Endress+Hauser P 200 Specifications

TI01062D/06/EN/03.15 71294170
Products Solutions Services
Technical Information
Proline Promag P 200
Electromagnetic flowmeter
The flowmeter for highest medium temperatures with genuine loop-powered technology
Application
• The measuring principle is virtually independent of pressure, density, temperature and viscosity
• Dedicated for chemical and process applications with corrosive liquids and high medium temperatures
Device properties
• All common Ex approvals
• Liner made of PTFE or PFA
• Loop-powered technology
• Robust two-chamber housing
• Plant safety: worldwide approvals (SIL, Haz. area)
Your benefits
• Versatile applications – wide variety of wetted materials
• Energy-saving flow measurement – no pressure loss due to cross-section constriction
• Maintenance-free – no moving parts
• Convenient device wiring – separate connection compartment
• Safe operation – no need to open the device due to display with touch control, background lighting
• Integrated verification – Heartbeat Technology™

Table of contents

Proline Promag P 200
Document information ....................... 3
Symbols used ................................ 3
Function and system design ................... 3
Measuring principle ............................ 3
Measuring system ............................. 5
Safety ..................................... 5
Input ..................................... 5
Measured variable ............................. 5
Measuring range .............................. 5
Operable flow range ........................... 6
Output ................................... 7
Output signal ................................ 7
Signal on alarm ............................... 8
Load ...................................... 9
Ex connection data ........................... 10
Low flow cut off ............................. 13
Galvanic isolation ............................ 13
Protocol-specific data .......................... 13
Power supply ............................. 17
Terminal assignment .......................... 17
Pin assignment, device plug ...................... 18
Supply voltage .............................. 18
Power consumption ........................... 19
Current consumption .......................... 19
Power supply failure .......................... 19
Electrical connection .......................... 20
Potential equalization ......................... 23
Terminals ................................. 24
Cable entries ............................... 24
Cable specification ............................ 24
Overvoltage protection ......................... 25
Process .................................. 31
Medium temperature range ...................... 31
Conductivity ................................ 31
Pressure-temperature ratings .................... 31
Pressure tightness ............................ 33
Flow limit ................................. 34
Pressure loss ............................... 34
System pressure ............................. 34
Vibrations ................................. 34
Mechanical construction .................... 35
Dimensions in SI units ......................... 35
Dimensions in US units ......................... 36
Weight ................................... 38
Measuring tube specification ..................... 38
Materials .................................. 39
Fitted electrodes ............................. 40
Process connections ........................... 40
Surface roughness ............................ 40
Operability ............................... 41
Operating concept ............................ 41
Local operation .............................. 41
Remote operation ............................ 42
Service interface ............................. 44
Certificates and approvals ................... 45
CE mark ................................... 45
C-Tick symbol ............................... 45
Ex approval ................................ 45
Functional safety ............................. 46
HART certification ............................ 46
FOUNDATION Fieldbus certification ................ 46
Certification PROFIBUS ......................... 46
Other standards and guidelines ................... 46
Performance characteristics .................. 25
Reference operating conditions ................... 25
Maximum measured error ....................... 26
Repeatability ............................... 26
Influence of ambient temperature ................. 26
Installation ............................... 27
Mounting location ............................ 27
Orientation ................................ 28
Inlet and outlet runs .......................... 28
Adapters .................................. 28
Special mounting instructions .................... 29
Ordering information ....................... 47
Application packages ....................... 47
Diagnostics functions .......................... 47
Heartbeat Technology ......................... 47
Accessories ............................... 48
Device-specific accessories ...................... 48
Communication-specific accessories ................ 49
Service-specific accessories ...................... 49
System components ........................... 50
Documentation ............................ 50
Environment .............................. 29
Ambient temperature range ..................... 29
Storage temperature .......................... 30
Degree of protection .......................... 30
Shock resistance ............................. 30
Vibration resistance ........................... 30
Mechanical load ............................. 30
Electromagnetic compatibility (EMC) ............... 30
Standard documentation ........................ 50
Supplementary device-dependent documentation ....... 51
Registered trademarks ...................... 51
2 Endress+Hauser
Proline Promag P 200
,…,
-
.

