Emerson Liebert GXT MT+LB 10KL, Liebert GXT MT+LB 10K User Manual

Single Phase Online UPS
Liebert GXT MT+LB 10kVA UPS User Manual
1
Please comply with all warnings and operating
instructions in this manual strictly. Save this
manual properly and read carefully the following
instructions before installing the unit. Do not
operate this unit before reading through all safety
information and operating instructions carefully.
2
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS ................................................................................................. 3
1-1. T
RANSPORTATION AND STORAGE
.......................................................................................................... 3
1-2. P
REPARATION
................................................................................................................................. 3
1-3. I
NSTALLATION
................................................................................................................................. 3
1-4. O
PERATION
.................................................................................................................................... 4
1-5. S
TANDARDS
.................................................................................................................................... 4
2. INSTALLATION AND OPERATION .................................................................................................. 5
2-1. U
NPACKING AND INSPECTION
............................................................................................................... 5
2-2. R
EAR PANEL VIEW
............................................................................................................................ 5
2-3. S
INGLE
UPS I
NSTALLATION
................................................................................................................. 7
2-4. I
NSTALLATION FOR HOT STANDBY
.......................................................................................................... 9
2-5. S
OFTWARE INSTALLATION
................................................................................................................... 9
3. OPERATIONS ................................................................................................................................ 10
3-1. B
UTTON OPERATION
....................................................................................................................... 10
3-2. LED I
NDICATORS AND
LCD P
ANEL
...................................................................................................... 10
3-3. A
UDIBLE ALARM
............................................................................................................................ 12
3-4. S
INGLE
UPS O
PERATION
.................................................................................................................. 12
3-5. A
BBREVIATION MEANING IN
LCD D
ISPLAY
............................................................................................. 16
3-6. LCD D
ISPLAY
............................................................................................................................... 16
3-7. O
PERATING MODE/STATUS DESCRIPTION
.............................................................................................. 23
3-8. F
AULT CODE
................................................................................................................................. 24
3-9. W
ARNING INDICATOR
...................................................................................................................... 24
4. TROUBLE SHOOTING ................................................................................................................... 25
5. STORAGE AND MAINTENANCE ..................................................................................................... 27
5-1. S
TORAGE
..................................................................................................................................... 27
5-2. M
AINTENANCE
.............................................................................................................................. 27
6. SPECIFICATIONS ......................................................................................................................... 28
3
1. Safety and EMC instructions
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1-1. Transportation and Storage
Please transport the UPS system only in the original package to protect against shock and impact.
The UPS must be stored in the room where it is ventilated and dry.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment)) to the UPS output sockets or terminal.
Place cables in such a way that no one can step on or trip over them.
Do not block air vents in the housing of UPS. The UPS must be installed in a location with good ventilation. Ensure enough space on each side for ventilation.
UPS has provided earthed terminal, in the final installed system configuration, equipotential earth bonding to the external UPS battery cabinets.
The UPS can be installed only by qualified maintenance personnel.
An appropriate disconnect device as short-circuit backup protection should be provided in the building wiring installation.
An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation.
Connect the earth before connecting to the building wiring terminal.
Installation and Wiring must be performed in accordance with the local electrical laws and regulations.
4
1-4. Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by any individuals with no previous experience.
1-5. Standards
* Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2 Category C3
Radiated Emission..................................:IEC/EN 62040-2 Category C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2 Level 4
RS........................................................ ...:IEC/EN 61000-4-3 Level 3
EFT......................................................... :IEC/EN 61000-4-4 Level 4
SURGE................................................... :IEC/EN 61000-4-5 Level 4
CS........................................................... :IEC/EN 61000-4-6 Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8 Level 3
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the second environment-installation restrictions or additional measures may be needed to prevent disturbances.
5
2. Installation and Operation
There are two different types of online UPS: standard and long-run models. Please refer to the following model table.
