Function and design .......................... 114
Registered trademarks ..................... 132
HART® .................................. 132
PROFIBUS® ............................... 132
FOUNDATIONTMFieldbus ...................... 132
Endress+Hauser3
Document information
DANGER
WARNING
CAUTION
NOTICE
A
,…,
1.
2.
3.
Cerabar M PMC51, PMP51, PMP55
Document function
The document contains all the technical data on the device and provides an overview of the
accessories and other products that can be ordered for the device.
Symbols usedSafety symbols
SymbolMeaning
Electrical symbols
SymbolMeaningSymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
seriousor fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
seriousor fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minoror medium injury.
NOTICE!
This symbol contains information on procedures and other facts which do not result in
personalinjury.
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
Ground connection
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
SymbolMeaning
1, 2, 3 ...Item numbers
Series of steps
4Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
A-A, B-B, C-C, ... Sections
SymbolMeaning
A, B, C, ...Views
Documentation
See chapter "Additional documentation" → 128
The document types listed are available:
In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download
Endress+Hauser5
Terms and abbreviations
URLOPLMWP
LRL
0
p
LRV
URV
1
2
3
4
Cerabar M PMC51, PMP51, PMP55
A0029505
Item Term/abbreviationExplanation
1OPLThe OPL (over pressure limit = sensor overload limit) for the measuring device depends on the lowest-rated element,
with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in
addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and
additional notes see the → 47 section.
The OPL may only be applied for a limited period of time.
2MWPThe MWP (maximum working pressure) for the sensors depends on the lowest-rated element, with regard to
pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the
measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes see
the → 47 section.
The MWP may be applied at the device for an unlimited period.
The MWP can also be found on the nameplate.
3Maximum sensor
measuring range
4Calibrated/adjusted
span
p-Pressure
-LRLLower range limit
-URLUpper range limit
-LRVLower range value
-URVUpper range value
-TD (Turn down)Turn down
Span between LRL and URL
This sensor measuring range is equivalent to the maximum calibratable/adjustable span.
Span between LRV and URV
Factory setting: 0 to URL
Other calibrated spans can be ordered as customized spans.
• Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)
• Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
TD =
URL
|URV-LRV|
10 bar (150 psi)
TD =
|5 bar (75 psi)-0 bar (0 psi)|
In this example, the TD is 2:1.
This span is based on the zero point.
= 2
Endress+Hauser7
Device selection
Cerabar M PMC51, PMP51, PMP55
Function and system design
A0023673
PMC51 with capacitive measuring cell and ceramic process isolating diaphragm (Ceraphire®)
A0023675
PMP51 with piezoresistive measuring cell and metal welded process isolating diaphragm
PMP55 with diaphragm seal
Field of application
• Gauge pressure and absolute pressure
• Level
Process connections
PMC51:
• Thread
• EN flanges DN 25 – DN 80
• ANSI flanges 1" – 4"
• JIS flanges 50 A – 100 A
• Flush mount hygienic connections
PMP51:
• Thread
• EN flanges DN 25 – DN 80
• ANSI flanges 1" – 4"
• Prepared for diaphragm seal mount
• Flush mount hygienic connections
PMP55:
Wide range of diaphragm seals
Measuring ranges
• PMC51: From –100/0 to 100 mbar (–1.5/0 to 1.5 psi) to –1/0 to 40 bar (–15/0 to 600 psi)
• PMP51: From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 400 bar (–15/0 to 6000 psi)
• PMP55: From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 400 bar (–15/0 to 6000 psi)
A0023676
8Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
OPL
• PMC51: max. 60 bar (900 psi)
• PMP51: max. 600 bar (9000 psi)
• PMP55: max. 600 bar (9000 psi)
Process temperature range
• PMC51: –20 to +130 °C (–4 to +266 °F)
For a maximum of 60 minutes: +150 °C (+302 °F)
• PMP51: –40 to +130 °C (–40 to +266 °F)
For a maximum of 60 minutes: +150 °C (+302 °F)
• PMP55: –70 to +400 °C (–94 to +752 °F)
(depending on the filling oil)
Ambient temperature range
• Without LCD: –40 to +85 °C (–40 to +185 °F)
• With LCD display: –20 to +70 °C (–4 to +158 °F)
(extended temperature application range–40 to +85 °C (–40 to +185 °F) with limitations in optical
