Direct current and alternating currentGround connection
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
Symbols for certain types of information
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Equipotential connection
A connection that has to be connected
to the plant grounding system: This
may be a potential equalization line
or a star grounding system depending
on national or company codes of
practice.
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
SymbolMeaningSymbolMeaning
1, 2, 3,...Item numbers
A, B, C, ...ViewsA-A, B-B, C-C, ... Sections
Hazardous area
Series of steps
Safe area (non-hazardous area)
Flow direction
Function and system design
Measuring principle
Endress+Hauser3
Following Faraday's law of magnetic induction, a voltage is induced in a conductor moving through a
magnetic field.
In the electromagnetic measuring principle, the flowing medium is the moving conductor. The
voltage induced (Ue) is proportional to the flow velocity (v) and is supplied to the amplifier by means
of two measuring electrodes. The flow volume (Q) is calculated via the pipe cross-section (A). The DC
magnetic field is created through a switched direct current of alternating polarity.
Formulae for calculation
• Induced voltage Ue = B · L · v
• Volume flow Q = A · v
4Endress+Hauser
Proline Promag P 200
Measuring system
The device consists of a transmitter and a sensor.
The device is available as a compact version:
The transmitter and sensor form a mechanical unit.
Transmitter
Promag 200Materials:
Aluminum, AlSi10Mg, coated
Configuration:
• External operation via four-line, illuminated local display with touch
control and guided menus ("Make-it-run" wizards) for applications
• Via operating tools (e.g. FieldCare)
A0013471
Sensor
Promag PNominal diameter range: DN 15 to 200 (½ to 8")
We only provide a warranty if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any inadvertent
changes to the device settings.
IT security measures in line with operators' security standards and designed to provide additional
protection for the device and device data transfer must be implemented by the operators themselves.
Input
Measured variableDirect measured variables
Volume flow (proportional to induced voltage)
Calculated measured variables
Mass flow
Measuring range
Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy
Endress+Hauser5
Flow characteristic values in SI units
Proline Promag P 200
Nominal
diameter
[mm][in][dm3/min][dm3/min][dm3][dm3/min]
15½4 to 100250,20,5
2519 to 300750,51
32–15 to 50012512
401 ½25 to 7002001,53
50235 to 11003002,55
65–60 to 200050058
80390 to 3000750512
1004145 to 470012001020
125–220 to 750018501530
150620 to 600 m3/h150 m3/h0.03 m
200835 to 1100 m3/h300 m3/h0.05 m
Recommended
flow
Min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
3
3
Low flow cut off
(v ~ 0.04 m/s)
2.5 m3/h
5 m3/h
Flow characteristic values in US units
Nominal
diameter
[in][mm][gal/min][gal/min][gal][gal/min]
½151.0 to 2760,10,15
1252.5 to 80180,20,25
1 ½407 to 190500,50,75
25010 to 300750,51,25
38024 to 80020022,5
410040 to 125030024
615090 to 2650600512
8200155 to 485012001015
Recommended
flow
Min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
To calculate the measuring range, use the Applicator sizing tool → 49
Recommended measuring range
"Flow limit" section → 34
Operable flow range
Over 1000 : 1
6Endress+Hauser
Proline Promag P 200
Output
Output signalCurrent output
Current output4-20 mA HART (passive)
Resolution< 1 µA
DampingAdjustable: 0.0 to 999.9 s
Assignable measured
variables
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionPassive, open collector
Maximum input values• DC 35 V
• Volume flow
• Mass flow
• 50 mA
For information on the Ex connection values → 10
Voltage drop• For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current≤ 0.05 mA
Pulse output
Pulse widthAdjustable: 5 to 2000 ms
Maximum pulse rate100 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Output frequencyAdjustable: 0 to 1000 Hz
DampingAdjustable: 0 to 999 s
Pulse/pause ratio1:1
Assignable measured
variables
Switch output
Switching behaviorBinary, conductive or non-conductive
Switching delayAdjustable: 0 to 100 s
Number of switching
cycles
Assignable functions• Off
• Volume flow
• Mass flow
• Volume flow
• Mass flow
Unlimited
• On
• Diagnostic behavior
• Limit value
– Volume flow
– Mass flow
• Flow direction monitoring
• Status
– Empty pipe detection
– Low flow cut off
Endress+Hauser7
FOUNDATION Fieldbus
Signal encodingManchester Bus Powered (MBP)
