Emerson Liebert Xtreme Density User Manual

Precision Cooling For Business-Critical Continuity™
Liebert® Xtreme Density
System Design Manual
TABLE OF CONTENTS
1.0 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 European Union Fluorinated Greenhouse Gas Requirements . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Direct and Indirect System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Liebert XDO—Overhead Cooling Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Liebert XDV—Vertical, Above-Cabinet Cooling Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5 Liebert XDH—Horizontal Cooling Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 Liebert XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.7 Liebert XDA—Air Flow Enhancer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.8 Liebert XDP—Pumping Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.8.1 Liebert XDP Minimum Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.9 Liebert XDC—Refrigerant Chiller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.9.1 Liebert XDC Minimum Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.10 Liebert XD Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.10.1 Liebert XD Field Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.0 STARTING A NEW EQUIPMENT COOLING PROJECT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1 Determining Cooling Equipment Needs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Implementing a Hot-Aisle/Cold Aisle Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.0 DESIGNING A LIEBERT XD SOLUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Determine Cooling Requirements and Select Liebert XD System . . . . . . . . . . . . . . . . . . . . 13
3.2 Calculate the Heat Load to be Handled by Liebert XD System . . . . . . . . . . . . . . . . . . . . . . 13
3.3 Selecting Liebert XD Cooling Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Airflow Requirements for Liebert XD Solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.5 Configuring a Liebert XD System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.5.1 Number of Modules Supported by a Liebert XDP or Liebert XDC . . . . . . . . . . . . . . . . . . . . . 14
3.6 Liebert XDO Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.6.1 Determining Spacing of Liebert XDOs in an Aisle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.6.2 Determining Vertical Placement of Liebert XDOs Above the Cold Aisle . . . . . . . . . . . . . . . . 16
3.7 Liebert XDV Unit Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.8 Liebert XDCF Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.9 Liebert XDH Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.10 Liebert XDP/Liebert XDC Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.11 Examples of Expansion and Interlaced Connection of Liebert XD Cooling Modules. . . . . . 20
3.12 Liebert XD Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.13 Liebert XD Piping System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.14 Liebert XD Piping Slope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.15 Bypass Flow Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.16 Determining Refrigerant Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.16.1 Liebert XDP/Liebert XDC Pumped R-134a Circuit Volume . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.16.2 Calculating Refrigerant Charge—Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.17 Liebert XDC DX R-407c Circuit Volume—Air Cooled Units . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.18 Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.19 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
i
3.20 Display Panel and Remote Temperature/Humidity Sensor Locations . . . . . . . . . . . . . . . . . 29
4.0 LIEBERT XD COOLING MODULES—LIEBERT XDO, LIEBERT XDV, LIEBERT
XDH AND LIEBERT XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
4.1 Liebert XDO Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.1.1 Optional Features Liebert XDO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.2 Liebert XDV Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.2.1 Optional Features—Liebert XDV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.3 Liebert XDCF Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.4 Liebert XDCF Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.5 Liebert XDCF Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.6 Liebert XDCF Piping Connection Methods and Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.6.1 Header System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.7 Liebert XDH Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.7.1 Optional Features—Liebert XDH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.7.2 Piping Connections to Liebert XDP or Liebert XDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.8 Liebert XD Flex Pipe Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.9 Liebert XD Piping Dimensions and Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.9.1 Piping Installation Method prefabricated headers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.10 Liebert XDP Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.11 Liebert XDC Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.11.1 Liebert XDC Optional Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
FIGURES
Figure 1 Pressure enthalpy diagram - refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Direct system configuration—hydraulic system diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 3 Indirect system configuration—hydraulic system diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 4 Suspended Liebert XDO modules in hot aisle-cold aisle arrangement . . . . . . . . . . . . . . . . . . . . . . 3
Figure 5 Top-mounted Liebert XDV modules with fixed piping in hot aisle-cold aisle arrangement. . . . . . 4
Figure 6 Top-mounted Liebert XDV modules with flexible piping in hot aisle-cold aisle arrangement. . . . 4
Figure 7 Liebert XDH—horizontal cooling module in hot aisle-cold aisle arrangement . . . . . . . . . . . . . . . . 5
Figure 8 Liebert XDCF units on BladeFrame EX cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 9 Liebert XDA—air flow enhancer—on Liebert Foundation enclosure . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 10 Liebert XDP pumping unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 11 Liebert XD Chiller unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 12 Liebert XD connection port kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 13 Hot aisle-cold aisle arrangement with under-floor source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 14 Liebert XDO placement over cold aisle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 15 Liebert XDO spacing—horizontal and vertical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 16 Positioning Liebert XDV on top of cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 17 Liebert XDCF unit mounting locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 18 Liebert XDH placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 19 Liebert XDV units mounted on racks emitting 3kW of heat, top view . . . . . . . . . . . . . . . . . . . . . 20
Figure 20 Liebert XDV units mounted on racks emitting 5kW of heat, top view . . . . . . . . . . . . . . . . . . . . . 20
Figure 21 Liebert XDV units mounted on racks emitting 8kW of heat top view . . . . . . . . . . . . . . . . . . . . . . 21
Figure 22 Liebert XDV units mounted on racks emitting 16kW of heat top view . . . . . . . . . . . . . . . . . . . . . 21
Figure 23 Piping for Liebert XDP/Liebert XDC used with Liebert XD cooling units . . . . . . . . . . . . . . . . . . 23
ii
Figure 24 Hydraulic diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 25 Bypass flow controller details, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 26 Bypass flow controller arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 27 Bypass flow controller piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 28 Dimensional data—Liebert XDO hard-piped units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 29 Dimensional data—Liebert XDO with pre-charged option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 30 Liebert XDO internal mounting location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 31 Liebert XDO top and front electrical access points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 32 Liebert XDV dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 33 Liebert XDV dimensions with one-shot connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 34 Liebert XDV electrical connections for CE approved units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 35 Liebert XDV electrical connections for CSA-approved units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 36 Suspending single Liebert XDV from Unistruts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 37 Suspending single Liebert XDV from the roof structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 38 Alternative mounting methods—mounting multiple Liebert XDV units . . . . . . . . . . . . . . . . . . . 39
Figure 39 Liebert XDCF hydraulic diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 40 Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 41 Liebert XDCF unit mounting locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 42 Liebert XDCF supply and return piping access points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 43 Liebert XDH dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 44 Supply and return piping connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 45 Hard-pipe connection diagram for Liebert XDV, Liebert XDO and Liebert XDH
cooling modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 46 Two-port prefabricated piping for Liebert XD cooling modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 47 Four-port prefabricated piping for Liebert XD cooling modules . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 48 Five-port prefabricated piping for Liebert XD cooling modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 49 Ten-port prefabricated piping for Liebert XD cooling modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 50 Liebert XDP dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 51 Liebert XDP piping access points and external features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 52 Front view of Liebert XDP and electrical enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Figure 53 Liebert XDP electrical enclosure knockout locations for field wiring . . . . . . . . . . . . . . . . . . . . . . 53
Figure 54 Liebert XDP 60Hz high voltage connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 55 Liebert XDP 50Hz high voltage connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 56 Liebert XDC dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Figure 57 Liebert XDC piping locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 58 Positioning a water/glycol Liebert XDC for placement on a floor stand . . . . . . . . . . . . . . . . . . . . 57
Figure 59 Piping locations—floor stand and valve assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 60 Front view of Liebert XDC and electrical enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Figure 61 Liebert XDC electrical enclosure knockout locations for field wiring . . . . . . . . . . . . . . . . . . . . . . 59
Figure 62 Liebert XDC high voltage connections—primary disconnect switch, 60Hz models . . . . . . . . . . . 60
Figure 63 Liebert XDC high voltage connections—primary disconnect switch, 50Hz models . . . . . . . . . . . 60
Figure 64 Liebert XDC high voltage connections—secondary disconnect switch, 60Hz models . . . . . . . . . . 61
Figure 65 Liebert XDC high voltage connections—secondary disconnect switch, 50Hz models . . . . . . . . . . 61
Figure 66 Liebert XDC heat rejection electrical connection points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Figure 67 Liebert XDC electrical enclosure knockout locations for Extra Low Voltage connections . . . . . . 62
Figure 68 Liebert XDC Extra Low Voltage field connections points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3
iii
TABLES
Table 1 Liebert XD field-installed port kits header connection size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 2 Maximum and minimum modules supported by a Liebert XDP or Liebert XDC . . . . . . . . . . . . . 14
Table 3 Calculating quantity and spacing of Liebert XDO modules (example below is Liebert
XDO20) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 4 Determine required number of Liebert XDV modules (example below is Liebert XDV10) . . . . . 17
Table 5 Supply, return pipe sizes for refrigerant loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 6 Bypass flow controllers for Liebert XDC- or Liebert XDP-based systems . . . . . . . . . . . . . . . . . . . 24
Table 7 System R-134a charge for a Liebert XDP/Liebert XDC with any model Liebert XDH/
Liebert XDO/Liebert XDV/Liebert XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 8 System refrigerant charge for the supply and return mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 9 R-134a refrigerant charge for hard-piped connector lines to and from any model
Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 10 R-134a refrigerant charge for Flex Pipe connector lines to and from any model
Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 11 Calculating refrigerant charge—example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 12 Worksheet to calculate refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 13 Indoor unit refrigerant charge—R-407c . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 14 Air cooled systems - liquid line charge - R-407c refrigerant per 100 ft (30 m) of Type "L"
copper tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 15 Indoor water/glycol cooled module – R-407c refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 16 Outdoor condenser charge—R-407c . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 17 Liebert XD Flex Pipe assemblies, supply and return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 18 Two-port prefabricated piping legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Table 19 Four-port prefabricated piping legend. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 20 Five-port prefabricated piping legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 21 Ten-port prefabricated piping legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 22 Liebert XDP dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 23 Unit piping outlet connection sizes, inches, OD Cu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 24 Liebert XD Chiller dimensions, weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table 25 Liebert XD Chiller piping connection sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Table 26 Liebert XDC Water/Glycol Piping Connection Sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 27 Liebert XDC160 specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Table 28 Floor stand specifications—water-cooled Liebert XDC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Table 29 Floor stand specifications—Liebert XDC with 40% propylene glycol . . . . . . . . . . . . . . . . . . . . . . 65
Table 30 Floor stand specifications—Liebert XDC with 40% ethylene glycol . . . . . . . . . . . . . . . . . . . . . . . 66
Table 31 Liebert XDP160 specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 32 Liebert XDO16 specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Table 33 Liebert XDO20 specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Table 34 Liebert XDO20 dimensions—domestic and export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Table 35 Liebert XDO16 dimensions—domestic and export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Table 36 Liebert XDV8 specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Table 37 Liebert XDV10 specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Table 38 Liebert XDV8 dimensions—domestic and export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 39 Liebert XDV10 dimensions—domestic and export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Table 40 Liebert XDCF specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Table 41 Liebert XDH specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
73
iv

1.0 SYSTEM DESCRIPTION

Enthalpy
Pressure
Liquid Liquid/Vapor Mix Vapor
Traditional
Vapor
Compression
Cycle
Pumped
Two -Phase
Cycle
XD CoolFrame, XDH,
XDO, XDV
The Liebert XD™ family of cooling units delivers efficient, sensible cooling to high-heat environ­ments. Liebert XD systems are designed to cool computer racks and hot zones in a data center or com­puter room without taking up expensive floor space for cooling components.
The Liebert XD family includes:
Liebert XDC—Liebert XD Chiller; cools and pumps refrigerant to cooling modules
Liebert XDP—Liebert XD Pumping unit; pumps refrigerant to cooling modules
Liebert XDA—mounts on the rear of the equipment cabinet
Liebert XDCF—mounts on the rear of an Egenera BladeFrame EX cabinet
Liebert XDH—Liebert XD Horizontal row cooler; integrated into hot aisle-cool aisle room layout
Liebert XDO—Liebert XD Overhead unit, suspended from the ceiling structure
Liebert XDV—Liebert XD Vertical unit; mounted on top of the equipment cabinet or suspended from the ceiling structure
Systems combining Liebert XDO and Liebert XDV units can remove more than 20 kW (5.7 tons) of heat per cabinet. A set of Liebert XDCF modules also can remove 20kW (5.7 tons) of heat from an Egenera BladeFrame EX cabinet. A system with Liebert XDH units can remove more than 30kW (8.5tons) of heat per rack.
For minimum Liebert XDP and Liebert XDC load recommendations, see 1.8.1 - Liebert XDP Mini- mum Load; 1.9.1 - Liebert XDC Minimum Load; and Tables 27 and 31.
System Description
The Liebert XD system also performs at high efficiency rates. Properly spaced cooling modules and the Liebert XD system’s fluid phase change technology, combine to reduce a Liebert XD system’s energy consumption to at least 27 percent less than a traditional cooling system.
The Liebert XD family maintains this energy efficiency by employing the heat absorption properties of a liquid (pumped refrigerant) through a phase change. Refrigerant is pumped as a liquid, becomes a gas within the heat exchangers of the cooling modules (either the Liebert XDCF, Liebert XDH, Lie­bert XDO or Liebert XDV) and then is returned to either the Liebert XDP or Liebert XDC where it condenses to a liquid. This eliminates the compression cycle required by traditional systems. And, if a leak were to occur, the environmentally friendly refrigerant would escape as a gas, causing no harm to critical equipment (see Figure 1). Because no compressor is used in the circuit, no oil is needed.

Figure 1 Pressure enthalpy diagram - refrigerant

1

1.1 European Union Fluorinated Greenhouse Gas Requirements

Pump ed
Refrigerant
Supply Piping
Return Pipi ng
Pump ed
Refrigerant
Liebert XDC
Liebert XDC
Liebert XD
Cooling Module*
Liebert Heat
Rejection
Air Cooled or
Water/Glycol
Cooled
Liebert XD
Cooling Module*
Liebert XD
Cooling Module*
Liebert XD
Cooling Module*
* Liebert XDCF,
Liebert XDH, Liebert XDO or Liebert XDV
Direct Liebert XD System Configuration
Pumping and control are performed by chiller.
Liebert
XDP
Liebert XD
Cooling Module *
Liebert XD
Cooling Module *
Building
Chille d
Water
Liebert
XDP
Liebert XD
Cooling Module *
Supply Piping
Return Piping
Pumped
Refrigerant
Pumped
Refrigerant
* Liebert XDCF,
Liebert XDH, Liebert XDO or Lie bert XD V
Indirect Liebert XD System Configuration Liebert XDPs pump refrigerant to Liebert XDCF, Liebert XDH, Liebert XDO or Liebert XDV modules, isolate refrigerant circuit from building chilled water supply with an internal heat exchanger and maintains refrigerant temperature above the actual dew point.
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys­tems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo­sphere.
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas before disposing of equipment, as well as during service and maintenance.
Refer to the full regulation for additional details.