properties, such as display speed and contrast)
• Separate housing:–20 to +60 °C (–4 to +140 °F)
• PMP55: Diaphragm seal systems depending on the version
Reference accuracy
• PMC51: up to ±0.10% of the set span
PLATINUM version: up to ±0.075% of the set span
• PMP51: up to ±0.10% of the set span
PLATINUM version: up to ±0.075% of the set span
• PMP55: up to ±0.10% of the set span
Supply voltage
• 11.5 to 45 V DC (versions with plug-in connection 35 V DC)
• For intrinsically safe device versions: 11.5 to 30 V DC
Output
4 to 20 mA, 4 to 20 mA with superimposed HART protocol, PROFIBUS PA or FOUNDATION Fieldbus
Options
• Inspection certificate 2.2 or 3.1 or other certificates
• 3A approval and EHEDG approval
• Specific firmware versions
• Initial device settings
• Separate housing
• Broad range of accessories
• NACE-compliant materials
Specialties
• PMC51:
• Metal-free measurement with PVDF connection
• Special cleaning of the transmitter to remove paint-wetting impairment substances, for use in
paint shops
• PMP51:
• Process connections with minimum oil volume
• Gas-tight, elastomer-free
• PMP55:
• Wide range of diaphragm seals
• For extreme medium temperatures
• Process connections with minimum oil volume
• Fully welded versions
Endress+Hauser9
Cerabar M PMC51, PMP51, PMP55
1
2
3
4
p
p
1
3
4
2
Measuring principle
Ceramic process isolating diaphragm used in PMC51 (Ceraphire®)
The ceramic sensor is a dry sensor, i.e. the process pressure acts directly on the robust ceramic
process isolating diaphragm and deflects it. A pressure-dependent change in capacitance is
measured at the electrodes of the ceramic substrate and the process isolating diaphragm. The
measuring range is determined by the thickness of the ceramic process isolating diaphragm.
Advantages:
• Guaranteed overload resistance up to 40 times the nominal pressure
• Thanks to ultrapure 99.9% ceramic (Ceraphire®, see also "www.endress.com/ceraphire")
• extremely high chemical stability, comparable with Alloy C
• high mechanical stability
• Can be used in absolute vacuum
Metallic process isolating diaphragm used in PMP51 and PMP55
A0016448
1Silicon measuring element, substrate
2Wheatstone bridge
3Channel with fill fluid
4Metallic process isolating diaphragm
PMP51
The operating pressure deflects the process isolating diaphragm and a fill fluid transfers the pressure
to a resistance bridge (semiconductor technology). The pressure-dependent change in the bridge
output voltage is measured and evaluated.
Advantages:
• Can be used for process pressure up to 400 bar (6000 psi)
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
• Significantly less thermal effect compared to diaphragm seal systems
10Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
h =
p
ρ g
h
Fieldgate
FXA520
FXN 520
FXN 520
Multidrop-Connector
FXN520
Cerabar M
Á
11
2
PMP55
The operating pressure acts on the process isolating diaphragm of the diaphragm seal and is
transferred to the process isolating diaphragm of the sensor by a diaphragm seal fill fluid. The
process isolating diaphragm is deflected and a fill fluid transfers the pressure to a resistance bridge.
The pressure-dependent change in the bridge output voltage is measured and evaluated.
Advantages:
• Depending on the version, can be used for process pressure up to 400 bar (6000 psi) and
simultaneous extreme process temperatures
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
Level measurement (level,
volume and mass)
Electrical differential
pressure measurement with
gauge pressure sensors
A0023678
hHeight (level)
pPressure
ρDensity of the medium
gGravitation constant
Your benefits
• Choice of different level measuring modes in the device software
• Volume and mass measurements in any tank shapes by means of a freely programmable
characteristic curve
• Choice of diverse level units
• Has a wide range of uses, even in the following cases:
• in the event of foam formation
• in tanks with agitators of screen fittings
• in the event of liquid gases
A0023680
1Shut-off valves
2e.g. filter
In the example given, two Cerabar M devices (each with a gauge pressure sensor) are
interconnected. The pressure difference can thus be measured using two independent Cerabar M
devices.
Endress+Hauser11
Cerabar M PMC51, PMP51, PMP55
WARNING
L
Risk of explosion!
If using intrinsically safe devices, strict compliance with the rules for interconnecting intrinsically
‣
safe circuits as stipulated in IEC60079-14 (proof of intrinsic safety) is mandatory.