Document information

Symbols used Electrical symbols

Symbol Meaning Symbol Meaning
Direct current Alternating current
Direct current and alternating current Ground connection
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Symbols for certain types of information
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential equalization line or a star grounding system depending on national or company codes of practice.
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbols in graphics
Symbol Meaning Symbol Meaning
1, 2, 3,... Item numbers
A, B, C, ... Views A-A, B-B, C-C, ... Sections
Hazardous area
Series of steps
Safe area (non-hazardous area)
Flow direction

Function and system design

Measuring principle

Endress+Hauser 3
Following Faraday's law of magnetic induction, a voltage is induced in a conductor moving through a magnetic field.
Proline Promag P 200
I
L
B
I
U
e
v
A0017035
Ue Induced voltage B Magnetic induction (magnetic field) L Electrode spacing I Current v Flow velocity
In the electromagnetic measuring principle, the flowing medium is the moving conductor. The voltage induced (Ue) is proportional to the flow velocity (v) and is supplied to the amplifier by means of two measuring electrodes. The flow volume (Q) is calculated via the pipe cross-section (A). The DC magnetic field is created through a switched direct current of alternating polarity.
Formulae for calculation
• Induced voltage Ue = B · L · v
• Volume flow  Q = A · v
4 Endress+Hauser
Proline Promag P 200

Measuring system

The device consists of a transmitter and a sensor.
The device is available as a compact version: The transmitter and sensor form a mechanical unit.
Transmitter
Promag 200 Materials:
Aluminum, AlSi10Mg, coated
Configuration:
• External operation via four-line, illuminated local display with touch control and guided menus ("Make-it-run" wizards) for applications
• Via operating tools (e.g. FieldCare)
A0013471
Sensor
Promag P Nominal diameter range: DN 15 to 200 (½ to 8")
Materials:
• Sensor housing: aluminum, AlSi10Mg, coated
• Measuring tubes: stainless steel, 1.4301/1.4306
• Liner: PFA, PTFE
• Electrodes: stainless steel, 1.4435 (F316L); Alloy C22, 2.4602 (UNS N06022); platinum; tantalum; titanium
• Process connections: stainless steel, 1.0425/316L/1.4571/316L;
A0017703
carbon steel, A105/F316L/FE410WB/HII/S235JRG2; Alloy C22,
2.4602 (UNS N06022)
• Seals: as per DIN EN 1514-1
• Ground disks: stainless steel, 1.4435 (316L); Alloy C22, 2.4602 (UNS N06022); tantalum; titanium

Safety IT security

We only provide a warranty if the device is installed and used as described in the Operating Instructions. The device is equipped with security mechanisms to protect it against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide additional protection for the device and device data transfer must be implemented by the operators themselves.

Input

Measured variable Direct measured variables

Volume flow (proportional to induced voltage)
Calculated measured variables
Mass flow

Measuring range

Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy
Endress+Hauser 5
Flow characteristic values in SI units
Proline Promag P 200
Nominal
diameter
[mm] [in] [dm3/min] [dm3/min] [dm3] [dm3/min]
15 ½ 4 to 100 25 0,2 0,5
25 1 9 to 300 75 0,5 1
32 15 to 500 125 1 2
40 1 ½ 25 to 700 200 1,5 3
50 2 35 to 1 100 300 2,5 5
65 60 to 2 000 500 5 8
80 3 90 to 3 000 750 5 12
100 4 145 to 4 700 1200 10 20
125 220 to 7 500 1850 15 30
150 6 20 to 600 m3/h 150 m3/h 0.03 m
200 8 35 to 1 100 m3/h 300 m3/h 0.05 m
Recommended
flow
Min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
3
3
Low flow cut off
(v ~ 0.04 m/s)
2.5 m3/h
5 m3/h
Flow characteristic values in US units
Nominal
diameter
[in] [mm] [gal/min] [gal/min] [gal] [gal/min]
½ 15 1.0 to 27 6 0,1 0,15
1 25 2.5 to 80 18 0,2 0,25
1 ½ 40 7 to 190 50 0,5 0,75
2 50 10 to 300 75 0,5 1,25
3 80 24 to 800 200 2 2,5
4 100 40 to 1 250 300 2 4
6 150 90 to 2 650 600 5 12
8 200 155 to 4 850 1200 10 15
Recommended
flow
Min./max. full scale value
(v ~ 0.3/10 m/s)
Factory settings
Full scale value current
output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
To calculate the measuring range, use the Applicator sizing tool →  49
Recommended measuring range
"Flow limit" section →  34