Model Type Model Type
10K Standard Model 10KL Long Model
2-1. Unpacking and Inspection
Unpack the package and check the package contents. The shipping package contains:
● One UPS
● One user manual
● One monitoring software CD
● One RS-232 cable (option)
● One USB cable
● One battery cable (option)
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts. Please keep the original package in a safe place for future use.
2-2. Rear Panel View
Diagram1: 6K/10K Rear Panel
6
13
Diagram 2: 6KL/10KL Rear Panel Diagram 3: 6K(L)/10K(L) Input/Output Terminal
1. External battery connector
2. RS-232 communication port
3. Intelligent slot
4. USB communication
5. Emergency power off function connector (EPO connector)
6. Cooling fan
7. Input circuit breaker
8. Input/Output terminal (Refer to Diagram 3 for the details)
9. Maintenance bypass switch
10. Output terminal
11. Grounding terminal
12. Hot standby terminals (BPS/L0)
13. Utility input terminal
7
2-3. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following instructions by professional personnel.
1) Make sure the mains wire and breakers in the building are in compliance with the standard of rated capacity of UPS to avoid the hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
Wiring spec (AWG)
Input Output Battery Ground
10K 8 8 8
10KL 8 8 8 8
NOTE 1: The cable for 6K/6KL should be able to withstand over 50A current. It is recommended to use 10AWG or thicker wire for safety and efficiency.
NOTE 2: The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to use 8AWG or thicker wire for safety and efficiency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and regulations.
5) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire disconnection!)
In put Neu tral
In put L in e
L0
Bp s
Output Li ne
Output Ne utral
Gr oun d
Terminal Block wiring diagram for 6K(L)/10K(L)
NOTE 1: Make sure that the wires are connected tightly with the terminals.
NOTE 2: Please install the output breaker between the output terminal and the load, and the breaker should be
qualified with leakage current protective function if necessary.
NOTE 3: For single operation, the terminals of “BPS” andL0” must be shorted.
6) Put the terminal block cover back to the rear panel of the UPS.
8
Warning: (Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection.
● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal battery to the external battery. The battery type and voltage and numbers may be different. If you connect them together, it maybe causes the hazard of electric shock or fire!
Warning: (Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
Warning:
● For standard battery pack, there are one DC breaker to disconnect the battery pack and the UPS. But for other external battery pack, make sure a DC breaker or other protection device between UPS and external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the numbers of the battery pack, please make sure you modify the setting simultaneously. The connection with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
● Pay highly attention to the polarity marking on external battery terminal block, and make sure the correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The current spec, color, position, connection and conductance reliability of wire should be checked carefully.
● Make sure the utility input & output wiring is correct. The current spec, color, position, connection and conductance reliability of wire should be checked carefully. Make sure the L/N terminal is correct, not reverse or short-circuited.
9
2-4. Installation for hot standby
If the hot standby function is not used, you may skip this section.
1) Disconnect the jumper wire between the terminals of “BPS” and “L0” on the host UPS.
2) Keep the jumper wire between the terminals of “BPS” and “L0” on the standby UPS.
3) Connect the “L1” of the standby UPS to the “BPS” of the host UPS.
4) Connect the “Output N” of the standby UPS to the “Output N” of the host UPS.
BPS
L0
GND
BPSL0GN D
Standby UPS
Host UPS
Output
Input
NOTE: Each UPS must be connected to an independent battery pack.
2-5. Software Installation
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
10
3. Operations
3-1. Button Operation
Button Function
ON/Enter Button
Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS. Enter Key: Press this button to confirm the selection in setting menu.
OFF/ESC Button
Turn off the UPS: Press and hold the button more than 0.5s to turn off the UPS. Esc key: Press this button to return to last menu in setting menu.
Test/Up Button
Battery test: Press and hold the button more than 2s to test the battery while in
AC mode, or CVCF mode.
UP key: Press this button to display next menu.
Mute/Down Button
Mute the alarm: Press and hold the button more than 2s to mute the buzzer.
Please refer to section 3-4-9 for details.
Down key: Press this button to display previous selection.
