Endress+Hauser PMP55 Specifications

TI00436P/00/EN/29.20 71475825 2020-04-01
Products
Solutions Services
Technical Information
Cerabar M PMC51, PMP51, PMP55
Process pressure measurement
Pressure transmitter with ceramic and metal sensors
Application
The device is used for the following measuring tasks:
• Absolute pressure and gauge pressure measurement in gases, steams or liquids in all areas of process engineering and process measurement technology
• Level, volume or mass measurement in liquids
• High process temperature
150 °C (302 °F)
• with diaphragm seals up to 400 °C (752 °F)
• High pressure up to 400 bar (6 000 psi)
• International usage thanks to a wide range of approvals
Your benefits
• Very good reproducibility and long-term stability
• High reference accuracy up to ±0.10 % as PLATINUM version: ±0.075 %
• Turn down up to 100:1
• Uniform platform for differential pressure, hydrostatics and pressure (Deltabar M – Deltapilot M – Cerabar M)
• Simple, fast commissioning through a user interface designed for real-world applications
• Used for process pressure monitoring up to SIL 2, certified to IEC 61508 Edition
2.0 and IEC 61511 by TÜV NORD
• The patented TempC Membrane for the diaphragm seal reduces measured errors caused by environmental and process temperature influences to a minimum
• ASME-BPE-compliant device versions

Table of contents

Cerabar M PMC51, PMP51, PMP55
Document information ....................... 4
Document function ............................ 4
Symbols used ................................ 4
Documentation ............................... 5
Terms and abbreviations ........................ 6
Turn down calculation .......................... 7
Function and system design ................... 8
Device selection .............................. 8
Measuring principle ........................... 10
Level measurement (level, volume and mass) .......... 11
Electrical differential pressure measurement with gauge
pressure sensors ............................. 11
Communication protocol ........................ 12
Input .................................... 13
Measured variable ............................ 13
Measuring range ............................. 13
Output .................................. 15
Output signal ............................... 15
Signal range 4 to 20 mA ........................ 15
Signal on alarm .............................. 15
Load - 4 to 20 mA Analog 4...20 mA HART ........... 15
Damping .................................. 16
Firmware version ............................ 16
Protocol-specific data HART ..................... 16
Wireless HART data ........................... 16
Protocol-specific data PROFIBUS PA ................ 16
Protocol-specific data FOUNDATION Fieldbus .......... 17
Power supply ............................. 20
Terminal assignment .......................... 20
Supply voltage .............................. 20
Current consumption .......................... 21
Electrical connection .......................... 21
Terminals ................................. 21
Cable entry ................................. 21
Device plugs ................................ 22
Cable specification ............................ 23
Start-up current ............................. 24
Residual ripple .............................. 24
Influence of power supply ....................... 24
Overvoltage protection (optional) .................. 24
Performance characteristics for measuring devices with ceramic process isolating
diaphragm ............................... 25
Response time .............................. 25
Reference operating conditions ................... 25
Maximum measured error (total performance) ......... 25
Resolution ................................. 27
Total error ................................. 28
Long-term stability ........................... 28
Response time T63 and T90 ..................... 29
Installation factors ............................ 31
Performance characteristics for measuring devices with metal process isolating diaphragm .. 32
Response time .............................. 32
Reference operating conditions ................... 32
Maximum measured error (total performance) ......... 32
Resolution ................................. 35
Total error ................................. 35
Long-term stability ........................... 36
Response time T63 and T90 ..................... 36
Installation factors ............................ 38
Installation ............................... 39
General installation instructions ................... 39
Measuring arrangement for devices without diaphragm
seal – PMC51, PMP51 ......................... 39
Measuring arrangement for devices with diaphragm seal –
PMP55 ................................... 39
Wall and pipe mounting, transmitter (optional) ........ 40
Wall and pipe-mounting manifold (optional) .......... 40
"Separate housing" version ....................... 41
Oxygen applications ........................... 42
PWIS cleaning .............................. 42
Ultrapure gas applications (PMC51 und PMP51) ........ 42
Applications with hydrogen ...................... 42
Environment .............................. 43
Ambient temperature range ..................... 43
Storage temperature range ...................... 43
Climate class ............................... 43
Degree of protection .......................... 43
Vibration resistance ........................... 43
Electromagnetic compatibility .................... 44
Operation in very corrosive environment ............. 44
Process .................................. 45
Process temperature range PMC51 ................. 45
Process temperature limits ...................... 45
Process temperature limits of flexible capillary armoring:
PMP55 ................................... 46
Pressure specifications ......................... 47
Mechanical construction .................... 48
Device height ............................... 48
F31 housing, aluminum ........................ 48
F15 housing, stainless steel (hygienic) .............. 49
PMC51: process connections with internal process
isolating diaphragm ........................... 50
PMC51: process connections with internal process
isolating diaphragm ........................... 52
PMC51: process connections with internal process
isolating diaphragm - height H ................... 52
PMC51: process connections with flush-mounted process
isolating diaphragm ........................... 53
PMC51: process connections with flush-mounted process
isolating diaphragm ........................... 54
PMC51: process connections with flush-mounted process
isolating diaphragm - height H ................... 54
2 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
PMC51: process connections with flush-mounted process
isolating diaphragm ........................... 55
PMC51: process connections with flush-mounted process
isolating diaphragm ........................... 58
PMC51: process connections with flush-mounted process
isolating diaphragm - height H ................... 58
PMC51: hygienic process connections with flush mount
process isolating diaphragm ..................... 59
PMP51: process connections with internal process
isolating diaphragm ........................... 64
PMP51: process connections with internal process
isolating diaphragm ........................... 65
PMP51: process connections with flush-mounted process
isolating diaphragm ........................... 66
ANSI threaded connection ...................... 68
PMP51: process connections with flush-mounted process
isolating diaphragm ........................... 69
PMP51: process connections with flush-mounted process
isolating diaphragm ........................... 70
PMP51: process connections with flush-mounted process
isolating diaphragm ........................... 71
PMP51: hygienic process connections with flush mount
process isolating diaphragm ..................... 72
Valve manifold DA63M- (optional) ................. 76
PMP51: process connections ..................... 77
PMP55 basic device - examples ................... 78
Process connections for PMP55 with flush-mounted
process isolating diaphragm ..................... 79
PMP55: process connections with flush-mounted process
isolating diaphragm ........................... 80
PMP55: process connections with flush-mounted process
isolating diaphragm ........................... 81
PMP55: process connections with flush-mounted process
isolating diaphragm ........................... 82
PMP55: hygienic process connections with flushmounted
process isolating diaphragm ..................... 83
PMP55: hygienic process connections with flush mount
process isolating diaphragm ..................... 84
PMP55: process connections with flush-mounted process
isolating diaphragm ........................... 90
PMP55: process connections with flush-mounted process
isolating diaphragm ........................... 92
PMP55 process connections ..................... 95
Wall and pipe mounting with "Separate housing" version ... 98
Reduction in installation height ................... 99
Weight ................................... 99
Flushing rings .............................. 100
Materials not in contact with process .............. 101
Materials in contact with the process .............. 104
Seals .................................... 105
Fill fluid .................................. 105
Operability .............................. 107
Operating concept ........................... 107
Local operation ............................. 107
Operating languages ......................... 110
Remote operation ........................... 111
System integration (Except analog electronics) ........ 112
Diaphragm seal filling oils ...................... 115
Operating temperature range .................... 116
Cleaning instructions ......................... 116
Installation instructions ....................... 116
Vacuum applications ......................... 117
Certificates and approvals .................. 119
CE mark .................................. 119
RoHS .................................... 119
RCM-Tick marking ........................... 119
Ex approvals ............................... 119
EAC conformity ............................. 119
Suitable for hygiene applications ................. 119
Certificate of current Good Manufacturing Practices
(cGMP) .................................. 120
Certificate of Compliance ASME BPE 2012 ........... 120
Functional safety SIL ......................... 120
CRN approvals ............................. 120
Other standards and guidelines .................. 120
AD2000 .................................. 120
Pressure Equipment Directive 2014/68/EU (PED) ...... 121
Manufacturer declaration ...................... 121
Marine approval ............................ 121
Drinking water approval ....................... 122
Classification of process sealing between electrical systems and (flammable or combustible) process fluids in
accordance with ANSI/ ISA 12.27.01 .............. 122
Inspection certificate ......................... 122
Calibration; unit ............................ 122
Calibration ................................ 123
Service ................................... 123
Ordering information ...................... 124
Special device versions ........................ 124
Scope of delivery ............................ 124
Measuring point (TAG) ........................ 124
Configuration data sheet (HART, PROFIBUS PA,
FOUNDATION Fieldbus electronics) ............... 124
Configuration data sheet (Analog electronics) ......... 127
Additional documentation .................. 128
Field of Activities ............................ 128
Technical Information ........................ 128
Special Documentation ........................ 128
Operating Instructions ........................ 128
Brief operating instruction ..................... 128
Functional safety manual (SIL) ................... 128
Safety instructions ........................... 128
Accessories .............................. 131
Manifolds ................................ 131
Additional mechanical accessories ................ 131
Welding necks and weld-in adapters ............... 131
Mounting bracket for wall and pipe mounting ......... 132
M12 connector ............................. 132
Service-specific accessories ..................... 132
Planning instructions for diaphragm seal
systems ................................. 113
Applications ............................... 113
Function and design .......................... 114
Registered trademarks ..................... 132
HART® .................................. 132
PROFIBUS® ............................... 132
FOUNDATIONTMFieldbus ...................... 132
Endress+Hauser 3

