Emerson LR125 Instruction Manual

Instruction Manual
November 2014
Type LR125
Type LR125 Pressure Reducing Liquid Regulator
TYPE LR125 REGULATOR
Figure 1. Type LR125 Pressure Reducing Liquid Regulator and Type MR95H Pilot
WARNING
Failure to follow these instructions or to properly install and maintain this equipment could result in bursting of the equipment and/or chemical contamination causing property damage and personal injury or death.
Fisher® regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. (Emerson™) instructions.
If the regulator discharges process
 uid or a leak develops in the system, service to the unit may be required.
TYPE MR95H PILOT
Failure to correct trouble could result in a hazardous condition.
Call a quali ed service person to service
the unit. Installation, operation and maintenance procedures performed
by unquali ed personnel may result
in improper adjustment and unsafe operation. Either condition may result in equipment damage or personal injury.
Only a quali ed person must install or service the regulator.
The Type LR125 is designed for liquid
service. Do not operate the regulator
in applications where temperatures are
below the process  uid’s freezing point or above its boiling point which are dependent on the process  uid and the
application pressures.
www.fisherregulators.com
D103576X012
Type LR125
Specications
Specications for the Type LR125 regulator are shown below. Other information for the main valve appears on the
nameplate. The control spring range for the pilot is marked on the nameplate of Type MR95H pilot.
Main Valve Body Sizes, End Connection Styles and Structural Design Ratings
(1)
See Table 1
Maximum Inlet Pressures
Type LR125 Main Valve: See Table 1
(1)
Type MR95H Pilot: See Table 2 Type 112 Restrictor: 1500 psig / 103 bar
Outlet (Control) Pressure Ranges
See Table 3
Type LR125 Main Valve (continued)
Cage: Stainless steel
Spring: Stainless steel
Top Plug: Stainless steel
Bottom Plug: Stainless steel Internal Inlet Strainer: Stainless steel Diaphragm: Nitrile (NBR) or Fluorocarbon (FKM) O-rings: Nitrile (NBR) or Fluorocarbon (FKM) Flanged Locknut: Stainless steel Backup Rings: Polytetrauoroethylene (PTFE) Upper Spring Seat: Stainless steel
Main Valve Plug Travel 1 in. / DN 25: 0.37 in. / 9.4 mm 2 in. / DN 50: 0.68 in. / 17 mm 3 in. / DN 80: 0.98 in. / 25 mm 4 in. / DN 100: 1.19 in. / 30 mm
Main Valve Minimum Differential Pressures
(1)
See Table 5
Main Valve Internal Inlet Strainer Sizes 1 in. / DN 25: 12 Mesh (0.0661 in. / 1.68 mm)
(2)
2, 3 and 4 in. / DN 50, 80 and 100: 10 Mesh (0.0787 in. / 2 mm)
Temperature Capabilities
(2)
(1)
See Table 4
Pressure Registration
External: 1/2 NPT
Spring Case Vent
Type Y602-12
Construction Materials
Type LR125 Main Valve Body: WCC Steel, CF8M or CF3M Stainless steel Bonnet: LF2 Steel or 316/316L Stainless steel
Indicator Protector and Cover: Plastic Indicator Stem: Stainless steel Indicator Fitting: Stainless steel Travel Indicator Plug: Stainless steel
Type MR95H Pilot
Body: WCC Steel or CF8M Stainless steel Spring Case: WCC Steel or CF8M Stainless steel
Orice: Stainless steel
Diaphragm: Neoprene (CR) or Fluorocarbon (FKM)
Disk: Nitrile (NBR) or Fluorocarbon (FKM)
Mounting Parts
Pilot Mounting Pipe Nipple: Plated steel or Stainless steel Pipe Fittings: Plated steel or Stainless steel Tubing: Stainless steel
Type 112 Restrictor
Body: 15-5 Stainless steel Groove Valve: Stainless steel Retainer: Stainless steel Pipe Plug: Stainless steel
O-rings: Nitrile (NBR) or Fluorocarbon (FKM)
Options
• Pre-piped Pilot Supply
• Travel Indicator
Bonnet Bushing: Stainless steel
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Nominal sieve opening
Introduction
Scope of the Manual
This instruction manual provides installation, startup, adjustment, maintenance and parts ordering information for Type LR125 pressure reducing regulator, 1/2 NPT Type MR95H pilot and Type 112 restrictor.
2
Product Description
The Type LR125 pilot-operated, pressure reducing regulator is used for liquid applications and include a Type 112 restrictor and a 1/2 NPT Type MR95H pilot.
Pilot Type Description
Type MR95H — Pressure reducing pilot for 15 to 150 psig / 1.0 to 10.3 bar outlet pressures. Designed to handle inlet pressures up to 300 psig / 20.7 bar.
