.
• FOUNDATION Fieldbus
• Endress+Hauser devices meet the requirements specified by the FISCO model.
• Due to a low current consumption of 15.5 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO: up to 6 devices for Ex ia, CSA IS and FM IS applications or up to 24 devices for all other applications e.g. in non-hazardous areas, Ex nA etc. Further information on FOUNDATION Fieldbus, such as requirements for bus system components, can be found in Operating Instructions BA00013S "FOUNDATION Fieldbus Overview".
12 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75

Input

Measured variable Measured process variables

• Absolute pressure
• Gauge pressure

Measuring range PMC71 – with ceramic process isolating diaphragm (Ceraphire®) for gauge pressure

Sensor Maximum sensor measuring range Lowest
lower (LRL) upper (URL)
calibratable span
[bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar
1)
MWP OPL Vacuum resistance Option
(psi
abs
)]
abs
100 mbar (1.5 psi) –0.1 (–1.5) +0.1 (+1.5) 0.005 (0.075) 2.7 (40.5) 4 (60) 0.7 (10.5) 1C
250 mbar (3.75 psi) –0.25 (–3.75) +0.25 (+3.75) 0.005 (0.075) 3.3 (49.5) 5 (75) 0.5 (7.5) 1E
400 mbar (6 psi) –0.4 (–6) +0.4 (+6) 0.005 (0.075) 5.3 (79.5) 8 (120) 0 1F
1 bar (15 psi) –1 (–15) +1 (+15) 0.01 (0.15) 6.7 (100.5) 10 (150) 0 1H
2 bar (30 psi) –1 (–15) +2 (+30) 0.02 (0.3) 12 (180) 18 (270) 0 1K
4 bar (60 psi) –1 (–15) +4 (+60) 0.04 (0.6) 16.7 (250.5) 25 (375) 0 1M
10 bar (150 psi) –1 (–15) +10 (+150) 0.1 (1.5) 26.7 (400.5) 40 (600) 0 1P
40 bar (600 psi) –1 (–15) +40 (+600) 0.4 (6) 40 (600) 60 (900) 0 1S
1) Turndown > 100:1 on request or can be set on device
2) Product Configurator, order code for "Sensor range; sensor over pressure limit"
PMC71 – with ceramic process isolating diaphragm (Ceraphire®) for absolute pressure
Sensor Maximum sensor measuring range Lowest
lower (LRL) upper (URL)
[bar
(psi
abs
)] [bar
abs
abs
(psi
calibratable
1)
span
)] [bar (psi)] [bar
abs
100 mbar (1.5 psi) 0 +0.1 (+1.5) 0.005 (0.075) 2.7 (40.5) 4 (60) 0 2C
250 mbar (3.75 psi) 0 +0.25 (+3.75) 0.005 (0.075) 3.3 (49.5) 5 (75) 0 2E
400 mbar (6 psi) 0 +0.4 (+6) 0.005 (0.075) 5.3 (79.5) 8 (120) 0 2F
1 bar (15 psi) 0 +1 (+15) 0.01 (0.15) 6.7 (100.5) 10 (150) 0 2H
2 bar (30 psi) 0 +2 (+30) 0.02 (0.3) 12 (180) 18 (270) 0 2K
4 bar (60 psi) 0 +4 (+60) 0.04 (0.6) 16.7 (250.5) 25 (375) 0 2M
10 bar (150 psi) 0 +10 (+150) 0.1 (1.5) 26.7 (400.5) 40 (600) 0 2P
40 bar (600 psi) 0 +40 (+600) 0.4 (6) 40 (600) 60 (900) 0 2S
MWP OPL Vacuum resistance Option
(psi
abs
)] [bar
abs
abs
(psi
)] [bar
abs
abs
(psi
abs
)]
2)
2)
1) Turndown > 100:1 on request or can be set on device
2) Product Configurator, order code for "Sensor range; sensor over pressure limit"
Endress+Hauser 13
Cerabar S PMC71, PMP71, PMP75
PMP71 and PMP75 – metal process isolating diaphragm for gauge pressure
abs
2)
)]
Sensor Maximum sensor measuring range Lowest
lower (LRL) upper (URL) Silicone oil/
calibratable span
[bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar
MWP OPL Vacuum resistance
1)
Inert oil
(psi
abs
400 mbar (6 psi) –0.4 (–6) +0.4 (+6) 0.005 (0.075) 4 (60) 6 (90)
1 bar (15 psi) –1 (–15) +1 (+15) 0.01 (0.15) 6.7 (100) 10 (150) 1H
2 bar (30 psi) –1 (–15) +2 (+30) 0.02 (0.3) 13.3 (200) 20 (300) 1K
4 bar (60 psi) –1 (–15) +4 (+60) 0.04 (0.6) 18.7 (280.5) 28 (420) 1M
10 bar (150 psi) –1 (–15) +10 (+150) 0.1 (1.5) 26.7 (400.5) 40 (600) 1P
0.01/0.04 (0.15/0.6)
40 bar (600 psi) –1 (–15) +40 (+600) 0.4 (6) 100 (1500) 160 (2400) 1S
100 bar (1 500 psi) –1 (–15) +100 (+1500) 1.0 (15) 100 (1500) 400 (6000)
4)
400 bar (6 000 psi) –1 (–15) +400 (+6000) 4.0 (60) 400 (6000) 600 (9000) 1W
700 bar (10 500 psi)