Document information

DANGER
WARNING
CAUTION
NOTICE
A
,…,
1.
2.
3.
Cerabar M PMC51, PMP51, PMP55

Document function

The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.

Symbols used Safety symbols

Symbol Meaning
Electrical symbols
Symbol Meaning Symbol Meaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in seriousor fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in seriousor fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minoror medium injury.
NOTICE!
This symbol contains information on procedures and other facts which do not result in personalinjury.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Symbols for certain types of information
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
Symbol Meaning
1, 2, 3 ... Item numbers
Series of steps
4 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
A-A, B-B, C-C, ... Sections
Symbol Meaning
A, B, C, ... Views

Documentation

See chapter "Additional documentation" →  128
The document types listed are available: In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download
Endress+Hauser 5

Terms and abbreviations

URL OPLMWP
LRL
0
p
LRV
URV
1
2
3
4
Cerabar M PMC51, PMP51, PMP55
A0029505
Item Term/abbreviation Explanation
1 OPL The OPL (over pressure limit = sensor overload limit) for the measuring device depends on the lowest-rated element,
with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes see the →  47 section. The OPL may only be applied for a limited period of time.
2 MWP The MWP (maximum working pressure) for the sensors depends on the lowest-rated element, with regard to
pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes see the →  47 section. The MWP may be applied at the device for an unlimited period. The MWP can also be found on the nameplate.
3 Maximum sensor
measuring range
4 Calibrated/adjusted
span
p - Pressure
- LRL Lower range limit
- URL Upper range limit
- LRV Lower range value
- URV Upper range value
- TD (Turn down) Turn down
Span between LRL and URL This sensor measuring range is equivalent to the maximum calibratable/adjustable span.
Span between LRV and URV Factory setting: 0 to URL Other calibrated spans can be ordered as customized spans.
Example - see the following section.
6 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
LRV
URLURV
LRL
1 = 2
3

Turn down calculation

1 Calibrated/adjusted span 2 Zero point-based span 3 URL sensor
Example
• Sensor:10 bar (150 psi)
• Upper range value (URL) = 10 bar (150 psi)
Turn down (TD):
A0029545
• Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)
• Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
TD =
URL
|URV - LRV|
10 bar (150 psi)
TD =
|5 bar (75 psi) - 0 bar (0 psi)|
In this example, the TD is 2:1. This span is based on the zero point.
= 2
Endress+Hauser 7

