Emerson Liebert XDP-W User Manual

Precision Cooling For Business-Critical Continuity
Water-Based Coolant Pumping Unit
Liebert XDP-W Water Pumping Unit
Liebert XDP-W Pumping Unit is part of the the highly energy-efficient, high
heat density Liebert XD cooling system, designed to support Liebert XDR-W
rackcooler, and Liebert XDK-W rack enclosure. Liebert XDP-W is an isolating
interface between the pumped water and the building chilled water system.
Liebert XDP-W may also be used with other brands of rack cooling equipment.
Flexibility:
Includes enclosure, pumps, heat exchanger, expansion tank, controls, valves and piping as a packaged unit for easy installation. Allows for scalability for future growth.
Offers 60 Hz and 50 Hz models.
Higher Availability:
Maintains the coolant at a temperature always above the actual dewpoint, to prevent condensation. Isolates the chilled water circuit from the XDK-W or XDR-W water circuit.
Lowest Total Cost of Ownership:
Operates with energy efficient redundant pumps. Uses floor space efficiently.
Ideally Suited For:
Liebert XDR-W and Liebert XDK-W systems. Other brands of water-cooled rack equipment.
Emerson Network Power.com
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
.
AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets Services Surge Protection
Liebert Corporation
1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800 877 9222 Phone (U.S. & Canada Only) 614 888 0246 Phone (Outside U.S.) 614 841 6022 FAX
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific 7/F., Dah Sing Financial Centre 108 Gloucester Rd, Wanchai Hong Kong 852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone 614 841 6755 (outside U.S.)
Specifications
BUILDING CHILLED
WATER
LOOP
HEAT
EXCHANGER
2-WAY VALVE CONTROLS SECONDARY FLUID ABOVE ROOM DEWPOINT
DUAL
PUMPS
Liebert XDP-W Coolant Distribution Unit
Nominal Capacity 100 kW
Input Voltage 460 V, 3 ph, 60 Hz
400 V, 3 ph, 50 Hz 208 V, 3 ph, 60 Hz
Full load amps 4.3A @ 400V
2.5A @ 460V
Height, unit only 78” (1981 mm)
Width 38” (965 mm)
Depth 35” (889 mm)
Weight, unit only 750 lbs (340 kg)
Liebert XDP-W units supporting Liebert XDR-W units
Hydraulic Schematic
XDP-W
Low pressure water circuit with a fluid temperature always above the actual dewpoint, to prevent condensation.
XDR-W modules or XDK-W enclosures
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2007 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.