5)
–1 (–15) +700 (+10500) 7.0 (105) 700 (10500) 1050 (15750) 1X
1) Turn down > 100:1 on request or can be set on device
2) The vacuum resistance applies for the measuring cell under reference operating conditions. A ceramic process isolating diaphragm is recommended for applications in the limit range. For type PMP75, the pressure and temperature application limits of the selected filling oil must also be observed →  115.
3) Product Configurator, order code for "Sensor range; sensor over pressure limit"
4) If the option "JN" is ordered in the order code for "Test, certificate", then the OPL is 160 bar (2 400 psi).
5) PMP71 only, PMP75 on request
Option
1F
1U
3)
PMP71 and PMP75 – metal process isolating diaphragm for absolute pressure
Sensor Maximum sensor measuring range
lower (LRL) upper (URL) Silicone oil/
[bar
(psi
abs
)] [bar
abs
abs
(psi
1)
Lowest calibratable
2)
span
)] [bar (psi)] [bar
abs
MWP OPL Vacuum resistance
Inert oil
(psi
abs
)] [bar
abs
abs
(psi
)] [bar
abs
abs
(psi
400 mbar (6 psi) 0 +0.4 (+6) 0.005 (0.075) 4 (60) 6 (90)
1 bar (15 psi) 0 +1 (+15) 0.01 (0.15) 6.7 (100) 10 (150) 2H
2 bar (30 psi) 0 +2 (+30) 0.02 (0.3) 13.3 (200) 20 (300) 2K
4 bar (60 psi) 0 +4 (+60) 0.04 (0.6) 18.7 (280.5) 28 (420) 2M
10 bar (150 psi) 0 +10 (+150) 0.1 (1.5) 26.7 (400.5) 40 (600) 2P
0.01/0.04 (0.15/0.6)
40 bar (600 psi) 0 +40 (+600) 0.4 (6) 100 (1500) 160 (2400) 2S
100 bar (1 500 psi) 0 +100 (+1500) 1.0 (15) 100 (1500) 400 (6000)
5)
400 bar (6 000 psi) 0 +400 (+6000) 4.0 (60) 400 (6000) 600 (9000) 2W
700 bar (10 500 psi)
1) PMP75: Within the sensor measuring range, the minimum upper range value of 80 mbar
6)
0 +700 (+10500) 7.0 (105) 700 (10500) 1050 (15750) 2X
(1.16 psi
abs
) must be observed.
abs
2) Turn down > 100:1 on request or can be set on device
3) The vacuum resistance applies for the measuring cell under reference operating conditions. A ceramic process isolating diaphragm is recommended for applications in the limit range. For type PMP75, the pressure and temperature application limits of the selected filling oil must also be observed →  115.
4) Product Configurator, order code for "Sensor range; sensor over pressure limit"
5) If the option "JN" is ordered in the order code for "Test, certificate", then the OPL is 160 bar (2 400 psi).
6) PMP71 only, PMP75 on request
abs
3)
)]
Option
2F
2U
4)
14 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
PMP71 - metallic process isolating diaphragms for absolute pressure with MID parts certificate
Sensor Maximum sensor
measuring range
[bar (psi)]
lower (LRL)
[bar (psi
abs
abs
upper
3)
(URL)
[bar (psi
abs
abs
)]
)]
10 (150) 0 +10 (150) 0.5 (7.5) 0.5 (7.5) 26.7
Min. WP for gas applications suitable for custody transfer measurement
4)
Min. WP for liquid applications suitable for custody transfer measurement
[bar (psi)] [bar (psi)] [bar
MWP OPL Vacuum
resistance
Silicone oil/ Inert oil
(psi
abs
abs
[bar (psi
abs
abs
)]
[bar (psi)]
)]
40 (600) 0.01/0.04
(400.5)
(0.15/1)
50 (750) 0 +50 (750) 10 (150) 2.5 (37.5) 100 (1500) 400 (6000) 0.01/0.04
1)
Option
MP
MT
2)
(0.15/1)
100 (1500)
0 +100 (1500) 5 (75) 5 (75) 100 (1500) 400 (6000) 0.01/0.04
(0.15/1)
MU
1) The vacuum resistance applies to the measuring cell under reference operating conditions
2) Product Configurator, order code for "Sensor range; sensor over pressure limit"
3) By default, the device is set to a lower sensor measuring range of 0 bar. Please specify when ordering if the lower sensor measuring range is to be set to a different default value.
4) Max. WP (working pressure) for gas and liquid applications suitable for calibration to regulatory standards
Endress+Hauser 15

