In the electromagnetic measuring principle, the flowing medium is the moving conductor. The
voltage induced (Ue) is proportional to the flow velocity (v) and is supplied to the amplifier by means
of two measuring electrodes. The flow volume (Q) is calculated via the pipe cross-section (A). The DC
magnetic field is created through a switched direct current of alternating polarity.
Formulae for calculation
• Induced voltage Ue = B · L · v
• Volume flow Q = A · v
Endress+Hauser5
Page 6
Proline Promag P 300
Measuring system
The device consists of a transmitter and a sensor.
The device is available as a compact version:
The transmitter and sensor form a mechanical unit.
• Material of window in transmitter housing:
Aluminum, coated: glass
Configuration:
• External operation via 4-line, backlit, graphic local display with touch
A0026708
control and guided menus ("Make-it-run" wizards) for applicationspecific commissioning.
• Via service interface or WLAN interface:
– Operating tools (e.g. FieldCare, DeviceCare, SmartBlue app)
– Web server (access via Web browser, e.g. Microsoft Internet
Explorer, Microsoft Edge)
Sensor
Promag PNominal diameter range: DN 15 to 600 (½ to 24")
Materials:
• Sensor housing:
– Aluminum, AlSi10Mg, coated
– DN 15 to 300 (½ to 12"): aluminum, AlSi10Mg, coated
– DN 350 to 600 (14 to 24"): carbon steel with protective varnish
1)For flanges made of carbon steel with Al/Zn protective coating (DN 15 to 300 (½ to 12")) or protective
varnish (DN 350 to 600 (14 to 24"))
2)With Al/Zn protective coating (DN 15 to 300 (½ to 12")) or protective varnish (DN 350 to 600 (14 to 24"))
6Endress+Hauser
Page 7
Proline Promag P 300
2
1
6
5
7
4
3
3
Equipment architecture
A0027512
1Possibilities for integrating measuring devices into a system
1Control system (e.g. PLC)
2Connecting cable (0/4 to 20 mA HART etc.)
3Fieldbus
4Segment coupler
5Non-hazardous area
6Hazardous area: Zone 2; Class I, Division 2
7Hazardous area: Zone 1; Class I, Division 1
SafetyIT security
Our warranty is valid only if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any inadvertent
changes to the settings.
IT security measures, which provide additional protection for the device and associated data transfer,
must be implemented by the operators themselves in line with their security standards.
Device-specific IT security
The device offers a range of specific functions to support protective measures on the operator's side.
These functions can be configured by the user and guarantee greater in-operation safety if used
correctly. An overview of the most important functions is provided in the following section.
Function/interfaceFactory settingRecommendation
Write protection via hardware write
protection switch → 8
Access code
(also applies for Web server login or
FieldCare connection) → 8
WLAN
(order option in display module)
WLAN security modeEnabled (WPA2-
WLAN passphrase
(password) → 8
WLAN modeAccess PointOn an individual basis following risk
Web server→ 8Enabled.On an individual basis following risk
CDI-RJ45 service interface → 9–On an individual basis following risk
Not enabled.On an individual basis following risk
assessment.
Not enabled
(0000).
Enabled.On an individual basis following risk
PSK)
Serial numberAssign a customized access code during
Assign a customized access code during
commissioning.
assessment.
Do not change.
commissioning.
assessment.
assessment.
assessment.
Endress+Hauser7
Page 8
Proline Promag P 300
Protecting access via hardware write protection
Write access to the device parameters via the local display, Web browser or operating tool (e.g.
FieldCare, DeviceCare) can be disabled via a write protection switch (DIP switch on the
motherboard). When hardware write protection is enabled, only read access to the parameters is
possible.
Hardware write protection is disabled when the device is delivered.
Protecting access via a password
Different passwords are available to protect write access to the device parameters or access to the
device via the WLAN interface.
• User-specific access code
Protect write access to the device parameters via the local display, Web browser or operating tool
(e.g. FieldCare, DeviceCare). Access authorization is clearly regulated through the use of a userspecific access code.
• WLAN passphrase
The network key protects a connection between an operating unit (e.g. notebook or tablet) and the
device via the WLAN interface which can be ordered as an option.
• Infrastructure mode
When the device is operated in infrastructure mode, the WLAN passphrase corresponds to the
WLAN passphrase configured on the operator side.
User-specific access code
Write access to the device parameters via the local display, Web browser or operating tool (e.g.
FieldCare, DeviceCare) can be protected by the modifiable, user-specific access code.
WLAN passphrase: Operation as WLAN access point
A connection between an operating unit (e.g. notebook or tablet) and the device via the WLAN
interface, which can be ordered as an optional extra, is protected by the network key. The WLAN
authentication of the network key complies with the IEEE 802.11 standard.
When the device is delivered, the network key is pre-defined depending on the device. It can be
changed via the WLAN settings submenu in the WLAN passphrase parameter.
Infrastructure mode
A connection between the device and WLAN access point is protected by means of an SSID and
passphrase on the system side. Please contact the relevant system administrator for access.
General notes on the use of passwords
• The access code and network key supplied with the device should be changed during
commissioning.
• Follow the general rules for generating a secure password when defining and managing the access
code or network key.
• The user is responsible for the management and careful handling of the access code and network
key.
Access via Web server
The device can be operated and configured via a Web browser with the integrated Web server. The
connection is via the service interface (CDI-RJ45) or the WLAN interface. For device versions with
the EtherNet/IP and PROFINET communication protocols, the connection can also be established via
the terminal connection for signal transmission with EtherNet/IP or PROFINET (RJ45 connector).
The Web server is enabled when the device is delivered. The Web server can be disabled if necessary
(e.g. after commissioning) via the Web server functionality parameter.
The device and status information can be hidden on the login page. This prevents unauthorized
access to the information.
For detailed information on device parameters, see:
The "Description of Device Parameters" document → 92
Access via OPC-UA
The "OPC UA Server" application package is available in the device version with the HART
communication protocol → 89.
8Endress+Hauser
Page 9
Proline Promag P 300
The device can communicate with OPC UA clients using the "OPC UA Server" application package.
The OPC UA server integrated in the device can be accessed via the WLAN access point using the
WLAN interface - which can be ordered as an optional extra - or the service interface (CDI- RJ45) via
Ethernet network. Access rights and authorization as per separate configuration.
The following Security Modes are supported as per the OPC UA Specification (IEC 62541):
• None
• Basic128Rsa15 – signed
• Basic128Rsa15 – signed and encrypted
Access via service interface (CDI-RJ45)
The device can be connected to a network via the service interface (CDI-RJ45). Device-specific
functions guarantee the secure operation of the device in a network.
The use of relevant industrial standards and guidelines that have been defined by national and
international safety committees, such as IEC/ISA62443 or the IEEE, is recommended. This includes
organizational security measures such as the assignment of access authorization as well as technical
measures such as network segmentation.
The device can be integrated in a ring topology. The device is integrated via the terminal
connection for signal transmission (output 1) and the connection to the service interface (CDIRJ45) → 78.
Input
Measured variableDirect measured variables
• Volume flow (proportional to induced voltage)
• Electrical conductivity
Calculated measured variables
• Mass flow
• Corrected volume flow
Measuring range
Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy
Flow characteristic values in SI units: DN 15 to 125 (½ to 4")
Nominal
diameter
[mm][in][dm3/min][dm3/min][dm3][dm3/min]
15½4 to 100250.20.5
2519 to 300750.51
32–15 to 50012512
401 ½25 to 7002001.53
50235 to 11003002.55
65–60 to 200050058
80390 to 3000750512
1004145 to 470012001020
125–220 to 750018501530
Recommended
min./max. full scale value
(v ~ 0.3/10 m/s)
flow
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
Endress+Hauser9
Page 10
Flow characteristic values in SI units: DN 150 to 600 (6 to 24")
Proline Promag P 300
Nominal
diameter
[mm][in][m3/h][m3/h][m3][m3/h]
150620 to 6001500.032.5
200835 to 11003000.055
2501055 to 17005000.057.5
3001280 to 24007500.110
35014110 to 330010000.115
40016140 to 420012000.1520
45018180 to 540015000.2525
50020220 to 660020000.2530
60024310 to 960025000.340
Recommended
flow
min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
Flow characteristic values in US units
Nominal
diameter
[in][mm][gal/min][gal/min][gal][gal/min]
½151.0 to 2760.10.15
1252.5 to 80180.20.25
1 ½407 to 190500.50.75
25010 to 300750.51.25
38024 to 80020022.5
410040 to 125030024
615090 to 2650600512
8200155 to 485012001015
10250250 to 750015001530
12300350 to 1060024002545
14350500 to 1500036003060
16400600 to 1900048005060
18450800 to 2400060005090
205001000 to 30000750075120
246001400 to 4400010500100180
Recommended
flow
min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
To calculate the measuring range, use the Applicator sizing tool → 91
Recommended measuring range
"Flow limit" section → 53
Operable flow range
Over 1000 : 1
10Endress+Hauser
Page 11
Proline Promag P 300
Input signalInput and output versions
→ 12
External measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device:
• Medium temperature to increase the accuracy of the electrical conductivity (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
Various pressure transmitters and temperature measuring devices can be ordered from Endress
+Hauser: see "Accessories" section → 91
It is recommended to read in external measured values to calculate the corrected volume flow.
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Current input
The measured values are written from the automation system to the measuring device via the
current input → 11.
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS DP
• PROFIBUS PA
• Modbus RS485
• EtherNet/IP
• PROFINET
Current input 0/4 to 20 mA
Current input0/4 to 20 mA (active/passive)
Current span• 4 to 20 mA (active)
• 0/4 to 20 mA (passive)
Resolution1 µA
Voltage dropTypically: 0.6 to 2 V for 3.6 to 22 mA (passive)
Maximum input voltage≤ 30 V (passive)
Open-circuit voltage≤ 28.8 V (active)
Possible input variables• Pressure
• Temperature
• Density
Status input
Maximum input values• DC –3 to 30 V
• If status input is active (ON): Ri >3 kΩ
Response timeAdjustable: 5 to 200 ms
Input signal level• Low signal: DC –3 to +5 V
• High signal: DC 12 to 30 V
Assignable functions• Off
• Reset the individual totalizers separately
• Reset all totalizers
• Flow override
Endress+Hauser11
Page 12
Output
Proline Promag P 300
Output and input variants
Depending on the option selected for output/input 1, different options are available for the other
outputs and inputs. Only one option can be selected for each output/input 1 to 3. The table must be
read vertically (↓).
Example: If the option BA "4–20 mA HART" was selected for output/input 1, one of the options A, B,
D, E, F, H, I or J is available for output 2 and one of the options A, B, D, E, F, H, I or J is available for
output 3.
Order code for "Output; input 1" (020) →Possible options
Current output 4 to 20 mA HARTBA
Current output 4 to 20 mA HART Ex i↓CA
FOUNDATION Fieldbus↓SA
FOUNDATION Fieldbus Ex i↓TA
PROFIBUS DP↓LA
PROFIBUS PA↓GA
PROFIBUS PA Ex i↓HA
Modbus RS485↓MA
EtherNet/IP 2-port switch integrated↓NA
PROFINET 2-port switch integrated↓RA
Order code for "Output; input 2" (021) →↓↓↓↓↓↓↓↓↓↓
Not assignedAAAAAAAAAA
Current output 0/4 to 20 mABBBBBBB
Current output 0/4 to 20 mA (Ex i)CCC
User configurable input/output
Pulse/frequency/switch outputEEEEEEE
Double pulse output
Pulse/frequency/switch output (Ex i)GGG
Relay outputHHHHHHH
Current input 0/4 to 20 mAIIIIIII
Status inputJJJJJJJ
Order code for "Output; input 3" (022) →↓↓↓↓↓↓↓↓↓↓
Not assignedAAAAAAAAAA
Current output 0/4 to 20 mABBBBB
Current output 0/4 to 20 mA (Ex i)C
User configurable input/outputDDDDD
Pulse/frequency/switch outputEEEEE
Double pulse output (slave)FF
Pulse/frequency/switch output (Ex i)G
Relay outputHHHHH
Current input 0/4 to 20 mAIIIII
Status inputJJJJJ
2)
1)
DDDDDDD
FF
1)A specific input or output can be assigned to a user configurable input/output → 16.
2)If double pulse output (F) is selected for output/input 2 (021), only the double pulse output (F) option is available for selection for output/input 3
(022).