Communication protocol
• 4 to 20 mA without communication protocol (analog electronics)
• 4 to 20 mA with HART communication protocol
• PROFIBUS PA
• The Endress+Hauser devices meet the requirements of the FISCO model.
• Due to a low current consumption of 11 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO: up to 8 devices for Ex ia, CSA IS and FM
IS applications or up to 31 devices for all other applications e.g. in non-hazardous areas, Ex nA
etc. Further information on PROFIBUS PA can be found in Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning" and in the PNO Guideline.
• FOUNDATION Fieldbus
• The Endress+Hauser devices meet the requirements of the FISCO model.
• Due to a low current consumption of 16 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO: up to 6 devices for Ex ia, CSA IS and FM
IS applications or up to 22 devices for all other applications e.g. in non-hazardous areas, Ex nA
etc. Further information on FOUNDATION Fieldbus, such as requirements for bus system
components, can be found in Operating Instructions BA00013S "FOUNDATION Fieldbus
Overview".
12Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
Input
Measured variableMeasured process variables
• Analog electronics: Absolute pressure and gauge pressure
• HART, PROFIBUS PA, FOUNDATION Fieldbus: Absolute pressure and gauge pressure, from which
level (level, volume or mass) is derived
Measuring rangePMC51 – with ceramic process isolating diaphragm (Ceraphire®) for gauge pressure
SensorMaximum sensor measuring range Smallest calibratable
1)Highest factory-configurable turn down: 20:1, higher available on request or can be set in device.
2)The vacuum resistance applies to the measuring cell at reference conditions. A ceramic process isolating diaphragm is recommended for
applications in the limit range. The pressure and temperature application limits of the selected filling oil must also be observed for the PMP55
→ 115.
3)Product Configurator, order code for "Sensor range"
Option
1F
3)
PMP51 and PMP55 – metallic process isolating diaphragm for absolute pressure
abs
3)
)]
SensorMaximum sensor
measuring
1)
lower (LRL)upper (URL)Silicone oil/
Lowest
calibratable
span (preset at
factory)
2)
MWPOPLVacuum resistance
Inert oil/
Synthetic oil
[bar
(psi
abs
abs
)]
[bar
abs
(psi
)] [bar (psi)][bar
abs
(psi
abs
abs
[bar
)]
(psi
abs
abs
)]
[bar
abs
(psi
400 mbar (6 psi) 0+0.4 (+6)0.02 (0.3)4 (60)6 (90)
1 bar (15 psi)0+1 (+15)0.05 (1)6.7 (100)10 (150)2H
2 bar (30 psi)0+2 (+30)0.1 (1.5)13.3 (200)20 (300)2K
4 bar (60 psi)0+4 (+60)0.2 (3)18.7 (280.5)28 (420)2M
10 bar (150 psi) 0+10 (+150)0.5 (7.5)26.7 (400.5)40 (600)2P
0.01/0.04/0.01
(0.15/0.6/0.15)
40 bar (600 psi) 0+40 (+600)2 (30)100 (1500)160 (2400)2S
100 bar
0+100 (+1500)5 (75)100 (1500)400 (6000)2U
(1500 psi)
400 bar
0+400 (+6000)20 (300)400 (6000)600 (9000)2W
(6000 psi)
1)PMP55: Within the sensor measuring range, the minimum upper range value of 80 mbar
(1.16 psi
abs
) must be observed.
abs
2)Highest factory-configurable turn down: 20:1, higher available on request or can be set in device.
3)The vacuum resistance applies to the measuring cell at reference conditions. A ceramic process isolating diaphragm is recommended for
applications in the limit range. The pressure and temperature application limits of the selected filling oil must also be observed for the PMP55
→ 115.