Output

on on
off off
damp.
damp.
Display Display
Sensor Sensor
HART HART
R R
FIELD COMMUNICATION PROTOCOL FIELD COMMUNICATION PROTOCOL
SW /min
SW /min
E
+
E
+
Cerabar S PMC71, PMP71, PMP75

Output signal

• 4 to 20 mA with superimposed digital communication protocol HART, 2-wire
• 1-5V DC, 3-wire
• Digital communication signal PROFIBUS PA (Profile 3.0), 2-wire
• Signal coding: Manchester Bus Powered (MBP): Manchester II
• Transmission rate: 31.25 KBit/s voltage mode
• Digital communication signal FOUNDATION Fieldbus, 2-wire
• Signal coding: Manchester Bus Powered (MBP): Manchester II
• Transmission rate: 31.25 KBit/s voltage mode
Output Internal + LCD External + LCD Internal
1)
Option
4 to 20mA HART B A C
4 to 20mA HART, Li=0 E D F
1-5V DC H G -
PROFIBUS PA N M O
FOUNDATION Fieldbus Q P R
1) Product Configurator, order code for "Display, operation: "
A0021280

Signal range 4 to 20 mA

3.8 mA to 20.5 mA
1-5V DC
0.95 to 5.125 V

Signal on alarm 4 to 20 mA HART

As per NAMUR NE43.
• Max. alarm: can be set from 21 to 23 mA (factory setting: 22 mA)
• Hold measured value: last measured value is held
• Min. alarm: 3.6 mA
1-5V DC
• Max. alarm: can be set from 5.25 to 5.75 V
• Min. Alarm: 0.9 V
PROFIBUS PA
As per NAMUR NE43.
Can be set in the Analog Input Block.
Options:
• Last Valid Out Value (factory setting)
• Fail Safe Value
• Status bad
FOUNDATION Fieldbus
As per NAMUR NE43.
Can be set in the Analog Input Block.
16 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
U – 11.5 V
U – 12 V
23 mA
23 mA
[ ]W
[ ]W
30
30
20
20
11.5
12
404045
45
1239
1217
1456
1434
804
782
369
347
Test
£
£
B
B
U – 10.5 V
U – 11 V
R
R
L
L
max
max
23 mA
23 mA
£
£
30
30
20
20
10.5
11
U
U
U
U
[V]
[V]
[V]
[V]
404045
45
1282
1260
1500
1478
847
826
413
391
[ ]W
[ ]W
R
R
L
L
max
max
Test
4
4
A
A
1
2
3
1
2
3
R
R
L
L
max
max
4
4
R
R
L
L
max
max
Options:
• Last Good Value
• Fail Safe Value (factory setting)
• Wrong Value