Device selection

Cerabar M PMC51, PMP51, PMP55

Function and system design

A0023673
PMC51 with capacitive measuring cell and ceramic process isolating diaphragm (Ceraphire®)
A0023675
PMP51 with piezoresistive measuring cell and metal welded process isolating diaphragm
PMP55 with diaphragm seal
Field of application
• Gauge pressure and absolute pressure
• Level
Process connections
PMC51:
• Thread
• EN flanges DN 25 – DN 80
• ANSI flanges 1" – 4"
• JIS flanges 50 A – 100 A
• Flush mount hygienic connections PMP51:
• Thread
• EN flanges DN 25 – DN 80
• ANSI flanges 1" – 4"
• Prepared for diaphragm seal mount
• Flush mount hygienic connections PMP55:
Wide range of diaphragm seals
Measuring ranges
• PMC51: From –100/0 to 100 mbar (–1.5/0 to 1.5 psi) to –1/0 to 40 bar (–15/0 to 600 psi)
• PMP51: From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 400 bar (–15/0 to 6000 psi)
• PMP55: From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 400 bar (–15/0 to 6000 psi)
A0023676
8 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
OPL
• PMC51: max. 60 bar (900 psi)
• PMP51: max. 600 bar (9 000 psi)
• PMP55: max. 600 bar (9 000 psi)
Process temperature range
• PMC51: –20 to +130 °C (–4 to +266 °F) For a maximum of 60 minutes: +150 °C (+302 °F)
• PMP51: –40 to +130 °C (–40 to +266 °F) For a maximum of 60 minutes: +150 °C (+302 °F)
• PMP55: –70 to +400 °C (–94 to +752 °F) (depending on the filling oil)
Ambient temperature range
• Without LCD: –40 to +85 °C (–40 to +185 °F)
• With LCD display: –20 to +70 °C (–4 to +158 °F) (extended temperature application range–40 to +85 °C (–40 to +185 °F) with limitations in optical properties, such as display speed and contrast)
• Separate housing:–20 to +60 °C (–4 to +140 °F)
• PMP55: Diaphragm seal systems depending on the version
Reference accuracy
• PMC51: up to ±0.10% of the set span PLATINUM version: up to ±0.075% of the set span
• PMP51: up to ±0.10% of the set span PLATINUM version: up to ±0.075% of the set span
• PMP55: up to ±0.10% of the set span
Supply voltage
• 11.5 to 45 V DC (versions with plug-in connection 35 V DC)
• For intrinsically safe device versions: 11.5 to 30 V DC
Output
4 to 20 mA, 4 to 20 mA with superimposed HART protocol, PROFIBUS PA or FOUNDATION Fieldbus
Options
• Inspection certificate 2.2 or 3.1 or other certificates
• 3A approval and EHEDG approval
• Specific firmware versions
• Initial device settings
• Separate housing
• Broad range of accessories
• NACE-compliant materials
Specialties
• PMC51:
• Metal-free measurement with PVDF connection
• Special cleaning of the transmitter to remove paint-wetting impairment substances, for use in
paint shops
• PMP51:
• Process connections with minimum oil volume
• Gas-tight, elastomer-free
• PMP55:
• Wide range of diaphragm seals
• For extreme medium temperatures
• Process connections with minimum oil volume
• Fully welded versions
Endress+Hauser 9
Cerabar M PMC51, PMP51, PMP55
1
2
3
4
p
p
1
3
4
2

Measuring principle

Ceramic process isolating diaphragm used in PMC51 (Ceraphire®)
A0020465
1 Air pressure (gauge pressure sensors) 2 Ceramic substrate 3 Electrodes 4 Ceramic process isolating diaphragm
The ceramic sensor is a dry sensor, i.e. the process pressure acts directly on the robust ceramic process isolating diaphragm and deflects it. A pressure-dependent change in capacitance is measured at the electrodes of the ceramic substrate and the process isolating diaphragm. The measuring range is determined by the thickness of the ceramic process isolating diaphragm.
Advantages:
• Guaranteed overload resistance up to 40 times the nominal pressure
• Thanks to ultrapure 99.9% ceramic (Ceraphire®, see also "www.endress.com/ceraphire")
• extremely high chemical stability, comparable with Alloy C
• high mechanical stability
• Can be used in absolute vacuum
Metallic process isolating diaphragm used in PMP51 and PMP55
A0016448
1 Silicon measuring element, substrate 2 Wheatstone bridge 3 Channel with fill fluid 4 Metallic process isolating diaphragm
PMP51
The operating pressure deflects the process isolating diaphragm and a fill fluid transfers the pressure to a resistance bridge (semiconductor technology). The pressure-dependent change in the bridge output voltage is measured and evaluated.
Advantages:
• Can be used for process pressure up to 400 bar (6 000 psi)
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
• Significantly less thermal effect compared to diaphragm seal systems
10 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
h =
p
ρ g
h
Fieldgate FXA520
FXN 520
FXN 520
Multidrop-Connector FXN520
Cerabar M
Á
11
2
PMP55
The operating pressure acts on the process isolating diaphragm of the diaphragm seal and is transferred to the process isolating diaphragm of the sensor by a diaphragm seal fill fluid. The process isolating diaphragm is deflected and a fill fluid transfers the pressure to a resistance bridge. The pressure-dependent change in the bridge output voltage is measured and evaluated.
Advantages:
• Depending on the version, can be used for process pressure up to 400 bar (6 000 psi) and simultaneous extreme process temperatures
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure

Level measurement (level, volume and mass)

Electrical differential pressure measurement with gauge pressure sensors

A0023678
h Height (level) p Pressure ρ Density of the medium g Gravitation constant
Your benefits
• Choice of different level measuring modes in the device software
• Volume and mass measurements in any tank shapes by means of a freely programmable characteristic curve
• Choice of diverse level units
• Has a wide range of uses, even in the following cases:
• in the event of foam formation
• in tanks with agitators of screen fittings
• in the event of liquid gases
A0023680
1 Shut-off valves 2 e.g. filter
In the example given, two Cerabar M devices (each with a gauge pressure sensor) are interconnected. The pressure difference can thus be measured using two independent Cerabar M devices.
Endress+Hauser 11
Cerabar M PMC51, PMP51, PMP55
WARNING
L
Risk of explosion!
If using intrinsically safe devices, strict compliance with the rules for interconnecting intrinsically
safe circuits as stipulated in IEC60079-14 (proof of intrinsic safety) is mandatory.