12Endress+Hauser
Page 13
Proline Promag P 300
Output signalHART current output
Current output4 to 20 mA HART
Current spanCan be set to: 4 to 20 mA (active/passive)
Open-circuit voltageDC 28.8 V (active)
Maximum input voltageDC 30 V (passive)
Load250 to 700 Ω
Resolution0.38 µA
DampingConfigurable: 0.07 to 999 s
Assignable measured
variables
Ex-i, passive
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Electronic temperature
PROFIBUS PA
PROFIBUS PAIn accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically
isolated
Data transmission31.25 kbit/s
Current consumption10 mA
16 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
PROFIBUS DP
Signal encodingNRZ code
Data transfer9.6 kBaud…12 MBaud
EtherNet/IP
StandardsIn accordance with IEEE 802.3
PROFINET
StandardsIn accordance with IEEE 802.3
FOUNDATION Fieldbus
FOUNDATION FieldbusH1, IEC 61158-2, galvanically isolated
Data transfer31.25 kbit/s
Current consumption10 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
Endress+Hauser13
Page 14
Modbus RS485
Physical interfaceRS485 in accordance with EIA/TIA-485 standard
Terminating resistorIntegrated, can be activated via DIP switches
Current output 0/4 to 20 mA
Current output0/4 to 20 mA
Maximum output values22.5 mA
Current spanCan be set to:
• 4 to 20 mA (active)
• 0/4 to 20 mA (passive)
Ex-i, passive
Open-circuit voltageDC 28.8 V (active)
Maximum input voltageDC 30 V (passive)
Load0 to 700 Ω
Resolution0.38 µA
DampingAdjustable: 0.07 to 999 s
Assignable measured
variables
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Temperature
• Electronic temperature
Proline Promag P 300
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionOpen collector
Can be set to:
• Active
• Passive
Ex-i, passive
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Voltage dropFor 22.5 mA: ≤ DC 2 V
Pulse output
Maximum input valuesDC 30 V, 250 mA (passive)
Maximum output current22.5 mA (active)
Open-circuit voltageDC 28.8 V (active)
Pulse widthAdjustable: 0.05 to 2000 ms
Maximum pulse rate10000 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
• Volume flow
• Mass flow
• Corrected volume flow
14Endress+Hauser
Page 15
Proline Promag P 300
Maximum input valuesDC 30 V, 250 mA (passive)
Maximum output current22.5 mA (active)
Open-circuit voltageDC 28.8 V (active)
Output frequencyAdjustable: end value frequency 2 to 10000 Hz (f
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
Switch output
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
Number of switching
cycles
Assignable functions• Off
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Temperature
• Electronic temperature
Unlimited
• On
• Diagnostic behavior
• Limit value:
– Off
– Volume flow
– Mass flow
– Corrected volume flow
– Flow velocity
– Conductivity
– Corrected conductivity
– Totalizer 1-3
– Temperature
– Electronic temperature
• Flow direction monitoring
• Status
– Empty pipe detection
– Low flow
= 12500 Hz)
max
Double pulse output
FunctionDouble pulse
VersionOpen collector
Can be set to:
• Active
• Passive
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Voltage dropFor 22.5 mA: ≤ DC 2 V
Output frequencyAdjustable: 0 to 1000 Hz
DampingAdjustable: 0 to 999 s
Endress+Hauser15
Page 16
Pulse/pause ratio1:1
Assignable measured
variables
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Temperature
• Electronic temperature
Relay output
FunctionSwitch output
VersionRelay output, galvanically isolated
Switching behaviorCan be set to:
• NO (normally open), factory setting
• NC (normally closed)
Maximum switching
capacity (passive)
Assignable functions• Off
• DC 30 V, 0.1 A
• AC 30 V, 0.5 A
• On
• Diagnostic behavior
• Limit value:
– Off
– Volume flow
– Mass flow
– Corrected volume flow
– Flow velocity
– Conductivity
– Corrected conductivity
– Totalizer 1-3
– Temperature
– Electronic temperature
• Flow direction monitoring
• Status
– Empty pipe detection
– Low flow
Proline Promag P 300
User configurable input/output
One specific input or output is assigned to a user-configurable input/output (configurable I/O)
during device commissioning.
The following inputs and outputs are available for assignment:
• Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Pulse/frequency/switch output
• Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Status input
The technical values correspond to those of the inputs and outputs described in this section.
Signal on alarm
Depending on the interface, failure information is displayed as follows:
HART current output
Device diagnosticsDevice condition can be read out via HART Command 48
16Endress+Hauser
Page 17
Proline Promag P 300
PROFIBUS PA
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
PROFIBUS DP
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
EtherNet/IP
Device diagnosticsDevice condition can be read out in Input Assembly
PROFINET
Device diagnosticsAccording to "Application Layer protocol for decentralized periphery", Version 2.3
FOUNDATION Fieldbus
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-891
0 mA
Modbus RS485
Failure modeChoose from:
• NaN value instead of current value
• Last valid value
Current output 0/4 to 20 mA
4 to 20 mA
Failure modeChoose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
0 to 20 mA
Failure modeChoose from:
• Maximum alarm: 22 mA
• Freely definable value between: 0 to 20.5 mA
Endress+Hauser17
Page 18
Pulse/frequency/switch output
Pulse output
Failure modeChoose from:
• Actual value
• No pulses
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value (f
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
Relay output
Failure modeChoose from:
• Current status
• Open
• Closed
2 to 12500 Hz)
max
Proline Promag P 300
Local display
Plain text displayWith information on cause and remedial measures
BacklightRed backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
– HART protocol
– FOUNDATION Fieldbus
– PROFIBUS PA
– PROFIBUS DP
– Modbus RS485
– EtherNet/IP
– PROFINET
• Via service interface
– CDI-RJ45 service interface
– WLAN interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 75
Web server
Plain text displayWith information on cause and remedial measures
18Endress+Hauser
Page 19
Proline Promag P 300
Light emitting diodes (LED)
Status informationStatus indicated by various light emitting diodes
Ex connection dataSafety-related values
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• EtherNet/IP network available
• EtherNet/IP connection established
• PROFINET network available
• PROFINET connection established
• PROFINET blinking feature
Order code for
Output typeSafety-related values
"Output; input 1"
Option BACurrent output
4 to 20 mA HART
UN = 30 V
UM = 250 V
Option GAPROFIBUS PAUN = 30 V
UM = 250 V
Option LAPROFIBUS DPUN = 30 V
UM = 250 V
Option MAModbus RS485UN = 30 V
UM = 250 V
Option SAFOUNDATION FieldbusUN = 30 V
UM = 250 V
Option NAEtherNet/IPUN = 30 V
UM = 250 V
Option RAPROFINETUN = 30 V
UM = 250 V
Order code for
"Output; input 2";
"Output; input 3"
Output typeSafety-related values
Output; input 2Output; input 3
24 (+)25 (–)22 (+)23 (–)
Option BCurrent output
4 to 20 mA
Option DUser configurable input/
output
Option EPulse/frequency/switch
output
UN = 30 V
UM = 250 V
UN = 30 V
UM = 250 V
UN = 30 V
UM = 250 V
Option FDouble pulse outputUN = 30 V
UM = 250 V
Option HRelay outputUN = 30 V
IN =100 mADC/500 mA
UM = 250 V
Option ICurrent input 4 to 20 mAUN = 30 V
UM = 250 V
Option JStatus inputUN = 30 V
UM = 250 V
"Output; input 1"
26 (+)27 (–)
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
AC
DC
AC
DC
AC
Endress+Hauser19
Page 20
Intrinsically safe values
Proline Promag P 300
Order code for
"Output; input 1"
Option CACurrent output
Option HAPROFIBUS PA Ex iEx ia
Option TAFOUNDATION Fieldbus
1)Only available for the Zone 1; Class I, Division 1 version
2)Only available for the Zone 2; Class I, Division 2 version transmitter
Order code for
"Output; input 2";
"Output; input 3"
Option CCurrent output
Option GPulse/frequency/switch
Output typeIntrinsically safe values
26 (+)27 (–)
Ui = 30 V
4 to 20 mA HART Ex i
Ex i
Output typeIntrinsically safe values or NIFW values
4 to 20 mA Ex i
output Ex i
li = 100 mA
Pi = 1.25 W
Li = 0
Ci = 0
1)
Ui = 30 V
li = 570 mA
Pi = 8.5 W
Li = 10 µH
Ci = 5 nF
1)
Ex ia
Ui = 30 V
li = 570 mA
Pi = 8.5 W
Li = 10 µH
Ci = 5 nF
Output; input 2Output; input 3
24 (+)25 (–)22 (+)23 (–)
Ui = 30 V
li = 100 mA
Pi = 1.25 W
Li = 0
Ci = 0
Ui = 30 V
li = 100 mA
Pi = 1.25 W
Li = 0
Ci = 0
"Output; input 1"
2)
Ex ic
Ui = 32 V
li = 570 mA
Pi = 8.5 W
Li = 10 µH
Ci = 5 nF
2)
Ex ic
Ui = 32 V
li = 570 mA
Pi = 8.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are user-selectable.
The outputs are galvanically isolated from one another and from earth (PE).
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x3C
HART protocol revision7
Device description files
(DTM, DD)
HART loadMin. 250 Ω
System integrationInformation on system integration: Operating Instructions → 92.
Information and files under:
www.endress.com
• Measured variables via HART protocol
• Burst Mode functionality
20Endress+Hauser
Page 21
Proline Promag P 300
PROFIBUS PA
Manufacturer ID0x11
Ident number0x156C
Profile version3.02
Device description files (GSD,
DTM, DD)
Supported functions• Identification & Maintenance
Configuration of the device
address
Compatibility with
earlier model
System integrationInformation regarding system integration: Operating Instructions → 92.
Information and files under:
• www.endress.com
• www.profibus.org
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e.g. FieldCare)
If the device is replaced, the measuring device Promag 300 supports the
compatibility of the cyclic data with previous models. It is not necessary to
adjust the engineering parameters of the PROFIBUS network with the Promag
300 GSD file.
Earlier models:
• Promag 50 PROFIBUS PA
– ID No.: 1525 (hex)
– Extended GSD file: EH3x1525.gsd
– Standard GSD file: EH3_1525.gsd
• Promag 53 PROFIBUS PA
– ID No.: 1527 (hex)
– Extended GSD file: EH3x1527.gsd
– Standard GSD file: EH3_1527.gsd
Description of the function scope of compatibility:
Operating Instructions → 92.
• Cyclic data transmission
• Block model
• Description of the modules
PROFIBUS DP
Manufacturer ID0x11
Ident number0x1570
Profile version3.02
Device description files (GSD,
DTM, DD)
Supported functions• Identification & Maintenance
Information and files under:
• www.endress.com
On the product page for the device: Documents/Software → Device drivers
• www.profibus.org
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
Endress+Hauser21
Page 22
Proline Promag P 300
Configuration of the device
address
System integrationInformation regarding system integration: Operating Instructions → 92.
• DIP switches on the I/O electronics module
• Via operating tools (e.g. FieldCare)
• Cyclic data transmission
• Block model
• Description of the modules
EtherNet/IP
Protocol• The CIP Networks Library Volume 1: Common Industrial Protocol
• The CIP Networks Library Volume 2: EtherNet/IP Adaptation of CIP
Communication type• 10Base-T
• 100Base-TX
Device profileGeneric device (product type: 0x2B)
Manufacturer ID0x11
Device type ID0x103C
Baud ratesAutomatic ¹⁰⁄₁₀₀ Mbit with half-duplex and full-duplex detection
PolarityAuto-polarity for automatic correction of crossed TxD and RxD pairs
Supported CIP connectionsMax. 3 connections
Explicit connectionsMax. 6 connections
I/O connectionsMax. 6 connections (scanner)
Configuration options for
measuring device
Configuration of the EtherNet
interface
Configuration of the device
address
Device Level Ring (DLR)Yes
System integrationInformation regarding system integration: Operating Instructions
• DIP switches on the electronics module for IP addressing
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• Electronic Data Sheet (EDS) integrated in the measuring device
• Speed: 10 MBit, 100 MBit, auto (factory setting)
• Duplex: half-duplex, full-duplex, auto (factory setting)
• DIP switches on the electronics module for IP addressing (last octet)
• DHCP
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• EtherNet/IP tools, e.g. RSLinx (Rockwell Automation)
→ 92.
• Cyclic data transmission
• Block model
• Input and output groups
PROFINET
Protocol"Application layer protocol for decentral device periphery and distributed
automation", version 2.3
Communication type100 MBit/s
Conformity classConformance Class B
Netload ClassNetload Class II
Baud ratesAutomatic 100 Mbit/s with full-duplex detection
Cycle timesFrom 8 ms
PolarityAuto-polarity for automatic correction of crossed TxD and RxD pairs
Response times• Direct data access: typically 25 to 50 ms
• Auto-scan buffer (data range): typically 3 to 5 ms
Device typeSlave
Slave address range1 to 247
Broadcast address range0
Function codes• 03: Read holding register
• 04: Read input register
• 06: Write single registers
• 08: Diagnostics
• 16: Write multiple registers
• 23: Read/write multiple registers
Broadcast messagesSupported by the following function codes:
• 06: Write single registers
• 16: Write multiple registers
• 23: Read/write multiple registers
24Endress+Hauser
Page 25
Proline Promag P 300
Supported baud rate• 1200 BAUD
• 2400 BAUD
• 4800 BAUD
• 9600 BAUD
• 19200 BAUD
• 38400 BAUD
• 57600 BAUD
• 115200 BAUD
Data transfer mode• ASCII
• RTU
Data accessEach device parameter can be accessed via Modbus RS485.