4)Product Configurator, order code for "Sensor range"
Option
2F
4)
14Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
U – 11.5 V
23 mA
[ ]W
30
20
11.5
40 45
1239
1456
804
369
£
U
[V]
1
2
R
L
max
3
R
L
max
Output
Output signal
Signal range 4 to 20 mA
Signal on alarm
• 4 to 20 mA analog, 2-wire
• 4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.02)
• Digital communication signal FOUNDATION Fieldbus
OutputOption
4 to 20mA1
4 to 20mA HART2
PROFIBUS PA3
FOUNDATION Fieldbus4
1)Product Configurator, "Output" ordering feature
4 to 20 mA Analog, 4 to 20 mA HART: 3.8 to 20.5 mA
As per NAMUR NE 43
• 4 to 20 mA Analog:
• Signal overshoot: > 20.5 mA
• Signal undershoot: < 3.8 mA
• Min Alarm (3.6 mA)
• 4 to 20 mA HART:
Options:
• Max. alarm: can be set from 21 to 23 mA (factory setting: 22 mA)
• Hold measured value: last measured value is held
• Min. alarm: 3.6 mA
• PROFIBUS PA: can be set in the Analog Input block
Options: Last Valid Out Value (factory setting), Fail-safe Value, Status Bad
• FOUNDATION Fieldbus: can be set in the Analog Input block
Options: Last Good Value, Fail-safe Value (factory setting), Wrong Value
1)
Load - 4 to 20 mA Analog
4...20 mA HART
A0023090
1Supply voltage 11.5 to 30 V DC for intrinsically safe device versions (not for analog)
2Supply voltage 11.5 to 45 V DC (versions with plug-in connector 35 V DC) for other types of protection and
for uncertified device versions
3R
USupply voltage
Maximum load resistance
Lmax
When operating via a handheld terminal or via a PC with an operating program, a minimum
Endress+Hauser15
communication resistance of 250 Ω must be taken into account.
Cerabar M PMC51, PMP51, PMP55
Damping
Firmware version
Protocol-specific data HART
A damping affects all outputs (output signal, display):
• Via on-site display, handheld terminal or PC with operating program, continuous from 0...999 s
• Via DIP-switch on the electronic insert, switch position
"on" (= set value) and "off" (= damping switched off)
Device description files (DTM, DD)Information and files can be found:
• www.endress.com
• www.fieldcommgroup.org
HART loadMin. 250 Ω
HART device variablesThe measured values can be freely assigned to the device variables:
Measured values for PV (primary variable)
• Pressure
• Level
• Tank content
Measured values for SV, TV (second and third variable)
• Pressure
• Level
Measured values for QV (fourth variable)
Temperature
Supported functions• Burst mode
• Additional Transmitter Status
• Device Locking
• Alternative operating modes
1)
Wireless HART data
Protocol-specific data
PROFIBUS PA
Minimum starting voltage11.5 V
Start-up current12 mA (default) or 22 mA (customer setting)
Starting time5 s
Minimum operating voltage11.5 V
Multidrop current4 mA
Time for connection setup1 s
1)Or higher if operating near ambient temperature limits (–40 to +85 °C (–40 to +185))
Manufacturer ID17 (11 hex)
Ident number1554 hex
Profile Version3.02
SW Version 01.00.zz
GSD Revision5
1)
1)
16Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
DD Revision1
GSD FileInformation and files can be found:
DD Files
Output valuesMeasured values for PV (via Analog Input Function Block)
Input valuesInput value sent from PLC, can be shown on display
Supported functions• Identification & Maintenance
• www.endress.com
• www.profibus.org
• Pressure
• Level
• Tank content
Measured values for SV
• Pressure
• Temperature
Simple device identification via control system and nameplate
• Condensed status
• Automatic ident number adaptation and switchable to following
ident numbers:
• 9700: Profile-specific transmitter identification number with the
"Classic" or "Condensed" status.
• 151C: Compatibility mode for the old Cerabar M (PMC41,
PMC45, PMP41, PMP45, PMP46, PMP48).
• 1553: Identification number for the new Cerabar M (PMC51,
PMP51 , PMP55).
• Device locking: The device can be locked by hardware or software.
Protocol-specific data
FOUNDATION Fieldbus
Device Type0x1019
Device Revision01 (hex)
DD Revision0x01021
Device description files (DTM, DD)Information and files can be found:
• www.endress.com
• www.fieldcommgroup.org
CFF Revision0x000102
ITK Version5.2.0
ITK-Certification Driver-No.IT067700
Link-Master (LAS) capableyes
Link Master / Basic Device selectableYes; Factory setting: Basic Device
Number of VCRs44
Number of Link Objects in VFD50
Number of FB-Schedule Objects40
Virtual communication references (VCRs)
Permanent Entries44
Client VCRs0
Server VCRs5
Source VCRs8
Sink VCRs0
Subscriber VCRs12
Publisher VCRs19
Endress+Hauser17
Cerabar M PMC51, PMP51, PMP55
Link settings
Slot time4
Min. Inter PDU delay12
Max. response delay40
Transducer Blocks
BlockContentOutput values
TRD1 BlockContains all parameters related to the
measurement
Diagnostic Block Contains diagnostic informationError code via DI channels (channel 10 to 15)
Display BlockContains parameters to configure the onsite
display
• Pressure or level (channel 1)
• Process temperature (channel 2)
• Measured pressure value (channel 3)
• Max. pressure (channel 4)
• Level before linearization (channel 5)
No output values
Function blocks
BlockContentNumber
of blocks
Resource BlockThe Resource Block contains all the data that uniquely identify the device. It is an
electronic version of a nameplate of the device.