Test/Up +
Mute/Down Button
Press and hold the two buttons simultaneous more than 1s to enter/escape the
setting menu.
* CVCF mode means converter mode.
3-2. LED Indicators and LCD Panel
LED Indicators:
There are 4 LEDs on front panel to show the UPS working status:
Mode LED Bypass Line Battery Fault
UPS Startup
Bypass mode
AC mode
Battery mode
CVCF mode
Battery Test
Fault
Note: ● means LED is lighting, and ○ means LED is faded.
Note2: If bypass LED flashes in bypass mode, it Indicates that the UPS output is cut off.
LCD panel
LED indicators
11
LCD Panel:
Display Function
Backup time information
Indicates the backup time in pie chart.
Indicates the backup time in numbers. H: hours, M: minute, S: second
Setting operation
Indicates the setting operation.
Fault & warning information
Indicates that the warning situation occurs.
Indicates the warning and fault codes, and the codes are listed in details in “Faults Reference Code” and “warning Reference Code” sections.
Mute operation
Indicates that the UPS alarm is disabled.
UPS information
Indicates the input and output voltage, frequency, battery voltage, load information, and internal temperature.
Vac: input/output voltage, Vdc: battery voltage, Hz: frequency, %: load level, °C/°F: temperature,
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
Mode operation information
Indicates the UPS is in online mode.
Indicates the UPS is in battery mode.
Indicates the UPS is bypass mode.
Indicates the UPS is in converter mode.
12
Indicates the UPS is charging battery.
Battery information
Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
3-3. Audible Alarm
Description
Buzzer status
Muted
UPS status
Bypass mode
Beep
ing once every
2 minutes
Yes
Battery mode
Beep
ing once every
4 seconds
Fault mode
Beeping continu
ou
sly
Warning
Overload
Beep
ing twice every second
No
Low
b
attery
Beeping once every second
Battery unconnected
Over
c
harge
EPO enable
Fan failure
/Over
temp
erature
Charger failure
IP fuse
broken
Over
l
oad 3
times in 30min
Cover of m
aintain switch is open
Fault
Bus start failure
Beeping continuously
Yes
Bus over
Bus under
Bus unbalance
Inverter soft start failure
High Inverter voltage
Low Inverter voltage
Inverter output short circuited
Negative power fa
ult
Battery SCR short
circuited
Inver
ter relay short
circuited
Over temperature
CPU communication
failure
Overload
Charger short
3-4. Single UPS Operation
1. Turn on the UPS with utility power supply (in AC mode)
1) After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the step only available for long-run model). Then set the input breaker at “ON” position. At this time the fan is
13
running and the UPS supplies power to the loads via the bypass. The UPS is operating in Bypass mode.
NOTE: When UPS is in Bypass mode, the output voltage will directly power from utility after you switch on
the input breaker. In Bypass mode, the load is not protected by UPS. To protect your precious devices, you should turn on the UPS. Refer to next step.
2) Press and hold the “ON” button for 0.5s to turn on the UPS and the buzzer will beep once.
3) A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will operate in Battery mode without interruption.
NOTE: When the UPS is running out battery, it will shut down automatically at Battery mode. When the utility power is restored, the UPS will auto restart in AC mode.
2. Turn on the UPS without utility power supply (in Battery mode)
1) Make sure that the breaker of the battery pack is at “ON” position (only for long-run model).
2) Press and hold the “ON” button for 0.5s to turn on the UPS, and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter to Battery mode.
3. Connect devices to UPS
After the UPS is turned on, you can connect devices to the UPS.
1) Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total load level.
2) If it is necessary to connect the inductive loads such as a printer, the in-rush current should be calculated carefully to see if it meets the capacity of the UPS, because the power consumption of this kind of loads is too big.
3) If the UPS is overload, the buzzer will beep twice every second.
4) When the UPS is overload, please remove some loads immediately. It is recommended to have the total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system safety.
