10.1 Function check ...................................................................... 43
10.2 Establishing a connection via FieldCare .................................................... 43
10.3 Configuring the device address via software ................................................. 43
10.4 Configuring the measuring device ........................................................ 44
10.5 Defining the tag name ................................................................. 44
10.6 Protecting settings from unauthorized access ................................................ 44
11Diagnostic information ......................................................... 47
Endress+Hauser3
Page 4
Document informationProline Promag P 100
DANGER
WARNING
CAUTION
NOTICE
1 Document information
1.1 Symbols used
1.1.1 Safety symbols
SymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in personal
injury.
1.1.2 Electrical symbols
SymbolMeaning
Direct current
A terminal to which DC voltage is applied or through which direct current flows.
Alternating current
A terminal to which alternating voltage is applied or through which alternating current flows.
Direct current and alternating current
• A terminal to which alternating voltage or DC voltage is applied.
• A terminal through which alternating current or direct current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
equalization line or a star grounding system depending on national or company codes of practice.
4Endress+Hauser
Page 5
Proline Promag P 100Document information
,…,
,…,
1.1.3 Tool symbols
SymbolMeaning
Allen key
Open-ended wrench
1.1.4 Symbols for certain types of information
SymbolMeaning
Permitted
Indicates procedures, processes or actions that are permitted.
Preferred
Indicates procedures, processes or actions that are preferred.
Forbidden
Indicates procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Refers to the corresponding device documentation.
Reference to page
Refers to the corresponding page number.
Reference to graphic
Refers to the corresponding graphic number and page number.
Series of steps
Result of a sequence of actions
Visual inspection
1.1.5 Symbols in graphics
SymbolMeaning
1, 2, 3,...Item numbers
Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
Flow direction
Endress+Hauser5
Page 6
Basic safety instructionsProline Promag P 100
-
.
SymbolMeaning
Hazardous area
Indicates a hazardous area.
Safe area (non-hazardous area)
Indicates the non-hazardous area.
2 Basic safety instructions
2.1 Requirements for the personnel
The personnel must fulfill the following requirements for its tasks:
Trained, qualified specialists must have a relevant qualification for this specific function
‣
and task
Are authorized by the plant owner/operator
‣
Are familiar with federal/national regulations
‣
Before beginning work, the specialist staff must have read and understood the instructions
‣
in the Operating Instructions and supplementary documentation as well as in the
certificates (depending on the application)
Following instructions and basic conditions
‣
2.2 Designated use
Application and media
Depending on the version ordered, the measuring device can also measure potentially
explosive, flammable, poisonous and oxidizing media.
Measuring devices for use in hazardous areas, in hygienic applications or in applications
where there is an increased risk due to process pressure, are labeled accordingly on the
nameplate.
To ensure that the measuring device remains in proper condition for the operation time:
Only use the measuring device in full compliance with the data on the nameplate and the
‣
general conditions listed in the Operating Instructions and supplementary documentation.
Based on the nameplate, check whether the ordered device is permitted for the intended
‣
use in the hazardous area (e.g. explosion protection, pressure vessel safety).
Use the measuring device only for media against which the process-wetted materials are
‣
adequately resistant.
If the measuring device is not operated at atmospheric temperature, compliance with the
‣
relevant basic conditions specified in the associated device documentation is absolutely
essential: "Device documentation" section (Verweisziel existiert nicht, aber
@y.link.required='true').
Incorrect use
Non-designated use can compromise safety. The manufacturer is not liable for damage caused
by improper or non-designated use.
6Endress+Hauser
Page 7
Proline Promag P 100Basic safety instructions
WARNING
L
Danger of breakage of the sensor due to corrosive or abrasive fluids!
Verify the compatibility of the process fluid with the sensor material.
‣
Ensure the resistance of all fluid-wetted materials in the process.
‣
Observe the specified pressure and temperature range.
‣
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in
‣
verifying the corrosion resistance of fluid-wetted materials, but does not accept any
warranty or liability as minute changes in the temperature, concentration or level of
contamination in the process can alter the corrosion resistance properties.
Residual risks
The external surface temperature of the housing can increase by max. 10 K due to the power
consumption of the electronic components. Hot process fluids passing through the measuring
device will further increase the surface temperature of the housing. The surface of the sensor,
in particular, can reach temperatures which are close to the fluid temperature.
Possible burn hazard due to fluid temperatures!
For elevated fluid temperature, ensure protection against contact to prevent burns.
‣
2.3 Workplace safety
For work on and with the device:
Wear the required personal protective equipment according to federal/national
‣
regulations.
For welding work on the piping:
Do not ground the welding unit via the measuring device.
‣
If working on and with the device with wet hands:
It is recommended to wear gloves on account of the higher risk of electric shock.
‣
2.4 Operational safety
Risk of injury.
Operate the device in proper technical condition and fail-safe condition only.
‣
The operator is responsible for interference-free operation of the device.