Load 4 to 20 mA HART

In order to guarantee sufficient terminal voltage in two-wire devices, a maximum load resistance R (including line resistance) must not be exceeded depending on the supply voltage U0 of the supply unit. In the following load diagrams, observe the position of the jumper and the explosion protection:
A0020467
A Jumper for 4 to 20 mA test signal set to "Non-test" position B Jumper for 4 to 20 mA test signal set to "Test" position 1 Power supply 10.5 (11.5) to 30 V DC for 1/2 G, 1 GD, 1/2 GD, FM IS, CSA IS, IECEx ia, NEPSI Ex ia 2 Power supply 10.5 (11.5) to 45 V DC for devices for non-hazardous areas, 1/2 D, 1/3 D, 2 G Ex d, 3 G Ex nA,
FM XP, FM DIP, FM NI, CSA XP, CSA dust ignition-proof, NEPSI Ex d 3 Power supply 11 (12) to 45 V DC for PMC71, Ex d[ia], NEPSI Ex d[ia] 4 R
Lmax
U Supply voltage
When operating via a handheld terminal or via a PC with an operating program, a minimum communication resistor of 250 Ω must be taken into account.
maximum load resistance
1-5V DC
The load must be at least 100 kΩ.
Endress+Hauser 17
Cerabar S PMC71, PMP71, PMP75

Damping

Alarm current

Firmware version

A damping affects all outputs (output signal, display):
• via local display, handheld terminal or PC (handheld terminal or PC not for 1-5V DC) with operating program, continuous from 0 to 999 s
• Also for HART and PROFIBUS PA: Via DIP switch on the electronic insert, switch position "on" = set value and "off"
• 1-5V DC: via DIP switch on electronic insert switch position "on" = set value and "off"
• Factory setting: 2 s
Designation Option
Min alarm current J
HART burst mode PV J
Min alarm current + HART burst mode PV J
1) Product Configurator, order code for "Additional options 1" and "Additional options 2"
Designation Option
02.20.zz, HART 7, DevRev22 72
02.11.zz, HART 5, DevRev21 73
04.00.zz, FF, DevRev07 74
04.01.zz, PROFIBUS PA, DevRev03 75
02.10.zz, HART 5, DevRev21 76
03.00.zz, FF, DevRev06 77
04.00.zz, PROFIBUS PA 78
02.30.zz, HART 7 71
1)
1)

Protocol-specific data HART

1) Product Configurator, order code for "Firmware version"
Manufacturer ID 17 (11 hex)
Device type ID 24 (18 hex)
Device revision • 21 (15 hex) - SW version 02.1y.zz - HART specification 5
• 22 (16 hex) - SW version 02.2y.zz - HART specification 7
HART specification • 5
• 7
DD revision • 4 (Russian in language selection) for device revision 21
• 3 (Dutch in language selection) for device revision 21
• 1 for device revision 22
Device description files (DTM, DD) Information and files under:
www.endress.com
www.fieldcommgroup.org
HART load Min. 250 Ω
18 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
HART device variables The measured values are assigned to the device variables as follows:
Supported functions • Burst mode
Measured values for PV (primary variable)
• Pressure
• Level
• Tank content
Measured values for SV, TV (second and third variable)
Pressure
Measured values for QV (fourth variable)
Temperature
• Additional transmitter status
• Device locking
• Alternative measuring modes

Wireless HART data

Protocol-specific data PROFIBUS PA

Minimum starting voltage 11.5 V (default) or 10.5 V if jumper not set to "Test" position
Start-up current 12 mA
Starting time 10 s
Minimum operating voltage 11.5 V (default) or 10.5 V if jumper not set to "Test" position
Multidrop current 4 mA
Time for connection setup 1 s
1) Or higher if operating near the ambient temperature limits (–40 to +85 °C (–40 to +185))
Manufacturer ID 17 (11 hex)
Identification number 1541 hex
Profile version 3.0
• SW version 03.00.zz
• SW version 04.00.zz
3.02 SW version 04.01.zz ( device revision 3) Compatibility with SW version 03.00.zz and higher.
GSD revision • 4 (SW version 3.00.zz and 4.00.zz)
• 5 (device revision 3)
DD revision • 1 (SW version 3.00.zz and 4.00.zz)
• 1 (device revision 3)
GSD file Information and files under:
DD files
Output values Measured values for PV (via Analog Input Function Block)
www.endress.com
www.profibus.org
• Pressure
• Level
• Tank content
Measured values for SV
• Pressure
• Temperature
1)
1)
Endress+Hauser 19
Cerabar S PMC71, PMP71, PMP75
Input values Input value sent from PLC, can be shown on display
Supported functions • Identification & maintenance, simplest device identifier on the
control system and nameplate
• Condensed status (only with Profile Version 3.02)
• Automatic ID number adjustment and switchable to the following ID numbers (only with Profile Version 3.02):
• 9700: Profile-specific transmitter identification number with the
"Classic" or "Condensed" status.
• 1501: Compatibility mode for the old Cerabar S generation
(PMC731, PMP731, PMC631, PMP635).
• 1541: Identification number of the new Cerabar S generation
(PMC71, PMP71, PMP75).
• Device locking: The device can be locked by hardware or software.

