Emerson Liebert TYPE SS User Manual

Surge Protection For Business-Critical Continuity
Liebert TYPE SS Transient Voltage Surge Suppression
Advanced Hybrid Surge Suppression Technology
Approved by Motorola R56 2005 Version, Standards and
Guidelines for Communication Sites — Type 1, Type 2 Devices
Utilizes advanced SAD/MOV array technology for industry leading transient suppression voltages
Modular design for flexibility and ease of servicing 160 kA surge current capacity for increased reliability Real-time system monitoring Product performance and safety standards — UL1283, UL 1449 Second Edition 2005, (effective Feb. 9, 2007), C22.2 No. 8 Bulletin 516 and NEMA LS1-1992
Two Different Units Available:
Type 1 Hybrid TVSS — 20 kA of SAD protection and 160 kA of MOV protection Type 2 MOV only TVSS — 160 kA of MOV protection
Warranty:
Covered 24x7 by Emerson Network Power Service
siness: 10-Years for Parts, 5-Years On-Site Labor
Bu
Typical Applications:
s
e
ll Sit
e
C Communication shelters AC main and distribution panels and load centers
rs
e
ansmitt
r
T Base Stations
Emerson Network Power.com
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
.
AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services
Surge Protection
Liebert Corporation
1050
Dearborn Drive
P.O.
Box 29186
Col
umbus, Ohio 43229
800 877 9222
Phone (U.S. &
Canada Onl
y)
614 888 0246
Phone (Outside U.S.)
614 841 6022
FAX
Via
Leonardo Da Vinci 8
Zona
Industriale Tognana
35028
Piove Di Sacco (PD)
Ital
y
39 049 971
9 111 Phone
39 049 584
1 257 FAX
Emerson Network Power Asia Pacific 7/F., Dah Sing Financial Centre 108 G
loucester Rd, Wanchai
Hong
Kong 852 25722201 Phone 852 28029250 FAX
liebert.com
Technical Support
800 288 6169 Toll-Free 607 724 2484 Phone 607 722 8713 Fax
Liebert TYPE SS Transient Voltage Surge Suppression
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0 0 5000 10000 15000 20000 25000 300
00
8/20 µs Surge Current (Amperes)
Surge Current (%)
SAD Module
MOV Module
MOV/SAD Current Sharing – Type 1 Model
The Liebert Answer:
The Liebert TYPE SS Type I Model offers a true, coordinated multi-stage system of suppression. It integrates the fast response time of the silicon avalanche diode (SAD) with the high­energy capability of the metal oxide varistor (MOV) for increased reliability and performance. This unique circuitry does not sacrifice the sensitive SAD module when subjected to a damaging high-energy transient event.
Technical Specifications
Voltage Configurations 120/240V and 120/208V
Maximum Continuous ≥125% Operating Voltage (MCOV)
Fault Current Rating (AIC) 200 kAIC
Operating Frequency Range 47 – 63 Hz
Connection Parallel (4-6 AWG recommended and 14-1/0 AWG capable); wire lug or disconnect
Modes of Protection Line to Neutral/standard
Surge Current Capacity 160 kA per mode
Response Time <0.5 nanoseconds
Dimensions 15.32 in. x 13.32 in. x 6.60 in.
Weight 35 lbs.
Operating Temperature -40°C to +60°C
Status Indication LEDs, Form “C” contacts — 2 sets
Form “C” Contact Rating 120 VAC, 5.0 amps, pF of 1.0
Certifications Product performance and safety standards — UL 1283, UL 1449 Second Edition 2005,
hnology Type 1 Hybrid TVSS — 20 kA of SAD protection and 160 kA of MOV protection
ec
T
e NEMA 4X; suitable for indoor or outdoor applications
sur
lo
Enc
Warranty Covered 24x7 by Emerson Network Power Service Business 10-Years Parts and 5-Years
Typical NEMA LS1 Data
Category A Ringwave 176 284 (6 kV / 0.2 kA)
Category B Ringwave 288 304 (6 kV / 0.5 kA)
UL 1449 Combination Wave 256 300 (6 kV / 0.5 kA)
Category B Combination 304 336
e (6 kV / 3.0 kA)
v
a
W
Category C Combination 440 408 Wave (20 kV / 10.0 kA)
lease consult factory for additional voltage configurations)
(P
(effective Feb. 9, 2007), C22.2 No.8 Bulletin 516, NEMA LS1-1992
Type 2 MOV only TVSS — 160 kA of MOV protection
On-Site Labor
Type 1 Unit; Type 2 Unit;
Line - Neutral Line - Neutral
120/208V & 120/240V 120/208V & 120/240V
lamping Voltage (Vpk) Clamping Voltage (Vpk)
C
y precaution has been taken to ensure accuracy and
r
e
v
e e
l
Whi
t
e
pl
om
c
esponsibility, and disclaims all liability for damages resulting
r
s
om u
r
f
© 2007 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
f their respective owners.
o
® Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-22090 (R05/07) Printed in USA
erature, Liebert Corporation assumes no
s in this lit
s
ne
e
f this information or for any errors or omissions.
e o
usiness-Critical Continuity
B
d the Eme
r an
e
w
o
P trademarks and service marks of Emerson Electric Co. ©2007 Emerson Electric Co.
rson Network
, Eme
rson Network Power logo are
Loading...