Operable flow range

Over 1000 : 1
6 Endress+Hauser
Proline Promag P 200

Output

Output signal Current output

Current output 4-20 mA HART (passive)
Resolution < 1 µA
Damping Adjustable: 0.0 to 999.9 s
Assignable measured variables
Pulse/frequency/switch output
Function Can be set to pulse, frequency or switch output
Version Passive, open collector
Maximum input values • DC 35 V
• Volume flow
• Mass flow
• 50 mA
For information on the Ex connection values →  10
Voltage drop • For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current ≤ 0.05 mA
Pulse output
Pulse width Adjustable: 5 to 2 000 ms
Maximum pulse rate 100 Impulse/s
Pulse value Adjustable
Assignable measured variables
Frequency output
Output frequency Adjustable: 0 to 1 000 Hz
Damping Adjustable: 0 to 999 s
Pulse/pause ratio 1:1
Assignable measured variables
Switch output
Switching behavior Binary, conductive or non-conductive
Switching delay Adjustable: 0 to 100 s
Number of switching cycles
Assignable functions • Off
• Volume flow
• Mass flow
• Volume flow
• Mass flow
Unlimited
• On
• Diagnostic behavior
• Limit value – Volume flow – Mass flow
• Flow direction monitoring
• Status – Empty pipe detection – Low flow cut off
Endress+Hauser 7
FOUNDATION Fieldbus
Signal encoding Manchester Bus Powered (MBP)
Data transfer 31.25 KBit/s, Voltage mode
PROFIBUS PA
Signal encoding Manchester Bus Powered (MBP)
Data transfer 31.25 KBit/s, Voltage mode
Proline Promag P 200

Signal on alarm

Depending on the interface, failure information is displayed as follows:
Current output
HART
Device diagnostics Device condition can be read out via HART Command 48
Pulse/frequency/switch output
Pulse output
Failure mode Choose from:
• Actual value
• No pulses
Frequency output
Failure mode Choose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1 250 Hz
Switch output
Failure mode Choose from:
• Current status
• Open
• Closed
FOUNDATION Fieldbus
Status and alarm messages
Error current FDE (Fault Disconnection Electronic)
Diagnostics in accordance with FF-912
0 mA
PROFIBUS PA
Status and alarm messages
Error current FDE (Fault Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
8 Endress+Hauser
Proline Promag P 200
0
100
200
300
400
500
14
16 18 20
22 24
26 28 30 32
U [V]
s
R [ ]bW
1.1 1.21
34 36
Local display
Plain text display With information on cause and remedial measures
Backlight Additionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Operating tool
• Via digital communication: – HART protocol – FOUNDATION Fieldbus – PROFIBUS PA
• Via service interface
Plain text display With information on cause and remedial measures
Additional information on remote operation →  42

Load

Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power supply unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB) including line resistance must be observed to ensure adequate terminal voltage at the device. In doing so, observe the minimum terminal voltage
• For US = 18 to 18.9 V: RB ≤ (US - 18 V): 0.0036 A
• For US = 18.9 to 24.5 V: RB ≤ (US - 13.5 V): 0.022 A
• For US = 24.5 to 30 V: RB ≤ 500 Ω
A0013563
1 Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with non-Ex and Ex d
Sample calculation
Supply voltage of the power supply unit: US = 19 V Maximum load: RB ≤ (19 V - 13.5 V): 0.022 A = 250 Ω
Endress+Hauser 9