Communication protocol

• 4 to 20 mA without communication protocol (analog electronics)
• 4 to 20 mA with HART communication protocol
• PROFIBUS PA
• The Endress+Hauser devices meet the requirements of the FISCO model.
• Due to a low current consumption of 11 mA ± 1 mA, the following number of devices can be operated on one bus segment if installing as per FISCO: up to 8 devices for Ex ia, CSA IS and FM IS applications or up to 31 devices for all other applications e.g. in non-hazardous areas, Ex nA etc. Further information on PROFIBUS PA can be found in Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and in the PNO Guideline.
• FOUNDATION Fieldbus
• The Endress+Hauser devices meet the requirements of the FISCO model.
• Due to a low current consumption of 16 mA ± 1 mA, the following number of devices can be operated on one bus segment if installing as per FISCO: up to 6 devices for Ex ia, CSA IS and FM IS applications or up to 22 devices for all other applications e.g. in non-hazardous areas, Ex nA etc. Further information on FOUNDATION Fieldbus, such as requirements for bus system components, can be found in Operating Instructions BA00013S "FOUNDATION Fieldbus Overview".
12 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55

Input

Measured variable Measured process variables

• Analog electronics: Absolute pressure and gauge pressure
• HART, PROFIBUS PA, FOUNDATION Fieldbus: Absolute pressure and gauge pressure, from which level (level, volume or mass) is derived

Measuring range PMC51 – with ceramic process isolating diaphragm (Ceraphire®) for gauge pressure

Sensor Maximum sensor measuring range Smallest calibratable
lower (LRL) upper (URL)
measuring span (preset at the factory)
1)
[bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar
MWP OPL Vacuum
resistance
abs
(psi
abs
)]
100 mbar (1.5 psi) –0.1 (–1.5) +0.1 (+1.5) 0.01 (0.15) 2.7 (40.5) 4 (60) 0.7 (10.5) 1C
250 mbar
–0.25 (–3.75) +0.25 (+3.75) 0.01 (0.15) 3.3 (49.5) 5 (75) 0.5 (7.5) 1E
(3.75 psi)
400 mbar (6 psi) –0.4 (–6) +0.4 (+6) 0.02 (0.3) 5.3 (79.5) 8 (120) 0 1F
1 bar (15 psi) –1 (–15) +1 (+15) 0.05 (1) 6.7 (100.5) 10 (150) 0 1H
2 bar (30 psi) –1 (–15) +2 (+30) 0.1 (1.5) 12 (180) 18 (270) 0 1K
4 bar (60 psi) –1 (–15) +4 (+60) 0.2 (3) 16.7 (250.5) 25 (375) 0 1M
10 bar (150 psi) –1 (–15) +10 (+150) 0.5 (7.5) 26.7 (400.5) 40 (600) 0 1P
40 bar (600 psi) –1 (–15) +40 (+600) 2 (30) 40 (600) 60 (900) 0 1S
1) Factory calibration turn down: Max 20:1, higher on request or configurable in the device.
2) Product Configurator, "Sensor range" ordering feature
PMC51 – with ceramic process isolating diaphragm (Ceraphire®) for absolute pressure
Sensor Maximum sensor measuring
range
lower (LRL) upper (URL)
100 mbar
[bar
abs
(psi
)]
abs
0 +0.1 (+1.5) 0.01 (0.15) 2.7 (40.5) 4 (60) 0 2C
[bar
abs
(psi
(1.5 psi)
250 mbar
0 +0.25 (+3.75) 0.01 (0.15) 3.3 (49.5) 5 (75) 0 2E
(3.75 psi)
400 mbar (6 psi) 0 +0.4 (+6) 0.02 (0.3) 5.3 (79.5) 8 (120) 0 2F
1 bar (15 psi) 0 +1 (+15) 0.05 (1) 6.7 (100.5) 10 (150) 0 2H
2 bar (30 psi) 0 +2 (+30) 0.1 (1.5) 12 (180) 18 (270) 0 2K
4 bar (60 psi) 0 +4 (+60) 0.2 (3) 16.7 (250.5) 25 (375) 0 2M
10 bar (150 psi) 0 +10 (+150) 0.5 (7.5) 26.7 (400.5) 40 (600) 0 2P
40 bar (600 psi) 0 +40 (+600) 2 (30) 40 (600) 60 (900) 0 2S
Smallest calibratable measuring span (preset at the factory)
)] [bar (psi)] [bar
abs
1)
MWP OPL Vacuum
resistance
(psi
abs
)] [bar
abs
abs
(psi
)] [bar
abs
abs
(psi
abs
)]
Option
Option
2)
2)
1) Factory calibration turn down: Max 20:1, higher on request or configurable in the device.
2) Product Configurator, "Sensor range" ordering feature
Endress+Hauser 13
Cerabar M PMC51, PMP51, PMP55
PMP51 and PMP55 – metallic process isolating diaphragm for gauge pressure
Sensor Maximum sensor measuring
range
lower (LRL) upper (URL) Silicone oil/
Lowest calibratable span (preset at factory)
1)
MWP OPL Vacuum resistance
Inert oil/
2)
Synthetic oil
[bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar
abs
(psi
abs
)]
400 mbar (6 psi) –0.4 (–6) +0.4 (+6) 0.02 (0.3) 4 (60) 6 (90)
1 bar (15 psi) –1 (–15) +1 (+15) 0.05 (1) 6.7 (100) 10 (150) 1H
2 bar (30 psi) –1 (–15) +2 (+30) 0.1 (1.5) 13.3 (200) 20 (300) 1K
4 bar (60 psi) –1 (–15) +4 (+60) 0.2 (3) 18.7 (280.5) 28 (420) 1M
10 bar (150 psi) –1 (–15) +10 (+150) 0.5 (7.5) 26.7 (400.5) 40 (600) 1P
0.01/0.04/0.01 (0.15/0.6/0.15)
40 bar (600 psi) –1 (–15) +40 (+600) 2 (30) 100 (1500) 160 (2400) 1S
100 bar
–1 (–15) +100 (+1500) 5 (75) 100 (1500) 400 (6000) 1U
(1 500 psi)
400 bar
–1 (–15) +400 (+6000) 20 (300) 400 (6000) 600 (9000) 1W
(6 000 psi)
1) Highest factory-configurable turn down: 20:1, higher available on request or can be set in device.
2) The vacuum resistance applies to the measuring cell at reference conditions. A ceramic process isolating diaphragm is recommended for applications in the limit range. The pressure and temperature application limits of the selected filling oil must also be observed for the PMP55 →  115.
3) Product Configurator, order code for "Sensor range"
Option
1F
3)
PMP51 and PMP55 – metallic process isolating diaphragm for absolute pressure
abs
3)
)]
Sensor Maximum sensor
measuring
1)
lower (LRL) upper (URL) Silicone oil/
Lowest calibratable span (preset at factory)
2)
MWP OPL Vacuum resistance
Inert oil/ Synthetic oil
[bar (psi
abs
abs
)]
[bar
abs
(psi
)] [bar (psi)] [bar
abs
(psi
abs
abs
[bar
)]
(psi
abs
abs
)]
[bar
abs
(psi
400 mbar (6 psi) 0 +0.4 (+6) 0.02 (0.3) 4 (60) 6 (90)
1 bar (15 psi) 0 +1 (+15) 0.05 (1) 6.7 (100) 10 (150) 2H
2 bar (30 psi) 0 +2 (+30) 0.1 (1.5) 13.3 (200) 20 (300) 2K
4 bar (60 psi) 0 +4 (+60) 0.2 (3) 18.7 (280.5) 28 (420) 2M
10 bar (150 psi) 0 +10 (+150) 0.5 (7.5) 26.7 (400.5) 40 (600) 2P
0.01/0.04/0.01 (0.15/0.6/0.15)
40 bar (600 psi) 0 +40 (+600) 2 (30) 100 (1500) 160 (2400) 2S
100 bar
0 +100 (+1500) 5 (75) 100 (1500) 400 (6000) 2U
(1 500 psi)
400 bar
0 +400 (+6000) 20 (300) 400 (6000) 600 (9000) 2W
(6 000 psi)
1) PMP55: Within the sensor measuring range, the minimum upper range value of 80 mbar
(1.16 psi
abs
) must be observed.
abs
2) Highest factory-configurable turn down: 20:1, higher available on request or can be set in device.
3) The vacuum resistance applies to the measuring cell at reference conditions. A ceramic process isolating diaphragm is recommended for applications in the limit range. The pressure and temperature application limits of the selected filling oil must also be observed for the PMP55 →  115.
4) Product Configurator, order code for "Sensor range"
Option
2F
4)
14 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
U – 11.5 V
23 mA
[ ]W
30
20
11.5
40 45
1239
1456
804
369
£
U
[V]
1
2
R
L
max
3
R
L
max