5) If the overload time is over acceptable time listed in spec at AC mode, the UPS will automatically transfer to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is over acceptable time listed in spec at Battery mode, the UPS will become fault status. At this time, if bypass is enabled, the UPS will power to the load via bypass. If bypass function is disabled or the input power is not within bypass acceptable range, it will cut off output directly.
4. Charge the batteries
1) After the UPS is connected to the utility power, the charger will charge the batteries automatically except in Battery mode or during battery self-test.
2) Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter than expected time.
3) Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for detailed setting) is consistent to real connection.
4) The charging current can be changed from 0.5A to 6A via LCD or software. Please make sure that the charging current is suitable to battery specification.
14
5. Battery mode operation
1) When the UPS is in Battery mode, the buzzer will beep according to different battery capacity. If the battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery voltage drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that the battery is at low level and the UPS will shut down automatically soon. Users could switch off some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no more load to be switched off at that time, you have to shut down all loads as soon as possible to protect the devices or save data. Otherwise, there is a risk of data loss or load failure.
2) In Battery mode, if buzzer sound annoys, users can press the Mute button to disable the buzzer.
3) The backup time of the long-run model depends on the external battery capacity.
4) The backup time may vary from different environment temperature and load type.
5) When setting backup time for 16.5 hours (default value from LCD panel), after discharging 16.5 hours, UPS will shut down automatically to protect the battery. This battery discharge protection can be enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section)
6. Test the batteries
1) If you need to check the battery status when the UPS is running in AC mode/CVCF mode, you could press the “Test” button to let the UPS do battery self-test.
2) To keep the system reliable, the UPS will perform the battery self-test automatically periodically. The default setting period is once per week.
3) Users also can set battery self-test through monitoring software.
4) If the UPS is at battery self-test, the LCD display and buzzer indication will be the same as at Battery mode except that the battery LED is flashing.
7. Turn off the UPS with utility power supply in AC mode
1) Turn off the inverter of the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once. The UPS will turn into Bypass mode.
NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from utility power to output sockets and terminal even though you have turned off the UPS (inverter).
NOTE 2: After turning off the UPS, please be aware that the UPS is working at Bypass mode and there is risk of power loss for connected devices.
2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the input breaker. A few seconds later, there is no display shown on the display panel and UPS is complete off.
8. Turn off the UPS without utility power supply in Battery mode
1) Turn off the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once.
2) Then UPS will cut off power to output and there is no display shown on the display panel.
9. Mute the buzzer
1) To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the buzzer is muted, the buzzer will beep again.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the details.
15
10. Operation in warning status
1) When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems for UPS operation. Users can get the fault code from LCD panel. Please check the trouble shooting table in chapter 4 for details.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the details.
11. Operation in Fault mode
1) When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the UPS. Users can get the fault code from display panel. Please check the trouble shooting table in chapter 4 for details.
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try to turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact the distributor or service people immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output immediately to avoid more risk or danger.
12. Operation of changing battery numbers
1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3) Switch off the input breaker, and switch off the battery breaker (only available for long-run model), or disconnect battery wire for standard model.
4) Remove the cabinet cover, and then modify the jumpers (JP1, JS3) on the control board to set the battery numbers as following table:
Battery Number
JP1
JS3
pin1 & pin2 pin3 & pin4 Pin5 & pin6 pin7 & pin8
16 X X 0 0 0
17 X X 1 1 0
18 X X 0 0 1
19 X X 1 0 1
20 X X 1 1 1
Note1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.
5) Modify the battery pack for the setting number carefully. After complete it, put the cover back, and switch on the battery breaker for long-run model.
6) Switch on the input breaker and the UPS will enter Bypass mode. If the UPS is in maintenance Bypass mode, turn the maintenance switch to “UPS” position and then turn on the UPS.