‣
2.5 Product safety
This measuring device is designed in accordance with good engineering practice to meet stateof-the-art safety requirements, has been tested, and left the factory in a condition in which it
is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EC
directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms
this by affixing the CE mark to the device.
Endress+Hauser7
Page 8
Basic safety instructionsProline Promag P 100
2.6 IT security
We only provide a warranty if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any
inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
8Endress+Hauser
Page 9
Proline Promag P 100Product description
3
2
1
4
5
6
7
3 Product description
3.1 Product design
3.1.1 Device version with HART, EtherNet/IP and PROFIBUS DP communication
types
Proline Promag P 100Incoming acceptance and product identification
1
+
2
1
+
2
4 Incoming acceptance and product identification
4.1 Incoming acceptance
Are the order codes on the
delivery note (1) and the
product sticker (2) identical?
Are the goods undamaged?
Do the nameplate data match
the ordering information on
the delivery note?
Is the CD-ROM with the
Technical Documentation
(depends on device version)
and documents present?
• If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center.
• Depending on the device version, the CD-ROM might not be part of the delivery! The
Technical Documentation is available via the Internet or via the Endress+HauserOperations App.
Endress+Hauser11
Page 12
Storage and transportProline Promag P 100
Order code:
Ext. ord. cd.:
Ser. no.:
Order code:
Ext. ord. cd.:
Ser. no.:
1
2
3
4
4.2 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is displayed.
• Enter the serial number from the nameplates into the Endress+Hauser Operations App or
scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser OperationsApp: all the information for the measuring device is displayed.
A0021952
3Example of a nameplate
1Order code
2Serial number (Ser. no.)
3Extended order code (Ext. ord. cd.)
42-D matrix code (QR code)
For detailed information on the breakdown of the specifications on the nameplate, see
the Operating Instructions for the device .
5 Storage and transport
5.1 Storage conditions
Observe the following notes for storage:
• Store in original packaging.
• Do not remove protective covers or protective caps installed on process connections.
• Protect from direct sunlight.
• Select a storage location where moisture cannot collect in the measuring device.
• Store in a dry and dust-free place.
• Do not store outdoors.
• Storage temperature→ 14
12Endress+Hauser
Page 13
Proline Promag P 100Storage and transport
5.2 Transporting the product
WARNING
L
Center of gravity of the measuring device is higher than the suspension points of the
webbing slings.
Risk of injury if the measuring device slips.
Secure the measuring device from rotating or slipping.
‣
Observe the weight specified on the packaging (stick-on label).
‣
Observe the transport instructions on the stick-on label on the electronics compartment
‣
cover.
A0015606
• Transport the measuring device to the measuring point in the original packaging.
• Do not remove protective covers or protective caps installed on process connections.
They prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
A0015604
Endress+Hauser13
Page 14
MountingProline Promag P 100
h
h
2
1
6 Mounting
6.1 Installation conditions
6.1.1 Mounting position
Mounting location
A0023343
h ≥ 2 × DN
Installation in down pipes
Install a siphon with a vent valve downstream of the sensor in down pipes whose length h ≥
5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of damage to
the measuring tube. This measure also prevents the system losing prime.
A0017064
4Installation in a down pipe
1Vent valve
2Pipe siphon
hLength of down pipe
14Endress+Hauser
Page 15
Proline Promag P 100Mounting
³ 5 × DN
³ 2 × DN
Installation in partially filled pipes
A partially filled pipe with a gradient necessitates a drain-type configuration. The empty pipe
detection (EPD) function offers additional protection by detecting empty or partially filled
pipes.
A0017063
Orientation
The direction of the arrow on the sensor nameplate helps you to install the sensor according
to the flow direction.
An optimum orientation position helps avoid gas and air accumulations and deposits in the
measuring tube.
Vertical
A0015591
This is the optimum for self-emptying piping systems and for use in conjunction with empty
pipe detection.
Endress+Hauser15
Page 16
MountingProline Promag P 100
1
2
3
2
5 × DN≥
2 × DN≥
Horizontal
A0016260
1EPD electrode for empty pipe detection
2Measuring electrodes for signal detection
3Reference electrode for potential equalization
• The measuring electrode plane must be horizontal. This prevents brief insulation of
the two measuring electrodes by entrained air bubbles.
• The empty pipe detection only works if the transmitter housing is pointing upwards as
otherwise there is no guarantee that the empty pipe detection function will actually
respond to a partially filled or empty measuring tube.
Inlet and outlet runs
For the dimensions and installation lengths of the device, see the "Technical Information"
document, "Mechanical construction" section
6.1.2 Requirements from environment and process
Ambient temperature range
For detailed information on the ambient temperature range, see the Operating
Instructions for the device (Verweisziel existiert nicht, aber @y.link.required='true')
If operating outdoors:
• Install the measuring device in a shady location.
• Avoid direct sunlight, particularly in warm climatic regions.
• Avoid direct exposure to weather conditions.