Output

Output signal

Signal range 4 to 20 mA

Signal on alarm

• 4 to 20 mA analog, 2-wire
• 4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.02)
• Digital communication signal FOUNDATION Fieldbus
Output Option
4 to 20mA 1
4 to 20mA HART 2
PROFIBUS PA 3
FOUNDATION Fieldbus 4
1) Product Configurator, "Output" ordering feature
4 to 20 mA Analog, 4 to 20 mA HART: 3.8 to 20.5 mA
As per NAMUR NE 43
• 4 to 20 mA Analog:
• Signal overshoot: > 20.5 mA
• Signal undershoot: < 3.8 mA
• Min Alarm (3.6 mA)
• 4 to 20 mA HART: Options:
• Max. alarm: can be set from 21 to 23 mA (factory setting: 22 mA)
• Hold measured value: last measured value is held
• Min. alarm: 3.6 mA
• PROFIBUS PA: can be set in the Analog Input block Options: Last Valid Out Value (factory setting), Fail-safe Value, Status Bad
• FOUNDATION Fieldbus: can be set in the Analog Input block Options: Last Good Value, Fail-safe Value (factory setting), Wrong Value
1)
Load - 4 to 20 mA Analog
4...20 mA HART
A0023090
1 Supply voltage 11.5 to 30 V DC for intrinsically safe device versions (not for analog) 2 Supply voltage 11.5 to 45 V DC (versions with plug-in connector 35 V DC) for other types of protection and
for uncertified device versions
3 R U Supply voltage
Maximum load resistance
Lmax
When operating via a handheld terminal or via a PC with an operating program, a minimum
Endress+Hauser 15
communication resistance of 250 Ω must be taken into account.
Cerabar M PMC51, PMP51, PMP55

Damping

Firmware version

Protocol-specific data HART

A damping affects all outputs (output signal, display):
• Via on-site display, handheld terminal or PC with operating program, continuous from 0...999 s
• Via DIP-switch on the electronic insert, switch position "on" (= set value) and "off" (= damping switched off)
• Factory setting: 2 s
Designation Option
01.00.zz, FF, DevRev01 76
01.00.zz, PROFIBUS PA, DevRev01 77
01.00.zz, HART, DevRev01 78
1) Product Configurator, "Firmware version" ordering feature
Manufacturer ID 17 (11 hex)
Device Type Code 25 (19 hex)
Device Revision 01 (01 hex) - SW version 01.00.zz
HART specification 6
DD Revision • 01 (Dutch))
• 02 (Russian))
Device description files (DTM, DD) Information and files can be found:
www.endress.com
www.fieldcommgroup.org
HART load Min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables:
Measured values for PV (primary variable)
• Pressure
• Level
• Tank content
Measured values for SV, TV (second and third variable)
• Pressure
• Level
Measured values for QV (fourth variable)
Temperature
Supported functions • Burst mode
• Additional Transmitter Status
• Device Locking
• Alternative operating modes
1)

Wireless HART data

Protocol-specific data PROFIBUS PA

Minimum starting voltage 11.5 V
Start-up current 12 mA (default) or 22 mA (customer setting)
Starting time 5 s
Minimum operating voltage 11.5 V
Multidrop current 4 mA
Time for connection setup 1 s
1) Or higher if operating near ambient temperature limits (–40 to +85 °C (–40 to +185))
Manufacturer ID 17 (11 hex)
Ident number 1554 hex
Profile Version 3.02
SW Version 01.00.zz
GSD Revision 5
1)
1)
16 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
DD Revision 1
GSD File Information and files can be found:
DD Files
Output values Measured values for PV (via Analog Input Function Block)
Input values Input value sent from PLC, can be shown on display
Supported functions • Identification & Maintenance
www.endress.com
www.profibus.org
• Pressure
• Level
• Tank content
Measured values for SV
• Pressure
• Temperature
Simple device identification via control system and nameplate
• Condensed status
• Automatic ident number adaptation and switchable to following ident numbers:
• 9700: Profile-specific transmitter identification number with the
"Classic" or "Condensed" status.
• 151C: Compatibility mode for the old Cerabar M (PMC41,
PMC45, PMP41, PMP45, PMP46, PMP48).
• 1553: Identification number for the new Cerabar M (PMC51,
PMP51 , PMP55).
• Device locking: The device can be locked by hardware or software.