For Modbus register information
Compatibility with
earlier model
System integrationInformation on system integration: Operating Instructions → 92.
If the device is replaced, the measuring device Promag 300 supports the
compatibility of the Modbus registers for the process variables and the
diagnostic information with the previous model Promag 53. It is not necessary
to change the engineering parameters in the automation system.
Description of the function scope of compatibility:
Terminal assignment of the remote display and operating module → 31.
Device plugs may not be used in hazardous areas!
Device plugs for fieldbus systems:
Order code for "Input; output 1"
• Option SA "FOUNDATION Fieldbus" → 26
• Option GA "PROFIBUS PA" → 26
• Option RA "PROFINET" → 27
• Option NA "EtherNet/IP" → 27
Device plug for connecting to the service interface:
Order code for "Accessory mounted"
option NB, adapter RJ45 M12 (service interface) → 28
Order code for "Input; output 1", option SA "FOUNDATION Fieldbus"
Order code forCable entry/connection → 30
"Electrical connection"23
M, 3, 4, 57/8" connector–
Order code for "Input; output 1", option GA "PROFIBUS PA"
Order code forCable entry/connection → 30
"Electrical connection"23
L, N, P, UConnector M12 × 1–
26Endress+Hauser
Page 27
Proline Promag P 300
1
2
4
3
1
2
4
3
Order code for "Input; output 1", option RA "PROFINET"
Order code forCable entry/connection → 30
"Electrical connection"23
L, N, P, UConnector M12 × 1–
1) 2)
1) 2)
1) 2)
R
, S
, T
, V
1) 2)
Connector M12 × 1Connector M12 × 1
1)Cannot be combined with an external WLAN antenna (order code for "Enclosed accessories", option P8) of
an RJ45 M12 adapter for the service interface (order code for "Accessories mounted", option NB) or of the
remote display and operating module DKX001.
2)Suitable for integrating the device in a ring topology.
Order code for "Input; output 1", option NA "EtherNet/IP"
Order code forCable entry/connection → 30
"Electrical connection"23
L, N, P, UConnector M12 × 1–
1) 2)
1) 2)
1) 2)
R
, S
, T
, V
1) 2)
Connector M12 × 1Connector M12 × 1
1)Cannot be combined with an external WLAN antenna (order code for "Enclosed accessories", option P8) of
an RJ45 M12 adapter for the service interface (order code for "Accessories mounted", option NB) or of the
remote display and operating module DKX001
2)Suitable for integrating the device in a ring topology.
Order code for "Accessory mounted", option NB "Adapter RJ45 M12 (service interface)"
Order codeCable entry/coupling → 30
"Accessory mounted"Cable entry
NBPlug M12 × 1–
Pin assignment, device plugFOUNDATION Fieldbus
PROFIBUS PA
Cable entry
2
3
PinAssignmentCodingPlug/socket
1+Signal +APlug
2-Signal –
3Grounding
4Not assigned
PinAssignmentCodingPlug/socket
1+PROFIBUS PA +APlug
2Grounding
3-PROFIBUS PA –
4Not assigned
Endress+Hauser27
Page 28
PROFINET
3
2
4
3
2
4
3
2
4
PinAssignment
1+TD +
2+RD +
3-TD –
4-RD –
A0032047
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.
CodingPlug/socket
DSocket
EtherNet/IP
PinAssignment
1+Tx
2+Rx
3-Tx
4-Rx
A0032047
CodingPlug/socket
DSocket
Proline Promag P 300
Supply voltage
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.
Service interface
Order code for "Accessories mounted", option NB: Adapter RJ45 M12 (service interface)
PinAssignment
1+Tx
2+Rx
3-Tx
4-Rx
A0032047
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.
Order code for
"Power supply"
Option DDC24 V±20%–
Option EAC100 to 240 V –15…+10%50/60 Hz, ±4 Hz
Option I
CodingPlug/socket
DSocket
terminal voltageFrequency range
DC24 V±20%–
AC100 to 240 V –15…+10%50/60 Hz, ±4 Hz
28Endress+Hauser
Page 29
Proline Promag P 300
Power consumptionTransmitter
Max. 10 W (active power)
Current consumptionTransmitter
• Max. 400 mA (24 V)
• Max. 200 mA (110 V, 50/60 Hz; 230 V, 50/60 Hz)
Power supply failure
Depending on the device version, the configuration is retained in the device memoryor in the
pluggable data memory (HistoROM DAT).
Endress+Hauser29
Page 30
Electrical connectionConnecting the transmitter
1
2
3
4
1
2
3
4
• Terminal assignment→ 25
• Device plugs available→ 26
1Terminal connection for supply voltage
2Terminal connection for signal transmission, input/output
3Terminal connection for signal transmission, input/output or terminal for network connection via service
interface (CDI-RJ45); Optional: terminal connection for external WLAN antenna or connection for remote
display and operating module DKX001
4Protective ground (PE)
An adapter for RJ45 and the M12 connector is optionally available:
Order code for "Accessories", option NB: "Adapter RJ45 M12 (service interface)"
The adapter connects the service interface (CDI-RJ45) to an M12 connector mounted in the
cable entry. Therefore the connection to the service interface can be established via an M12
connector without opening the device.
Network connection via service interface (CDI-RJ45) → 80
Proline Promag P 300
A0026781
Connecting in a ring topology
Device versions with EtherNet/IP and PROFINET communication protocols can be integrated into a
ring topology. The device is integrated via the terminal connection for signal transmission (output 1)
and the connection to the service interface (CDI-RJ45).
Integrate the transmitter into a ring topology:
• EtherNet/IP → 78
• PROFINET → 79
A0026781
1Terminal connection for supply voltage
2Terminal connection for signal transmission: PROFINET or EtherNet/IP (RJ45 connector)
3Connection to service interface (CDI-RJ45)
4Protective earth (PE)
If the device has additional input/outputs, these are routed via the cable entry for the
connection to the service interface (CDI-RJ45).
30Endress+Hauser
Page 31
Proline Promag P 300
1
3
81
Vcc
82
Gnd
83A84
B
81
Vcc
82
Gnd
83A84
B
2
4
5
4
4...20 mA
5
2
1
3
6
Connecting the remote display and operating module DKX001
The remote display and operating module DKX001 is available as an optional extra → 89.
• The measuring device is always supplied with a dummy cover when the remote display and
operating module DKX001 is ordered directly with the measuring device. Display or operation
at the transmitter is not possible in this case.
• If ordered subsequently, the remote display and operating module DKX001 may not be
connected at the same time as the existing measuring device display module. Only one
display or operation unit may be connected to the transmitter at any one time.
2Connection example for 4 to 20 mA HART current output (active)
1Automation system with current input (e.g. PLC)
2Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications → 41
3Connection for HART operating devices → 75
4Resistor for HART communication (≥ 250 Ω): observe maximum load → 13
5Analog display unit: observe maximum load → 13
6Transmitter
Endress+Hauser31
Page 32
Proline Promag P 300
2
3
4...20 mA
41
5
2
4...20 mA
4
1
2
3
3
6
5
A0028762
3Connection example for 4 to 20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Power supply
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
4Connection example for HART input with a common negative (passive)
1Automation system with HART output (e.g. PLC)
2Active barrier for power supply (e.g. RN221N)
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
4Analog display unit: observe maximum load
5Pressure transmitter (e.g. Cerabar M, Cerabar S): see requirements
6Transmitter
32Endress+Hauser
Page 33
Proline Promag P 300
2134
78
66
6
6
5
6
6
5
2
1
A
B
3
4
4
A
B
A
B
PROFIBUS PA
A0028768
5Connection example for PROFIBUS PA
1Control system (e.g. PLC)
2PROFIBUS PA segment coupler
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
1Control system (e.g. PLC)
2Ethernet switch
3Observe cable specifications → 41
4Connecting cable between the two transmitters
5Transmitter
FOUNDATION Fieldbus
9Connection example for FOUNDATION Fieldbus
1Control system (e.g. PLC)
2Power Conditioner (FOUNDATION Fieldbus)
3Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
10Connection example for Modbus RS485, non-hazardous area and Zone 2/Div. 2
1Control system (e.g. PLC)
2Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
3Distribution box
4Transmitter
Current output 4-20 mA
A0028758
11Connection example for 4-20 mA current output (active)
1Automation system with current input (e.g. PLC)
2Analog display unit: observe maximum load
3Transmitter
A0028759
12Connection example for 4-20 mA current output (passive)
1Automation system with current input (e.g. PLC)
2Active barrier for power supply (e.g. RN221N)
3Analog display unit: observe maximum load
4Transmitter
36Endress+Hauser
Page 37
Proline Promag P 300
1
2
3
12345
1
2
3
1
2
3
4
Pulse/frequency output
A0028761
13Connection example for pulse/frequency output (passive)
1Automation system with pulse/frequency input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 14
Switch output
14Connection example for switch output (passive)
1Automation system with switch input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 14
Double pulse output
15Connection example for double pulse output (active)
1Automation system with relay input (e.g. PLC)
2Power supply
3Transmitter: Observe input values → 16
Current input
A0028760
A0028915
18Connection example for 4 to 20 mA current input
1Power supply
2Terminal box
3External measuring device (for reading in pressure or temperature, for instance)
4Transmitter
38Endress+Hauser
Page 39
Proline Promag P 300
1
2
3
DN 300≤DN 350≥
Status input
19Connection example for status input
1Automation system with status output (e.g. PLC)
2Power supply
3Transmitter
Potential equalizationRequirements
Please consider the following to ensure correct measurement:
• Same electrical potential for the fluid and sensor
• Company-internal grounding concepts
• Pipe material and grounding
A0028764
Connection example, standard scenario
Metal, grounded pipe
20Potential equalization via measuring tube
Connection example in special situations
Unlined and ungrounded metal pipe
This connection method also applies in situations where:
• The customary potential equalization is not used
• Equalizing currents are present
Ground cableCopper wire, at least 6 mm2 (0.0093 in2)
A0016315
Endress+Hauser39
A0029338
21Potential equalization via ground terminal and pipe flanges
Page 40
Proline Promag P 300
+
–
Note the following when installing:
• Connect both sensor flanges to the pipe flange via a ground cable and ground them.
• Connect the connection housing of the transmitter or sensor to ground potential by means of the
ground terminal provided for the purpose. To mount the ground cable:
– If DN ≤ 300 (12"): Mount the ground cable directly on the conductive flange coating of the
sensor with the flange screws.
– If DN ≥ 350 (14"): Mount the ground cable directly on the metal transport bracket.
You can order the necessary ground cable from Endress+Hauser: → 89.
Plastic pipe or pipe with insulating liner
This connection method also applies in situations where:
• The customary potential equalization is not used
• Equalizing currents are present
Ground cableCopper wire, at least 6 mm2 (0.0093 in2)
A0029339
22Potential equalization via ground terminal and ground disks
Note the following when installing:
The ground disks must be connected to the ground terminal via the ground cable and be connected
to ground potential.
The ground cable and ground disks can be ordered from Endress+Hauser .
Pipe with a cathodic protection unit
This connection method is only used if the following two conditions are met:
• Metal pipe without liner or pipe with electrically conductive liner
• Cathodic protection is integrated in the personal protection equipment
Ground cableCopper wire, at least 6 mm2 (0.0093 in2)
A0030377
1Connection of the two flanges of the pipe via a ground cable
2Signal line shielding via a capacitor
3Measuring device connected to power supply such that it is floating in relation to the protective ground
(isolation transformer)
Note the following when installing:
The sensor is installed in the pipe in a way that provides electrical insulation.
You can order the necessary ground cable from Endress+Hauser: → 89.
40Endress+Hauser
Page 41
Proline Promag P 300
terminals
Spring-loaded terminals: Suitable for strands and strands with ferrules.
Conductor cross-section 0.2 to 2.5 mm2 (24 to 12 AWG).
Cable entries
• Cable gland: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
– NPT ½"
– G ½"
– M20
• Device plug for digital communication: M12
Only available for certain device versions → 26.
Cable specificationPermitted temperature range
• The installation guidelines that apply in the country of installation must be observed.
• The cables must be suitable for the minimum and maximum temperatures to be expected.
Power supply cable
Standard installation cable is sufficient.
Signal cable
Current output 4 to 20 mA HART
A shielded cable is recommended. Observe grounding concept of the plant.