1.2 Direct and Indirect System Configurations

Liebert XD systems are available in Direct and Indirect configurations—differentiated essentially by the method of heat rejection (see Figures 2 and 3). The indirect system uses a pumping unit con­nected to a building chilled water system to control and circulate the refrigerant. In the direct system, the pumping functions are incorporated in the chiller, which must be connected to a separate heat rejection system.

Figure 2 Direct system configuration—hydraulic system diagram

System Description

Figure 3 Indirect system configuration—hydraulic system diagram

2

1.3 Liebert XDO—Overhead Cooling Module

Cold Aisle
Cold Aisle
Cold Aisle
Hot Aisle
Hot Aisle
Hot aisles and cold aisles alternate, taking advantage of airflow properties to increase cooling efficiency
The Liebert XDO ceiling-mounted cooling module draws in hot air rising from densely populated cab­inets, passes it over the Liebert XDO’s coils and exhausts cooled air downward into the cold aisle. The unit is available with optional, flexible metal pipes with quick-connect couplings at each end for easy connection to the refrigerant distribution pipes.

Figure 4 Suspended Liebert XDO modules in hot aisle-cold aisle arrangement

System Description
3

1.4 Liebert XDV—Vertical, Above-Cabinet Cooling Module

Hot aisles and cold aisles alternate, taking advantage of airflow properties to increase cooling efficiency
Cold Aisle
Cold Aisle
Cold Aisle
Hot Aisle
Hot Aisle
Hot aisles and cold aisles alternate, taking advantage of airflow properties to increase cooling efficiency
Cold Aisle
Cold Aisle
Hot Aisle
Hot Aisle
The Liebert XDV is installed on top of or above a rack enclosure. It is available with optional flexible metal pipes with automatic shutoff with quick-connect couplings at the ends for easy connection to the refrigerant distribution pipes. The Liebert XDV may be set up in either of two ways:
• The Liebert XDV can take hot air directly from an equipment enclosure, cool the air and dis­charge it downward into the cold aisle.
OR
• The Liebert XDV can draw hot air from the room, cool the air and discharge the cool air down­ward into the cold aisle.
System Description
Figure 5
Top-mounted Liebert XDV modules with fixed piping in hot aisle-cold aisle arrangement
Figure 6 Top-mounted Liebert XDV modules with flexible piping in hot aisle-cold aisle
arrangement
4

1.5 Liebert XDH—Horizontal Cooling Module

The Liebert XDH cooling module is designed to be placed within a row of server enclosures in a hot aisle-cold aisle arrangement. The Liebert XDH has dual refrigeration circuits and is available in a half-rack-width unit. The Liebert XDH is intended for use with a Liebert XD pumped refrigerant cool­ing system, supplied by either a Liebert XDP or Liebert XDC.
The Liebert XDH is available with optional, flexible metal pipes with quick-connect couplings at each end for easy connection to the refrigerant distribution pipes.

Figure 7 Liebert XDH—horizontal cooling module in hot aisle-cold aisle arrangement

System Description
5

1.6 Liebert XDCF

The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment without exhausting heat into the room. Two modules (top and bottom) may be mounted on the rear of a BladeFrame cabinet. CF modules consist of a sheet-metal frame, coil and filter dryer. It has no moving parts and needs no electricity.
The unit is available with optional, flexible metal pipes with quick-connect couplings at each end for easy connection to the refrigerant distribution pipes.

Figure 8 Liebert XDCF units on BladeFrame EX cabinets

System Description
6

1.7 Liebert XDA—Air Flow Enhancer

The Liebert XDA is a fan unit that boosts the airflow through densely populated enclosures, removing hot spots from within the racks. One or two units can be mounted on the rear of most rack enclosures.

Figure 9 Liebert XDA—air flow enhancer—on Liebert Foundation enclosure

System Description
7

1.8 Liebert XDP—Pumping Unit

The Liebert XDP isolates the building’s chilled water circuit from the pumped refrigerant circuit. The Liebert XDP circulates refrigerant to Liebert XDCF, Liebert XDH, Liebert XDO or Liebert XDV mod­ules while preventing condensation by maintaining the refrigerant’s temperature above the dew point. The Liebert XDP employs two sets (for redundancy) of remote sensors to determine the temper­ature and humidity in the air and instantly adjusts refrigerant supply temperature to compensate for changing conditions.

1.8.1 Liebert XDP Minimum Load

The Liebert XDP’s minimum recommended operating load is 20% of system nominal capacity. For example, a Liebert XDP160 60Hz system’s minimum load would be 32 kW. Loading below this value can unfavorably affect system operation. Consult factory for any loading below this recommendation.
Figure 10 Liebert XDP pumping unit
System Description
8

1.9 Liebert XDC—Refrigerant Chiller

The Liebert XDC is an indoor chiller that connects directly to the Liebert XD cooling modules and pro­vides refrigerant circulation and control. The Liebert XDC keeps the refrigerant temperature above the dew point and eliminates the need for a separate pumping unit in the direct system configuration. The Liebert XDC employs two sets (for redundancy) of remote sensors to determine the temperature and humidity in the air and instantly adjusts refrigerant supply temperature to compensate for changing conditions.

1.9.1 Liebert XDC Minimum Load

The Liebert XDC’s minimum recommended operating load is 40% of system nominal capacity. For example, a Liebert XDC160 60Hz system’s minimum load would be 64 kW. Loading below this value can unfavorably affect system operation. Consult factory for any loading below this recommendation.
Figure 11 Liebert XD Chiller unit
System Description
9

1.10 Liebert XD Piping

Return valve shown Supply valve appearance is similar, but is smaller
Liebert XD Piping is prefabricated distribution piping that is installed in anticipation of a growing sys­tem. Liebert XD cooling modules are added as required and are quickly made operational with flexible connection piping with threaded couplings. This unique system allows the room cooling capacity to increase to more than 30kW per rack with no additional disruptive piping installation. The flexible connection piping also allows the cooling modules to be re-positioned without interruption in operation.

1.10.1 Liebert XD Field Piping

Flexible Piping Kit
Flex pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters). Connection style to the module end may be straight or 90 degrees with one-shot style couplings or removable cou­plings. Connection to the prefabricated piping assembly is a threaded coupler. For information on acquiring the correct kit for your installation refer to DPN000780_Rev1, available by calling 1-800-LIEBERT and from your local Emerson Network Power representative.
Prefabricated Headers
Field piping kits are available in several versions
• 10 ft. (3.05m) with five or 10 ports
• 8 ft. (2.44m) with two or four ports
Each version is available in two pipe sizes:
• Supply pipe: 1-1/8"; return pipe: 2-1/8"
• Supply pipe: 1-3/8"; return pipe: 2-5/8"
Each kit contains supply pipe(s) and return pipe(s). Each port has a threaded coupling at the end with automatic shutoff when disconnected. Each port also has a ball valve for manual shutoff. For more information refer to section 4.9 - Liebert XD Piping Dimensions and Features.
System Description
Liebert XD Connection Port Kit
The connection ports in the Liebert XD Field Piping Kits are available as Liebert XD Connection Port Kit. Each port has a threaded coupling, with automatic shutoff when disconnected, at the end. Each port also has a ball valve for manual shutoff. Each kit contains one supply and one return port. Two kit sizes are available:
• Supply pipe: 1-1/8"; return pipe: 2-1/8"
• Supply pipe: 1-3/8"; return pipe: 2-5/8"
Figure 12 Liebert XD connection port kit
Table 1 Liebert XD field-installed port kits header connection size
Assembly P#
183169G3 1-1/8" 2-1/8"
183169G4 1-3/8" 2-5/8"
Supply Header
Diameter
Return Header
Diameter
10

2.0 STARTING A NEW EQUIPMENT COOLING PROJECT

2.1 Determining Cooling Equipment Needs

1. Is adequate space available for a Liebert XD installation?
2. Is the hot aisle/cold aisle approach being utilized for this room design or can it be utilized in this room design?
3. Is redundant cooling equipment required?
4. Are there access considerations for all components (possible rigging problems)
5. What heat load growth is anticipated over the next few years?
6. How are the cabinets going to be populated (density of heat generation)?
7. What monitoring requirements are desired or needed?
8. Who will be involved in this project (stakeholders)?
9. Is there existing computer room environmental cooling systems for humidity control and filtration?
10. Is the vapor barrier sufficient?
11. Is a chilled water system available?
a. What is the system’s capacity?
b. What is the system’s chilled water supply temperature?
Starting a New Equipment Cooling Project
c. Does the chilled water supply temperature vary during the year or is the
temperature constant?
12. How much power is available for cooling equipment?
13. What is the maximum distance between the Liebert XDP/Liebert XDC unit and the farthest Liebert XD cooling module in the proposed layout?
14. If an air cooled Liebert XDC is used – is an area available for the remote condenser?
11

2.2 Implementing a Hot-Aisle/Cold Aisle Design

Cold air supplied through perforated floor tiles is drawn into racks
Heated air expelled from racks is drawn into cooling unit and returned to floor supply
A best practice is to use rows of equipment racks in an alternating arrangement of cold aisles and hot aisles. This is best accomplished when the layout of the file-server farm area is first being planned, and it is exceedingly more difficult to accomplish when the computer room is already populated with operating hardware.
In the cold aisle, the equipment racks are arranged face to face so the cooling air discharged up through the perforated floor tiles is drawn into the face of the computer hardware and exhausted out the back of the equipment rack onto the adjacent hot aisles.
Hot aisles are literally hot because the objective of the alternating cold and hot aisle design is to sepa­rate the source of cooling air from hot air discharge which returns to the computer-room cooling unit. Therefore, no perforated tiles should be placed in the hot aisles. as this would mix hot and cold air and thereby lower the temperature of the air returning to the cooling units, which reduces their usable capacity.

Figure 13 Hot aisle-cold aisle arrangement with under-floor source

Starting a New Equipment Cooling Project
12
Designing a Liebert XD Solution

3.0 DESIGNING A LIEBERT XD SOLUTION

Liebert XD systems are intended for use with precision air conditioning equipment, such as the Lie­bert Deluxe System/3 and Liebert DS. The precision air conditioning equipment is required to control the room’s humidity and to filter the air.
The Liebert XD systems provide efficient, highly effective heat removal (sensible cooling only), and provide no dehumidification. The Liebert XD control system maintains the refrigerant temperature just above the dew point of the space to prevent condensation. Since the capacity of the system is lim­ited by the dew point in the space, sufficient dehumidification and an adequate vapor barrier must be provided to maintain the dew point at or below the level necessary to achieve the required capacity.
The Liebert XD system is optimized for hot aisle/cold aisle equipment configurations, the industry’s most highly recommended method for dealing with extremely high heat loads.
Refer to the technical data manual of either the Deluxe System/3 (SL-18100) or the Liebert DS (SL-18810) for additional installation and application guidelines that apply to all critical space cooling applications.

3.1 Determine Cooling Requirements and Select Liebert XD System

1. Calculate the total cooling required
2. Determine placement of the Liebert XD units
3. Determine required pipe sizes
4. Calculate the refrigerant volume of the Liebert XD systems
5. Complete design details including, electrical, mounting, piping, etc.

3.2 Calculate the Heat Load to be Handled by Liebert XD System

When designing a cooling solution using the Liebert XD system, the initial steps are similar to those required to cool a conventional critical space. The total heat load must be calculated, including sensi­ble and latent cooling requirements. These should be increased by the reserve capacity needed for pull-down situations where the room temperature must be reduced and to provide for unexpected increases in heat load.
NOTE
Reserve capacity is distinct from redundant capacity in that redundant capacity may or may not be available concurrently with normal operating capacity. Reserve capacity is available concurrently with normal operating capacity.
The next step is to determine how much of the required cooling capacity is to be provided by Liebert Deluxe or Liebert DS units. If the facility is new, typically up to 150 watts per square foot (1500W/m of cooling can be obtained from Liebert precision air conditioning units supplying air through a raised floor. In existing facilities, such factors as raised floor height, under-floor obstructions or other limita­tions may reduce this to less than 50 watts per square foot (500 watts per m
Once the total required sensible cooling capacity is known, subtract the sensible cooling portion to be provided by Liebert Deluxe or Liebert DS units. This yields the cooling capacity to be provided by the Liebert XD system.
2
)
2
).
13

3.3 Selecting Liebert XD Cooling Modules

The next step is to select the Liebert XD cooling modules to be configured into the solution. Liebert XD modules that use pumped refrigerant can be connected to the same Liebert XDP/Liebert XDC pip­ing circuit. This includes the Liebert XDCF, Liebert XDH, Liebert XDO and Liebert XDV.
Generally, the Liebert XDO is selected for use in new installations or renovations where the unit can be installed on the ceiling or in the overhead space.
The Liebert XDV is designed to permit mounting directly on top of an equipment cabinet, for ease of installation in existing facilities. The Liebert XDV may also be suspended from overhead, using suit­able mounting methods.
The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment without exhausting heat into the room. Two modules may be mounted on the rear of a BladeFrame cabinet.
The Liebert XDH is installed among equipment cabinets and is particularly suited to new installa­tions.