Ex connection data Safety-related values

Type of protection Ex d
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
Option E FOUNDATION Fieldbus U
Option G PROFIBUS PA U
Pulse/frequency/switch output U
Pulse/frequency/switch output U
Pulse/frequency/switch output U
Proline Promag P 200
= DC 35 V
nom
U
= 250 V
max
= DC 35 V
nom
U
= 250 V
max
= DC 35 V
nom
U
= 250 V
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
1)
= 1 W
= DC 32 V = 250 V = 0.88 W
= DC 35 V = 250 V
1)
= 1 W
= DC 32 V = 250 V = 0.88 W
= DC 35 V = 250 V
1)
= 1 W
1) Internal circuit limited by Ri = 760.5 Ω
Ex nA type of protection
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
Pulse/frequency/switch output U
Option E FOUNDATION Fieldbus U
Pulse/frequency/switch output U
Option G PROFIBUS PA U
Pulse/frequency/switch output U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 32 V = 250 V = 0.88 W
= DC 35 V = 250 V
1)
= 1 W
= DC 32 V = 250 V = 0.88 W
= DC 35 V = 250 V
1)
= 1 W
1) Internal circuit limited by Ri = 760.5 Ω
10 Endress+Hauser
Proline Promag P 200
Type of protection XP
Order code for "Output" Output type Safety-related values
Option A 4-20mA HART U
Option B 4-20mA HART U
Pulse/frequency/switch output U
Option E FOUNDATION Fieldbus U
Pulse/frequency/switch output U
Option G PROFIBUS PA U
Pulse/frequency/switch output U
nom
U
max
nom
U
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
nom
U
max
P
max
= DC 35 V = 250 V
= DC 35 V = 250 V
= DC 35 V = 250 V
1)
= 1 W
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
= DC 32 V = 250 V
= 0.88 W
= DC 35 V = 250 V
1)
= 1 W
1) Internal circuit limited by Ri = 760.5 Ω
Intrinsically safe values
Type of protection Ex ia
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
Endress+Hauser 11
Proline Promag P 200
Order code for "Output" Output type Intrinsically safe values
Option G PROFIBUS PA STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Type of protection Ex ic
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 35 V
Ii = n.a. Pi = 1 W Li = 0 μH Ci = 6 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 32 V li = 300 mA Pi = n.a. Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 35 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Option G PROFIBUS PA STANDARD
Ui = 32 V li = 300 mA Pi = n.a. Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 35 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = n.a. Pi = n.a. Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = n.a. Pi = n.a. Li = 10 µH Ci = 5 nF
12 Endress+Hauser
Proline Promag P 200
Type of protection IS
Order code for "Output" Output type Intrinsically safe values
Option A 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Option B 4-20mA HART Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 5 nF
Pulse/frequency/switch output Ui = DC 30 V
Ii = 300 mA Pi = 1 W Li = 0 μH Ci = 6 nF
Option E FOUNDATION Fieldbus STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
Option G PROFIBUS PA STANDARD
Ui = 30 V li = 300 mA Pi = 1.2 W Li = 10 µH Ci = 5 nF
Pulse/frequency/switch output Ui = 30 V
li = 300 mA Pi = 1 W Li = 0 µH Ci = 6 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF
FISCO Ui = 17.5 V li = 550 mA Pi = 5.5 W Li = 10 µH Ci = 5 nF

Low flow cut off

Galvanic isolation

The switch points for low flow cut off are user-selectable.
All outputs are galvanically isolated from one another.