16Endress+Hauser
A0016275
Page 17
Proline Promag P 100Mounting
L
Temperature tables
SI units
T
a
[°C]
305095130150150150
50–95130150150150
60–95110110110110
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
T1
[450 °C]
US units
T
a
[°F]
86122203266302302302
122–203266302302302
140–203230230230230
T6
[185 °F]
T5
[212 °F]
T4
[275 °F]
T3
[392 °F]
T2
[572 °F]
T1
[842 °F]
System pressure
A0015594
Furthermore, install pulse dampers if reciprocating, diaphragm or peristaltic pumps are
used.
Vibrations
A0016266
5Measures to avoid device vibrations (L > 10 m (33 ft))
Endress+Hauser17
Page 18
MountingProline Promag P 100
100
10
0.5
d / D
[mbar]
0.60.70.80.9
1 m/s
2 m/s
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
1
D
d
max. 8°
Adapters
A0016359
6.2 Mounting the measuring device
6.2.1 Required tools
For sensor
For flanges and other process connections:
• Screws, nuts, seals etc. are not included in the scope of supply and must be provided by the
customer.
• Appropriate mounting tools
6.2.2 Preparing the measuring device
1.Remove all remaining transport packaging.
2.Remove any protective covers or protective caps present from the sensor.
3.Remove stick-on label on the electronics compartment cover.
18Endress+Hauser
Page 19
Proline Promag P 100Mounting
6.2.3 Mounting the sensor
WARNING
L
Danger due to improper process sealing!
Ensure that the inside diameters of the gaskets are greater than or equal to that of the
‣
process connections and piping.
Ensure that the gaskets are clean and undamaged.
‣
Install the gaskets correctly.
‣
1.Ensure that the direction of the arrow on the sensor matches the flow direction of the
medium.
2.To ensure compliance with device specifications, install the measuring device between
the pipe flanges in a way that it is centered in the measurement section.
3.If using ground disks, comply with the Installation Instructions provided.
5.Install the measuring device or turn the transmitter housing so that the cable entries do
not point upwards.
A0013964
Mounting the seals
CAUTION
L
An electrically conductive layer could form on the inside of the measuring tube!
Risk of measuring signal short circuit.
Do not use electrically conductive sealing compounds such as graphite.
‣
Comply with the following instructions when installing seals:
• When mounting the process connections, make sure that the seals concerned are clean and
centered correctly.
• For DIN flanges: only use seals according to DIN EN 1514-1.
• For "PFA" lining: additional seals are always required.
• For "PTFE" lining: generally additional seals are not required.
Mounting the ground cable/ground disks
Comply with the information on potential equalization and detailed mounting instructions for
the use of ground cables/ground disks → 31.
Screw tightening torques
For detailed information on the screw tightening torques, see the "Mounting the sensor"
section of the Operating Instructions for the device
Endress+Hauser19
Page 20
MountingProline Promag P 100
1.
2.
3.
4.
5.
6.
7.
4.
4.
3 mm
6.2.4 Turning the display module
The display module can be turned to optimize display readability.
Aluminum housing version, AlSi10Mg, coated
6.3 Post-installation check
Is the device undamaged (visual inspection)?
Does the measuring device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure (refer to the section on "Pressure-temperature ratings" in the "Technical Information"
document on the CD-ROM provided)
• Ambient temperature
• Measuring range
Has the correct orientation for the sensor been selected ?
• According to sensor type
• According to medium temperature
• According to medium properties (outgassing, with entrained solids)
Does the arrow on the sensor nameplate match the direction of flow of the fluid through the piping ?
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected from precipitation and direct sunlight?
Have the fixing screws been tightened with the correct tightening torque?
20Endress+Hauser
A0023192
Page 21
Proline Promag P 100Electrical connection
7 Electrical connection
The measuring device does not have an internal circuit breaker. For this reason, assign
the measuring device a switch or power-circuit breaker so that the power supply line can
be easily disconnected from the mains.
7.1 Connection conditions
7.1.1 Required tools
• For cable entries: Use corresponding tools
• For securing clamp (on aluminum housing): Allen screw3 mm
• For securing screw (for stainless steel housing): open-ended wrench 8 mm
• Wire stripper
• When using stranded cables: crimping tool for ferrule
7.1.2 Requirements for connecting cable
The connecting cables provided by the customer must fulfill the following requirements.
Electrical safety
In accordance with applicable federal/national regulations.
Permitted temperature range
• –40 °C (–40 °F) to +80 °C (+176 °F)
• Minimum requirement: cable temperature range ≥ ambient temperature +20 K
Power supply cable
Standard installation cable is sufficient.
Signal cable
Current output
For 4-20 mA HART: Shielded cable recommended. Observe grounding concept of the plant.
Pulse/frequency/switch output
Standard installation cable is sufficient.
PROFIBUS DP
The IEC 61158 standard specifies two types of cable (A and B) for the bus line which can be
used for every transmission rate. Cable type A is recommended.