3.4 Airflow Requirements for Liebert XD Solutions

Computer manufacturers typically specify a temperature change from intake to exhaust (delta T) of 18-27°F (10-15°C) for the air passing through a rack enclosure. The heat generated by electronic equipment combined with the tight quarters of equipment cabinets mean that high volumes of air must move through an enclosure to meet this cooling specification.
A Liebert XD system can supply the cooled air to satisfy this cooling demand, but airflow through the enclosure must be adequate to extract the heat from the cabinet. Liebert’s XDA units can boost the airflow to levels necessary to protect critical equipment. The Liebert XDA is particularly suited to the hot aisle/cold aisle arrangement.
Designing a Liebert XD Solution

3.5 Configuring a Liebert XD System

3.5.1 Number of Modules Supported by a Liebert XDP or Liebert XDC

The numerals designating the model size of a Liebert XD unit may be used to configure a cooling sys­tem. For example, a Liebert XDO20 has a model size of 20 and a Liebert XDP160 will accommodate cooling modules with a cumulative model size of 160.
Similarly, the minimum number of modules connected to a Liebert XDP or Liebert XDC may be calcu­lated using the model size number for the Liebert XDP or Liebert XDC and the modules. See Table 2.
Table 2 Maximum and minimum modules supported by a Liebert XDP or Liebert XDC
Cooling
Module Type
Liebert XDCF 16 6 16 4
Liebert XDH20 8 4 8 2
Liebert XDH32 5 2 5 1
Liebert XDO16 10 4 10 2
Liebert XDO20 8 4 8 2
Liebert XDV8 20 8 20 4
Liebert XDV10 16 7 16 4
Different types of Liebert XD cooling modules may be connected to the same Liebert XDP or Liebert XDC as long as the sum of their cooling capacity does not exceed the supporting Liebert XDP’s or Lie­bert XDC’s model size number.
Liebert XDC Liebert XDP
Max Min Max Min
NOTE
Connecting only Liebert XDCF modules to a Liebert XD unit is not recommended because the Liebert XDCF heat loading is dependent on server airflow and server load. Consult factory to determine if sufficient heat load is available from the server for the Liebert XD system to operate effectively.
14

3.6 Liebert XDO Placement

HOT AISLE
Cold Aisle Spacing
Hot air is
drawn into
the XDO for
cooling
XDOXDO
Critical
Equipment
Critical
Equipment
Critical
Equipment
Critical
Equipment
COLD AISLE
Hot air goes
into the hot
aisle
Cooled air enters the
rack...
Hot air goes
into the hot
aisle
Cooled air enters the
rack...
COLD AISLE

3.6.1 Determining Spacing of Liebert XDOs in an Aisle

Liebert XDO units should be placed in rows directly above the cold aisles of a room for optimum cool­ing. Each Liebert XDO serves an area equal in width to the cold aisle spacing, typically 12 to 16 feet (3.7 to 4.9m). The length of the area served includes any space between Liebert XDO modules in a row. Depending on the cooling capacity to be achieved, spacing between Liebert XDO modules in a row may vary from zero to as much as 6 feet (1.8m). When the spacing increases to more than 6 feet (1.8m), overall performance of the system may be negatively affected and gaps in cooling may occur.
Emerson recommends installing one Liebert XDO at the end of each aisle being cooled and to space the remainder between these end units in pairs as shown in Figure 15. This layout will block the incursion of hot air around the side of the end cabinets.
Figure 14 Liebert XDO placement over cold aisle
Designing a Liebert XD Solution
Table 3 can be used to determine the correct number and spacing of Liebert XDOs.
Table 3 Calculating quantity and spacing of Liebert XDO modules (example below is Liebert XDO20)
Input Information Step Result
Total heat load in the room, kW A
Reserve capacity needed (10% to 25% of A is recommended)
Existing/planned Liebert Deluxe/DS unit sensible capacity, kW
Room area, square feet H
Spacing of cold aisles, center-to-center, typically 12-16 ft (3.7 to 4.9m)
B
C Required cooling capacity, kW = A + B
D
E Required Liebert XD system cooling capacity, kW = C – D
Number of Liebert XDO20s required = E ÷ 20, rounded up (60Hz)
F
Number of Liebert XDP
G
rounded up (60Hz and 50Hz)
I Area served by each Liebert XDO20 = H ÷ F
J
K Spacing between each Liebert XDO = (I ÷ J) - 2
L
Required Liebert XD system cooling density = E x 1000 ÷ H OK if under 640; otherwise, additional cooling is required from Liebert Deluxe or Liebert DS units.
15
/Liebert XDC modules required = F ÷ 8,
= E ÷ 16, rounded up (50Hz)
Designing a Liebert XD Solution
Front-to-rear spacing of pairs of XDO modules
XDO height above equipment to be cooled
Heat-Generating Critical Equipment
Pairs of XDO modules
above critical equipment
Liebert recom­mends install­ing one Liebert XDO at the end of each aisle being cooled and to space the remainder between these “end units” in pairs. This lay­out will block the incursion of hot air around the side of the end cabinets.

3.6.2 Determining Vertical Placement of Liebert XDOs Above the Cold Aisle

In the maximum density configuration, Emerson recommends placing the Liebert XDOs between 18 and 24 inches (457-609mm) above the equipment cabinets. In some cases where the required density is less, the front-to-rear spacing of Liebert XDOs in a row will be increased. To ensure coverage of the wider spaces between the Liebert XDO units, the vertical distance between the cabinets and the Lie­bert XDOs should be increased. However, the recommended maximum height of the Liebert XDO above the cabinets is 30 inches (762mm). See Figures 15.
Figure 15 Liebert XDO spacing—horizontal and vertical
16

3.7 Liebert XDV Unit Placement

INCORRECT
Liebert XDV
hangs over front
edge of rack
INCORRECT
Liebert XDV is
too far from front
edge of rack
CORRECT
Liebert XDV is flush with
front edge of rack
X
Liebert XDV is suspended from ceiling structure. ..
X
....the separation
between the rack and the Liebert XDV should be held to less than 1" (25mm). If this is not possible, an air blocker should be added to prevent unwanted airflow between the hot aisle and the cold aisle.
Liebert XDV units should be placed on top of the cabinets that generate the greatest amount of heat. If heat loads are dispersed evenly throughout the room, the Liebert XDV modules may be spread out accordingly.
The Liebert XDV must be placed toward the front of the equipment cabinet, so that its front bottom edge is flush with the front top edge of the cabinet. Placing the unit farther back on the top of the unit will restrict airflow into the cold aisle. Placing the unit farther to the front will decrease the amount of hot air drawn into the unit.

Figure 16 Positioning Liebert XDV on top of cabinet

Designing a Liebert XD Solution
Both of the Liebert XDV’s power cords should be connected to power sources. If only one power source is available, then only the power cord labeled “SECONDARY” should be connected to the power source.
Piping for the Liebert XDV is routed upward to the main return and supply pipes to and from the Lie­bert XDP/Liebert XDC.
Table 4, below, may be used to determine the correct number of Liebert XDV modules.

Table 4 Determine required number of Liebert XDV modules (example below is Liebert XDV10)

Total heat load in the room, kW A Reserve capacity needed
(10% to 25% of A is recommended)
Existing/planned Liebert Deluxe/DS sensible capacity, kW
Room area, square feet H
Input Information Step Results
B
C Required cooling capacity, kW = A + B
D
E Required Liebert XD system cooling capacity, kW = C – D
Number of Liebert XDV10 modules required = E ÷ 10, rounded up (60Hz)
F
Number of Liebert XDP/Liebert XDC modules required = F ÷ 16, rounded
G
up (60Hz and 50Hz)
I Area served by each Liebert XDV10 = H ÷ F
L
Required Liebert XD system cooling density = E x 1000 ÷ H OK if under 580 for 12-foot cold aisle spacing OK if under 435 for 16-foot cold aisle spacing Otherwise, additional Liebert Deluxe or Liebert DS unit capacity is needed.
17
= E ÷ 8, rounded up (50Hz)

3.8 Liebert XDCF Placement

Liebert XDCF Modules
attached to
Egenera BladeFrame EX Cabinet
Upper Module
Lower Module
The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment. Liebert XDCF modules attach to the rear of the Egenera BladeFrame EX cabinet, beside the power modules (see Figure 17). No cutting or drilling is required to attach the modules; all mounting holes, slots and pins required are fabricated at the factory. The Liebert XDCF does not require electrical connections.
The number of Liebert XDCF modules required is determined by the heat load of the cabinet—cabi­nets cannot share cooling from a Liebert XDCF module.
The Egenera BladeFrame EX cabinet has provisions for mounting two Liebert XDCF modules, should the heat load require two modules. If only one Liebert XDCF will be needed, Liebert recommends using the lower Liebert XDCF module.
The complete system consists of Liebert XDCF modules, piping, Liebert XDP or Liebert XDC refriger­ant distribution units and those units’ chillers or drycoolers.

Figure 17 Liebert XDCF unit mounting locations

Designing a Liebert XD Solution
18

3.9 Liebert XDH Placement

X
D
H
X
D
H
X
D
H
X
D
H
X
D
H
X
D
H
X
D
H
X
D
H
Hot
Aisle
Cold Aisle
Hot
Aisle
Cold Aisle
X
D
H
X
D
H
X
D
H
X
D
H
X
D
H
The free-standing Liebert XDH cooling unit is best placed among the equipment cabinets in a hot aisle-cold aisle arrangement (see Figure 18). The Liebert XDH draws in air from the hot aisle, cools it and discharges the cooled air into the cold aisle where it is drawn into the equipment cabinets. Reg­ular spacing aids in optimizing cooling.
Liebert XDH units should be placed among the cabinets that generate the greatest amount of heat. If heat loads are dispersed evenly throughout the room, the Liebert XDH modules may be spread out accordingly.
If a Liebert XDH is installed at the end of a row, Liebert recommends using uni-directional air diffus­ers on that Liebert XDH. The uni-directional diffusers can be used for left or right air discharge by removing them from the Liebert XDH, turning them 180 degrees, then reattaching them to the Lie­bert XDH.
Liebert recommends using bi-directional air diffusers on Liebert XDH modules installed between racks.

Figure 18 Liebert XDH placement

Designing a Liebert XD Solution

3.10 Liebert XDP/Liebert XDC Placement

The Liebert XDP/Liebert XDC may be placed in the critical space or in an adjacent equipment room. The allowable distance between the Liebert XDP/Liebert XDC and its connected cooling modules is determined by the piping design and by the amount of refrigerant required. Refer to 3.12 - Liebert XD Refrigerant and 3.13 - Liebert XD Piping System Design.
The maximum height of any of the main or connecting piping should be no more than 20 feet (6m) above the top of the Liebert XDP/Liebert XDC unit. Liebert XDV/Liebert XDO modules should be placed as close to the same level as possible. The differences in elevation between the highest and low­est Liebert XDV or Liebert XDO module in a system should be no more than 6 feet (2m).
19
Designing a Liebert XD Solution
Downflow
Cooling
Unit
Downflow
Cooling
Unit
XDVs Mounted on Equipment Rack s
Perforated Raised Floor Tile s
Circuit 1
Equipment Racks without XDVs
Downflow
Cooling
Unit
Downflow
Cooling
Unit
Equipment Racks without XDVs
XDVs Mounted on Equipment Ra cks
Circuit 2Circuit 1
Perforated Raised Floor Tile s
Interlaced piping arrangement for enhanced protection

3.11 Examples of Expansion and Interlaced Connection of Liebert XD Cooling Modules

Figure 19 Liebert XDV units mounted on racks emitting 3kW of heat, top view

Figure 20 Liebert XDV units mounted on racks emitting 5kW of heat, top view

20

Figure 21 Liebert XDV units mounted on racks emitting 8kW of heat top view

Downflow
Cooling
Unit
Downflow
Cooling
Unit
XDVs Mounte d on Equipment Racks
Circuit 1 Circuit 2 Circuit 3
Perforated Raised Floor Tiles
Interlaced piping arrangement for enhanced protection
Downflow
Cooling
Unit
Downflow
Cooling
Unit
Perforated Raised Floor Tiles
XDOs Mounted on Equipment Ra cks
Circuit 4
Circuit 5 Circuit 6
XDVs Mounted on Equipment Ra cks
Circuit 3Circuit 1 Circuit 2
Interlaced piping arrangement for enhanced protection
Designing a Liebert XD Solution

Figure 22 Liebert XDV units mounted on racks emitting 16kW of heat top view

21

3.12 Liebert XD Refrigerant

!
The refrigerant used in the Liebert XD system is HFC-134a (1,1,1,2-tetrafluoroethane), made by a number of manufacturers. The amount of refrigerant used by the Liebert XD system may be signifi­cantly higher than in typical DX cooling systems.
CAUTION
Risk of improper oil use. Can cause equipment damage.
The Liebert XD pumped R-134a refrigerant circuits do not use refrigerant oil. Do NOT put oil in the R-134a system.
Designing a Liebert XD Solution
All the major components of a Liebert XD system must be installed in a space with a volume of at least 1,000 ft dard 15-2001, Safety Standard for Refrigeration Systems. If the Liebert XDP/Liebert XDC is placed in a separate area, such as a machine room, then this area must also meet the volume requirement. Inside the critical space, this includes the space under the raised floor, and the space between the top of the raised floor and the bottom of a suspended ceiling. If the suspended ceiling is all open grates, then this additional space, up to the overhead deck, would also be included.
Example
A space is 5,000 square feet, with an 18" raised floor and an 8' 6" suspended ceiling. Liebert XDOs and a Liebert XDP are to be placed in this raised-floor area.
The volume of the space is (1.5 + 8.5) x 5,000 or 50,000 cubic feet. The maximum amount of R-134a refrigerant that can be used in a single Liebert XDP/Liebert
XDC/Liebert XD module system within this space is 16 * (50000/1000) = 16 * 50 = 800 lb. Multiple Liebert XD systems can be installed in this space, as long as the amount of R-134a
refrigerant in any one system does not exceed 800 lb.
3
(28.3m3) for each 13 pounds of refrigerant in that system from Table 1, ASHRAE Stan-
NOTE
Local codes might permit exceeding the maximum refrigerant limit stated above if refrigerant detector and an exhaust system are installed. As an alternative, oxygen sensors may be installed to meet some local codes.

3.13 Liebert XD Piping System Design

All piping must be ASTM (American Society for Testing and Materials) Type “L” copper pipe. The typ­ical maximum operating pressure in the system is 90 psi (620kPa).
Piping for the Liebert XD system is arranged in a manner similar to piping for a chilled water system. Liebert XD cooling modules (Liebert XDCF, Liebert XDH, Liebert XDO or Liebert XDV) are connected in parallel between the main return and supply pipes going to and from the Liebert XDP/Liebert XDC.
Figure 23 represents a typical configuration. The guidelines provided for pipe size must be strictly followed. Failure to size the main lines and connection lines adequately may result in reduced cooling capacity. The critical aspects of pipe sizing are related to refrigerant volume and
pressure drop. Each must be minimized.
22
Designing a Liebert XD Solution
Liebert XDP/
Liebert XDC
SLOPE—The main supply and return lines to and from the Liebert XDP/Liebert XDC must be sloped downward toward the Liebert XDP/Liebert XDC at a rate of 1-2" per 20 feet (25.4-51mm per 6m) of pipe run. Horizontal connector lines should also be sloped downward from the cooling modules toward the main supply and return lines.
Liebert XD Cooling Modules
All supply and return mains must be level with or above the top of all Liebert XDP or Liebert XDC units
9ft.
(2.7m)
max.
20ft.
(6.7m)
max.

Figure 23 Piping for Liebert XDP/Liebert XDC used with Liebert XD cooling units

The assembly and connection means used for piping in the Liebert XD system are similar to that of conventional refrigeration systems. All piping should be installed with high temperature brazed joints. Soft solder is not recommended. The lines being brazed MUST be filled with flowing dry nitro­gen during brazing to prevent excessive oxidation and scale formation inside the piping.
Insulate all piping lines to prevent condensation in applications where the dew point approaches the R-134a refrigerant temperature.
Please see Table 5 below for recommended pipe sizes and Figure 24 for piping segment locations.