Protocol-specific data FOUNDATION Fieldbus

Manufacturer ID 452B48 hex
Device type 1007 hex
Device revision • 6 - SW version 03.00.zz
• 7 - SW version 04.00.zz (FF-912)
DD revision • 3 (device revision 6)
• 2 (device revision 7)
CFF revision • 4 (device revision 6)
• 1 (device revision 7)
DD files Information and files under:
CFF files
Device tester version (ITK version) • 5.0 (device revision 6)
Number of ITK test campaign • IT054600 (Device Revision 6)
Link-Master (LAS) capable Yes
Choice of "Link Master" and "Basic Device"
Node address Factory setting: 247 (F7 hex)
Supported functions Field diagnostics profile (only with FF912)
Number of VCRs • 44 (device revision 6)
Number of Link Objects in VFD 50
www.endress.com
www.fieldcommgroup.org
• 6.01 (device revision 7)
• IT085500 (Device Revision 7)
Yes; Factory setting: Basic Device
The following methods are supported:
• Reboot
• Configure error as warning or alarm
• HistoROM
• Peakhold
• Alarm info
• Sensor trim
• 24 (device revision 7)
20 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
Virtual communication references (VCRs)
Permanent Entries 44 1
Client VCRs 0 0
Server VCRs 5 10
Source VCRs 8 43
Sink VCRs 0 0
Subscriber VCRs 12 43
Publisher VCRs 19 43
Link settings
Slot time 4 4
Min. Inter PDU delay 12 10
Max. response delay 10 10
Device revision 6 Device revision 7
Device revision 6 Device revision 7
Transducer Blocks
Block Contents Output values
TRD1 Block Contains all parameters related to
the measurement
Service Block Contains service information • Pressure after damping (channel 3)
Diagnostic block Contains diagnostic information Error code via DI channels (channel 0 to 16)
Display block Contains parameters to configure
the onsite display
• Pressure or level (channel 1)
• Process temperature (channel 2)
• Pressure peakhold indicator (channel 4)
• Counter for max. pressure transgressions (channel
5)
No output values
Endress+Hauser 21
Function blocks
Cerabar S PMC71, PMP71, PMP75
Block Contents Number
Blocks
Resource Block The Resource Block contains all the data that uniquely identify the
device. It is an electronic version of a nameplate of the device.
Analog Input Block 1 Analog Input Block 2
Digital Input Block
Digital Output Block
PID Block This block is used as a proportional-integral-derivative controller and
Arithmetic Block
Input Selector Block
Signal Characterizer Block
Integrator Block The Integrator Block integrates a variable as a function of the time or
Analog Alarm Block
The AI Block receives the measuring data from the Sensor Block, (selectable via a channel number) and makes the data available to other function blocks at its output. Enhancement: Digital outputs for process alarms, fail safe mode
This block contains the discrete data of the Diagnose Block (selectable via a channel number 0 to 16) and provides them for other blocks at the output.
This block converts the discrete input and thus initiates an action (selectable via a channel number) in the DP Flow Block or in the Service Block. Channel 1 resets the counter for max. pressure transgressions.
can be used universally for closed-loop-control in the field. It enables cascade mode and feedforward control. Input IN can be indicated on the display. The selection is performed in the Display Block (DISPLAY_MAIN_LINE_CONTENT).
This block is designed to permit simple use of popular measurement math functions. The user does not have to know how to write equations. The math algorithm is selected by name, chosen by the user for the function to be performed.
The Input Selector Block facilitates the selection of up to four inputs and generates an output based on the configured action. This block normally receives its inputs from AI Blocks. The block enables the selection of maximum, minimum, average and ‘first good’ values. Inputs IN1 to IN4 can be shown on the display. The selection is performed in the Display Block (DISPLAY_MAIN_LINE_CONTENT).
The Signal Characterizer Block has two sections, each with an output value that is a non-linear function of the input value. The non-linear function is generated by a single look-up table with 21 arbitrary x-y pairs.
accumulates the counts from a Pulse Input Block. The block may be used as a totalizer that counts up until reset or as a batch totalizer that has a setpoint, where the integrated or accumulated value is compared to pre-trip and trip settings, generating a binary signal when the setpoint is reached.
This block contains all process alarm conditions (working like a comparator) and represents them at the output.
1 enhanced enhanced
2 45 ms 45 ms
1 40 ms 30 ms standard enhanced
1 60 ms 40 ms standard enhanced
1 120 ms 70 ms standard enhanced
1 50 ms 40 ms standard enhanced
1 35 ms 35 ms standard enhanced
1 30 ms 40 ms standard enhanced
1 35 ms 40 ms standard enhanced
1 35 ms 35 ms standard enhanced
Execution time Functionality
Device Revision 6
Device Revision 7
(without trend and alarm reports)
Device Revision 6
enhanced enhanced
Device Revision 7
Additional function block information:
Instantiate Function Block JA JA
Number of additional instantiatable function blocks 11 5
22 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
4... 20mA
Test
Test
Test
4... 20mA Test
1
8
6
7
2
3
4
5
1
6
7
2
3
4
5
POWER
Vout