Cable typeA
Characteristic impedance135 to 165 Ωat a measuring frequency of 3 to 20 MHz
Cable capacitance<30 pF/m
Wire cross-section
Cable typeTwisted pairs
Endress+Hauser21
>0.34 mm2 (22 AWG)
Page 22
Electrical connectionProline Promag P 100
Loop resistance≤110 Ω/km
Signal dampingMax. 9 dB over the entire length of the cable cross-section
ShieldingCopper braided shielding or braided shielding with foil shield. When grounding the
cable shield, observe the grounding concept of the plant.
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be
used for every transmission rate. Cable type A is recommended.
Cable typeA
Characteristic impedance135 to 165 Ωat a measuring frequency of 3 to 20 MHz
Cable capacitance<30 pF/m
Wire cross-section
Cable typeTwisted pairs
Loop resistance≤110 Ω/km
Signal dampingMax. 9 dB over the entire length of the cable cross-section
ShieldingCopper braided shielding or braided shielding with foil shield. When grounding the
>0.34 mm2 (22 AWG)
cable shield, observe the grounding concept of the plant.
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a
cable used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to
the "Media Planning and Installation Manual. EtherNet/IP" of the ODVA Organization.
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Spring terminals:
Wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
22Endress+Hauser
Page 23
Proline Promag P 100Electrical connection
L
L
26
27
+
_
24
25
1
2
+
_
+
_
1
2
3
7.1.3 Terminal assignment
Transmitter
Connection version 4-20 mA HART with pulse/frequency/switch output
Order code for "Output", option B
Depending on the housing version, the transmitters can be ordered with terminals or device
plugs.
A0016888
6Terminal assignment 4-20 mA HART with pulse/frequency/switch output
1Power supply: DC 24 V
2Output 1: 4-20 mA HART (active)
3Output 2: pulse/frequency/switch output (passive)
Terminal number
Order code for
"Output"
Option BDC 24 V4-20 mA HART (active)Pulse/frequency/switch
Order code for "Output":
Option B: 4-20 mA HART with pulse/frequency/switch output
Endress+Hauser23
Power supplyOutput 1Output 2
2 (L-)1 (L+)27 (–)26 (+)25 (–)24 (+)
output (passive)
Page 24
Electrical connectionProline Promag P 100
L
L
26
27BA
1
2
+
_
1
2
PROFIBUS DP connection version
For use in the non-hazardous area and Zone 2/Div. 2.
Order code for "Output", option L
Depending on the housing version, the transmitters can be ordered with terminals or device
plugs.
A0022716
7PROFIBUS DP terminal assignment
1Power supply: DC 24 V
2PROFIBUS DP
Terminal number
Order code for
"Output"
Option LDC 24 VBA
Order code for "Output":
Option L: PROFIBUS DP, for use in non-hazardous areas and Zone 2/div. 2
24Endress+Hauser
Power supplyOutput
2 (L-)1 (L+)26 (RxD/TxD-P) 27 (RxD/TxD-N)
Page 25
Proline Promag P 100Electrical connection
L
L
26
27AB
1
2
+
_
1
2
Modbus RS485 connection version
Order code for "Output", option M
Depending on the housing version, the transmitters can be ordered with terminals or device
plugs.
A0019528
8Modbus RS485 terminal assignment
1Power supply: DC 24 V
2Modbus RS485
Terminal number
Order code for
"Output"
Option MDC 24 VModbus RS485
Order code for "Output":
Option M: Modbus RS485
Power supplyOutput
2 (L-)1 (L+)27 (B)26 (A)
Endress+Hauser25
Page 26
Electrical connectionProline Promag P 100
L
L
1
2
+
_
1
2
1
2
4
3
5
EtherNet/IP connection version
Order code for "Output", option N
Depending on the housing version, the transmitters can be ordered with terminals or device
plugs.
A0017054
9EtherNet/IP terminal assignment
1Power supply: DC 24 V
2EtherNet/IP
Terminal number
Order code for
"Output"
Option NDC 24 VEtherNet/IP
Order code for "Output":
Option N: EtherNet/IP
Power supplyOutput
2 (L-)1 (L+)Device plug M12x1
7.1.4 Pin assignment, device plug
Supply voltage
For all connection versions (device side)
PinAssignmentCodingPlug/socket
1L+DC 24 VAPlug
2
3
4L-DC 24 V
5Grounding/shielding
A0016809
26Endress+Hauser
Page 27
Proline Promag P 100Electrical connection
3
2
4
1
5
3
2
4
1
5
3
2
4
1
5
4-20 mA HART with pulse/frequency/switch output
Device plug for signal transmission (device side)
PinAssignmentCodingPlug/socket
1+4-20 mA HART (active)ASocket
2-4-20 mA HART (active)
3+ Pulse/frequency/switch output (passive)
4-Pulse/frequency/switch output (passive)
5Grounding/shielding
A0016810
PROFIBUS DP
For use in the non-hazardous area and Zone 2/Div. 2.