Table 5 Supply, return pipe sizes for refrigerant loop

Key to Piping
Pipe Function
Liebert XDP supply line, from Liebert XDP supply to farthest Liebert XD cooling module
Liebert XDP return line, from farthest Liebert XD cooling module to Liebert XDP return
From any model Liebert XDO/Liebert XDH supply to supply line of Liebert XDP
From any model Liebert XDO/Liebert XDH return to return line of Liebert XDP
From any model Liebert XDV/Liebert XDCF supply to supply line of Liebert XDP
From any model Liebert XDV/Liebert XDCF return to return line of Liebert XDP
in Figure 24 Size / Equivalent Pipe Length
A
B
C
D
C
D
1-1/8" OD for lengths up to 60 feet
1-3/8" OD for lengths over 60 but less than 175 feet
2-1/8" OD for lengths up to 60 feet
2-5/8" OD for lengths over 60 but less than 175 feet
1/2" OD for lengths up to 10 feet
7/8" OD for lengths over 10 but less than 25 feet
7/8" OD for lengths up to 10 feet
1-1/8" OD for lengths over 10 but less than 25 feet
1/2" OD for lengths up to 10 feet
5/8" OD for lengths over 10 but less than 35 feet
5/8" OD for lengths up to 10 feet
7/8" OD for lengths over 10 but less than 35 feet
For additional information about piping connections, see the unit’s user manual: Liebert XDP, 16641; Liebert XDC, SL-16671; Liebert XDO, SL-16666; Liebert XDV, SL-16626; Liebert XDCF, SL-16678; and Liebert XDH20 and Liebert XDH32, SL-17210.
NOTE
To minimize the amount of refrigerant required, do NOT oversize the piping.
23

Figure 24 Hydraulic diagram

Liebert XDC
or
Liebert XDP
XD Cooling
Module *
XD Cooling
Module *
XD Cooling
Module *
XD Cooling
Module *
Pumped
Refrigerant
Liebert XDC
or
Liebert XDP
Supply Lines
Return Lines
Pumped
Refrigerant
* XD CoolFrame,
XDH, XDO or XDV
A
B
A
B
C
D
C
D
C
D
C
D

3.14 Liebert XD Piping Slope

The main supply and return lines to and from the XDP/XDC must be sloped downward toward the XDP/XDC at a rate of 1-2" per 20 feet (25-51mm per 6m) of pipe run. Horizontal connector lines should also be sloped downward from the cooling modules toward the main supply and return lines.
Designing a Liebert XD Solution

3.15 Bypass Flow Controllers

To ensure the XDP/XDC pumps operate within the optimum range, some installations require one or more bypass flow controller(s). These devices are added to the field piping, and simulate the flow of additional cooling modules.
Each bypass flow controller should be installed with one shutoff valve to allow the controller to be dis­abled when cooling modules are added to a Liebert XD system.
If bypass flow controllers are required, they should be connected between the main supply and the main return lines of the field piping. The connection points to the main supply and return lines should be in a convenient and accessible location between the Liebert XDP/Liebert XDC and the first Liebert XD module in the circuit. See Figures 26 and 25 for piping details of the bypass flow controller.
Refer to Table 6 to determine the number of bypass flow controllers needed, based on the total nomi­nal cooling capacity of the cooling modules in each Liebert XD system.

Table 6 Bypass flow controllers for Liebert XDC- or Liebert XDP-based systems

Cooling Modules ­Cumulative Model Size
32 to 63 3 N/A
64 to 95 2 2
96 to 127 1 1
128 to 160 0 0
Required Number of Bypass Flow Controllers
Liebert XDP Liebert XDC
24

Figure 25 Bypass flow controller details, dimensions

7/8
"
(2.2mm) ID
4
"
(102mm)
Return
Main
7/8" Refrigerant Grade Full Port Ball Valve Field-Supplied and Field-Installed
Supply
Main
Bypass Flow Controller (Field-Installed)
Flow Di rection
Filter Dryer Assembly
Liebert XD
Cooling
Module #1
Liebert XD
Cooling
Module #2
Coolant Supply
Coolant Return
Bypass Flow Controllers
Liebert XDP
or
Liebert XDC

Figure 26 Bypass flow controller arrangement

Designing a Liebert XD Solution

Figure 27 Bypass flow controller piping

25

3.16 Determining Refrigerant Volume

After the preliminary system design is completed, Tables 7, through 15 may be used to determine the amount of refrigerant required. Perform the calculation below for each Liebert XD system being configured.
NOTE All lengths in Tables 7, 8, 9 and 10, are actual pipe lengths, not equivalent pipe lengths.

3.16.1 Liebert XDP/Liebert XDC Pumped R-134a Circuit Volume

NOTE
System refrigerant volume calculations in Tables 7, 8, 9 and 10, are based on a fully loaded system. Additional charge may be required for lightly loaded systems.
Table 7 System R-134a charge for a Liebert XDP/Liebert XDC with any model Liebert
XDH/Liebert XDO/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb (kg)
157 lb. (65.7kg) Liebert XDP/Liebert XDC
3.55 lb. (0.66kg) Liebert XDO
2.32 lb. (1.05kg) Liebert XDV
5.32 lb. (2.41kg) Liebert XDH
1.41 lb. (0.64kg) Liebert XDCF
Per Liebert XD Unit (Excludes Connector Lines to and from Liebert XD Cooling Module)
Designing a Liebert XD Solution
Table 8 System refrigerant charge for the supply and return mains
Refrigerant Charge,
lb/foot (kg/m)
0.45 (0.67) Main supply actual length per 1-1/8" OD copper tubing
0.68 (1.01) Main supply actual length per 1-3/8" OD copper tubing
0.28 (0.42) Main return actual length per 2-1/8" OD copper tubing
0.43 (0.64) Main return actual length per 2-5/8" OD copper tubing
Supply/Return Main Length and Diameter
Table 9 R-134a refrigerant charge for hard-piped connector lines to and from any model
Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb/foot (kg/m)
0.08 (0.12)
0.13 (0.19) 5/8" OD copper tubing Liebert XDV/Liebert XDCF supply connector actual length
0.26 (0.39) 7/8" OD Liebert XDO/Liebert XDH supply connector actual length "
0.02 (0.03) 5/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length
0.04 (0.06) 7/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length
0.04 (0.06) 7/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length
0.07 (0.1) 1-1/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length
Hard-Piped Connector Length and Diameter
1/2" OD Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF supply connector actual length
26
Designing a Liebert XD Solution
Table 10 R-134a refrigerant charge for Flex Pipe connector lines to and from any model
Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF
Refrigerant Charge, lb. (kg) Metal Flex Pipe Connector Length
Supply Line Diameter 1/2"
0.3 lb. (0.14) 4 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.5 lb. (0.23) 6 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.7 lb. (0.32) 8 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert
0.8 lb. (0.36) 10 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert
Return Line Diameter 5/8"
0.01 lb. (0.01) 4 ft. Flex Pipe existing Liebert XDV systems
0.02 lb. (0.01) 6 ft. Flex Pipe existing Liebert XDV systems
0.03 lb. (0.01) 8 ft. Flex Pipe existing Liebert XDV systems
0.03 lb. (0.01) 10 ft. Flex Pipe existing Liebert XDV systems
Return Line Diameter 1"
0.13 lb. (0.05) 4 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert
0.2 lb. (0.09) 6 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert
0.27 lb. (0.12) 8 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert
0.33 lb. (0.15) 10 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply
XDV/Liebert XDCF supply
XDV/Liebert XDCF supply
XDV/Liebert XDCF supply
XDV/Liebert XDCF supply
XDV/Liebert XDCF supply
27

3.16.2 Calculating Refrigerant Charge—Example

!
Using Tables 7, 8, 9 and 10, calculate the refrigerant charge of the individual sections of your Liebert XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF, Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20 Liebert XDV8 cooling modules.
Table 11 Calculating refrigerant charge—example
Components
Liebert XDP/Liebert XDC 1 157 157
Liebert XDV8 Cooling Modules 20 2.32 46.4
Supply Main, 1-1/8" 100 0.45 45
Return Main, 2-1/8" 100 0.28 28
Liebert XDV 1/2" supply Flex Pipes
Liebert XDV 5/8" return Flex Pipes
Table 12 Worksheet to calculate refrigerant charge
Components
Number of Units
or Piping Length, feet Pounds Per Component Total, lb.
20 0.8 16
20 0.03 0.6
Number of Units
or Piping Length Pounds Per Component Total
Designing a Liebert XD Solution
Total 293
Verify that the refrigerant volume of the Liebert XD system with the longest piping length is within the allowable limit. If the allowable limit is exceeded, the Liebert XDP/Liebert XDC should be moved closer to the cooling modules (refer to 3.12 - Liebert XD Refrigerant for limits and related details). Another way to shorten the total pipe length is to reroute the pipe runs.

3.17 Liebert XDC DX R-407c Circuit Volume—Air Cooled Units

CAUTION
Risk of improper lubrication. May cause equipment damage.
Liebert XDCs with refrigerant R-407c charges over 35 lb. (15.9kg) require additional oil. Refer to the Liebert XDC user manual, SL-16671, available at Liebert’s Web site,
Weigh in the calculated charge based on Tables 13, 14 and 15.

Table 13 Indoor unit refrigerant charge—R-407c

Model 60/50 Hz Charge/Circuit, lb. (kg)
Liebert XDC160 17.5 (8.0)
28
Total
www.liebert.com
Designing a Liebert XD Solution

Table 14 Outdoor condenser charge—R-407c

Model Charge / Circuit, lb (kg)
CDL830 200 (90.8)
CSL616 254 (115.2)
CSL415 200 (90.8)
Table 15 Air cooled systems - liquid line charge - R-407c refrigerant per 100 ft (30 m) of Type "L"
copper tube
O.D.,
inches
3/8 3.7 (1.7) -
1/2 6.9 (3.1) -
5/8 11.0 (5.0 2.2 (1.0)
3/4 15.7 (7.1) 3.1 (1.4)
7/8 23.0 (10.4) 17.5 (8.0)
1-1/8 39.3 (17.8) 7.8 (3.5)
1-3/8 59.8 (27.1 11.8 (5.4)
1-5/8 - 16.7 (7.6)
Liquid Line,
lb (kg)
Hot Gas Line,
lb (kg)

Table 16 Indoor water/glycol cooled module – R-407c refrigerant charge

Model 60 Hz Charge / Circuit, lb(kg)
Liebert XDC 160 30.0 (13.2) per circuit

3.18 Chilled Water Piping

The Liebert XDP is offered only with a two-way chilled water control valve. Some applications may require the use of a pressure activated bypass valve, to prevent dead-heading of the chilled water pump. This bypass valve must be specified by the engineer responsible for design of the chilled water field piping system.
Chilled water connections to the Liebert XDP are near the bottom of the unit. Refer to the Liebert XDP user manual (SL-16641) for further information. Piping is routed downward from the unit to chilled water piping under the raised floor. Connections are made using standard practices for copper chilled water piping. Victaulic
®
connections may be used to simplify installation in existing facilities.
Refer to Table 31 for additional information.

3.19 Electrical

Make all wiring and electrical connections in accordance with local and national codes. Refer to the applicable table in 5.0 - Specifications regarding wire size and circuit protection requirements. Refer to electrical schematic when making connections.

3.20 Display Panel and Remote Temperature/Humidity Sensor Locations

The display panel must always be installed in the conditioned space. The display panel may be mounted on the Liebert XDC/XDP’s front door if the unit is located in the area that it conditions.
The remote temperature / humidity sensor for the Liebert XDP and the Liebert XDC should be located in the higher-temperature portion of the cold aisle where the XD modules are located. Alternatively, it can be placed on the return air side of the primary air mover (e.g., Liebert Deluxe System/3 room if it represents the conditions where all the XD cooling modules are located. It should not be installed where ambient air might cause false readings, for example, near unsealed doors, windows and similar areas.
) in the
29

Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

4.0 LIEBERT XD COOLING MODULES—LIEBERT XDO, LIEBERT XDV, LIEBERT XDH
AND LIEBERT XDCF

4.1 Liebert XDO Standard Features

• Micro Channel Heat Exchanger—The Liebert XDO unit includes two all-aluminum micro channel heat exchangers.
• Fan—Air is drawn in the sides of the unit through the heat exchangers and is discharged by the fan to the area below—Liebert XDO fan tray hinges down to allow access to replace or service all electrical components.
• Internal Mounting—The Liebert XDO unit is typically suspended from the overhead building structure by inserting field-supplied threaded rods into the internal mounting brackets.