Protocol-specific data FOUNDATION Fieldbus

Device Type 0x1019
Device Revision 01 (hex)
DD Revision 0x01021
Device description files (DTM, DD) Information and files can be found:
www.endress.com
www.fieldcommgroup.org
CFF Revision 0x000102
ITK Version 5.2.0
ITK-Certification Driver-No. IT067700
Link-Master (LAS) capable yes
Link Master / Basic Device selectable Yes; Factory setting: Basic Device
Number of VCRs 44
Number of Link Objects in VFD 50
Number of FB-Schedule Objects 40
Virtual communication references (VCRs)
Permanent Entries 44
Client VCRs 0
Server VCRs 5
Source VCRs 8
Sink VCRs 0
Subscriber VCRs 12
Publisher VCRs 19
Endress+Hauser 17
Cerabar M PMC51, PMP51, PMP55
Link settings
Slot time 4
Min. Inter PDU delay 12
Max. response delay 40
Transducer Blocks
Block Content Output values
TRD1 Block Contains all parameters related to the
measurement
Diagnostic Block Contains diagnostic information Error code via DI channels (channel 10 to 15)
Display Block Contains parameters to configure the onsite
display
• Pressure or level (channel 1)
• Process temperature (channel 2)
• Measured pressure value (channel 3)
• Max. pressure (channel 4)
• Level before linearization (channel 5)
No output values
Function blocks
Block Content Number
of blocks
Resource Block The Resource Block contains all the data that uniquely identify the device. It is an
electronic version of a nameplate of the device.
Analog Input Block 1 Analog Input Block 2
Digital Input Block
Digital Output Block
PID Block The PID Block serves as a proportional-integralderivative controller and is used almost
Arithmetic Block This block is designed to permit simple use of popular measurement math functions.
Input Selector Block
Signal Characterizer Block
Integrator Block The Integrator Block integrates a variable as a function of the time or accumulates the
The AI Block receives the measuring data from the Sensor Block, (selectable via a channel number) and makes the data available to other function blocks at its output. Enhancement: digital outputs for process alarms, fail safe mode.
This block contains the discrete data of the Diagnose Block (selectable via a channel number 10 to 15) and provides them for other blocks at the output.
This block converts the discrete input and thus initiates an action (selectable via a channel number) in the DP Flow Block or in the im TRD1 Block. Channel 20 resets the counter for max. pressure transgressions value.
universally for closed-loop-control in the field including cascade and feedforward. Input IN can be indicated on the display. The selection is performed in the Display Block (DISPLAY_MAIN_LINE_CONTENT).
The user does not have to know how to write equations. The math algorithm is selected by name, chosen by the user for the function to be performed.
The Input Selector Block facilitates the selection of up to four inputs and generates an output based on the configured action. This block normally receives its inputs from AI Blocks. The block performs maximum, minimum, average and ‘first good’ signal selection. Inputs IN1 to IN4 can be indicated on the display. The selection is performed in the Display Block (DISPLAY_MAIN_LINE_1_CONTENT).
DThe Signal Characterizer Block has two sections, each with an output that is a non­linear function of the respective input. The non-linear function is generated by a single look-up table with 21 arbitrary x-y pairs.
counts from a Pulse Input Block. The block may be used as a totalizer that counts up until reset or as a batch totalizer that has a setpoint, where the integrated or accumulated value is compared to pre-trip and trip settings, generating a binary signal when the setpoint is reached.
1 enhanced
2 25 ms enhanced
1 20 ms standard
1 20 ms standard
1 40 ms standard
1 35 ms standard
1 30 ms standard
1 40 ms standard
1 35 ms standard
Execution time
Functionality
18 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
Additional function block information:
Instantiate Function Block YES
Number of additional instantiatable function blocks 20
Endress+Hauser 19

Terminal assignment

- +
1
2
3
4
5
6
7
Cerabar M PMC51, PMP51, PMP55

Power supply

WARNING
L
An incorrect connection compromises electrical safety!
When using the measuring device in hazardous areas, the relevant national standards and
regulations as well as the Safety Instructions or Installation or Control Drawings must be observed →  128. All explosion protection data are given in separate documentation which is available upon
request. The Ex documentation is supplied as standard with all Ex-systems →  128. In accordance with IEC/EN61010 a suitable circuit breaker must be provided for the device.
HART: Overvoltage protection HAW569-DA2B for the non-hazardous area, ATEX II 2 (1) Ex ia
IIC and IEC Ex ia can be ordered as an option (see the "Ordering information" section). Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
1 External grounding terminal (only for devices with certainly approvals or if "Measuring point" (TAG) is
2 Internal grounding terminal 3 Supply voltage →  20 4 4...20 mA for HART devices 5 For HART and FOUNDATION Fieldbus devices: With a handheld terminal, all the parameters can be
6 Terminals 7 For HART devices: test terminals, see section "Taking 4 to 20 mA test signal" →  20

Supply voltage 4 to 20 mA HART

Type of protection Supply voltage
Intrinsically safe 11.5 to 30 V DC
• Other types of protection
• Devices without certificate
Taking 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the test terminals without interrupting the measurement.
PROFIBUS PA
Version for non-hazardous areas: 9 to 32 V DC
A0023505
ordered)
configured anywhere along the bus line via menu operation.
11.5 to 45 V DC (versions with plug-in connection 35 V DC)
20 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
FOUNDATION Fieldbus
Version for non-hazardous areas: 9 to 32 V DC

Current consumption

Electrical connection

• PROFIBUS PA: 11 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 16 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Cable entry Degree of protection Option
M20 gland IP66/67 NEMA 4X/6P A
G ½" thread IP66/67 NEMA 4X/6P C
NPT ½" thread IP66/67 NEMA 4X/6P D
M12 plug IP66/67 NEMA 4X/6P I
7/8" plug IP66/67 NEMA 4X/6P M
HAN7D plug 90 deg IP65 P
PE cable 5m IP66/68 NEMA4X/6P + pressure compensation via cable S
M16 valve connector IP64 V
1) Product Configurator, order code for "Electrical connection"
1)
PROFIBUS PA
The digital communication signal is transmitted over the bus via a 2-wire connection. The bus also provides the power supply. For further information on the network structure and grounding, and for further bus system components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the PNO Guideline.