The shielding and grounding concept requires compliance with the following:
• Electromagnetic compatibility (EMC)
• Explosion protection
• Personal protection equipment
• National installation regulations and guidelines
• Observe cable specification → 21.
• Keep the stripped and twisted lengths of cable shield to the ground terminal as short as
possible.
• Seamless cable shielding.
Grounding of the cable shield
To comply with EMC requirements:
• Ensure the cable shield is grounded to the potential matching line at multiple points.
• Connect every local ground terminal to the potential matching line.
NOTICE
In systems without potential matching, the multiple grounding of the cable shield causes
mains frequency equalizing currents!
Damage to the bus cable shield.
Only ground the bus cable shield to either the local ground or the protective ground at one
‣
end.
7.1.6 Preparing the measuring device
1.Remove dummy plug if present.
2.
NOTICE
Insufficient sealing of the housing!
Operational reliability of the measuring device could be compromised.
Use suitable cable glands corresponding to the degree of protection.
‣
If measuring device is delivered without cable glands:
Provide suitable cable gland for corresponding connecting cable → 21.
3.If measuring device is delivered with cable glands:
Observe cable specification → 21.
28Endress+Hauser
Page 29
Proline Promag P 100Electrical connection
12
A
7.2 Connecting the measuring device
NOTICE
Limitation of electrical safety due to incorrect connection!
For use in potentially explosive atmospheres, observe the information in the device-specific
‣
Ex documentation.
7.2.1 Connecting the transmitter
The connection of the transmitter depends on the following order codes:
• Housing version: compact or ultra-compact
• Connection version: device plug or terminals
A0019824
10Device versions and connection versions
AHousing version: compact, aluminum coated
1Cable entry or device plug for signal transmission
2Cable entry or device plug for supply voltage
Endress+Hauser29
Page 30
Electrical connectionProline Promag P 100
10 (0.4)
mm (in)
12
3
3 mm
A0019823
11Device versions with connection examples
1Cable
2Device plug for signal transmission
3Device plug for supply voltage
Depending on the housing version disconnect the local display from the main electronics
module: Operating Instructions for the device .
Connect the cable in accordance with the terminal assignment or the device plug pin
‣
assignment .
30Endress+Hauser
Page 31
Proline Promag P 100Electrical connection
DN 300≤DN 350≥
7.2.2 Ensuring potential equalization
CAUTION
L
Electrode damage can result in the complete failure of the device!
Make sure that the fluid and sensor have the same electrical potential.
‣
Pay attention to internal grounding concepts in the company.
‣
Pay attention to the pipe material or grounding.
‣
Connection examples for standard situations
Metal, grounded pipe
A0016315
12Potential equalization via measuring tube
Connection example in special situations
Unlined and ungrounded metal pipe
This connection method also applies in situations where:
• The customary potential equalization is not used
• Equalizing currents are present
Ground cable
13Potential equalization via ground terminal and pipe flanges
Endress+Hauser31
Copper wire, at least6 mm2 (0.0093 in2)
A0016317
Page 32
Electrical connectionProline Promag P 100
+
–
Plastic pipe or pipe with insulating liner
This connection method also applies in situations where:
• The customary potential equalization is not used
• Equalizing currents are present
Ground cable
Copper wire, at least6 mm2 (0.0093 in2)
14Potential equalization via ground terminal and ground disks
Pipe with a cathodic protection unit
This connection method is only used if the following two conditions are met:
• Metal pipe without liner or pipe with electrically conductive liner
• Cathodic protection is integrated in the personal protection equipment
Ground cable
Copper wire, at least6 mm2 (0.0093 in2)
A0016318
A0016319
Prerequisite: The sensor is installed in the pipe in a way that provides electrical insulation.
1.Connect the two flanges of the pipe to one another via a ground cable.
2.Guide the shield of the signal lines through a capacitor.
3.Connect the measuring device to the power supply such that it is floating in relation to
the protective ground (isolation transformer).
32Endress+Hauser
Page 33
Proline Promag P 100Electrical connection
OFF ON
1
2
3
4
5
6
7
8
9
10
1
2
4
8
16
32
64
128
- Write protection
- Default Ethernet
network settings
IP 192.168.1.212
IP Address setting
(last octet)
7.3 Hardware settings
7.3.1 Setting the device address
EtherNet/IP
The IP address of the measuring device can be configured for the network via DIP switches.
Addressing data
IP address and configuration options
1st octet2nd octet3rd octet4th octet
192.168.1.XXX
↓↓
Can only be configured via software addressingCan be configured via
IP address range1 to 254 (4th octet)
IP address broadcast255
Addressing mode ex worksSoftware addressing; all DIP switches for hardware addressing are set to OFF.