16
3-5. Abbreviation Meaning in LCD Display
Abbreviation Display content Meaning
ENA
Enable
DIS
Disable
ATO
Auto
ON
On
OFF
Off
FBD
Not allowed
OPN
Allow
3-6. LCD Display
3-6-1. LCD Main Interface
A. Single model: Press up and down key to select the displayed information.
1 Output Voltage
2 Output Frequency
3 Battery Voltage
4 Load Level
5 Environmental Temperature
6 Input Voltage
7 Input Frequency
17
3-6-2. LCD Setting
At the main interface; press and hold the “up” and “down” buttons simultaneous for more than 1 second to enter
or escape from setting menu.
There are two parameters to set up the UPS. Refer to following diagram.
Parameter 1: It’s for program alternatives. Refer to below table for the details.
Parameter 2: Setting options or values for each program.
11 programs available list for parameter 1:
Code Description Bypass AC CVCF Battery
Battery
Test
01 Output voltage Y
02 CVCF mode enable/disable Y
03 Output frequency Y
04 Bypass mode open/forbidden Y Y
05 Bypass mode enable/disable Y Y
06 Battery backup time setting Y Y Y Y Y
07 Hot standby function enable/disable Y Y Y Y Y
08 Voltage range for bypass –low loss Y
09 Voltage range for bypass –high loss Y
10 Frequency range for bypass –low loss Y
11 Frequency range for bypass –high loss Y
12 Battery voltage Calibration Y Y Y Y Y
13
Charger voltage adjustment
Y Y Y Y Y
14
Inverter voltage Calibration
Y Y Y
15 Charger maximum current setting Y Y Y Y Y
16 Battery capacity setting Y Y Y Y Y
17 Battery groups setting Y Y Y Y Y
18 Backup time calibration Y Y Y Y Y
*Y means that this program can be set in this mode.
18
01: Output voltage
Inter
face Setting
Parameter
2
: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac 220: Presents output voltage is 220Vac 230: Presents output voltage is 230Vac 240: Presents output voltage is 240Vac
02: Frequency Converter enable/disable
Interface
Setting
Parameter
2
: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You may choose following two options in parameter 3: ENA: Setting UPS to CVCF mode. If selected, the output frequency will be fixed at 50Hz or 60Hz according to “Output frequency setting”. The input frequency could be from 46Hz to 64Hz. DIS: Setting UPS to normal mode (not CVCF mode). If selected, the output frequency will synchronize with the input frequency within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to setting in “Output frequency setting”. If 50 Hz is selected in “Output frequency setting”, UPS will transfer to battery mode when input frequency is not within 46~54 Hz. If 60 Hz is selected in “Output frequency setting”, UPS will transfer to battery mode when input frequency is not within 56~64 Hz.
03: Output frequency setting
Interface
Setting
Parameter 2: Output Frequency
50.0Hz: The output frequency is setting for 50.0Hz.
60.0Hz: The output frequency is setting for 60.0Hz. ATO: If selected, output frequency will be changed based on the
latest input utility frequency. If it is within 46Hz and 54Hz, the output frequency will be 50.0Hz. If it is within 56Hz and 64Hz, the output frequency will be 60.0Hz. ATO is default setting.
If converter mode is enabled and output frequency is set to ATO mode, it will display “A50” when UPS is working on 50Hz mode or “A60” when UPS is working on 60Hz mode in LCD.
04: Bypass mode forbidden/allowed
19
Interface
Setting
Parameter 2:
Allow or forbidden bypass mode FBD: Bypass not allowed. When selected, it’s not allowed for running in Bypass mode under any situations. OPN: Bypass allowed. When selected, UPS will run at Bypass mode depending on the setting of “Switch off Bypass mode enable/disable”.
05: Manual bypass enable/disable
Interface
Setting
Parameter 2:
ENA: Bypass enabled. When selected, bypass mode is activated.
DIS: Manual bypass disabled. When selected, automatic bypass is acceptable, but manual bypass* is not allowed. *Manual bypass means users manually operate UPS in Bypass mode. For example, pressing OFF button in AC mode to turn into Bypass mode.