Type LR125
Table 1. Type LR125 Main Valve Body Sizes, End Connection Styles, Structural Design Ratings
and Maximum Operating Inlet Pressures
MAIN VALVE BODY SIZES
In. DN psig bar psig bar
1, 2, 3 and 4 25, 50, 80 and 100
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Ratings and end connections for other than ASME standard can usually be provided. Contact your local Sales Ofce for assistance.
3. Maximum cold working pressure (CWP) per ASME B16.34 or product bulletin limit, whichever is lowest. Temperature may decrease these maximum pressures.
4. Not available for 4 in. / DN 100 body size.
Principle of Operation
MAIN VALVE BODY
MATERIAL
WCC Steel
CF8M Stainless
Steel
END CONNECTION STYLES
NPT or SWE
(1 and 2 in. only)
CL150 RF 290 20.0 290 20.0
CL300 RF 750 51.7
PN 16/25/40 RF
(1 and 2 in. only)
CL150 RF 275 19.0 275 19.0
CL300 RF 720 49.6
PN 16/25/40 RF
(4)
NPT
(4)
Type LR125 Installation
(1)
STRUCTURAL DESIGN
(2)
1500 103 300 20.7
580 40.0
1440 99.2 300 20.7
580 40.0
RATING
(3)
MAXIMUM OPERATING
INLET PRESSURE
300 20.7CL600 RF 1500 103
300 20.7CL600 RF 1440 99.2
(3)
As long as the outlet (control) pressure is above the outlet pressure setting, the pilot valve plug or disk remains closed (Figure 2). Force from the main spring, in addition to inlet pressure bleeding through
the restrictor, provide downward loading pressure to
keep the main valve diaphragm and plug assembly tightly shutoff.
When the outlet pressure decreases below the pilot
outlet pressure setting, the pilot plug or disk assembly
opens. Loading pressure bleeds downstream through
the pilot faster than it can be replaced through the supply line. This reduces loading pressure on top of the main valve diaphragm and plug assembly and
lets the unbalanced force between inlet and loading
pressure overcome the main spring force to open the Type LR125 diaphragm and plug assembly.
As the outlet pressure rises toward the outlet pressure
setting, it compresses the pilot diaphragm against the pilot control spring and lets the pilot valve plug or disk close. Loading pressure begins building on the Type LR125 diaphragm and plug assembly. The
loading pressure, along with force from the main
spring, pushes the diaphragm and plug assembly onto the tapered-edge seat, producing tight shutoff.
WARNING
Personal injury, equipment damage or
leakage due to escaping process uid
or bursting of pressure-containing parts may result if this regulator is
overpressured or is installed where service conditions could exceed the limits given in Specications
section or where conditions exceed any ratings of the adjacent piping or piping connections.
To avoid such injury or damage, provide pressure-relieving or pressure-limiting devices (as required by the appropriate code, regulation or standard) to prevent service conditions from exceeding limits.
Additionally, physical damage to the
regulator could break the pilot off the main valve, causing personal injury
and property damage due to escaping
process uid. To avoid such injury
and damage, install the regulator in a safe location.
3
Type LR125
TYPE 112 RESTRICTOR
CONTROL SPRING
TYPE MR95H PILOT
DIAPHRAGM
SUPPLY
LINE
VALVE PLUG
MAIN SPRING
DIAPHRAGM AND PLUG ASSEMBLY
INTERNAL STRAINER
M1215
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE
4
Figure 2. Type LR125 Operational Schematic
Type LR125
BLOCK VALVE
INLET
SUPPLY PRESSURE LINE
B2605_A
TYPE MR95H PILOT INSTALLATION WITH PILOT EXHAUST INTO CONTROL LINE
WARNING
RESTRICTOR
Figure 3. Typical Type LR125 Installation Schematic
Liquid pressure control systems should be designed using engineering practices
to eliminate quick control starting or stopping of the  ow stream, which can
produce water hammer.
The robust design of the Type LR125 allows this
regulator to be installed indoors or outdoors. This
regulator is designed to withstand the elements. The powder paint coating protects against minor
impacts, abrasions and corrosion. When installed outdoors, the Type LR125 does not require protective
housing. However, the Type MR95H pilot should be
oriented so that the pilot spring case vent is pointed
down. Otherwise, make sure the vent is protected so that rain, moisture, insects or any debris will not
accumulate inside or block the vent assembly.
When installed indoors, no remote venting is required except on the pilot spring case. Refer to Step 5 of the
following procedure for the correct venting practices.
1. Only personnel quali ed through training and
experience should install, operate and maintain a regulator. Before installation, make sure that there is no damage to or debris in the regulator. Also, make sure that all tubing and piping are clean and unobstructed.