IP address ex worksDHCP server active
software addressing
and hardware
addressing
For device addressing via software → 43
Setting the address
Endress+Hauser33
A0017913
Page 34
Electrical connectionProline Promag P 100
OFF ON
1
2
3
4
5
6
7
8
9
10
1
2
4
8
16
32
64
- Write protection
- Not used
PROFIBUS
address
- Software addressing
Set the desired IP address using the corresponding DIP switches on the I/O electronics
‣
module.
Hardware addressing with the configured IP address is enabled after 10 s.
PROFIBUS DP
The address must always be configured for a PROFIBUS DP/PA device. The valid address
range is between 1 and 126. In a PROFIBUS DP/PA network, each address can only be
assigned once. If an address is not configured correctly, the device is not recognized by the
master. All measuring devices are delivered from the factory with the device address 126 and
with the software addressing method.
Setting the address
A0021265
15Addressing using DIP switches on the I/O electronics module
1.Disable software addressing via DIP switch 8 (OFF).
2.Set the desired device address via the corresponding DIP switches.
Example → 15, 34: 1 + 16 + 32 = device address 49
The device demands rebooting after 10 s. After rebooting, hardware addressing is
enabled with the configured IP address.
7.3.2 Enabling the terminating resistor
PROFIBUS DP
To avoid incorrect communication transmission caused by impedance mismatch, terminate
the PROFIBUS DP cable correctly at the start and end of the bus segment.
34Endress+Hauser
Page 35
Proline Promag P 100Electrical connection
390 Ω
DIP 1
5V
26
27
220 Ω
DIP 2
0V
390 Ω
DIP 3
OFF ON
1
2
3
4
Bus polarisation
Bus termination
Bus polarisation
Not used
4.
1.
2.
3.
• If the device is operated with a baud rate of 1.5 MBaud and under:
For the last transmitter on the bus, terminate via DIP switch 2 (bus termination) and DIP
switch 1 and 3 (bus polarization). Setting: ON – ON – ON → 16, 35.
• For baud rates > 1.5 MBaud:
Due to the capacitance load of the user and the line reflections generated as a result, ensure
that an external bus terminator is used.
It is generally advisable to use an external bus terminator as the entire segment can fail
if a device that is terminated internally is defective.
A0021274
16Termination using DIP switches on the I/O electronics module (for baud rates < 1.5 MBaud)
Modbus RS485
To avoid incorrect communication transmission caused by impedance mismatch, terminate
the Modbus RS485 cable correctly at the start and end of the bus segment.
Endress+Hauser35
Page 36
Electrical connectionProline Promag P 100
2 - Not used
1 - Write protection
4 - Bus termination
3 - Not used
OFFON
26
27AB
220 W
If the transmitter is used in the non-hazardous area or Zone 2/Div. 2
A0017610
17Terminating resistor can be enabled via DIP switch on the main electronics module
7.4 Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type
4X enclosure.
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps
after the electrical connection:
1.Check that the housing seals are clean and fitted correctly. Dry, clean or replace the
seals if necessary.
2.Tighten all housing screws and screw covers.
3.Firmly tighten the cable glands.
4.To ensure that moisture does not enter the cable entry, route the cable so that it loops
down before the cable entry ("water trap").
A0013960
5.Insert dummy plugs into unused cable entries.
36Endress+Hauser
Page 37
Proline Promag P 100Electrical connection
7.5 Post-connection check
Are cables or the device undamaged (visual inspection)?
Do the cables comply with the requirements → 21?
Do the cables have adequate strain relief?
Are all the cable glands installed, firmly tightened and leak-tight? Cable run with "water trap" → 36 ?
Depending on the device version: are all the device plugs firmly tightened → 29?
• Does the supply voltage match the specifications on the transmitter nameplate ?
• For device version with Modbus RS485 intrinsically safe: does the supply voltage match the
specifications on the nameplate of the Safety Barrier Promass 100 ?
Is the terminal assignment or the pin assignment of the device plug correct?
• If supply voltage is present, is the power LED on the electronics module of the transmitter lit green
→ 9?
• For device version with Modbus RS485 intrinsically safe, if supply voltage is present, is the power LED
on the Safety Barrier Promass 100 lit → 9?
Is the potential equalization established correctly → 31?
Depending on the device version, is the securing clamp or fixing screw firmly tightened?
Endress+Hauser37
Page 38
Operation optionsProline Promag P 100
!
Expert
Operating menu for experts
Language
Operation
Setup
Diagnostics
Operating menu for operators and maintenances
Operator
Maintenance
task-oriented
function-oriented
Expert
8 Operation options
8.1 Structure and function of the operating menu
8.1.1 Structure of the operating menu
18Schematic structure of the operating menu
8.1.2 Operating philosophy
The individual parts of the operating menu are assigned to certain user roles. Each user role
corresponds to typical tasks within the device lifecycle.
For detailed information about the operating philosophy of the device, see the Operating
A0014058-EN
Instructions for the device (Verweisziel existiert nicht, aber @y.link.required='true').