06: Battery backup time setting
Interface
Setting
Parameter 2:
000~999: Set the maximum backup time from 0 min to 999 min.
UPS will shut down to protect battery after backup time arrives. The default value is 990. DIS: Disable battery discharge protection and backup time will depend on battery capacity.
07: Hot standby function enable/disable
Interface Setting
Parameter 2
:
Enable or disable hot standby function. ENA: Hot standby function is enabled. It means that the current UPS is set to host of the hot standby function, and it will restart after AC recovery even without battery connected. DIS: Hot standby function is disabled. The UPS is running at normal mode and can’t restart without battery.
20
08: Voltage range for bypass
Interface Setting
Parameter 2
:
Set the acceptable low voltage for bypass.
Setting range is from 110V to 209V and the default value is 176V
09: Voltage range for bypass
Interface Setting
Parameter 2
:
Set the acceptable low voltage for bypass.
Setting range is from 231V to 276V and the default value is 264V
10: Frequency range for bypass
Interface Setting
Parameter 2:
Set the acceptable low frequency for bypass. 50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 60 Hz system: Setting range is from 56.0Hz to 59.0Hz. The default value is 46.0Hz/56.0Hz.
11: Frequency range for bypass
Interface Setting
Parameter 2:
Set the acceptable high frequency for bypass. 50 Hz: Setting range is from 51.0Hz to 54.0 Hz. 60 Hz: Setting range is from 61.0Hz to 64.0Hz. The default value is 54.0Hz/64.0Hz.
12: Battery voltage calibration
Interface Setting
21
Parameter 2:
Set Battery voltage calibration. the voltage range is from -5.7V to 5.7V.the default value is 0V.
13: charger voltage calibration
Interface Setting
Parameter 2:
Set charger voltage calibration. the voltage range is from -6.4V to 6.4V, the default value is 0V.
14: Inverter voltage calibration
Interface Setting
Parameter 2:
Set Inverter voltage calibration. the voltage range is from -6.4V to 6.4V, the default value is 0V.
22
15: Charger maximum current setting
Interface Setting
Parameter 2:
The maximum charging current could be adjusted. Default value is 4A for long run model and 1A for standard model. The setting range is 0.5A~6A for long run model, and
0.5A~2A for standard model Note: Any modification should be suitable to battery specifications. If input voltage is below 200VAC, the UPS will reduce charging current to 4A automatically even though the setting is 6A.
16: Battery capacity setting
Interface Setting
Parameter 2:
Set the battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH, 26AH, 40AH, 65AH, 100AH and so on. The default value is 9AH.
17: Battery groups setting
Interface Setting
Parameter 2:
Set battery group range from 1 to 6. The default value is 1 group. These parameters are for the battery backup time calculation
18: Backup time calibration
Interface Setting
Parameter 2:
Calibrate the displayed backup time by adjusting this multiplier factor. The displayed backup time will be equal with the original calculated backup time multiply this value. The default value is 1.0, and the range is from 0.5 to 2
23
3-7. Operating Mode/Status Description
Operating mode/status
Description
LCD display
AC mode
When the input voltage is within acceptable
range, UPS will provide pure and stable AC
power to output. The UPS will also charge
the battery at AC mode.
CVCF mode When input frequency is between 46Hz and
64Hz, the UPS can be set at a constant
output frequency, 50 Hz or 60 Hz. The UPS
will still charge battery under this mode.
Battery mode When the input voltage is beyond the
acceptable range or power failure, UPS will
backup power from battery and alarm will
beep every 4 seconds.
Battery Test When UPS is in AC mode or CVCF mode,
press “Test” key for more than 2 seconds.
Then, UPS will beep once and start “Battery
Test”. This operation is used to check the
battery status.
Bypass mode When input voltage is within acceptable
range and bypass is enabled, turn off the
UPS and it will enter Bypass mode. Alarm
beeps every two minutes.
Fault status When fault occurs in UPS, it will display fault
icon and fault code in LCD panel.