Analog Input
Block 1
Analog Input
Block 2
Digital Input
Block
Digital Output
Block
PID BlockThe PID Block serves as a proportional-integralderivative controller and is used almost
Arithmetic Block This block is designed to permit simple use of popular measurement math functions.
Input Selector
Block
Signal
Characterizer
Block
Integrator Block The Integrator Block integrates a variable as a function of the time or accumulates the
The AI Block receives the measuring data from the Sensor Block, (selectable via a
channel number) and makes the data available to other function blocks at its output.
Enhancement: digital outputs for process alarms, fail safe mode.
This block contains the discrete data of the Diagnose Block (selectable via a channel
number 10 to 15) and provides them for other blocks at the output.
This block converts the discrete input and thus initiates an action (selectable via a
channel number) in the DP Flow Block or in the im TRD1 Block. Channel 20 resets the
counter for max. pressure transgressions value.
universally for closed-loop-control in the field including cascade and feedforward. Input
IN can be indicated on the display. The selection is performed in the Display Block
(DISPLAY_MAIN_LINE_CONTENT).
The user does not have to know how to write equations. The math algorithm is selected
by name, chosen by the user for the function to be performed.
The Input Selector Block facilitates the selection of up to four inputs and generates an
output based on the configured action. This block normally receives its inputs from AI
Blocks. The block performs maximum, minimum, average and ‘first good’ signal
selection. Inputs IN1 to IN4 can be indicated on the display. The selection is performed
in the Display Block (DISPLAY_MAIN_LINE_1_CONTENT).
DThe Signal Characterizer Block has two sections, each with an output that is a nonlinear function of the respective input. The non-linear function is generated by a single
look-up table with 21 arbitrary x-y pairs.
counts from a Pulse Input Block. The block may be used as a totalizer that counts up
until reset or as a batch totalizer that has a setpoint, where the integrated or
accumulated value is compared to pre-trip and trip settings, generating a binary signal
when the setpoint is reached.
1enhanced
225 msenhanced
120 msstandard
120 msstandard
140 msstandard
135 msstandard
130 msstandard
140 msstandard
135 msstandard
Execution
time
Functionality
18Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
Additional function block information:
Instantiate Function BlockYES
Number of additional instantiatable function blocks20
Endress+Hauser19
Terminal assignment
- +
1
2
3
4
5
6
7
Cerabar M PMC51, PMP51, PMP55
Power supply
WARNING
L
An incorrect connection compromises electrical safety!
When using the measuring device in hazardous areas, the relevant national standards and
‣
regulations as well as the Safety Instructions or Installation or Control Drawings must be
observed → 128.
All explosion protection data are given in separate documentation which is available upon
‣
request. The Ex documentation is supplied as standard with all Ex-systems → 128.
In accordance with IEC/EN61010 a suitable circuit breaker must be provided for the device.
‣
HART: Overvoltage protection HAW569-DA2B for the non-hazardous area, ATEX II 2 (1) Ex ia
‣
IIC and IEC Ex ia can be ordered as an option (see the "Ordering information" section).
Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
‣
1External grounding terminal (only for devices with certainly approvals or if "Measuring point" (TAG) is
2Internal grounding terminal
3Supply voltage → 20
44...20 mA for HART devices
5For HART and FOUNDATION Fieldbus devices: With a handheld terminal, all the parameters can be
6Terminals
7For HART devices: test terminals, see section "Taking 4 to 20 mA test signal" → 20
Supply voltage4 to 20 mA HART
Type of protectionSupply voltage
Intrinsically safe11.5 to 30 V DC
• Other types of protection
• Devices without certificate
Taking 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the test terminals without interrupting the
measurement.
PROFIBUS PA
Version for non-hazardous areas: 9 to 32 V DC
A0023505
ordered)
configured anywhere along the bus line via menu operation.