BLOCK VALVE
OUTLET
HAND VALVE
CONTROL LINE
TYPE MR95H PILOT
ALTERNATE CONTROL LINE
Note
The Type LR125 internal inlet strainer
is intended to prevent occasional
large particles from entering the main
valve. If the  owing media contains continuous particles, upstream  ltration
is recommended before the main
valve and in the pilot supply piping. See the Speci cations section for the
corresponding mesh size of the internal inlet strainer.
2. A Type LR125 regulator may be installed in any
orientation, as long as  ow through the regulator matches the direction of the arrow on the main valve body and the pilot vent is pointed down. However, for easier maintenance, install the regulator with the bonnet up.
CAUTION
Provide adequate support to the bonnet
when disassembling Type LR125 pressure reducing regulator installed in
a vertical installation or other application
where the bonnet is not oriented upward. Without adequate support, the bonnet may fall and cause physical injury when the cap screws are loosened.
3. The standard pilot mounting position is as shown in Figure 1. Other mounting positions are available.
5
Type LR125
Table 2. Type MR95H Pilot Maximum Operating Pressures
BODY SIZE
1/2 NPT
1. The pressure/temperature limits in this manual, and any applicable standard or code limitation should not be exceeded.
BODY AND SPRING
CASE MATERIAL
Steel
Stainless Steel
MAXIMUM INLET PRESSURE MAXIMUM OUTLET PRESSURE
300 psig / 20.7 bar 300 psig / 20.7 bar
(1)
Table 3. Outlet (Control) Pressure Ranges
PILOT
Type MR95H
OUTLET PRESSURE RANGE
SPRING WIRE
DIAMETER
psig bar In. mm In. mm
15 to 30 25 to 75
70 to 150
1.0 to 2.1
1.7 to 5.2
4.8 to 10.3
0.207
0.234
0.283
5.26
5.94
7.19
SPRING
FREE LENGTH
2.50
2.60
2.44
63.5
65.9
62.0
SPRING PART NUMBER
AND COLOR
1E395627022, Yellow
1D7455T0012, Green
1E395727192, Red
Table 4. Diaphragm Material Selection Information
CRITERIA
17E68 Nitrile (NBR) (Standard) 17E97 Nitrile (NBR) 17E88 Fluorocarbon (FKM)
Liquid Temperature -20 to 150°F / -29 to 66°C 0 to 150°F / -18 to 66°C 0 to 250°F / -18 to 121°C
Best for low pressure differential
General Applications
service or cold temperature
applications
Heavy Particle Erosion Fair Excellent Good
1. Fluorocarbon (FKM) is limited to 200°F / 93°C in hot water.
DIAPHRAGM MATERIAL
Best for abrasive or erosive service
applications
Best for high temperature applications
(1)
Table 5. Main Valve Minimum Differential Pressures
MAIN VALVE BODY SIZE DIAPHRAGM
In. DN Diaphragm Code Diaphragm Material psid bar d psid bar d
17E68 (Standard) Nitrile (NBR), Low Minimum Differential 30 2.1 30 2.1
1 25
2 50
3 80
4 100
1. See Table 1 for Type LR125 main valve structural design ratings and Table 2 for Type MR95H pilot rating.
17E97 Nitrile (NBR), High Erosion Resistance 35 2.5 35 2.5
17E88
17E68 (Standard) Nitrile (NBR), Low Minimum Differential 18 1.2 19 1.3
17E97 Nitrile (NBR), High Erosion Resistance 24 1.7 24 1.7
17E88
17E68 (Standard) Nitrile (NBR), Low Minimum Differential 21 1.5 28 1.9
17E97 Nitrile (NBR), High Erosion Resistance 23 1.6 23 1.6
17E88
17E68 (Standard) Nitrile (NBR), Low Minimum Differential 16 1.1 30 2.1
17E97 Nitrile (NBR), High Erosion Resistance 16 1.1 34 2.3
17E88
Fluorocarbon (FKM),
High Temperature Capability
Fluorocarbon (FKM),
High Temperature Capability
Fluorocarbon (FKM),
High Temperature Capability
Fluorocarbon (FKM),
High Temperature Capability
30 2.1 30 2.1
18 1.2 19 1.3
21 1.5 28 1.9
16 1.1 30 2.1
(1)
MINIMUM DIFFERENTIAL, PERCENT OF CAPACITY
For 90% Capacity For 100% Capacity
6
Type LR125
4. Apply a good grade of pipe compound to the
external pipeline threads for a threaded body,
or use suitable line gaskets for a anged body. Use approved piping procedures when installing
the regulator.
CAUTION
A regulator may leak toxic chemical to the environment. In toxic or hazardous liquid service, leaked chemical may
accumulate and cause personal injury, death or property damage due to
escaping uid.