PROFIBUS PA
Twisted, shielded two-wire cable. Cable type A is recommended .
For further information on planning and installing PROFIBUS networks see:
• Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning"
(BA00034S)
• PNO Directive 2.092 "PROFIBUS PA User and Installation Guideline"
• IEC 61158-2 (MBP)
PROFIBUS DP
The IEC 61158 standard specifies two types of cable (A and B) for the bus line which can be used for
every transmission rate. Cable type A is recommended.
Cable typeA
Characteristic impedance135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance< 30 pF/m
Wire cross-section
Cable typeTwisted pairs
Loop resistance≤110 Ω/km
Signal dampingMax. 9 dB over the entire length of the cable cross-section
ShieldCopper braided shielding or braided shielding with foil shield. When grounding
> 0.34 mm2 (22 AWG)
the cable shield, observe the grounding concept of the plant.
For further information on planning and installing PROFIBUS networks see:
• Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning"
(BA00034S)
• PNO Directive 2.092 "PROFIBUS PA User and Installation Guideline"
• IEC 61158-2 (MBP)
Endress+Hauser41
Page 42
Proline Promag P 300
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a cable
used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to the
"Media Planning and Installation Manual. EtherNet/IP" of ODVA Organization
PROFINET
Standard IEC 61156-6 specifies CAT 5 as the minimum category for a cable used for PROFINET. CAT
5e and CAT 6 are recommended.
For more information on planning and installing PROFINET networks, see: "PROFINET Cabling
and Interconnection Technology", Guideline for PROFINET
FOUNDATION Fieldbus
Twisted, shielded two-wire cable.
For further information on planning and installing FOUNDATION Fieldbus networks see:
• Operating Instructions for "FOUNDATION Fieldbus Overview" (BA00013S)
• FOUNDATION Fieldbus Guideline
• IEC 61158-2 (MBP)
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used
for every transmission rate. Cable type A is recommended.
Cable typeA
Characteristic impedance135 to 165 Ω at a measuring frequency of 3 to 20 MHz
Cable capacitance< 30 pF/m
Wire cross-section
Cable typeTwisted pairs
Loop resistance≤110 Ω/km
Signal dampingMax. 9 dB over the entire length of the cable cross-section
ShieldCopper braided shielding or braided shielding with foil shield. When grounding
> 0.34 mm2 (22 AWG)
the cable shield, observe the grounding concept of the plant.
Current output 0/4 to 20 mA
Standard installation cable is sufficient.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Double pulse output
Standard installation cable is sufficient.
Relay output
Standard installation cable is sufficient.
Current input 0/4 to 20 mA
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
42Endress+Hauser
Page 43
Proline Promag P 300
Connecting cable for transmitter - remote display and operating module DKX001
Standard cable
A standard cable can be used as the connecting cable.
Standard cable4 cores (2 pairs); pair-stranded with common shield
Operating temperatureWhen mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
1)UV radiation can impair the cable outer sheath. Protect the cable from direct sunshine where possible.
2 × 2 × 0.34 mm2 (22 AWG) PVC cable
stranded)
can move freely: –25 to +105 °C (–13 to +221 °F)
1)
with common shield (2 pairs, pair-
Performance characteristics
• Error limits following DIN EN 29104, in future ISO 20456
• Water, typically: +15 to +45 °C (+59 to +113 °F); 0.5 to 7 bar (73 to 101 psi)
• Data as indicated in the calibration protocol
• Accuracy based on accredited calibration rigs according to ISO 17025
Maximum measured errorError limits under reference operating conditions
o.r. = of reading
Endress+Hauser43
Page 44
Volume flow
2.5
[%]
2.0
1.5
1.0
0.5
0
0.2 %
0.5 %
0
1
246810 [m/s]
v
5101520253032 [ft/s]0
• ±0.5 % o.r. ± 1 mm/s (0.04 in/s)
• Optional: ±0.2 % o.r. ± 2 mm/s (0.08 in/s)
Fluctuations in the supply voltage do not have any effect within the specified range.
23Maximum measured error in % o.r.
Proline Promag P 300
A0028974
Repeatability
Influence of ambient
temperature
Electrical conductivity
Max. measured error not specified.
Accuracy of outputs
The outputs have the following base accuracy specifications.
Current output
Accuracy±5 µA
Pulse/frequency output
o.r. = of reading
AccuracyMax. ±50 ppm o.r. (over the entire ambient temperature range)
o.r. = of reading
Volume flow
Max. ±0.1 % o.r. ± 0.5 mm/s (0.02 in/s)
Electrical conductivity
Max. ±5 % o.r.
Current output
Temperature coefficientMax. 1 μA/°C
Pulse/frequency output
Temperature coefficientNo additional effect. Included in accuracy.
44Endress+Hauser
Page 45
Proline Promag P 300
h
h
2
1
2 x DN³
5 x DN³
Mounting location
Installation
No special measures such as supports etc. are necessary. External forces are absorbed by the
construction of the device.
A0029343
Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the next pipe
elbow: h ≥ 2 × DN
Installation in down pipes
Install a siphon with a vent valve downstream of the sensor in down pipes whose length h ≥
5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of damage to the
measuring tube. This measure also prevents the system losing prime.
24Installation in a down pipe
1Vent valve
2Pipe siphon
hLength of down pipe
Installation in partially filled pipes
A partially filled pipe with a gradient necessitates a drain-type configuration.
A0028981
A0029257
Endress+Hauser45
Page 46
For heavy sensors DN ≥ 350 (14")
Proline Promag P 300
A0016276
Orientation
The direction of the arrow on the sensor nameplate helps you to install the sensor according to the
flow direction (direction of medium flow through the piping).
OrientationRecommendation
AVertical orientation
A0015591
BHorizontal orientation, transmitter at
top
A0015589
CHorizontal orientation, transmitter at
bottom
A0015590
DHorizontal orientation, transmitter at
side
A0015592
1)Applications with low process temperatures may decrease the ambient temperature. To maintain the
minimum ambient temperature for the transmitter, this orientation is recommended.
2)Applications with high process temperatures may increase the ambient temperature. To maintain the
maximum ambient temperature for the transmitter, this orientation is recommended.
3)To prevent the electronics module from overheating in the case of a sharp rise in temperature (e.g. CIP or
SIP processes), install the device with the transmitter component pointing downwards.
1)
2) 3)
Horizontal
• Ideally, the measuring electrode plane should be horizontal. This prevents brief insulation of the
two measuring electrodes by entrained air bubbles.
• Empty pipe detection only works if the transmitter housing is pointing upwards as otherwise there
is no guarantee that the empty pipe detection function will actually respond to a partially filled or
empty measuring tube.
46Endress+Hauser
Page 47
Proline Promag P 300
1
2
3
≥ 5 × DN
≥ 2 × DN
100
10
0.5
d / D
[mbar]
0.60.70.80.9
1 m/s
2 m/s
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
1
D
d
max. 8°
A0029344
1EPD electrode for empty pipe detection
2Measuring electrodes for signal detection
3Reference electrode for potential equalization
Measuring devices with tantalum or platinum electrodes can be ordered without an EPD
electrode. In this case, empty pipe detection is performed via the measuring electrodes.
Inlet and outlet runs
Adapters
If possible, install the sensor upstream from fittings such as valves, T-pieces or elbows.
Observe the following inlet and outlet runs to comply with accuracy specifications:
A0028997
Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in largerdiameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very
slow-moving fluids.
The nomogram shown here can be used to calculate the pressure loss caused by reducers and
expanders:
• Calculate the ratio of the diameters d/D.
• From the nomogram read off the pressure loss as a function of flow velocity (downstream from
the reduction) and the d/D ratio.
The nomogram only applies to liquids with a viscosity similar to that of water.
Endress+Hauser47
A0029002
Page 48
Environment
Proline Promag P 300
Ambient temperature range
Storage temperature
TransmitterStandard: –40 to +60 °C (–40 to +140 °F)
Local display–20 to +60 °C (–4 to +140 °F), the readability of the display may be
impaired at temperatures outside the temperature range.
Sensor• Process connection material, carbon steel:
–10 to +60 °C (+14 to +140 °F)
• Process connection material, stainless steel:
–40 to +60 °C (–40 to +140 °F)
LinerDo not exceed or fall below the permitted temperature range of the liner .
If operating outdoors:
• Install the measuring device in a shady location.
• Avoid direct sunlight, particularly in warm climatic regions.
• Avoid direct exposure to weather conditions.
You can order a weather protection cover from Endress+Hauser. → 89.
The storage temperature corresponds to the operating temperature range of the transmitter and the
sensor → 48.
• Protect the measuring device against direct sunlight during storage in order to avoid unacceptably
high surface temperatures.
• Select a storage location where moisture cannot collect in the measuring device as fungus or
bacteria infestation can damage the liner.
• If protection caps or protective covers are mounted these should never be removed before
installing the measuring device.
Degree of protection
Vibration resistance
Shock resistance
Shock resistance
Mechanical load
Electromagnetic
compatibility (EMC)
Measuring device
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure
External WLAN antenna
IP67
• Oscillation, sinusoidal, following IEC 60068-2-6
– 2 to 8.4 Hz, 3.5 mm peak
– 8.4 to 2000 Hz, 1 g peak
• Oscillation, broadband noise following IEC 60068-2-64
– 10 to 200 Hz, 0.003 g2/Hz
– 200 to 2000 Hz, 0.001 g2/Hz
– Total: 1.54 g rms
Shock, half-sine according to IEC 60068-2-27
6 ms 50 g
Shock due to rough handling following IEC 60068-2-31
• Protect the transmitter housing against mechanical effects, such as shock or impact.
• Never use the transmitter housing as a ladder or climbing aid.
• As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
• Device version with PROFIBUS DP: Complies with emission limits for industry as per EN 50170
Volume 2, IEC 61784
The following applies for PROFIBUS DP: If baud rates > 1.5 MBaud, an EMC cable entry must be
used and the cable shield must continue as far as the terminal wherever possible.
Details are provided in the Declaration of Conformity.
48Endress+Hauser
Page 49
Proline Promag P 300
0
0
0
0
-20-40
-40
20
20
40
60
140
[°F] [°C]
40 60 80 100
100
120 140 160
200300
180
360
-20
-40
-40
T
A
T
F
[°F]
[°C]
2
1
34
0
0
0
0
-20-40
-40
20
20
40
60
140
[°F] [°C]
40 60 80 100
100
120 140 160
200300
180
360
-20
-40
-40
T
A
T
F
[°F]
[°C]
1
Process
Medium temperature range
• –20 to +150 °C (–4 to +302 °F) for PFA, DN 25 to 200 (1 to 8")
• –20 to +180 °C (–4 to +356 °F) for PFA high-temperature, DN 25 to 200 (1 to 8")
• –40 to +130 °C (–40 to +266 °F) for PTFE, DN 15 to 600 (½ to 24")
A0035803
25PFA
TAAmbient temperature range
TFFluid temperature
1Colored area: the ambient temperature range –10 to –20 °C (+14 to –4 °F) applies to stainless flanges only
2Hatched area: harsh environment only for fluid temperature range –20 to +130 °C (–4 to +266 °F)
3–20 to +150 °C (–4 to +302 °F) for PFA, DN 25 to 200 (1 to 8")
4–20 to +180 °C (–4 to +356 °F) for PFA high-temperature, DN 25 to 200 (1 to 8")
Endress+Hauser49
26PTFE
TAAmbient temperature range
TFFluid temperature
1Colored area: the ambient temperature range of –10 to –40 °C (+14 to –40 °F) applies to stainless flanges
only
A0029808
Page 50
Proline Promag P 300
0
5
10
15
20
25
35
30
40
[bar][psi]
-40
-20
0 20
40 60 80 100140180 [°C]
360 [°F]
0-40100200300
200
100
400
300
500
600
0
120160
PN25
PN16
PN10
PN 6
PN40
PN25
PN16
PN10
PN 6
PN40
0
5
10
15
20
25
35
30
40
[bar][psi]
-40
-20
0 20
40 60 80 100140180 [°C]
360 [°F]
0-40100200300
200
100
400
300
500
600
0
120160
PN16
PN10
PN40
PN 6
PN25
PN16
PN10
PN40
PN 6
PN25
Conductivity
Pressure-temperature
ratings
≥ 5 μS/cm for liquids in general. Stronger filter damping is required for very low conductivity values.
The following pressure/temperature diagrams apply to all pressure-bearing parts of the device and
not just the process connection. The diagrams show the maximum permissible medium pressure
depending on the specific medium temperature.