Terminals

Cable entry

FOUNDATION Fieldbus
The digital communication signal is transmitted over the bus via a 2-wire connection. The bus also provides the power supply. For further information on the network structure and grounding and for further bus system components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
• Supply voltage and internal ground terminal: 0.5 to 2.5 mm2 (20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm2 (20 to 12 AWG)
Approval Type Clamping area
Standard, CSA GP ATEX II1/2G or II2G Ex ia, IEC Ex ia Ga/Gb or Ex ia Gb, FM/ CSA IS
ATEX II1/2D Ex t, II1/2GD Ex ia, II3G Ex nA, IEC Ex t Da/Db
Plastic M20x1.5 5 to 10 mm (0.2 to 0.39 in)
Metal M20x1.5 (Ex e) 7 to 10.5 mm (0.28 to 0.41 in)
For other technical data, see the housing section →  48
Endress+Hauser 21

Device plugs Devices with valve connector (HART)

+
2 1
+
A B
BU BN GNYE
2
1
3
+
Han7D
+ –
+
A B
+
+
PE
1 2 3 4
 1 BN = brown, BU = blue, GNYE = green
A Electrical connection for devices with valve connector B View of the plug connector at the device
Material: PA 6.6
Cerabar M PMC51, PMP51, PMP55
A0023097
Devices with Harting plug Han7D (HART)
A Electrical connection for devices with Harting plug Han7D B View of the plug-in connector at the device
Material: CuZn, contacts for plug-in jack and connector are gold-plated
Connecting the cable version (all device versions)
A0019990
1 RD = red 2 BK = black 3 GNYE = green 4 4...20 mA
22 Endress+Hauser
A0019991
Cerabar M PMC51, PMP51, PMP55
2
1
34
4
2
3
1
Devices with M12 plug(Analog, HART, PROFIBUS PA)
1 Signal + 2 Not assigned 3 Signal – 4 Ground
Endress+Hauser offers the following accessories for devices with an M12 plug:
Plug-in jack M 12x1, straight
• Material: body PA; coupling nut CuZn, nickel-plated
• Degree of protection (fully locked): IP66/67
• Order number: 52006263 Plug-in jack M 12x1, elbowed
• Material: body PBT/PA; coupling nut GD-Zn, nickel-plated
• Degree of protection (fully locked): IP66/67
• Order number: 71114212
Cable 4x0.34 mm2 (20 AWG) with M12 socket, elbowed, screw plug, length 5 m (16 ft)
• Material: body PUR; coupling nut CuSn/Ni; cable PVC
• Degree of protection (fully locked): IP66/67
• Order number: 52010285
A0011175
Devices with 7/8" plug (Analog, HART, FOUNDATION Fieldbus)
1 Signal ­2 Signal + 3 Not assigned 4 Shield
External thread: 7/8 - 16 UNC
• Material: 316L (1.4401)
• Protection: IP66/68

Cable specification Analog

• Endress+Hauser recommends using twisted, shielded two-wire cables.
• The cable outer diameter depends on the cable entry used.
HART
• Endress+Hauser recommends using twisted, shielded two-wire cables.
• The cable outer diameter depends on the cable entry used.
A0011176
Endress+Hauser 23
Cerabar M PMC51, PMP51, PMP55
1
2
3
4
+
-
+
-
rt
sw
+
-
A
B
PROFIBUS PA
Use a twisted, shielded two-wire cable, preferably cable type A
For further information on the cable specifications, see Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092 PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Use a twisted, shielded two-wire cable, preferably cable type A
For further information on the cable specifications, see Operating Instructions BA00013S "FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).

Start-up current

Residual ripple

Influence of power supply

Overvoltage protection (optional)

• Analog electronics:: 12 mA
• HART: 12 mA or 22 mA (selectable)
No influence on 4 to 20 mA signal up to ±5 % residual ripple within the permitted voltage range [according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)].
≤0.001 % of URL/V
The device can be fitted with overvoltage protection. The overvoltage protection is mounted at the factory on the housing thread (M20x1.5) for the cable gland and is approx. 70 mm (2.76 in) in length (take additional length into account when installing). The device is connected as illustrated in the following graphic.
For details refer to TI01013KDE, XA01003KA3 and BA00304KA2.
Ordering information:
Product Configurator, "Mounted accessories" ordering feature, option NA
Wiring
A Without direct shield grounding B With direct shield grounding 1 Incoming connection cable 2 HAW569-DA2B 3 Unit to be protected 4 Connection cable
24 Endress+Hauser
A0023111
Cerabar M PMC51, PMP51, PMP55

Performance characteristics for measuring devices with ceramic process isolating diaphragm

Response time HART

• Acyclic: min. 330 ms, typically 590 ms (depending on command # and number of preambles)
• Cyclic (burst): min. 160 ms, typically 350 ms (depending on command # and number of preambles)
PROFIBUS PA
• Acyclic: approx. 23 ms to 35 ms (depending on Min. Slave Interval)
• Cyclic: approx. 8 ms to 13 ms (depending on Min. Slave Interval)
FOUNDATION Fieldbus
• Acyclic: typically 70 ms (for standard bus parameter settings)
• Cyclic: max. 20 ms (for standard bus parameter settings)

Reference operating conditions

Maximum measured error (total performance)