8.2 Access to the operating menu via the Web browser
This type of access is available with the following device version:
Order code for "Output", option N: EtherNet/IP
38Endress+Hauser
Page 39
Proline Promag P 100Operation options
OFF ON
1
2
3
4
5
6
7
8
9
10
1
2
4
8
16
32
64
128
- Write protection
- Default Ethernet
network settings
IP 192.168.1.212
IP Address setting
(last octet)
8.2.1 Function range
Thanks to the integrated Web server the device can be operated and configured via a Web
browser.
8.2.2 Prerequisites
Hardware
Connecting cableStandard Ethernet cable with RJ45 connector
ComputerRJ45 interface
Measuring device:Web server must be enabled; factory setting: ON
IP addressIf the IP address of the device is not known, communication with the Web server
can be established via the standard IP address 192.168.1.212.
The DHCP function is enabled in the device at the factory, i.e. the device expects
an IP address to be assigned by the network. This function can be disabled and
the device can be set to the standard IP address 192.168.1.212: set switch DIP
switch No. 10 from OFF → ON.
• Once the DIP switch has been activated, the device must be restarted
before the device uses the standard IP address.
• If the standard IP address (DIP switch No. 10 = ON) is used, there is no
connection to the EtherNet/IP network.
Software of the computer
Web browsers supported• Microsoft Internet Explorer (min. 8.x)
Recommended operating systems• Windows XP
Endress+Hauser39
• Mozilla Firefox
• Google chrome
• Windows 7
A0017965
Page 40
Operation optionsProline Promag P 100
User rights for TCP/IP settingsUser rights required for TCP/IP settings (e.g. for changes to IP address, subnet
Computer configuration• JavaScript is enabled
mask)
• If JavaScript cannot be enabled, enter http://XXX.XXX.X.XXX/basic.html in the
address line of the Web browser, e.g. http://192.168.1.212/basic.html. A
fully functional but simplified version of the operating menu structure starts
in the Web browser.
8.2.3 Establishing a connection
Configuring the Internet protocol of the computer
The following information refers to the default Ethernet settings of the device.
IP address of the device: 192.168.1.212 (factory setting)
IP address192.168.1.XXX; for XXX all numerical values except: 0, 212 and 255 → e.g.
Subnet mask255.255.255.0
Default gateway192.168.1.212 or leave cells empty
192.168.1.213
1.Switch on the measuring device and connect to the computer via the cable .
2.If a 2nd network card is not used: all the applications on the notebook should be closed,
or all the applications that require the Internet or network, such as e-mail, SAP
applications, Internet or Windows Explorer, i.e. close all open Internet browsers.
3.Configure the properties of the Internet protocol (TCP/IP) as defined in the table above.
Starting the Web browser
1.Enter the IP address of the Web server in the address line of the Web browser:
192.168.1.212
2.If the IP address of the measuring device is known, enter the defined device address in
the address line of the Web browser. If it is unknown, set DIP switch No. 10 to ON,
restart the device and enter the standard IP address: 192.168.1.212 → 39.
The login page appears.
40Endress+Hauser
Page 41
Proline Promag P 100Operation options
Device tag
Webserv.language
English
Ent. access code
Access stat.toolMaintenance
12
OK
24
6
5
1324
6
5
1324
6
5
1324
6
5
1324
6
5
13
A0017362
1Device tag → 44
2Picture of device
8.2.4 Logging on
Access code0000 (factory setting); can be changed by customer → 44
8.2.5 User interface
1
Picture of device
2
Function row with 6 functions
3
Device tag
4
Header
5
Working area
6
Navigation area
Endress+Hauser41
A0017757-EN
Page 42
System integrationProline Promag P 100
Header
The following information appears in the header:
• Device tag → 44
• Device status with status signal
• Current measured values
Function row
FunctionsMeaning
Measured valuesThe measured values of the device are displayed
MenuAccess to the operating menu structure of the device, same as for the operating tool
Device statusDisplays the diagnostic messages currently pending, listed in order of priority
• Data exchange between PC and measuring device:
– Upload the configuration from the device (XML format, create configuration back-up)
– Save the configuration to the device (XML format, restore configuration)
Data management
Network
configuration
LogoutEnd the operation and call up the login page
– Export the event list (.csv file)
– Export parameter settings (.csv file, create documentation of the measuring point
configuration)
– Export the Heartbeat verification log (PDF file, only available with the "Heartbeat
Verification" application package)
• Upload the device driver for system integration from the device
Configuration and checking of all the parameters required for establishing the connection to the
device:
• Network settings (e.g. IP address, MAC address)
• Device information (e.g. serial number, firmware version)
8.3 Access to the operating menu via the operating tool
For detailed information about access to the operating menu via operating tool, refer to
the Operating Instructions for the device (Verweisziel existiert nicht, aber
@y.link.required='true').
9 System integration
For information on system integration, see the Operating Instructions for the device
(Verweisziel existiert nicht, aber @y.link.required='true').