Process connection: flange according to EN 1092-1 (DIN 2501)
Nominal diameterLimit values for absolute pressure in [mbar] ([psi]) for medium temperatures:
[mm][in]+25 °C (+77 °F)+80 °C (+176 °F)+100 to +180 °C
(+212 to +356 °F)
2510 (0)0 (0)0 (0)
32–0 (0)0 (0)0 (0)
401 ½0 (0)0 (0)0 (0)
5020 (0)0 (0)0 (0)
65–0 (0)0 (0)0 (0)
8030 (0)0 (0)0 (0)
10040 (0)0 (0)0 (0)
125–0 (0)0 (0)0 (0)
15060 (0)0 (0)0 (0)
20080 (0)0 (0)0 (0)
Liner: PTFE
Nominal diameterLimit values for absolute pressure in [mbar] ([psi]) for medium temperatures:
[mm][in]+25 °C (+77 °F)+80 °C (+176 °F)+100 °C (+212 °F)+130 °C (+266 °F)
15½0 (0)0 (0)0 (0)100 (1.45)
2510 (0)0 (0)0 (0)100 (1.45)
32–0 (0)0 (0)0 (0)100 (1.45)
401 ½0 (0)0 (0)0 (0)100 (1.45)
5020 (0)0 (0)0 (0)100 (1.45)
65–0 (0)–40 (0.58)130 (1.89)
8030 (0)–40 (0.58)130 (1.89)
10040 (0)–135 (1.96)170 (2.47)
125–135 (1.96)–240 (3.48)385 (5.58)
1506135 (1.96)–240 (3.48)385 (5.58)
2008200 (2.90)–290 (4.21)410 (5.95)
52Endress+Hauser
Page 53
Proline Promag P 300
DN80
(3")
DN65
(2½")
DN50
(2")
500
450
400
350
300
250
200
150
100
50
0
01020 30 4050 60 7080 90 100 110 120
[mbar]
[m /h]³
010020030040050050150250350450
[gal/min]
7
0
1
2
3
4
5
6
Nominal diameterLimit values for absolute pressure in [mbar] ([psi]) for medium temperatures:
[mm][in]+25 °C (+77 °F)+80 °C (+176 °F)+100 °C (+212 °F)+130 °C (+266 °F)
25010330 (4.79)–400 (5.80)530 (7.69)
30012400 (5.80)–500 (7.25)630 (9.14)
35014470 (6.82)–600 (8.70)730 (10.6)
40016540 (7.83)–670 (9.72)800 (11.6)
45018
No negative pressure permitted!50020
60024
Flow limit
Pressure loss
The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The
optimum velocity of flow is between 2 to 3 m/s (6.56 to 9.84 ft/s). Also match the velocity of flow
(v) to the physical properties of the fluid:
• v < 2 m/s (6.56 ft/s): for abrasive fluids (e.g. potter's clay, lime milk, ore slurry)
• v > 2 m/s (6.56 ft/s): for fluids producing buildup (e.g. wastewater sludge)
A necessary increase in the flow velocity can be achieved by reducing the sensor nominal
diameter.
For an overview of the full scale values for the measuring range, see the "Measuring range"
section → 9
• No pressure loss occurs if the sensor is installed in a pipe with the same nominal diameter.
• Pressure losses for configurations incorporating adapters according to DIN EN 545 → 47
33Pressure loss DN 50 to 80 (2 to 3") in the case of order code for "Design", option C "Insertion length short
ISO/DVGW to DN300, without inlet/outlet runs, constricted meas.tube"
A0032667-EN
Endress+Hauser53
Page 54
Proline Promag P 300
DN300
(12")
DN100
(4")
DN250
(10")
DN200
(8")
DN150
(6")
DN125
(5")
[mbar]
900
800
700
600
500
400
300
200
100
0
0200400600800 1000 1200 1400 1600 1800
[m /h]³
0
13
12
11
10
9
8
7
6
5
4
3
2
1
01000 2000 3000 4000 5000 6000 7000 8000
[gal/min]
A0032668-EN
34Pressure loss DN 100 to 300 (4 to 12") in the case of order code for "Design", option C "Insertion length
short ISO/DVGW to DN300, without inlet/outlet runs, constricted meas.tube"
System pressure
Never install the sensor on the pump suction side in order to avoid the risk of low pressure, and thus
damage to the liner.
Furthermore, install pulse dampers if reciprocating, diaphragm or peristaltic pumps are used.
• Information on the liner's resistance to partial vacuum → 52
• Information on the shock resistance of the measuring system → 48
• Information on the vibration resistance of the measuring system → 48
Thermal insulation
If process fluids are very hot, it is necessary to insulate pipes in order to reduce energy loss and to
prevent individuals from accidentally coming into contact with hot pipes. Please observe the
applicable standards and guidelines for insulating pipes.
A housing support/an extended neck is used for heat dissipation:
• Devices with the order code for "Lining", option B "PFA high-temperature" always come with a
housing support.
• In the case of all other devices, a housing support can be ordered via the order code for
"Sensor option", option CG "Sensor extended neck".
WARNING
L
Electronics overheating on account of thermal insulation!
The housing support is used for heat dissipation and must be completely free (i.e. uncovered). At
‣
the very maximum, the sensor insulation may extend as far as the upper edge of the two sensor
half-shells.
54Endress+Hauser
A0028777
Page 55
Proline Promag P 300
max.
L
D
L
E
F
A
CB
K
G
H
I
M
Vibrations
A0031216
A0029004
35Measures to avoid device vibrations (L > 10 m (33 ft))
In the event of very strong vibrations, the pipe and sensor must be supported and fixed.
• Information on the shock resistance of the measuring system → 48
• Information on the vibration resistance of the measuring system → 48
Mechanical construction
Dimensions in SI unitsCompact version
A0033783
Order code for "Housing", option A "Aluminum, coated"
1)Depending on the cable gland used: values up to + 30 mm
2)With order code for "Sensor option", option CG "Sensor extended neck for insulation" or order code for
"Liner", option B "PFA high temperature": values + 110 mm
3)For version without local display: values – 30 mm
4)Depends on the liner
5)Total length is independent of the process connections. Length according to DVGW (German Technical and
Scientific Association for Gas and Water).→ 58
Order code for "Housing", option A "Aluminum, coated"; Ex d
1)Depending on the cable gland used: values up to + 30 mm
2)With order code for "Sensor option", option CG "Sensor extended neck for insulation" or order code for
"Liner", option B "PFA high temperature": values + 110 mm
3)For version without local display: values – 30 mm
4)Depends on the liner
5)Total length is independent of the process connections. Length according to DVGW (German Technical and
Scientific Association for Gas and Water).→ 58
Endress+Hauser57
Page 58
Proline Promag P 300
C
D
A
B
E
L
Flange connections
Flange
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN 10
P245GH (1.0352): order code for "Process connection", option D2K
1.4404 (F316/F316L): order code for "Process connection", option D2S
DN
[mm]
2003402958 × Ø2226220.9350
25039535012 × Ø2228275.5450
30044540012 × Ø2228326.5500
35050546016 × Ø2226346550
40056551516 × Ø2626396600
45061556520 × Ø2628447650
50067062020 × Ø2628498650
60078072520 × Ø3030600780
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 6.3 to 12.5 µm
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
1)
L
[mm]
A0015621
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN 16
P245GH (1.0352): order code for "Process connection", option D3K
1.4404 (F316/F316L): order code for "Process connection", option D3S
DN
[mm]
651851458 × Ø182077.1200
802001608 × Ø182089.9200
1002201808 × Ø1822115.3250
1252502108 × Ø1824141.3250
1502852408 × Ø2224170.2300
20034029512 × Ø2226220.9350
25040535512 × Ø2632275.7450
30046041012 × Ø2632326.5500
35052047016 × Ø2630346550
40058052516 × Ø3032396600
50071565020 × Ø3336498650
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
1)
L
[mm]
58Endress+Hauser
Page 59
Proline Promag P 300
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN 16
P245GH (1.0352): order code for "Process connection", option D3K
1.4404 (F316/F316L): order code for "Process connection", option D3S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
60084077020 × Ø3640600780
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 6.3 to 12.5 µm
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN 25
P245GH (1.0352): order code for "Process connection", option D4K
1.4404 (F316/F316L): order code for "Process connection", option D4S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
20036031012 × Ø2632220.9350
25042537012 × Ø3036275.7450
30048543016 × Ø3040326.5500
35055549016 × Ø3338346550
40062055016 × Ø3640396600
50073066020 × Ø3648498650
60084577020 × Ø3948600780
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 6.3 to 12.5 µm
1)
L
[mm]
1)
L
[mm]
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
Flange in accordance with EN 1092-1 (DIN 2501 / DIN 2512N): PN 40
P245GH (1.0352): order code for "Process connection", option D5K
1.4404 (F316/F316L): order code for "Process connection", option D5S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
1595654 × Ø141422.2200
25115854 × Ø141634.2200
321401004 × Ø181843200
401501104 × Ø181849.1200
501651254 × Ø182061.3200
651851458 × Ø182477.1200
802001608 × Ø182689.9200
1002351908 × Ø2226115.3250
1252702208 × Ø2628141.3250
1503002508 × Ø2630170.2300
Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 6.3 to 12.5 µm
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
1)
L
[mm]
Endress+Hauser59
Page 60
Proline Promag P 300
Flange according to ASME B16.5, Class 150
A 105: order code for "Process connection", option A1K
1.4404 (F316/F316L): order code for "Process connection", option A1S
DN
[mm]
1588.960.54 × Ø169.622.3200
2510879.24 × Ø1612.634.2200
4012798.64 × Ø1615.949.1200
50152.4120.74 × Ø19.117.561.3200
80190.5152.44 × Ø19.122.389.9200
100228.6190.58 × Ø19.122.3115.3250
150279.4241.38 × Ø22.423.8170.2300
200342.9298.58 × Ø22.426.8220.9350
250406.436212 × Ø25.429.6275.7450
300482.6431.812 × Ø25.430.2326.5500
350535476.312 × Ø28.635.4346550
400595539.816 × Ø28.637396600
450635577.916 × Ø31.840.1447650
50070063520 × Ø31.843.3498650
600815749.320 × Ø34.948.1600780
Surface roughness (flange): Ra 6.3 to 12.5 µm
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
1)
L
[mm]
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
Flange according to ASME B16.5, Class 300
A 105: order code for "Process connection", option A2K
1.4404 (F316/F316L): order code for "Process connection", option A2S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
1595.366.54 × Ø1612.622.3200
25123.988.94 × Ø19.115.934.2200
40155.4114.34 × Ø22.41949.1200
50165.11278 × Ø19.120.861.3200
80209.6168.18 × Ø22.426.889.9200
100254200.28 × Ø22.430.2115.3250
150317.5269.712 × Ø22.435170.2300
Surface roughness (flange): Ra 6.3 to 12.5 µm
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
Flange according to JIS B2220, 10K
A 105/A350LF2: order code for "Process connection", option N3K
1.4404 (F316L): order code for "Process connection", option N3S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
501551204 × Ø191661.1200
651751404 × Ø191877.1200
801851508 × Ø191890200
1)
L
[mm]
1)
L
[mm]
60Endress+Hauser
Page 61
Proline Promag P 300
Flange according to JIS B2220, 10K
A 105/A350LF2: order code for "Process connection", option N3K
1.4404 (F316L): order code for "Process connection", option N3S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
1002101758 × Ø1918115.4250
1252502108 × Ø2320141.2250
1502802408 × Ø2322169300
20033029012 × Ø2322220350
25040035512 × Ø2524274450
30044540016 × Ø2524325500
Surface roughness (flange): Ra 6.3 to 12.5 µm
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
Flange according to JIS B2220, 20K
A 105/A350LF2: order code for "Process connection", option N4K
1.4404 (F316L): order code for "Process connection", option N4S
DN
[mm]
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
1595704 × Ø151422.2200
25125904 × Ø191634.5200
321351004 × Ø191843.2200
401401054 × Ø191849.1200
501551208 × Ø191861.1200
651751408 × Ø192077.1200
802001608 × Ø232290200
1002251858 × Ø2324115.4250
1252702258 × Ø2526141.2250
15030526012 × Ø2528169300
20035030512 × Ø2530220350
25043038012 × Ø2734274450
30048043016 × Ø2736325500
Surface roughness (flange): Ra 6.3 to 12.5 µm
1)
L
[mm]
1)
L
[mm]
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
Endress+Hauser61
Page 62
Accessories
146 (5.75)
48 (1.9)
12 (0.47)
280 (11.0)255 (10.0)
134 (5.3)
30 (1.18)
136 (5.35)
114 (4.49)
86 (3.39)
78 (3.07)
!103 (4.06)
!12 (0.47)
7.0 (0.27)
68 (2.7)105 (4.1)
173 (6.8)
Protective cover
Remote display and operating module DKX001
Proline Promag P 300
A0029553
36Engineering unit mm (in)
External WLAN antenna
The external WLAN antenna is not suitable for use in hygienic applications.