To prevent such injury or damage, provide piping or tubing to vent the
hazardous liquid to a remote, safe
location away from air intakes or any
hazard-prone location. The exhaust piping must be designed and installed to
guard against excessive ow restriction. Protect the vent line or stack opening
against condensation or clogging.
5. If system operation during maintenance is required, install isolating and vent valves as needed.
6. A clogged pilot spring case vent may cause the regulator to function improperly. To prevent plugging (and to keep the spring case from collecting moisture, corrosive chemicals or other
foreign material) point the vent down, orient it to the lowest possible point on the spring case or otherwise protect it. Protect the vent assembly
from icing, moisture or debris that may cause blockage, as required. Inspect the vent regularly to make sure it has not been plugged. To remotely vent a spring case, remove the vent and install obstruction-free tubing or piping into the 1/4 NPT vent tapping. Provide protection on a remote vent by installing a screened vent cap onto the remote end of the vent pipe.
7. As shown in Figure 3, run a supply pressure line
from the upstream pipeline to the restrictor inlet (use 3/8 NPT outer diameter tubing or larger).
Install a lter or strainer upstream of the restrictor,
if needed, to keep the supply source from clogging
the restrictor or pilot. Inspect and clean this lter
regularly to make sure it has not been plugged
which can prevent proper regulator operation.
8. Install a downstream pressure control line with a minimum size of 1/2 in. / 13 mm (as shown
in Figure 3) to the pilot control line or outlet connection. Connect the other end of the control
line at a minimum of 8 to 10 pipe diameters
downstream of the regulator in a straight run of
pipe. Do not place a control line connection in a
turbulent area, such as in or directly downstream of a swage or elbow. Signicant restrictions in
the control line can prevent proper pressure registration. When using a hand valve, it should be
a full ow valve, such as a full port ball valve.
9. Good piping practices usually require swaging up to larger downstream piping to obtain reasonable downstream uid velocity.
Startup and Adjustment
Note
Tables 1 and 2 show the maximum inlet
pressures for specic constructions.
Use pressure gauges to monitor inlet pressure, outlet pressure and any intermediate pressure during startup.
Startup
1. Make sure all block and vent valves are closed.
2. Back out the pilot adjusting screw.
3. Set the restrictor to the “4” position.
4. SLOWLY OPEN the valves in the following order:
a. Pilot supply and control line valve(s), if used
b. Inlet block valve
c. Outlet block valve
5. Set the pilot to the desired outlet (control) pressure according to the pilot adjustment procedure.
Pilot Adjustment
The factory setting of the regulator can be varied
within the pressure range stamped on the nameplate.
To change the outlet pressure, loosen the jam nut
(key 17, Figure 15) and turn the adjusting screw (key 15) clockwise to increase outlet pressure or counterclockwise to decrease it. Monitor the outlet pressure with a test gauge during the adjustment.
Tighten the locknut to maintain the desired setting.
All regulator springs can be backed off to provide zero outlet. Recommended outlet pressure ranges available and color codes of the respective springs are shown in Table 3.
7
Type LR125
Regulator Performance 2 4 6 8
Accuracy
Hysteresis Stability Speed of Response (Demand Decrease) Speed of Response (Demand Increase)
Increased Performance Decreased Performance
Regulator Performance
2 4 6 8
Accuracy
Hysteresis
Stability
Speed of Response (Demand Decrease)
Speed of Response (Demand Increase)
Increased Performance Decreased Performance
Regulator Performance
2 4 6 8
Accuracy
Hysteresis
Stability
Speed of Response (Demand Decrease)
Speed of Response (Demand Increase)
Increased Performance Decreased Performance
112 Restrictor Adjustment Guide
112 Restrictor Adjustment Guide
112 Restrictor Adjustment Guide
PILOT SUPPLY CONNECTION: 1/4 NPT PIPE CONNECTS TO UPSTREAM PILOT SUPPLY TAP
LOADING CONNECTION: 1/4 NPT PIPE CONNECTS TO TYPE LR125 DIAPHRAGM LOADING PORT
OUTLET CONNECTION: 1/4 NPT PIPE CONNECTS TO PILOT INLET CONNECTION
11B5004-A
OPTIONAL LOADING CONNECTION: 1/4 NPT NORMALLY PLUGGED
Figure 4. Type 112 Restrictor
W4559_1
RESTRICTOR ADJUSTMENT
REGULATOR PERFORMANCE 2 4 6 8
Accuracy
Hysteresis
Stability
Speed of Response (Demand Decrease)
Speed of Response (Demand Increase)
TYPE 112 RESTRICTOR SETTING
Increased Performance
RESTRICTOR ADJUSTMENT GUIDE
Figure 5. Restrictor Adjustment
8
Decreased Performance
Loading...
+ 16 hidden pages