Protocol-specific data HART

Manufacturer ID 0x11
Device type ID 0x48
HART protocol revision 7
Device description files (DTM, DD)
HART load • Min. 250 Ω
Information and files under:
www.endress.com
• Max. 500 Ω
Endress+Hauser 13
Dynamic variables Read out the dynamic variables: HART command 3
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Off
• Volume flow
• Mass flow
Measured variables for SV, TV, QV (secondary, tertiary and quaternary dynamic variable)
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
Device variables Read out the device variables: HART command 9
The device variables are permanently assigned.
FOUNDATION Fieldbus
Manufacturer ID 0x452B48
Ident number 0x1048
Device revision 1
DD revision Information and files under:
CFF revision
Device Tester Version (ITK version)
ITK Test Campaign Number IT094200
Link Master capability (LAS) Yes
Choice of "Link Master" and "Basic Device"
Node address Factory setting: 247 (0xF7)
Supported functions The following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs 44
Number of link objects in VFD 50
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Device Link Capabilities
Slot time 4
Min. delay between PDU 8
Max. response delay Min. 5
www.endress.com
www.fieldbus.org
6.1.1
Yes Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
Proline Promag P 200
14 Endress+Hauser
Proline Promag P 200
Transducer Blocks
Block Contents Output values
Setup Transducer Block (TRDSUP)
Advanced Setup Transducer Block (TRDASUP)
Display Transducer Block (TRDDISP)
HistoROM Transducer Block (TRDHROM)
Diagnostic Transducer Block (TRDDIAG)
Expert Configuration Transducer Block (TRDEXP)
Expert Information Transducer Block (TRDEXPIN)
Service Sensor Transducer Block (TRDSRVS)
Service Information Transducer Block (TRDSRVIF)
Total Inventory Counter Transducer Block (TRDTIC)
Heartbeat Technology Transducer Block (TRDHBT)
Heartbeat Results 1 Transducer Block (TRDHBTR1)
Heartbeat Results 2 Transducer Block (TRDHBTR2)
Heartbeat Results 3 Transducer Block (TRDHBTR3)
Heartbeat Results 4 Transducer Block (TRDHBTR4)
All parameters for standard commissioning. No output values
All parameters for more accurate measurement configuration.
Parameters for configuring the local display. No output values
Parameters for using the HistoROM function. No output values
Diagnostics information. Process variables (AI Channel)
Parameters that require the user to have in­depth knowledge of the operation of the device in order to configure the parameters appropriately.
Parameters that provide information about the state of the device.
Parameters that can only be accessed by Endress +Hauser Service.
Parameters that provide Endress+Hauser Service with information about the state of the device.
Parameters for configuring all the totalizers and the inventory counter.
Parameters for the configuration and comprehensive information about the results of the verification.
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
Information about the results of the verification. No output values
No output values
• Temperature (7)
• Volume flow (9)
• Mass flow (11)
No output values
No output values
No output values
No output values
Process variables (AI Channel)
• Totalizer 1 (16)
• Totalizer 2 (17)
• Totalizer 3 (18)
No output values
Endress+Hauser 15
Function blocks
Proline Promag P 200
Block Number
of
blocks
Resource Block (RB)
Analog Input Block (AI)
Discrete Input Block (DI)
PID Block (PID)
Multiple Digital Output Block (MDO)
Integrator Block (IT)
1 This Block (extended functionality) contains
4 This Block (extended functionality) receives
2 This Block (standard functionality) receives a
1 This Block (standard functionality) acts as a
1 This Block (standard functionality) receives
1 This Block (standard functionality) integrates
Contents Process variables (Channel)
– all the data that uniquely identify the device; it is the equivalent of an electronic nameplate for the device.
Process variables (AI Channel) the measurement data provided by the Sensor Block (can be selected via a channel number) and makes the data available for other blocks at the output.
Execution time: 25 ms
discrete value (e.g. indicator that measuring range has been exceeded) and makes the value available for other blocks at the output.
Execution time: 19 ms
proportional-integral-differential controller and can be used universally for control in the field. It enables cascading and feedforward control.
Execution time: 25 ms
several discrete values and makes them available for other blocks at the output.
Execution time: 19 ms
a measured variable over time or totalizes the pulses from a Pulse Input Block. The Block can be used as a totalizer that totalizes until a reset, or as a batch totalizer whereby the integrated value is compared against a target value generated before or during the control routine and generates a binary signal when the target value is reached.
Execution time: 21 ms
• Temperature (7)
• Volume flow (9)
• Mass flow (11)
• Switch output state (101)
• Empty pipe detection (102)
• Low flow cut off (103)
• Status verification (105)
Channel_DO (122)
• Value 1: Reset totalizer 1
• Value 2: Reset totalizer 2
• Value 3: Reset totalizer 3
• Value 4: Flow override
• Value 5: Start heartbeat verification
• Value 6: Status switch output
• Value 7: Not assigned
• Value 8: Not assigned
PROFIBUS PA
Manufacturer ID 0x11
Ident number 0x1563
Profile version 3.02
Device description files (GSD, DTM, DD)
Information and files under:
www.endress.com
www.profibus.org
16 Endress+Hauser