Power supply

WARNING
L
Electrical safety is compromised by an incorrect connection!
When using the measuring device in hazardous areas, the relevant national standards and
regulations as well as the Safety Instructions or Installation or Control Drawings must be observed →  129. All explosion protection data are given in separate documentation which is available upon
request. The Ex documentation is supplied as standard with all Ex-systems →  129. Devices with integrated overvoltage protection must be grounded →  28.
Protective circuits against reverse polarity, HF influences and overvoltage peaks are integrated.

Terminal assignment 4 to 20 mA HART

A0019989
1 Housing 2 Supply voltage 3 4 to 20 mA 4 Devices with integrated overvoltage protection are labeled "OVP" (overvoltage protection) here. 5 External ground terminal 6 4 to 20 mA test signal between positive and test terminal 7 Internal ground terminal 8 Jumper for 4 to 20 mA test signal →  24
1-5V DC
A0031676
1 Housing 2 Supply voltage 3 1-5V DC 4 Overvoltage protection (OVP) marking 5 External ground terminal 6 Terminals 7 Internal ground terminal
Endress+Hauser 23
PROFIBUS PA and FOUNDATION Fieldbus
1
4
5
2
3
Test
Test
1 Housing 2 Supply voltage 3 Devices with integrated overvoltage protection are labeled "OVP" (overvoltage protection) here. 4 External ground terminal 5 Internal ground terminal

Supply voltage 4 to 20 mA HART

Cerabar S PMC71, PMP71, PMP75
A0020158
Electronic version Jumper for 4 to 20 mA test signal in
"Test" position (delivery status)
Version for non­hazardous area
Intrinsically safe 11.5 to 30 V DC 10.5 to 30 V DC
• Other types of protection
• Devices without certificate
11.5 to 45 V DC 10.5 to 45 V DC
11.5 to 45 V DC (versions with 35 V DC plug-in connection)
Jumper for 4 to 20 mA test signal in "Non-test" position
10.5 to 45 V DC (versions with 35 V DC plug-in connection)
Measuring a 4 to 20 mA test signal
Jumper position for test signal
Description
• Measurement of 4-20 mA test signal via the positive and test terminal: Possible. (Thus, the output current can be measured without interruption via the diode.)
• As-delivered state
• Minimum supply voltage: 11.5 V DC
A0019992
• Measurement of 4-20 mA test signal via positive and test terminal: Not possible.
• Minimum supply voltage: 10.5 V DC
A0019993
1-5V DC
• Non-hazardous area: 9 to 35 V DC
• Ex-d: 9 to 35 V DC
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC
• Ex ia: 10.5 to 30 V DC
24 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
Han7D
+ –
+
A B
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
• Ex ia: 10.5 to 30 V DC

Current consumption

• 1-5V DC: 9 V = 1.8 mA 35 V = 0.8 mA
• PROFIBUS PA: 13 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15.5 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Electrical connection PROFIBUS PA

The digital communication signal is transmitted to the bus via a two-wire connection. The bus also provides the power supply. For further information on the network structure and grounding and for further bus system components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the PNO Guideline.
FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a two-wire connection. The bus also provides the power supply. For further information on the network structure and grounding and for further bus system components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.