Data transfer31.25 KBit/s, Voltage mode
PROFIBUS PA
Signal encodingManchester Bus Powered (MBP)
Data transfer31.25 KBit/s, Voltage mode
Proline Promag P 200
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
HART
Device diagnosticsDevice condition can be read out via HART Command 48
Pulse/frequency/switch output
Pulse output
Failure modeChoose from:
• Actual value
• No pulses
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1250 Hz
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-912
0 mA
PROFIBUS PA
Status and alarm
messages
Error current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
8Endress+Hauser
Proline Promag P 200
0
100
200
300
400
500
14
161820
2224
26283032
U [V]
s
R [ ]bW
1.11.21
3436
Local display
Plain text displayWith information on cause and remedial measures
BacklightAdditionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Operating tool
• Via digital communication:
– HART protocol
– FOUNDATION Fieldbus
– PROFIBUS PA
• Via service interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 42
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply
unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage
• For US = 18 to 18.9 V: RB ≤ (US - 18 V): 0.0036 A
• For US = 18.9 to 24.5 V: RB ≤ (US - 13.5 V): 0.022 A
• For US = 24.5 to 30 V: RB ≤ 500 Ω
A0013563
1Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with non-Ex and Ex d
Sample calculation
Supply voltage of the power supply unit: US = 19 V
Maximum load: RB ≤ (19 V - 13.5 V): 0.022 A = 250 Ω
Endress+Hauser9
Ex connection dataSafety-related values
Type of protection Ex d
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Option EFOUNDATION FieldbusU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
Pulse/frequency/switch outputU
Pulse/frequency/switch outputU
Proline Promag P 200
= DC 35 V
nom
U
= 250 V
max
= DC 35 V
nom
U
= 250 V
max
= DC 35 V
nom
U
= 250 V
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Ex nA type of protection
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
10Endress+Hauser
Proline Promag P 200
Type of protection XP
Order code for "Output"Output typeSafety-related values
Option A4-20mA HARTU
Option B4-20mA HARTU
Pulse/frequency/switch outputU
Option EFOUNDATION FieldbusU
Pulse/frequency/switch outputU
Option GPROFIBUS PAU
Pulse/frequency/switch outputU
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V
= 250 V
= DC 35 V
= 250 V
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
= DC 32 V
= 250 V
= 0.88 W
= DC 35 V
= 250 V
1)
= 1 W
1)Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
Type of protection Ex ia
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Endress+Hauser11
Proline Promag P 200
Order code for "Output"Output typeIntrinsically safe values
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Type of protection Ex ic
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 35 V
Ii = n.a.
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 32 V
li = 300 mA
Pi = n.a.
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 35 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = n.a.
Pi = n.a.
Li = 10 µH
Ci = 5 nF
12Endress+Hauser
Proline Promag P 200
Type of protection IS
Order code for "Output"Output typeIntrinsically safe values
Option A4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Option B4-20mA HARTUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 5 nF
Pulse/frequency/switch outputUi = DC 30 V
Ii = 300 mA
Pi = 1 W
Li = 0 μH
Ci = 6 nF
Option EFOUNDATION FieldbusSTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
Option GPROFIBUS PASTANDARD
Ui = 30 V
li = 300 mA
Pi = 1.2 W
Li = 10 µH
Ci = 5 nF
Pulse/frequency/switch outputUi = 30 V
li = 300 mA
Pi = 1 W
Li = 0 µH
Ci = 6 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
FISCO
Ui = 17.5 V
li = 550 mA
Pi = 5.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
The switch points for low flow cut off are user-selectable.
All outputs are galvanically isolated from one another.
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x48
HART protocol revision7
Device description files
(DTM, DD)
HART load• Min. 250 Ω
Information and files under:
www.endress.com
• Max. 500 Ω
Endress+Hauser13
Dynamic variablesRead out the dynamic variables: HART command 3
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Off
• Volume flow
• Mass flow
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
Device variablesRead out the device variables: HART command 9
The device variables are permanently assigned.