24
3-8. Fault Code
Fault event
Fault code
Icon Fault event
Fault code
Icon
Bus start failure 01 None Battery SCR short circuited 21 None Bus over 02 None Inverter relay short circuited 24 None Bus under 03 None Charger output short 2A None Bus unbalance 04 None Parallel communication
failure
35 None
Inverter soft start failure 11 None Parallel output current
unbalance
36 None
High Inverter voltage 12 None Over temperature 41 None Low Inverter voltage 13 None CPU communication failure 42 None Inverter output short circuited
14
Overload 43
Negative power fault 1A None
3-9. Warning Indicator
Warning
Description
code
Icon (flashing)
Alarm
Battery is not connected
01
Beeping every second
Over charge
07
Beeping every second
Low battery
08
Beeping every second
Overload
09
Beeping twice every second
Fan failure
0A
Beeping every second
EPO enabled
0B
Beeping every second
Over temperature
0D
Beeping every second
Charger failure
0E
Beeping every second
I/P fuse broken
10
Beeping every second
Overload 3 times in 30 minutes
33
Beeping every second
Cover of maintain switch is open
3A
Beeping every second
25
4. Trouble Shooting
If the UPS system does not operate correctly, please solve the problem by referring to the table below:
Alarm
type
C
odeIcon Possible cause
Remedy
Warning 01
1) The battery is not connected well;
2) The battery protection device is open.
1) Connect the battery well;
2) Replace or restore the protection device.
Warning 07
1) Battery numbers and its setting is not matching;
2) Charger voltage is too high. It will cause charger failure.
1) Correct the battery number or its setting;
2) Disconnect the battery and check the charger output voltage. Then, contact the dealer for repair.
Warning
08
1) Battery is discharged deeply to low voltage.
2) Battery number is not correct.
3) Battery is in the end of life.
1) Recharge the battery.
2) Correct the battery number.
3) Replace the battery.
Warning
09
Overload. Remove excess loads from UPS output.
Warning
0A
1) Fan is blocked.
2) Fan is in the end of life.
3) Fan circuit failed.
1) Clean fan to make sure it is not blocked.
2) Contact the dealer to replace the fan.
3) Contact the dealer for repair.
Warning
0B
EPO plug (jumper) is removed or the external EPO switch is off.
Connect the EPO plug (jumper) well or switch on the external EPO switch.
Warning
0D
The internal temperature is too high and reaches warning level:
1) Maybe the environment is hot.
2) Maybe the fan is blocked or failed.
3) Maybe the ventilation is blocked by the wall or other goods.
4) Overload
1) Make sure the ambient temperature
is not over 40°C.
2) Make sure the fan is OK.
3) Make sure ventilation is well.
4) Remove some loads if possible.
Warning
0E
Charger failure. Contact the dealer for repair.
Warning
10
Input fuse on the power stage board is blown.
Check and replace the input fuse.
Warning
33
Locked in bypass after overload 3 times in 30 minutes.
Remove excess loads from UPS output first, then shut down the UPS and restart it.
Warning
3A
Cover of maintain switch is open.
Please put the cover back.
26
Alarm
type
Code
Icon
Possible cause Remedy
Fault
01
The internal converter failed, so the DC bus voltage could not be boosted correctly.
Contact the dealer for repair
Fault
02
1) The mains input or load transient current cause the DC bus voltage too high.
2) The internal converter failed.
1) Shut down and restart the UPS to see if it happens again. If the problem still persists, please contact the dealer for repair.
2) Contact the dealer for repair.
Fault
03
The internal converter fails, so the DC bus voltage is too low.
Contact the dealer for repair.
Fault
04
1) The load is special or abnormal, so the internal positive and negative DC bus voltages are unbalanced;
2) The internal converter failed.
Contact the dealer.
Fault
11
The internal inverter fails, so the inverter voltag
e could not start up
correctly.
Contact the dealer for repair.
Fault
12
The internal inverter fails, so the inverter voltage is too high.
Contact the dealer for repair.