4.1.1 Optional Features Liebert XDO

Refrigerant Pre-Charge—Liebert XDO units with the pre-charged refrigerant option will have one-shot style fittings or removable couplings that contain pressurized refrigerant inside the Lie­bert XDO. The fittings ease connection to Liebert XD Piping and filling with refrigerant.
Field-Installed Flexible Piping (for use with prefabricated piping assemblies)—Field-installed flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters). Con­nection style to the unit end may be straight or 90 degrees. Connection to the prefabricated piping assembly is with a threaded coupler. For information on acquiring the correct kit for your instal­lation, refer to DPN000780, available by calling 1-800-LIEBERT and from your local Emerson Network Power representative.
External Mounting Brackets—The Liebert XDO unit can be suspended by external mounting brackets that are attached to the front and rear panels of the unit. The external mounting brack­ets are optional ship-loose items.
Condensate Detection—The Liebert XDO unit is available with optional factory-installed con­densate detection. The condensate detection has connection points (dry contacts) inside the unit.
Lighting Fixture—Field-installable lighting fixtures are available in two voltages, 120V and 277V. Light Fixture maybe attached to the bottom of the light panel to the left and right of the fan. Each fixture consists of housing, reflector, ballast and diffuser. Fixtures are compatible with standard 48" fluorescent tubes. Lamps are not included.
30
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
24-1/8"
(613mm)
72-1/4"
(1835mm)
BACK
LEFT SIDE OF XDO
FRONT OF XDO
Do Not Lift Here
Do Not Lift Here
FRONT OF XDO
RIGHT SIDE OF XDO
24-1/4"
(616mm)
3"
(76mm)
22-1/2"
(572mm)
Rear of XDO
Left Side
of XDO
72-1/4"
(1835mm)
24-1/8"
(613mm)
Front of XDO
Right Side of XDO
Figure 28 Dimensional data—Liebert XDO hard-piped units
Figure 29 Dimensional data—Liebert XDO with pre-charged option
31
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
DPN000771 Pg. 5 Rev. 3
7/8" (22mm) diameter mounting holes
7/8" (22mm) diameter mounting holes
1"
(25mm)
26-3/4"
(679mm)
26-3/4"
(679mm)
18-1/2"
(470mm)
FRONT OF XDO
TOP VIEW
REAR OF XDO
1"
(25mm)
Figure 30 Liebert XDO internal mounting location
32
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Mounting Hole
Mounting Hole
TOP OF XDO
FRONT OF XDO
Knockouts for High-Voltage Wiring
Knockouts for Low-Voltage Wiring
The low-voltage connection is present only if the Liebert XDO is equipped with the optional condensation detection system.
Figure 31 Liebert XDO top and front electrical access points

4.2 Liebert XDV Standard Features

• Micro Channel Heat Exchanger—The Liebert XDV unit includes one all-aluminum micro channel heat exchanger.
• Dual IEC Power Cords and Power Inlets—The Liebert 115V, 60Hz Liebert XDV unit is supplied with two detachable, 10 ft (3m) power cords that attach to two IEC power inlets in the rear of the unit. Each power cord has a NEMA 5-15P (IEC 320-C14) plug at the opposite end.
The Liebert 230V, 60/50 Hz Liebert XDV unit is supplied with two non-detachable 10 ft (3m) power cords.
This feature allows the unit to be powered by two separate power sources.
• Dual Air Inlets—The Liebert XDV unit can be configured to allow air to enter from the rear grille or the bottom of the unit.
• Dual Fans—Airflow is provided by two fans on the front of the unit. Dual switches—Controls on the front of the unit permit the use of one fan or both fans.
• Foundation Mounting—There are two 1/4-20 cage nuts located on the underside of unit which allow direct attachment to any Liebert Foundation cabinet, bolts provided with Liebert XDV unit.
• Mounting Clips for non-Liebert cabinets—The Liebert XDV unit is supplied with mounting clips that allow attachment to a non-Liebert cabinet (Some drilling maybe required).
33
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Rear
2-3/8"
(60.3mm)
2-5/8"
(66mm)
3/4"
(19mm)
3/4"
(19mm)
39-1/2"
(1003mm)
Depth, Top
Width
29-5/8"
(752mm)
18-5/8"
(473mm)
22-7/8"
(581mm)
14"
(355mm)
Unit Height
Piping Height
Depth, Bottom
DPN000770, Page 2 Rev. 2
Schrader Valve
Supply (In)
Return (Out)

4.2.1 Optional Features—Liebert XDV

Refrigerant Pre-Charge—Liebert XDV units with the pre-charged refrigerant option will have one-shot style fittings or removable couplings that contain pressurized refrigerant inside the Lie­bert XDV. The fittings ease connection to Liebert XD Piping and filling with refrigerant.
External Mounting Brackets—The Liebert XDV can be suspended from the overhead building structure. The external mounting brackets are ship-loose items.
Field-Installed Flexible Piping (for use with prefabricated piping assemblies)—Field-installed flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters). Con­nection style to the unit end may be straight or 90 degrees. Connection to the prefabricated piping assembly is with a threaded coupler. For information on acquiring the correct kit for your instal­lation, refer to DPN000781_Rev1, available from Liebert by calling 1-800-LIEBERT and from your local Emerson Network Power representative.
Condensate Detection—The Liebert XDV unit is available with factory-installed condensate detection. The condensate detection has connection points (dry contacts) at the external rear of the unit.
Figure 32 Liebert XDV dimensions
34
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Detail Area “A”
Detail “A”
Return Connection 5/8"
Supply Connection 1/2"
TOP VIEW OF LIEBERT XDV
Figure 33 Liebert XDV dimensions with one-shot connection
35
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
PRIMARY
POWER
SOURCE
SECONDARY
82 83
60Hz M ODELS ONLY .
FIELD WIRING
CONNECTIONS
AT TERMINAL STRIP
TO BE N.E.C. CLASS 2
USE SWI TCH
CONTACTS WITH 75 V.A.
MINIMUM
50Hz M ODELS ONLY .
FIELD WIRING
CONNECTIONS AT TERMINAL STRIP FOR SAFETY EXTRA
LOW VOLTAGE CIRCUITS
ONL Y. USE SWI TCH CONTACTS RATED
75 V.A. MINIMUM,
24 VOLTS A C
MAXIMUM.
1774241 P1 REV 1
1774241P1
Condensate Detection Dry Contacts – Low Voltage Connections
Knockout for Optional Wiring
Primary and Secondary Power Cords
Figure 34 Liebert XDV electrical connections for CE approved units
36
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Rear of XDV
Condensate Detection Dry Contacts – Low Voltage Connections
IEC Primary and Secondary Power Inlet
PRIMARY
POWER
SOURCE
SECONDARY
82 83
60Hz MODELS ONLY.
FIELD WI RING
CONNECTIONS
AT TERMINAL STRIP
TO BE N.E.C. CLASS 2
USE SWI TCH
CONTACTS WITH 75 V.A.
MINIMUM
50Hz MODELS ONLY.
FIELD WI RING
CONNECTIONS AT TERMINAL STRIP FOR SAFETY EXTRA
LOW VOLTA GE CIRCUITS
ONLY. USE SWITCH CONTACTS RATED
75 V.A. MINIMUM,
24 VOLTS AC
MAXIMUM.
1774241 P1 REV 1
1774241P1
Knockout for Optional Wiring
Rear of XDV
Right Side of XDV
Figure 35 Liebert XDV electrical connections for CSA-approved units
37
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Unistrut (field-supplied)
Bolt 3/8" -16; nut and washer provided in kit
Bolt a bracket to each corner of the XDV
3/8"-16 all-thread bolts, eld-supplied, typical
To prevent bypass air from recirculating through the XDV without it passing through the cabinet, this space between the hanging XDV and the cabinet must be blocked.
Hanging XDV unit
Figure 36 Suspending single Liebert XDV from Unistruts
Figure 37 Suspending single Liebert XDV from the roof structure
38
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Attach hanger brackets to each corner of each XDV. This arrangement permits mounting from either Unistruts or from overhead structure.
10 - 32 x 5/8" length; factory-supplied
10 - 32 x 5/8" length typical, 3; factory-supplied
1/4 - 20 x 5/8" length typical, 2; factory-supplied
Unistrut field-supplied upper XDV: 1 lower XDV: 2
Bolt 3/8"- 16, nut and washer factory-supplied
Figure 38 Alternative mounting methods—mounting multiple Liebert XDV units
39
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Liebert XDC
or
Liebert XDP
XD Cooling
Module *
XD Cooling
Module *
XD Cooling
Module *
XD Cooling
Module *
Pumped
Refrigerant
Liebert XDC
or
Liebert XDP
Supply Lines (2 per unit)
Return Lines (2 per unit)
Pumped
Refrigerant
* XD CoolFrame,
XDH, XDO or XDV

4.3 Liebert XDCF Standard Features

The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment without exhausting heat into the room.
Upper and lower modules may be mounted on the rear of an Egenera BladeFrame. Liebert XDCF modules use R-134a refrigerant. When attached to a fully loaded BladeFrame EX rack, each Liebert XDCF module has a nominal cooling capacity of 10kW (2.8 tons; 34,000 BTUh). Performance is based on:
• Entering fluid temperature—55°F (12.8°C) and
• Dew point—50°F (10°C) or lower.
Liebert XDCF modules consist of a sheet-metal frame, coil and filter dryer. It has no moving parts and needs no electricity.
The Liebert XDCF system (see Figure 39 below) consists of:
• Liebert XDCF modules—upper and lower models are available
• Flex pipe—connects Liebert XDCF units to supply and return piping
• Liebert XD Piping—delivers pumped R-134a refrigerant through flexible piping
• Liebert XDP or Liebert XDC—supplies R-134a refrigerant to Liebert XDCF modules (see Liebert XDP or Liebert XDC user manual for required chiller or drycooler)

Figure 39 Liebert XDCF hydraulic diagram

40
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
R-134a
RETURN
ONCE FLEX PIPE CONNECTIONS ARE MADE TO THE UNIT DO NOT DISASSEMBLE FROM THE UNIT. REMOVE CONNECTIONS FROM CEILING HEADERS BY TURNING THE SUPPLY VALVE TO THE OFF POSITION AND THEN TURNING THE RETURN VALVE TO THE OFF POSITION THE HEADER CONNECTIONS MAY BE REMOVED.
SUPPLY
1194311 P1
7-5/16"
(186mm)
1-7/16"
(37mm)
3-9/16"
(90mm)
TIGHTEN FLEX PIPE TO UNIT WITH THE SCHRADER VALVE IN TH IS P O S ITIO N
TIGHTEN FLEX PIPE TO UNIT WITH THE SCHRADER VALVE IN TH IS P O S ITIO N
13-7/16"
(341mm)
31-3/8"
(797mm)
EMERSON
NETWORK POWER
Liebert
XD
TM
3-9/16"
(90mm)
1-7/16" (37mm)
TM
BACK
TOP
RIGHT
SIDE
Upper unit shown;
both upper and
lower units have
same dimensions
Return Pipe
Piping is not load-bearing and should never be used to lift or move the Liebert XDCF

4.4 Liebert XDCF Mechanical Considerations

The Liebert XDCF is engineered to fit on the rear of the Egenera BladeFrame enclosure. Figure 40 illustrates the unit’s dimensions and the location of pipes. Figure 41 shows the attachment positions of each module.

Figure 40 Overall dimensions

41
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
!
Detail Area: A
(Lower Module
Mounting Area)
BladeFrame Power Modules
Detail Area: B
(Upper Module Mounting Area)
Enlarged Detail Area "A"
(Lower Module Mounting Area)
Captive nuts for right side mounting fasteners
Captive nuts for right side mounting fasteners
Enlarged Detail Area "B"
(Upper Module Mounting Area)
Locator stud for upper unit mounting angle
Locator stud for lower unit mounting angle
Egenera BladeFrame

4.5 Liebert XDCF Installation Considerations

No cutting or drilling is required to attach the modules to the rear of the Egenera BladeFrame cabi­net. All mounting holes, slots and pins required are fabricated at the factory.
Liebert XDCF modules attach beside the power modules on the rear of the Egenera BladeFrame (see Figure 41).

Figure 41 Liebert XDCF unit mounting locations

4.6 Liebert XDCF Piping Connection Methods and Points

The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination.
Supply piping connection is 1/2" OD copper pipe, and return piping connection is 5/8" OD copper. Both supply and return fittings are one-shot connections. These fittings contain pressurized R-134a refrig­erant inside the Liebert XDCF.
The Liebert XDCF has supply and return piping access on the top of each module.
WARNING
Risk of explosive discharge. Can cause death, injury and equipment damage. Do not disconnect one-shot connections after they have been connected. Disconnection will
release pressurized R-134a refrigerant from the Liebert XDCF.
42
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
1-7/16"
(37mm)
3-9/16"
(90mm)
7-5/16"
(186mm)
Supply Pipe
(1/2" diameter)
Return Pipe
(5/8" diameter)
Pipe locations and dimensions are the same for upper and lower units

4.6.1 Header System

The Liebert XDCF module system requires use of the Liebert XD prefabricated piping assembly. The prefabricated piping is compatible with the flex pipe required to attach to the Liebert XDCF modules.
Figure 42 Liebert XDCF supply and return piping access points

4.7 Liebert XDH Standard Features

Dual Refrigeration Circuits—Each Liebert XDH has two refrigeration circuits, one in the upper half of the unit and one in the lower half. Dual refrigeration circuits permit altering cooling levels in response to server room conditions. The dual refrigeration circuits permits interlaced connection of two refrigerant sources to enhance system reliability.
Dual Power Cords and Power Inlets—The Liebert XDH is supplied with two (2) detachable power cords 10 ft (3m) long that attach to two IEC power inlets on the rear of the unit. Each power cord has a NEMA 5-15P (IEC 320-C14) plug at the opposite end. The dual power cords allow the unit to be powered by two separate power sources. If the secondary power cord is con­nected to a UPS, the Liebert XDH unit fans will continue to operate if utility power fails.
Top Piping Access—The Liebert XDH has supply and return piping access on the top of each module. Supply piping connection is 1/2" OD copper pipe, and return piping connection is 7/8" OD copper.
Corner Stabilizers—A stabilizer in each corner permits rolling the Liebert XDH with greater ease and less chance of tipping.
Air Diffusers—Two diffusers, one on the upper half of the unit and one on the lower half, enhance flow of cooling air. Uni-directional and bi-directional diffusers are available.

4.7.1 Optional Features—Liebert XDH

Condensate Detection—A Liqui-tect moisture detection device and a contact-closure output are available as factory-installed options. These detect condensation in the Liebert XDH’s catch pan and connect to a monitoring or alarm system. A front panel alarm and indicator alert the user to condensation inside the unit.
Refrigerant Pre-Charge—Liebert XDH units with the pre-charged refrigerant option will have one-shot style fittings or removable couplings that contain pressurized refrigerant inside the Lie­bert XDH. The fittings ease connection to Liebert XD Piping and filling with refrigerant.
Field-Installed Flexible Piping (for use with prefabricated piping assemblies)—Field-installed flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters). Con­nection style to the unit end may be straight or 90 degrees. Connection to the prefabricated piping assembly is with a threaded coupler. For information on acquiring the correct kit for your instal­lation, refer to DPN000780, available by calling 1-800-LIEBERT and from your local Emerson Network Power representative.
43
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
78"
(1981mm)
42
(1067mm)
FRONT
FRONT
12" (305mm)
80"
(2032mm)
Top of Liebert XDH
Detail “A”
Rear of Liebert XDH
7/8" Return, Lower Refrigeration Circuit
7/8" Return, Upper Refrigeration Circuit
Detail "A"
6-1/16"
(154mm)
5"
(127mm)
Rear of XDH
DPN001180 Page 2, Rev. 0
4-1/8"
(105mm)
2-1/16"
(52mm)
3-11/16"
(94mm)
1-3/8"
(35mm)
1/2" Supply, Lower Refrigeration Circuit
1/2" Supply, Upper Refrigeration Circuit
Figure 43 Liebert XDH dimensions
Figure 44 Supply and return piping connections
44
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Return Main (seen from end ) 2-1/8" O.D. Or 2-5/8" O .D.
Supply Main (seen from end ) 1-1/8" O.D. or 1-3/8" O.D.
Recommended Arc
Acceptable A rc
1/2” Refrigerant -Grade Full-Port Ball Valve Fiel d-Supplied and
Fiel d Installed
Either 5/8” or 7/8" Refrigerant -Grade Full-Port Ball Valve Field-Supplied and Field Installed
Copper Tubing Total length of each li ne from XD cooling module (XDH, XDO, XDV) to Main; not to exceed 72" (1829 mm)
Return from Cooling Module
Supply to Cooling Module
Rear of XD Cooling Module
Top of XD Cooling Module
Refer to Table 5 for details.

