Emerson LT410, LT300 User Manual

LIQUI-TECT® 410
Point Leak Detection Sensor

Description

The Liqui-tect 410 (LT410) provides a single-point detection of leaks. The point detection sensor has two gold-plated sensing probes to prevent corrosion resistance and to provide accurate readings. The LT410 constantly monitors points for leaks, internal faults and power failures and warns of any abnormal conditions. Mounting brackets allow for sensor height adjustment and leveling.
The LT410 is the ideal solution for sensing leaks under a raised computer floor or air conditioning drip pans. Two independent outputs provide added flexibility with the capacity to signal both a local alarm panel and a remote building management system or external equipment, such as motorized water shut-off valves.
The LT410 is also ideally suited for the following:

Applications Locations

• Glycol, Chilled Water Cooling
• Humidification Feed Water Piping
• Condensate Pumps and Drains
• Unit and Ceiling Auxiliary Drip Pans
• Overhead Piping Troughs

Placement on Subfloor

Under Cooling Support Equipment

• Large-Scale Network Control Centers
• Data Centers
• Server Rooms - Closets
• Unattended Remote Shelters
• Mechanical Equipment Rooms
• Sensitive Areas With Overhead Piping
• Industrial Process Control Rooms

Specifications

Liqui-tect 410 Sensor
Power requirements 24 VAC 100 mA, 50/60 Hz, 3 VA (max.) Dimensions
W x D x H Weight (assembled) 2.0 lbs (0.9 kg) Metal enclosure NEMA 1, IP 30
Environmental Conditions
Operating temperature 50°F to 104°F (10°C to 40°C)
Operating humidity
Operating altitude 0 to 10,000 ft (0 to 3,048 m)
Output Relays
Contact rating 2 Form-C; 3 A rating at 24 VAC
Agency Listings
UL UL916 C-UL C22.2, No. 205-M1983 CE Yes FCC Compliance 47 CFR, Part 15
6.35" x 2.25" x 4.46" (161.2 mm x 57.2 mm x 113.2 mm)
10% to 95% relative humidity (non-condensing)
Dimensions-Top, Front & Side Views
4.46"
(113.2mm)
TOP VIEW
5.85"
(148.5mm)
FRONT VIEW
6.35"
(161.2mm)
Form-C relay outputs & power wiring connection
Adjustable probe height
0.0–0.5" (0.0–12.7mm)
Shipping weight: 2 Ibs (0.9 kg) Mounting holes: #8 screws
SIDE VIEW
2.25"
(57.2mm)

Wiring Interconnections

Red Wires Orange Wires Yellow Wires
24 V, AC/DC
@0.10A, 50-60 Hz, DC
Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
Power
Power
1-NO
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
1-NC
1-COM
2-NO
2-NC
2-COM
To a Liebert
environmental
unit and
an optional*
monitoring
panel
To e x tern al power supply or directly from unit
LT4 10
* Output connections to external alarm monitoring panels
such as the Liebert contact closure alarm panels
Leak detection zone (directly beneath unit)

Ordering Information

Product Number
LT410 Point Leak Detection Sensor
Gold-plated probes
Quantity Description
Height adjustable 0-0.5" (0-12.7mm)
Product Specification Sheet page 1 11/02 (Rev. 0)

Power Wiring

4
t
t
24V from Transformer to LT460

Wiring to Auxiliary Alarm Panels

The LT410 is rated for 24 VAC, 50/60 Hz and
0.10 amp.
Figure 1 24V from Liebert environmental units to LT410
Liebert Deluxe Sys/3,
Liebert Deluxe System/3,
Challenger, Himod or
Challenger, Himod or
MM2 (8 Ton)
Mini-Mate2 (8 ton) LT410
TB1
T5
(24V)
T5 (24V)
G5
(Ground)
G5 (Ground)
Liebert MM2 (1 to 5 Ton) LT460
V transformer of
ere are no ted terminal ions)
V transformer of
ere are no ted terminal ions)
Power Wiring
(24V)
(Ground)
24V from Liebert Environmental Unit to LT460
Liebert Deluxe Sys/3,
24V from Transformer to LT460
Challenger, Himod or MM2 (8 Ton)
Transformer
TB1
T5
(24V) From 24V transformer
G5
(Ground)
Liebert Mini-Mate2
Liebert MM2 (1 to 5 Ton) LT460
(1 to 5 ton)
(24V)
From 24V
(Ground)
transformer*
* Requires a 24V external transformer (there are
no designated terminal connections on the unit)
24V from Transformer to LT460
LT460
Red wiresTB1
TB1
TB1
LT460
LT460
TB1
TB1
LT410
Red wires
TB1
TB1-1
Red
TB1-2
Red
TB1-1
TB1-2
Location of T5 (24V) connection on main controller board of Liebert unit
TB1-1
TB1-1
TB1-2
TB1-2
TB1-1
Red
TB1-2
Red
The LT410 has two Form-C dry contact alarm out­put contacts: orange wires (1) and yellow wires (2). Each contact is rated for 24 VAC at 3 amp.
Figure 3 LT410 to Liebert environmental units
LT460 to Liebert Environme ntal Unit
LT460
LT410
Orange wires
TB2
TB2-3
(N.C.)
1-NC
TB2-2
(C)
1-COM
TB2-1
(N.O.)
1-NO
LT460
LT410
Orange wires
TB2
TB2-3
(N.C.)
1-NC
TB2-2
(C)
1-COM
TB2-1
(N.O.)
1-NO
Liebert Deluxe System/3,
Liebert Deluxe Sys/3, Challenger, Himod or
Challenger, Himod or
MM2 (8 Ton)
Mini-Mate2 (8 ton)
Environmental
Env. Unit
unit
24
(24V)
24 (24V)
51
51, 55 or 56
Liebert Mini-Mate2
Liebert MM2 (1 to 5 Ton)
(1 to 5 ton)
Environmental
Env. Unit
unit
TB1-1
(24V)
TB1-1 (24V)
TB1-2
TB1-2 or TB1-3
OR
Figure 4 LT410 to Liebert contact monitor panel
Liebert Contact Monitor Panel
panel
Alarm panel
Alarm P anel
Input
Input
Contact
contact
(N.O.)
(N.O.)
TB2-3
2-NC
TB2-2
2-COM
TB2-1
2-NO
LT460
LT4 10
Yellow wires
TB2
(N.C.)
(C)
(N.O.)
Liebert contact monitor
LT460
Figure 2 24V from transformer to LT410
Transformer LT410
Transformer
From 24V
From 24V
transformer
transformer
LT460
Red wires
TB1
Red
TB1-1
TB1-2
Red
Product Specification Sheet page 2 11/02 (Rev. 0)
Loading...