11.5 to 45 V DC
(versions with plug-in connection 35 V DC)
20Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
FOUNDATION Fieldbus
Version for non-hazardous areas: 9 to 32 V DC
Current consumption
Electrical connection
• PROFIBUS PA: 11 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 16 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Cable entryDegree of protectionOption
M20 glandIP66/67 NEMA 4X/6PA
G ½" threadIP66/67 NEMA 4X/6PC
NPT ½" threadIP66/67 NEMA 4X/6PD
M12 plugIP66/67 NEMA 4X/6PI
7/8" plugIP66/67 NEMA 4X/6PM
HAN7D plug 90 degIP65P
PE cable 5mIP66/68 NEMA4X/6P + pressure compensation via cableS
M16 valve connectorIP64V
1)Product Configurator, order code for "Electrical connection"
1)
PROFIBUS PA
The digital communication signal is transmitted over the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding, and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the PNO
Guideline.
Terminals
Cable entry
FOUNDATION Fieldbus
The digital communication signal is transmitted over the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
• Supply voltage and internal ground terminal: 0.5 to 2.5 mm2 (20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm2 (20 to 12 AWG)
ApprovalTypeClamping area
Standard, CSA GP
ATEX II1/2G or II2G Ex ia,
IEC Ex ia Ga/Gb or Ex ia Gb,
FM/ CSA IS
ATEX II1/2D Ex t, II1/2GD Ex ia,
II3G Ex nA,
IEC Ex t Da/Db
Plastic M20x1.55 to 10 mm (0.2 to 0.39 in)
Metal M20x1.5 (Ex e)7 to 10.5 mm (0.28 to 0.41 in)
For other technical data, see the housing section → 48
Endress+Hauser21
Device plugsDevices with valve connector (HART)
+
2 1
–
+
AB
BU BN GNYE
2
1
3
+
–
–
Han7D
+ –
–
+
AB
–
+
+
PE
–
1234
1BN = brown, BU = blue, GNYE = green
AElectrical connection for devices with valve connector
BView of the plug connector at the device
Material: PA 6.6
Cerabar M PMC51, PMP51, PMP55
A0023097
Devices with Harting plug Han7D (HART)
AElectrical connection for devices with Harting plug Han7D
BView of the plug-in connector at the device
Material: CuZn, contacts for plug-in jack and connector are gold-plated
Connecting the cable version (all device versions)
A0019990
1RD = red
2BK = black
3GNYE = green
44...20 mA
22Endress+Hauser
A0019991
Cerabar M PMC51, PMP51, PMP55
2
1
34
4
2
3
1
Devices with M12 plug(Analog, HART, PROFIBUS PA)
1Signal +
2Not assigned
3Signal –
4Ground
Endress+Hauser offers the following accessories for devices with an M12 plug:
Plug-in jack M 12x1, straight
• Material: body PA; coupling nut CuZn, nickel-plated
• Degree of protection (fully locked): IP66/67
• Order number: 52006263
Plug-in jack M 12x1, elbowed
• Material: body PBT/PA; coupling nut GD-Zn, nickel-plated
• Degree of protection (fully locked): IP66/67
• Order number: 71114212
Cable 4x0.34 mm2 (20 AWG) with M12 socket, elbowed, screw plug, length 5 m (16 ft)
• Material: body PUR; coupling nut CuSn/Ni; cable PVC
• Degree of protection (fully locked): IP66/67
• Order number: 52010285
A0011175
Devices with 7/8" plug (Analog, HART, FOUNDATION Fieldbus)
1Signal 2Signal +
3Not assigned
4Shield
External thread: 7/8 - 16 UNC
• Material: 316L (1.4401)
• Protection: IP66/68
Cable specificationAnalog
• Endress+Hauser recommends using twisted, shielded two-wire cables.
• The cable outer diameter depends on the cable entry used.
HART
• Endress+Hauser recommends using twisted, shielded two-wire cables.
• The cable outer diameter depends on the cable entry used.
A0011176
Endress+Hauser23
Cerabar M PMC51, PMP51, PMP55
1
2
3
4
+
-
+
-
rt
sw
+
-
A
B
PROFIBUS PA
Use a twisted, shielded two-wire cable, preferably cable type A
For further information on the cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092
PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Use a twisted, shielded two-wire cable, preferably cable type A
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Start-up current
Residual ripple
Influence of power supply
Overvoltage protection
(optional)
• Analog electronics:: 12 mA
• HART: 12 mA or 22 mA (selectable)
No influence on 4 to 20 mA signal up to ±5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)].