4.7.2 Piping Connections to Liebert XDP or Liebert XDC

Piping Installation for Hard Piped System
The assembly and connection means for piping in the Liebert XD system are similar to those used for conventional refrigeration systems. All piping should be installed with high-temperature brazed joints. Soft solder is not recommended. During brazing, the lines must be filled with flowing dry nitro­gen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrigeration piping.
Follow all guidelines in 3.13 - Liebert XD Piping System Design and 3.14 - Liebert XD Piping Slope during installation.
Figure 45 Hard-pipe connection diagram for Liebert XDV, Liebert XDO and Liebert XDH cooling modules
45
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

4.8 Liebert XD Flex Pipe Kit

Flex Pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8,2.4 and 3 meters). Connection style to the unit end may be straight or 90 degrees. Connection to the prefab piping assembly is a threaded coupler. For data on acquiring the correct kit for your installation, see Table 17.

Table 17 Liebert XD Flex Pipe assemblies, supply and return

Liebert XD
Liebert XDV
CoolFrame
Liebert
XDO Liebert XDH
One-shot
Description
Couplings
4ft long (1.2m), 0º 186568G4 187867G4 186568G4
Removable
Couplings
One-shot
Couplings
One-shot
Couplings
2
186566G4 2 x 186566G4 2 x 187865G4
One-shot
Couplings
Removable
Couplings
4ft long (1.2m), 90º 186567G4 187866G4 - 186565G4 2 x 186565G4 2 x 187864G4
2
6ft long (1.8m), 0º 186568G1 187867G1 186568G1
186566G1 2 x 186566G1 2 x 187865G1
6ft long (1.8m), 90º 186567G1 187866G1 - 186565G1 2 x 186565G1 2 x 187864G1
3
8ft long (2.5m), 0º 186568G3 187867G3 186568G3
186566G3 2 x 186566G3 2 x 187865G3
8ft long (2.5m), 90º 186567G3 187866G3 - 186565G3 2 x 186565G3 2 x 187864G3
3
10ft long (10m), 0º 186568G2 187867G2 186568G2
186566G2 2 x 186566G2 2 x 187865G2
10ft long (10m), 90º 186567G2 187866G2 - 186565G2 2 x 186565G2 2 x 187864G2
Min Bend Radius, Supply
Min Bend Radius, Return
1. The minimum bend radius is for the flexible portion of the Liebert XD Flex Pipe. Because a section of hard pipe is at each end of the Liebert XD Flex Pipe, the minimum bend radius can be larger.
2. Top Module
3. Bottom Module
1
1
7" (178mm) 7" (178mm)
8" (203mm) 9" (229mm)
46
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
DPN000773 Page 1, Rev. 3
Return
Supply
Nominal
H
L
96"
(2438mm)
ODS
ODR
Ref. Typ.
Ref.
Typ.
48"
(1219mm)
Ref. Typ.
8-5/16"
(211mm)
24"
(610mm)

4.9 Liebert XD Piping Dimensions and Features

4.9.1 Piping Installation Method prefabricated headers

The assembly and connection means used for piping in the Liebert XD system are similar to those used for conventional refrigeration systems. All piping should be installed with high-temperature brazed joints. Soft solder is not recommended. During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrigeration piping.
Follow all guidelines in 3.13 - Liebert XD Piping System Design and 3.14 - Liebert XD Piping Slope during installation.
Figure 46 Two-port prefabricated piping for Liebert XD cooling modules
Table 18 Two-port prefabricated piping legend
Branch Piping Standard Run Long Run *
Two Port 185797G21 185800G21
Outside Diameter (ODS) 1-1/8 1-3/8
Supply inch (mm)
Return inch (mm)
* Pipe runs greater than 60 equivalent feet
Height (H) 8-3/4 (222) 8-3/4 (222) Length (L) 6-3/4 (171) 6-7/8 (175) Outside Diameter (ODR) 2-1/8 2-5/8 Height (H) 10-1/2 (267) 10-1/2 (267) Length (L) 8-3/4 (222) 9-1/8 (232)
47
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
DPN000773 Page 2, Rev. 3
Return
Supply
Nominal
H
L
96"
(2438mm)
ODS
ODR
48"
(1219mm)
Ref. Typ.
Ref.
Ref.
Ref.
Ref.
28-9/16"
(725mm)
28-9/16"
(725mm)
19-7/16"
(494mm)
19-7/16"
(494mm)
Figure 47 Four-port prefabricated piping for Liebert XD cooling modules
Table 19 Four-port prefabricated piping legend
Supply inch (mm)
Return inch (mm)
* Pipe runs greater than 60 equivalent feet
Branch Piping Standard Run Long Run *
Four Port 186551G21 186552G21
Outside Diameter (ODS) 1-1/8 1-3/8 Height (H) 8-3/4 (222) 8-3/4 (222) Length (L) 6-3/4 (171) 6-7/8 (175) Outside Diameter (ODR) 2-1/8 2-5/8 Height (H) 10-1/2 (267) 10-1/2 (267) Length (L) 8-3/4 (222) 9-1/8 (232)
48
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
DPN000773 Page 3, Rev. 3
Return
Supply
120"
(3048mm)
24" (610mm) Ref. Typ.
8-5/16"
(211mm) Ref. Typ.
4-5/8"
(117mm)
Nominal
ODR
ODS
H
L
Figure 48 Five-port prefabricated piping for Liebert XD cooling modules
Table 20 Five-port prefabricated piping legend
Branch Piping Standard Run Long Run *
Supply inch (mm)
Return inch (mm)
* Pipe runs greater than 60 equivalent feet
Five Port 185797G51 185800G51
Outside Diameter (ODS) 1-1/8 1-3/8 Height (H) 8-3/4 (222) 8-1/2 (216) Length (L) 6-3/4 (171) 7 (178) Outside Diameter (ODR) 2-1/8 2-5/8 Height (H) 10-1/2 (267) 10-1/2 (267) Length (L) 8-3/4 (222) 9-1/8 (232)
49
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
DPN000773 Page 4, Rev. 3
Return
Supply
H
L
ODS
ODR
Ref.
120"
(3048mm)
Ref. Typ.
Ref. Typ.
Ref. Typ.
Ref. Typ.
7-7/16"
(189mm)
7-7/16"
(189mm)
9-1/16"
(230mm)
16-9/16"
(421mm)
24"
(610mm)
Figure 49 Ten-port prefabricated piping for Liebert XD cooling modules
Table 21 Ten-port prefabricated piping legend
Supply inch (mm)
Return inch (mm)
* Pipe runs greater than 60 equivalent feet
Branch Piping Standard Run Long Run *
Ten Port 186650G51 186553G51
Outside Diameter (ODS) 1-1/8 1-3/8 Height (H) 8-3/4 (222) 8-3/4 (222) Length (L) 6-3/4 (171) 6-7/8 (175) Outside Diameter (ODR) 2-1/8 2-5/8 Height (H) 10-1/2 (267) 10-1/2 (267) Length (L) 8-3/4 (222) 9-1/8 (232)
50
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Unit Dimensional Data
Floor Cutout Dimensions
E
D
A
Overall
C
Side Panel
B
Overall
DPN000767 Pg. 2, Rev. 6
D
Unit Base
E
Unit Base
78"
(1981mm)
11"
(279mm)
5
"
(
1
2
7
m
m
)
1" (25mm)
5-1/2"
(140mm)
The shaded area indicates a recommended clearance of 36" (914mm) for component access.

4.10 Liebert XDP Standard Features

• Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed.
• Pumps—Centrifugal type, end suction, internally cooled, canned rotor design.
• Standard Control Processor—The standard control system is microprocessor-based with an exter­nal LCD numerical display to allow observation of specified adjustable functions. Operating con­ditions and status are indicated on the LCD panel, which is mounted either on the unit or on the wall, depending on application details (see user manual, SL-16641). The control system also mon­itors unit operation and activates an alarm when any of the specified factory preset conditions are exceeded.
• Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a protected enclosure for all high voltage components. Frame is con­structed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating system.

Figure 50 Liebert XDP dimensions

Table 22 Liebert XDP dimensions

Model
50/60Hz
Liebert
XDP160
* The dimension does not include the bezel of the disconnect switch.
Dimensional Data inches (mm) Shipping Weight, lb (kg)
A B C D E Domestic Export
38 (965) 34 (864) 33-1/8 (841) 33 (838) 36 (914) 990 (449) 1067 (484)
51
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Dimensions are approximate and subject to change without notice.
16-1/8"
(410mm)
17-1/4"
(438mm)
10" (254mm)
19"
(483mm)
A - Return From Cooling Modules
B - Supply to Cooling Modules
D - Chilled Water Return To Chilled Water Source
C - Chilled Water Supply From Chilled Water Source
* Allow 8" (204mm) clearance for filter replacement. ** To ensure ensure all refrigerant flow is filtered, install the filter dryer assembly between the discharge line of the XD P and the first bypass flow controller or the first cooling module.
DPN000767 Pg. 3, Rev. 6
Install replaceable filter dryer assembly in liquid supply line B.
To first cooling module or bypass flow controller **
* Orientation determined by installer.

Figure 51 Liebert XDP piping access points and external features

Table 23 Unit piping outlet connection sizes, inches, OD Cu

Model Pipe Connection Point
50/60 HZABCD
Liebert
XDP160
2-1/8 1-1/8 2-5/8 2-5/8
52
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Disconnect Switch
Status Lamps
User Interface
Front of Liebert XDP
Enclosure Cover Latch
Hazardous Voltage Enclosure Cover
Liebert XD Module Condensate Connections (optional; depends on features supplied with Liebert XD Module)
User Interface (Wall Box) Wiring
Temperature/Humidity Sensor Wiring
Alternate Knockout for Temperature/Humidity Sensor Wiring
Enclosure Cover Not Shown for Clarity

Figure 52 Front view of Liebert XDP and electrical enclosure

Figure 53 Liebert XDP electrical enclosure knockout locations for field wiring

53
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Customer Power Connection
Ground Lug
Disconnect Switch
Control Fuse Blocks
Power Block
Pump Fuse Blocks
Pump Contactors
Transformer 1
Transformer 2
Busbar
Customer Power Connection
Pump Circuit Breakers
Pump Contactors
Ground Lug
Disconnect Switch
Transformer 1
Power Block
Transformer 2
Fuse Blocks

Figure 54 Liebert XDP 60Hz high voltage connections

Figure 55 Liebert XDP 50Hz high voltage connections

54
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
C
D
B
Overall
5"
(127mm)
17"
(432mm)
1"
(25.4mm)
2"
(51mm)
78"
1981mm
A
Overall
Shaded areas indicate a recommended clearance of 34" (864mm) for component access.
D
Unit
Base
E
Unit Base
Unit Dimensional Data
Floor Cutout Dimensions
DPN000768 Page 2, Rev. 6
Recommended Minimum Hot Gas Supply & Liquid Return Piping Opening

4.11 Liebert XDC Standard Features

• Compressors—Scroll with a suction gas cooled motor, vibration isolators, thermal overloads, man­ual reset high-pressure switch and pump down low-pressure switch.
• Refrigeration System—Dual refrigeration circuits each including liquid line filter dryers, refriger­ant sight glass with moisture indicator, electronic control valve, adjustable externally equalized expansion valves and liquid line solenoid valves.
• Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed. PUMPS Centrifugal type, end suction, canned rotor design.
• Standard Control Processor—The standard control system is microprocessor-based with an exter­nal LCD numerical display to allow observation of specified adjustable functions. Normal operat­ing conditions are indicated on the LCD panel, which is mounted either on the unit or on the wall, depending on application details (see user manual, SL-16671). The control system also monitors unit operation and activates an alarm when any of the specified factory preset conditions are exceeded.
• Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a protected enclosure for all high voltage components. Frame is con­structed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating system.

