The Liebert Liqui-tect 460 (LT460) provides zone
detection of leaks, protecting equipment by constantly monitoring the area for leaking liquids. The
LT460 is the ideal solution for perimeter sensing or
serpentine coverage of areas requiring up to 100 feet
of cable.
Selectable modes of
operation provide flexible alarming options
and protection for the
cable. The LT460 constantly monitors a zone
for leaks, internal
faults and power failures and warns of any
abnormal conditions.
Top cover LEDs provide
status indication and also ensure the cable is properly installed and operational under raised floors.
Two independent outputs provide a signal to a local
alarm panel, Liebert environmental unit,remote
building management system or external equipment, such as motorized water shut-off valves.
Components
Liqui-tect 460 Module
The LT460 consists of a metal enclosure with a
hinged top door providing access to the internal circuit board for wiring termination and configuration
of DIP switches. The LT460 will monitor up to 100
feet of connected LT500Y leak detection cable.
LT500Y Leak Detection Cable
The cable material and construction allow the cable
to lie flat when used with hold-down clips. The
LT500Y is plenum-rated and UL-listed for safe
operation.
• If obtained separately,cables are available in
lengths of 15, 35 and 50 feet. These cables can be
connected incrementally to monitor from 15 feet
up to 100 feet. An end terminator and hold-down
clips (two clips required for each 6-8 ft. of cable)
must be ordered separately.
• If obtained in a kit,cables are available in
lengths of 20, 25, 30, 35 and 45 feet. Cables in kits
cannot be lengthened. Hold-down clips are
provided.
Refer to the matrix on page 2 (Prepackaged Sizes for Liebert Units) to select a
preconfigured kit sized to specific lengths for
Liebert environmental units.
The LT460 kit is ideally suited for the following:
Applications
• Glycol, Condenser Water and Chilled Water
Cooling Piping Leak
• Humidification Feed Water Piping
• Condensate Pumps and Drains
• Unit and Ceiling Auxiliary Drip Pans
• Overhead Piping Troughs
Locations
• Large-Scale Network Control Centers
• Data Centers
• MRI, CAT Scan Rooms
• Server Rooms - Closets
• Unattended Remote Shelters
• Sensitive Areas With Overhead Piping
• Mechanical Equipment Rooms
• Industrial Process Control Rooms
Configuration Switch Settings
A four-position DIP switch is used to select two
alarm (filter) delays and three mutually exclusive
alarm modes. The switches are located next to the
wiring termination blocks.
Switch SettingsOFFON
1. Leak Detect Filter10sec 2min
2. Alarm LatchNoYes
3. Alarm Retest DelayNo1hr
4. Not Used——
ALL CIRCUITS: CLASS 2
Contacts shown in POWERED, NON-ALARM state
Contacts
Rating:
24V,3A
Contacts
Rating:
24V,3A
24V
50/60Hz
0.12A
TB3-3
TB3-2
TB3-1
TB2-3
TB2-2
TB2-1
TB1-2
TB1-1
CONNECT ENCLOSURE TO EARTH GROUND
S1
N.C.
C
N.O.
N.C.
C
N.O.
2
1
1
Specifications
Liqui-tect 460 Module
Power requirements
Enclosure dimensions
W x D x H
24 VAC 120 mA, 50/60 Hz
3 VA (max.)
5.35" x 3.23" x 3.5"
(135.9mm x 82mm x 88.9mm)
Mounting hole dimensions See diagrams at right
Weight (assembled)2.0 lb. (0.9 kg)
Sensing cable
compatibility
Maximum length of
sensing cable
All Liebert LT500 sensing
cables
100ft (30.5m)
Metal enclosureNEMA 1, IP 30
Environmental Conditions
Operating temperature50°F to 104°F (10°C to 40°C)
Operating humidity
10% to 95% relative humidity
(non-condensing)
Operating altitude0 to 10,000 ft. (0 to 3,048m)
Output Relays
Contact rating2 Form-C, 3 A rating at 24 VAC
Agency Listings
ULUL916
C-ULC22.2, No. 205-M1983
CEYes
FCC Compliance47 CFR, Part 15
Placement on Subfloor
Under Cooling Support Equipment
To a Liebert
environmental
unit and an
optional*
monitoring
panel
To e x ter n al
power
supply or
directly
from
unit
LT460
* Output connections to external alarm monitoring panels
such as the Liebert contact closure alarm panels
Leak
detection
cable
Leak detection
zone (directly
beneath unit)
Dimensions - Top & Front Views
Leak
detection
cable
connector
TOP VIEW
4.75"
(121mm)
Form-C
relay outputs
& power
wiring
connection
Shipping weight: 2 Ibs (0.9 kg)
Mounting holes: #8 screws
FRONT VIEW
4.25"
(108mm)
3.25"
(83mm)
4.75"
(121mm)
2"
(51mm)
Prepackaged Sizes for Liebert Units
Leak Detection Kit Installation Suggestions
Scenarios
Upflow
Unit
Detection
around
Note:
indicates
placement
of LT460
module
Distance:Distance From Unit
In back
On sides
In front
Unit
(footprint- in.)