≤0.001 % of URL/V
The device can be fitted with overvoltage protection. The overvoltage protection is mounted at the
factory on the housing thread (M20x1.5) for the cable gland and is approx. 70 mm (2.76 in) in
length (take additional length into account when installing). The device is connected as illustrated in
the following graphic.
For details refer to TI01013KDE, XA01003KA3 and BA00304KA2.
Ordering information:
Product Configurator, "Mounted accessories" ordering feature, option NA
Wiring
AWithout direct shield grounding
BWith direct shield grounding
1Incoming connection cable
2HAW569-DA2B
3Unit to be protected
4Connection cable
24Endress+Hauser
A0023111
Cerabar M PMC51, PMP51, PMP55
Performance characteristics for measuring devices with
ceramic process isolating diaphragm
Response timeHART
• Acyclic: min. 330 ms, typically 590 ms (depending on command # and number of preambles)
• Cyclic (burst): min. 160 ms, typically 350 ms (depending on command # and number of
preambles)
PROFIBUS PA
• Acyclic: approx. 23 ms to 35 ms (depending on Min. Slave Interval)
• Cyclic: approx. 8 ms to 13 ms (depending on Min. Slave Interval)
FOUNDATION Fieldbus
• Acyclic: typically 70 ms (for standard bus parameter settings)
• Cyclic: max. 20 ms (for standard bus parameter settings)
Reference operating
conditions
Maximum measured error
(total performance)
• As per IEC 62828-2 / IEC 60770
• Ambient temperature TA = constant, in the range of +21 to +33 °C (+70 to +91 °F)
•
Humidity j = constant, in the range: 5 to 80 % RH ± 5 %
• Ambient pressure pA = constant, in the range: 860 to 1060 mbar (12.47 to 15.37 psi)
• Position of the measuring cell: horizontal ±1°
• Input of LOW SENSOR TRIM and HIGH SENSOR TRIM for lower range value and upper range value
• Zero based span
• Material of the process isolating diaphragm: Al2O3 aluminum oxide ceramic FDA, ultrapure 99.9 %
• Supply voltage: 24 V DC ±3 V DC
• Load with HART: 250 Ω
• Turn down (TD) = URL/|URV - LRV|
The performance characteristics refer to the accuracy of the measuring device. The factors
influencing accuracy can be divided into two groups
• Total performance of measuring device
• Installation factors
All performance characteristics are in conformance with ≥ ± 3 sigma.
The total performance of the measuring device comprises the reference accuracy and the ambient
temperature effect and is calculated using the following formula:
Total performance = ± √ ( (E1)² + (E2)²)
E1 = Reference accuracy
E2 = Temperature effect per ±28 °C (50 °F)
(corresponds to the range from –3 to +53 °C (+27 to +127 °F))
Calculation of E2:
E2 = E2M + E2
E2M = Main temperature error
E2E = Electronics error
The values refer to the calibrated span
E
Endress+Hauser25
Cerabar M PMC51, PMP51, PMP55
Calculation of the total performance with the Endress+Hauser Applicator
Detailed measured errors, such as for other temperature ranges, for example, can be calculated with
the Applicator "Sizing Pressure Performance".
A0038927
Reference accuracy [E1]
Reference accuracy comprises the non-linearity [IEC 62828-1 / DIN EN 61298-2] including the
hysteresis [IEC 62828-1 / DIN EN 61298-2] and the non-repeatability [IEC 62828-1 / DIN EN
61298-2] in accordance with the limit point method as per [IEC 62828-1 / DIN EN 60770-2].
Gauge pressure sensors
100 mbar (1.5 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.15 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
250 mbar (3.75 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi) and
10 bar (150 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.1 %
40 bar (600 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
Gauge pressure sensors with hygienic process connections
100 mbar (1.5 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.10 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
250 mbar (3.75 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi) and
10 bar (150 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.1 %
40 bar (600 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
Absolute pressure sensors
100 mbar (1.5 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.15 %; TD >10:1 to 20:1 = ±0.015 % · TD
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.015 % · TD
250 mbar (3.75 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi) and
10 bar (150 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.1 %
40 bar (600 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
26Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
Absolute pressure sensors with hygienic process connections
100 mbar (1.5 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.15 % · TD
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.015 % · TD
250 mbar (3.75 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi) and
10 bar (150 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.1 %
40 bar (600 psi) sensor
• Standard: TD 1:1 to 10:1 = ±0.1 %; TD >10:1 to 20:1 = ±0.2 %
• Platinum: TD 1:1 to 10:1 = ±0.075 %; TD >10:1 to 20:1 = ±0.0075 % · TD
Temperature effect [E2]
E2M - Main temperature error
The output changes due to the effect of the ambient temperature [IEC 62828-1 / IEC 61298-3] with
respect to the reference temperature [IEC 62828-1 / DIN 16086]. The values specify the maximum
error due to min./max. ambient or process temperature conditions.