4.11.1 Liebert XDC Optional Features

• Water / Glycol Condensers—A water/glycol floor stand condenser option is available for heat rejection requirements. The water/glycol floor stand can be located beneath the XDC unit or installed nearby.
Figure 56 Liebert XDC dimensional data
Table 24 Liebert XD Chiller dimensions, weight
Air Cooled
* Dimension does not include the bezel of the disconnect switch.
Model Dimensional Data, inches (mm) Shipping Weight, lb (kg)
50/60Hz A B C D E Domestic Export
Liebert
XDC160
74 (1880) 34 (864)
33-1/8
(841)
55
33 (838) 72 (1829) 1945 (882) 2093 (949)
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Install replaceable filter dryer assembly in liquid supply line G
** To first cooling module or bypass flow controller
Dimensions are approximate and subject to change without notice.
G - Supply to Cooling Units
F - Return From Cooling Units
B - Liquid Refrigerant Lines
* Allow 8" (204mm) of clearance for filter replacement
** To ensure all refrigerant flow is filtered, install the filter dryer assembly
between the discharge line of the XDC and the first bypass flow controller or the first cooling module.
A - Hot Gas Refrigerant Lines
* Orientation determined by installer.
23"
(584.2mm)
6" (152mm)
47"
(1193.8mm)
44"
(1117.6mm)
DPN000768 Page 3, Rev. 6
Figure 57 Liebert XDC piping locations
Table 25 Liebert XD Chiller piping connection sizes
Air Cooled Models Piping Outlet Connection Sizes, OD Cu, inches
50/60Hz A B C D E F G
Liebert XDC160 1-3/8 7/8 - - - 2-1/8 1-1/8
56
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Customer Water Supply
Customer Water Return
Customer Provided Piping
C - Hot Gas Refrigerant Lines
D - Liquid Refrigerant Lines
6"
(153mm)
B - Supply to Cooling Units
F - Cup Fitting
E - Threaded Female Connections
A - Return from Cooling Units
23"
(584mm)
47"
(1194mm)
44"
(1118mm)
Capillary Lines are 48" (1220mm) Limit Valve Distance from Condensers
DPN001419 Pg. 01, Rev. 01
Figure 58 Positioning a water/glycol Liebert XDC for placement on a floor stand
Table 26 Liebert XDC Water/Glycol Piping Connection Sizes
Model Piping Outlet Connection Sizes, OD Cu, inches
50/60Hz A B C D E* F**
XDC160 2-1/8 1-1/8 1-3/8 7/8 2-1/2 2-1/8 or 2-5/8
* Threaded Female Conection ** 2-1/8" for 1" WRV, 2-5/8" for 1-1/4" WRV
57
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Shaded areas indicate a recommended clearance of 36" (915mm) for component access and water/glycol piping.
TOP VIEW OF FLOOR STAND
LEFT SIDE OF CABINET
FLOOR STAND CONNECTIONS
33"
(838mm)
33" (838mm)
72"
(1828mm)
12-5/16"
(313mm)
26-15/16" (684mm)
2-1/4" - 5-1/4" (57 - 133 mm)
Liquid 1
Liquid 2
24" Nominal
(609mm)
20-1/4"
(514mm)
Circuit 1
Circuit 2
Inlet
Outlet
Hot Gas 1
Hot Gas 2
6-1/2"
(165mm)
10-1/2"
(267mm)
DPN001419 Pg. 2 , Rev. 01
Figure 59 Piping locations—floor stand and valve assembly
58
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Enclosure Cover Latch
Enclosure Cover Latch
Hazardous Vo lt age
Enclosure Cover
Hazardous Volta ge
EnclosureCover
Primary Disconnect Switch
Status Lamps
User Interface
Secondary
Disconnec t
Switch
PRIMARY
ELECTRICAL ENCLOSURE
PUMP SECTION
SECONDARY
ELECTRICAL ENCLOSURE
COMPRESSOR SECTION
Knockout for Input Power
Enclosure Cover Not Shown for Clarity
Figure 60 Front view of Liebert XDC and electrical enclosures
Figure 61 Liebert XDC electrical enclosure knockout locations for field wiring
59
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Transformer Fuse Block
Compressor Fuse Blocks
Customer Power Connection
Ground Lug
Primary Disconnect Switch
Primary Power Block
Electronic Hot Gas Bypass Controllers
Relay
Compressor Contactors
Transformer 3
Compressor Circuit Breakers
Compressor Contactors
Transformer 3
Wire Raceway
Relay
Ground Lug
Customer Power Connection
Primary Power Block
Primary Disconnect Switch
Electronic Hot Gas Bypass Controllers
Busbar
Figure 62 Liebert XDC high voltage connections—primary disconnect switch, 60Hz models
Figure 63 Liebert XDC high voltage connections—primary disconnect switch, 50Hz models
60
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Power Connection From Primary Power Block
Ground Lug
Secondary Disconnect Switch
Transformer Fuse Block
Secondary Power Block
Pump Circuit Breakers
Pump Contactors
Transformer 1
Transformer 2
Busbar
Power Connection From Primary Power Block
Pump Circuit Breakers
Pump Contactors
Ground Lug
Secondary Disconnect Switch
Transformer 1
Power Block
Transformer 2
Fuse Blocks
Figure 64 Liebert XDC high voltage connections—secondary disconnect switch, 60Hz models
Figure 65 Liebert XDC high voltage connections—secondary disconnect switch, 50Hz models
61
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Electrical handy box, factory-installed with cover
HEAT REJECTION ELECTRICAL CONNECTION POINTS Field-supplied 24V. Class 1 wiring to interlock heat rejection from pigtails: 70A and 71A - Compressor 1 circuit 70B and 71B - Compressor 2 circuit 70C and 71C - Dual Source relay (optional)
Liebert XD Module Condensate Connections (optional; depends on features supplied with Liebert XD Module)
User Interface (Wall Box) Wiring
Temperature/Humidity Sensor Wiring
Alternate Knockout for Temperature/Humidity Sensor Wiring
Enclosure Cover Not Shown for Clarity
Figure 66 Liebert XDC heat rejection electrical connection points
Figure 67 Liebert XDC electrical enclosure knockout locations for Extra Low Voltage connections
62
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
Control wiring must be Class 2 and installed in accordance with the National Electrical Code (NEC)
Requires shielded cable
Control Display Panel Four thermostatic wires to be connected toTB3
Temperature/Humidity Sensor Cable Provided with Temperature/Humidity Sensor Board
Factory-Wired Temperature Sensor(s)
TS-3
37 38
78
77
K3NCL
K3NO
K3COM
H2O (24)
XDOC (51)
RAD1 (50)
TS-4 TS-5 TS-6
Figure 68 Liebert XDC Extra Low Voltage field connections points
63

5.0 SPECIFICATIONS

Table 27 Liebert XDC160 specifications

XDC160 Water /
XDC160 Air
189192G3
Models
Cooling Capacity, tons (kW) 46 (160) 37 (130)
Minimum Load
Electrical Requirements
Input 460V-3ph-60Hz 380/415V-3ph-50Hz 460V-3ph-60Hz
Full Load Amps 79A
Minimum supply wire sizing ampacity 84A
Maximum fuse or circuit breaker size 100A
Dimensions, inches (mm)
Height - Main unit only 78 (1981)
Height - Main unit only, as shipped 83 (2108)
Width - Main unit 74 (1879)
Depth - Main unit 34-5/8 (879)
Height - Water / Glycol cooled condenser stand N/A 24 (607)
Width - Water / Glycol cooled condenser stand N/A 72 (1829)
Depth - Water / Glycol cooled condenser stand N/A 33 (839)
Weight, lb (kg)
Main unit only 1800 (817)
Main unit only, as shipped Domestic: 1945 (882); Export: 2093 (949)
Water / Glycol cooled condenser stand N/A 1075 (488)
Water / Glycol cooled condenser stand, as shipped N/A 1150 (521)
Pipe Connections, inches, O.D., Cu
Liebert XD Coolant supply to XD cooling modules 1-1/8
Liebert XD Coolant return from XD cooling modules 2-1/8
Liquid line, DX circuit 7/8
Hot gas line, DX circuit 1-3/8
Heat Rejection Equipment
95°F ambient air cooled condenser 1-CDL830 or 2-CSL415 N/A
Number of XD Cooling Units Connected, Maximum (Minimum)
Liebert XDCF10 16 (6)
Liebert XDH20 8 (4)
Liebert XDH32 5 (2)
Liebert XDO16 10 (4)
Liebert XDO20 8 (4)
Liebert XDV8 20 (8)
Liebert XDV10 16 (7)
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Maximum Ambient Operating Temperature °F(°C) 86 (30)
Agency
Approvals CSA CE CSA
XDC160AA XDC160AM
The Liebert XDC’s minimum recommended operating load is 40% of system nominal capacity. For example, a Liebert XDC160 60Hz system’s minimum load would be 64 kW. Loading below this value can unfavorably affect system operation. Consult factory for any loading below this recommendation.
189192G5
See Tables 28, 29
and 30 for
Water/Glycol
performance data
Specifications
Glycol
64

Table 28 Floor stand specifications—water-cooled Liebert XDC

Models - 60 Hz XDC160 Water Floor Stand - 60Hz
Entering Fluid Temp °F (C) 65 (18) 70 (21) 75 (24) 85 (29) 95 (35)
Performance Data
Cooling capacity, tons (kW) 46.1(162.3) 46.1(162.3) 46.1(162.3) 46.1(162.3) 44.5(156.5)
Flow, GPM 50 58 70 110 142
Pressure Drop, psi (Ft Water) 2.7 (6.2) 4.9 (11.3) 5.4 (12.5) 20.7 (47.8) 27.3 (63.1)
Heat Rejection Equipment
Water regulating valve size 1" 1" 1" 1" 1"
Piping Connections
Water / glycol supply and return lines 2-1/8" 2-1/8" 2-1/8" 2-1/8" 2-1/8"

Table 29 Floor stand specifications—Liebert XDC with 40% propylene glycol

Models - 60 Hz XDC160 Glycol Floor Stand - 60Hz - 40% PG
Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)
Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43)
Performance Data
Cooling capacity, tons (kW) 42.5 (149.4)
Total Heat Rejection, (kW) 192.6
Flow, GPM 206
Pressure Drop, psi (ft water) 37.2 (85.9)
Specifications
Heat Rejection Equipment
Drycooler DNT 940A 2 x DNT 880A*
Drycooler Pressure Drop, psi (ft water) 6.7 (15.5) 2.9 (6.6)
Glycol pump package - 10hp 9A31258G3
Pump Control Package - 208V 9A34606G47
Pump Control Package - 460V 9A32114G4
Pump Total Head @ 204 GPM, ft water 145
Water regulating valve size 1-1/4"
Piping Connections
Water / glycol supply and return lines 2-5/8"
* When multiple drycoolers are used ensure flow is balanced.
65

Table 30 Floor stand specifications—Liebert XDC with 40% ethylene glycol

Models - 60 Hz XDC160 Glycol Floor Stand - 60Hz - 40% EG
Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)
Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43)
Performance Data
Cooling capacity, tons (kW) 42.5 (149.4)
Total Heat Rejection, (kW) 192.6
Flow, GPM 204
Pressure Drop, psi (ft water) 35.9 (82.9)
Heat Rejection Equipment
Drycooler DNT 940A 2 x DNT 880A*
Drycooler Pressure Drop, psi (ft water) 6.5 (15.1) 2.7 (6.3)
Glycol pump package - 10HP 9A31258G3
Pump Control Package - 208V 9A34606G47
Pump Control Package - 460V 9A32114G4
Pump Total Head @ 204 GPM, ft water 145
Water regulating valve size 1-1/4"
Piping Connections
Water / glycol supply and return lines 2-5/8"
* When multiple drycoolers are used ensure flow is balanced.
Specifications
66

Table 31 Liebert XDP160 specifications

Models XDP160RC XDP160RA XDP160RM
160 kW / 46 Tons, 60Hz 140 kW / 40 Tons, 50Hz
Cooling Capacity, Nominal
Minimum Load
Electrical Requirements
Input 208V/3ph/60Hz 460V/3/ph60Hz 380/415V/3ph/50Hz
Full Load Amps 4A 2.1A 2.3A
Dimensions, inches (mm)
Height – Unit only 78 (1981)
Height – As shipped 83 (2108)
Width 38 (965)
Depth 34 (864)
Weight, lb (kg)
Unit only 821 (372)
Shipping weight Domestic: 990 (449); Export: 1067 (484)
Installed, with refrigerant and chilled
water
Pipe Connections
Refrigerant supply to Liebert XD
cooling module
Refrigerant return from Liebert XD
cooling module
Chilled water supply and return 2-5/8" OD, Cu
Control valve 2-way, 2" nominal; 35 PSIG close off pressure rating;
Pressure Drop – Chilled Water Side
Temperature Rise – Chilled Water Side at rated flow, °F (°C)
Number of Liebert XD cooling units connected, maximum (minimum
Liebert XDCF10 16 (4)
Liebert XDH20 8 (2)
Liebert XDH32 5 (1)
Liebert XDV8 20 (4)
Liebert XDV10 16 (4)
Liebert XDO16 10 (2)
Liebert XDO20 8 (2)
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Operating Ambient Temperature, Maximum, °F (°C)
Agency
Approvals CSA 60Hz CE 50Hz
Each capacity is based on 45ºF (7ºC) entering water temperature and 140gpm
(530lpm) water flow rate. Capacity is reduced when glycol mixtures are used in
place of 100% water.
The Liebert XDP’s minimum recommended operating load is 20% of system nominal capacity. For example, a Liebert XDP160 60Hz system’s minimum load would be 32 kW. Loading below this value can unfavorably affect system operation. Consult factory for any loading below this recommendation.
1038 (471)
1-1/8" OD, Cu
2-1/8" OD, Cu
150 PSIG maximum allowable pressure
20 psig (137kPa, 1.38bar), with 140 gpm (530lpm) water flow rate,
control valve fully open
8.0 (4.4) 6.9 (3.8)
86 (30)
Specifications
67
Specifications

Table 32 Liebert XDO16 specifications

XDO16BSP-0
XDO16BSPE0
XDO16DSP-0
XDO16DSPE0
XDO16BS--0
XDO16DS--0 XDO16BS-E0 XDO16DS-E0
(60Hz)
Models
XDO16BK--0
XDO16DK--0 XDO16BK-E0 XDO16DK-E0 XDO16BKP-0
XDO16BKPE0
XDO16DKP-0
XDO16DKPE0
(60Hz)
Cooling Capacity
Nominal (92°F [33°C] EAT): 17.2kW / 5 Tons
Maximum (90°F [32°C] EAT): 17.2 kW / 5 Tons
Conditions Capacity rating is @ 55°F (13°C) Entering Fluid Temperature and 50ºF or lower dew point
Electrical Requirements
Input Voltage 1ph-60Hz-120V 1ph-50 Hz-220-240V 1ph-50 Hz-230V
Input Power Connections Terminal blocks provided internal to unit
Full Load Amps 2.7A @ 120V 1.50 @ 230V 1.19 @ 230V
Wire Size Amps 3.4 2.0 1.28
Overcurrent Protection Device 15 15 15
Power consumption,
nominal, watts
335 250 250
Dimensions, inches (mm)
Length 72-1/4 (1835)
Width 24-1/8 (613)
Height 22-1/2 (572) not including electrical and piping access
Weight, lb (kg)
Unit only 150 (68)
Shipping weight 238 (108) 296 (134)
Installed, with refrigerant,
without options
155 (70)
Number of Fans 11
Airflow, Nominal, ft
3
/ hr)
(m
3
/ min
2700 (4587) 2250 (3822)
Audible Noise 85 dBa sound power 83 dBa sound power
Pipe Connections
from Liebert XDP/Liebert XDC
Refrigerant Supply
Refrigerant Return
to Liebert XDP/Liebert XDC
1/2" OD, Copper
7/8" OD, Copper
Serviceable Parts Fan and electrical components
Exterior Finish – Bottom, Sides, Front and Rear
Black, matte finish, heat-fused powder coat
Exterior Finish - Top Hot-dipped galvanized steel
Agency
Approvals CSA 60 Hz CSA 60Hz CE 50Hz
XDO16BSP-0
XDO16BSPE0
XDO16DSP-0
XDO16DSPE0
XDO16BS--0
XDO16DS--0 XDO16BS-E0 XDO16DS-E0
(50Hz)
Nominal (92°F [33°C] EAT): 17.1kW/4.9Tons Maximum (93°F [34°C]
EAT): 17.2 kW / 5 Tons
Options
Lighting Fixtures (ship loose) 2 Liebert XDOs per lighting unit; 120V or 277V; 4’ standard fluorescent tubes (not included)
Power, optional lighting fixture 0.9A per 120V light fixture; 0.4A per 277V light fixture None
Condensate sensing
(factory-installed)
Dry contact 24VAC - 1A maximum
68
Specifications