Terminals

• Supply voltage and internal ground terminal: 0.5 to 2.5 mm2 (20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm2 (20 to 12 AWG)

Cable entries

Approval Cable gland Clamping range
Standard, II 1/2 G Ex ia, IS Plastic M20x1.5 5 to 10 mm (0.2 to 0.39 in)
ATEX II 1/2 D, II 1/3 D, II 1/2 GD Ex ia, II 1 GD Ex ia, II 3 G Ex nA
Metal M20x1.5 (Ex e) 7 to 10.5 mm (0.28 to 0.41 in)

Device plugs Connection of devices with Harting plug Han7D

1-5V DC
The cable entries have a 1/2 FNPT thread. The connection on the customer's side is protected by a plastic connector. A cable gland is not envisaged.
For additional technical data, see section on housing →  54
A Electrical connection for devices with Harting plug Han7D B View of the plug-in connection on the device
Material: CuZn, contacts for plug-in jack and connector are gold-plated
A0019990
Endress+Hauser 25
Cable version connection
+
+
PE
1 2 3 4
+
+
PE
142 3
2
1
34
1 rd = red 2 bk = black 3 gnye = green 4 4 to 20 mA
Connection via cable version 1-5V DC
Cerabar S PMC71, PMP71, PMP75
A0019991
1 rd = red 2 bk = black 3 gnye = green 4 1-5V DC
Connection of devices with M12 plug
1 Signal + 2 Not assigned 3 Signal – 4 Ground
Endress+Hauser offers the following accessories for devices with an M12 plug:
Plug-in jack M 12x1, straight
• Material: body PA; coupling nut CuZn, nickel-plated
• Degree of protection (fully locked): IP67
• Order number: 52006263 Plug-in jack M 12x1, elbowed
• Material: body PBT/PA; coupling nut GD-Zn, nickel-plated
• Degree of protection (fully locked): IP67
• Order number: 71114212
Cable 4x0.34 mm2 (20 AWG) with M12 socket, elbowed, screw plug, length 5 m (16 ft)
• Material: body PUR; coupling nut CuSn/Ni; cable PVC
• Degree of protection (fully locked): IP67
• Order number: 52010285
A0032269
A0011175
26 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75
4
2
3
1
Connection of devices with 7/8" plug
1 Signal – 2 Signal + 3 Shielding 4 Not assigned
External thread: 7/8 - 16 UNC
• Material: 316L (1.4401)
• Degree of protection: IP68

Cable specification HART

• Endress+Hauser recommends using shielded, twisted-pair two-wire cables.
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) depending on the cable entry used →  25
A0011176
1-5V DC
• Endress+Hauser recommends using a shielded cable.
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) depending on the cable entry used →  25
Maximum cable length
The following table shows the tolerance of the voltage output for a representative cable with a length of up to 100 m (328 ft), a resistance of 18 Ohm/km and specification 18 AWG (cable cross­section 0.8 mm2).
Tolerance of voltage output at cable end Length
0.5 mV 25 m (82 ft)
1 mV 50 m (164 ft)
1.5 mV 75 m (246 ft)
2 mV 100 m (328 ft)
PROFIBUS PA
Use a twisted, shielded twin-core cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092 PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Use a twisted, shielded twin-core cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions BA00013S "FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).

Start-up current

Residual ripple

12 mA
Without influence on 4 to 20 mA signal up to ±5% residual ripple within the permitted voltage range [according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)].
Endress+Hauser 27
Cerabar S PMC71, PMP71, PMP75

Overvoltage protection (optionally for HART, PROFIBUS PA and FOUNDATION Fieldbus)

Influence of power supply

• Overvoltage protection:
• Nominal functioning DC voltage: 600 V
• Nominal discharge current: 10 kA
• Surge current check î = 20 kA satisfied as per DIN EN 60079-14: 8/20 μs
• Arrester AC current check I = 10 A satisfied Ordering information: Product Configurator, order code for "Additional options 1" or Additional
options 2", option "M"
NOTICE
Device could be destroyed!
Devices with integrated overvoltage protection must be grounded.
≤0.0006 % of URL/1 V
28 Endress+Hauser
Cerabar S PMC71, PMP71, PMP75

Performance characteristics for measuring devices with ceramic process isolating diaphragm