• As per IEC 62828-2 / IEC 60770
• Ambient temperature TA = constant, in the range of +21 to +33 °C (+70 to +91 °F)
Humidity j = constant, in the range: 5 to 80 % RH ± 5 %
• Ambient pressure pA = constant, in the range: 860 to 1 060 mbar (12.47 to 15.37 psi)
• Position of the measuring cell: horizontal ±1°
• Input of LOW SENSOR TRIM and HIGH SENSOR TRIM for lower range value and upper range value
• Zero based span
• Material of the process isolating diaphragm: Al2O3 aluminum oxide ceramic FDA, ultrapure 99.9 %
• Supply voltage: 24 V DC ±3 V DC
• Load with HART: 250 Ω
• Turn down (TD) = URL/|URV - LRV|
The performance characteristics refer to the accuracy of the measuring device. The factors influencing accuracy can be divided into two groups
• Total performance of measuring device
• Installation factors
All performance characteristics are in conformance with ≥ ± 3 sigma.
The total performance of the measuring device comprises the reference accuracy and the ambient temperature effect and is calculated using the following formula:
Total performance = ± √ ( (E1)² + (E2)²)
E1 = Reference accuracy
E2 = Temperature effect per ±28 °C (50 °F)
(corresponds to the range from –3 to +53 °C (+27 to +127 °F))
Calculation of E2:
E2 = E2M + E2
E2M = Main temperature error
E2E = Electronics error
The values refer to the calibrated span
E
Endress+Hauser 25
Cerabar M PMC51, PMP51, PMP55
Calculation of the total performance with the Endress+Hauser Applicator
Detailed measured errors, such as for other temperature ranges, for example, can be calculated with the Applicator "Sizing Pressure Performance".
A0038927
Reference accuracy [E1]
Reference accuracy comprises the non-linearity [IEC 62828-1 / DIN EN 61298-2] including the hysteresis [IEC 62828-1 / DIN EN 61298-2] and the non-repeatability [IEC 62828-1 / DIN EN 61298-2] in accordance with the limit point method as per [IEC 62828-1 / DIN EN 60770-2].
Gauge pressure sensors
100 mbar (1.5 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.15 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD 250 mbar (3.75 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi) and
10 bar (150 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.1 % 40 bar (600 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
Gauge pressure sensors with hygienic process connections
100 mbar (1.5 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.10 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD 250 mbar (3.75 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi) and
10 bar (150 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.1 % 40 bar (600 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
Absolute pressure sensors
100 mbar (1.5 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.15 %; TD >10:1 to 20:1 = ±0.015 % · TD
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.015 % · TD 250 mbar (3.75 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi) and
10 bar (150 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.1 % 40 bar (600 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
26 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
Absolute pressure sensors with hygienic process connections
100 mbar (1.5 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.15 % · TD
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.015 % · TD
250 mbar (3.75 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi) and 10 bar (150 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.1 %
40 bar (600 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
Temperature effect [E2]
E2M - Main temperature error
The output changes due to the effect of the ambient temperature [IEC 62828-1 / IEC 61298-3] with respect to the reference temperature [IEC 62828-1 / DIN 16086]. The values specify the maximum error due to min./max. ambient or process temperature conditions.
100 mbar (1.5 psi), 250 mbar (3.75 psi) and 400 mbar (6 psi) sensor
• Standard: ±(0.277 % · TD + 0.275 %)
• Platinum: ±(0.277 % · TD + 0.275 %)
1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• Standard: ±(0.157 % · TD + 0.235 %)
• Platinum: ±(0.157 % · TD + 0.235 %)

Resolution

With hygienic process connections
100 mbar (1.5 psi), 250 mbar (3.75 psi) and 400 mbar (6 psi) sensor
• Standard: ±(0.277 % · TD + 0.275 %)
• Platinum: ±(0.277 % · TD + 0.275 %)
1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• Standard: ±(0.157 % · TD + 0.235 %)
• Platinum: ±(0.157 % · TD + 0.235 %)
E2E - Electronics error
• Analog output (4 to 20 mA): 0.2 %
• Digital output (HART/PA/FF): 0 %
• Current output: 1 μA
• Display: can be set (factory setting: presentation of the maximum accuracy of the transmitter)
Endress+Hauser 27
Cerabar M PMC51, PMP51, PMP55

Total error

The total error of the measuring device comprises the total performance and the influence of long­term stability and is calculated using the following formula:
Total error = total performance + long-term stability
Calculation of the total error with the Endress+Hauser Applicator
Detailed measured errors, such as for other temperature ranges, for example, can be calculated with the Applicator "Sizing Pressure Performance".
A0038927
Calculation of the diaphragm seal error with the Endress+Hauser Applicator
Diaphragm seal errors are not taken into consideration. Diaphragm seal errors are calculated separately in the Applicator "Sizing Diaphragm Seal".

Long-term stability

A0038925
The specifications refer to the upper range limit (URL).
400 mbar (6 psi) and 1 bar (15 psi) sensor
• 1 year: ±0.20 %
• 5 years: ±0.40 %
• 10 years: ±0.50 % 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• 1 year: ±0.10 %
• 5 years: ±0.25 %
• 10 years: ±0.40 % With hygienic process connections
400 mbar (6 psi) and 1 bar (15 psi) sensor
• 1 year: ±0.35 %
• 5 years: ±0.50 %
• 10 years: ±0.60 % 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• 1 year: ±0.20 %
• 5 years: ±0.35 %
• 10 years: ±0.50 %
28 Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
I
63 %
t
t1t
2
90 %
t
3

Response time T63 and T90 Dead time, time constant

Presentation of the dead time and the time constant as per DIN 16086:
Dynamic behavior, current output (analog electronics)
Dead time (t1) Time constant T63 (= t2) Time constant T90 (= t3)
Max. 60 ms 40 ms 50 ms
A0019786
Dynamic behavior, current output (HART electronics)
Dead time (t1) Time constant T63 (= t2) Time constant T90 (= t3)
Max. 50 ms 85 ms 200 ms
Dynamic behavior, digital output (HART electronics)
Dead time (t1) Dead time (t1) +
Time constant T63 (= t2)
min. 210 ms 295 ms 360 ms
Max. 1010 ms 1095 ms 1160 ms
Dead time (t1) + Time constant T90 (= t3)
Reading cycle
• Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)
• Cyclic (burst): max. 3/s, typical 2/s
The device commands the BURST MODE function for cyclic value transmission via the HART communication protocol.
Cycle time (update time)
Cyclic (burst): min. 300 ms
Endress+Hauser 29
Dynamic behavior, PROFIBUS PA
Cerabar M PMC51, PMP51, PMP55
Dead time (t1) Dead time (t1) +
Time constant T63 (= t2)
min. 85 ms 170 ms 235 ms
Max. 1185 ms 1270 ms 1335 ms
Dead time (t1) + Time constant T90 (= t3)
Reading cycle (PLC)
• Acyclic: typically 25/s
• Cyclic: typically 30/s (dependent on the number and type of function blocks used in a closed­control loop)
Cycle time (update time)
min. 100 ms
The cycle time in a bus segment in cyclic data communication depends on the number of devices, on the segment coupler used and on the internal PLC cycle time.
Dynamic behavior, FOUNDATION Fieldbus
Dead time (t1) Dead time (t1) +
Time constant T63 (= t2)
min. 95 ms 180 ms 245 ms
Max. 1095 ms 1180 ms 1245 ms
Dead time (t1) + Time constant T90 (= t3)
Reading cycle
• Acyclic: typically 5/s
• Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control loop)
Cycle time (update time)
Cyclic: min. 100 ms
30 Endress+Hauser
Loading...
+ 104 hidden pages