Challenger
(32.5 x 32.5)LT460-Z30LT460-Z20LT460-Z30LT460-Z25
Himod
(69 x 35)LT460-Z35LT460-Z20LT460-Z35LT460-Z25
entire unit
2' clearance
in front
2 ft
2 ft
2 ft
Deluxe System/3
(50 x 35)LT460-Z30LT460-Z20LT460-Z35LT460-Z25
(74 x 35)LT460-Z35LT460-Z20LT460-Z35LT460-Z25
(99 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30
(122 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30
DS
(73 x 35)LT460-Z35LT460-Z20LT460-Z45LT460-Z30
(86 x 35) LT460-Z35LT460-Z20LT460-Z45LT460-Z30
(98 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30
(109 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30
(132 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30
Upflow
Unit
Detection
on sides and
in front of unit
2' clearance
in front
(No cable)
2 ft
2 ft
PART NUMBER
Downflow
Unit
Detection
around
entire unit
6' clearance
in front
1 ft
1 ft
6 ft
Downflow
Unit
Detection
on sides and
in front of unit
6' clearance
in front
(No cable)
1 ft
6 ft
Ordering Information
PackagingQuantityProduct NumberDescription
LT460-Z20Zone Leak Detection Kit With Cable and Hold-Down Clips20-Foot Cable
Prepackaged
Kits
Available
Separately
LT460-Z25Zone Leak Detection Kit With Cable and Hold-Down Clips25-Foot Cable
LT460-Z30Zone Leak Detection Kit With Cable and Hold-Down Clips30-Foot Cable
LT460-Z35Zone Leak Detection Kit With Cable and Hold-Down Clips35-Foot Cable
LT460-Z45Zone Leak Detection Kit With Cable and Hold-Down Clips45-Foot Cable
LT460Zone Leak Detection Module
LT500-15YLeak Detection Cable15-Foot Cable
LT500-35YLeak Detection Cable35-Foot Cable
LT500-50YLeak Detection Cable50-Foot Cable
LT500-ETEnd Terminator for LT500Y Cable
HDCHold-Down Clips
2
Power Wiring
4
t
t
The LT460 is rated for 24 VAC, 50/60 Hz and 0.12 amp.
Figure 1 24V from Liebert environmental units to LT460
Challenger, Himod or
Liebert DS, Deluxe System/3,
MM2 (8 Ton)
LT460
Challenger, Himod or Mini-Mate2 (8 ton)LT460
TB1TB1
TB1
T5
T5 (24V)
(24V)
TB1
TB1-1
TB1-1
G5 (Ground)
G5
(Ground)
Liebert MM2 (1 to5 Ton)LT460
V transformer of
ere are noted terminalions)
V transformer of
ere are noted terminalions)
Power Wiring
(24V)
(Ground)
24V from Liebert Environmental Unit toLT460
Liebert Deluxe Sys/3,
24V from Transformerto LT460
Challenger, Himod orMM2 (8Ton)
Transformer
TB1
(24V)
T5
From 24Vtransformer
G5
(Ground)
Liebert MM2 (1 to 5 Ton)LT460
Liebert Mini-Mate2 (1 to 5 ton)LT460
(24V)
From 24V
transformer*
(Ground)
* Requires a 24V external transformer (there are
no designated terminal connections on the unit)
TB1
LT460
LT460
TB1
TB1
TB1
TB1
TB1-2
TB1-2
TB1-1
TB1-2
Location of
T5 (24V)
connection
on Liebert unit
TB1-1
TB1-1
TB1-2
TB1-2
TB1-1
TB1-1
TB1-2
TB1-2
Figure 2 24V from transformer to LT460
TransformerLT460
Transformer
From 24V
From 24V
transformer
transformer
LT460
TB1
TB1
TB1-1
TB1-1
TB1-2
TB1-2
3
Wiring to Auxiliary Alarm Panels
The LT460 has two Form-C dry contact alarm output contacts (TB2 & TB3). Each contact is rated for 24 VAC
at 3 amp.
® Liebert and the Liebert logo are registered trademarks of
Liebert Corporation. All names referred to are trademarks or
registered trademarks of their respective owners.
SL-31052_REV0_06-07
4