Response time HART

• Acyclic: min. 330 ms, typically 590 ms (depending on command # and number of preambles)
• Cyclic (burst): min. 160 ms, typically 350 ms (depending on command # and number of preambles)
PROFIBUS PA
• Acyclic: approx. 60 ms to 70 ms (depending on Min. Slave Interval)
• Cyclic: approx. 10 ms to 13 ms (depending on Min. Slave Interval)
FOUNDATION Fieldbus
• Acyclic: typically 100 ms (for standard bus parameter settings)
• Cyclic: max. 20 ms (for standard bus parameter settings)

Reference operating conditions

Maximum measured error (total performance)

• As per IEC 62828-2 / IEC 60770
• Ambient temperature TA = constant, in the range +21 to +33 °C (+70 to +91 °F)
Humidity j = constant, in the range: 5 to 80 % RH ± 5 %
• Ambient pressure pA = constant, in the range: 860 to 1 060 mbar (12.47 to 15.37 psi)
• Position of the measuring cell: horizontal ±1°
• Input of LOW SENSOR TRIM and HIGH SENSOR TRIM for lower range value and upper range value
• Zero based span
• Membrane material PMC71: Al2O3 aluminum oxide ceramic FDA, ultrapure 99.9 %
• Supply voltage: 24 V DC ±3 V DC
• Load with HART: 250 Ω
• Turn down (TD) = URL/|URV - LRV|
The performance characteristics refer to the accuracy of the measuring device. The factors influencing accuracy can be divided into two groups
• Total performance of measuring device
• Installation factors
All performance characteristics are in conformance with ≥ ± 3 sigma.
The total performance of the measuring device comprises the reference accuracy and the ambient temperature effect and is calculated using the following formula:
Total performance = ± √ ( (E1)² + (E2)²)
E1 = Reference accuracy
E2 = Temperature effect per ±28 °C (50 °F)
(corresponds to the range from –3 to +53 °C (+27 to +127 °F))
Calculation of E2:
E2 = E2M + E2
E2M = Main temperature error
E2E = Electronics error
The values refer to the calibrated span
E
Endress+Hauser 29
Cerabar S PMC71, PMP71, PMP75
Calculation of the total performance with the Endress+Hauser Applicator
Detailed measured errors, such as for other temperature ranges or the high-temperature version of the measuring device, for example, can be calculated with the Applicator "Sizing Pressure Performance".
A0038927
Reference accuracy [E1]
Reference accuracy comprises the non-linearity [IEC 62828-1 / DIN EN 61298-2] including the hysteresis [IEC 62828-1 / DIN EN 61298-2] and the non-repeatability [IEC 62828-1 / DIN EN 61298-2] in accordance with the limit point method as per [IEC 62828-1 / DIN EN 60770-2]. Reference accuracy for standard up to TD 100:1, for platinum up to TD 5:1.
100 mbar (1.5 psi) sensor
• Standard: TD ≤ 10:1 = ±0.075 %; TD > 10:1 = ±0.0075 % · TD
• Platinum: TD 1:1 = ±0.05 %; TD > 1:1 = ±0.075 % 250 mbar (3.75 psi) sensor
• Standard: TD ≤ 10:1 = ±0.075 %; TD > 10:1 = ±0.0075 % · TD
• Platinum: TD ≥ 1:1 = ±0.05 % 400 mbar (6 psi) and 1 bar (15 psi) sensor
• Standard: TD ≤ 10:1 = ±0.05 %; TD > 10:1 = ±0.005 % · TD
• Platinum: TD ≥ 1:1 = ±0.035 % 2 bar (30 psi) sensor
• Standard: TD ≤ 10:1 = ±0.05 %; TD > 10:1 = ±0.005 % · TD
• Platinum: TD 1:1 = ±0.025 %; TD ≥ 1:1 = ±0.035 % 4 bar (60 psi) sensor
• Standard: TD ≤ 10:1 = ±0.05 %; TD > 10:1 = ±0.005 % · TD
• Platinum: TD ≥ 1:1 = ±0.025% 10 bar (150 psi) and 40 bar (600 psi) sensor
• Standard: TD ≤ 10:1 = ±0.05 %; TD > 10:1 = ±0.005 % · TD
• Platinum: TD ≥ 1:1 = ±0.035 %
30 Endress+Hauser
Loading...
+ 102 hidden pages