1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• Standard: ±(0.157 % · TD + 0.235 %)
• Platinum: ±(0.157 % · TD + 0.235 %)
E2E - Electronics error
• Analog output (4 to 20 mA): 0.2 %
• Digital output (HART/PA/FF): 0 %
• Current output: 1 μA
• Display: can be set (factory setting: presentation of the maximum accuracy of the transmitter)
Endress+Hauser27
Cerabar M PMC51, PMP51, PMP55
Total error
The total error of the measuring device comprises the total performance and the influence of longterm stability and is calculated using the following formula:
Total error = total performance + long-term stability
Calculation of the total error with the Endress+Hauser Applicator
Detailed measured errors, such as for other temperature ranges, for example, can be calculated with
the Applicator "Sizing Pressure Performance".
A0038927
Calculation of the diaphragm seal error with the Endress+Hauser Applicator
Diaphragm seal errors are not taken into consideration. Diaphragm seal errors are calculated
separately in the Applicator "Sizing Diaphragm Seal".
Long-term stability
A0038925
The specifications refer to the upper range limit (URL).
400 mbar (6 psi) and 1 bar (15 psi) sensor
• 1 year: ±0.20 %
• 5 years: ±0.40 %
• 10 years: ±0.50 %
2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• 1 year: ±0.10 %
• 5 years: ±0.25 %
• 10 years: ±0.40 %
With hygienic process connections
400 mbar (6 psi) and 1 bar (15 psi) sensor
• 1 year: ±0.35 %
• 5 years: ±0.50 %
• 10 years: ±0.60 %
2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• 1 year: ±0.20 %
• 5 years: ±0.35 %
• 10 years: ±0.50 %
28Endress+Hauser
Cerabar M PMC51, PMP51, PMP55
I
63 %
t
t1t
2
90 %
t
3
Response time T63 and T90Dead time, time constant
Presentation of the dead time and the time constant as per DIN 16086:
Dynamic behavior, current output (analog electronics)
Dead time (t1)Time constant T63 (= t2)Time constant T90 (= t3)
Max.60 ms40 ms50 ms
A0019786
Dynamic behavior, current output (HART electronics)
Dead time (t1)Time constant T63 (= t2)Time constant T90 (= t3)
Max.50 ms85 ms200 ms
Dynamic behavior, digital output (HART electronics)
Dead time (t1)Dead time (t1) +
Time constant T63 (= t2)
min.210 ms295 ms360 ms
Max.1010 ms1095 ms1160 ms
Dead time (t1) +
Time constant T90 (= t3)
Reading cycle
• Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)
• Cyclic (burst): max. 3/s, typical 2/s
The device commands the BURST MODE function for cyclic value transmission via the HART
communication protocol.
Cycle time (update time)
Cyclic (burst): min. 300 ms
Endress+Hauser29
Dynamic behavior, PROFIBUS PA
Cerabar M PMC51, PMP51, PMP55
Dead time (t1)Dead time (t1) +
Time constant T63 (= t2)
min.85 ms170 ms235 ms
Max.1185 ms1270 ms1335 ms
Dead time (t1) +
Time constant T90 (= t3)
Reading cycle (PLC)
• Acyclic: typically 25/s
• Cyclic: typically 30/s (dependent on the number and type of function blocks used in a closedcontrol loop)
Cycle time (update time)
min. 100 ms
The cycle time in a bus segment in cyclic data communication depends on the number of devices, on
the segment coupler used and on the internal PLC cycle time.
Dynamic behavior, FOUNDATION Fieldbus
Dead time (t1)Dead time (t1) +
Time constant T63 (= t2)
min.95 ms180 ms245 ms
Max.1095 ms1180 ms1245 ms
Dead time (t1) +
Time constant T90 (= t3)
Reading cycle
• Acyclic: typically 5/s
• Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control
loop)
Cycle time (update time)
Cyclic: min. 100 ms
30Endress+Hauser
Loading...
+ 104 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.