Applies only to device version with EtherNet/IP communication type
A detailed description of how to integrate the device into an automation system (e.g.
from Rockwell Automation) is available as a separate document: www.endress.com →
Select country → Automation → Digital Communication → Feldbus device
integration → EtherNet/IP
42Endress+Hauser
Page 43
Proline Promag P 100Commissioning
10 Commissioning
10.1 Function check
Before commissioning the device, make sure that the post-installation and post-connection
checks have been performed.
• "Post-installation check" checklist → 20
• "Post-connection check" checklist → 37
10.2 Establishing a connection via FieldCare
• For FieldCare connection → 42
• For establishing a connection via FieldCare
10.3 Configuring the device address via software
In the "Communication" submenu the device address can be set.
Navigation
"Setup" menu → Communication → Device address
10.3.1 Ethernet network and Web server
When delivered, the measuring device has the following factory settings:
IP address192.168.1.212
Subnet mask255.255.255.0
Default gateway192.168.1.212
• If hardware addressing is active, software addressing is disabled.
• If a switch is made to hardware addressing, the address configured via software
addressing is retained for the first 9 places (the first three octets).
If the IP address of the device is not known, the device address currently configured can
be read out: Operating Instructions for the device
10.3.2 PROFIBUS network
At time of delivery, the measuring device has the following factory setting:
Device address126
If hardware addressing is active, software addressing is blocked → 33
Endress+Hauser43
Page 44
CommissioningProline Promag P 100
10.4 Configuring the measuring device
The Setup menu with its submenus is used for fast commissioning of the measuring device.
The submenus contain all the parameters required for configuration, such as parameters for
measurement or communication.
SubmenuMeaning
System unitsConfiguring the units for all measured values
Medium selectionDefining the medium
CommunicationConfiguration of the digital communication interface
Low flow cut offConfiguring the low flow cut off
10.5 Defining the tag name
To enable fast identification of the measuring point within the system, you can enter a unique
designation using the Device tag parameter and thus change the factory setting.
Navigation
"Setup" menu → Device tag
Parameter overview with brief description
ParameterDescriptionUser entryFactory setting
Device tagEnter the name for the
measuring point.
Max. 32 characters, such as
letters, numbers or special
characters (e.g. @, %, /).
Promag
10.6 Protecting settings from unauthorized access
The following options exist for protecting the configuration of the measuring device from
unintentional modification after commissioning:
• Write protection via access code for Web browser → 44
• Write protection via write protection switch → 45
10.6.1 Write protection via access code
With the customer-specific access code, access to the measuring device via the Web browser is
protected, as are the parameters for the measuring device configuration.
2.Define a max. 4-digit numeric code as an access code.
3.Enter the access code again to confirm the code.
The Web browser switches to the login page.
If no action is performed for 10 minutes, the Web browser automatically returns to the
login page.
The user role with which the user is currently logged on via the Web browser is indicated
by the Access status tooling parameter. Navigation path: Operation → Access status
tooling
10.6.2 Write protection via write protection switch
The write protection switch makes it possible to block write access to the entire operating
menu with the exception of the following parameters:
• External pressure
• External temperature
• Reference density
• All parameters for configuring the totalizer
The parameter values are now read only and cannot be edited any more:
• Via service interface (CDI)
• Via HART protocol
• Via Modbus RS485
• Via service interface (CDI-RJ45)
• Via Ethernet network
• Via PROFIBUS DP
For device version with HART communication type
A0022571
For device version with Modbus RS485 communication type
Endress+Hauser45
Page 46
CommissioningProline Promag P 100
OFFON
1 - Write protection
2 - Not used
3 - Not used
4 - Bus termination
OFF ON
1
2
3
4
5
6
7
8
9
10
1
2
4
8
16
32
64
128
- Write protection
- Default Ethernet
network settings
IP 192.168.1.212
IP Address setting
(last octet)
A0017954
For device version with EtherNet/IP communication type
A0017915
For device version with PROFIBUS DP communication type
46Endress+Hauser
Page 47
Proline Promag P 100Diagnostic information
OFF ON
1
2
3
4
5
6
7
8
9
10
1
2
4
8
16
32
64
- Write protection
- Not used
PROFIBUS
address
- Software addressing
A0021262
Setting the write protection switch on the electronics module to the ON position enables
‣
the hardware write protection.
If hardware write protection is enabled, the Hardware locked option is displayed in
the Locking status parameter.
11 Diagnostic information
Any faults detected by the measuring device are displayed on the home page of the operating
tool once the connection has been established and on the home page of the web browser once
the user has logged on.
Remedial measures are provided for each diagnostic event to ensure that problems can be
rectified quickly.
• Web browser: Remedial measures are displayed in red on the home page next to the
diagnostic event.
• FieldCare: Remedial measures are displayed on the home page in a separate field below the
diagnostic event.
Endress+Hauser47
Page 48
www.addresses.endress.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.