Fault
13
The internal inverter fails, so the inverter voltage is too low.
Contact the dealer for repair.
Fault
14
Short circuit occurs on the UPS output.
Remove short circuited output/situation. If the problem still persists, please contact the dealer for repair.
Fault
1A
UPS output power is negative. It means there is energy feedback into the internal of UPS from output. It may be caused by regenerative load or the current control failure in the parallel system.
Contact the dealer.
Fault
21
The internal battery SCR failed and short circuited.
Contact the dealer for repair.
Fault
2A
Short circuit occurs on the charger output.
Remove short circuited output/situation. If the problem still persists, please contact the dealer for repair.
Fault
24
The internal inverter relay is stick to short circuited or the SCR of STS (Static Transfer Switch) is short-circuited.
Contact the dealer for repair.
Fault
41
The internal temperature is too high and reaches the fault level (shutdown point):
1) Maybe the environment is hot.
2) Maybe the fan is blocked or failed.
3) Maybe the ventilation is blocked by the wall or other goods.
4) Overload
1) Make sure the ambient
temperature not over 40ºC;
2) Make sure the fan is OK;
3) Make sure the ventilation is well;
4) Remove some loads if possible.
Fault
42
Internal communication between the CPUs failed
Contact the dealer for repair.
Fault
43
Overload times are out of the specification and the UPS shuts down automatically.
Remove excess loads from UPS output and restart it.
27
5. Storage and Maintenance
5-1. Storage
Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours
5-2. Maintenance
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified
maintenance personnel.
Even after the unit is disconnected from the mains, components inside the UPS system are still
connected to the battery packs which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Verify that no voltage between the battery terminals and the ground is present before maintenance or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground.
Batteries may cause electric shock and have a high short-circuit current. Please remove all wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools with insulated grips and handles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The batteries must be rightly deposed according to local regulation.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.
28
6. Specifications
MODEL GXT MT+ LB, 10kVA CAPACITY* 10000 VA / 8000 W
INPUT
Voltage Range
Low Line Loss
110 VAC ± 3 % at 50% Load;
176 VAC ± 3 % at 100% Load Low Line Comeback Low Line Loss Voltage + 10V High Line Loss 300 VAC ± 3 % High Line Comeback High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system Phase Single phase with ground Power Factor
> 0.99 at 100% Load
OUTPUT
Output voltage 208/220/230/240VAC
AC Voltage Regulation ± 1% Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 10min110%~130%: 1min>130% : 1sec
Battery mode
100%~110%: 30sec110%~130%: 10sec>130% : 1sec
Current Crest Ratio 3:1 max Harmonic Distortion
3 % @ 100% Linear Load; 6 % @ 100% Non-linear Load
Transfer Time
Line Battery 0 ms Inverter Bypass 0 ms
EFFICIENCY
AC mode
> 90%
Battery Mode > 89%
BATTERY
Standard Model
Type & Numbers 12 V / 9 Ah x 20
Recharge Time 9 hours recover to 90% capacity
Charging Current
Default : 1 A ± 10%
M
ax.
: 2
A ± 10%
Charging Voltage 14.4 V ± 1%
Long-run Model
Type Depending on applications Numbers 16 – 20 Derating capacity = original real power capacity x N/20
Charging Current
Default: 4 A ± 10%
Max.: 6A ± 10%
Charging Voltage
14.4 V ± 1%
PHYSICAL
Standard Model
Dimension, DXWXH(mm)
442x 190 x 688
Net Weight (kgs) 82 Long-run Model
Dimension, DXWXH(mm)
442x 190 x 318
Net Weig
ht
(kgs) 23
ENVIRONMENT
Operation Temperature
0 ~ 40°C
(battery life cycle will be shorten when temperature is above 25°C) Operation Humidity <95 % and non-condensing Operation Altitude** <1000m
Acoustic Noise Level
Less than
58
dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and
MAC
Optional SNMP Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC. **If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m. ***Product specifications are subject to change without further notice.
Loading...