Table 33 Liebert XDO20 specifications

XDO20DK--*; XDO20BKP-*
XDO20DKP-*; XDO20BK-E*
Models
XDO20DK-E*; XDO20BKPE*
XDO20DKPE*
60Hz 60Hz 50Hz
Cooling Capacity
Conditions
Nominal (92°F [33°C] EAT): 20kW / 5.7 Tons
Maximum (100°F [38°C] EAT): 23kW / 6.5 Tons
Capacity rating is @ 55ºF (13°C) Entering Fluid Temperature and
50ºF (10°C) or lower dew point
Electrical Requirements
Input Voltage 1ph-60Hz-120V 1ph-60Hz-220-240V 1ph-50 Hz-220-240V
Input Power Connections Terminal blocks provided internal to unit
Full Load Amps 2.7A @ 120V 1.64A @ 230V 1.47 @ 230V
Wire Size Amps 3.4 2.0 1.84
Overcurrent Protection Device 15 15 15
Power consumption,
nominal, watts
335 350 250
Dimensions, inches (mm)
Length 72-1/4 (1835)
Width 24-1/8 (613)
Height 22-1/2 (572) not including electrical and piping access
Weight, lb (kg)
Unit only 150 (68)
Shipping weight 238 (108) 296 (134)
Installed, with refrigerant,
without options
Number of Fans 11
Airflow, Nominal, ft
3
(m
/ hr)
3
/ min
2700 (4587) 2250 (3822)
Audible Noise 85 dBa sound power 83 dBa sound power
Pipe Connections (without flex pipe)
from Liebert XDP/Liebert XDC
Refrigerant Supply
Refrigerant Return
to Liebert XDP/Liebert XDC
1/2" OD, Copper
7/8" OD, Copper
Serviceable Parts Fan and electrical components
Exterior Finish – Bottom, Sides, Front and Rear
Black matte finish, heat-fused powder coat
Exterior Finish - Top Hot-dipped galvanized steel
Agency
Approvals CSA 60 Hz CE 50Hz
Options
Lighting Fixtures (ship loose) 2 Liebert XDOs per lighting unit; 120V or 277V; 4’ standard fluorescent tubes (not included)
Power, optional lighting fixture
Condensate sensing
(factory-installed)
0.9A per 120V light fixture;
0.4A per 277V light fixture
Dry contact 24VAC - 1A maximum
Pre-Charged Refrigerant R-134a Refrigerant, one-shot connections
* = Revision level
XDO20BS--*; XDO20DS--*
XDO20BSP-*; XDO20DSP-v
XDO20BS-E*; XDO20DS-E*
XDO20BSPE*; XDO20DSPE*
Nominal (92°F [33°C] EAT):
17.7kW / 5 Tons
Maximum (103°F [39°C]
EAT): 23kW / 6.5 Tons
155 (70)
None
69

Table 34 Liebert XDO20 dimensions—domestic and export

Shipping Dimensions, inches (mm)
Model
All Models
* Includes piping connections
Length Width Height Length Width Height Length Width Height *
84
(2134)
30
(762)
30 (762)
83
(2108)
(762)

Table 35 Liebert XDO16 dimensions—domestic and export

Shipping Dimensions, inches (mm)
Model
All Models
* Includes piping connections
Length Width Height Length Width Height Length Width Height *
84
(2134)
30
(762)
30
(762)
83
(2108)
30
(762)
(762)
30
30
30 (762)
Unit Dimension
Unpacked, inches (mm)Domestic Export
72-1/4 (1835)
72-1/4
(1835)
24-1/8
(613)
Unit Dimension
Unpacked, inches (mm)Domestic Export
24-1/8
(613)
25-1/2
(648)
Specifications
25-1/2
(648)
70
Specifications

Table 36 Liebert XDV8 specifications

XDV8BK--*; XDV8DK--* XDV8BKP-*; XDV8DKP-* XDV8BK-E*; XDV8DK-E*
XDV8BKPE*;
XDV8DKPE* XDV8BKR-*; XDV8BKRE* XDV8DKR-*; XDV8DKRE*
Models
Cooling Capacity
Conditions
Maximum (95°F [35°C] EAT): 8.8kW / 2.5 Tons
60 Hz 60 Hz 50 Hz 50 Hz
Nominal (98°F [37°C] EAT): 8.8kW / 2.5 Tons
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and
50ºF (10ºC) or lower dew point, rear air inlet.
Electrical Requirements
Input 120V model: 1ph-60 Hz 230V model: 1ph-60 Hz 230V model: 1ph-50 Hz
Input power connections 2 power connections, each model
Full Load Amps 120V model: 2.0A 230V model: 1.0A
Power consumption,
nominal, watts
180 190 190 190
Dimensions, inches (mm)
Height – unit only 14 (355) not including pipe connections
Height – including pipe
connections
Width 22-7/8 (581)
Depth – Top 39-1/2 (1003)
Depth – Bottom 29-5/8 (752)
Weight, lb (kg)
Unit only 77 (35)
Shipping weight 125 (57)
Installed, with
refrigerant
Number of Fans 2222
Airflow, Nominal,
3
/ min (m3/ hr)
ft
1000 (1699) with rear inlet. Bottom inlet airflow may
be less, depending on restrictions inside cabinet
Audible noise 78 dBa sound power 73 dBa sound power
Pipe Connections (without Liebert Flex Pipe)
Refrigerant Supply
from Liebert
1/2" OD Cu, (optional 1/2" threaded coupler flex piping)
XDP/Liebert XDC
Refrigerant Return
to Liebert XDP/Liebert
5/8" OD Cu, (optional 3/4" threaded coupler flex piping)
XDC
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish
Black, matte finish, heat-fused powder coat
Options
Condensate sensing
(factory-installed)
Pre-Charged R-134a Refrigerant, one-shot connections
Agency
Approvals CSA 60Hz CSA 50Hz CE 50Hz
* = Revision level of unit
XDV8BT--*; XDV8DT--* XDV8BTP-*; XDV8DTP-* XDV8BT-E*; XDV8DT-E*
XDV8BTPE*; XDV8DTPE*
XDV8BTR-*; XDV8BTRE* XDV8DTR-*; XDV8DTRE*
Nominal (98°F [37°C] EAT): 8kW/ 2.3 Tons
Maximum (103°F [39°C] EAT): 8.8kW/2.5Tons
18-5/8 (473)
79 (36)
833 (1415) with rear inlet. Bottom inlet airflow
may be less, depending on restrictions inside
Dry contact outgoing signal
XDV8BS--*; XDV8DS--* XDV8BSP-*; XDV8DSP-* XDV8BS-E*; XDV8DS-E*
XDV8BSPE*; XDV8DSPE*
XDV8BSR-*; XDV8BSRE* XDV8DSR-*; XDV8DSRE*
cabinet
71
Specifications

Table 37 Liebert XDV10 specifications

XDV10BT--*; XDV10DT--* XDV10BTP-*; XDV10DTP-* XDV10BT-E*; XDV10DT-E*
XDV10BTPE*; XDV10DTPE*
XDV10BTR-*; XDV10BTRE* XDV10DTR-*; XDV10DTRE*
Nominal (98ºF [37ºC] EAT): 8kW / 2.3 Tons
Maximum (116ºF [47ºC] EAT): 11.8kW/3.4 Tons
Models
Cooling Capacity
Conditions
XDV10BK--*; XDV10DK--* XDV10BKP-*; XDV10DKP-* XDV10BK-E*; XDV10DK-E*
XDV10BKPE*; XDV10DKPE*
XDV10BKR-*; XDV10BKRE* XDV10DKR-*; XDV10DKRE*
60 Hz 60 Hz 50 Hz 50 Hz
Nominal (98ºF [37ºC] EAT): 10kW / 2.8 Tons
Maximum (106ºF [41ºC] EAT): 11.8kW/3.4 Tons
Capacity Rating is @ 55ºF (13ºC) Entering Fluid Temperature and
50ºF (10ºC) or lower dew point, rear air inlet.
Electrical Requirements
Input 120V model: 1ph-60 Hz
230V model:
1ph-60 Hz
Input power connections 2 power connections, each model
Full Load Amps 120V model: 2.0A 230V model: 1.0A
Power consumption,
nominal, watts
180 190 190 190
Dimensions, inches (mm)
Height – unit only 14 (355) not including pipe connections
Height – including hard
pipe connections
Height – including one-
shot connections
18-5/8 (473)
19-5/8 (498)
Width 22-7/8 (581)
Depth – Top 39-1/2 (1003)
Depth – Bottom 29-5/8 (752)
Weight, lb (kg)
Unit only 77 (35)
Shipping weight 125 (57)
Installed, with refrigerant 79 (36)
Number of fans 2222
Airflow, Nominal,
3
/ min (m3/ hr)
ft
1000 (1699) with rear inlet. Bottom inlet airflow
may be less, depending on restrictions inside
cabinet
833 (1415) with rear inlet. Bottom inlet airflow may be less, depending on restrictions inside
Audible noise 78 dBa sound power 73 dBa sound power
Pipe Connections (without Liebert Flex Pipe)
Refrigerant supply
from Liebert XDP/ XDC
Refrigerant return
to Liebert XDP/ XDC
1/2" OD, Cu, (optional 1/2" threaded coupler flex piping)
5/8" OD, Cu, (optional 3/4" threaded coupler flex piping)
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Options
Condensate sensing
(factory-installed)
Dry contact outgoing signal
Pre-Charged Refrigerant R-134a Refrigerant, one-shot connections
Agency
Approvals CSA 60Hz CSA 50Hz CE 50Hz
* = Revision level of unit
XDV10BS--*; XDV10DS--* XDV10BSP-*; XDV10DSP-* XDV10BS-E*; XDV10DS-E*
XDV10BSPE*; XDV10DSPE*
XDV10BSR-*; XDV10BSRE* XDV10DSR-*; XDV10DSRE*
230V model: 1ph-50 Hz
cabinet
72

Table 38 Liebert XDV8 dimensions—domestic and export

Unit Dimensions Unpacked
Length x Width x Height
inches (mm)
39-1/2 x 22-7/8 x 14
(1003 x 581 x 356)
Model
All Models
Shipping Dimensions
Length x Width x Height
inches (mm)
Domestic Export Unit Only
48 x 40 x 24-1/4 (1219 x 1016 x 616)
45-4/5 x 30-3/4 x 33
(1163 x 781 x 839mm)

Table 39 Liebert XDV10 dimensions—domestic and export

Model
All Models
Shipping Dimensions
Length x Width x Height
inches (mm)
Domestic Export Unit Only
48 x 40 x 24-1/4 (1219 x 1016 x 616)
45-4/5 x 30-3/4 x 33
(1163 x 781 x 839mm)
Unit Dimensions Unpacked
Length x Width x Height
inches (mm)
39-1/2 x 22-7/8 x 14
(1003 x 581 x 356)

Table 40 Liebert XDCF specifications

XD-CF-10-TP-0, XD-CF-10-TPE-0
Models
Cooling capacity, maximum 10kWH / 2.8 Tons / 34,000 BTUh
Conditions
Dimensions, inches (mm)
Height – including pipe connections 31-3/8" (797mm)
Width 13-7/16" (341mm)
Depth 7-5/16" (186mm)
Weight, lb (kg)
Unit only 18 (8.2)
Shipping weight 30 lb. (13.06 kg)
Pipe connections
Refrigerant Supply
from Liebert XDP/Liebert XDC
Refrigerant Return
to Liebert XDP/Liebert XDC
Cabinet exterior finish Gray
Agency
Safety CSA — CE
XD-CF Top EXP, XD-CF-10-BPE-0
XD-CF BTM EXP, XD-CF-10-BP-0
55°F (13°C) entering fluid temperature,
50°F (10°C) or lower dew point
1/2" threaded one-shot coupling on the unit
5/8" threaded one-shot coupling on the unit
Specifications
73

Table 41 Liebert XDH specifications

XDH32DKP-0
XDH32DK--0
XDH32BKP-0
XDH32BK--0
XDH32DKPE0
XDH32DK-E0
XDH32BKPE0
XDH32BK-E0
(60Hz)
point
80 (2032)
Models
Cooling Capacity
Conditions
Electrical Requirements
Input 120V-1ph-60Hz
Input Power Connections
Full Load Amps 5 10 2.5 5
Power Consumption,
Nominal, Watts
Dimensions, inches (mm)
Height—Unit Only 78 (1981)
Height—Including
Pipe Connections
Width 12 (305)
Depth 42 (1067)
Weight, lb (kg)
Unit Only 233 (106) 246 (112) 233 (106) 246 (112)
Shipping Weight 317 (144) 330 (150) 317 (144) 330 (150)
XDH20DKP-0
XDH20DK--0
XDH20BKP-0
XDH20BK--0
XDH20DKPE0
XDH20DK-E0
XDH20BKPE0
XDH20BK-E0
(60Hz)
XDH20, 60Hz Nominal (98ºF [37°C] EAT): 22kW/6.3 Tons XDH20, 60Hz Maximum(105ºF [40°C] EAT): 25.5kW/7.3 Tons
XDH20, 50Hz Nominal (98ºF [37°C] EAT): 19kW / 5.4 Tons XDH20, 50Hz Maximum(116ºF [47°C] EAT): 25.5kW/7.3 Tons
XDH32, 60Hz Nominal (98ºF [37°C] EAT): 30kW/8.5 Tons XDH32, 60Hz Maximum(105ºF [40°C] EAT): 34.5kW/7.3 Tons
XDH32, 50Hz Nominal (98ºF [37°C] EAT): 27kW / 7.7 Tons XDH32, 50Hz Maximum(108ºF [42°C] EAT): 34.5kW/7.3 Tons
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew
Two IEC320-C14 power inlets and two IEC
power cords with NEMA 5-15P connectors
600 1200 575 1150
Number of Fans
Airflow, Nominal,
3
ft
/min (m3/hr)
Audible Noise, Sound Power
Pipe Connections
Refrigerant Supply 1/2" OD, Cu (optional 1/2" threaded one-shot coupling on the unit)
Refrigerant Return 7/8" OD, Cu (optional 7/8" threaded one-shot coupling on the unit)
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Options
Agency
Approvals CSA 60Hz CE 50Hz, CSA 50/60Hz
2500 (4248) 4000 (6796) 2428 (4125) 3850 (6541)
81 dBa 86 dBa 81 dBa 86 dBa
Condensate Sensing (factory-installed)
Dry contact outgoing signal (24VAC - 1A maximum)
One-shot style flex pipe connections
Uni-directional or bi-directional air diffusers
XDH20DSP-0
XDH20DS--0
XDH20BSP-0
XDH20BS--0
XDH20DSPE0
XDH20DS-E0
XDH20BSPE0
XDH20BS-E0
(50/60Hz)
220-240V-1ph-50Hz, CE /
208-240V-1ph-60Hz, CSA
Two IEC320-C14 power inlets and two IEC
power cords with IEC320-C14 receptacles
6
Specifications
XDH32DSP-0
XDH32DS--0
XDH32BSP-0
XDH32BS--0
XDH32DSPE0
XDH32DS-E0
XDH32BSPE0
XDH32BS-E0
(50/60Hz)
74
Notes
Specifications
75
Specifications
76
Ensuring The High Availability 0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@emersonnetworkpower.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
SL-16655_REV08_06-08
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
AC Power Connectivity DC Power
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and ser vice marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Embedded Computing Embedded Power Power Switching & Controls Monitoring
Outside Plant
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
Loading...