External WLAN antenna mounted on device
37Engineering unit mm (in)
A0028921
A0028923
62Endress+Hauser
Page 63
Proline Promag P 300
70 (2.8)
1500 (59.1)
72 (2.8)
D
D
DN £ 300 (12")
t
E
Æ
B
Æ
A
Æ
C
Æ
A
Æ
B
Æ
t
³DN 350 (14")
C
Æ
E
Æ
External WLAN antenna mounted with cable
The external WLAN antenna can be mounted separately from the transmitter if the transmission/
reception conditions at the transmitter mounting location are poor.
A0033597
38Engineering unit mm (in)
Ground disk for flange connection
A0003221
1)
DN
EN (DIN), JIS, AS
[mm][mm][mm][mm][mm][mm][mm]
15164361.5736.52
25266277.587.56.52
32358087.594.56.52
4041821011036.52
5052101115.51086.52
6568121131.51186.52
8080131154.51356.52
100104156186.51536.52
125130187206.51606.52
1501582172561846.52
2002062672882056.52
2)
ABCDEt
PFA, PTFE
Endress+Hauser63
Page 64
1)
D
L
E
F
A
CB
K
G
H
I
M
DN
EN (DIN), JIS, AS
[mm][mm][mm][mm][mm][mm][mm]
2502603283592406.52
3)
300
4)
300
3)
350
3)
400
3)
450
3)
500
3)
600
1)Ground disks DN 15 to 250 (½ to 10") can be used for all available flange standards/pressure ratings.
2)For flanges to AS, only DN 25 and DN 50 are available.
3)PN 10/16
4)PN 25, JIS 10K/20K
Dimensions in US unitsCompact version
2)
Proline Promag P 300
ABCDEt
PFA, PTFE
3123754132736.52
3103754042686.52
3434334793659.02
3934805423959.02
4395385834179.02
4935926504609.02
5936937665229.02
A0033783
Order code for "Housing", option A "Aluminum, coated"
1)Depending on the cable gland used: values up to +1.18 in
2)With order code for "Sensor option", option CG "Sensor extended neck for insulation" or order code for
"Liner", option B "PFA high temperature": values + 4.33 in
3)For version without local display: values – 1.18 in
4)Depends on the liner
5)Total length is independent of the process connections. Length according to DVGW (German Technical and
Scientific Association for Gas and Water).→ 66
Order code for "Housing", option A "Aluminum, coated"; Ex d
1)Depending on the cable gland used: values up to +1.18 in
2)With order code for "Sensor option", option CG "Sensor extended neck for insulation" or order code for
"Liner", option B "PFA high temperature": values + 4.33 in
3)For version without local display: values – 1.18 in
4)Depends on the liner
5)Total length is independent of the process connections. Length according to DVGW (German Technical and
Scientific Association for Gas and Water).→ 66
Endress+Hauser65
Page 66
Proline Promag P 300
C
D
A
B
E
L
Flange connections
Flange
Flange according to ASME B16.5, Class 150
A 105: order code for "Process connection", option A1K
1.4404 (F316/F316L): order code for "Process connection", option A1S
DN
[in]
½3.52.384 × Ø0.630.380.887.87
14.253.124 × Ø0.630.51.357.87
1 ½53.884 × Ø0.630.631.937.87
264.754 × Ø0.750.692.417.87
37.564 × Ø0.750.883.547.87
497.58 × Ø0.750.884.549.84
6119.58 × Ø0.880.946.711.8
813.511.758 × Ø0.881.068.713.8
101614.2512 × Ø11.1710.8517.7
12191712 × Ø11.1912.8519.7
1421.0618.7512 × Ø1.131.3913.6221.7
1623.4321.2516 × Ø1.131.4615.5923.6
182522.7516 × Ø1.251.5817.625.6
2027.562520 × Ø1.251.719.6125.6
2432.0929.520 × Ø1.371.8923.6230.7
Surface roughness (flange): Ra 6.3 to 12.5 µm
A
[in]
B
[in]
C
[in]
D
[in]
E
[in]
L
[in]
A0015621
1)
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
Flange according to ASME B16.5, Class 300
A 105: order code for "Process connection", option A2K
1.4404 (F316/F316L): order code for "Process connection", option A2S
DN
[in]
½3.752.624 × Ø0.630.50.887.87
14.883.54 × Ø0.750.631.357.87
1 ½6.124.54 × Ø0.880.751.937.87
26.558 × Ø0.750.822.417.87
66Endress+Hauser
A
[in]
B
[in]
C
[in]
D
[in]
E
[in]
1)
L
[in]
Page 67
Proline Promag P 300
146 (5.75)
48 (1.9)
12 (0.47)
280 (11.0)255 (10.0)
134 (5.3)
30 (1.18)
136 (5.35)
114 (4.49)
86 (3.39)
78 (3.07)
!103 (4.06)
!12 (0.47)
7.0 (0.27)
Flange according to ASME B16.5, Class 300
A 105: order code for "Process connection", option A2K
1.4404 (F316/F316L): order code for "Process connection", option A2S
DN
[in]
38.256.628 × Ø0.881.063.547.87
4107.888 × Ø0.881.194.549.84
612.510.6212 × Ø0.881.386.711.8
Surface roughness (flange): Ra 6.3 to 12.5 µm
1)Length according to DVGW (German Technical and Scientific Association for Gas and Water).
A
[in]
B
[in]
C
[in]
D
[in]
E
[in]
Accessories
Protective cover
L
[in]
1)
Remote display and operating module DKX001
39Engineering unit mm (in)
External WLAN antenna
The external WLAN antenna is not suitable for use in hygienic applications.
A0029553
A0028921
Endress+Hauser67
Page 68
Proline Promag P 300
68 (2.7)105 (4.1)
173 (6.8)
70 (2.8)
1500 (59.1)
72 (2.8)
D
D
DN £ 300 (12")
t
E
Æ
B
Æ
A
Æ
C
Æ
A
Æ
B
Æ
t
³DN 350 (14")
C
Æ
E
Æ
External WLAN antenna mounted on device
A0028923
40Engineering unit mm (in)
External WLAN antenna mounted with cable
The external WLAN antenna can be mounted separately from the transmitter if the transmission/
reception conditions at the transmitter mounting location are poor.
41Engineering unit mm (in)
Ground disk for flange connection
68Endress+Hauser
A0033597
A0003221
Page 69
Proline Promag P 300
1)
DN
ASMEPFA, PTFE
[in][in][in][in][in][in][in]
½0.631.692.422.870.260.08
11.022.443.053.440.260.08
1 ½1.613.233.984.060.260.08
22.053.984.554.250.260.08
33.155.166.085.310.260.08
44.096.147.346.020.260.08
66.228.5410.087.240.260.08
88.1110.5111.348.070.260.08
1010.2412.9114.139.450.260.08
1212.2814.7616.2610.750.260.08
1413.5017.0518.8614.370.350.08
1615.4718.9021.3415.550.350.08
1817.2821.1822.9516.420.350.08
2019.4123.3125.5918.110.350.08
2423.3527.2830.1620.550.350.08
ABCDEt
Weight
1)Ground disks can be used for all available pressure ratings.
All values (weight exclusive of packaging material) refer to devices for standard pressure ratings.
Weight specifications including transmitter as per order code for "Housing", option A "Aluminum,
coated".
Different values due to different transmitter versions:
Transmitter version for the hazardous area
(Order code for "Housing", option A "Aluminum, coated"; Ex d): +2 kg (+4.4 lbs)
• DN 15 to 300 (½ to 12"): coated aluminum AlSi10Mg
• DN 350 to 600 (14 to 24"): carbon steel with protective varnish
Measuring tubes
Stainless steel, 1.4301/304/1.4306/304L
For flanges made of carbon with Al/Zn protective coating (DN 15 to 300 (½ to 12")) or protective
varnish (DN 350 to 600 (14 to 24"))
Liner
• PFA
• PTFE
Process connections
EN 1092-1 (DIN 2501)
Stainless steel, 1.4571 (F316L); carbon steel, E250C
For information on the different materials used in the process connections → 72
Stainless steel electrodes, 1.4435 (F316L); Alloy C22, 2.4602 (UNS N06022); platinum; tantalum;
titanium:
≤ 0.3 to 0.5 µm (11.8 to 19.7 µin)
(All data relate to parts in contact with fluid)
Liner with PFA:
≤ 0.4 µm (15.7 µin)
(All data relate to parts in contact with fluid)
Operability
Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Fast and safe commissioning
• Guided menus ("Make-it-run" wizards) for applications
• Menu guidance with brief descriptions of the individual parameter functions
• Device access via Web server or SmartBlue app → 91
• WLAN access to the device via mobile handheld terminal, tablet or smart phone
Reliable operation
• Operation in local language → 73
• Uniform operating philosophy applied to device and operating tools
• If replacing electronic modules, transfer the device configuration via the integrated memory
(HistoROM backup) which contains the process and measuring device data and the event logbook.
No need to reconfigure.
• Order code for "Display; operation", option F "4-line, illuminated, graphic display; touch control"
• Order code for "Display; operation", option G "4-line, illuminated, graphic display; touch control +
WLAN"
Information about WLAN interface → 80
Endress+Hauser73
Page 74
Proline Promag P 300
43Operation with touch control
Display elements
• 4-line, illuminated, graphic display
• White background lighting; switches to red in event of device errors
• Format for displaying measured variables and status variables can be individually configured
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
Operating elements
• External operation via touch control (3 optical keys) without opening the housing: , ,
• Operating elements also accessible in the various zones of the hazardous area
A0026785
Via remote display and operating module DKX001
The remote display and operating module DKX001 is available as an optional extra → 89.
• The measuring device is always supplied with a dummy cover when the remote display and
operating module DKX001 is ordered directly with the measuring device. Display or operation
at the transmitter is not possible in this case.
• If ordered subsequently, the remote display and operating module DKX001 may not be
connected at the same time as the existing measuring device display module. Only one
display or operation unit may be connected to the transmitter at any one time.
44Operation via remote display and operating module DKX001
Display and operating elements
The display and operating elements correspond to those of the display module → 73.
A0026786
Material
The housing material of the display and operating module DKX001 depends on the choice of
transmitter housing material.
Transmitter housingRemote display and operating module
Order code for "Housing"MaterialMaterial
Option A "Aluminum, coated"AlSi10Mg, coatedAlSi10Mg, coated
74Endress+Hauser
Page 75
Proline Promag P 300
1235
8
47
6
Cable entry
Corresponds to the choice of transmitter housing, order code for "Electrical connection".
Connecting cable
→ 43
Dimensions
→ 62
Remote operationVia HART protocol
This communication interface is available in device versions with a HART output.
45Options for remote operation via HART protocol (active)
1Control system (e.g. PLC)
2Field Communicator 475
3Computer with Web browser (e.g. Internet Explorer) for access to the integrated device Web server or
computer with an operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) with COM
DTM "CDI Communication TCP/IP"
4Commubox FXA195 (USB)
5Field Xpert SFX350 or SFX370
6Field Xpert SMT70
7VIATOR Bluetooth modem with connecting cable
8Transmitter
A0028747
Endress+Hauser75
Page 76
Proline Promag P 300
1
10
2
3
457
69
8
12
3
1
9898
4
66
5
46Options for remote operation via HART protocol (passive)
1Control system (e.g. PLC)
2Transmitter power supply unit, e.g. RN221N (with communication resistor)
3Connection for Commubox FXA195 and Field Communicator 475
4Field Communicator 475
5Computer with Web browser (e.g. Internet Explorer) for access to the integrated device Web server or
computer with an operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) with COM
DTM "CDI Communication TCP/IP"
6Commubox FXA195 (USB)
7Field Xpert SFX350 or SFX370
8Field Xpert SMT70
9VIATOR Bluetooth modem with connecting cable
10 Transmitter
A0028746
Via FOUNDATION Fieldbus network
This communication interface is available in device versions with FOUNDATION Fieldbus.
47Options for remote operation via FOUNDATION Fieldbus network
1Automation system
2Computer with FOUNDATION Fieldbus network card
3Industry network
4High Speed Ethernet FF-HSE network
5Segment coupler FF-HSE/FF-H1
6FOUNDATION Fieldbus FF-H1 network
7Power supply FF-H1 network
8T-box
9Measuring device
A0028837
76Endress+Hauser
Page 77
Proline Promag P 300
12
3
444
2
3
1
76
5
4
Via PROFIBUS DP network
This communication interface is available in device versions with PROFIBUS DP.
A0020903
48Options for remote operation via PROFIBUS DP network
1Automation system
2Computer with PROFIBUS network card
3PROFIBUS DP network
4Measuring device
Via PROFIBUS PA network
This communication interface is available in device versions with PROFIBUS PA.