FOUNDATION Fieldbus
Manufacturer ID0x452B48
Ident number0x1048
Device revision1
DD revisionInformation and files under:
CFF revision
Device Tester Version (ITK
version)
ITK Test Campaign NumberIT094200
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Max. response delayMin. 5
• www.endress.com
• www.fieldbus.org
6.1.1
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
Proline Promag P 200
14Endress+Hauser
Proline Promag P 200
Transducer Blocks
BlockContentsOutput values
Setup Transducer Block
(TRDSUP)
Advanced Setup
Transducer Block
(TRDASUP)
Display Transducer
Block
(TRDDISP)
HistoROM Transducer
Block
(TRDHROM)
Diagnostic Transducer
Block
(TRDDIAG)
Expert Configuration
Transducer Block
(TRDEXP)
Expert Information
Transducer Block
(TRDEXPIN)
Service Sensor
Transducer Block
(TRDSRVS)
Service Information
Transducer Block
(TRDSRVIF)
Total Inventory
Counter Transducer
Block
(TRDTIC)
Heartbeat Technology
Transducer Block
(TRDHBT)
Heartbeat Results 1
Transducer Block
(TRDHBTR1)
Heartbeat Results 2
Transducer Block
(TRDHBTR2)
Heartbeat Results 3
Transducer Block
(TRDHBTR3)
Heartbeat Results 4
Transducer Block
(TRDHBTR4)
All parameters for standard commissioning.No output values
All parameters for more accurate measurement
configuration.
Parameters for configuring the local display.No output values
Parameters for using the HistoROM function.No output values
Parameters that require the user to have indepth knowledge of the operation of the device
in order to configure the parameters
appropriately.
Parameters that provide information about the
state of the device.
Parameters that can only be accessed by Endress
+Hauser Service.
Parameters that provide Endress+Hauser Service
with information about the state of the device.
Parameters for configuring all the totalizers and
the inventory counter.
Parameters for the configuration and
comprehensive information about the results of
the verification.
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
No output values
• Temperature (7)
• Volume flow (9)
• Mass flow (11)
No output values
No output values
No output values
No output values
Process variables (AI Channel)
• Totalizer 1 (16)
• Totalizer 2 (17)
• Totalizer 3 (18)
No output values
Endress+Hauser15
Function blocks
Proline Promag P 200
BlockNumber
of
blocks
Resource Block
(RB)
Analog Input
Block
(AI)
Discrete Input
Block
(DI)
PID Block
(PID)
Multiple Digital
Output Block
(MDO)
Integrator Block
(IT)
1This Block (extended functionality) contains
4This Block (extended functionality) receives
2This Block (standard functionality) receives a
1This Block (standard functionality) acts as a
1This Block (standard functionality) receives
1This Block (standard functionality) integrates
ContentsProcess variables (Channel)
–
all the data that uniquely identify the device; it
is the equivalent of an electronic nameplate
for the device.
Process variables (AI Channel)
the measurement data provided by the Sensor
Block (can be selected via a channel number)
and makes the data available for other blocks
at the output.
Execution time: 25 ms
discrete value (e.g. indicator that measuring
range has been exceeded) and makes the
value available for other blocks at the output.
Execution time: 19 ms
proportional-integral-differential controller
and can be used universally for control in the
field. It enables cascading and feedforward
control.
Execution time: 25 ms
several discrete values and makes them
available for other blocks at the output.
Execution time: 19 ms
a measured variable over time or totalizes the
pulses from a Pulse Input Block. The Block can
be used as a totalizer that totalizes until a
reset, or as a batch totalizer whereby the
integrated value is compared against a target
value generated before or during the control
routine and generates a binary signal when
the target value is reached.
Execution time: 21 ms
• Temperature (7)
• Volume flow (9)
• Mass flow (11)
• Switch output state (101)
• Empty pipe detection (102)
• Low flow cut off (103)
• Status verification (105)
–
Channel_DO (122)
• Value 1: Reset totalizer 1
• Value 2: Reset totalizer 2
• Value 3: Reset totalizer 3
• Value 4: Flow override
• Value 5: Start heartbeat
verification
• Value 6: Status switch output
• Value 7: Not assigned
• Value 8: Not assigned
–
PROFIBUS PA
Manufacturer ID0x11
Ident number0x1563
Profile version3.02
Device description files (GSD,
DTM, DD)
Information and files under:
• www.endress.com
• www.profibus.org
16Endress+Hauser