A0028838
49Options for remote operation via PROFIBUS PA network
1Automation system
2Computer with PROFIBUS network card
3PROFIBUS DP network
4Segment coupler PROFIBUS DP/PA
5PROFIBUS PA network
6T-box
7Measuring device
Via Modbus RS485 protocol
This communication interface is available in device versions with a Modbus-RS485 output.
Endress+Hauser77
Page 78
Proline Promag P 300
12
3
4
213
555
A0029437
50Options for remote operation via Modbus-RS485 protocol (active)
1Control system (e.g. PLC)
2Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP" or Modbus DTM
3Transmitter
Via EtherNet/IP network
This communication interface is available in device versions with EtherNet/IP.
Star topology
51Options for remote operation via EtherNet/IP network: star topology
1Automation system, e.g. "RSLogix" (Rockwell Automation)
2Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell
Automation) or with Electronic Data Sheet (EDS)
3Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP"
4Ethernet switch
5Measuring device
Ring topology
The device is integrated via the terminal connection for signal transmission (output 1) and the
service interface (CDI-RJ45).
A0032078
78Endress+Hauser
Page 79
Proline Promag P 300
4
213
5
55
312
444
A0033725
52Options for remote operation via EtherNet/IP network: ring topology
1Automation system, e.g. "RSLogix" (Rockwell Automation)
2Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell
Automation) or with Electronic Data Sheet (EDS)
3Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP"
4Ethernet switch
5Measuring device
Via PROFINET network
This communication interface is available in device versions with PROFINET.
Star topology
A0026545
53Options for remote operation via PROFINET network: star topology
1Automation system, e.g. Simatic S7 (Siemens)
2Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare, SIMATIC PDM) with COM DTM "CDI Communication
TCP/IP"
3Switch, e.g. Scalance X204 (Siemens)
4Measuring device
Ring topology
This communication interface is available in device versions with PROFINET.
Endress+Hauser79
Page 80
Proline Promag P 300
3
12
444
2
3
54Options for remote operation via PROFINET network: ring topology
1Automation system, e.g. Simatic S7 (Siemens)
2Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare, SIMATIC PDM) with COM DTM "CDI Communication
TCP/IP"
3Switch, e.g. Scalance X204 (Siemens)
4Measuring device
A0033719
Service interfaceVia service interface (CDI-RJ45)
A point-to-point connection can be established to configure the device onsite. With the housing
open, the connection is established directly via the service interface (CDI-RJ45) of the device.
An adapter for RJ45 and the M12 connector is optionally available:
Order code for "Accessories", option NB: "Adapter RJ45 M12 (service interface)"
The adapter connects the service interface (CDI-RJ45) to an M12 connector mounted in the
cable entry. Therefore the connection to the service interface can be established via an M12
connector without opening the device.
55Connection via service interface (CDI-RJ45)
1Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated
device Web server or with "FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"
or Modbus DTM
2Standard Ethernet connecting cable with RJ45 connector
3Service interface (CDI-RJ45) of the measuring device with access to the integrated Web server
A0027563
Via WLAN interface
The optional WLAN interface is available on the following device version:
Order code for "Display; operation", option G "4-line, illuminated, graphic display; touch control +
WLAN"
80Endress+Hauser
Page 81
Proline Promag P 300
213
4
3
4
567
A0034570
1Transmitter with integrated WLAN antenna
2Transmitter with external WLAN antenna
3LED lit constantly: WLAN reception is enabled on measuring device
4LED flashing: WLAN connection established between operating unit and measuring device
5Computer with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for
accessing the integrated device Web server or with operating tool (e.g. FieldCare, DeviceCare)
6Mobile handheld terminal with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft
Edge) for accessing the integrated device Web server or operating tool (e.g. FieldCare, DeviceCare)
7Smart phone or tablet (e.g. Field Xpert SMT70)
Network integration
FunctionWLAN: IEEE 802.11 b/g (2.4 GHz)
• Access point with DHCP server (default setting)
• Network
EncryptionWPA2-PSK AES-128 (in accordance with IEEE 802.11i)
Configurable WLAN channels1 to 11
Degree of protectionIP67
Available antennas• Internal antenna
• External antenna (optional)
In the event of poor transmission/reception conditions at the place of
installation.
Available as an accessory → 89.
Only one antenna active in each case!
Max. range50 m (164 ft)
Materials:
External WLAN antenna
• Antenna: ASA plastic (acrylic ester-styrene-acrylonitrile) and nickelplated brass
• Adapter: Stainless steel and nickel-plated brass
• Cable: Polyethylene
• Connector: Nickel-plated brass
• Angle bracket: Stainless steel
With the optional OPC-UA-Server application package, the device can be integrated into an Ethernet
network via the service interface (CDI-RJ45 and WLAN) and communicate with OPC-UA clients. If
the device is used in this way, IT security must be considered.
For permanent access to device data and for device configuration via the Web server, the device is
incorporated directly in a network via the service interface (CDI-RJ45). In this way, the device can be
accessed any time from the control station. The measured values are processed separately via the
inputs and outputs through the automation system.
Endress+Hauser81
Page 82
213
555
4
6
7
8
1Automation system, e.g. Simatic S7 (Siemens)
2Ethernet switch
3Edge Gateway
4Cloud
5Measuring device
6Ethernet network
7Measured values via inputs and outputs
8Optional WLAN interface
Proline Promag P 300
A0033618
Supported operating tools
The optional WLAN interface is available on the following device version:
Order code for "Display; operation", option G "4-line, illuminated, graphic display; touch control +
WLAN"
Special Documentation for the OPC-UA-Server application package → 93.
Different operating tools can be used for local or remote access to the measuring device. Depending
on the operating tool used, access is possible with different operating units and via a variety of
interfaces.
Supported operating
tools
Web browserNotebook, PC or tablet
DeviceCare SFE100Notebook, PC or tablet
Operating unitInterfaceAdditional information
with Web browser
with Microsoft Windows
system
• CDI-RJ45 service
interface
• WLAN interface
• Ethernet-based
fieldbus (EtherNet/IP,
PROFINET)
• CDI-RJ45 service
interface
• WLAN interface
• Fieldbus protocol
Special Documentation for
device
→ 91
82Endress+Hauser
Page 83
Proline Promag P 300
Supported operating
tools
FieldCare SFE500Notebook, PC or tablet
Device XpertField Xpert SFX
Operating unitInterfaceAdditional information
with Microsoft Windows
system
100/350/370
• CDI-RJ45 service
interface
• WLAN interface
• Fieldbus protocol
HART and
FOUNDATION Fieldbus
fieldbus protocol
→ 91
Operating Instructions
BA01202S
Device description files:
Use update function of
handheld terminal
Other operating tools based on FDT technology with a device driver such as DTM/iDTM or
DD/EDD can be used for device operation. These operating tools are available from the
individual manufacturers. Integration into the following operating tools, among others, is
supported:
• FactoryTalk AssetCentre (FTAC) by Rockwell Automation → www.rockwellautomation.com
• Process Device Manager (PDM) by Siemens → www.siemens.com
• Asset Management Solutions (AMS) by Emerson → www.emersonprocess.com
• FieldCommunicator 375/475 by Emerson → www.emersonprocess.com
• Field Device Manager (FDM) by Honeywell → www.honeywellprocess.com
• FieldMate by Yokogawa → www.yokogawa.com
• PACTWare → www.pactware.com
The associated device description files are available at: www.endress.com → Downloads
Web server
Thanks to the integrated Web server, the device can be operated and configured via a Web browser
and via a service interface (CDI-RJ45) or via a WLAN interface. The structure of the operating menu
is the same as for the local display. In addition to the measured values, status information on the
device is also displayed and allows the user to monitor the status of the device. Furthermore the
device data can be managed and the network parameters can be configured.
A device that has a WLAN interface (can be ordered as an option) is required for the WLAN
connection: order code for "Display; operation", option G "4-line, illuminated; touch control + WLAN".
The device acts as an Access Point and enables communication by computer or a mobile handheld
terminal.
Supported functions
Data exchange between the operating unit (such as a notebook for example) and the measuring
device:
– Upload the configuration from the measuring device (XML format, configuration backup)
– Save the configuration to the measuring device (XML format, restore configuration)
– Export event list (.csv file)
– Export parameter settings (.csv file or PDF file, document the measuring point configuration)
– Export the Heartbeat verification log (PDF file, only available with the "Heartbeat Verification"
application package)
– Flash firmware version for device firmware upgrade, for instance
– Download driver for system integration
– Visualize up to 1000 saved measured values (only available with the Extended HistoROM
application package → 88)
Web server special documentation → 93
HistoROM data management
The measuring device features HistoROM data management. HistoROM data management
comprises both the storage and import/export of key device and process data, making operation and
servicing far more reliable, secure and efficient.
When the device is delivered, the factory settings of the configuration data are stored as a
backup in the device memory. This memory can be overwritten with an updated data record, for
example after commissioning.
Endress+Hauser83
Page 84
Additional information on the data storage concept
There are different types of data storage units in which device data are stored and used by the device:
Device memoryT-DATS-DAT
Available data• Event logbook such as diagnostic events for example
• Parameter data record backup
• Device firmware package
• Driver for system integration for exporting via Web
server, e.g:
– GSD for PROFIBUS DP
– GSD for PROFIBUS PA
– GSDML for PROFINET
– EDS for EtherNet/IP
– DD for FOUNDATION Fieldbus
Storage location Fixed on the user interface board in the connection
compartment
• Measured value logging
("Extended HistoROM" order
option)
• Current parameter data record
(used by firmware at run time)
• Peakhold indicator (min/max
values)
• Totalizer values
Attachable to the user interface
board in the connection
compartment
Data backup
Automatic
• The most important device data (sensor and transmitter) are automatically saved in the DAT
modules
• If the transmitter or measuring device is replaced: once the T-DAT containing the previous device
data has been exchanged, the new measuring device is ready for operation again immediately
without any errors
• If the sensor is replaced: once the sensor has been replaced, new sensor data are transferred from
the S-DAT in the measuring device and the measuring device is ready for operation again
immediately without any errors
• If exchanging the electronics module (e.g. I/O electronics module): Once the electronics module
has been replaced, the software of the module is compared against the current device firmware.
The module software is upgraded or downgraded where necessary. The electronics module is
available for use immediately afterwards and no compatibility problems occur.
Manual
Additional parameter data record (complete parameter settings) in the integrated device memory
HistoROM backup for:
• Data backup function
Backup and subsequent restoration of a device configuration in the device memory HistoROM
backup
• Data comparison function
Comparison of the current device configuration with the device configuration saved in the device
memory HistoROM backup
Proline Promag P 300
• Sensor data: nominal diameter
etc.
• Serial number
• Calibration data
• Device configuration (e.g. SW
options, fixed I/O or multi I/O)
In the sensor plug in the transmitter
neck part
Data transfer
Manual
• Transfer of a device configuration to another device using the export function of the specific
operating tool, e.g. with FieldCare, DeviceCare or Web server: to duplicate the configuration or to
store in an archive (e.g. for backup purposes)
• Transmission of the drivers for system integration via Web server, e.g.:
– GSD for PROFIBUS DP
– GSD for PROFIBUS PA
– GSDML for PROFINET
– EDS for EtherNet/IP
– DD for FOUNDATION Fieldbus
Event list
Automatic
• Chronological display of up to 20 event messages in the events list
• If the Extended HistoROM application package (order option) is enabled: up to 100 event
messages are displayed in the events list along with a time stamp, plain text description and
remedial measures
• The events list can be exported and displayed via a variety of interfaces and operating tools e.g.
DeviceCare, FieldCare or Web server
84Endress+Hauser
Page 85
Proline Promag P 300
Data logging
Manual
If the Extended HistoROM application package (order option) is enabled:
• Record up to 1000 measured values via 1 to 4 channels
• User configurable recording interval
• Record up to 250 measured values via each of the 4 memory channels
• Export the measured value log via a variety of interfaces and operating tools e.g. FieldCare,
DeviceCare or web server
Certificates and approvals
Currently available certificates and approvals can be called up via the product configurator.
CE mark
C-Tick symbol
Ex approval
The device meets the legal requirements of the applicable EU Directives. These are listed in the
corresponding EU Declaration of Conformity along with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
The measuring device is certified for use in hazardous areas and the relevant safety instructions are
provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on
the nameplate.
The separate Ex documentation (XA) containing all the relevant explosion protection data is
available from your Endress+Hauser sales center.
ATEX, IECEx
Currently, the following versions for use in hazardous areas are available:
Ex db eb
CategoryType of protection
II2GEx db eb ia IIC T6…T1 Gb
Ex tb
CategoryType of protection
II2DEx tb IIIC Txxx Db
Ex ec
CategoryType of protection
II3GEx ec ic IIC T5…T1 Gc
cCSAus
Currently, the following versions for use in hazardous areas are available:
IS (Ex i) and XP (Ex d)
Class I, II, III Division 1 Groups A-G
NI (Ex nA)
Class I Division 2 Groups A - D
Ex de
Class I, Zone 1 AEx/ Ex de ia IIC T6…T1 Gb
Ex nA
Class I, Zone 2 AEx/Ex nA ic IIC T5...T1 Gc
Endress+Hauser85
Page 86
Ex tb
Zone 21 AEx/ Ex tb IIIC T** °C Db
Proline Promag P 300
Pharmaceutical compatibility
Functional safety
HART certificationHART interface
FOUNDATION Fieldbus
certification
• FDA
• USP Class VI
• TSE/BSE Certificate of Suitability
The measuring device can be used for flow monitoring systems (min., max., range) up to SIL 2
(single-channel architecture; order code for "Additional approval", option LA) and SIL 3
(multichannel architecture with homogeneous redundancy) and is independently evaluated and
certified by the TÜV in accordance with IEC 61508.
The following types of monitoring in safety equipment are possible:
Volume flow
Functional Safety Manual with information on the SIL device → 92
The measuring device is certified and registered by the FieldComm Group. The measuring system
meets all the requirements of the following specifications:
• Certified according to HART 7
• The device can also be operated with certified devices of other manufacturers (interoperability)
FOUNDATION Fieldbus interface
The measuring device is certified and registered by the FieldComm Group. The measuring system
meets all the requirements of the following specifications:
• Certified in accordance with FOUNDATION Fieldbus H1
• Interoperability Test Kit (ITK), revision version 6.2.0 (certificate available on request)
• Physical Layer Conformance Test
• The device can also be operated with certified devices of other manufacturers (interoperability)
Certification PROFIBUSPROFIBUS interface
The measuring device is certified and registered by the PNO (PROFIBUS User Organization
Organization). The measuring system meets all the requirements of the following specifications:
• Certified in accordance with PROFIBUS PA Profile 3.02
• The device can also be operated with certified devices of other manufacturers (interoperability)
EtherNet/IP certification
Certification PROFINETPROFINET interface
Radio approval
The measuring device is certified and registered by the ODVA (Open Device Vendor Association).
The measuring system meets all the requirements of the following specifications:
• Certified in accordance with the ODVA Conformance Test
• EtherNet/IP Performance Test
• EtherNet/IP PlugFest compliance
• The device can also be operated with certified devices of other manufacturers (interoperability)
The measuring device is certified and registered by the PNO (PROFIBUS User Organization
Organization). The measuring system meets all the requirements of the following specifications:
• Certified according to:
– Test specification for PROFINET devices
– PROFINET Security Level 2 – Netload Class
• The device can also be operated with certified devices of other manufacturers (interoperability)
The measuring device has radio approval.
For detailed information on the radio approval, see the Special Documentation
Pressure Equipment
Directive
The devices can be ordered with or without a PED approval. If a device with a PED approval is
required, this must be explicitly stated in the order. For devices with nominal diameters less than or
equal to DN 25 (1"), this is neither possible nor necessary.
86Endress+Hauser
Page 87
Proline Promag P 300
• With the identification PED/G1/x (x = category) on the sensor nameplate, Endress+Hauser
confirms conformity with the "Essential Safety Requirements" specified in Appendix I of the
Pressure Equipment Directive 2014/68/EU.
• Devices bearing this marking (PED) are suitable for the following types of medium:
Media in Group 1 and 2 with a vapor pressure greater than, or smaller and equal
to0.5 bar (7.3 psi)
• Devices not bearing this marking (PED) are designed and manufactured according to good
engineering practice. They meet the requirements of Article 4 paragraph 3 of the Pressure
Equipment Directive 2014/68/EU. The range of application is indicated in tables 6 to 9 in Annex II
of the Pressure Equipment Directive 2014/68/EU.
Measuring instrument
approval
Additional certificationPWIS-free
Other standards and
guidelines
The measuring device is qualified to OIML R117 and has an OIML Certificate of Conformity
(optional).
PWIS = paint-wetting impairment substances
Order code for "Service":
• Option HC: PWIS-free (version A)
• Option HD: PWIS-free (version B)
• Option HE: PWIS-free (version C)
For more information on PWIS-free certification, see "Test specification" document TS01028D
• EN 60529
Degrees of protection provided by enclosures (IP code)
• EN 61010-1
Safety requirements for electrical equipment for measurement, control and laboratory use general requirements
• IEC/EN 61326
Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC
requirements).
• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment
• NAMUR NE 32
Data retention in the event of a power failure in field and control instruments with
microprocessors
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with
analog output signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics
• NAMUR NE 105
Specifications for integrating fieldbus devices in engineering tools for field devices
• NAMUR NE 107
Self-monitoring and diagnosis of field devices
• NAMUR NE 131
Requirements for field devices for standard applications
• ETSI EN 300 328
Guidelines for 2.4 GHz radio components.
• EN 301489
Electromagnetic compatibility and radio spectrum matters (ERM).
Endress+Hauser87
Page 88
Proline Promag P 300
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field ->
Open product page -> The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Application packages
Many different application packages are available to enhance the functionality of the device. Such
packages might be needed to address safety aspects or specific application requirements.
The application packages can be ordered with the device or subsequently from Endress+Hauser.
Detailed information on the order code in question is available from your local Endress+Hauser sales
center or on the product page of the Endress+Hauser website: www.endress.com.
Diagnostics functions
Heartbeat Technology
PackageDescription
Extended HistoROMComprises extended functions concerning the event log and the activation of the
measured value memory.
Event log:
Memory volume is extended from 20 message entries (standard version) to up to
100 entries.
Data logging (line recorder):
• Memory capacity for up to 1000 measured values is activated.
• 250 measured values can be output via each of the 4 memory channels. The
recording interval can be defined and configured by the user.
• Measured value logs can be accessed via the local display or operating tool e.g.
FieldCare, DeviceCare or Web server.
PackageDescription
Heartbeat Verification
+Monitoring
Heartbeat Verification
Meets the requirement for traceable verification to DIN ISO 9001:2008 Chapter
7.6 a) "Control of monitoring and measuring equipment".
• Functional testing in the installed state without interrupting the process.
• Traceable verification results on request, including a report.
• Simple testing process via local operation or other operating interfaces.
• Clear measuring point assessment (pass/fail) with high test coverage within the
framework of manufacturer specifications.
• Extension of calibration intervals according to operator's risk assessment.
Heartbeat Monitoring
Continuously supplies data, which are characteristic of the measuring principle, to
an external condition monitoring system for the purpose of preventive
maintenance or process analysis. These data enable the operator to:
• Draw conclusions - using these data and other information - about the impact
process influences (such as corrosion, abrasion, buildup etc.) have on the
measuring performance over time.
• Schedule servicing in time.
• Monitor the process or product quality, e.g. gas pockets.
88Endress+Hauser
Page 89
Proline Promag P 300
Cleaning
OPC-UA server
PackageDescription
Electrode cleaning circuit
(ECC)
PackageDescription
OPC-UA-ServerThe application package provides the user with an integrated OPC-UA server for
Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are
available for the device. Detailed information on the order code in question is available from your
local Endress+Hauser sales center or on the product page of the Endress+Hauser website:
www.endress.com.
Device-specific accessoriesFor the transmitter
The electrode cleaning circuit (ECC) function has been developed to have a solution
for applications where magnetite (Fe3O4) deposits frequently occur (e.g. hot
water). Since magnetite is highly conductive this build up leads to measuring errors
and ultimately to the loss of signal. The application package is designed to AVOID
build up of highly conductive matter and thin layers (typical of magnetite).
comprehensive instrument services for IoT and SCADA applications.
Special Documentation for the "OPC-UA-Server" application package
→ 93.
AccessoriesDescription
Proline 300 transmitterTransmitter for replacement or storage. Use the order code to define the following
specifications:
• Approvals
• Output
• Input
• Display/operation
• Housing
• Software
Order code: 5X3BXX
Installation Instructions EA01150
Remote display and
operating module
DKX001
• If ordered directly with the measuring device:
Order code for "Display; operation", option O "Separate 4-line display, illum.;
10 m (30 ft)Cable; touch control".
• If ordered separately:
– Measuring device: order code for "Display; operation", option M "None,
prepared for separate display".
– DKX001: Via the separate product structure DKX001.
• If ordered subsequently:
DKX001: Via the separate product structure DKX001.
Mounting bracket for DKX001
• Ordered directly with the DKX001:
Order code for "Enclosed accessories", option RA "Mounting bracket, 1"/2" pipe".
• If ordered subsequently: order number: 71340960
Connecting cable (replacement cable)
Via the separate product structure: DKX002
Further information on display and operating module DKX001→ 74.
Special Documentation SD01763D
Endress+Hauser89
Page 90
Proline Promag P 300
External WLAN antennaExternal WLAN antenna with 1.5 m (59.1 in) connecting cable and two angle
brackets. Order code for "Enclosed accessories", option P8 "Wireless antenna wide
area".
• The external WLAN antenna is not suitable for use in hygienic
applications.
• Further information on the WLAN interface → 80.
Order number: 71351317
Installation Instructions EA01238D
Protective coverIs used to protect the measuring device from the effects of the weather: e.g.
rainwater, excess heating from direct sunlight.
Order number: 71343505
Installation Instructions EA01160
Ground cableSet, consisting of two ground cables for potential equalization.
For the sensor
AccessoriesDescription
Ground disksAre used to ground the medium in lined measuring tubes to ensure proper
measurement.
For details, see Installation Instructions EA00070D
Communication-specific
accessories
AccessoriesDescription
Commubox FXA195
HART
HART Loop Converter
HMX50
Fieldgate FXA320Gateway for the remote monitoring of connected 4-20 mA measuring devices via a
Fieldgate FXA520Gateway for the remote diagnostics and remote configuration of connected HART
Field Xpert SFX350Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
For intrinsically safe HART communication with FieldCare via the USB interface.
Technical Information TI00404F
Is used to evaluate and convert dynamic HART process variables to analog current
signals or limit values.
• Technical Information TI00429F
• Operating Instructions BA00371F
Web browser.
Technical Information TI00025S
Operating Instructions BA00053S
measuring devices via a Web browser.
Technical Information TI00025S
Operating Instructions BA00051S
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices and can be used in non-hazardous areas.
Operating Instructions BA01202S
90Endress+Hauser
Page 91
Proline Promag P 300
Field Xpert SFX370Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices and can be used in the non-hazardous area and in the hazardous
area.
Operating Instructions BA01202S
Field Xpert SMT70The Field Xpert SMT70 tablet PC for device configuration enables mobile plant
asset management in hazardous and non-hazardous areas. It is suitable for
commissioning and maintenance staff to manage field instruments with a digital
communication interface and to record progress.
This tablet PC is designed as an all-in-one solution with a preinstalled driver library
and is an easy-to-use, touch-sensitive tool which can be used to manage field
instruments throughout their entire life cycle.
• Technical Information TI01342S
• Operating Instructions BA01709S
• Product page: www.endress.com/smt70
Service-specific accessories
AccessoriesDescription
ApplicatorSoftware for selecting and sizing Endress+Hauser measuring devices:
• Choice of measuring devices for industrial requirements
• Calculation of all the necessary data for identifying the optimum flowmeter: e.g.
nominal diameter, pressure loss, flow velocity and accuracy.
• Graphic illustration of the calculation results
• Determination of the partial order code, administration, documentation and
access to all project-related data and parameters over the entire life cycle of a
project.
Applicator is available:
• Via the Internet: https://portal.endress.com/webapp/applicator
• As a downloadable DVD for local PC installation.
W@MW@M Life Cycle Management
Improved productivity with information at your fingertips. Data relevant to a plant
and its components is generated from the first stages of planning and during the
asset’s complete life cycle.
W@M Life Cycle Management is an open and flexible information platform with
online and on-site tools. Instant access for your staff to current, in-depth data
shortens your plant’s engineering time, speeds up procurement processes and
increases plant uptime.
Combined with the right services, W@M Life Cycle Management boosts
productivity in every phase. For more information, visit
www.endress.com/lifecyclemanagement
FieldCareFDT-based plant asset management tool from Endress+Hauser.
It can configure all smart field units in your system and helps you manage them. By
using the status information, it is also a simple but effective way of checking their
status and condition.
Operating Instructions BA00027S and BA00059S
DeviceCareTool to connect and configure Endress+Hauser field devices.
Innovation brochure IN01047S
System components
AccessoriesDescription
Memograph M graphic
data manager
The Memograph M graphic data manager provides information on all the relevant
measured variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on a SD card or USB stick.
• Technical Information TI00133R
• Operating Instructions BA00247R
Endress+Hauser91
Page 92
Proline Promag P 300
Supplementary documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from
nameplate
• Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D
matrix code (QR code) on the nameplate
Standard documentationBrief Operating Instructions